22005-Bluestone Final Sealed Drawings.pdf
PDF 7 MB Posted
- Attached to
- Bluestone State Park Bathhouse
- Solicitation number
- CRFQ 0310 DNR2400000011 2
- Issued by
- Randolph County, West Virginia
About this file
Summary
This document consists of sealed structural, plumbing, and electrical drawings for an ADA Toilet Rooms and Sidewalk project at Bluestone State Park in Hinton, West Virginia, prepared by Chapman Technical Group for the West Virginia Division of Natural Resources, Parks and Recreation. The project involves renovation of park headquarters toilet rooms with modifications to plumbing fixtures, electrical systems, and associated infrastructure. The drawings establish design standards based on the 2018 International Building Code, with structural requirements including a roof snow load of 25 PSF, basic wind speed of 115 MPH (Exposure Category C), and seismic design category B. Foundation design assumes a soil bearing value of 2,000 PSF with compaction requirements of 98% maximum dry density. Concrete construction specifications require 4,500 PSI strength with 6% air entrainment for freeze-thaw exposed applications, while structural steel must comply with AISC standards using ASTM A325-N high-strength bolts or welded connections. Plumbing plans detail fixture removal and installation, including a new lavatory with Zurn DJR-40 air admittance device, and require slope-to-drain pipe configuration for winterization. Electrical work includes removal of existing luminaires and lighting controls, installation of new recessed luminaires with emergency battery backup, and provision of dedicated circuits with proper grounding and firestopping through fire-rated assemblies.
All work must comply with state and local licensing requirements, National Electrical Code standards, and obtain local Authority Having Jurisdiction certificates of compliance and electrical inspection. The contractor bears responsibility for special inspection services, including concrete construction inspections per 2018 IBC Section 1705.3 and soils construction inspections per Section 1705.6, with qualified inspection agencies approved by the building official, architect, and structural engineer. Shop drawings are required for reinforcing steel, concrete mix designs, and all electrical materials and equipment prior to procurement. The contractor is solely responsible for job-site safety, construction procedures, and OSHA compliance, with all demolition work requiring proper removal and disposal of existing materials. No cutting or burning of structural steel in the field is permitted without written engineer approval, and all exterior railings must be hot-dip galvanized.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIRPORT PLANNING / DEVELOPMENT
ARCHITECTURE / INTERIOR DESIGN
CIVIL ENGINEERING / SITE DEVELOPMENT
ENVIRONMENTAL ENGINEERING
LANDSCAPE ARCHITECTURE
SURVEYING
St. Albans, WV
(304) 727-5501
Buckhannon, WV
(304) 472-8914 a division of
GRW
GENERAL STRUCTURAL NOTES
1. THESE STRUCTURAL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH ALL OTHER DRAWINGS, SPECIFICATIONS & CONTRACT DOCUMENTS.
2. THE DESIGN, CONSTRUCTION, QUALITY CONTROL AND SAFETY OF ALL WORK PERFORMED ON THE PROJECT SHALL CONFORM TO THE REFERENCED CODES AND STANDARDS, INCLUDING ALL SPECIFICATIONS REFERENCED WITH THE LATEST EDITIONS SHALL APPLY UNLESS NOTED.
3. BUILDING CODE - INTERNATIONAL BUILDING CODE - 2018
4. COUNTY/STATE SUMMERS / WEST VIRGINIA
5. RISK CATEGORY II
6. DESIGN LIVE LOADS
ROOF SNOW LOAD 25 PSF
RAILINGS 200 LB CONCENTRATED LOAD, ANY DIRECTION OR
50 LB/LF, ANY DIRECTION, WHICHEVER IS MINIMUM
7. LATERAL LOADS - WIND
BASIC WIND SPEED 115 MPH
EXPOSURE CATEGORY C
8. LATERAL LOADS - SEISMIC
MAPPED SHORT PERIOD SPECTRAL RESPONSE ACCELERATION SS 0.229g MAPPED 1 SECOND SPECTRAL RESPONSE ACCELERATION S1 0.070g
DESIGN SHORT PERIOD SPECTRAL RESPONSE ACCELERATION SDS 0.245
DESIGN 1 SECOND SPECTRAL RESPONSE ACCELERATION SD1 0.112
SEISMIC IMPORTANCE FACTOR Ie 1.0
SOIL SITE CLASS D (ASSUMED)
SEISMIC DESIGN CATEGORY B
9. ALL CONTRACTOR PROPOSED STRUCTURAL SUBSTITUTIONS, INCLUDING CONCRETE ADDITIVES, SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND
APPROVAL PRIOR TO ANY PERTINENT WORK AND PRIOR TO THE AWARD OF A SUBCONTRACTOR.
10. SHOP DRAWINGS, TEST REPORTS, AND CERTIFICATIONS ARE REQUIRED FOR THE FOLLOWING STRUCTURAL ITEMS:
A. REINFORCING STEEL SHOP DRAWINGS
B. CONCRETE MIX DESIGNS
C. CONCRETE CYLINDER TESTS
12. CONSTRUCTION METHODS, PROCEDURES, AND SEQUENCES ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL TAKE ALL NECESSARY MEANS TO MAINTAIN AND PROTECT THE STRUCTURAL INTEGRITY OF ALL CONSTRUCTION AT ALL STAGES.
13. IMPLEMENTING JOB SITE SAFETY AND CONSTRUCTION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
14. IN CASE OF CONFLICT BETWEEN THE GENERAL NOTES, DETAILS AND SPECIFICATIONS, THE MOST RIGID REQUIREMENTS SHALL GOVERN.
GENERAL FOUNDATION/GEOTECHNICAL NOTES
1. THE SOIL BEARING VALUE IS ASSUMED TO BE 2000 PSF, (NO BORINGS).
2. AFTER PERFORMING THE INITIAL SITE PREPARATION ACTIVITIES, THE EXPOSED SOILS WITHIN THE LIMITS OF THE PROPOSED STRUCTURE AND PAVEMENT AREAS SHALL BE PROOFROLLED IN THE PRESENCE OF A REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER.
3. VERIFY LOCATIONS OF COLUMNS, UNDERGROUND UTILITIES, ETC., WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND CIVIL DRAWINGS PRIOR TO
PLACEMENT OF FOUNDATIONS.
4. UNLESS DETERMINED OTHERWISE BY GEOTECHNICAL EVALUATION, FILL MATERIAL FOR SLAB AND FOOTING AREAS SHALL BE PLACED IN LAYERS NOT EXCEEDING 8 INCHES (UNCOMPACTED THICKNESS) AND COMPACTED TO 98% OF MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D698. CRUSHED STONE BACKFILL SHALL BE COMPACTED WITH HAND EQUIPMENT TO THE SATISFACTION OF THE GEOTECHNICAL ENGINEER.
5. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO BRACE FOUNDATION WALLS WHEN BACK FILLING AND WHEN THERE IS A POSSIBILITY OF
DAMAGE BY EXCESS WATER.
6. COMPACTION OF BACKFILL WITHIN 2 FEET OF FOUNDATION WALLS SHALL BE ACCOMPLISHED WITH HAND EQUIPMENT. WHERE FILL IS REQUIRED ON BOTH SIDES OF FOUNDATION WALL, BRING THE FILL UP EACH SIDE SIMULTANEOUSLY AND UNIFORMLY.
7. THE SURFACE AREA ADJACENT TO THE FOUNDATION WALL SHALL BE PROVIDED WITH ADEQUATE DRAINAGE AND SHALL BE GRADED SO AS TO DRAIN
SURFACE WATER AWAY FROM FOUNDATION WALLS.
8. IF FOOTING EXCAVATIONS ENCOUNTER ISOLATED AREAS OF RELATIVELY HARD ROCK AT OR ABOVE THE PLANNED FOOTING ELEVATIONS, THE ROCK SHALL BE OVER EXCAVATED TO A DEPTH OF APPROXIMATELY ONE FOOT BELOW THE FOUNDATION BEARING ELEVATION AND BACKFILLED WITH
STRUCTURAL FILL.
9. FOUNDATIONS SHALL NOT BE PLACED ON MUD OR MUCK, SOFT OR LOOSE SOIL, IN STANDING WATER OR ON FROZEN GROUND.
CAST-IN-PLACE CONCRETE
1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING CODES
AND STANDARDS:
"BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, ACI 318-14", AMERICAN CONCRETE INSTITUTE
"ACI MANUAL OF CONCRETE PRACTICE - PARTS 1 THROUGH 5", LATEST EDITION
"MANUAL OF STANDARD PRACTICE", CONCRETE REINFORCING STEEL INSTITUTE
ACI 305 AND ACI 306 FOR HOT AND COLD WEATHER CONCRETE CONSTRUCTION
ACI 347 FOR SHORING AND RESHORING OF CONCRETE STRUCTURES
2. CONTRACTOR SHALL PROVIDE MATERIALS WHICH COMPLY WITH THE FOLLOWING ASTM REQUIREMENTS, AS REQD.:
CEMENT ASTM C150: TYPE I/II
AGGREGATES ASTM C33
FLY ASH ASTM C618
PLAIN REINFORCING BARS ASTM A615, GRADE 60
WELDED WIRE FABRIC ASTM A1064
AIR-ENTRAINING ADMIXTURE: ASTM C260
3. CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING TABLE, U.N.O. ON THE
CONSTRUCTION DRAWINGS:
APPLICATION COVER
- CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
- CONCRETE EXPOSED TO WEATHER (U.N.O.):
#6 THROUGH #18 BARS: 2"
#5 BAR, W31 OR D31 WIRE AND SMALLER: 1-1/2"
- CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
SLABS, WALLS, AND JOISTS:
#14 AND #18 BARS: 1-1/2"
#11 BAR AND SMALLER: 3/4"
4. CONCRETE MIXES SHALL BE AS FOLLOWS:
APPLICATION COMP. STRENGTH, AIR, W/C
- CONCRETE USED FOR FOUNDATION CONSTRUCTION (STRIP/SPREAD
FOOTINGS, FOUNDATION WALLS ETC.), OR CONCRETE 4,500 PSI, 6%, 0.45
EXPOSED TO CYCLES OF FREEZE THAW (SIDEWALKS, EXTERIOR SLAB
ON GRADE ETC.):
5. SHOP DRAWINGS SHOWING THE SIZE, LENGTH, QUANTITY, LOCATION AND MARK OF ALL REINFORCING BARS, SUPPORTS AND
ACCESSORIES SHALL BE SUBMITTED FOR APPROVAL PRIOR TO FABRICATION.
6. MIX DESIGNS AND ADMIXTURE PRODUCT DATA SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING CONCRETE.
7. THE TYPICAL DETAILS, PLANS, AND SECTIONS ON THESE DRAWINGS CONTAIN ADDITIONAL GENERAL CONCRETE
CONSTRUCTION NOTES AND INFORMATION.
8. ALL CONCRETE SHALL BE REINFORCED UNLESS NOTED OTHERWISE.
9. REINFORCING STEEL SHALL BE CLEAN OF ALL DIRT AND OILS PRIOR TO CONCRETE POUR UNLESS SPECIFIED OTHERWISE.
10. SUPPORTS TO ADEQUATELY POSITION REINFORCING BARS DURING CONSTRUCTION SHALL BE INSTALLED.
11. FOUNDATION DOWELS OF THE SAME SIZE AND SPACING AS VERTICAL STEEL SHALL BE INSTALLED FOR ALL WALLS, PIERS, AND COLUMNS.
12. ALL REINFORCING AT WALL AND FOOTING CORNERS AND INTERSECTIONS SHALL BE CONTINUOUS BY THE USE OF BENT
BARS OR CORNER BARS UNLESS INDICATED OTHERWISE.
13. CONSTRUCTION JOINTS SHALL BE POSITIONED SO AS NOT TO ADVERSELY AFFECT THE STRUCTURAL PERFORMANCE.
CONSTRUCTION JOINT LOCATIONS NOT INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER.
14. PIPE SLEEVES AND INSERTS SHALL BE INSTALLED IN CONCRETE WORK AT ALL PENETRATIONS. PENETRATIONS OF BEAMS, JOISTS, COLUMNS OR STRUCTURAL SLABS NOT INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER.
15. ONLY WELDABLE REINFORCING BARS MAY BE WELDED.
16. ADMIXTURES CONTAINING CHLORIDE OR OTHER CORROSIVE CHEMICALS SHALL NOT BE USED IN CONCRETE.
17. AGGREGATES SHALL BE FREE OF DELETERIOUS OR NON-DURABLE MATERIALS SUCH AS CHERTS.
18. REINFORCING SHALL BE ADEQUATELY TIED AND SUPPORTED TO HOLD IT IN THE CORRECT POSITION DURING
CONSTRUCTION AND THE PLACEMENT OF CONCRETE.
19. CONCRETE SHALL BE CONSOLIDATED ADEQUATELY DURING PLACEMENT BY MECHANICAL VIBRATION IN ACCORDANCE WITH
PUBLISHED PRACTICES.
20. PLASTIC CHAIRS SHALL BE USED IN ALL CONCRETE THAT WILL BE EXPOSED TO VIEW IN THE COMPLETED STRUCTURE.
21. EXPOSED CONCRETE CORNERS SHALL BE CHAMFERED MINIMUM 3 4", OR AS INDICATED ON THE ARCHITECTURAL/CIVIL
DRAWINGS.
22. FILL POCKETS AROUND CONNECTIONS WITH CONCRETE FLUSH AND SMOOTH UNLESS INDICATED OTHERWISE.
23. FORMED SURFACES SHALL HAVE A SMOOTH-FORM FINISH WHERE EXPOSED TO VIEW AND A ROUGH-FORM FINISH WHERE
NOT EXPOSED TO VIEW UNLESS INDICATED OTHERWISE.
24. UNFORMED SURFACES SHALL HAVE A TROWEL FINISH WHERE EXPOSED TO VIEW AND A FLOAT FINISH WHERE NOT EXPOSED
TO VIEW U.N.O. EXCEPT THAT STAIRS AND EXTERIOR WALKING SURFACES SHALL HAVE A BROOM FINISH U.N.O.
25. SLABS-ON-GRADE SHALL BE PLACED ON A VAPOR BARRIER OVER 4" MINIMUM OF WELL GRADED CRUSHED STONE OVER
COMPACTED SUBGRADE, U.N.O.
26. ALL COLD JOINTS SHALL BE ROUGHENED TO A FULL AMPLITUDE OF 14" AND A CONCRETE BONDING AGENT SHALL BE APPLIED
PRIOR TO THE PLACEMENT OF FRESH CONCRETE.
27. IN SLABS-ON-GRADE, LAP WELDED WIRE FABRIC TWO FULL MESH PANELS AND WIRE TOGETHER.
28. SPLICE LAP LENGTHS FOR REINFORCING SHALL BE IN ACCORDANCE WITH THE FOLLOWING TABLE, U.N.O. ON THE PLANS:
BAR SIZE LAP LENGTH
#3 24" #4 36" #5 48"
#6-#8 60"
29. PROVIDE ISOLATION JOINTS IN SLABS AS FOLLOWS:
A. BETWEEN SLABS-ON-GRADE AND FOUNDATION WALLS
B. BETWEEN SLABS AND INSERTS SUCH AS PIPES
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE AND SCHEDULE THE SPECIAL INSPECTOR'S INSPECTIONS AND TESTING FOR THE WORK NOTED BELOW. THE FOLLOWING INFORMATION IS PROVIDED FOR THE CONTRACTOR'S INFORMATION AND COORDINATION
PURPOSES.
2. SPECIAL INSPECTIONS SHALL BE PERFORMED FOR THE FOLLOWING WORK AS REQUIRED IN THE 2018 INTERNATIONAL BUILDING CODE:
2.1. CONCRETE CONSTRUCTION IN ACCORDANCE WITH SECTION 1705.3
2.2. SOILS CONSTRUCTION IN ACCORDANCE WITH SECTION 1705.6
3. THE TYPE AND EXTENT OF EACH TEST AND INSPECTION REQUIRED FOR EACH TYPE OF WORK SHALL BE AS INDICATED IN THE BUILDING CODE
AND THE REFERENCES INCORPORATED THEREIN.
4. SPECIAL INSPECTION SERVICES SHALL BE CONTRACTED AND PAID FOR BY THE CONTRACTOR.
5. WORK REQUIRING SPECIAL INSPECTION SHALL BE INSPECTED BY THE SPECIAL INSPECTOR FOR CONFORMANCE WITH THE APPROVED
DRAWINGS AND SPECIFICATIONS. INSPECTION REPORTS INDICATING THE RESULTS OF SPECIAL INSPECTIONS SHALL BE PROMPTLY
SUBMITTED DIRECTLY TO THE ARCHITECT, THE STRUCTURAL ENGINEER AND THE CONTRACTOR.
6. ALL SPECIAL INSPECTIONS INDICATING NON-CONFORMING WORK SHALL BE REPORTED IMMEDIATELY AND DIRECTLY TO THE ARCHITECT, THE STRUCTURAL ENGINEER AND THE CONTRACTOR. IMPENDING CONSTRUCTION WORK THAT WOULD IMPEDE ECONOMICAL CORRECTION OF
NON-CONFORMING WORK SHALL NOT PROCEED WITHOUT WRITTEN APPROVAL.
7. A FINAL REPORT DOCUMENTING COMPLETION OF ALL REQUIRED SPECIAL INSPECTIONS AND CORRECTION OF ANY NON-CONFORMING WORK NOTED IN THE INSPECTIONS SHALL BE SUBMITTED DIRECTLY TO THE ARCHITECT, THE STRUCTURAL ENGINEER AND THE CONTRACTOR BY THE SPECIAL INSPECTOR AT THE COMPLETION OF THE PROJECT. FINAL REPORT SHALL IDENTIFY ALL NON-CONFORMING WORK AND DISCUSS
REMEDIATION THAT OCCURRED.
8. SPECIAL INSPECTIONS SHALL BE PERFORMED BY A QUALIFIED INSPECTION AND TESTING AGENCY APPROVED BY THE BUILDING OFFICIAL, THE ARCHITECT, AND THE STRUCTURAL ENGINEER.
SPECIAL INSPECTIONS
C. SURFACES TO BE FIELD WELDED.
B. MEMBERS RECEIVING SPRAY FIREPROOFING.
5. ONE SHOP COAT OF PAINT SHALL BE APPLIED TO ALL STRUCTURAL MEMBERS EXCEPT:
A. MEMBERS ENCASED IN CONCRETE.
4. CUTTING OR BURNING OF STRUCTURAL STEEL IN THE FIELD IS NOT ALLOWED, UNLESS BY WRITTEN APPROVAL BY ENGINEER.
OR DEVIATIONS AND RECEIVE WRITTEN APPROVAL BEFORE ANY FIELD CORRECTIONS ARE MADE.
3. THE GENERAL CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY FABRICATION OR ERECTION ERRORS
WITH UNMARKED NUTS AND BOLTS WILL BE REJECTED. ALL BOLTED CONNECTIONS SHALL HAVE A MINIMUM OF 2 BOLTS.
AND NUTS SHALL BE CLEARLY MARKED AS REQUIRED BY AISC SPECIFICATIONS. ALL CONNECTIONS MADE
2. ALL SHOP AND FIELD CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS OR WELDS. ALL BOLTS
"STRUCTURAL WELDING CODE ANSI/AWS D1.1/D1.1M", AMERICAN WELDING SOCIETY.
"DETAILING FOR STEEL CONSTRUCTION" AISC 326, AMERICAN INSTITUTE OF STEEL CONSTRUCTION, LATEST ADDITION.
SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, AND AISC CODE OF INSTITUTE OF STEEL CONSTRUCTION (INCLUDING SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, STEEL CONSTRUCTION MANUAL - AISC FIFTEENTH EDITION, 2017, AMERICAN
1. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING CODES
STRUCTURAL STEEL
D. GALVANIZED SURFACES.
WELDING ELECTRODES
THREADED ROD
ANCHOR RODS
HIGH-STRENGTH BOLTS
STRUCTURAL PIPE
STANDARD PRACTICE).
PLATES & OTHER SHAPES
AND STANDARDS:
AWS A5.1 OR A5.5 E70XX
ASTM A36
ASTM F1554
ASTM A325-N
ASTM A53, GRADE B, Fy=35 KSI OR ASTM A501, Fy=36 KSI
ASTM A36
6. CONTRACTOR AND ERECTOR ARE RESPONSIBLE FOR COMPLYING WITH ALL OSHA REGULATIONS.
7. ALL EXTERIOR RAILINGS SHALL BE HOT-DIP GALVANIZED.
G C
TG
D N R B a th h o u se s\ W o rk in g
D ra w in g s\ B lu e st o n e A u to c a d B S S .d w g
:3 :2
P M rk e n n e d y
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
PROJECT INFORMATION
AutoCAD SHX Text Chapman
AutoCAD SHX Text Technical
AutoCAD SHX Text Group
AutoCAD SHX Text www.chaptech.com
AutoCAD SHX Text
RJK
AutoCAD SHX Text
RJK
AutoCAD SHX Text
KJW
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 22005
AutoCAD SHX Text S-001
AutoCAD SHX Text
STRUCTURAL NOTES
AutoCAD SHX Text
PARKS AND RECREATION
AutoCAD SHX Text
BLUESTONE STATE PARK
AutoCAD SHX Text
ADA TOILET ROOMS AND SIDEWALK
AutoCAD SHX Text
AUGUST 2023
AutoCAD SHX Text
WV DIVISION OF NATURAL RESOURCES
AutoCAD SHX Text
HINTON, WEST VIRGINIA
SCALE: 1/2"=1'-0" 0 2' 4'1'1 PARK HEADQUARTERS TOILET ROOM - PLUMBING PLAN
L-1
6 2
AIRPORT PLANNING / DEVELOPMENT
ARCHITECTURE / INTERIOR DESIGN
CIVIL ENGINEERING / SITE DEVELOPMENT
ENVIRONMENTAL ENGINEERING
LANDSCAPE ARCHITECTURE
SURVEYING
St. Albans, WV
(304) 727-5501
Buckhannon, WV
(304) 472-8914 a division of
GRW
GENERAL NOTES:
KEYNOTES:
1. SEE SHEET M-00-001 AND M-00-002 FOR PLUMBING LEGEND AND ADDITIONAL
GENERAL NOTES.
2. DO NOT INSTALL ANY PLUMBING PIPE OVER ANY ELECTRICAL PANELS.
3. SLOPE ALL PIPE TO DRAIN FOR WINTERIZATION. REFER TO RISER DIAGRAMS.
4. ALL EXISTING PLUMBING TO REMAIN AND/OR BE MODIFIED AS NOTED. SEE
ARCHITECTURAL PLAN.
1. REMOVE EXISTING LAVATORY AND PROVIDE NEW FIXTURE AS SHOWN.
2. PROVIDE ZURN DJR-40 AIR ADMITTANCE DEVICE. INSTALL WASTE, TRAP AND AIR
ADMITTANCE DEVICE TO COMPLY WITH ADA ACCESSIBILITY REQUIREMENTS.
3. CONNECT TO EXISTING WASTE AND DOMESTIC WATER PIPES.
4. EXISTING LAVATORY TO REMAIN.
5. EXISTING WATER CLOSET TO REMAIN.
6. EXISTING URINAL TO REMAIN.
1 1/4"
L-12"
2.
1.
NOTES:
3.
TYPICAL UNFINISHED WALL TYPICAL FINISHED WALL
SCH 40 GALV STEEL SLEEVE
SECURED TO PARTITION.
PIPE - WITH OR WITHOUT
INSULATION.
CAULK AND SEAL ANNULAR SPACE
BETWEEN PIPE AND SLEEVE.
TYPICAL FOR NON-INSULATED PIPE AND CONDUIT.
ALL CAULKING AND SEALANT SHALL BE FIRE RATED
(SEE SPECIFICATIONS).
WHERE PIPING IS EXPOSED AT FINISHED FLOOR, FLUSH
MOUNT SLEEVE AND PROVIDE ESCUTCHEON PLATE.
NOT TO SCALE3
PIPE PENETRATION THRU
INTERIOR WALL DETAIL
2.
1.
NOTES:
3.
SCH 40 PVC SLEEVE
SECURED IN FORM PRIOR
TO CONCRETE POUR.
PLUMBING PIPECAULK AND SEAL ANNULAR SPACE
BETWEEN PIPE AND SLEEVE.
TYPICAL FOR SANITARY AND WATER PIPING.
ALL CAULKING AND SEALANT SHALL BE WATER
TIGHT (SEE SPECIFICATIONS).
WHERE PIPING IS EXPOSED AT FINISHED FLOOR, FLUSH
MOUNT SLEEVE AND PROVIDE ESCUTCHEON PLATE.
NOT TO SCALE4
PIPE PENETRATION THRU CONCRETE
WALL AND FLOOR DETAIL
NOT TO SCALE2 PLUMBING RISER DIAGRAM
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
PROJECT INFORMATION
AutoCAD SHX Text Chapman
AutoCAD SHX Text Technical
AutoCAD SHX Text Group
AutoCAD SHX Text www.chaptech.com
AutoCAD SHX Text
CVS
AutoCAD SHX Text
MAS
AutoCAD SHX Text
MAS
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 22005
AutoCAD SHX Text P-100
AutoCAD SHX Text
PARK HEADQUARTERS
AutoCAD SHX Text
TOILET ROOM
AutoCAD SHX Text
PLUMBING PLAN, SCHEDULE & RISER DIAGRAM
AutoCAD SHX Text
PARKS AND RECREATION
AutoCAD SHX Text
BLUESTONE STATE PARK
AutoCAD SHX Text
ADA TOILET ROOMS AND SIDEWALK
AutoCAD SHX Text
AUGUST 2023
AutoCAD SHX Text
WV DIVISION OF NATURAL RESOURCES
SCALE: 1/2"=1'-0" 0 2' 4'1'1 PARK HEADQUARTERS TOILET ROOM - ELECTRICAL DEMOLITION PLAN
2 2
GENERAL NOTES:
A. ALL DEMOLITION WORK SHALL BE COORDINATED
WITH ALL OTHER WORK AND EXISTING CONDITIONS
TO ASSURE PROPER REMOVAL OF EXISTING
ELECTRICAL WORK.
B. EXISTING CONDUIT MAY BE REUSED, WHERE
POSSIBLE. REMOVE AND PROPERLY DISPOSE OF ALL
CONDUIT NOT REUSED.
SHEET KEYNOTES:
1. CONTRACTOR SHALL REMOVE AND PROPERLY
DISPOSE OF THE LUMINAIRE WITHIN THIS ROOM. IN
ADDITION, REMOVE AND PROPERLY DISPOSE OF THE
EXISTING CONDUCTORS BACK TO THE EXISTING
PANELBOARD.
2. CONTRACTOR SHALL REMOVE AND PROPERLY
DISPOSE OF THE LIGHTING CONTROLS WITHIN THIS
ROOM. IN ADDITION, REMOVE AND PROPERLY
DISPOSE OF THE EXISTING BACKBOX AND CONDUIT.
AIRPORT PLANNING / DEVELOPMENT
ARCHITECTURE / INTERIOR DESIGN
CIVIL ENGINEERING / SITE DEVELOPMENT
ENVIRONMENTAL ENGINEERING
LANDSCAPE ARCHITECTURE
SURVEYING
St. Albans, WV
(304) 727-5501
Buckhannon, WV
(304) 472-8914 a division of
GRW
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
PROJECT INFORMATION
AutoCAD SHX Text Chapman
AutoCAD SHX Text Technical
AutoCAD SHX Text Group
AutoCAD SHX Text www.chaptech.com
AutoCAD SHX Text
WLM
AutoCAD SHX Text
JPR
AutoCAD SHX Text
JPR
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 22005
AutoCAD SHX Text
ED-100
AutoCAD SHX Text
PARK HEADQUARTERS
AutoCAD SHX Text
TOILET ROOM
AutoCAD SHX Text
ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text
PARKS AND RECREATION
AutoCAD SHX Text
BLUESTONE STATE PARK
AutoCAD SHX Text
ADA TOILET ROOMS AND SIDEWALK
AutoCAD SHX Text
AUGUST 2023
AutoCAD SHX Text
WV DIVISION OF NATURAL RESOURCES
CONDUIT RUN UNDERGROUND OR IN CONCRETE
CONDUIT WITH END CAPPED
(6-60)
LP1-2
WIREWAY
(1) (3) (5) (3)
PHASE(S)
NEUTRAL
GROUND
OR
OR
OR
OR
CONDUIT TURNED UP
CONDUIT TURNED DOWN
CONDUIT EXPOSED OR CONCEALED
SIGNIFIES MULTIPLE CIRCUITS IN ONE CONDUIT
EXPLOSION PROOF CONDUIT SEALX
W
OR
EG
EG
EG
3/4-10 W
T 100
3-25
35/3
W 3/4-10
G
G
G
3-25
T 100
OR
XXX
RCEG
KEY INTERLOCKK
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
SPD
TS OR
CAPACITOR
GROUND
TRANSFORMER
THERMOSTATIC SWITCH
PRESSURE SWITCH
1 2
AUTOTRANSFORMER
BATTERY
GF
GROUND FAULT
PROTECTED BREAKER
THERMAL-MAGNETIC CIRCUIT
BREAKER (SINGLE POLE SHOWN)
MAGNETIC ONLY CIRCUIT
BREAKER (SINGLE POLE SHOWN)
CIRCUIT BREAKER
GENERIC
DAMPER MOTOR ACTUATOR,
SPRING RETURN
SURGE PROTECTIVE
DEVICE, TYPE 1 OR TYPE 2
LIGHTNING ARRESTOR
(CROWBAR STYLE)
RELAY CONTACT
(NORMALLY OPEN)
RELAY CONTACT
(NORMALLY CLOSED)
TERMINALS FOR WIRE
CONNECTIONS FROM
REMOTE DEVICE
DOT INDICATES
CONNECTION OF WIRES
HOMERUN TO PANEL (PANEL LP1
CIRCUIT 2 INDICATED)
CONDUIT CONCEALED IN WALL OR CEILING
TIC MARKS INDICATE NUMBER OF WIRES.
#12 IF NOT OTHERWISE SHOWN. CONDUIT
SHALL BE 3/4 " UNLESS OTHERWISE NOTED.
RECESSED LUMINAIRE WITH
EMERGENCY BATTERY BACKUP
RECESSED OR SURFACE MOUNTED
LUMINAIRE
2' x 2' RECESSED LUMINAIRE WITH
EMERGENCY BATTERY BACKUP
2' x 2' RECESSED LUMINAIRE
4' STRIP LUMINAIRE
1' x 4' SURFACE MOUNTED OR SUSPENDED
LUMINAIRE
2' x 4' RECESSED LUMINAIRE WITH
EMERGENCY BATTERY BACKUP
EXIT LIGHT WITH ARROW
2' x 4' RECESSED LUMINAIRE
DUPLEX RECEPTACLE, 125 VOLT, 2-POLE, 3 WIRE, NEMA 5-20R
GROUNDING TYPE
SPECIAL PURPOSE RECEPTACLE, NUMBER DENOTES NEMA
CONFIGURATION
QUADRUPLEX RECEPTACLE, 125 VOLT, 2-POLE, 3
WIRE, NEMA 5-20R GROUNDING TYPE
JUNCTION BOX WALL OR CLG MOUNTED FLUSH OR SURFACE AS
NOTED, 4"X4" SQUARE UNLESS OTHERWISE NOTED
MULTI-OUTLET SURFACE RACEWAY, SIZE AND NUMBER OF
RECEPTACLE AS SCHEDULED. # INDICATES CIRCUIT NUMBER
WW W
WALL SWITCH 120-277 VOLT, 20 AMP, SINGLE POLE
LIMIT SWITCH OR
TORQUE SWITCH
DOUBLE THROW SWITCH
OR TRANSFER SWITCH
MANHOLE, HANDHOLE, OR PULLBOX, SUBSCRIPT
DENOTES THE FOLLOWING:
EMH ELECTRICAL MANHOLE
CMH COMMUNICATIONS MANHOLE
EHH ELECTRICAL HANDHOLE
CHH COMMUNICATIONS HANDHOLE
EPB ELECTRICAL PULLBOX
CPB COMMUNICATIONS PULLBOX
SINGLE PHASE TRANSFORMER, POLE MOUNTED
25 KVA NOTED
PAD MOUNTED TRANSFORMER, 100 KVA
NOTED
FUSE CUTOUT WITH FUSE SIZE
AND TYPE NOTED
TRANSFORMER BANK POLE MOUNTED, SHOWN
AS THREE PHASE 25 KVA TRANSFORMERS
35/3
5M
ETM
TM
R
SV
LS
T
PC
PS
CR#
A
DM
EF
W
WH
V
FUSEOR
THERMAL OVERLOAD
PROTECTION
b
LF-X
a
LF-X
LF-X
b b
LF-X
b
LF-X
E b
LF-X
1' x 4' SURFACE MOUNTED OR
SUSPENDED LUMINAIRE WITH
EMERGENCY BATTERY BACKUP
b
LF-X
E
LF-X
LF-X
b b
LF-X
b
LF-X
E bLF-X
LF-X b b
LF-X
E b
LF-X
b
LF-X
E
OC
OC
P
OCCUPANCY SENSOR - CEILING MOUNTED
OCCUPANCY SENSOR - CEILING MOUNTED - WITH
AUTOMATIC DIMMING CONTROL PHOTOCELL
PP POWER PACK
8' STRIP LUMINAIRE
INTERIOR LIGHTING
CEILING MTD WALL MTD
INTERIOR CONDUIT & WIRE
POWER WIRING DEVICES
XXX
XXX
XXX
J
INTERIOR LIGHTING CONTROLS
EMERGENCY LUMINAIRE BATTERY
OPERATED
DISCONNECT SWITCH (ENCLOSURE TYPE, SIZE, AND
FUSING, IF REQUIRED, DESIGNATED ON DRAWINGS)
ENCLOSED CIRCUIT BREAKER (ENCLOSURE
TYPE, SIZE DESIGNATED ON DRAWINGS)
MOTOR CONTROLLER (ENCLOSURE TYPE,
SIZE DESIGNATED ON DRAWINGS)
COMBINATION STARTER/CIRCUIT BREAKER
(ENCLOSURE TYPE, SIZE DESIGNATED ON DRAWINGS)
VARIABLE FREQUENCY DRIVE (ENCLOSURE
TYPE, SIZE DESIGNATED ON DRAWINGS)
DRY TYPE TRANSFORMER - FLOOR MOUNTED
ON 4" HIGH HOUSEKEEPING PAD
EXTERIOREXISTING NEW
POLE, LENGTH AND CLASS AS INDICATED
DISCONNECT SWITCH OR
SECTIONALIZING SWITCH
XXX
OR
XXXXXX
OR
XXXXXX
XXX
OR WALLPACK EXTERIOR LUMINAIRE
WITH EMERGENCY BATTERY XXX
OR
XXX XXX
GROUND ROD, SIZE AS NOTED 3/4" X 10'
(W DENOTES INSTALLATION IN WELL)
LF-X
LF-X
LF-X
LF-X
EMERGENCY REMOTE HEAD
SUBSCRIPTS INDICATE THE FOLLOWING:
LF-X = INDICATES LUMINAIRE TYPE
E = INDICATES EMERGENCY BATTERY BACKUP
a = DENOTES SINGLE SWITCH DESIGNATION a/b = DENOTES DUAL SWITCH DESIGNATION
LF-X
LF-X
LF-X
LF-X
X
SUBSCRIPTS INDICATE THE FOLLOWING:
a = SWITCH DESIGNATION
D = DIMMER
2 = DOUBLE-POLE
3 = THREE-WAY
4 = FOUR-WAY
K = KEY-OPERATED
OC = OCCUPANCY SENSOR
P = PILOT LIGHT
T = TIMER
L = LOW-VOLTAGE
M = MOTOR RATED WITH OVERLOAD PROTECTION
IG = ISOLATED GROUND
EXP = EXPLOSION PROOF
WP = WEATHERPROOF
DR = DOOR SWITCH
X MULTIPLE WALL SWITCHES 120-277 VOLT, 20 AMP,
MTD IN A SINGLE BOX
OR OC
OC
P
OR
SUBSCRIPTS INDICATE THE FOLLOWING:
WP = WEATHERPROOF, IN-USE COVER
WR = WEATHER-RESISTANT WIRING DEVICE
GFCI = GROUND FAULT CIRCUIT INTERRUPTER
GF-BF = BLANK FACE GROUND FAULT INTERRUPTER
IG = ISOLATED GROUND
EXP = EXPLOSION PROOF
ACT = ABOVE COUNTER TOP
TR = TAMPER-RESISTANT WIRING DEVICE
AFCI = ARC FAULT CIRCUIT INTERRUPTER
SPD = SURGE PROTECTION DEVICE
SINGLE RECEPTACLE, 125 VOLT, 2-POLE, 3-WIRE, NEMA 5-20R
GROUNDING TYPE
SINGLE SPECIAL PURPOSE RECEPTACLE,
NEMA CONFIGURATION NOTED
FLOOR MOUNTED DUPLEX RECEPTACLE, 125-VOLT,
2-POLE, 3-WIRE, NEMA 5-20R GROUNDING TYPE
RANGE RECEPTACLE, 125/250 VOLT, 3-POLE, 4-WIRE,
NEMA 14-50R GROUNDING TYPE
FLOOR MOUNTED QUADRAPLEX RECEPTACLE, 125-VOLT,
2-POLE, 3-WIRE, NEMA 5-20R GROUNDING TYPE
POWER DEVICES
PP POWER PACK W/ 0-10V DIMMING OUTPUT
D
MOTOR CONNECTION (5 HP INDICATED)
PANELBOARD, SURFACE MOUNTED
PANELBOARD, RECESSED
BURIED GROUND WIRE
GROUND WIRE IN OR UNDER FLOOR SLAB
GROUND WIRE EXPOSED
GROUND CONNECTION OR EQUIPMENT BOND
ROOF CONDUCTOR
POLE MOUNTED LUMINAIRE
WALLPACK EXTERIOR LUMINAIRE
SINGLE LINE DIAGRAMS/CONTROLS
ELAPSED TIME METER
TIMER MOTOR
CONTROL RELAY
SOLENOID VALVE
CONNECTION
LIMIT SWITCH
CONNECTION
THERMOSTAT
CONNECTION
PHOTOCELL
PRESSURE SWITCH
CONNECTION
AMMETER
EXHAUST FAN MOTOR
VOLTMETER
WATTMETER
WATTHOUR METER
LINE REACTOR
M MOTOR STARTER COIL
SWITCH, NONFUSED
FUSED SWITCH
E-STOP
EMERGENCY STOP
PUSHBUTTON STATION
OR
N.O.T.C.
TIMER CONTACT -
NORMAL OPEN, TIME
CLOSE
N.C.T.O.
TIMER CONTACT -
NORMAL CLOSE, TIME
OPEN
N.O.T.O.
TIMER CONTACT -
NORMAL OPEN, TIME
OPEN
N.C.T.C.
TIMER CONTACT -
NORMAL CLOSE, TIME
CLOSE
FLOAT SWITCH
(NORMALLY CLOSED)
GENERAL NOTES:
1. THE MINIMUM STANDARD FOR ALL WORK SHALL BE THE
LATEST EDITION OF THE INTERNATIONAL BUILDING CODE
WITH IN STATE AMENDMENTS AND THE NATIONAL
ELECTRICAL CODE (NEC).
2. ALL ELECTRICAL WORK SHALL BE PERFORMED BY AN
IN-STATE LICENSED ELECTRICIAN.
3. ALL PERMITS NEEDED TO LEGALLY PERFORM THE
ELECTRICAL WORK SHALL BE OBTAINED BY THE
CONTRACTOR PRIOR TO START OF WORK. COST OF
PERMITTING IS BY THE CONTRACTOR.
4. AT COMPLETION OF THE WORK, A CERTIFICATE OF
COMPLIANCE FROM THE LOCAL AHJ OVER THE
ELECTRICAL WORK SHALL BE PROVIDED TO THE
ENGINEER AND OWNER. COST OF ELECTRICAL
INSPECTION IS BY THE CONTRACTOR.
5. ALL MATERIALS USED IN THE PROJECT GENERALLY SHALL
BE NEW AND UNUSED, UNLESS OTHERWISE NOTED ON
THE DRAWINGS. ALL NEW MATERIALS SHALL BE LISTED
AND LABELED BY UL OR OTHER ACCEPTABLE LISTING
AGENCY, WHERE A LISTING EXISTS.
6. THE CONTRACTOR SHALL VISIT THE SITE(S) PRIOR TO
BIDDING TO FAMILIARIZE THEMSELVES WITH PROJECT
REQUIREMENTS AND EXISTING CONDITIONS.
7. FIRESTOP ALL NEW CONDUIT INSTALLED THROUGH
EXISTING OR NEW FIRE RATED ASSEMBLIES.
8. SHOP DRAWINGS SHALL BE SUBMITTED ON ALL
ELECTRICAL MATERIALS AND EQUIPMENT FOR
ACCEPTANCE PRIOR TO PURCHASE BY THE
CONTRACTOR.
9. WHEN AN ITEM DEMOLISHED IS REMOVED, REMOVE ALL
CONCRETE PADS, FASTENERS, CONDUIT AND WIRING.
SCARIFY SURFACE AND RESTORE TO MATCH EXISTING
SURROUNDING SURFACE, INCLUDING PAINTING TO
MATCH.
10. ALL NEW WIRING SHALL BE ENCLOSED IN AN APPROVED
RACEWAY SYSTEM. OPEN WIRING IS PROHIBITED.
11. CIRCUIT BREAKERS USED FOR HVAC EQUIPMENT LOADS
SHALL BE HACR TYPE.
12. ENSURE DEDICATED ELECTRICAL SPACE IS PROVIDED AT
ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC
ARTICLE 110.26.
13. UP TO 3 CIRCUITS MAY BE COMBINED IN ONE CONDUIT, AS
LONG AS NEC DERATING RULES ARE FOLLOWED.
14. ALL CIRCUITS SHALL HAVE A DEDICATED NEUTRAL.
SHARED NEUTRALS AND MULTI-WIRE CIRCUITS ARE NOT
TO BE USED EXCEPT POSSIBLY TO COORDINATE WITH
SYSTEMS FURNITURE. SEE POWER PLAN.
15. 120 VOLT CIRCUITS THAT EXCEED 75 LINEAR CIRCUIT
FEET SHALL BE INCREASED TO #10 AWG AS A GENERAL
RULE. OTHER CIRCUITS WILL BE DESIGNED SPECIFICALLY
WITH VOLTAGE DROP CONSIDERED IN CONDUCTOR
SIZING.
16. COORDINATE ALL MOTOR STARTERS, FEEDERS AND
DISCONNECT SWITCHES FOR HVAC AND OTHER
UTILIZATION EQUIPMENT ACTUALLY PROVIDED IN
ACCEPTED SHOP DRAWINGS.
17. IN ORDER TO COMPLY WITH OSHA REQUIREMENTS, NO
OPERATOR DEVICE OF ANY PANEL OR DISCONNECT OR
MOTOR CONTROL SHALL BE HIGHER THAN 6'-6" AFF.
18. PROVIDE AN EXTERIOR RATED SERVICE RECEPTACLE
WITHIN 25 FEET HORIZONTALLY OF ANY EXTERIOR OR
ROOFTOP HVAC OUTDOOR UNIT (HEATING OR AIR
CONDITIONING ONLY).
19. SUPPORT ALL LUMINAIRES FROM THE STRUCTURE, NOT
FROM THE SUSPENDED CEILING GRID. ALSO ATTACH THE
LUMINAIRES TO THE GRID SYSTEM USING EARTHQUAKE
CLIPS (SIMILAR TO ERICO/CADDY FASTENERS OR
T&B/STEEL CITY).
20. DEVICE PLATES SHALL BE INSTALLED PLUMB. JUMBO OR
OVERSIZED PLATES SHALL NOT BE USED.
21. NEW RECEPTACLES SHALL BE INSTALLED WITH GROUND
PIN ORIENTATION TO MATCH EXISTING. IN NEW
CONSTRUCTION, GROUND PIN DOWN ABOVE COUNTERS
OR WORK BENCHES AND UP FOR LOW WALL MOUNTED
DEVICES.
22. AT COMPLETION OF PROJECT, ALL ELECTRICAL,
TELECOMMUNICATIONS, AND ELECTRONIC SAFETY
SYSTEMS SHALL BE FULLY OPERATIONAL.
23. INSTALL A NYLON PULLSTRING IN ALL SPARE CONDUITS,
ACCESSIBLE AT BOTH ENDS. CAP OFF SPARE CONDUITS
ON BOTH ENDS.
24. EGRESS LUMINAIRES AND EXIT SIGNS REQUIRE
UNSWITCHED LIGHTING CONDUCTOR.
25. WHERE DUPLEX RECEPTACLES ARE INDICATED
GENERALLY BACK TO BACK ON OPPOSITE SIDES OF A
PARTY WALL, THE RECEPTACLES SHALL NOT BE
INSTALLED IN THE SAME STUD SPACE, BUT SHALL BE
SEPARATED BY AT LEAST ONE STUD SPACE.
26. PROVIDE LABEL WITH ESTIMATED FAULT CURRENT AND
DATE CALCULATED ON THE MAIN SERVICE DISCONNECT
ENCLOSURE. PROVIDE COORDINATION STUDY AND ARC
FLASH STUDY, AND APPLY JOB SPECIFIC ARC FLASH
HAZARD WARNING LABELS ON ALL SWITCHBOARDS,
SWITCHGEAR, MCC'S AND PANELBOARDS.
E
AIRPORT PLANNING / DEVELOPMENT
ARCHITECTURE / INTERIOR DESIGN
CIVIL ENGINEERING / SITE DEVELOPMENT
ENVIRONMENTAL ENGINEERING
LANDSCAPE ARCHITECTURE
SURVEYING
St. Albans, WV
(304) 727-5501
Buckhannon, WV
(304) 472-8914 a division of
GRW
AutoCAD SHX Text
PARKS AND RECREATION
AutoCAD SHX Text
BLUESTONE STATE PARK
AutoCAD SHX Text
ADA TOILET ROOMS AND SIDEWALK
AutoCAD SHX Text
AUGUST 2023
AutoCAD SHX Text
WV DIVISION OF NATURAL RESOURCES
AutoCAD SHX Text
HINTON, WEST VIRGINIA
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
PROJECT INFORMATION
AutoCAD SHX Text Chapman
AutoCAD SHX Text Technical
AutoCAD SHX Text Group
AutoCAD SHX Text www.chaptech.com
AutoCAD SHX Text
WLM
AutoCAD SHX Text
JPR
AutoCAD SHX Text
JPR
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 22005
AutoCAD SHX Text E-001
AutoCAD SHX Text
ELECTRICAL SYMBOLS
AND GENERAL NOTES
SCALE: 1/2"=1'-0" 0 2' 4'1'1 PARK HEADQUARTERS TOILET ROOM - ELECTRICAL PLAN
LF-1E LF-1E 1
GENERAL NOTES:
A. PROVIDE AN UNSWITCHED LIGHTING CONDUCTOR
TO EACH LUMINAIRE CONTAINING AN EMERGENCY
BATTERY DRIVER.
SHEET KEYNOTES:
1. PROVIDE TWO (2) #12 CONDUCTORS AND ONE (1) #12
GROUND IN 3/4" CONDUIT TO EXISTING LIGHTING
BRANCH CIRCUIT SERVING THIS AREA.
2. PATCH AND REPAIR WOOD CEILING TO MATCH
EXISTING AS REQUIRED AFTER INSTALLATION OF
THE NEW LUMINAIRE.
AIRPORT PLANNING / DEVELOPMENT
ARCHITECTURE / INTERIOR DESIGN
CIVIL ENGINEERING / SITE DEVELOPMENT
ENVIRONMENTAL ENGINEERING
LANDSCAPE ARCHITECTURE
SURVEYING
St. Albans, WV
(304) 727-5501
Buckhannon, WV
(304) 472-8914 a division of
GRW
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
JOB NUMBER:
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
PROJECT INFORMATION
AutoCAD SHX Text Chapman
AutoCAD SHX Text Technical
AutoCAD SHX Text Group
AutoCAD SHX Text www.chaptech.com
AutoCAD SHX Text
WLM
AutoCAD SHX Text
JPR
AutoCAD SHX Text
JPR
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 22005
AutoCAD SHX Text E-100
AutoCAD SHX Text
PARK HEADQUARTERS
AutoCAD SHX Text
TOILET ROOM
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text
PARKS AND RECREATION
AutoCAD SHX Text
BLUESTONE STATE PARK
AutoCAD SHX Text
ADA TOILET ROOMS AND SIDEWALK
AutoCAD SHX Text
AUGUST 2023
AutoCAD SHX Text
WV DIVISION OF NATURAL RESOURCES
| 22005-bs-01 |
| 22005-bs-02 |
| 22005-bs-03 |
| 22005-bs-04 |
| 22005-bs-05 |
| 22005-bs-06 |
| 22005-bs-07 |
| 22005-bs-08 |
| 22005-bs-09 |
| 22005-bs-10 |
| 22005-bs-11 |
| 22005-bs-12 |
| 22005-bs-13 |
| 22005-bs-14 |
| 22005-bs-15 |
| 22005-BS-S-001-Layout1 |
| 22005-bs-16 |
| 22005-bs-17 |
| 22005-bs-18 |
| 22005-bs-19 |
| 22005-bs-20 |
| 22005-BS-P-100-P-100 |
| Sheets and Views |
| P-100 |
| 22005-BS-ED-100 |
| Sheets and Views |
| ED-100 |
| 22005-BS-E-001 |
| Sheets and Views |
| E-00-001 |
| 22005-BS-E-100 |
| Sheets and Views |
| E-100 |
File details come from the government source that posted it. Updated .