21128.10_Attachment 5 - Construction Spec.pdf
PDF 637 KB Posted
- Attached to
- OceanSpray Project
- Solicitation number
- BD-21-1296-02346-MGED1-69671
- Issued by
- Plymouth County, Massachusetts
About this file
This document is a Construction Specification for the Ocean Spray project in Middleborough, Massachusetts. Cornerstone Energy Services, Inc. has been retained by Middleborough Gas and Electric (MGED) to perform engineering services and oversee the fabrication and installation of additional overpressure and backflow protection to the existing MGED meter assembly located within the Ocean Spray campus. The work will conform to applicable federal and state pipeline safety regulations. The contractor must be qualified to perform the covered tasks, minimize damage to surrounding infrastructure, and properly dispose of all debris and excess materials.
The specification outlines detailed requirements for materials, installation, concrete work, pipe welding, coating, pressure testing, and bolting procedures. It includes specific torque tables and values for various pipe sizes and flange classes. The contractor will be responsible for providing concrete testing, welding inspection, and a final report with torque values. The project appears to be funded by MGED, but the document does not mention pricing, set asides, incumbents, or funding sources.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 21128.10_Attachment 4 - OQ Task List.pdf | ||
| 21128.10_Attachment 2 - Prevailing Wage.pdf | ||
| 21128.10_Attachment 3 - General Contract.docx | DOCX document | |
| 21128.10_Scope of Work.pdf | ||
| 21128.10_Attachment 1 - IFB.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSTRUCTION
SPECIFICATION
Page: 1 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
Revision (By): A (RRG) Date: 12/16/21
Cornerstone Energy Services: Company Specifications - Construction Specification (CS)
Successful projects start with the Cornerstone
1. SCOPE/GENERAL
This document outlines methods and procedures for the fabrication and installation of additional overpressure and backflow protection to the existing Middleborough Gas and Electric (MGED) meter assembly located within the Ocean Spray campus at 152 Bridge St., Middleborough, MA.
Cornerstone Energy Services, Inc. (Cornerstone) has been retained by MGED to perform Owner’s engineering services.
All procedures will conform to CFR 49 Part 192 and Massachusetts Natural Gas Pipeline Safety Code 220 CMR 101.00, where applicable.
All materials used must be identical to that listed on the bill of materials as supplied unless prior written approval has been received from Cornerstone.
2. SPECIFICATION COMPLIANCE
The equipment shall comply with any drawings, data sheets, standards, codes and specifications incorporated by the Standards listed in Section 1. Any applicable national, state, or local codes or regulations shall be considered as part of this specification.
3. CONTRACTOR
The contractor shall ensure that all rules and regulations applicable are met. This includes, but is not limited to, Federal, State and Local rules/regulations.
Contractor will conduct work as to minimize damage to any of the following: sidewalks, roadways, underground utilities and structures.
Contractor shall remove all excess material and debris in a timely manner at his/her expense.
At all times during the work, Contractor shall keep, or cause to be kept, the premises clean and orderly and free from accumulation of waste material or rubbish created in the work. Upon completion of the work, Contractor shall repair all damage caused by equipment and leave the project free of rubbish or excess materials of any kind.
The Contractor shall be solely and directly responsible to the Owner and owners of such properties for any damage, injury, expense, loss, inconvenience, delay, suits, actions, or claims of any character brought because of any injuries or damage which may result from the construction operations under this Contract.
Prior to commencing work, Contractor shall be responsible for enacting the appropriate “one‐ call” system in order to acquire locates of existing utilities within, or adjacent to, all pipeline alignment(s).
Operator qualifications requirements as defined in the Scope of Work shall be strictly adhered to.
4. RESPONSIBILITY FOR MATERIAL
Contractor shall ensure all materials are transported, loaded/unloaded and stored in such a manner as to protect the integrity of the materials. Any materials damaged or suspect of damage will be replaced with new.
Contractor shall verify compliance with the provided Bill of Material. Any discrepancies shall be brought to the attention of MGED and Cornerstone.
Page: 2 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
The Contractor shall inspect all products or equipment delivered to the site prior to their unloading and shall reject all products or equipment that are damaged, used, or in any other way unsatisfactory for use on project.
Pipe Storage and Handling
i. All pipe, tubing and fittings will be kept clean and stored in original packaging until ready for use.
ii. Store products or equipment off ground and protected from weather. Handle products or equipment in accord with manufacturer's recommendations and instructions.
iii. While storing, take care to avoid creating a humidity chamber by venting the area.
iv. Store products or equipment in location to avoid physical damage to items while in storage, and to facilitate prompt inspection.
v. Delicate instruments and materials subject to vandalism shall be placed under locked cover, and if necessary, provided with temperature control as recommended by manufacturer.
All hazardous and/or toxic materials shall be stored in conformance with Federal, State and local regulations.
5. OPERATOR QUALIFICATIONS
Any contractor performing a covered task as indicated in the attached Covered Task List must be qualified in accordance with Northeast Gas Association (NGA) and within the stated expiration window.
6. INSTALLATION
During the progress of construction, it is expected that minor relocations of the work will be necessary. Such relocations shall be made only by direction of the Owner. If existing structures are encountered that prevent the construction, and that are not properly shown on the Drawings (if applicable), Contractor shall notify the Owner’s Engineer or on‐site representative before continuing with the construction in order that the Owner may make such field revision as necessary to avoid conflict with the existing structures. If the Contractor shall fail to so notify the Owner’s Engineer or on‐site representative when an existing structure is encountered, and shall proceed with the construction despite the interference, he shall do so at his own risk.
7. EXCAVATION PREPARATION
Contractor shall notify applicable One Call Systems or governing authorities, and any other private companies or municipalities having utilities in the vicinity of construction prior to the commencement of any activities in the work area, including hand excavation to verify top-of-utility elevations.
Copies of all applicable permits are to be kept at the trenching and excavating sites during these activities.
Excavation must be performed using hydro-vac methods in the area of the meter assembly.
8. BACKFILL
Section deleted. Not applicable.
Page: 3 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
9. PLAIN AND REINFORCED CONCRETE
Prior to placing concrete, the Contractor shall provide the Company with concrete mix design(s).
Codes and Standards: All activities related to concrete proportioning, mixing, placing, testing and curing shall comply with the latest edition of the codes and standards outlined below, as appropriate:
i. American Concrete Institute (ACI)
ii. ACI SP-066 ACI Detailing Manual
iii. ACI 117 Tolerances for Concrete Construction and Materials
iv. ACI 211.1 Selecting Proportions for Normal, Heavyweight, and Mass Concrete
v. ACI 211.2 Selecting Proportions for Structural Lightweight Concrete
vi. ACI 301 Structural Concrete
vii. ACI 302.1R Concrete Floor and Slab Construction
viii. ACI 304R Measuring, Mixing, Transporting, and Placing Concrete
ix. ACI 304.2R Placing Concrete by Pumping Methods
x. ACI 305R Hot Weather Concreting
xi. ACI 306R Cold Weather Concreting
xii. ACI 306.1 Cold Weather Concreting
xiii. ACI 308 Curing Concrete
xiv. ACI 318 Building Code Requirements for Reinforced Concrete
xv. ACI 347R Formwork for Concrete
xvi. ACI 504R Joint Sealants for Concrete Structures
xvii. American Society for Testing and Materials (ASTM)
xviii. ASTM A185 Standard Specification for Steel Welded Wire Fabric, Plain, for Concrete Reinforcement
xix. ASTM A615/A615M Standard Specification for Deformed and Plain Billet-Steel Bars for Concrete Reinforcement
xx. ASTM C33 Standard Specification for Concrete Aggregates
xxi. ASTM C39 Standard Test Method for Compressive Strength of Cylindrical Concrete
Specimens
xxii. ASTM C494 Standard Admixtures for Concrete
xxiii. ASTM C94/C94M Standard Specification for Ready Mixed Concrete
xxiv. ASTM C150 Standard Specification for Portland Cement
xxv. ASTM C618 Standard Specification for Fly Ash/Natural Pozzolan
xxvi. ASTM C4832 Standard Test Method for preparation and testing of controlled low strength material (CLSM) Test Cylinders
xxvii. ASTM D1557 Test Method for Laboratory Compaction Characteristics of Soil Using Modified Effort xxviii. National Ready Mixed Concrete Association (NRMCA)
xxix. Checklist for Ready Mixed Concrete Production Facilities, Sixth Edition
xxx. The concrete production facilities shall be currently certified by the National Ready
Mixed Concrete Association, and Contractors, if requested by the Company, shall submit a copy of that certificate to the Company Representative prior to the start of concrete work. The Company reserves the right to inspect and approve or reject the batch plant.
Page: 4 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
10. FORMWORK
Formwork shall be compliant with ACI 347R and ACI 117.
Exposed corners shall have 45-degree, ¾ in. (19 mm) chamfers.
Sonotube concrete tube forms or compatible shall be utilized. Contractor to follow manufacturer installation instructions.
11. REINFORCING STEEL AND EMBEDMENTS
Reinforcing bars shall conform to ASTM A615/A615M Grade 60 unless noted otherwise in the Contract Documents.
Welded wire fabric shall conform to ASTM A185.
Tie wire shall be 16 gauge or heavier.
Reinforcement placing and bending detail drawings shall be prepared in accordance with ACI SP-
066.
Crossing bars shall not be welded.
Direct embedment (precast) of piping support into concrete pillars is utilized as defined in the foundation drawings. There are no anchor bolts.
12. CONCRETE MATERIALS
Portland cement shall conform to ASTM C150 Type I, unless otherwise specified in the Contract Documents.
Fly ash used in accordance with ACI 301 shall conform to ASTM C618, Class F.
Mixing water and water used to make ice shall be potable or otherwise tested for suitability in accordance with ASTM C94/C94M.
Aggregate shall conform to ASTM C33 and shall be obtained from a single source.
13. PLACING CONCRETE
Concrete shall not be placed during rain or reasonable threat of rain unless provisions have been made to tent or cover the formwork and prevent stormwater runoff from entering the excavation.
The Contractor shall provide a copy of all concrete delivery tickets to the Company.
Concrete that has achieved initial set or has been contaminated by foreign matter shall not be utilized.
Concrete shall not be retempered and water shall not be added after the concrete is first mixed on site.
The addition of ice at the construction site shall only occur if it is included in the mix design. The concrete manufacturer shall provide written instructions on the required amount of ice and the mixing procedure as part of the concrete mix design.
Before any concrete is placed, all ice, snow, mud, and frost shall be completely removed, and the temperature of all surfaces that the concrete shall be raised above the freezing point. Concrete shall not be placed on frozen subgrade or on a surface that contains frozen materials
Prior to placing concrete, the sub-base material shall be mechanically compacted adjacent to foundations and within the limits of the proposed foundation to a minimum of 95% Standard Proctor Maximum Dry Density as determined by ASTM D1557, unless otherwise specified in the Contract Documents.
Page: 5 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
Concrete shall be placed as quickly as possible to avoid exposure of footing bottoms to wetting and drying. If possible, the foundation and concrete shall be placed on the same day the excavation is made. If required to be left open for more than one day, excavations shall be protected to prevent evaporation or entry of moisture. Surface runoff shall be drained away from excavations and not be allowed to pond.
Concrete shall be deposited as near as practicable to its final position to prevent segregation due to handling and flowing and to prevent splashing the forms or reinforcement with concrete. The concreting shall be carried on at such a rate that the concrete shall at all times be plastic and work readily into the spaces between the bars. No concrete that has partially hardened or has been contaminated by foreign materials shall be deposited, nor shall retempered concrete be used
14. CURING AND PROTECTION
Concrete shall be cured and protected in accordance with ACI 301.
Moisture shall be preserved as provided in ACI 301 for concrete not in contact with forms.
Ponding sprayed water or wet sand shall not be used for interior concrete slabs.
Liquid membrane curing compounds shall not be used on surfaces receiving bonded treatment, tile, paint or other adhered finishes, epoxy toppings or additional concrete.
Concrete shall be cured for a period of seven (7) days in weather above 70°F. Concrete shall be cured for a period of fourteen (14) days in weather below 70°F. The concrete temperature shall be maintained above 55°F and in moist conditions for at least the first seven (7) days after placing.
Any concrete, proven by tests to be frozen prior to curing, shall be completely removed from the structure and replaced at no additional cost to the Company
During the entire curing period, concrete shall be kept wet and covered with materials such as a polyethylene film or other suitable moisture barrier conforming to ASTM C 171 and approved by the Company Representative. The curing material shall be securely fastened to the concrete. Hot weather may necessitate water cooling of concrete in addition to membrane curing
Concrete to be exposed to the weather shall have an entrained air content of four percent (4%) to six percent (6%). Concrete to be exposed to the weather with less than four percent (4%) entrained air content shall be rejected.
15. SURFACE FINISHING
The specified surface finish shall be completed within the tolerances as defined in ACI 117.
Exposed concrete surfaces shall be professionally finished within 24 hours of the removal of the formwork to a smooth and uniform finish. Such finish shall be effected either by rubbing or by grinding with a carborundum stone. If plastering is required, a uniform color and appearance must be achieved. The sand-cement grout shall have a minimum seven (7) day compressive strength of three thousand pounds per square inch (3,000 psi). All form work ties shall be broken back one inch (1") from the surface of the concrete and the cavity patched with grout materials prior to finishing.
All exposed edges of concrete shall have a 45-degree chamfer.
Should any honeycombed concrete be discovered upon removal of forms, repairs shall be made within 24 hours after form removal. The Contractor shall chip the honeycombed portions back to solid concrete and shall fill the opening with grout or concrete of the same proportions as that specified for the section in which the fault occurs. Non-destructive or destructive testing to
Page: 6 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
determine the presence of internal honeycombs shall be performed, if required by the Company Representative. If it is determined by the Company Representative that the honeycombing is too extensive to repair, the foundation shall be removed and replaced at no additional cost to the Company.
16. TEMPERATURE CONCERNS
During hot and cold weather, concrete supply and construction shall be in accordance with ACI 305R and ACI 306.1.
Concrete Testing Requirements Company reserves the right to request concrete sampling and testing. If requested, concrete samples shall be obtained by a certified independent third party and tested by a certified independent laboratory in accordance with ACI 301. Testing shall be completed in accordance with the requirements of the Contract Documents. The rate of sampling shall be per ACI 301 and the following:
At least one sample shall be obtained per supplier per day that concrete is poured, unless the amount of concrete poured is less than 15 cubic yards (11 cubic meters).
For structures and foundations, at least one sample shall be obtained per supplier for each cumulative 65 cubic yards (50 cubic meters) of concrete poured.
For paving and slabs on grade, at least one sample shall be obtained per supplier for each cumulative 50 cubic yards (38 cubic meters) of concrete poured.
For all other applications, the rate of sampling shall be specified in the Contract Documents. For large pours (50 yds. or greater) when the concrete will be exposed to the weather, one (1) volumetric measurement of entrained air content shall be preformed for each truckload of concrete. Contractor shall be responsible for the performing air tests. Samples with less than four (4%) entrained air shall be rejected.
During placement of the concrete, representative samples of fresh concrete shall be cast in six inch (6”) diameter by twelve inch (12”) tall cylinders according to ASTM C 31 in order to determine the quality and strength of the hydrated concrete. The Contractor shall provide, prepare, and transport the concrete test cylinders. The Contractor shall be responsible for the selection of samples, storage of specimens, and protection of specimens against injury or loss throughout the operations. The Contractor shall furnish all concrete for testing.
Any group of compressive test samples taken shall consist of two (2) each of seven (7) day strength and two twenty-eight (28) day strength cylinders.
For other applications, the frequency of test samples required shall be one of the following; not less than three (3) samples for every fifty (50) yards (or fraction thereof) of placed concrete, not less than one (1) sample for each one thousand (1000) square feet of surface area placed (or fraction thereof), or as designated by the Company Representative.
At the discretion of the Company Representative, the Contractor may be directed to take additional test samples at no additional cost to the Company.
Test samples shall remain at the site exposed to the same conditions as the placed concrete for the first twenty-four (24) hours. Following the twenty-four (24) hours field cure period, the cylinders shall be immediately transported to a laboratory for controlled curing and testing. During periods of cold weather, the cylinders shall be transported in a temperature-controlled environmental (60- 80°F) or shall otherwise be insulated to protect against freezing.
Page: 7 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
No vehicular traffic, construction equipment, or materials shall be placed or permitted on foundations or floor slabs for at least three (3) days after placement and only if the concrete has achieved at least seventy-five percent (75%) of its specified twenty-eight (28) day compressive strength.
Prior to the end of the seven (7) day and/or fourteen (14) day cure period, the Company Representative may elect to qualify the concrete for loading based on testing cylinders to determine that the required concrete strength has been achieved. Upon approval by Company of alternative concrete mixture, Contractor may use high-early strength concrete. Contractor shall provide the Company adequate opportunity to place thermo-couples in completed formwork prior to placement of concrete.
The Company Representative and chief inspector will review concrete mixes, pours and curing times and work with the Contractor to minimize the curing time with Company design department approval. Each instance should be documented by the Contractor with a “request for information” (RFI).
If the Contractor elects to place equipment, materials, or traffic on concrete prior to the seven (7) day compressive test results, additional test cylinders shall be required to verify three (3) day compressive strength at no additional cost to the Company.
Strength of concrete shall be considered satisfactory if the average of two (2) twenty-eight (28) day tests in each set of cylinders equals or exceeds the specified twenty-eight (28) day strength and neither of the twenty-eight (28) day tests is five hundred (500) psi or more below the specified twenty-eight (28) day strength.
17. CARBON STEEL PIPE
Carbon steel pipe shall be manufactured and tested by the pipe manufacturer in accordance with the CFR 49 Part 192.
18. PIPE WELDING
Steel pipe jointing shall be performed by personnel trained and certified in the methods of such in Welding procedures shall be in accordance with 49 CFR Part 192.225 Welding procedures must be recorded in detail including the results of qualifying tests Welds will undergo 100% nondestructive inspection by a certified welding inspector to be provided by the Contractor.
19. COATING
All carbon steel piping, buried and above ground, shall be coated to protect from corrosion.
Contractor shall submit a two-part epoxy coating selection and color to match existing assembly for approval.
In addition to the requirements of this specification, all above ground coating application shall meet the requirements of the Steel Structures Painting Council (SSPC) and the Coating Manufacturer’s recommendations.
The Contractor/Applicator will follow the Company or coating manufacturer's recommendations for application and for curing time.
During application of coatings nearby structures or property shall be protected to avoid damage by overspray and/or drips.
Page: 8 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
If damage occurs, Applicator shall cease coating application until effective measures are taken to prevent further damage.
All damage will be reported to the Company immediately.
Any damages are repaired at the Applicator’s expense.
The Contractor takes sufficient WFT readings, using an approved instrument or measuring device, to allow an accurate estimation of the final Dry Film Thickness (DFT) of each coat.
DFT information will be recorded for record keeping purposed.
20. PRESSURE TESTING
All piping shall be tested by the contractor in accordance with CFR 49 Part 192 Subpart J.
Test requirements will be provided by Owner in accordance with CFR 49 Part 192 Subpart J and the Massachusetts Natural Gas Pipeline Safety Code.
Contractor is responsible for conducting the test in accordance with the provide procedures including provision of temporary blinds, fittings, hoses, nitrogen, air, recorders, and other equipment that may be necessary.
21. BOLTING
MATERIALS
i. Studs in this specification shall conform to ASTM A193.
ii. Nuts & washers in this specification shall conform to ASTM A194.
iii. Studs and nuts shall be Grade B7, Teflon coated.
iv. Nuts shall be 2H heavy hex.
LUBRICANTS
i. Studs shall be lubricated using Loctite Nickel Anti-Seize or equivalent if approved by Engineering.
ii. All threaded fasteners shall be lubricated immediately prior to installation. Lubricant shall be applied liberally to both ends of the stud bolt prior to the installation of the nuts.
WASHERS
i. A single 1/8 thick washer shall be installed between the nut that is to be turned and the flange.
ii. If desired, contractor may use washers on both side of flange for simplicity.
DOCUMENTATION
i. All studs nuts and washers shall be provided with Material Test Reports (MTRs) or
Certificates of Conformance (CFCs) identifying the material and treatment of the hardware.
PRIOR TO INSTALLATION
i. Contractor shall provide its torqueing plan, equipment conversion tables and calibration certifications (good within the last 12 months) to Cornerstone prior to commencement of the work. Contractor shall not use striking wrenches.
Page: 9 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ii. The number, diameter, and length of studs for various flange sizes and ratings shall meet the requirements of Section 9- Torque Tables
iii. All gaskets shall be CGI type, with a 304SS or 316SS inner ring and a carbon steel outer ring.
iv. Nuts shall be hand tightened first, ensuring both full engagement of the nut threads as well as an equal division of excess bolt length between both ends.
v. Contractor is responsible for the integrity of all installed threaded fasteners. This includes proper storage to prevent corrosion or damage. Fasteners shall be stored out of the weather and kept out of the dirt when the flange is being fit up.
vi. Studs and nuts shall be inspected for thread damage and fit. Contractor shall replace any studs and nuts where difficult engagement is encountered or too loose when threaded by hand. Studs and nuts with damaged threads are not to be used.
INSTALLATION
i. Torquing shall be required on all applications and not as a substitute for the equipment manufacturer's specifications and/or standards.
ii. Studs and nuts shall be replaced if studs have been torqued to a load that exceeds the applicable value specified by more than 30%. Contractor shall replace, at no additional cost to others, any studs that are over-torqued.
iii. Pneumatic or adjustable torque wrenches shall be used for tightening studs to the zero-tension point, which is commonly known as “snugging up”.
iv. Contractor shall submit calibration certificates for all torqueing equipment used.
v. Properly calibrated pneumatic, hydraulic or manual torqueing equipment may be used.
The Contractor is responsible for selecting the appropriate torqueing equipment.
vi. Torque wrenches may be used on flange connections, however in applications larger than
24” Engineering should be consulted prior to doing so.
vii. Studs shall be centered in torqued flange connections (approximately equivalent bolt protrusion beyond the nut faces on either side after tightening). Bolt threads shall fully engage the nut threads on both sides of the connection prior to tightening. Studs shall have a minimum engagement of .5 exposed threads and a maximum of 4.
viii. Studs shall be torqued to the values given in Torque Tables
ix. When torqueing, studs shall be tightened in 25% increments of final torque following the sequential order shown on torque forms. When 100% of the final torque value is reached all studs shall be rechecked in a ring pattern until no studs move to ensure the 100% torque value is maintained.
x. Contractor shall submit a report with final torque values for every flange, with the appropriate signoffs and a map indicating where each flange is located. Report templates can be found in Section 8. Torque maps shall be submitted on engineering drawings unless approved by Engineering to do otherwise.
LEAK TIGHTENING
i. Repair of leaking flanges during pressure testing of a newly constructed pipe system shall meet the following requirements.
Page: 10 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ii. The determination of whether to tighten leaking flanges while under pressure or to depressurize prior to retightening shall be mutually agreed upon between the Contractor and the Inspector. Inspector approval is required prior to tightening of leaking flanges and the pressure must be lowered to 0 PSIG, or as close as possible.
iii. Extreme caution shall be exercised when it is deemed prudent to tighten leaking flanges or threaded fittings while under pressure.
iv. Studs shall be retightened by increasing the specified torque value by 15%.
v. Continued leakage shall be eliminated by depressurizing the system, disassembling and inspecting the flange, checking the alignment, cleaning and inspecting the gasket seal area on the flange face, or replacing damaged or improper flanges, reassembling with a new gasket, and re-tightening.
vi. Contractor shall be responsible for ensuring that all flanged connections are properly tightened prior to pipelines and appurtenances being placed in service.
Page: 11 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
22. TORQUE TABLES
ANSI CLASS 150 RAISED FACE FLANGES
Application: B8 studs and nuts, with washer
Flange Size
Bolt Dia.
2H Nut Size
Bolt Lengths
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 1/2" 7/8” 3-1/4” 4 42 11, 21, 32 49
1-1/2” 1/2" 7/8” 3-1/4” 4 60 15, 30, 45 69
2" 5/8" 1-1/16” 3-3/4” 4 85 22, 43, 64 98
2 1/2" 5/8" 1-1/16” 4” 4 85 22, 43, 64 98
3" 5/8" 1-1/16” 4-1/4" 4 85 22, 43, 64 98
3 1/2" 5/8" 1-1/16” 4-1/4" 8 85 22, 43, 64 98
4" 5/8" 1-1/16” 4-1/4" 8 85 22, 43, 64 98
6" 3/4" 1-1/4” 4-1/2" 8 153 39, 77, 115 176
8" 3/4" 1-1/4” 4-3/4" 8 153 39, 77, 115 176
10" 7/8" 1-7/16” 5-1/2" 12 248 62, 124, 186 286
12" 7/8" 1-7/16” 5-1/2" 12 248 62, 124, 186 286
16" 1" 1-5/8” 6-1/4" 16 372 93, 186, 279 428
18" 1-1/8" 1-13/16” 6-3/4" 16 553 139, 277, 415 636
20" 1-1/8" 1-13/16” 7” 20 553 139, 277, 415 636
24" 1-1/4" 2” 7-3/4” 20 784 196, 392, 588 902
26" 1-1/4" 2” 9-1/2” 24 784 196, 392, 588 902
30" 1-1/4" 2” 10” 28 784 196, 392, 588 902
36" 1-1/2" 2-3/8” 11-1/2” 32 1424 356, 712, 1,068 1,638
Page: 12 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ANSI CLASS 300 RAISED FACE FLANGES
Application: B8 studs and nuts, with washer
Flange Size
Bolt Dia.
2H Nut Size
Bolt Lengths
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 5/8" 1-1/16” 3-3/4” 4 85 22, 43, 64 98
2" 5/8" 1-1/16” 4” 8 85 22, 43, 64 98
2 1/2" 3/4" 1-1/4” 4-1/2” 8 153 39, 77, 115 176
3" 3/4" 1-1/4” 4-3/4” 8 153 39, 77, 115 176
3 1/2" 3/4" 1-1/4” 5” 8 153 39, 77, 115 176
4" 3/4" 1-1/4” 5” 8 153 39, 77, 115 176
6" 3/4" 1-1/4” 5-1/2” 12 153 39, 77, 115 176
8" 7/8" 1-7/16” 6-1/4” 12 248 62, 124, 186 286
10" 1" 1-5/8” 7” 16 372 93, 186, 279 428
12" 1-1/8" 1-13/16” 7-1/2” 16 553 139, 277, 415 636
16" 1-1/4" 2” 8-1/4” 20 784 196, 392, 588 902
18" 1-1/4" 2” 8-1/2” 24 784 196, 392, 588 902
20" 1-1/4" 2” 9” 24 784 196, 392, 588 902
24" 1-1/2" 2-3/8” 10” 24 1424 356, 712, 1,068 1,638
26" 1-5/8" 2-9/16” 11” 28 1844 461, 922, 1,383 2,121
30" 1-3/4" 2-3/4” 12-1/4” 28 2339 585, 1,170, 1,755 2,690
36" 2" 3-1/8” 13-3/4” 32 3582 896, 1,791, 2,687 4,120
Page: 13 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ANSI CLASS 600 RAISED FACE FLANGES
Flange Size
Bolt Dia.
2H Nut Size
Bolt Lengths
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 5/8" 1-1/16” 4-1/4” 4 85 22, 43, 64 98
2" 5/8" 1-1/16” 4-3/4” 8 85 22, 43, 64 98
2-1/2" 3/4" 1-1/4” 5-1/4” 8 153 39, 77, 115 176
3" 3/4" 1-1/4” 5-1/2” 8 153 39, 77, 115 176
4" 7/8" 1-7/16” 6-1/2” 8 248 62, 124, 186 286
6" 1" 1-5/8” 7-1/2” 12 372 93, 186, 279 428
8" 1-1/8" 1-13/16” 8-1/2” 12 553 139, 277, 415 636
10" 1-1/4" 2” 9-1/4” 16 784 196, 392, 588 902
12" 1-1/4" 2” 9-1/2” 20 784 196, 392, 588 902
16" 1-1/2" 2-3/8” 10-3/4” 20 1424 356, 712, 1,068 1,638
18" 1-5/8" 2-9/16” 11-1/2” 20 1844 461, 922, 1,383 2,121
20" 1-5/8" 2-9/16” 12-1/4” 24 1844 461, 922, 1,383 2,121
24" 1-7/8" 2-15/16” 13-3/4” 24 2917 730, 1,459, 2,188 3,355
26" 1-7/8" 2-15/16” 14-1/4” 28 2917 730, 1,459, 2,188 3,355
30" 2" 3-1/8” 15” 28 3582 896, 1,791, 2,687 4,120
36" 2-1/2" 3-7/8” 16-3/4” 28 7245 1,812, 3,623, 5,434 8,332
Page: 14 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ANSI CLASS 900 RAISED FACE FLANGES
Flange Size
Bolt Dia.
2H Nut Size
Bolt Lengths
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 7/8" 1-7/16” 5-3/4” 4 248 62, 124, 186 285
2" 7/8" 1-7/16” 6-1/2" 8 248 62, 124, 186 285
2-1/2" 1" 1-5/8” 7” 8 372 93, 186, 279 428
3" 7/8" 1-7/16” 6-1/2" 8 372 93, 186, 279 428
4" 1-1/8" 1-13/16” 7-1/2" 8 248 62, 124, 186 285
6" 1-1/8" 1-13/16” 8-1/2" 12 553 138, 276, 414 636
8" 1-3/8" 2-3/16” 9-1/2" 12 553 138, 276, 414 636
10" 1-3/8" 2-3/16” 10” 16 1073 268, 536, 804 1234
12" 1-3/8" 2-3/16” 10-3/4" 20 1073 268, 536, 804 1234
16" 1-5/8" 2-9/16” 12” 20 1844 461, 922, 1383 2121
18" 1-7/8" 2-15/16” 13-1/2" 20 2917 729, 1458, 2187 3355
20" 2" 3-1/8” 14-1/2" 20 3582 896, 1792, 2688 4119
24" 2-1/2" 3-7/8” 18” 20 7245 1811, 3622, 5433 8332
26" 2-3/4" 4-1/4” 18-1/2" 20 9764 2441, 4882, 7323 11229
30" 3" 4-5/8” 19-3/4" 20 12809 3202, 6404, 9606 14730
36" 3-1/2" 5-3/8” 22-1/2" 20 20674 5169, 10338, 15507 23775
Page: 15 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ANSI CLASS 1500 RAISED FACE FLANGES
Flange Size
Bolt Dia.
2H Nut Size
Bolt Length s
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 7/8" 1-7/16” 5-3/4” 4 248 62, 124, 186 285
2" 7/8" 1-7/16” 6-1/2” 8 248 62, 124, 186 285
2-1/2" 1" 1-5/8” 7” 8 372 93, 186, 279 428
3" 1-1/8” 1-13/16” 7-3/4” 8 553 138, 276, 414 636
4” 1-1/4” 2” 8-1/2” 8 784 196, 392, 588 902
ANSI CLASS 2500 RAISED FACE FLANGES
Flange Size
Bolt Dia.
2H Nut Size
Bolt Lengths
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 7/8” 1-7/16” 6-1/4” 4 248 62, 124, 186 285
2" 1” 1-5/8” 7-3/4” 8 372 93, 186, 279 428
2-1/2" 1-1/8” 1-13/16” 8-1/2” 8 553 138, 276, 414 636
3" 1-1/4” 2” 9-1/2” 8 784 196, 392, 588 902
4” 1-1/2” 2-3/8” 10-3/4” 8 1424 356, 712, 1068 1638
Page: 16 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT
ANSI CLASS 150 FLAT FACE FLANGES
Flange Size
Bolt Dia.
2H Nut Size
Bolt Lengths
Number of Studs
Final Torque (ft-lb)
Torque Increments (ft-lbs)
15% Over Value (ft-lbs)
1" 1/2" 7/8” 3-1/4” 4 60 15, 30, 45 69
1-1/2” 1/2" 7/8” 3-1/4” 4 90 23, 46, 69 104
2" 5/8" 1-1/16” 3-3/4” 4 120 30, 60, 90 138
2 1/2" 5/8" 1-1/16” 4” 4 120 30, 60, 90 138
3" 5/8" 1-1/16” 4-1/4" 4 120 30, 60, 90 138
3 1/2" 5/8" 1-1/16” 4-1/4" 8 120 30, 60, 90 138
4" 5/8" 1-1/16” 4-1/4" 8 120 30, 60, 90 138
6" 3/4" 1-1/4” 4-1/2" 8 200 50, 100, 150 230
8" 3/4" 1-1/4” 4-3/4" 8 200 50, 100, 150 230
10" 7/8" 1-7/16” 5-1/2" 12 320 80, 160, 240 368
12" 7/8" 1-7/16” 5-1/2" 12 320 80, 160, 240 368
16" 1" 1-5/8” 6-1/4" 16 490 123, 246, 369 564
18" 1-1/8" 1-13/16” 6-3/4" 16 710 178, 356, 534 817
20" 1-1/8" 1-13/16” 7” 20 710 178, 356, 534 817
24" 1-1/4" 2” 7-3/4” 20 1000 250, 500, 750 1150
26" 1-1/4" 2” 9-1/2” 24 1000 250, 500, 750 1150
30" 1-1/4" 2” 10” 28 1000 250, 500, 750 1150
36" 1-1/2" 2-3/8” 11-1/2” 32 1800 450, 900, 1350 2070
Page: 17 of 17
Specification Number: CS-21128
MGED: OCEAN SPRAY PROJECT