This document provides details on a federal solicitation amendment for the Lovell Control Building and Breaker Replacement project. The solicitation number 89503222BWA000051 has been amended under number AMD0001 by the Department of Energy Western Area Power Administration to procure services for replacing the control building and breakers at the Lovell substation. The amendment references Attachment B - Drawings but does not provide further details on the specific products, services, response deadline, or award date required by the agency.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment B
Drawings AMD 0001
89503222BWA000051
15 July 2022
PROJECT DRAWINGS
LOVELL SUBSTATION
SERVICE BUILDING AND BREAKER REPLACEMENT
STATE
SECTION C
DESCRIPTION/SPECIFICATIONS
Spec. No. 1048
WYOMING
SERVICE BUILDING and BREAKER REPLACEMENT
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION DRAWINGS: Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale. Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: Where details shown on standard drawings included herein differ from construction or project drawings or text, the details of construction or project drawings or text shall govern. A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise WAPA of any errors or omissions.
B. LIST OF DRAWINGS:
LOCATION MAP:
1. LV 0016 Rev D – Location and Vicinity Map
ELECTRICAL:
2. LV 0001 Rev R (EI) – Switching Diagram (Existing Installation)
3. LV 0001 Rev S – Switching Diagram
4. LV 0010 Rev J (EI) – General Plot Plan (Existing Installation)
5. LV 0010 Rev K – General Plot Plan
6. LV 1000 E (FIO) – 12.47kV Bus Structures Sections G-G & J-J (For Information Only)
7. LV 1001 G (EI) – 115/34.5kV Transformer KY4A Area Plan (Existing Installation)
8. LV 1001 H – 115/34.5kV Transformer KY4A Area Plan
9. LV 1002 G (EI) – 69kV Bus Structure Sections B-B, C-C, & D-D (Existing Installation)
10. LV 1002 H – 69kV Bus Structure Sections B-B, C-C, & D-D
11. LV 1003 G (EI) – 115-34.5kV Transformer Sections A-A, B-B, E-E, & I-I (Existing Installation)
12. LV 1003 H – 115-34.5kV Transformer Sections A-A, B-B, E-E, & I-I
13. LV 1004 E (EI) – 115kV Bus Structure Section D-D (Existing Installation)
14. LV 1004 F – 115kV Bus Structure Section D-D
15. LV 1005 M (EI) – 115kV Bus Structure Equipment and Bus Plan (Existing Installation)
16. LV 1005 N – 115kV Bus Structure Equipment and Bus Plan
17. LV 1006 I (EI) – 115kV Bus Structure Sections A-A & PP (Existing Installation)
18. LV 1006 J – 115kV Bus Structure Sections A-A & PP
19. LV 1007 G (EI) – 115kV Bus Structure Section B-B (Existing Installation)
20. LV 1007 H – 115kV Bus Structure Section B-B
21. LV 1008 G (EI) – 115kV Bus Structure Section C-C (Existing Installation)
22. LV 1008 H – 115kV Bus Structure Section C-C
23. LV 1009 D (EI) – 115kV Bus Structure Section E-E (Existing Installation)
24. LV 1009 E – 115kV Bus Structure Section E-E
25. LV 1010 J (EI) – 115kV Bus Structure Sections H-H & R-R (Existing Installation)
26. LV 1010 K – 115kV Bus Structure Sections H-H & R-R
27. LV 1012 E (EI) – 115kV Sections Section M-M (Existing Installation)
28. LV 1012 F – 115kV Sections Section M-M
29. LV 1015 C (EI) – 34.5kV & 12.47kV Bus Structures Sections C-C and F-F (Existing Installation)
30. LV 1015 D – 34.5kV & 12.47kV Bus Structures Sections C-C and F-F
31. LV 1017 C (EI) – 69/115kV XFMR Structure Sections A-A, E-E, F-F & G-G (Existing Installation)
32. LV 1017 D – 69/115kV XFMR Structure Sections A-A, E-E, F-F & G-G
33. LV 1018 E (EI) – 115kV Bus Structures Sections S-S & T-T (Existing Installation)
34. LV 1018 F – 115kV Bus Structures Sections S-S & T-T
35. LV 1019 (EI) – 115kV Transformer KY1A Area Plan (Existing Installation)
36. LV 1019 A – 115kV Transformer KY1A Area Plan
37. LV 1100 G – Equipment and Material Index
38. LV 1101 C – Equipment and Material Index
39. LV 1102 – Substation Signs
40. LV 1500 Rev B (EI) – 69kV Bus Structure Conduit and Grounding Plan (Existing Installation)
41. LV 1500 Rev C – 69kv Bus Structure Conduit and Grounding Plan
42. LV 1501 Rev C (EI) – 34.5kV Grounding and Conduit Plan (Existing Installation)
43. LV 1501 Rev D – 34.5kV Grounding and Conduit Plan
44. LV 1502 Rev F (EI) – 115kV Bus Structure Conduit and Grounding Plan (Existing Installation)
45. LV 1502 Rev G – 115kV Bus Structure Conduit and Grounding Plan
46. LV 1503 – Communications Grounding Details
47. 31 1502 – Communication Site Grounding – Typical Plan
48. 31 1503 – Communication Tower Grounding – Details
49. 31 1504 Rev. B – Building Growing Substation Details
50. LV 1610 Rev. C (EI) – Unit Substation DWA Wiring Diagram (Existing Installation)
51. LV 1610 Rev. E – Unit Substation DWA Wiring Diagram
CIVIL & SITE DRAWINGS:
52. LV 2017 Rev B (FIO) – Grading and Drainage Plan (For Information Only)
53. LV 2018 Rev B (FIO) – Grading & Drainage Facility (For Information Only)
FOUNDATION and STRUCTURAL DRAWING INDEX:
54. LV 2001-1 – Foundation/Structural Data and Drawings Index (Sh 1 of 2)
55. LV 2001-2 – Foundation/Structural Data and Drawings Index (Sh 2 of 2)
FOUNDATION PLANS:
56. LV 2000 Rev J (EI) – Foundation General Plan (Existing Installation)
57. LV 2000-1 – General Foundation Plan (Sh 1 of 4)
58. LV 2000-2 – 115/34.5kV Transformer KY4A Area Foundation Plan (Sh 2 of 4)
59. LV 2000-3 – 115kV Bus Structure Foundation Plan (Sh 3 of 4)
60. LV 2000-4 – 115kV Transformer Foundation Plan (Sh 4 of 4)
CONCRETE:
61. LV 2004 Rev D – Foundations Outline and Reinforcement
62. LV 2012 Rev E – Foundations Outline and Reinforcement
63. LV 2025 Rev E – Foundations Outline and Reinforcement
64. LV 2048 (EI) – Foundations Outline and Reinforcement (Existing Installation)
65. LV 2048 Rev A – Foundations Outline and Reinforcement
66. LV 2300 Rev A – Foundations Outline and Reinforcement
67. LV 2301 – Foundations Outline and Reinforcement
68. LV 2550 – Anchor Bolts & Embeds
69. LV 2877 – 30-Foot Monopole Drilled Auger Type
70. LV 2878 – 30-Foot Monopole Foundation Layout
CABLE TRENCH:
71. LV 2026-1 Rev A (FIO) – Cable Trench Plan, Sections and Details (For Information Only)
72. LV 2026-2 Rev A (FIO) – Cable Trench Plan, Sections and Details (For Information Only)
73. LV 2026-3 Rev A (EI) – Cable Trench Plan, Sections and Details (Existing Installation)
74. LV 2026-3 Rev B – Cable Trench Plan, Sections and Details
75. LV 2501 – Cable Trench Plan
STEEL STRUCTURES:
76. LV 2052 (FIO) – Equipment Supports (For Information Only)
77. LV 2054 (FIO) – 34.5 kV SW & Fuse Support Type I (For Information Only)
78. LV 2600 – Bus and Equipment Support Type I
79. LV 2925 – Equipment Cabinet Platform Type VII Details
80. LV 2876 – 30-Foot Monopole Outline
CONTROL BUILDING:
81. 01 2004-1 Rev. D – Concrete Standards – General Outline & Reinforcement Notes
82. 01 2004-2 Rev. D – Concrete Standards – General Outline & Reinforcement Notes
83. 01 2006-1 – Concrete Standards – Building Slabs-On-Ground Specifications, Notes, Plans & Details (Sheet 1 Of 3)
84. 01 2006-2 – Concrete Standards – Building Slabs-On-Ground Specifications, Notes, Plans & Details (Sheet 2 Of 3)
85. 01 2006-3 – Concrete Standards – Building Slabs-On-Ground Specifications, Notes, Plans & Details (Sheet 3 Of 3)
86. 31 2049-1 Rev. B – Control Switchboard Equipment & Communication Rack – Base Anchorage Details (Sheet 1 Of 2)
87. 31 2051 Rev. B – Structural Building Entry Platforms
88. LV 3010 – Architectural Floor Plan
89. LV 3011 – Battery Room Bridge Crane
90. LV 3012 Rev A – Reflected Ceiling Plan
91. LV 3014 – Elevations
92. LV 3016 – Building Sections
93. LV 3018 – Architectural Detailed Wall Sections
94. LV 3020 – Architectural Details
95. LV 3022 – Architectural Detailed Sections
96. LV 3024 – Door Schedules & Details
97. LV 3200 – General Structural Notes, Abbreviations & Reference Drawings
98. LV 3201 Rev A – Structural Foundation Plan
99. LV 3202 – Structural Roof Framing Plan
100. LV 3203-1 – Structural Foundation Sections & Details (Sh 1 Of 2)
101. LV 3203-2 – Structural Foundation Sections & Details (Sh 2 Of 2)
102. LV 3204-1 – Structural Foundation/Cable Entry Details (Sh 1 Of 2)
103. LV 3204-2 – Structural Foundation/Cable Entry Details (Sh 2 Of 2)
104. LV 3205-1 – Structural Typical Wood-Framed Wall (Sh 1 Of 2)
105. LV 3205-2 – Structural Typical Wood-Framed Wall (Sh 2 Of 2)
106. LV 3206 – Structural Equipment Mounting Details
107. LV 3300 – Mechanical-General Notes & Legends
108. LV 3301 – Mechanical HVAC Floor Plan
109. LV 3302 – Mechanical Details I
110. LV 3303 – Mechanical Details II
111. LV 3304 – Mechanical HVAC Schedules
112. LV 3305 – Mechanical HVAC Controls
113. LV 3306 - Mechanical HVAC Sections I
114. LV 3307 - Mechanical HVAC Sections II
115. LV 3400 Rev A – Electrical Power Plan
116. LV 3401 Rev A – Electrical Lighting Plan
117. LV 3402 Rev A – Electrical Security Plan
118. LV 3403 Rev A – Electrical Panelboards DHA, DHB
119. LV 3404 Rev A – Electrical Wiring Devices Schematic
120. LV 3405 Rev A – Electrical Luminaire and Equipment Schedules
CONTROLS:
121. LV T600-1 – Control Cable List (SH 1 OF 2)
122. LV T600-2 – Control Cable List (SH 2 OF 2)
123. LV 1611D – Outdoor Lighting Wiring Diagram
124. LV 4000 Rev I – Service Building Conduit, Arrangement, & Grounding
125. LV 6000 Rev I – 125VDC Distribution Panel BHA1 & BHA2 WD
126. LV 6021-1 Rev B – 115kV PT VY1A Wiring Diagram
127. LV 6021-2 Rev A – 115kV CCVT VY2A1 Wiring Diagram
128. LV 6021-3 Rev B – 115kV CCVT VY3A1 Wiring Diagram
129. LV 6021-4 Rev B – 115kV CCVT VY4A1 Wiring Diagram
130. LV 6021-5 Rev B – 115kV CCVT VY5A1 Wiring Diagram
131. LV 6021-6 Rev A – 115kV CCVT VY6A1 Wiring Diagram
132. LV 6021-7 Rev A – 115kV CCVT VY7A1 Wiring Diagram
133. LV 6022-1 – 69kV CCVT VZ1B Wiring Diagram
134. LV 6022-2 – 69kV CCVT VZ1A1 Wiring Diagram
135. LV 6023 Rev E – 34.5kV VX1A & VX2A & CT'S QX1A & QX2A WD
136. LV 6024 Rev D – 12.47kV CT QW1A & PT VW1A WD
137. LV 6146 – 12.47kV VW1B and RW1B Wiring Diagram
138. LV 6147 – 12.47kV VW4A and RW4A Wiring Diagram
GEOLOGY:
139. LV 0015 Rev C – Topographic Map and Location of Exploration
140. LV 8000 Rev B – Logs of Exploration
141. LV 8001 Rev B – Logs of Exploration
142. LV 8002 Rev B – Logs of Exploration
143. LV 8003 Rev B – Logs of Exploration
144. LV 8004 Rev B – Logs of Exploration
145. LV 8005 Rev B – Logs of Exploration
SUITABLE FOR CONSTRUCTION AS OF:
May 16, 2022- 4:32pm
May 16, 2022- 4:25pm
May 16, 2022- 4:27pm
May 16, 2022- 4:28pm
May 16, 2022- 4:31pm
May 16, 2022- 4:30pm
May 17, 2022- 6:56am
May 17, 2022- 6:59am
May 16, 2022- 5:10pm
POLE A POLE B POLE C
OPENOPENOPENOPEN
8D 8M
125VDC
MOTOR
May 16, 2022- 5:11pm
May 16, 2022- 5:13pm
May 17, 2022- 7:02am
May 16, 2022- 5:19pm
May 17, 2022- 7:04am
May 16, 2022- 5:29pm
May 17, 2022- 7:06am
May 16, 2022- 5:32pm
May 17, 2022- 7:32am
May 16, 2022- 5:33pm
SU
IT
AB
LE
F O
R C
O N
ST
R
U C
TI
O
N A
S O
F:
J ul
6, 3-
0:
am
May 17, 2022- 7:34am
May 16, 2022- 5:35pm
May 17, 2022- 7:36am
May 16, 2022- 5:37pm
May 17, 2022- 7:40am
May 16, 2022- 5:39pm
May 17, 2022- 7:43am
May 16, 2022- 5:40pm
May 17, 2022- 7:51am
May 16, 2022- 5:42pm
May 17, 2022- 7:54am
May 16, 2022- 5:44pm
May 17, 2022- 7:58am
May 16, 2022- 5:45pm
May 17, 2022- 8:02am
May 16, 2022- 5:47pm
May 17, 2022- 8:03am
May 16, 2022- 5:49pm
May 16, 2022- 5:50pm
May 16, 2022- 5:52pm
TRANSFORMER KY4A
LV 462
PCB JY4A 115KV
TRANSFORMER KY1A
LV 162
PCB JY1A 115KV
YELLOWTAIL NO. 1
LV 662
PCB JY2A 115KV
HILLTOP-THERMOPOLIS
LV 762
PCB JY3A 115KV
YELLOWTAIL NO. 2
LV 862
PCB JY6A 115KV
BIG HORN REA
VX1B1
INSTR XFMR 34.5KV
BIG HORN REA
VX1B2
INSTR XFMR 34.5KV
BIG HORN REA
VX1B3
INSTR XFMR 34.5KV
YELLOWTAIL NO. 1
VY2A1
INSTR XFMR 115KV
YELLOWTAIL NO. 1
EY2A
SECONDARY FUSE
TRANSFER BUS
VY4A1
INSTR XFMR 115KV
TRANSFER BUS
EY4A
SECONDARY FUSE
HILLTOP-THERMOPOLIS
VY3A1
INSTR XFMR 115KV
HILLTOP-THERMOPOLIS
EY3A
SECONDARY FUSE
YELLOWTAIL NO. 2
VY6A1
INSTR XFMR 115KV
YELLOWTAIL NO. 2
EY6A
SECONDARY FUSE
BIG GEORGE
VY7A1
INSTR XFMR 115KV
BIG GEORGE
EY7A
SECONDARY FUSE
GROUND FAULT CIRCUIT
VW4A1
VT 12.47KV
GROUND FAULT CIRCUIT
VW4A2
VT 12.47KV
GROUND FAULT CIRCUIT
VW4A3
VT 12.47KV
GROUND FAULT CIRCUIT
RW4A
RESISTOR 208V
GROUND FAULT CIRCUIT
EW4A
TERMINAL BLOCKS
GROUND FAULT CIRCUIT
VW1B1
VT 12.47KV
GROUND FAULT CIRCUIT
VW1B2
VT 12.47KV
GROUND FAULT CIRCUIT
VW1B3
VT 12.47KV
GROUND FAULT CIRCUIT
RW1B
RESISTOR 208V
GROUND FAULT CIRCUIT
EW1B
TERMINAL BLOCKS
NORTH CODY
EZ1A
SECONDARY FUSE
TRANSFORMER KY1A
EZ1B
SECONDARY FUSE
May 16, 2022- 5:53pm
May 17, 2022- 8:07am
May 16, 2022- 5:55pm
May 17, 2022- 8:09am
May 16, 2022- 5:57pm
May 17, 2022- 8:11am
May 16, 2022- 6:00pm
AS OF: May 16, 2022- 6:01pm
NOT TO BE USED FOR REVIEW SETINTERNAL ENGINEERING REVIEW
May 16, 2022- 6:01pm
May 17, 2022- 8:13am
Jul 11, 2022- 11:13am
May 17, 2022- 8:19am
May 17, 2022- 8:24am
May 16, 2022- 6:16pm
May 16, 2022- 6:17pm
May 17, 2022- 8:15am
May 16, 2022- 6:05pm
May 16, 2022- 6:07pm
May 16, 2022- 6:07pm
May 16, 2022- 6:10pm
May 16, 2022- 6:12pm
May 16, 2022- 6:14pm
May 17, 2022- 8:17am
May 16, 2022- 6:52pm
May 16, 2022- 6:53pm
May 17, 2022- 8:42am
May 17, 2022- 8:38am
May 16, 2022- 7:03pm
May 17, 2022- 8:49am
May 16, 2022- 7:08pm
May 16, 2022- 7:13pm
May 16, 2022- 7:14pm
May 17, 2022- 8:26am
May 17, 2022- 8:30am
May 17, 2022- 8:32am
May 16, 2022- 6:55pm
May 16, 2022- 7:07pm
May 17, 2022- 8:45am
May 17, 2022- 8:47am
May 16, 2022- 7:10pm
May 16, 2022- 7:16pm
May 16, 2022- 7:11pm
Ψ
Ψ
Ψ
Ψ
May 16, 2022- 7:18pm
May 16, 2022- 7:19pm
Jul 11, 2022- 11:15am
May 16, 2022- 7:23pm
May 16, 2022- 7:25pm
May 16, 2022- 7:27pm
May 16, 2022- 7:28pm
May 16, 2022- 7:30pm
May 16, 2022- 7:31pm
May 16, 2022- 7:33pm
Jul 11, 2022- 11:17am
May 16, 2022- 7:38pm
May 16, 2022- 7:39pm
May 16, 2022- 7:41pm
May 16, 2022- 7:43pm
May 16, 2022- 7:44pm
May 16, 2022- 7:46pm
May 16, 2022- 7:48pm
May 16, 2022- 7:49pm
AIRFLOW ARROW
BA BREATHING AIR DROP
CA COMPRESSED AIR DROP
SUPPLY AIR OR OUTSIDE AIR
ROUND DUCT SECTION
RETURN AIR ROUND DUCT
SECTION
EXHAUST AIR ROUND DUCT
SECTION
DP
DIFFERENTIAL PRESSURE
SENSOR
S STATIC PRESSURE SENSOR
OCC OCCUPANCY SENSOR
ROUND & RECTANGULAR DUCT
TAKEOFF
CO CARBON MONOXIDE SENSOR
HVAC LEGEND
M
CONTROL DAMPER, MOTOR
OPERATED
MANUAL BALANCE DAMPER
BD
BACKDRAFT DAMPER
AD
AD
ACCESS DOOR (AD)
ACCESS PANEL (AP)
S
AD
S
DAMPERS:
FIRE (F) -
SMOKE (S) -
FIRE SMOKE (F/S) -
AD
SECURITY BARS
FLEXIBLE DUCT CONNECTION
RECTANGLUAR ELBOW WITH
TURNING VANES
RECTANGULAR TEE WITH
TURNING VANES
RECTANGULAR RADIUS ELBOW
R RISE IN RESPECT TO AIR-FLOW
D DROP IN RESPECT TO AIR-FLOW
SQUARE OR RECTANGULAR TO
ROUND TRANSITION
SUPPLY AIR OR OUTSIDE AIR
RECTANGULAR DUCT SECTION
RETURN AIR RECTANGULAR
DUCT SECTION
EXHAUST AIR RECTANGULAR
DUCT SECTION
ROUND FLEXIBLE DUCT
(5'-0" MAX LENGTH)
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
T THERMOSTAT
CO2 CARBON DIOXIDE SENSOR
H HUMIDISTAT
LINEAR SLOT DIFFUSER
VAV-
VARIABLE AIR VOLUME
TERMINAL BOX
(3'-0") FINNED TUBE RADIATION.
LENGTH OF ELEMENT SHOWN
IN PARENTHESIS
ESS EMERGENCY SHUT-OFF SWITCH
M MOTOR
FCP FAN CONTROL PANEL
PIPE LINE ACCESSORIES
3-WAY VALVE
2-WAY VALVE
ANGLE VALVE
AV
AUTOMATIC AIR VENT
ASSEMBLY
BFP
BACKFLOW PREVENTION
ASSEMBLY
BALANCING VALVE / CIRCUIT
SETTER
BALL VALVE
BLIND FLANGE
BUTTERFLY VALVE
CHECK VALVE
FLEX CONNECTION
FLOW ARROW
FM FLOW METER
GATE VALVE
GLOBE VALVE
HOSE GATE DRAIN VALVE
IF
INSULATING FLANGE
MV
MANUAL AIR VENT ASSEMBLY
- SEE SPECIFICATIONS FOR
APPROPRIATE VALVE TYPE
M METER
M MOTORIZED CONTROL VALVE
OS&Y
OUTSIDE SCREW & YOKE VALVE
PIPE WITH HEAT TRACE
PLUG VALVE
PRESSURE GUAGE
SELF CONTAINED PRESSURE
REDUCING (REGULATING)
VALVE
PUMP
REDUCER (CONCENTRIC)
RELIEF, SAFETY OR THERMAL
RELIEF VALVE
REMOVABLE CAP
REMOVABLE PLUG
S STRAINER
SUCTION DIFFUSER
TEST CONNECTION
THERMOMETER
UNION
Y-TYPE STRAINER
SRC SPRING RETURN CLOSED BALL
VALVE
PIPE SYMBOLS
PIPE ELBOW
PIPE DOWN
PIPE UP
PIPE CONTINUATION
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
GENERAL NOTES & LEGENDS
JUNE 24, 2022
A. OHM D. OLSEN
PIPELINE ABBREVIATIONS
MECHANICAL ABBREVIATIONS GENERAL NOTES:
DETAIL / ENLARGED
CALLOUT SYMBOL
A
M-001
INDICATES
LIMITS OF
DETAIL/SECTION
DETAIL/SECTION
DESIGNATOR
SHEET WHERE
DETAIL/SECTION IS
SHOWN
DETAIL/SECTION TITLE
TITLE
A1
LOCATION WHERE
DETAIL / SECTION
IS SHOWN ON
SHEET
SECTION CUT SYMBOL
A
M-001
INDICATES PERSPECTIVE
AND LIMITS OF SECTION
SECTION
DESIGNATOR
DRAWING WHERE
SECTION IS SHOWN
CONSTRUCTION INTERFACE
DEMOLITION
EXISTING
NEW
EXISTING
EXISTING
NEW
DEMOLITION
AIR DISTRIBUTION DEVICE
IDENTIFICATION
AIR FLOW NECK SIZE
QUANTITY
SYSTEM TYPE SPEC. TYPE
SA-A
(2)175-8Ø
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS APPLICABLE TO
PROJECT. SEE PLANS FOR SPECIFIC SYMBOLS AND ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM ALL LABOR
REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE
DRAWINGS, AS SPECIFIED, AND AS REQUIRED BY CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND
REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL, CIVIL, ELECTRICAL
WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT DRAWINGS.
5. UNLESS OTHERWISE INDICATED MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND VALVING.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE, OR PIPE INSULATION
UNLESS NOTED OTHERWISE.
9. DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET METAL SIZE SHALL BE AIR OPENING DIMENSION PLUS THE THICKNESS OF ACOUSTICAL LINER WHERE LINER IS INSTALLED.
WHERE LINER IS NOT INSTALLED, AIR OPENING SIZE AND SHEET METAL SIZE SHALL BE THE SAME.
10. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND ARCHITECTURAL PLANS.
11. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR AND COORDINATE WITH OTHER
DEVICES LOCATED ON WALLS. COORDINATE WITH ARCHITECTURAL WALL FINISHES.
12. PROVIDE STRUCTURAL EQUIPMENT PADS IN ACCORDANCE WITH STRUCTURAL DRAWINGS AND
SPECIFICATIONS.
13. CONTRACTOR SHALL AIR BALANCE ALL GRILLES TO CFM'S SHOWN ON PLANS.
14. MOUNT ALL OVERHEAD MECHANICAL EQUIPMENT AND FIXTURES WEIGHING 31 POUNDS OR MORE TO SUPPORTS THAT SHALL RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL
DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION.
15. BASIS OF DESIGN MANUFACTURER AND MODEL ARE INCLUDED FOR COORDINATION PURPOSES.
PROVIDE BASIS OF DESIGN EQUIPMENT OR APPROVED EQUAL.
BLWDN BLOWDOWN
CD CONDENSATE DRAIN
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSATE RETURN
CT CHEMICAL TREATMENT
CTB COOLING TOWER BLOWDOWN
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
DI DEIONIZED WATER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
MPS MEDIUM PRESSURE STEAM
MW MAKEUP WATER (AFTER
BACKFLOW PREVENTER)
N NITROGEN
NG NATURAL GAS
O OXYGEN
PCR PUMPED CONDENSATE RETURN
V VACUUM
12"Ø ROUND DUCT DIMENSION
24x12 RECTANGULAR DUCT DIMENSION
(INCHES)
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
ARF ABOVE RAISED FLOOR
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
CD CONTROL DAMPER
CFM CUBIC FEET PER MINUTE
CL CENTER LINE OF PIPE ELEVATION
CONC CONCENTRIC
COND COOLING COIL CONDENSATE DRAIN
CTR CONTROLLER
CU CONDENSING UNIT
DB DRY BULB
DN DOWN
DRG DIFFUSER, REGISTER, GRILLE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
EL ELEVATION
ELL ELBOW
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
FCU FAN COIL UNIT
FF FLAT FACED
FO FLAT OVAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
HS HYDROGEN SENSOR
HT HUMIDITY TRANSMITTER
I.E. INVERT ELEVATION
IN. W.C INCHES WATER COLUMN
L LOUVER
LAT LEAVING AIR TEMPERATURE
LR LONG RADIUS
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MFR MANUFACTURER
MJ MECHANICAL JOINT
NC NORMALLY CLOSED (FAIL POSITION)
NO NORMALLY OPEN (FAIL POSITION)
OA OUTSIDE AIR
OB OPPOSED BLADE
PB PARALLEL BLADE
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
RA RETURN AIR
RED REDUCER-REDUCING
RL REFRIGERANT LIQUID
RMJ RESTRAINED MECHANICAL JOINT
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SCH SCHEDULE
SCR SPRING RETURN CLOSED
SHR SHORT RADIUS
SP STATIC PRESSURE SENSOR
SR SUPPLY REGISTER
ST STEAM TRAP
SW SOCKET WELD
TA TRANSFER AIR
TOA TREATED OUTSIDE AIR
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS TOP OF STEEL
V VENT
VFD VARIABLE FREQUENCY DRIVE
WB WET BULB
WE WELD END
WN WELD NECK
ZT ZONE TRANSMITTER
6/23/2022
CTR-1T
T
H
T T
TT
495-12x12
TA-A
495-12x12
RA-A
12x12 RA
7' - 0" BOD EL
VERTICAL SWITCHBOARDS
VERTICAL SWITCHBOARDS
C A
B L
E E
N T
R Y
B O
X
R E
F E
R
T O
S T
R U
C T
U R
A L
COMM RACKS
V
D C
B
A T
T E
R Y
CH-1
495-12x12
SA-B
ERU-1
12x12 SA
9' - 0" BOD EL
12x12 EA
9' - 0" BOD EL
12x12 OA
8' - 9" BOD EL
CD-2
LVR-1
16x14 SA
6' - 10" BOD EL
HS1
OCC
OCC
WEATHERHOOD 10
OT-1
ZT-1
HT-1
ZT-2 13
(6)235-10x10
SA-B
FCU-1CU-1
3/8" RL
7/8" RS
3/8" RL
7/8" RS
3/8" RL
5/8" RS
4 4
ST-2
ST-1 16
2019 20
3/4" COND2019
C
A
CD-1
18x18 OA
6' - 8" BOD EL
FCU-3
FCU-2
3/4" COND 3/4" COND
8 21
/1
1' - 0"
PAD BY
STRUCTURAL
CU-3CU-2
3 3
B
3' - 0"
PAD BY
STRUCTURAL
30' - 6"
2' - 1"
9' - 8 7/16"
/4
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC FLOOR PLAN
JUNE 24, 2022
A. OHM D. OLSEN
NOTES: KEYED NOTES:
1. CONTRACTOR SHALL LOCATE EQUIPMENT SUCH THAT ALL REQUIRED
MAINTENANCE CLEARANCE/ACCESS ARE COORDINATED WITH WORK BY
OTHER TRADES.
2. ALL HORIZONTAL DUCTWORK SHALL BE SUPPORTED PER SMACNA USING
UNISTRUT AND MIN 3/8" ALL-THREAD ROD, SPACED NO MORE THAN 6'-0"
APART. DUCT SHALL BE SECURED TO UNISTRUT BY 24 GAUGE 1-1/2" STRAP.
3. CONTRACTOR TO FIELD ROUTE ALL DUCTWORK. DUCTWORK SHALL BE
ROUTED BE BELOW CABLE TRAYS WERE THEY OCCURE. THIS DRAWING IS
FOR REFERANCE ONLY.
4. TESTING, ADJUSTING AND BALANCING (TAB) SHALL BE PERFORMED
FOLLOWING COMPLETION AND APPROVAL OF EACH HVAC SYSTEM.
5. REFRIGERANT PIPING SIZES AND ROUTING ARE DIAGRAMMATIC AND MUST
BE VERIFIED WITH EQUIPMENT MANUFACTURER PRIOR TO INSTALLATION.
1. FURNISH AND INSTALL MACURCO GD-6 HYDROGEN SENSOR OR APPROVED
EQUAL. INSTALL HYDROGEN SENSOR AT MOUNTING ELEVATION PER
MANUFACTURER'S RECOMMENDATIONS, OR WHERE NOT PROVIDED,
MOUNT 0'-6" BELOW CEILING. INTERLOCK WITH ERU-1. REFER TO
CONTROL SCHEMATIC ON DWG 3305 FOR DETAILS.
2. FURNISH AND INSTALL OCCUPANCY SENSOR, WATTSTOPPER MODEL
DT300 OR APPROVED EQUAL. MOUNT ON CEILING. INTERLOCK WITH ERU-1.
3. INSTALL CONDENSING UNIT WITH MANUFACTURER'S STANDARD 12"
EQUIPMENT STAND ON CONCRETE PAD WITH HILTI KWIK BOLT 3
EXPANSION ANCHORS 3/8"Ø WITH 3-1/2" EMBEDMENT IN CONCRETE.
4. MOUNT CONTROL ROOM UNIT ON FAN COIL SUPPORT AS DETAILED ON
DWG 3303, AND ON MANUFACTURER'S STANDARD PLENUM STAND. INSTALL
PIPING PER DETAIL 2 ON 3302.
5. INSTALL TRANSFER GRILLE WITH 1 HOUR FIRE DAMPER AT 1'-0" AFF.
REFER TO DETAIL 3 ON DWG 3303.
6. PENETRATION THROUGH BATTERY ROOM WALL SHALL BE SEALED WITH
FIRESTOP SEALANT, PER ARHITECTURAL REQUIREMENTS BY OTHERS.
CONTRACTOR TO PROVIDE FIRE-STOPPING DETAILS FOR PENETRATIONS
THROUGH FIRE WALL. INCLUDE UL SYSTEM NUMBERS FOR EACH DETAIL.
7. INSTALL ERU AT 8'-6" AFF TO BASE OF CABINET. VERIFY DUCT
CONNECTION SIZES WITH MANUFACTURER PRIOR TO INSTALLATION AND
UTILIZE DUCT TRANSITIONS AS NECESSARY.
8. INSTALL RETURN GRILLE WITH 1 HOUR FIRE DAMPER AT 9'-8" AFF.
9. PROVIDE WITH MOTORIZED DAMPER AT INLET OF LOUVER PER DETAIL 1
ON DWG 3302.
10. PROVIDE WITH MANUFACTURER'S STANDARD 12"x12" 45° WEATHERHOOD, GREENHECK WTHD-12 OR APPROVED EQUAL. PROVIDE WITH BACKDRAFT
DAMPER AND BIRDSCREEN PER DETAIL 4 ON DWG 3302. MOUNT AT
UNDERSIDE OF SOFFIT.
11. WALL MOUNT BATTERY ROOM UNIT 7'-9" AFF. INSTALL PIPING PER DETAIL 2
ON DWG 3302.
12. INSTALL CONVECTION HEATER AT 0'-0" AFF BELOW BATTERY ROOM UNIT
PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
13. PROVIDE ZONE TRANSMITTER ACCORDING TO SCHEDULE ON DWG 3304.
14. PROVIDE HUMIDITY TRANSMITTER ACCORDING TO SCHEDULE ON DWG
3304.
15. INSTALL OUTDOOR AIR TEMPERATURE SENSOR ACCORDING TO
SENSOR/TRANSMITTER SCHEDULE ON DWG 3304.
16. MOUNT THERMOSTAT IN DUCT ABOVE FAN COIL UNIT, SEE DETAIL D ON
DWG 3308.
17. INSTALL CONTROLLER ACCORDING TO SENSOR/TRANSMITTER SCHEDULE
ON DWG 3304.
18. PROVIDE FAN COIL UNIT WITH MANUFACTURER'S STANDARD REMOTE
PROGRAMMABLE THERMOSTAT.
19. FIELD ROUTE PIPING, DRAWING IS FOR REFERANCE ONLY. PROVIDE
WEATHER RESISTANT LINESET COVER AND FITTINGS WITH UV INHIBITORS
FOR PIPING THROUGH SOFFIT TO INDOOR UNIT. APPLY CAULKING TO SEAL
WHERE THE LINESET ENTERS AND EXITS THE EXTERIOR WALL.
20. CONDENSATE PIPING SHALL EXTEND PAST CONCRETE SLAB TO DRAIN ON
GRAVEL SURFACING. TURN DOWN TO SPLASH BLOCK.
21. FOR PENETRATION DETAIL REFER TO ARCHITECTURAL BY OTHERS.
SCALE IN FEET
0 2' 4' 8'
NORTH
HVAC PLAN
ACTUATED DAMPER
J-MOLDING
AND CAULKING
ALL AROUND
REFER TO ARCH DRAWINGS
FOR WALL DETAILS.
WOOD BLOCKING ALL
AROUND OPENING
MASONRY VENEER
MASONRY TIE
20 GA GALVANIZED
STEEL FLASHING
WRAP MOISTURE BARRIER
AROUND OPENING
20 GA GALVANIZED STEEL
CLOSURE, REFER TO
ARCH DOOR DETAILS
LOUVER WITH
INTEGRAL FLANGE
MASONRY VENEER
BEYOND
SOFFIT
CHARGING VALVE
LIQUID PIPING
SUCTION PIPING
FILTER-DRIER
SIGHT GLASS
PROVIDE OIL TRAP
INSTALL SENSING BULB
45` ABOVE BOTTOM OF
PIPING, AS CLOSE TO
COIL AS POSSIBLE
CONDENSATE DRAIN
NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR COORDINATING
REFRIGERANT LIQUID AND SUCTION PIPING, SIZES, ROUTING,
AND ALL ACCESSORIES WITH EQUIPMENT MANUFACTURER.
MAINTAIN UNIFORM SLOPE TO PREVENT OIL FROM POOLING IN
LOW POINTS IN THE REFRIGERANT PIPING SYSTEM.
EVAPORATOR COIL
ISOLATION VALVE (TYP.)
EXPANSION VALVE
EQUALIZATION LINE
AIR COOLED
CONDENSING UNIT
STRAP HANGERS
60" MAX.
HANGER
STRAPS
UNLESS FOOT OF STRAP
IS PLACED UNDER A
BOTTOM REINFORCEMENT
SCREWS
SCREWS MAY
BE OMITTED
IF HANGER LOOPS 1" MIN.
NOTES:
1. REFER TO STRUCTURAL DRAWINGS
FOR UNISTRUT SUPPORT DETAILS.
2. REINFORCEMENT MAY BE USED
FOR ATTACHMENT IF IT QUALIFIES
FOR BOTH DUTIES. DO NOT
EXCEED ALLOWABLE LOAD LIMITS.
ROD
STRAP OR
ANGLE
TRAPEZE HANGERS
SIZE BOLT(S)
FOR LOAD
SOFFIT
WEATHER HOOD
MASONRY
VENEER BEYOND
20 GA GALVANIZED
STEEL FLASHING
MASONRY TIE
MASONRY VENEER
20 GA GALVANIZED STEEL
CLOSURE, REFER TO
ARCH DOOR DETAILS
REFER TO ARCH DRAWINGS
FOR WALL DETAILS.
J-MOLDING AND
CAULKING ALL
AROUND
DUCT
WRAP MOISTURE BARRIER
AROUND OPENING
WOOD BLOCKING ALL
AROUND OPENING
BIRDSCREEN
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC DETAILS I
JUNE 24, 2022
A. OHM D. OLSEN
NOT TO SCALE
LOUVER DETAIL 1
NOT TO SCALE
DX SPLIT SYSTEM PIPING 2
NOT TO SCALE
LOWER DUCT HANGAR
ATTACHMENTS 3
NOT TO SCALE
WEATHERHOOD DETAIL 4
1/4"
PIPE SLEEVE
BACKUP MATERIAL
SEALANT
INSULATION
CENTER OF PIPE
3/8"
PIPE
ESCUTCHEON
INTERIOR SIDE OF
EXTERIOR WALL
HANGER ROD
LOCKING NUT
SUPPORT NUT
INSULATION
PIPE
HEAVY DUTY
CLEVIS HANGER
INSULATION SHIELD MIN. 6" LONG
STEEL SLEEVE : 16 GAUGE 24" MAX.
14 GAUGE OVER 24"
1. SECURE DAMPER TO SLEEVE ON 8" CENTERS WITH:
A. 1/4" BOLTS AND NUTS IN HOLES PROVIDED.
B. NO. 10 STEEL SCREWS.
2. REFER TO MANUFACTURER'S INSTALLATION
INSTRUCTIONS FOR COMPLETE INSTALLATION DETAILS.
NOTES:
TRANSFER/SUPPLY
AIR GRILLE (TYP.)
FUSIBLE LINK
FIRE DAMPER
BATTERY ROOM CONTROL ROOM
STEEL SLEEVE : 16 GAUGE 24" MAX.
14 GAUGE OVER 24"
TRANSFER/RETURN
AIR GRILLE (TYP.)
FUSIBLE LINK
FIRE DAMPER
BATTERY ROOMCONTROL ROOM
RETURN
AIR DUCT
UNISTRUT P1001
CHANNEL, TYP. 4
UNISTRUT P2073
POST BASE, TYP. 4
FILTER ACCESS
PANEL
UNISTRUT P1498
ANGLE FITTINGS,
TYP. 2 EACH LEG
NOTE:
1. SECURE FAN COIL UNITS TO SUPPORTS WITH AT
LEAST FOUR ANGLE FITTINGS. CONNECT ANGLE
FITTINGS TO CHANNEL WITH 1/4" DIA HEX
SLOTTED SCREWS AND P1006 NUTS WITH
SPRINGS AND TO UNIT WITH 1/4" DIA SLOTTED
WASHER SHEET METAL SCREWS.
UNISTRUT P1498
ANGLE FITTING, TYP.FILTER ACCESS
PANEL
UNISTRUT P1001
C3 CHANNEL
GASKET TAPE
SEE SECTION ON LEFTCONNECT ANGLE
FITTINGS TO OPEN SIDE
OF CHANNEL, TYP.
UNISTRUT P1036 PLATE
FITTING, TYP. EACH CORNER
APPLY GASKET TAPE TO
SMOOTH SIDE OF CHANNEL
UNISTRUT P1001 C3
CHANNEL, TYP. 4 SIDES
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC DETAILS II
JUNE 24, 2022
A. OHM D. OLSEN
NOT TO SCALE
PIPE PENETRATIONS THROUGH
EXTERIOR WALLS 1
NOT TO SCALE
PIPE HANGER - CLEVIS TYPE 2
NOT TO SCALE
FIRE DAMPER IN WALL WITH
GRILLE 3
NOT TO SCALE
FAN COIL SUPPORT 4
NOT TO SCALE
CHANNEL SECTION 5
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC SCHEDULES
JUNE 24, 2022
A. OHM D. OLSEN
FAN COIL UNIT SCHEDULE
TAG NO. SERVICE
BASIS OF DESIGN
ALTITUDE
(FT.)
TOTAL
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W.C.)
FAN
HP
COOLING
ELECTRIC HEAT
(KW)
ELECTRICAL
FILTER
SIZE
(INxIN)
FILTER
THICKNESS
(IN)
WEIGHT
(LBS) REMARKS
MAN. MODEL NO.
SENSIBLE
CAPACITY
(MBTUH)
EAT
DB
(°F)
LAT
DB
(°F)
VOLTS PHASE
FCU-1 BATTERY ROOM MITSUBISHI TPKA0A024 3832 705 0.5 0.07 24 75 55 0 230 1 N/A N/A 46 1, 3, 5, 6, 7
FCU-2 CONTROL ROOM TRANE GAM5B0C42 3832 1410 0.5 0.5 42 75 55 10 230 3 16X20 1 163 1, 2, 3, 4, 7
FCU-3 CONTROL ROOM TRANE GAM5B0C42 3832 1410 0.5 0.5 42 75 55 10 230 3 16X20 1 163 1, 2, 3, 4, 7
DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)
TAG DESCRIPTION MOUNTING
THROW
PATTERN
PROVIDE
DAMPER?
BASIS OF DESIGN:
REMARKS
MFR.
MODEL
NO.
RA-A
RECTANGULAR RETURN
OR TRANSFER AIR GRILLE
DUCT N/A NO TITUS 350RL
1, 2, 5
SA-B
RECTANGULAR SUPPLY
AIR GRILLE
DUCT N/A YES TITUS 300RS
1-5
ENERGY RECOVERY UNIT SCHEDULE 1/2
TAG NO. SERVICE
ALTITUDE
(FT)
OUTSIDE
AIRFLOW (CFM)
SUPPLY FAN EXHAUST FAN
EXTERNAL
STATIC
PRESSURE
(IN. W.C.)
TOTAL
STATIC
PRESSURE
(IN. W.C.)
FAN RPM TYPE MOTOR HP
EXTERNAL
STATIC
PRESSURE
(IN.W.C)
TOTAL
STATIC
PRESSURE
(IN.W.C.)
FAN RPM TYPE
MOTOR
HP
ERU-1
BATTERY AND
CONTROL ROOMS 3832 495 0.5 0.61 1124
FORWARD
CURVE 0.5 0.5 0.55 1395
FORWARD
CURVE 0.5
ENERGY RECOVERY UNIT SCHEDULE 2/2
TAG NO.
COOLING HEATING
APPROX. UNIT
WEIGHT (LBS)
UNIT ELECTRICAL BASIS OF DESIGN
REMARKS
EAT DB
(°F)
EAT WB
(°F)
LAT
DB
(°F)
LAT WB
(°F)
SENSIBLE
CAPACITY
(MBH)
EAT
(°F)
LAT
(°F)
TOTAL CAPACITY
(MBH)
VOLTS PHASE MOP MCA MAN. MODEL
ERU-1 97.5 62.6 78.7 59.3 5.5 -12.7 56.3 37.1 308 230 1 15 8.4 GREENHECK ERV-10-20L-VG 1-7
CONDENSING UNIT SCHEDULE
TAG NO. SERVICE
BASIS OF DESIGN
COMPRESSOR
TYPE
EFFICIENCY
(SEER)
RATED
OUTDOOR
DB (°F)
REFRIGERANT
TYPE
ELECTRICAL
WEIGHT
(LBS)
REMARKS
MAN. MODEL VOLT PH. MCA
CU-1 BATTERY ROOM MITSUBISHI TRUYA024 INVERTER 21.4 97.5 R410A 230 1 1 151 1-5
CU-2 CONTROL ROOM TRANE 4TTR SCROLL 14 97.5 R410A 230 3 20 246 1-5
CU-3 CONTROL ROOM TRANE 4TTR SCROLL 14 97.5 R410A 230 3 20 246 1-5
LOUVER SCHEDULE
TAG SERVICE
SIZE
(INxIN)
AIRFLOW
(CFM)
PRESSURE
DROP (IN.W.C)
BASIS OF DESIGN
MANF/MODEL
REMARKS
LVR-1 OA INTAKE 18x18 495 0.055 RUSKIN ELF375X 1-3
NOTES:
1. PROVIDE WITH BIRD SCREEN.
2. PROVIDE LOUVER WITH INTEGRAL FLANGE AND INSTALL ACCORDING TO DETAIL 1 ON SHEET 3302.
3. PROVIDE BASIS OF DESIGN LOUVER OR APPROVED EQUAL.
NOTES:
1. DIFFUSER SIZES ARE NOTED IN DRAWINGS.
2. COLOR SHALL MATCH ACOUSTICAL CEILING TILES OR WALL. COORDINATE WITH ARCH
PLANS.
3. DIFFUSERS SHALL BE INITIALLY ADJUSTED FOR DISCHARGE OF AIR DOWNWARD AT
APPROXIMATELY 30° BELOW HORIZONTAL AND IN A HORIZONTALLY SPREAD PATTERN.
4. SUPPLY AIR GRILLE SERVING ERU-1 SHOULD NOT BE PROVIDED WITH DAMPER.
5. PROVIDE BASIS OF DESIGN DIFFUSERS AND GRILLES OR APPROVED EQUAL.
NOTES:
1. PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR NAME AND MARK.
2 PROVIDE WITH MANUFACTURER'S STANDARD 2" MERV 8 FILTERS FOR OUTDOOR AND EXHAUST AIR OPENINGS.
3. PROVIDE ENERGY RECOVERY UNIT END CONNECTIONS IN CONFIGURATION WITH DUCTWORK LAYOUT.
4. THE ENERGY RECOVERY UNIT SHALL BE PROVIDED FROM THE FACTORY WITH AN INTEGRAL CONTROL CENTER INCLUDING A SINGLE NON-FUSED DISCONNECT, 24 VAC TRANSFORMER, TERMINAL STRIP, AND FAN STARTERS (CONTACTOR AND OVERLOAD).
5. PROVIDE WITH INTERNAL BACKDRAFT DAMPERS.
6. STANDARD SINGLE POINT POWER TO BE PROVIDED BY MANUFACTURER.
7. PROVIDE BASIS OF DESIGN ENERGY RECOVERY UNIT OR APPROVED EQUAL.
NOTES:
1. PROVIDE ELECTRICAL DISCONNECT.
2. PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE
ENERGY STAR NAME AND MARK.
3. PROVIDE WITH LOW AMBIENT KIT FOR OPERATION TO -20°F.
4. PROVIDE ON CONCRETE EQUIPMENT PAD WITH MANUFACTURER'S STANDARD 12" EQUIPMENT STAND. SEE ARCH DRAWINGS FOR ADDITIONAL
INFORMATION.
5. PROVIDE BASIS OF DESIGN CONDENSING UNIT OR APPROVED EQUAL.
NOTES:
1. PROVIDE VERTICAL FLOOR MOUNT EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR NAME AND MARK.
2. PROVIDE WITH MANUFACTURER'S STANDARD PLENUM STAND. MOUNT ON PLENUM STAND PER MANUFACTURER'S RECOMMENDATIONS.
3. POWER PROVIDED BY OUTDOOR UNIT, CONTRACTOR TO PROVIDE WIRING AND FIELD ROUTE. CONNECT PER MANUFACTURER'S RECOMMENDATIONS.
4. PROVIDE WITH SEPARATE CONTROLLER ALLOWING LEAD/LAG CONTROL, ZONE TEMPERATURE MONITORING, AND ALARMING TO SCADA SYSTEM.
5. PROVIDE WITH MANUFACTURER'S STANDARD REMOTE PROGRAMMABLE THERMOSTAT.
6. PROVIDE WITH MANUFACTURER'S STANDARD WALL MOUNT KIT. MOUNT UNIT ON WALL PER MANUFACTURER'S RECOMMENDATIONS.
7. PROVIDE BASIS OF DESIGN FAN COIL UNIT OR APPROVED EQUAL.
CONVECTION HEATER SCHEDULE
MARK
BASIS OF DESIGN ELECTRICAL CAPACITY
(MBH)
CAPACITY
(KW) WEIGHT REMARKS
MANUFACTURER MODEL VOLTS PHASE HZ
CH-1 BERKO CUH945 230 3 60 34 10 160 1-2
NOTES:
1. PROVIDE WITH MANUFACTURER'S STANDARD TAMPERPROOF THERMOSTAT.
2. PROVIDE BASIS OF DESIGN CONVECTION HEATER OR APPROVED EQUAL.
CONTROL DAMPER SCHEDULE
TAG NO. FUNCTION CFM HEIGHT WIDTH
BLADE
OPERATION
ACTUATOR
TYPE
INTERLOCK
WITH
MAX PRESSURE
DROP (IN. W.C.)
REMARKS
CD-1 ERU-1 OUTDOOR AIR 495 18" 18" OPPOSED BELIMO ERU-1 0.05 1-4
CD-2 ERU-1 EXHAUST AIR 495 12" 12" OPPOSED BELIMO ERU-1 0.05 1-4
NOTES:
1. COORDINATE FINAL SIZE WITH WALL OPENING SIZE/DUCTWORK SIZE.
2. BELIMO 120 VAC ELECTRIC ACTUATOR, TWO POSITION CONTROL, SPRING TO CLOSED (NORMALLY CLOSED), PROVIDE WITH
END SWITCH OPTION FOR MONITORING THROUGH BAS.
3. PROVIDE WITH EPDM BLADE SEALS.
4. PROVIDE BASIS OF DESIGN CONTROL DAMPER OR APPROVED EQUAL.
SENSOR/TRANSMITTER SCHEDULE
TAG MANUFACTURER/MODEL OUTPUT RANGE REMARKS
CTR-1 QUEST CONTROLS RSC 1000 - - WALL MOUNT 54" AFF. CONTROLS FCU-2 AND FCU-3
HT-1 VERIS MODEL HEW 2MSX HUMIDITY TRANSMITTER 4-20mA 0-100% WALL MOUNT 60" AFF.
OT-1 VERIS MODEL TOA M10 OUTDOOR AIR TRANSMITTER 4-20mA -40°F-122°F
OUTDOOR WALL MOUNT, 8'-0" ABOVE GRADE, BELOW
SOFFIT.
ST-1 VERIS MODEL TDDA M20 SUPPLY AIR TRANSMITTER 4-20mA 32°F-122°F FCU-2 SUPPLY DUCT MOUNT
ST-2 VERIS MODEL TDDA M20 SUPPLY AIR TRANSMITTER 4-20mA 32°F-122°F FCU-3 SUPPLY DUCT MOUNT
ZT-1 VERIS MODEL TEA MS ZONE TRANSMITTER 4-20mA 50°F-90°F WALL MOUNT 60" AFF. CONNECTED TO CTR-1.
ZT-2 VERIS MODEL TEA MS ZONE TRANSMITTER 4-20mA 50°F-90°F WALL MOUNT 60" AFF. CONNECTED TO CTR-1.
ENERGY RECOVERY UNIT
ERU-1
SF
N 230V
POWER
GENERAL NOTE:
TYPICAL OF TWO (2) OCCUPANCY
SENSORS. REFER TO DRAWING 3301
FOR LOCATIONS.
OCC
M
CD-1
HYDROGEN SENSOR
HS
OCCUPANCY
SENSOR
UNIT BOUNDARY
M
CD-2
POWER PROVIDED BY
ELECTRICAL, SEE ELECTRICAL
DRAWINGS FOR DETAILS.
ENERGY WHEEL
EF
OA
EA RA
SA
UNIT
CONTROLLER
24V
ERU CONTROL SEQUENCE:
A. OPERATING MODES OF SYSTEM: EQUIPMENT SHALL OPERATE PER THE FOLLOWING:
1. UPON ACTIVATION OF THE BUILDING OCCUPANCY SENSOR:
a. CONTROL DAMPERS, CD-1 AND CD-2, SHALL OPEN.
b. AFTER DAMPERS ARE VERIFIED OPEN, ERU-1 SHALL RECEIVE ENABLE SIGNAL
AND ENERGIZE.
2. UPON ACTIVATION OF THE HYDROGEN SENSOR:
A. CONTROLS DAMPERS, CD-1 AND CD-2, SHALL OPEN.
B. AFTER DAMPERS ARE VERIFIED OPEN, ERU-1 SHALL RECEIVE ENABLE SIGNAL
AND ENERGIZE.
B. ALARM
a. UPON EQUIPMENT FAILURE TO START, AN ALARM SHALL BE SENT TO THE SCADA
SYSTEM.
TS
AI - ZONE TEMPERATURE
SA
DX
SF
M
CT
STARTER
AI - ZONE SETPOINT ADJUSTMENT
M
CT
MOTOR
STARTER
OUTDOOR CONDENSING UNIT
INDOOR FAN
COIL UNIT
BOUNDARY
RA
FILTER
UNIT
CONTROLLER
ST
DI - FAN STATUS
DI - FAN START/STOP
DI - FAN STATUS
INTERCONNECTING
COMMUNICATIONS
PROVIDED WITH
EQUIPMENT
ST-1 & ST-2
SUPPLY AIR TEMPERATURE
FAN COIL UNITS
FCU-1/CU-1,
FCU-2/CU-2,
FCU-3/CU-3
(FOR FCU-1)
TO CTR-1 (FOR FCU-2 & FCU-3)
SA
FCU-2 &
FCU-3 ONLY
FCU-1 CONTROL SEQUENCE:
A. OPERATING MODES OF SYSTEM: EQUIPMENT SHALL BE OPERATED CONTINOUSLY TO CONDITION THE ASSOCIATED SPACE.
1. OPERATING MODE: THE UNIT SHALL ENERGIZE AND MAINTAIN ZONE AIR TEMPERATURE SET POINT OF THE FOLLOWING UNDER
ALL LOAD VARIATIONS:
a. COOLING SETPOINT: 78°F (ADJ)
b. SETPOINTS SHALL BE ADJUSTABLE AT ROOM LEVEL (+/- 2°F).
2. UNIT SHALL BE ENABLED AND RUN THROUGH THE STAND ALONE CONTROLLER PROVIDED BY THE MANUFACTURER.
B. FANS
1. THE SUPPLY AIR FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN. TO PREVENT SHORT CYCLING, THE SUPPLY
FAN SHALL HAVE A USER DEFINABLE MINIMUM RUNTIME.
2. FAN WILL OPERATE UNLESS SHUTDOWN ON SAFETIES.
C. COOLING SEQUENCE
1. THE CONTROLLER SHALL MEASURE THE SPACE TEMPERATURE AND ENABLE DX COOLING. UNIT SHALL MODULATE FAN AND
COOLING CAPACITY TO MAINTAIN THE ZONE AIR TEMPERATURE SETPOINT.
2. COOLING SHALL BE ENABLED WHENEVER:
a. ZONE AIR TEMPERATURE IS GREATER THAN SETPOINT (+/- 2°F).
b. AND THE UNIT IS OPERATING IN COOLING MODE.
FCU-2 & FCU-3 CONTROL SEQUENCE:
A. GENERAL
a. THE UNIT CONTROLLER (CTR-1) SHALL OPERATE FCU-2 AND FCU-3 ON A LEAD-LAG BASIS, SWITCHING THE LEAD FCU
WEEKLY (ADJ.) BASED ON TOTAL RUN TIME. UPON FAILURE OF THE LEAD FCU, THE LAG FCU SHALL ENERGIZE AND AN
ALARM SHALL BE SENT TO THE SCADA SYSTEM.
B. OPERATING MODES OF SYSTEM: EQUIPMENT SHALL BE OPERATED CONTINOUSLY TO CONDITION THE ASSOCIATED SPACE.
1. OPERATING MODE: THE UNIT SHALL ENERGIZE AND MAINTAIN ZONE AIR TEMPERATURE SET POINT OF THE FOLLOWING
UNDER ALL LOAD VARIATIONS:
a. COOLING SETPOINT: 78°F (ADJ)
b. HEATING SETPOINT: 68°F (ADJ)
c. SETPOINTS SHALL BE ADJUSTABLE AT ROOM LEVEL (+/- 2°F).
2. UNIT SHALL BE ENABLED AND RUN THROUGH THE STAND ALONE CONTROLLER (QUEST CONTROLLER RSC-1000 OR
APPROVED EQUAL).
C. FANS
1. THE SUPPLY AIR FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN. TO PREVENT SHORT CYCLING, THE SUPPLY
FAN SHALL HAVE A USER DEFINABLE MINIMUM RUNTIME.
2. FAN WILL OPERATE UNLESS SHUTDOWN ON SAFETIES.
D. COOLING SEQUENCE
1. THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND ENABLE DX COOLING. UNIT SHALL OPERATE TO
MAINTAIN THE ZONE AIR TEMPERATURE SETPOINT.
2. COOLING SHALL BE ENABLED WHENEVER:
a. ZONE AIR TEMPERATURE IS GREATER THAN SETPOINT (+/- 2°F).
b. AND SUPPLY AIR TEMPERATURE IS GREATER THAN SETPOINT.
c. AND THE UNIT IS OPERATING IN COOLING MODE.
E. HEATING SEQUENCE
1. THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND ENABLE HEATING. SUPPLY FAN SHALL MODULATE
TO MAINTAIN THE ZONE AIR TEMPERATURE SETPOINT.
2. HEATING SHALL BE ENABLED WHENEVER:
a. ZONE AIR TEMPERATURE IS LESS THAN SETPOINT.
b. AND SUPPLY AIR TEMPERATURE IS LESS THAN SETPOINT.
c. AND THE UNIT IS OPERATING IN HEATING MODE.
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC CONTROLS
JUNE 24, 2022
A. OHM D. OLSEN
Level 1 100' - 0"
TOP OF CEILING
111' - 0"
BOTTOM OF SOFFIT
110' - 2"
PLENUM STAND
PROVIDED WITH
FCU
FLOOR STAND
PER DETAILS 4 & 5
ON DWG 3303
FCU-3
3/4" COND
RS 7/8" RL 3/8"
16x14 SA
14x16 SA
6' - 10" BOD EL
Level 1 100' - 0"
TOP OF CEILING
111' - 0"
BOTTOM OF SOFFIT
110' - 2"
CU-3
FCU-3
BACKDRAFT DAMPER,
SHALL BE HORIZONTALLY
MOUNTED WITH THE
HORIZONTAL AIRFLOW NORTH.
DAMPER SHALL BE
GREENHECK ES-10 OR
APPROVED EQUAL.
16x14 SA
6' - 10" BOD EL
ST-2, SUPPLY AIR
TRANSMITTER MOUNTED
IN DUCT. MOUNT FAR
ENOUGH TO ALLOW FOR
FULL MIXING.
FLEXIBLE DUCT
CONNECTOR
6" 6"
MANUFACTURER'S
STANDARD 12" EQUIPMENT
STAND
FLOOR STAND PER
DETAILS 4 & 5 ON DWG
PLENUM STAND
PROVIDED WITH FCU
7/8" RS
3/4" COND
3/8" RL
4 56
5 5
2 4
PAD BY
STRUCTURAL
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC SECTIONS I
JUNE 24, 2022
A. OHM D. OLSEN
NOT TO SCALE 3301
SPLIT UNIT FRONT PIPING
SECTION A
NOTES:
KEYED NOTES:
1. CONTRACTOR SHALL LOCATE EQUIPMENT SUCH THAT ALL
REQUIRED MAINTENANCE CLEARANCE/ACCESS ARE
COORDINATED WITH WORK BY OTHER TRADES.
2. CONTRACTOR TO FIELD ROUTE ALL DUCTWORK. DUCTWORK
SHALL BE ROUTED BE BELOW CABLE TRAYS WERE THEY
OCCURE. THIS DRAWING IS FOR REFERANCE ONLY.
3. REFRIGERANT PIPE SIZES AND ROUTING ARE DIAGRAMMATIC
AND MUST BE VERIFIED WITH EQUIPMENT MANUFACTURER
PRIOR TO INSTALLATION.
1. MOUNT FAN COIL UNIT ON FAN COIL SUPPORT AS DETAILED ON
DWG 3303, DETAILS 4 & 5, AND ON MANUFACTURER'S PLENUM
STAND PER DRAWINGS 3301 & 3303.
2. PROVIDE INSULATION FOR REFRIGERANT PIPING PER
SPECIFICATION 23 07 00 - THERMAL INSULATION FOR
MECHANICAL SYSTEMS.
3. FOR PENETRATION DETAIL REFER TO ARCHITECTURAL BY
OTHERS.
4. PROVIDE LINESET COVERS WITH A WALL COVER INLET. APPLY
CAULKING TO SEAL WHERE THE LINESET ENTERS AND EXITS
THE EXTERIOR WALL.
5. PENETRATION SHALL BE SEALED PER ARCHITECTURAL
REQUIRMENTS BY OTHERS.
6. MOUNT CONDENSING UNIT ON MANUFACTURER'S STANDARD
12" EQUIPMENT STAND ON MECHANICAL EQUIPMENT PAD.
EQUIPMENT SLAB PROVIDED BY STRUCTURAL.
2 2
FLEX DUCT
CONNECTOR
NOT TO SCALE 3301
SPLIT UNIT PIPING & DUCT TAKE
OFF B
Level 1 100' - 0"
TOP OF CEILING
111' - 0"
ERU-1
BOTTOM OF SOFFIT
110' - 2"
CD-1 18x18 OA
6' - 8" BOD EL
CD-2
495-12x12
SA-B
12x12 SA
9' - 0" BOD EL
12x12 RA
7' - 0" BOD EL
12x12 RA
9' - 0" BOD EL
12x12 EA
9' - 0" BOD EL
12x12 OA
8' - 9" BOD EL
495-12x12
RA-A
WEATHERHOOD,
REFER TO DETAIL
4 ON DWG 3302
CONTROL ROOMBATTERY ROOM 12x12 OA
6' - 11" BOD EL
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
LV
MECHANICAL
HEADQUARTERS - LAKEWOOD, COLORADO
LOVELL SUBSTATION
SERVICE BUILDING
WYOMING
HVAC SECTIONS II
JUNE 24, 2022
A. OHM D. OLSEN
NOTES:
KEYED NOTES:
1. CONTRACTOR SHALL LOCATE EQUIPMENT SUCH THAT ALL
REQUIRED MAINTENANCE CLEARANCE/ACCESS ARE
COORDINATED WITH WORK BY OTHER TRADES.
2. REFRIGERANT PIPE SIZES AND ROUTING ARE DIAGRAMMATIC
AND MUST BE VERIFIED WITH EQUIPMENT MANUFACTURER
PRIOR TO INSTALLATION.
3. CONTRACTOR TO FIELD ROUTE ALL DUCTWORK. DUCTWORK
SHALL BE ROUTED BE BELOW CABLE TRAYS WERE THEY
OCCURE. THIS DRAWING IS FOR REFERANCE ONLY.
1. FOR PENETRATION DETAIL REFER TO ARCHITECTURAL BY
OTHERS.
NOT TO SCALE 3301
ERU EXHAUST AIR SECTION C
Jul 11, 2022- 11:19am
Jul 11, 2022- 11:21am
Jul 11, 2022- 11:23am
Jul 11, 2022- 11:25am
Jul 11, 2022- 11:27am
Jul 11, 2022- 11:28am
May 16, 2022- 8:27pm
May 16, 2022- 8:29pm
May 16, 2022- 6:04pm
May 16, 2022- 8:03pm
May 16, 2022- 8:05pm
May 16, 2022- 8:07pm
May 16, 2022- 8:08pm
May 16, 2022- 8:10pm
May 16, 2022- 8:11pm
May 16, 2022- 8:13pm
May 16, 2022- 8:15pm
May 16, 2022- 8:16pm
May 16, 2022- 8:18pm
May 16, 2022- 8:19pm
May 16, 2022- 8:21pm
May 16, 2022- 8:22pm
May 16, 2022- 8:24pm
May 16, 2022- 8:26pm
| Cover Page |
| Project Drawings |
| lv_0016d |
| lv_0001r_ei |
| lv_0001s |
| lv_0010j_ei |
| lv_0010k |
| lv_1000e_fio |
| lv_1001g_ei |
| lv_1001h |
| lv_1002g_ei |
| lv_1002h |
| lv_1003g_ei |
| lv_1003h |
| lv_1004e_ei |
| lv_1004f |
| lv_1005m_ei |
| lv_1005n |
| lv_1006i_ei |
| lv_1006j |
| lv_1007g_ei |
| lv_1007h |
| lv_1008g_ei |
| lv_1008h |
| lv_1009d_ei |
| lv_1009e |
| lv_1010j_ei |
| lv_1010k |
| lv_1012e_ei |
| lv_1012f |
| lv_1015c_ei |
| lv_1015d |
| lv_1017c_ei |
| lv_1017d |
| lv_1018e_ei |
| lv_1018f |
| lv_1019_ei |
| lv_1019a |
| lv_1100g |
| lv_1101c |
| lv_1102 |
| lv_1500b_ei |
| lv_1500c |
| lv_1501c_ei |
| lv_1501d |
| lv_1502f_ei |
| lv_1502g |
| lv_1503 |
| 31_1502 |
| 31_1503 |
| 31_1504b |
| lv_1610c_ei |
| lv_1610e |
| lv_2017b_fio |
| lv_2018b_fio |
| lv_2001_1 |
| lv_2001_2 |
| lv_2000j_ei |
| lv_2000_1 |
| lv_2000_2 |
| lv_2000_3 |
| lv_2000_4 |
| lv_2004d |
| lv_2012e |
| lv_2025e |
| lv_2048_ei |
| lv_2048a |
| lv_2300a |
| lv_2301 |
| lv_2550 |
| lv_2877 |
| lv_2878 |
| lv_2026_1a_fio |
| lv_2026_2a_fio |
| lv_2026_3a_ei |
| lv_2026_3b |
| lv_2501 |
| lv_2052_fio |
| lv_2054_fio |
| lv_2600 |
| lv_2925 |
| lv_2876 |
| 01_2004_1d |
| 01_2004_2d |
| 01_2006_1 |
| 01_2006_2 |
| 01_2006_3 |
| 31_2049_1b |
| 31_2051b |
| lv_3010 |
| lv_3011 |
| lv_3012a |
| lv_3014 |
| lv_3016 |
| lv_3018 |
| lv_3020 |
| lv_3022 |
| lv_3024 |
| lv_3200 |
| lv_3201a |
| lv_3202 |
| lv_3203_1 |
| lv_3203_2 |
| lv_3204_1 |
| lv_3204_2 |
| lv_3205_1 |
| lv_3205_2 |
| lv_3206 |
| lv_3300 |
| lv_3301 |
| lv_3302 |
| lv_3303 |
| lv_3304 |
| lv_3305 |
| lv_3306 |
| lv_3307 |
| lv_3400a |
| lv_3401a |
| lv_3402a |
| lv_3403a |
| lv_3404a |
| lv_3405a |
| lv_t600_1 |
| lv_t600_2 |
| lv_1611d |
| lv_4000i |
| lv_6000i |
| lv_6021_1b |
| lv_6021_2a |
| lv_6021_3b |
| lv_6021_4b |
| lv_6021_5b |
| lv_6021_6a |
| lv_6021_7a |
| lv_6022_1 |
| lv_6022_2 |
| lv_6023e |
| lv_6024d |
| lv_6146 |
| lv_6147 |
| lv_0015c |
| lv_8000b |
| lv_8001b |
| lv_8002b |
| lv_8003b |
| lv_8004b |
| lv_8005b |