2026.5.5. CMS Play Add 3.pdf
PDF 4 MB Posted
- Solicitation number
- S-P26028-00016709
- Issued by
- Oregon
About this file
This is Addendum Number Three to the contract documents for the Centennial Middle School Site Renovations Project #260512-01, issued by the Centennial School District in Portland, Oregon on May 5, 2026. The addendum modifies the original contract documents dated April 22, 2026, and provides updates to project specifications, drawings, and administrative procedures. A non-mandatory pre-bid conference was held on April 28, 2026 at 4:30 PM at Centennial Middle School (17650 SE Brooklyn Street, Portland, OR 97236), with an attendance record included in the addendum. Bidders must submit questions, requests for information (RFIs), and substitution requests by end of day May 1, 2026, with substitution requests directed to jfulton@dlrgroup.com and questions to scott@randcmanagement.com. Site visit scheduling can be arranged by contacting Dan Bodell at dan@randcmanagement.com. Bids are due on Tuesday, May 12, 2026 at 2:00 PM, deliverable to the Centennial School District District Office at 18135 SE Brooklyn Street, Portland, OR 97236, either by U.S. Mail or hand delivery. The project timeline includes School Board approval on May 13, 2026; Notice to Proceed on May 14, 2026; contractor mobilization on May 18, 2026; covered play shelter delivery on July 31, 2026; and substantial completion on August 28, 2026.
The base bid for the complete project is expected at approximately $450,000, with bid bonds required at submission and performance and payment bonds to be provided with the signed contract. The project is subject to State of Oregon prevailing wage requirements, and the contractor must comply with City of Portland work hour regulations. Building permit fees are procured and paid by the Centennial School District, while trade permit fees are the responsibility of the general contractor's subcontractors. The contract is classified as a Public Works project under the agreement between the District and Contractor. Revised drawings included in this addendum address the stormwater management plan (Sheet C3.0), civil details (Sheet C5.0), landscape planting plan (Sheet L3.1), and landscape details (Sheet L5.1), with work encompassing drainage infrastructure, site grading, landscaping, fencing, basketball and volleyball courts, and play structure preparation at the school's play area.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CENTENNIAL MIDDLE SCHOOL SITE RENOVATIONS
PROJECT #260512-01
May 5, 2026
ADDENDUM NO. THREE (3)
THE FOLLOWING CHANGES, ADDITIONS, AND DELETIONS TO THE CONTRACT DOCUMENTS
DATED MAY 5, 2026, HEREBY BECOME A PART OF THE CONTRACT DOCUMENTS, PER THE
ORIGINAL CONTRACT DOCUMENTS DATED APRIL 22, 2026.
NOTIFY ALL SUBCONTRACTORS AFFECTED BY THIS ADDENDUM.
BID DUE UNCHANGED: Tuesday, May 12, 2026, 2:00 PM
SPECIFICATIONS
N/A
DRAWINGS
See Narrative Attached.
GENERAL INFORMATION
1. Pre-Bid conference agenda attached.
2. Record of Attendance of the non-mandatory Pre-Bid conference attached.
END OF ADDENDUM THREE (3)
Attachments:
Pre-Bid Agenda
Pre-Bid Record of Attendance
DLR Group narrative with drawings
NON-MANDATORY PRE-BID MEETING AGENDA
p
ITEM # DESCRIPTION
1.0 Team Introductions
2.0 Non-Mandatory Pre-Bid meeting - Record of Attendance
3.0 Future Site Visit:
3.1 Contact Dan Bodell, dan@randcmanagement.com to schedule future site visits.
4.0 Request for Bids / Bid Dates
4.1 Bids Due 2:00 PM, May 12, 2026
4.2 Substitution Requests
4.2.1 Send to jfulton@dlrgroup.com
4.2.2 Submit any substitution requests by end of day May 1, 2026, per Instructions to Bidders.
4.2.3 See specification section 01 6000 - PRODUCT REQUIREMENTS AND
SUBSTITUTION for substitution requirements/procedures.
4.2.4 Substitution request need to be filled out on the Substitution Request form available in section 01 6325 of the specifications.
4.3 Any Questions / RFI’s .
4.3.1 Send to scott@randcmanagment.com
4.3.2 Submit any questions/RFI requests by end of day May 1, 2026.
4.3.3 Last Addendum will be issued by May 5, 2026, that will include record of attendance, pre-bid agenda and city comments.
4.4 Bids Due, Received until May 12, 2026 at 2:00 PM
To: Centennial School District
By U.S. Mail:
Centennial School District District Office – Bid #260512-01 18135 SE Brooklyn Street Portland, OR 97236
CENTENNIAL SCHOOL DISTRICT
Project #260512-01 Revised Site Renovations at Centennial Middle School Pre-Bid Meeting
Date of Meeting: 4/28/26 @ 4:30 PM Location of Meeting:
Centennial Middle School 17650 SE Brooklyn St., Portland, OR
97236
By hand delivery:
Centennial School District 18135 SE Brooklyn Street Portland, OR 97236 District Office Bid #260512-01
5.0 Construction Schedule (See Spec 00 72 10 – Additional Conditions section 1.03 Schedule of work)
The General Contractor shall include the following anticipated date constraints for the Work.
1. School Board Approval of the Agreement. 5/13/26
2. Issuance of the Notice to Proceed. 5/14/26
3. Site available for Contractor mobilization. 5/18/26
4. Agency Release of the Permit 5/17/26
5. Covered Play Shelter arrives on site 7/31/26
6. Date of Substantial Completion. 8/28/26
6.0 Bid Form Section 00 41 00
6.1 Base Bid Complete Project, Expected bid of $450,000
6.2 Bid Bond requirements – see instruction to bidders.
6.3 Performance / Payment bonds provided with signed contract – see instruction to bidders.
7.0 Agreement / General Conditions
7.1 Agreement between CSD and Contractor. Public Works contract.
8.0 Prevailing Wage
8.1 Must comply with State of Oregon prevailing wage requirements.
9.0 Jobsite / Site Logistics
9.1 Work hours-comply with City regulations.
9.2 Site laydown areas within the limits of the site.
10.0 Permits/Fees
10.1 Building permit fees – Procured and paid by District.
10.2 Trade permits fees – Procured paid by GC’s subcontractors.
10.3 Status – Under review with City.
10.4 Owner shall provide Special Inspections as needed.
11.0 Summary of Work
11.1 Scope of work.
12.0 Questions
ADDENDUM 3
DRAWINGS
The following Drawings are revised and reissued with this Addendum.
Item 1. SHEET – C3.0 – STORMWATER MANAGEMENT PLAN
Item 2. SHEET – C5.0 – CIVIL DETAILS
Item 3. SHEET – L3.1 – LANDSCAPE PLANTING PLAN
Item 4. SHEET – L5.1 – LANDSCAPE DETAILS
Correction to Narrative for Addendum 2
DRAWINGS
Item 8. SHEET – C2.0 L5.1 – LANDSCAPE DETAILS
DW
CB
CB
CB
CO CO
CO
COCO
CO
CO
CO
STORMWATER
MANAGEMENT
PLAN
C3.0
PLAN SCALE
N
STORMWATER MANAGEMENT PLAN
SCALE: 1" = 10'
5/ 1/
:4
3:
P M
74-23118-00
03/20/2026
C
EN
TE
N
N
IA
L M
ID
D
LE
S
C H
O O
L
- P
LA
Y
AR
EA
BID & PERMIT SET
REVISIONS
A B C D E F
C3.0
SO
U
TH
EA
ST
B R
O O
KL
YN
S
TR
EE
T
CE
NT
EN
NI
AL
S
CH
OO
L
DI
ST
RI
CT
EXPIRATION DATE: 06/30/26
91653PE
OREGON
ENG INEER
SEPT 13 , 20 16
A N
DREA W . STANCL
I F
F
RE
G I S
TERED PROFESS IONAL
1498 E. Main Street, Suite 103, #345
Cottage Grove, Oregon 97424 www.gaia-engineering.com
503-830-3635
PO
R
TL
AN
D , O
R
EG
O N
SHEET NOTES
CONSTRUCTION NOTES
1. CONSTRUCT CLEAN OUT PER DETAIL 2/C5.0.
2. CONSTRUCT LYNCH-STYLE CATCH BASIN PER DETAIL 3/C5.0.
3. CONSTRUCT DRYWELL PER DETAIL 4/C5.0.
4. ROOF DOWNSPOUT CONNECTION. SEE ROOF STRUCTURE DRAWINGS FOR
CONTINUATION OF DRAIN PIPE IN THE ROOF.
5. CONSTRUCT 4-INCH WIDE CLASS B RATED TRENCH DRAIN PER DETAIL 5/C5.0.
INSTALL STORM DRAIN OUTLET IN THE VERTICAL POSITION AND CONSTRUCT A 90°
VERTICAL BEND TO CONNECT INTO 6" SD AT ELEVATION AS SHOWN ON PLANS.
6. CONSTRUCT 4" PERFORATED PVC PIPE SET IN 12" - 1" DRAIN ROCK, 12" MIN DEEP.
REFER TO LANDSCAPE ARCHITECTURAL PLANS FOR SWING SET AREA, INCLUDING
BARK MULCH DETAILS. SEPARATION GEOTEXTILE TO BE INSTALLED AT TOP OF
DRAIN ROCK. SEE DETAIL 9/C5.0.
7. CONSTRUCT GRASSY SWALE PER DETAIL 10/C5.0.
1. REFER TO SHEET C0.00 FOR GENERAL NOTES, LEGEND AND CIVIL DETAILS.
2. REFER TO SHEET SURVEY DRAWING FOR SURVEY CONTROL POINTS.
3. USE BUILDING APPROVED MATERIALS FOR ANY AND ALL ELEMENTS OF UTILITY
SYSTEMS INSTALLED WITHIN 2-FEET OF BUILDINGS OR OTHER STRUCTURES.
4. CONTRACTOR SHALL VERIFY EXISTING PIPE ELEVATIONS, SIZES, ORIENTATION AND
PIPE CONDITIONS PRIOR TO STARTING CONSTRUCTION. NOTIFY ENGINEER OF
DISCREPANCIES.
N165053.58, E397243.50
CONST 48" DIA DRYWELL #1
RIM= 261.22
6"FL (S) = 255.00
6"FL (W) = 255.00
BOTTOM= 241.22
N164966.33, E397302.98
END TRENCH DRAIN
RIM= 262.29
TD FL = 260.37
6"FL = 260.37
CONST 6" SD 4.6 LF
S=0.0227 FT/FT
EXISTING SCHOOL
FFE=262.43'
EXISTING
PARKING
LOT
EXISTING ASPHALT
TRACK AREA
EXISTING
PROPERTY LINE,
TYP.
N164878.59, E397243.50
CONST SD CB #3
RIM= 261.35
6"FL = 259.85
CONST 6" SD 9.2 LF
S=0.0100 FT/FT
N16500.17, E397186.48
CONST SD CB #2
RIM= 261.39
6"FL = 258.77
CONST 6" SD 55.7 LF
S=0.0500 FT/FT
N165046.59, E397243.49
CONST SD CB #1
RIM= 261.20
6"FL (IN-S) = 258.19
6"FL (OUT-N) = 255.19
CONST 6" SD 4.0 LF
S=0.0475 FT/FT
N164886.33, E397303.51
BEGIN TRENCH DRAIN (TD)
RIM= 261.67
TD FL = 261.17
CONST TD 80.0 LF
S=0.0100 FT/FT
N165046.76, E397307.44
START SWALE
FG = 261.45
CONST SWALE 63.0 LF
S=0.0040 FT/FT
N164036.86, E397209.99
START SWALE
FG = 261.30
CONST SWALE 32.5 LF
S=0.0031 FT/FT
N164965.99, E397248.05
CONST ROOF DOWNSPOUT
4"FL = 259.58
CONST 4" SD 6.4 LF
S=0.0200 FT/FT
N164886.00, E397248.05
CONST ROOF DOWNSPOUT
4"FL = 259.87
CONST 4" SD 6.4 LF
S=0.0200 FT/FT
N1648970.43, E397243.50
CONST SD CLEANOUT
RIM= 262.19
6"FL = 258.94
CONST 6" SD 6.1 LF
S=0.0100 FT/FT
N164970.38, E397301.82
CONST SD CLEANOUT
RIM= 262.19
6"FL = 260.27
CONST 6" SD 52.1 LF
S=0.0227 FT/FT
N165043.58, E397197.01
CONST SD CLEANOUT
RIM= 261.30
6"FL = 257.44
CONST 6" SD 28.9 LF
S=0.0200 FT/FT
N164888.32, E397243.49
CONST SD CLEANOUT
RIM= 261.57
6"FL = 259.76
CONST 6" SD 2.2 LF
S=0.0100 FT/FT
N164890.55, E397243.49
CONST 6"X4" WYE
4"&6"FL = 259.74
CONST 6" SD 79.9 LF
S=0.0100 FT/FT
N164976.57, E397243.50
CONST 6" WYE
6"FL = 258.88
CONST 6" SD 69.0 LF
S=0.0100 FT/FT N164970.38, E397249.69
CONST 6" 45° BEND
6"FL = 259.09
CONST 6" SD 8.8 LF
S=0.0239 FT/FT
N164890.55, E397243.49
CONST 6" WYE
6"FL = 255.99
CONST 6" SD 14.1 LF
S=0.0500 FT/FT
N165053.58, E397235.88
CONST 6" 45° BEND
6"FL = 255.28
CONST 6" SD 5.6 LF
S=0.0500 FT/FT
N165043.58, E397103.07
CONST SD CLEANOUT
RIM= 260.75
4"PERF FL = 259.60
CONST 4" PERF 90.9 LF
S=0.0030 FT/FT
N1645019.58, E397193.92
END 4" PERF
CONNECT TO 6" SD HEADER
4"PERF FL = 259.33
6"SD FL=258.79
CONST 6" SD 8.0 LF
S=0.0500 FT/FT
N1645019.58, E397193.92
END 4" PERF
CONNECT TO 6" SD HEADER
4"PERF FL = 259.33
6"SD FL=257.59
CONST 6" SD 3.1 LF
S=0.0500 FT/FT
N1645035.60, E397194.02
END 4" PERF
CONNECT TO 6" SD HEADER
4"PERF FL = 259.33
6"SD FL=257.99
CONST 6" SD 8.0 LF
S=0.0500 FT/FT
N1645027.58, E397193.92
END 4" PERF
CONNECT TO 6" SD HEADER
4"PERF FL = 259.33
6"SD FL=258.39
CONST 6" SD 8.0 LF
S=0.0500 FT/FT
N165035.58, E397103.07
CONST SD CLEANOUT
RIM= 260.75
4"PERF FL = 259.60
CONST 4" PERF 90.9 LF
S=0.0030 FT/FT
N165027.58, E397103.07
CONST SD CLEANOUT
RIM= 260.75
4"PERF FL = 259.60
CONST 4" PERF 90.9 LF
S=0.0030 FT/FT
N165019.58, E397103.07
CONST SD CLEANOUT
RIM= 260.75
4"PERF FL = 259.60
CONST 4" PERF 90.9 LF
S=0.0030 FT/FT
FUTURE ASPHALT
BASKETBALL
COURT AREA, TYP.
2 04/21/2026 ADDENDUM #2
3 05/05/2026 ADDENDUM #3
AutoCAD SHX Text
1 INCH = FT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1 C5.0
CIVIL DETAILS
5/ 1/
:3
3:
P M
74-23118-00
03/20/2026
C
EN
TE
N
N
IA
L M
ID
D
LE
S
C H
O O
L
- P
LA
Y
AR
EA
BID & PERMIT SET
REVISIONS
A B C D E F
C5.0
SO
U
TH
EA
ST
B R
O O
KL
YN
S
TR
EE
T
CE
NT
EN
NI
AL
S
CH
OO
L
DI
ST
RI
CT
EXPIRATION DATE: 06/30/26
91653PE
OREGON
ENG INEER
SEPT 13 , 20 16
A N
DREA W . STANCL
I F
F
RE
G I S
TERED PROFESS IONAL
1498 E. Main Street, Suite 103, #345
Cottage Grove, Oregon 97424 www.gaia-engineering.com
503-830-3635
PO
R
TL
AN
D , O
R
EG
O N
NO SCALE
TRENCHING & BACKFILL SECTION
TYPICAL
NO SCALE
STANDARD CLEANOUT (CO)
NO SCALE
TRENCH DRAIN (TD)
STANDARD
CURB
AT GRADE CURB
NO SCALE
AT GRADE CURB
6 NO SCALE
VALLEY GUTTER SECTION
NO SCALE
CATCH BASIN (CB)
SECTION A-A
NO SCALE
DRYWELL
NO SCALE
MOUNTABLE CURB
NO SCALE
MULCH AREA DRAINAGE SECTION
9 NO SCALE
GRASSY SWALE
3 05/05/2026 ADDENDUM #3
AutoCAD SHX Text NOTES 1. WATER LINES THAT PARALLEL SANITARY SEWER LINES SHALL BE LOCATED A MINIMUM OF 12" ABOVE WATER LINES THAT PARALLEL SANITARY SEWER LINES SHALL BE LOCATED A MINIMUM OF 12" ABOVE SEWER LINES, WHERE SERVICES ARE NOT HORIZONTALLY SEPARATED BY 10'. 2. WITHIN 5' OF A BUILDING STRUCTURE, BUILDING CODE APPROVED PIPE MATERIAL AND "-0 WITHIN 5' OF A BUILDING STRUCTURE, BUILDING CODE APPROVED PIPE MATERIAL AND "-0 34"-0 CRUSHED ROCK BACKFILL SHALL BE USED. 3. SAWCUT, REMOVE AND REPAIR EXISTING SURFACES TO MATCH EXISTING ASPHALT, CONCRETE, OR SAWCUT, REMOVE AND REPAIR EXISTING SURFACES TO MATCH EXISTING ASPHALT, CONCRETE, OR LANDSCAPING IN AREAS WHICH DO NOT RECEIVE NEW IMPROVEMENTS. PROVIDE 4" MIN DEPTH ASPHALT PAVEMENT, 4" MIN DEPTH CONCRETE PAVEMENT, OR MATCH EXISTING PAVEMENT DEPTH, WHICHEVER IS GREATER. 4. 36" MINIMUM FOR FIRE SERVICE PIPES UNDER AREAS TRAFFICKED BY VEHICLES. (NFPA 24, 10-4) 36" MINIMUM FOR FIRE SERVICE PIPES UNDER AREAS TRAFFICKED BY VEHICLES. (NFPA 24, 10-4) 5. INSTALL TRACER WIRE ON ANY PIPELINE(S) CONSTRUCTED OF NON-METALLIC PIPE MATERIAL.INSTALL TRACER WIRE ON ANY PIPELINE(S) CONSTRUCTED OF NON-METALLIC PIPE MATERIAL.
AutoCAD SHX Text
PAVED AND/OR SIDEWALK AREAS
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
PIPE OD
AutoCAD SHX Text
SS AND SD LINES-VARIES WATER LINES - 30" MIN SEE NOTE 4
AutoCAD SHX Text
PIPE OD
AutoCAD SHX Text 4"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
LANDSCAPED AREAS
AutoCAD SHX Text
REFER TO LANDSCAPE DRAWINGS FOR SURFACE TREATMENT SEE NOTE 3
AutoCAD SHX Text
AC PVMT AND BASE ROCK AS PER PLANS SEE NOTE 3
AutoCAD SHX Text 34"-0 CRUSHED ROCK IN PAVED, SIDEWALK, OR TRAFFIC AREAS, OR NATIVE MATERIALS IN LANDSCAPED AREAS. SEE NOTE 2
AutoCAD SHX Text
34"-0 CRUSHED ROCK
AutoCAD SHX Text
SEE NOTE 2
AutoCAD SHX Text
UNDISTURBED EARTH
AutoCAD SHX Text NOTES 1. TRACER WIRE SHALL ENTER STRUCTURE WITH RISER PIPE. PROVIDE ENOUGH FREE WIRE TO TRACER WIRE SHALL ENTER STRUCTURE WITH RISER PIPE. PROVIDE ENOUGH FREE WIRE TO EXTEND 24" ABOVE FINISHED GRADE TO FACILITATE TESTING. VERIFY FREE END OF WIRE IS WITHIN EASY REACH OF OPENING IN TOP SECTION. 2. RISER PIPE SIZE: RISER PIPE SIZE: 4", 6", AND 8" DIA MAIN - 4" DIA RISER PIPE 10" DIA AND LARGER MAIN - 6" DIA RISER PIPE. 3. ADJUST END OF RISER PIPE TO MAINTAIN 3" MIN AND 6" MAX CLEARANCE BETWEEN END PIPE ADJUST END OF RISER PIPE TO MAINTAIN 3" MIN AND 6" MAX CLEARANCE BETWEEN END PIPE AND BOTTOM OF VALVE BOX LID.
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
UTILITY MAIN PIPE EXTENSION AS REQD SEE PLAN FOR PIPE LOCATION, DIA AND SLOPE
AutoCAD SHX Text
MECHANICAL PLUG (AT PIPE END ONLY)
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text CAST IRON VALVE BOX TOP SECTION AND COVER. SLIP TYPE WITH TOP FLANGE. HEAVY DUTY IN PAVEMENT AREAS. COVER MARKED PER SPECIFICATIONS
AutoCAD SHX Text
SET TOP TO MATCH FINISHED GRADE
AutoCAD SHX Text
6" MIN THK CRUSHED ROCK BACKFILL UNDER VALVE BOX IN LANDSCAPED AREAS
AutoCAD SHX Text
MECHANICAL PLUG
AutoCAD SHX Text
RISER SECTION LENGTH AS REQD SEE NOTE 2
AutoCAD SHX Text
45° BEND
AutoCAD SHX Text PE x PE EXTENSION
AutoCAD SHX Text
LATERAL CONNECTION TO MAIN - SIZES PER PLAN
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
WYE
AutoCAD SHX Text
10" MIN
AutoCAD SHX Text
SEE NOTE 3
AutoCAD SHX Text
HORIZONTAL AND VERTICAL LOCATION AS SHOWN ON PLANS
AutoCAD SHX Text NOTES 1. TRACER WIRE SHALL ENTER STRUCTURE AT PIPE INLET OR OUTLET. PROVIDE ENOUGH TRACER WIRE SHALL ENTER STRUCTURE AT PIPE INLET OR OUTLET. PROVIDE ENOUGH FREE WIRE TO EXTEND 24" ABOVE TOP OF GRATE TO FACILITATE TESTING. COIL WIRE AND SECURE WITH NON-CORROSIVE FASTENER 2" UNDER FRAME. 2. CONSTRUCT CONCRETE ENCASEMENT PER MANUFACTURER RECOMMENDATIONS. PROVIDE CONSTRUCT CONCRETE ENCASEMENT PER MANUFACTURER RECOMMENDATIONS. PROVIDE TOOLED TRANSVERSE CONTRACTION JOINTS AT TOP AND SIDES OF CONCRETE ENCASEMENT AT CHANNEL JOINT LOCATIONS PER MANUFACTURER RECOMMENDATIONS. 3. GRATE SHALL BE SLOTTED, HEEL PROOF, ADA COMPLIANT, CLASS B. GRATE SHALL BE SLOTTED, HEEL PROOF, ADA COMPLIANT, CLASS B.
AutoCAD SHX Text 8"
AutoCAD SHX Text 8"
AutoCAD SHX Text
12" MIN
AutoCAD SHX Text 6"
AutoCAD SHX Text 12"
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text 6"
AutoCAD SHX Text 1"
AutoCAD SHX Text
AC PVMT AS PER PLANS TYP
AutoCAD SHX Text
COMPACTED ROCK BASE
AutoCAD SHX Text
CURB BACKFILL AND SURFACE TREATMENT AS PER PLANS
AutoCAD SHX Text
34" RAD TYP
AutoCAD SHX Text
EXPANSION/CONTRACTION JOINT - SEE NOTE 1
AutoCAD SHX Text
ASPHALT AS PER PLANS
AutoCAD SHX Text 8"
AutoCAD SHX Text
12" MIN
AutoCAD SHX Text NOTES 1. EXPANSION JOINTS IN NON-EXTRUDED CURB. CONTRACTION JOINTS IN EXTRUDED EXPANSION JOINTS IN NON-EXTRUDED CURB. CONTRACTION JOINTS IN EXTRUDED CURB. 2. EXPANSION JOINTS SHALL BE PLACED EVERY 15' IN NON-EXTRUDED CURB AND EXPANSION JOINTS SHALL BE PLACED EVERY 15' IN NON-EXTRUDED CURB AND GUTTER. CONTRACTION JOINTS SHALL MATCH SIDEWALK CONTRACTION JOINTS.
AutoCAD SHX Text
COMPACTED ROCK BASE
AutoCAD SHX Text
APPLY TACK COAT TO EDGE OF CONCRETE PRIOR TO PLACEMENT OF NEW PAVEMENT TYP
AutoCAD SHX Text
PCC CONCRETE
AutoCAD SHX Text 30"'
AutoCAD SHX Text 15"
AutoCAD SHX Text 15"
AutoCAD SHX Text 1"
AutoCAD SHX Text 7"
AutoCAD SHX Text
6" MIN
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
DUCTILE IRON, SCHEDULE 40, OR C900 PVC PIPE AND FITTINGS
AutoCAD SHX Text
PVC PIPE
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
6" MIN
AutoCAD SHX Text NOTES 1. TRACER WIRE SHALL ENTER STRUCTURE AT PIPE INLET OR OUTLET. PROVIDE TRACER WIRE SHALL ENTER STRUCTURE AT PIPE INLET OR OUTLET. PROVIDE ADEQUATE FREE WIRE TO EXTEND 24" ABOVE TOP OF GRATE TO FACILITATE TESTING. COIL WIRE AND SECURE WITH NON-CORROSIVE FASTENER 2" UNDER FRAME. 2. LOCATION SPECIFIED ON PLAN INDICATES CENTER OF GRATED SECTION OF LOCATION SPECIFIED ON PLAN INDICATES CENTER OF GRATED SECTION OF BASIN, FACE OF CURB AT CENTER OF GRATED SECTION, OR INTERSECTION BETWEEN FACE OF CURBS. 3. ALL STRUCTURES SHALL BE PROVIDED WITH HEAVY DUTY GRATE WITH ALL STRUCTURES SHALL BE PROVIDED WITH HEAVY DUTY GRATE WITH BICYCLE BARS
AutoCAD SHX Text
RIM SET TO FINISHED GRADE
AutoCAD SHX Text
STRUCTURE GRATE SEE NOTE 3
AutoCAD SHX Text
FLEX-TRANSITION COUPLER
AutoCAD SHX Text
FLEX-TRANSITION COUPLER
AutoCAD SHX Text
PROJECTED FLOWLINE AS INDICATED ON PLAN
AutoCAD SHX Text
24" SQUARE CHAMBER WITH SUMP
AutoCAD SHX Text
SET BASIN ON COMPACTED CRUSHED ROCK BASE
AutoCAD SHX Text 24"
AutoCAD SHX Text
HINGED ACCESS COVER
AutoCAD SHX Text
PE X PE EXTENSION LENGTH AS REQUIRED
AutoCAD SHX Text
45° BEND
AutoCAD SHX Text
45° BEND
AutoCAD SHX Text 6"
AutoCAD SHX Text
GRASS SEEDED AREA PER LANDSCAPE DRAWINGS
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
ISOLATION JOINT AND SEALANT, BOTH SIDES OF ENCASEMENT
AutoCAD SHX Text
3000 PSI CONCRETE ENCASEMENT SEE NOTE 2
AutoCAD SHX Text
COMPACTED CRUSHED ROCK BASE
AutoCAD SHX Text
APPROVED SUBGRADE
AutoCAD SHX Text
TRENCH DRAIN WITH FRAME AND GRATE AS SPECIFIED SEE NOTE 3
AutoCAD SHX Text
ASPHALT CONCRETE PAVEMENT SECTION PER PAVING PLAN
AutoCAD SHX Text
12" MIN
AutoCAD SHX Text
1" RADIUS
AutoCAD SHX Text 12"
AutoCAD SHX Text NOTES 1. REFER TO ODOT STANDARD DRAWING RD700, REFER TO ODOT STANDARD DRAWING RD700, CURBS, TYPE "B" MOUNTABLE CURB
AutoCAD SHX Text 1"
AutoCAD SHX Text 4"
AutoCAD SHX Text 8"
AutoCAD SHX Text
4" MIN
AutoCAD SHX Text
COMPACTED ROCK BASE
AutoCAD SHX Text
AC PAVEMENT SECTION AS SPECIFIED
AutoCAD SHX Text
SURFACE TREATMENT AS SPECIFIED
AutoCAD SHX Text 48"
AutoCAD SHX Text
DRYWELL FULL DEPTH= 20'
AutoCAD SHX Text
PERFORATED BARREL DEPTH 15'
AutoCAD SHX Text
EL=240.55'
AutoCAD SHX Text
EL=117.95'
AutoCAD SHX Text
EL=241.22'
AutoCAD SHX Text
RIM=261.22'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 12"
AutoCAD SHX Text 12"
AutoCAD SHX Text
AutoCAD SHX Text
3" MIN, 12" MAX
AutoCAD SHX Text
6" SD FL= 255.00'
AutoCAD SHX Text
6" SD FL= 255.00'
AutoCAD SHX Text 8"
AutoCAD SHX Text
SET DRYWELL ON COMPACTED CRUSHED ROCK BASE
AutoCAD SHX Text NOTES 1. ALL PRECAST CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF THE CITY OF GRESHAM ALL PRECAST CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF THE CITY OF GRESHAM MANUFACTURING STANDARDS FOR PRECAST CONCRETE PRODUCTS, AS REVISED. 2. CAST-IN-PLACE CONCRETE SHALL BE STRUCTURAL CONCRETE HAVING A MINIMUM CAST-IN-PLACE CONCRETE SHALL BE STRUCTURAL CONCRETE HAVING A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 4,000 PSI. 3. ALL CONNECTING PIPE SHALL HAVE A FLEXIBLE JOINT WITHIN 18" OF OUTSIDE WALL OF DRYWELL. ALL CONNECTING PIPE SHALL HAVE A FLEXIBLE JOINT WITHIN 18" OF OUTSIDE WALL OF DRYWELL. 4. INLET LEADS SHALL BE CONNECTED 6' BELOW RIM OR 14" ABOVE LOWEST PIPE INVERT, UNLESS SHOWN INLET LEADS SHALL BE CONNECTED 6' BELOW RIM OR 14" ABOVE LOWEST PIPE INVERT, UNLESS SHOWN OTHERWISE ON THE PLANS. IN ALL CASES INLET LEADS SHALL BE CONNECTED BELOW THE CONE SECTION, A MINIMUM OF 8" CLEAR OF A PRECAST SECTION JOINT AND 12" CLEAR OF JOINT IN BASE SECTION. 5. ALL PIPING TO AND FROM PRECAST DRYWELL SHALL HAVE AT LEAST 8" OF 1-1/2" MINUS CLEAN ROCK ALL PIPING TO AND FROM PRECAST DRYWELL SHALL HAVE AT LEAST 8" OF 1-1/2" MINUS CLEAN ROCK COVER CONTINUOUSLY AROUND PIPE WHERE DRAIN ROCK WOULD OTHERWISE BE IN CONTACT WITH PIPE. 6. ANY PROTRUDING ENDS OF PIPES SHALL BE TRIMMED FLUSH WITH THE INSIDE WALLS AND GROUTED.ANY PROTRUDING ENDS OF PIPES SHALL BE TRIMMED FLUSH WITH THE INSIDE WALLS AND GROUTED.
AutoCAD SHX Text
12" DEEP WASHED DRAIN ROCK, "-0 TO 2 "-0 34"-0 TO 2 "-0 12"-0 UNIFORMLY GRADED
AutoCAD SHX Text
PREPARED SUBGRADE
AutoCAD SHX Text 12" FIBER MULCH LAYER IN SWINGSET AREA. REFER TO LANDSCAPE ARCHITECT PLANS FOR DETAILS
AutoCAD SHX Text
4" PERFORATED PVC DRAIN PIPE PER PLAN, TYP.
AutoCAD SHX Text
GEOTEXTILE SEPARATION FABRIC TO BE WRAPPED AROUND ENTIRE DRAIN ROCK AREA
AutoCAD SHX Text
34"-0" TO 2 "-0" 12 "-0" UNIFORMLY GRADED WASHED DRAIN ROCK
AutoCAD SHX Text 6.83'
AutoCAD SHX Text 3'±
AutoCAD SHX Text
1' MINIMUM
AutoCAD SHX Text
4:1 MAXIMUM
AutoCAD SHX Text
4:1 MAXIMUM
AutoCAD SHX Text
GRASSY SWALE 3"± DEPTH. LONGITUDINAL SLOPE PER PLANS
AutoCAD SHX Text
TOPSOIL PER LANDSCAPE PLANS
PREPARED SUBGRADE
LANDSCAPE NOTES:
1. CONTRACTOR SHALL VERIFY LOCATION OF ALL UTILITIES
BEFORE STARTING ANY WORK.
2. EXISTING UNDERGROUND (U/G) UTILITIES AND DRAINAGE
STRUCTURES HAVE BEEN PLOTTED FROM AVAILABLE
INFORMATION AND THEREFORE, THEIR LOCATIONS MUST
BE CONSIDERED APPROXIMATE ONLY. IT IS THE
RESPONSIBILITY OF THE INDIVIDUAL CONTRACTORS TO
NOTIFY THE UTILITY COMPANIES TO LOCATE UTILITIES
BEFORE ACTUAL CONSTRUCTION.
3. THE CONTRACTOR WILL SHOW PROOF OF PROCUREMENT,
SOURCES, QUANTITIES AND VARIETIES FOR ALL SHRUBS,
PERENNIALS, ORNAMENTAL GRASSES, AND ANNUALS.
4. SUBSTITUTIONS WILL BE ALLOWED ONCE THE
CONTRACTOR HAS EXHAUSTED ALL SOURCES FOR THE
SPECIFIED MATERIAL, AND HAS PROVEN THAT THE
SPECIFIED MATERIAL IS NOT AVAILABLE. THE CONTRACTOR
MUST PROVIDE NAME AND VARIETY OF SUBSTITUTION IN
THE SUBSTITUTION REQUEST FORM TO THE LANDSCAPE
ARCHITECT FOR APPROVAL PRIOR TO TAGGING OR
PLANTING. SUBSTITUTIONS WILL BE NEAREST EQUIVALENT
SIZE OF VARIETY OF PLANT HAVING SAME ESSENTIAL
CHARACTERISTICS.
5. SIZE AND QUALITY OF PLANT MATERIAL WILL CONFORM TO
AMERICAN STANDARDS FOR NURSERY STOCK, ANSI
260-1992, OR MOST RECENT EDITION.
6. ALL PLANT MATERIAL WILL BE NURSERY GROWN, SOUND,
HEALTHY, VIGOROUS AND FREE FROM INSECTS, DISEASE
AND INJURIES, WITH HABIT OF GROWTH THAT IS NORMAL
FOR THE SPECIES. SIZES WILL BE EQUAL TO OR
EXCEEDING SIZES INDICATED ON THE PLANT LIST. THE
CONTRACTOR WILL SUPPLY PLANTS IN QUANTITY AS
SHOWN ON THE DRAWINGS.
7. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING
POSITIVE SURFACE DRAINAGE IS PROVIDED IN ALL
PLANTING AND TURF AREAS. ALL GRADE SURFACES WILL
BE FINISHED TO UNIFORM GRADES AND SLOPED IN SUCH A
MANNER TO BE FREE OF DEPRESSIONS THAT CAUSE AREAS
OF STANDING WATER. THE CONTRACTOR WILL REPORT
ANY CONFLICTS WITH THIS REQUIREMENT TO THE
LANDSCAPE ARCHITECT/OWNER FOR RESOLUTION PRIOR
TO FINAL OPERATIONS.
8. THE CONTRACTOR WILL REPORT SUB-SURFACE SOIL OR
DRAINAGE ISSUES TO THE LANDSCAPE ARCHITECT.
9. CONTRACTOR SHALL STAKE PLANT LOCATIONS IN THE
FIELD AND HAVE APPROVAL BY THE LANDSCAPE
ARCHITECT BEFORE PLANT PITS ARE EXCAVATED AND
BEFORE PROCEEDING WITH INSTALLATION.
10. TREES, SHRUBS & GROUND COVERS SHALL BE LAID OUT IN
A UNIFORM AND CONSISTENT PATTERN.
11. CONTRACTOR TO PLACE MULCH AROUND ALL TREES AND IN
ALL PLANTING BEDS UNLESS OTHERWISE NOTED, TO A
DEPTH OF 3" OR AS DESCRIBED IN THE SPECIFICATIONS.
ALL PLANTING BEDS TO BE SEPARATED FROM LAWN AREAS
WITH SPECIFIED EDGING OR CONCRETE CURB EDGE PER
DRAWINGS.
12. ELEVATION OF TOP OF MULCH SHALL BE 1/2" MIN. BELOW
ANY ADJACENT PAVEMENT OR 2" min. BELOW FINISHED
FLOOR ELEVATION.
13. ALL SHRUB BEDS SHALL BE MULCHED WITH SPECIFIED
ORGANIC OR DECORATIVE AGGREGATE MULCH AND
SEPARATED FROM LAWN AREAS WITH SPECIFIED EDGING
OR CONCRETE CURB EDGE PER DRAWINGS.
14. CONTRACTOR SHALL FINE GRADE AND SEED ALL AREAS
DISTURBED DURING CONSTRUCTION AND ESTABLISH NEW
LAWN AREA, NOT DESIGNATED FOR SOD, NATIVE MEADOW,
OR PLANTING BEDS. CONTRACTOR TO SEED ALL AREAS
WITHIN CONTRACT LIMITS NOT COVERED BY PAVING,
BUILDINGS, OR PLANTING BEDS UNLESS OTHERWISE
NOTED.
15. CONTRACTOR SHALL BE RESPONSIBLE FOR CALCULATING
ACTUAL AREAS OF SEED AND QUANTITIES REQUIRED FOR
COVERAGE.
16. ALL PLANT MATERIALS DELIVERED TO THE SITE FOR
APPROVAL AND INSTALLATION SHALL BE IDENTIFIED AND
TAGGED, TO ENSURE THE PLANTS PROVIDED ARE AS
SPECIFIED. PLANTS SHALL BE APPROVED BY THE
LANDSCAPE ARCHITECT PRIOR TO INSTALLATION.
17. ALL TREES SHALL BE CALLIPERED AND UNDERSIZED TREES
SHALL BE REJECTED.
18. PLANT QUANTITIES ARE PROVIDED FOR CONTRACTOR
CONVENIENCE ONLY. PROVIDE AND INSTALL ALL PLANTS
SHOWN ON THE PLANTING PLANS.
19. SPACING OF ALL PLANTINGS TO BE AS SHOWN ON PLANS.
20. ALL LANDSCAPE AREAS AND PLAYING FIELD AREAS TO
HAVE A MINIMUM OF 6" TOPSOIL.
21. ALL TURF AREAS TO HAVE 4” MINIMUM OF IMPORTED
TOPSOIL - SEE SPECS FOR SOIL AMENDMENTS.
22. PROVIDE, INSTALL, AND INCORPORATE SOIL AMENDMENTS
PER RECOMMENDATIONS PER THE SOILS REPORT.
LEGEND
KENTUCKY BLUEGRASS HYDROSEED
WOOD FIBER MULCH
REF: SPECS
ASPHALT; REF: CIVIL
NOTE:
FINE GRADE & SOD ONLY IN AREAS DISTURBED
AeccDbGeneralLabel (AeccLand130)
DW
CB
CO
PLAY
STRUCTURE
FUTURE
COURT,
NOT IN
CONTRACT
BASKETBALL
COURT
LIMIT OF WORK
LIMIT OF WORK
VOLLEYBALL VOLLEYBALL
ENG WOOD FIBER
OVERHEAD PLAY STRUCTURE;
BY OTHERS, NOT IN CONTRACT
BED EDGER
LIND
P:
\P
D X\
-2
-0 0\
^d w g\ La
\L 3.
PL
AN
TI
N G
P
LA
N .d w g
M ay
4, 9:
am m cr ow no ve r
OVERALL LAYOUT PLAN
SCALE:
20' 40'10'5'0' 1"=20'
REVISIONS
D
LR
G ro up
A B C D E F
MARCH 20, 2026
BID & PERMIT
SET
C en te nn ia l M
S Pl ay gr ou nd
R en ov at io n
C en te nn ia l M
S Pl ay gr ou nd
R en ov at io n
SE
B ro ok ly n St
, P or tla nd
, O R
CE
NT
EN
NI
AL
S
CH
OO
L
DI
ST
RI
CT
74-26104-00
L3.1
LANDSCAPE
PLANTING PLAN
PLANT & GROUNDCOVER SCHEDULE
ADDENDUM 02 04.21.2026
ADDENDUM 03 05.05.2026
AutoCAD SHX Text
6.0' CHAINLINK FENCE AND 6.0' WOODEN FENCE
AutoCAD SHX Text
AC
AutoCAD SHX Text
AC
AutoCAD SHX Text
RAMBLEWOOD BLOCK 2
EXTRUDED CURB ON AC
NOTES:
1. PROVIDE 1% (1/8" PER FOOT) CROSS SLOPE FOR POSITIVE
DRAINAGE UNLESS OTHERWISE INDICATED.
2. PROVIDE 3000 PSI CONC AT 28 DAYS.
3. 2% MAX. CROSS SLOPE
#3 BAR @ 18" O.C.E.W.
#4 BAR, CONT.
1/4" RADIUS TOOLED
EDGE
8"
2"
8"
COMPACTED
SUBGRADE
REF: GEOTECH
REPORT
CONC PAVING
REF: LANDSCAPE PLANS FOR FINISH
SAW JOINT, 3/8" DEEP & 1/8" WIDE
REF: PLAN FOR LOCATION
4"
4"
1/4" EXP. JT.
SEALANT, COLOR TO
MATCH CONC
BOND BREAKER AS
REQUIRED
PRE-MOLDED
FIBERBOARD W/
REMOVABLE SEALANT
STRIP
1/16" RADIUS TYP.
SPEED DOWEL SLEEVE
REINFORCING ROD DOWEL
#4x24" @ 18" O.C.
FLUSH
8"
CONC PAVING REINFORCE
#3 @ 18" O.C.
OR PER ENGINEER DWG.
COMPACTED SUBGRADE
AND BASE
REF: GEOTECH REPORT
CONC WALK
REF: LANDSCAPE
PLANS FOR FINISH
1"
4"
TYP.
SCALE: NTS
REFER TO PLAN
FOR LOCATION
FLUSH
4"
VARIES
1/4" CONTROL JOINT
SAWCUT JOINT
(25% OF SLAB
THICKNESS)
CONC PAVING
REINFORCE #3
@ 18" O.C. OR
PER ENGINEER
DWG.
COMPACTED
SUBGRADE BASE
REF: GEOTECH
REPORT
REFER TO PLAN
FOR LOCATION
COMPACTED SOIL/PLANTING MIX
UNDISTURBED SUBGRADE
2-3x WIDER
THAN ROOTBALL
EXCAVATE TREE PIT 2 TIMES
ROOTBALL DIAMETER
TREE BACKFILL MIX
REF: SPECS
UNDISTURBED SUBGRADE
SCARIFY EDGE OF TREE PIT.
NO SMOOTH OR COMPACTED
SURFACES.
FINISHED GRADE
ROOTBALL
3" MULCH LAYER
REF: SPECS
ROOT ANCHOR™ UNDERGROUND
TREE STAKING SYSTEM
TOP OF ROOTBALL TO BE 2"
ABOVE FINISHED GRADE
DO NOT CUT OR DAMAGE THE
CENTRAL LEADER
3" HIGH WATER RETENTION BASIN
4" DIA. INSPECTION TUBE;
CUT 1'-0" ABOVE FINISHED
GRADE AND CAP W/ 4" DIA.
DRAIN GRATE COVER
NOTES:
1. ONLY STAKE TREES THAT ARE NOT
CAPABLE OF STANDING UPRIGHT
WITHOUT FALLING OR LEANING.
2. INSTALL INSPECTION TUBES AND
TREE TIES. REF. MANUFACTURER'S
SPECIFICATIONS.
3. REMOVE ALL ROPES, WIRES AND
CONTAINERS PRIOR TO PLANTING. IF
BALL AND BURLAP, REMOVE TOP 1/3
OF BURLAP.
4. REF. PLANTING SPECIFICATIONS
FOR MORE INFORMATION.
WEED BARRIER FABRIC
NOTES:
1. INSTALL CHEMICAL WEED BARRIER OVER SOIL UNDER ENG WOOD FIBER,
FOLLOWING PLANTING AND OVER ALL FINISH MULCH AREAS.
2. INSTALL BED EDGER BETWEEN ALL WOOD FIBER MULCH AND ADJACENT TURF OR
PLANTING BED.
3. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
COMPACTED SUBGRADE
REF: GEOTECH REPORT
PVC FLEXIBLE EDGER, BY OLY-OLA
EDGINGS, INC., REF: SPECS
FINISH GRADE
PROVIDE 12" LENGTH GALV STL
STAKE AT 24" OC, MIN
UNDISTURBED SOIL
1'
-0
ENG WOOD FIBER
RE: SPECS
6" MIN. OVERLAP
6"
10' CENTER OF POST TO CENTER OF POST (MAX)
POST CAP
H T.
V
AR
IE
S.
SE
E
PL
AN
S
2" MAX.
"A"
CONCRETE
FOOTING
POST
(OD)
2.875"
4.000"
GATE
3' TO 6'
7' TO 12'
3' TO 5'
6' TO 9'
10' TO 12'
3' TO 5'
6' TO 9'
10' TO 12'
12" 14" 16" 14" 16" 18"
42" 46" 42" 42" 46"
40" 44" 48" 40" 44" 48"
42"
LINE AND TERMINAL POSTS
FABRIC
HEIGHT
"C" "B"
FABRIC
HEIGHT
"A"
DIAM
"B"
DEPTH
POST
EMBEDLEAF
WIDTH
GATE
38" 38" 38" 38" 38" 38" 52"
"C" MIN.
FOOTING DEPTH
KNUCKLED SELVAGE TOP
1.66" TOP RAIL
2.375 MIN. DIA.
OF POST AS
SPECIFIED
38"
TENSION WIRE
TOP OF FINISH GRADE
SET IN 2-1/2" Ø BORED
HOLES 8" DEEP. FILL
WITH NON-SHRINK
GROUT
12" 12" 12" 12" 12" 18" 18"
12"
"B" POST
DEPTH
"A"
DIAM
TYPE
POST
3'-0" TO 4'-0"
5'-0"
6'-0" TO 9'-0"
10'-0" TO 12'-0"
LINE
TERMINAL
LINE
TERMINAL
LINE
TERMINAL
LINE
TERMINAL
GATE POST
NOTE:
TERMINAL POSTS INCLUDE END, CORNER
AND PULL POSTS
CLCL
CL
CL
36" 36" 36" 36" 36" 36" 36" 48"
12" WIDE x 6" DEEP
CONC CURB, LIGHT
BROOM FINISH
FINISH GRADE
SLOPE
C O
F
FE
N C
E L
1/4" CONT. TOOLED RADIUS
CONC FOOTING
FOR FENCE
POST, BEYOND
COMPACTED SUBGRADE
REF: GEOTECH REPORT
(2) - #4 BARS, CONT.
SAW CUT AT MID POINT
FOOTING, BEYOND GRADE
EXPANSION JOINT
AT FOOTING, TYP.
PLAN (NOT TO SCALE)
SECTION
WRAP FENCE POSTS WITH BUILDING
FELT AS BOND BREAKER.
1'-0"
6"
10'-0" MAX. SPACING
2'-6" MIN.
NOTE:
INSTALL REINFORCED CONCRETE FOOTING
AND GOAL POST PER DELEGATED DESIGN BY
MANUFACTURER.
2'-6" MIN.
1/2" EXPANSION JOINT
ASPHALT PAVING
RE: CIVIL
COMPACTED SUBBASE TYP.
BASKET GOAL POST
(4) - #5 BARS
VERTICAL &
HORIZONTAL
@ 12" O.C.
6"
5'-0"
MIN.
BASKET
GOAL POST
MOUNT
PLATE
(4) J BOLTS
R6'
1'-6" 3' 2"2"
3' 2"
3' 1'
3' 2"
4'-21 2"
4'-0"
19'-9"
5'-71 2"
39'-6"
47'-01 2"
BASKETBALL GOAL
POST
REF: SPECS
STRIPING SHALL BE
2" WIDE, TYP.
STRIPING SHALL BE
2" WIDE x 8" DEEP, TYP.
STRIPING SHALL BE
12" WIDE x 8" DEEP, TYP.
BASKETBALL COURT
VOLLEYBALL/ PICKLE BALL COURT
20'
10'
STRIPING SHALL BE
2" WIDE (TYP.)
LINE PAINT, TYP.
SUBMIT PRODUCT
DATA FOR
APPROVAL.
44'
15' 7' NET AREA
(FILLED) FIXED VOLLEYBALL NET POST LOCATION, TYP;
POST BETWEEN TWO COURTS TO BE SHARED; REF: SPECS
(OPEN) REMOVABLE PICKLEBALL NET POST LOCATION, TYP; REF: SPECS & MFR RECS
22' O.C.
24' O.C.
CL
CL
R6'
CL CL CL CL
R2'-6"
3/4" PLUNGER ROD INTO
CONC. KEEPER IN TURF
AREAS
CONC. FOOTING W/ 1" S.S.
SLEEVE IN TURF AREAS;
SLOPE TOP OF FOOTING TO
DRAIN WATER AWAY FROM
SLEEVE
PE
R
E
LE
V
5'-0" CLEAR OPENING
2" LC
"C " R
E:
T
AB
LE
E/
L5 .3
HEAVY-DUTY LATCH
WITH LOCKABLE HASP;
OWNER PROVIDED
PAD-LOCK
3/4" PLUNGER WITH KEEPER
STL RODS
2"
3" DIA X 12 GA.
POST WITH CAP
H T.
V
AR
IE
S.
SE
E
PL
AN
S
2" HC
2" LC
2" HC
NOTES:
1. PROVIDE CAPABILITY FOR GATE TO BE SECURED IN BOTH
OPEN AND CLOSED POSITIONS.
2. PROVIDE 2 1/2" KEEPER POSTS FOR GATE IN OPEN POSITION
OPPOSITE GATE LEAF
CONC FOOTING FOR POST
REF: MFR RECOMMENDATIONS
6" DEPTH CONCRETE
MAINTENANCE STRIP
REF: 4E/L5.1
EXP. JOINT
NOTES:
1. FOOTING WIDTH TO BE (4)X POST WIDTH.
2. GALVANIZED CHAIN LINK FENCE, COLOR BLACK; RE: SPECS 1-3/4" Ø X 14 GA. GATE END
TUBULAR RAIL
1-1/2" x 1-1/2" x 14 GA.
GALVANIZED CHAIN LINK
3" Ø X 12GA. POST
SELF CLOSING
SPRING-LOADED GATE
HARDWARE: SGXSX3
CLAMP-TYPE HINGE
PANIC HARDWARE BAR.
SUBMIT SHOP DRAWINGS &
SPECS.
PROVIDE PERFORATED
METAL AT GATE AND
MINIMUM 4' PAST GATE
POST. SUBMIT SHOP
DRAWINGS & SPECS.
2"
5-1/2"
1-1/8"
2"
SEE PLAN
2"
36" MIN
5' -1
0"
6'-0"
3'-4"
KEY
1 2
LANDSCAPE
DETAILS
L5.1
CONCRETE WALK, TYP
L5.1 1A
SCALE: 1"=1'-0" SECTION
EXPANSION JOINT W/ DOWEL
SCALE: 1"=1'-0"
L5.1
1B CONTROL JOINT
SCALE: 1"=1'-0"
L5.1 1D
SECTION SECTION
DECIDUOUS TREE PLANTING
L5.1 5A
SCALE: 1 1/2"=1'-0" SECTION
BED EDGER AT SWING STATION
L5.1 1E
SCALE: 1"=1'-0" SECTION
REVISIONS
D
LR
G ro up
A B C D E F
MARCH 20, 2026
BID & PERMIT
SET
C en te nn ia l M
S Pl ay gr ou nd
R en ov at io n
C en te nn ia l M
S Pl ay gr ou nd
R en ov at io n
SE
B ro ok ly n St
, P or tla nd
, O R
CE
NT
EN
NI
AL
S
CH
OO
L
DI
ST
RI
CT
74-26104-00
6'-0" CHAIN LINK FENCE, TYP
L5.1 3A
SCALE: 1"=1'-0" SECTION
CONC MOW STRIP AT FENCE
L5.1 4E
SECTIONSCALE: 1"=1'-0"
BASKETBALL POLE
L5.1 5E
NO SCALE SECTION
COURT STRIPING
L5.1 5B
5'-0" CHAIN LINK UTILITY GATE, TYP
L5.3 3C
SCALE: NO SCALE
4'-0" CHAIN LINK PEDESTRIAN GATE
L5.3 3D
SCALE: NO SCALE
SCALE: 1 1/2"=1'-0" SECTION
ADDENDUM 02 04.21.2026
ADDENDUM 03 05.05.2026
File details come from the government source that posted it. Updated .