Station Houston Emergency Generator Fuel Recirculation System List of Requirements
Station Houston is designed to be provided with auxiliary power upon demand via an emergency generator. The generator is currently fed by a 10,000 gallons diesel fuel tank with no means of treatment nor filtration capacity. Our engineering department has determined the overall negative impact the unit will incurred whether be financial or operational if this fuel gets compromised. The installation of the fuel recirculation system will be the most effective way to optimize and maintain diesel fuel indefinitely. System will remove particulate, separate water, and condition stored fuel and ensure clean reliable fuel at all times.
The following are the installation requirements under the system specifications:
Power: 120V/60Hz/15A Pluming: Stainless Steel Ports: In 1” NPT Out 1” NPT Weatherproof Cabinet Installation: Mounting Rated for +- 513 lbs STS 6000 Series Safety System Features:
· Automatic Alerts
· Pump Shutdown When Filter Needs Service
· Leak Detection
· Water Detection
· High Filter Vacuum
· High Pump Pressure
· Low Fuel Flow Alert
· Emergency Stop STS 6000 Series Smart Filtration Controllers Provide:
· Maintenance Alert
· Runtime Totalizer
· Alarm History
· On-Screen Help All STS 6000 System Include:
· Multi-stage Water Removal, Particulate Filtration, and Fuel Conditioning
· NEMA 12, 13, 3R, 4 Powder Coated or Stainless Steel Enclosure
· UL508A Smart Filtration Controller
· Stainless Steel Pluming Installation will be conducted by agency. Installation will not be included as part of the quote, only supply.