The provided file is a detailed ductwork and HVAC system map for the 20th Intelligence Squadron (IS) facility, annotated with technical observations about air handling units (AHUs), exhaust fans (EFs), and air distribution systems. The diagram uses color-coded lines to represent different air flow types: green for supply air, orange for return air, dark blue for outside air, and light blue for exhaust air.
The map highlights several key HVAC system characteristics, including: multiple air handling units (AHU-1 through AHU-5) with varying duct sizes ranging from 8"x10" to 72"x24"; non-functional fan coils; rooms with defunct package units; exhaust fans running continuously; and specific ventilation issues such as bathrooms exhausting into open mechanical areas and rooms with inconsistent return air configurations. The annotations suggest potential maintenance and upgrade needs for the facility's air handling infrastructure.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
These last two rooms are open-ceiling back to double doors
Fan coil does not appear to be working
Bathrooms in mech/storage area exhaust out to open mech/storage area
These three empty offices served by defunct package unit in one of their ceilings
Has ducted return in this room but also open return above ceiling, but no open return plenum grillsEF runs 24/7 in these two rooms, expels through roof/ceiling
To crac & underfloor distribution
Fan coil only has CW, no fresh air
No return air in this room
AHU-1
AHU-3
AHU-2
AHU-4
AHU-5
Green = Supply Air Orange = Return Air Dark Blue = Outside Air Light Blue = Exhaust
40”x24”
40”x24”
”x
”x
”x
”x
Exhaust size unknown
72”x24”72 ”x
54”x28”
”x
”x
28”x14”
28”x20”
Large EF duct from bathrooms exits here (30”x16”)
Large EF duct from bathrooms exits near here (30”x16”)
”x
20”x12”
10”x10”10”x10”
8”x10” 10”x10”
Slide Number 1