2031ZA27Q00004 Questions and Answers.pdf
PDF 163 KB Posted
- Solicitation number
- 2031ZA27Q00004
About this file
This document is a Questions and Answers (Q&A) clarification for federal contract solicitation 2031ZA27Q00004, addressing consolidated inquiries from prospective offerors regarding proposal submission, pricing, technical requirements, and operational logistics.
Submission and Technical Requirements: Volume I (Technical) proposals have a 5-page limit, excluding cover pages, tables of contents, resumes, ICC/NAFED technician certifications, and supporting documentation. Quotes must be submitted via email to bryan.sheppard@bep.gov with active SAM.GOV registration serving as sufficient compliance; signed SF-1449 forms are not required. Small-business prime contractors may satisfy the three-year experience and ICC/NAFED certification requirements through qualified subcontractors and field technicians, and FAR 52.219-14 does not apply. Past performance will be evaluated through CPARS only, with newer businesses without federal history assessed as neutral. No additional local licensing beyond ICC/NAFED certifications is required.
Pricing, Services, and Operations: Quoted fixed unit prices in Attachment 3 serve as firm-fixed pricing across the five-year contract term, with adjustments permitted only for Wage Determination rate increases under Service Contract Act job classification 23310 (Fire Extinguisher Repairer). The government estimates 160 six-year maintenance units, 80 twelve-year hydrotest units, and 40 replacement units annually for evaluation purposes only; actual quantities vary based on inspection results with no guaranteed minimum order. Unit prices must include all labor, recharge agents, replacement parts, hose continuity testing, transportation, and loaner extinguisher provision. The annual inspection covers approximately 1,000 extinguishers at 301 14th and C Street SW, Washington DC 20228 (two buildings opposite each other), with a December 1–22 inspection window during working hours (7:00 AM–3:00 PM) only. Service call fees apply as a single flat fee per authorized BPA call with estimated frequency of one call annually, with all travel costs bundled into the annual inspection price. Replacement units are ordered via individual BPA calls with contractor responsibility for disposal of condemned units. The contractor must collect and return extinguishers across all main, annex, and storage locations, and off-site testing at the contractor's shop is permitted with COR notification. Dedicated staging areas, loading dock access, and parking passes will be provided. Personnel will receive BEP-escorted access until background clearance completion, with award expected before December 1, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - PWS v3.pdf | ||
| 2031ZA27Q00004 Questions and Answers_Updated 10.26.26.pdf | ||
| RFQ 2031ZA27Q00004 v2.pdf | ||
| Attachment 3 - Pricing Sheet v2.xlsx | XLSX spreadsheet | |
| Attachment 1 - PWS v2.pdf | ||
| Attachment 2 - Wage Determination.pdf | ||
| Attachment 1 - PWS.pdf | ||
| Attachment 3 - Pricing Sheet.xlsx | XLSX spreadsheet | |
| RFQ 2031ZA27Q00004.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2031ZA27Q00004 – Q&A
Note: Due to the high volume of questions, duplicate and substantially similar questions have been consolidated below. Please review all questions and answers fully before submitting a response.
Category 1: Proposal Submission & Evaluation Instructions
1. Page Limit & Formatting
• Clarify the applicable page limit for Volume I (Technical), as the RFQ instructions specify a 5-page limit in one section and a 10-page limit in another. Page limit is 5.
• Specify which documents count toward this page limit and which are excluded (e.g., cover page, table of contents, resumes, ICC/NAFED technician certifications, and supporting documentation). Cover page, table of contents, resumes, ICC/NAFED technician certifications, and supporting documentation are excluded from the page limit.
2. Submission Instructions & Administration
• How should quotes be submitted (e.g., via email, SAM.gov, or another solicitation portal)? Email to bryan.sheppard@bep.gov.
• Should signed SF-1449 forms and Representations & Certifications be submitted with the quote, or is an active SAM.gov registration sufficient? Active SAM.GOV registration is sufficient.
• Confirm whether CLINs 0001–0006 correspond to Ordering Period 1 (Dec 2026 – Nov 2027) through CLINs 4001–4006 for Ordering Period 5. Correct, though see updated Attachment 3. CLINs have been expanded.
3. Subcontracting, Qualifications & Licensing
• Limitations on Subcontracting: FAR 52.219-6 is cited, but FAR 52.219-14 is not listed. Does the 50% service limitation apply, and do subcontracts awarded to similarly situated small businesses count toward the prime contractor’s share? Is there a cap on subcontracted work? FAR 52.219-14 is not applicable.
• Qualifications via Subcontractor: Sections 1.6.8 and 5.1.7/5.1.8 of the PWS state that the "Contractor" must meet the 3-year experience and ICC/NAFED certification requirements, whereas evaluation language indicates subcontractor capabilities may qualify. Confirm whether a small-business prime contractor may fulfill the technical experience and ICC/NAFED certification requirements through a qualified subcontractor and/or certified technicians performing the field work. Yes, subcontractor experience and certification is qualifying.
mailto:bryan.sheppard@bep.gov
• Licensing Requirements: Are there specific local licensing requirements imposed by the DC Fire and EMS Department beyond ICC/NAFED certifications? No other licensing needed.
4. Past Performance Assessment
• How will "no adverse past performance" be assessed (e.g., CPARS evaluation only, or submitted past customer references)? CPARS.
• Will an offeror/newer business with no prior federal past performance record be evaluated as Neutral? Yes.
5. MISC. What quality inspection plan the government will use, the insurance amounts required, and the format you want for the 48-hour report after the inspection.
These items will be shared after award. See clause 1052.228-70 INSURANCE (APR 2015).
Category 2: Pricing, Ordering & BPA Terms
1. Price Review & BPA Call Structure
• Clarify the language stating that "pricing will be reviewed on a per-call basis." Do quoted fixed unit prices in Attachment 3 serve as firm-fixed pricing for each ordering period, or will prices be subject to renegotiation upon issuance of each BPA call?
Quoted fixed unit prices in Attachment 3 serve as firm-fixed pricing. This language is removed to avoid any confusion.
• Will fixed unit prices remain fixed across the 5-year period, and will economic price adjustments (e.g., Service Contract Act / Wage Determination rate increases) be permitted? Adjustments will be considered as required by Wage Determination rate increases.
• Which Service Contract Act job classification applies to field personnel (e.g., Fire Extinguisher Repairer)? 23310 – Fire Extinguisher Repairer
2. Quantities & Guarantees
• Are the quantities listed in Attachment 3 (e.g., 160 six-year maintenance units, 80 twelve-year hydrotest units, 40 replacement units) evaluation estimates, and may the Government order more or fewer units? Confirm if these quantities apply to each annual ordering period. See updated Attachment 3. Estimates are for price evaluation purposes only and will vary depending on annual inspection results.
• Is there a guaranteed minimum order value or maximum ordering limit for this BPA?
No minimum order. A maximum will be established after evaluation of quotes.
Category 3: Scope of Work, Technical Requirements & Pricing Structure
1. Unit Inclusions, Repairs & Overlapping Services
• Cost Inclusions: Should unit prices for 6-year maintenance and hydrostatic testing include all associated labor, recharge agents, replacement parts (e.g., O-rings, stems, verification collars, seals, tags), hose continuity testing, and transportation?
Yes.
• Unscheduled Repairs: How should stand-alone repairs, replacement parts, or standalone recharges identified during inspections be priced, given that Attachment 3 does not include a separate repair or parts line item? See updated attachment 3.
• Overlapping Services: Confirm that when an extinguisher undergoes 5-year or 12-year hydrostatic testing (which includes teardown/maintenance), the service is billed under the hydrostatic testing line only, without a separate charge for 6-year maintenance or recharge. Do the 160 six-year maintenance units and 80 twelve-year hydrotest units represent distinct groups, or do they overlap? See updated attachment 3.
2. Annual Inspection Pricing Line
• Line Item CLIN x001 (Annual Inspection) reflects a quantity of 1. Should offerors quote a single lump-sum price to inspect all ~1,000 extinguishers, or a unit price per extinguisher? How will pricing be adjusted if the overall inventory increases or decreases over the contract term? See updated attachment 3.
3. Service Call Fee Application
• Please clarify precisely when CLIN x006 (Service Call Fee) applies:
o Does it cover a single trip/dispatch per authorized BPA call regardless of how many units are serviced, or does it apply per visit/collection/return? This is a single fee per BPA call.
o Does the service call fee apply to the scheduled annual inspection, or is travel/dispatch expected to be fully bundled into the annual inspection price? All costs (travel) should be priced into the annual inspection price.
o How many service calls per year should offerors assume for pricing purposes? Estimated to be 1 service call per year.
4. Replacement Extinguishers (CLIN x005)
• Attachment 3 lists a single fixed unit price for replacement extinguishers, but types range from 2.5 lb dry chemical up to 20 lb CO₂ and Class K units.
o Should offerors provide one blended/average unit price across the entire inventory? See updated attachment 3.
o Can the Government provide an estimated breakdown by size, type, rating, and spec (e.g., 10 lb ABC, 20 lb CO₂)? If not, should offerors quote separate prices by type/size? See updated attachment 3.
o Is the contractor expected to keep a revolving replacement inventory on-site, or will replacements be ordered via individual BPA calls as units fail inspection? Who is responsible for the disposal of condemned units?
Replacement units will be ordered via BPA call, though loaners shall be provided for any units taken off-site for servicing. Contractor is responsible for disposal.
Category 4: Operations, Logistics & Security
1. Inventory & Historical Data
• Can the Government provide an inventory list/breakdown of the ~1,000 extinguishers by type, capacity, manufacturer date, and last hydrostatic/6-year service dates? Inventory is not available, but see attachment 3 for updated quantities and weights.
• Is the prior contract/award number (e.g., 2031ZA27Q00001 or earlier), current/previous incumbent contractor name, or total historical award value available? Prior contract ID numbers are 2031ZA26P00049 and 2031ZA21P00002.
Full contract details are available on SAM.GOV.
2. Off-Site Testing & Loaner Units
• May 6-year teardowns and hydrostatic testing be performed off-site at the contractor's shop, and what approval process is required? Yes. COR will be notified.
• In accordance with OSHA 29 CFR 1910.157(e)(5), is the contractor required to supply temporary loaner extinguishers while units are removed for off-site servicing? If so, under which CLIN should loaner provision be quoted, or should it be built into service line prices? Yes, loaner prices should be built into fixed unit pricing.
3. December Inspection Window & Access
• The Period of Performance begins December 1, 2026, with annual inspections scheduled for December, alongside a BEP year-end shutdown between Christmas and New Year’s Day. What is the precise window and timeline to complete the ~1,000 unit inspections? December 1 – 22 is the anticipated timeline for annual inspections. Date adjustments will be coordinated as needed with the COR/CO.
• Are weekend, evening, or multi-shift work hours permitted to complete inspections prior to the holiday shutdown? Are contractors able to access all main and annex facility areas during regular working hours (7:00 AM – 3:00 PM)? No holiday, or evening hours. Access is limited to working hours defined in the PWS.
4. Site Logistics, Addresses & Parking
• What are the specific addresses for the annex buildings, and approximately how many extinguishers are located at each facility? 301 14th and C St SW Washington DC 20228. The buildings are directly opposite of each other on 14th st sw.
• Will the contractor be required to collect and return extinguishers throughout individual main and annex locations, or will BEP aggregate units at a central point?
Contractor be required to collect and return extinguishers throughout individual main and annex locations as well as service the extinguishers that are in the storage area.
• Will dedicated staging areas, loading dock access, or service vehicle parking passes be provided at the 14th & C Street SW facilities? Yes.
5. Security Clearances & Escorts
• What is the average processing timeline for BEP low-level background checks?
Typical processing time for the required background investigations or low-level BEP clearance vary person to person. The contractor will be escorted until the contractor clears the background investigation and get there badge.
• If background clearances are pending when performance begins on December 1, will continuous BEP-escorted access be provided so technicians can execute work on schedule? When is award expected? Escort will be provided as needed. Award is expected before December 1st.