This is a technical drawings file for an Invitation for Bid (IFB) related to the replacement of six air handling units (AHUs) at the Northern Virginia Mental Health Institute (NVMHI), located at 3302 Gallows Rd, Falls Church, Virginia. The project involves the Phase 1 design and installation of replacement AHUs at the facility. A mandatory pre-bid conference is scheduled for October 13, 2026, at 11:00 AM at the site location. Attendance at the pre-bid conference is required for all bidders submitting proposals. The sealed bid submission deadline and contract award date are not specified in this file; however, the drawings serve as essential technical documentation defining the scope of work, specifications, and installation requirements for the six replacement units.
The file contains architectural and mechanical drawings that establish the technical parameters, dimensions, and integration requirements for the AHU replacement project. Pricing terms, set-asides, incumbent contractor information, and funding sources are not addressed in this technical drawings document. Bidders should refer to the IFB notice and associated bid documents for complete information regarding cost requirements, evaluation criteria, contract terms, and submission procedures.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I-66
R O U
TE
ROUTE 50
ROUTE 236 I-
R O U
TE
R O U T E
PROJECT SITE
PROJECT
SITE
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
DBHDS NORTHERN VIRGINIA
MENTAL HEALTH INSTITUTE
NVMHI AHU REPLACEMENT, PHASE 1
IFB SUBMITTAL
3302 GALLOWS RD,
FALLS CHURCH, VA 22042
WILEY | WILSON: PROJECT INFORMATION:
PROJECT CODE: 720-10800-28-12
VICINITY MAP LOCATION MAP
SEPTEMBER 30, 2026
CLIENT:
PROGRAM MANAGER:
OFFICE:
EMAIL:
PROJECT MANAGER:
OFFICE:
EMAIL:
SHAWN GORE
804-539-2011
SHAWN.GORE@DBHDS.VIRGINIA.GOV
RAYMOND P. BALOG III, PE
804-200-1715
RBALOG@WILEYWILSON.COM
SHEET INDEX:
G-001 G-002 M-001 M-101 M-102
MD401
MD402
MD403
MD404
MD405
MD406
M-401 M-402 M-403 M-404 M-405 M-406 M-501 M-502 M-503 M-601 M-602
COVER SHEET
PHASING PLAN
LEGEND, ABBREVIATIONS, & GENERAL NOTES
FIRST FLOOR OVERALL
ROOF OVERALL
DEMOLITION - FIRST FLOOR - AHU-6
DEMOLITION - FIRST FLOOR - AHU-7
DEMOLITION - FIRST FLOOR - AHU-9
DEMOLITION - FIRST FLOOR - AHU-35
DEMOLITION - ROOF - AHU-33
DEMOLITION - ROOF - AHU-34
FIRST FLOOR - AHU-6 ENLARGED PLANS
FIRST FLOOR - AHU-7 ENLARGED PLANS
FIRST FLOOR - AHU-9 ENLARGED PLANS
FIRST FLOOR - AHU-35 ENLARGED PLANS
ROOF - AHU-33 ENLARGED PLANS
ROOF - AHU-34 ENLARGED PLANS
DETAILS
DETAILS
DETAILS
SCHEDULES
SCHEDULES
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
FUNCTION OF BUILDING:
MENTAL HEALTH HOSPITAL
GOVERNING CODES:
• CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL (CSPM) 2026, REV 0 - 7/31/2026
• VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) 2021
• VIRGINIA EXISTING BUILDING CODE, 2021
• VIRGINIA STATEWIDE FIRE PROTECTION CODE, 2021
• VIRGINIA MECHANICAL CODE, 2021
• VIRGINIA PLUMBING CODE, 2021
• NATIONAL ELECTRICAL CODE, 2020
HPBA COMPLIANCE STATEMENT:
IN ACCORD WITH THE HIGH PERFORMANCE BUILDING ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE
RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE BUILDING.
VECC COMPLIANCE PATH STATEMENT:
IN ACCORDANCE WITH VECC, THE BUILDING SHALL COMPLY WITH ASHRAE 90.1-2019 SECTIONS 5, 6, 7, 8, 9 & 10. SECTION 6 HVAC COMPLIANCE WILL BE VIA 6.1.1.3 ALTERATIONS TO HVAC AND REFRIGERATION IN EXISTING BUILDINGS, DIRECT REPLACEMENT OF HVAC EQUIPMENT.
EXISTING BUILDING DATA:
CONSTRUCTION TYPE: IIB EXISTING CONSTRUCTION
ALTERATION LEVEL: LEVEL 2
OCCUPANCY CLASSIFICATION: I-2 INSTUTUTIONAL
AREA OF BUILDING: 106,683 SF
NUMBER OF STORIES: PARTIAL BASEMENT, 1 STORY
M-701 M-702 M-703 E-001 E-101 E-102
ED401
ED402
EP001
EP002
EP401
EP402
EP601
EP701
EP702
EP703
CONTROLS
CONTROLS
CONTROLS
ELECTRICAL GENERAL NOTES, ABBREVIATIONS, LEGENDS AND SYMBOLS
OVERVIEW POWER PLAN - FIRST FLOOR
OVERVIEW POWER PLAN - ROOF
ENLARGED DEMOLITION PLAN
ENLARGED DEMOLITION PLAN
TEMPORARY POWER PLAN
TEMPORARY POWER PLAN
ENLARGED POWER PLAN
ENLARGED POWER PLAN
ELECTRICAL ONE LINE DIAGRAMS
ELECTRICAL SCHEDULES AND CALCULATIONS
PANEL SCHEDULES
PANEL SCHEDULES
ASBESTOS DISCLOSURE STATEMENT:
AN ASBESTOS INSPECTION WAS PERFORMED AND NO ACM WAS FOUND. THE
ASBESTOS INSPECTION REPORT IS INCLUDED AS AN APPENDIX TO THE
PROJECT SPECIFICATIONS.
LEAD DISCLOSURE STATEMENT:
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING
COMPONENTS HAS BEEN CONDUCTED AND CAN BE FOUND IN THE
PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE
CONTRACTOR’S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE
CONTRACTOR’S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA
OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY
PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED
BUILDING COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE.
SCOPE OF WORK:
THE SCOPE OF WORK IS PRIMARILY REMOVAL AND REPLACEMENT OF 6
EXISTING AIR HANDLING UNITS. NO MODIFICATIONS HAVE BEEN MADE TO
THE FIRE DAMPERS, SMOKE DAMPERS, OR SPACE USE. NO SPRINKLER
MODIFICATIONS ARE PROVIDED.
240020
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
COVER SHEET
SWL
MKD
9/30/2026
G-001
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A M
R K
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
N
/3
/2
IS
SU
E
FO
R
B
ID
S
/3
/2
09/30/2026
TEMPORARY DUCT HEATER REQUIREMENTS
DESIGNATION TDH-1A TDH-1B TDH-2A TDH-2B TDH-3A TDH-3B TDH-4A TDH-4B TDH-5A TDH-5B TDH-6A TDH-6B
UNIT SERVES AHU-6
AHU-6 HOT
DECK
AHU-7
AHU-7 HOT
DECK
AHU-9
AHU-9 HOT
DECK
AHU-33
AHU-33 HOT
DECK
AHU-34
AHU-34 HOT
DECK
AHU-35
AHU-35 HOT
DECK
TYPE ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC ELECTRIC
CONTROL TYPE SCR SCR SCR SCR SCR SCR SCR SCR SCR SCR SCR SCR
CAPACITY (KW) 24 37 48 74 46 70 42 64 54 83 49 75
AIRFLOW (CFM) 4,180 3,344 8,370 6,696 7,900 6,320 7,220 5,776 9,330 7,464 8,490 6,792
ENTERING AIR TEMPERATURE (DEGF) 36.7 55 36.7 55 36.7 55 36.7 55 36.7 55 36.7 55
LEAVING AIR TEMPERATURE (DEGF) 55 90 55 90 55 90 55 90 55 90 55 90
VOLTAGE (V) 480 480 480 480 480 480 480 480 480 480 480 480
PHASE 3 3 3 3 3 3 3 3 3 3 3 3
FREQUENCY (HZ) 60 60 60 60 60 60 60 60 60 60 60 60
REMARKS 1, 2, 3, 4 & 5 1, 2, 3 & 4 1, 2, 3, 4 & 5 1, 2, 3 & 4 1, 2, 3, 4 & 5 1, 2, 3 & 4 1, 2, 3, 4 & 5 1, 2, 3 & 4 1, 2, 3, 4 & 5 1, 2, 3 & 4 1, 2, 3, 4 & 5 1, 2, 3 & 4
REMARKS LEGEND:
1. PROVIDE DOWNSTREAM DUCT MOUNTED THERMOSTAT.
2. PROVIDE HEATER WITH FLANGED DUCT CONNECTIONS.
3. PROVIDE OUTDOOR RATED DUCT HEATER.
4. PROVIDE UPSTREAM AND DOWNSTREAM STRAIGHT DUCT LENGTHS PER INSTALLATION INSTRUCTIONS.
5. ELECTRIC HEATER MAY BE INTEGRAL TO THE TEMPORARY AHU.
TEMPORARY AIR HANDLING UNIT REQUIREMENTS
ASSOCIATED UNIT AHU-6 AHU-7 AHU-9 AHU-33 AHU-34 AHU-35
TOTAL FAN AIRFLOW (CFM) 4,180 8,370 7,900 7,220 9,330 8,490
EXTERNAL STATIC PRESSURE (IN. WG) 2.7 2.5 2.6 2.7 2.5 2.5
COOLING ENTERING AIR TEMPERATURE DB/WB (F) 91.1/74.9 91.1/74.9 91.1/74.9 91.1/74.9 91.1/74.9 91.1/74.9
COOLING LEAVING AIR TEMPERATURE DB/WB (F) 55/54 55/54 55/54 55/54 55/54 55/54
HEATING ENTERING AIR TEMPERATURE (F) 16.7 16.7 16.7 16.7 16.7 16.7
HEATING LEAVING AIR TEMPERATURE (F) 36.7 36.7 36.7 36.7 36.7 36.7
FILTER MERV 8 MERV 8 MERV 8 MERV 8 MERV 8 MERV 8
VOLTAGE (V) / PHASE / FREQUENCY (HZ) 480 / 3 / 60 480 / 3 / 60 480 / 3 / 60 480 / 3 / 60 480 / 3 / 60 480 / 3 / 60
REMARKS 1, 2, 3, 4, 5 1, 2, 3, 4, 5 1, 2, 3, 4, 5 1, 2, 3, 4, 5 1, 2, 3, 4, 5 1, 2, 3, 4, 5
1. PROVIDE 100% OUTSIDE AIR DX VAV TEMPORARY UNIT.
2. PROVIDE VFD FOR SUPPLY FAN.
3. TEMPORARY AHU SHALL BE CAPABLE OF HEAT PUMP OPERATION.
4. PROVIDE A MINIMUM OF TWO COMPRESSORS TO ALLOW STAGED CAPACITY CONTROL.
5. EXTERNAL STATIC PRESSURE IS BASED ON THE STATIC PRESSURE REQUIRED AT THE CONNECTION OF TEMPORARY DUCTWORK TO EXISTING DUCT SYSTEM. TEMPORARY UNIT MUST BE SIZED TO ACCOMMODATE THE STATIC PRESSURE LOSS OF THE TEMPORARY DUCT CONFIGURATION.
AHU SERVE AREA LEGEND
TEMPORARY AHU SKID LOCATION
AHU-34
AHU-35
AHU-7
AHU-6
RM K400
RM I400
RM L400
RM F400
AHU-9
AHU-33
PATIENT
FENCED AREA
PATIENT
FENCED AREA
PATIENT
FENCED AREA
PATIENT
FENCED
AREA
(E) SIDEWALK.
PATIENT
AREA
PATIENT
AREA
PATIENT
AREA
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
PHASING PLAN
SWL
MKD
9/30/2026
240020
G-002
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
1. BUILDING OPERATION
• THE PREMISES WILL REMAIN OCCUPIED FOR THE DURATION OF CONSTRUCTION. COORDINATE WITH THE OWNER REGARDING ANY INTERRUPTIONS TO UTILITIES, TEMPORARY
EXITS, DUST PARTITIONS, DELIVERIES, AND OTHER WORK ACTIVITIES THAT MAY AFFECT BUILDING OPERATIONS.
• PHASE DEMOLITION AND NEW WORK TO PROTECT BUILDING OCCUPANTS, MAINTAIN BUILDING OPERATIONS, AND KEEP REQUIRED ENTRANCES AND EXITS OPEN
THROUGHOUT THE PROJECT. SUBMIT A WRITTEN PHASING PLAN FOR REVIEW AND APPROVAL PRIOR TO STARTING WORK THAT MEETS THE INTENT OF THE REQUIREMENTS
OUTLINED BELOW. DO NOT PROCEED WITHOUT APPROVAL OF THE WRITTEN PHASING PLAN.
2. AIR HANDLING UNIT (AHU) SEQUENCING
• THE PROJECT INCLUDES SIX AIR HANDLING UNITS, EACH LOCATED IN A SEPARATE MECHANICAL ROOM. COORDINATE WITH THE OWNER DURING CONSTRUCTION TO
DETERMINE THE SEQUENCE IN WHICH THE UNITS WILL BE DEMOLISHED AND REPLACED.
3. PRE-CONSTRUCTION TAB VERIFICATION
• PRIOR TO DEMOLITION, PERFORM A PRE-CONSTRUCTION TAB VERIFICATION OF EACH AIR HANDLING UNIT TO BE REPLACED. MEASURE THE EXISTING PERFORMANCE OF EACH AHU AND SUBMIT THE TAB VERIFICATION REPORT TO THE ENGINEER OF RECORD FOR REVIEW.
• THE TAB VERIFICATION REPORT SHOULD INCLUDE SUPPLY, RETURN, AND OUTSIDE AIRFLOW RATES, AS WELL AS COOLING COIL AND HEATING COIL WATER FLOW RATES.
• AFTER INSTALLATION AND STARTUP OF EACH AHU, PERFORM TAB IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. BALANCING OF DISTRIBUTION SYSTEMS
DOWNSTREAM OF THE AHU IS NOT REQUIRED.
4. TEMPORARY AHU REQUIREMENTS (AHUS 6, 7, 9, 33, 34, 35)
• PROVIDE TEMPORARY AHUS TO ENSURE FULL AIR CONDITIONING FOR ALL SPACES AFFECTED BY EACH REPLACEMENT. PROVIDE A 100% OA DX TEMPORARY AHU AND TWO TEMPORARY DUCT HEATERS AS INDICATED IN THE TEMPORARY SCHEDULES. INSTALL (TDH-#A) AT THE DISCHARGE OF THE TEMPORARY AHU AND, VIA DUCTWORK, CREATE A HOT AND COLD DUCT ROUTE TO TIE INTO THE EXISTING HOT AND COLD DUCTS. LOCATE (TDH-#B) IN THE TEMPORARY HOT DUCT. REPLACE UNITS SEQUENTIALLY, ONE AT A TIME. TO PROVIDE RELIEF, LEAVE THE RETURN DUCT, RELIEF LOUVER, AND RELIEF HOOD OPEN IN THE MECHANICAL ROOM WHERE APPLICABLE. TEMPORARY DUCTWORK
SHALL CONNECT TO THE ASSOCIATED SUPPLY DUCTS WITHIN THE MECHANICAL ROOM.
• MINIMIZE DOWNTIME: LIMIT THE PERIOD BETWEEN EXISTING AHU SHUTDOWN AND TEMPORARY AHU STARTUP TO A MAXIMUM OF FIVE (5) HOURS.
• PATIENT ROOM TEMPERATURE LIMITS: DURING AHU SHUTDOWN AND TEMPORARY AHU OPERATION, MAINTAIN PATIENT ROOM TEMPERATURES WITHIN 70°F TO 78°F, OR
OTHER RANGE AS CONFIRMED WITH THE BUILDING OWNER, AND DO NOT ALLOW SPACES TO RISE ABOVE OR FALL BELOW APPROVED SETPOINTS REGARDLESS OF OUTAGE
DURATION.
• PREPARE IN ADVANCE: HAVE ALL MATERIALS AND EQUIPMENT ON SITE, WITH PREFABRICATION COMPLETED WHERE POSSIBLE, BEFORE SHUTDOWN.
• PROVIDE TEMPORARY CONSTRUCTION FENCING WITH FULL HEIGHT OPAQUE PRIVACY PANELS TO BLOCK VIEWS INTO THE WORK AREA FROM ADJACENT SIDEWALKS, PARKING AREAS, AND OCCUPIED SPACES. COORDINATE LOCATION, ASSEMBLY, LAYOUT, AND EXTENT WITH OWNER PRIOR TO INSTALLATION. MAINTAIN ALL REQUIRED EXITS
AND EMERGENCY ACCESS. REMOVE TEMPORARY FENCING AND PANELS AT COMPLETION OF WORK.
• TEMPORARY DUCTWORK SHALL BE ROUTED OVER ROOF AND SHALL NOT PASS THROUGH PATIENT AREAS EXCEPT AT REQUIRED ROOF DROP LOCATIONS TO ENTER THE
MECHANICAL ROOM THROUGH LOUVER OR DOOR OPENINGS.
• ADDITIONAL INSTRUCTION FOR AHU-6 AND AHU-9: PROVIDE TEMPORARY ANTI LIGATURE COVER OR WALL ENCLOSURE TO PROTECT TEMPORARY DUCTWORK ROUTED FROM ROOF THROUGH DOOR OR LOUVER INTO MECHANICAL ROOM L400 AND I400. CONSTRUCT ENCLOSURE WITH METAL STUD FRAMING AND THREE QUARTER INCH PLYWOOD SHEATHING WITH IMPACT RESISTANT PANEL OR METAL SKIN. SEAL ALL JOINTS. NO REMOVABLE PANELS PERMITTED WITHIN PATIENT AREA. COORDINATE INSTALLATION WITH OWNER AND OBTAIN BUILDING OWNER APPROVAL OF ENCLOSURE CONSTRUCTION PRIOR TO INSTALLATION.
• IF TEMPORARY DUCTWORK CROSSES A SIDEWALK: PROVIDE PEDESTRIAN PROTECTION INCLUDING TEMPORARY CANOPY OR COVERED WALKWAY, MINIMUM 8'-0" CLEAR HEADROOM, SECURE DUCT SUPPORTS, AND REQUIRED SIGNAGE AND BARRICADES TO MAINTAIN SAFE PEDESTRIAN ACCESS AT ALL TIMES.
5. PHASING PLAN CONTENT
• SUBMIT A DETAILED PLAN AND OBTAIN APPROVAL FROM OWNER AND ENGINEER OF RECORD PRIOR TO STARTING WORK. THE PLAN MUST INCLUDE, AT A MINIMUM, THE
FOLLOWING ITEMS:
• DEMOLITION OF THE EXISTING UNIT AND PROTECTION OF THE EXISTING SYSTEMS TO REMAIN.
• FINAL AHU REPLACEMENT SEQUENCING.
• INSTALLATION, POWER, CONTROLS, AND STARTUP OF THE TEMPORARY AHU; REQUIRED DUCT/PIPING TIE-INS AND INTERIM AIR/WATER BALANCING.
• TEMPORARY CONTROLS SEQUENCE AND MONITORING PLAN.
• PATIENT TEMPERATURE CONTROL VERIFICATION AND MONITORING PLAN.
• FREEZE PROTECTION MEASURES FOR TEMPORARY PIPING (IF WINTER CONDITIONS APPLY).
• DELIVERY AND ASSEMBLY OF THE NEW AHU AND FINAL DUCTWORK CONNECTIONS ALONG WITH POWER AND CONTROLS INTEGRATION.
• OUTAGE PROCEDURES AND BACKUP/CONTINGENCY EQUIPMENT PLANS.
• PIPING ISOLATION OR DRAINAGE PLAN, INCLUDING METHOD OF ISOLATION, EXTENT OF SYSTEM IMPACTED, AND ESTIMATED DURATION.
• SIDEWALK PEDESTRIAN PROTECTION OR SIDEWALK CLOSURE PLAN.
• TEMPORARY FENCING AND SITE LOGISTICS PLAN.
• ANTI-LIGATURE ENCLOSURE DESIGN AND TIMING OF INSTALLATION.
• ESTIMATED SHUTDOWN DURATIONS FOR ALL AFFECTED SYSTEMS AND THE PROPOSED SEQUENCING/WINDOWS.
• RISKS TO COMPLETING THE WORK WITHIN ALLOWABLE DOWNTIME AND DESCRIBE MITIGATION MEASURES.
• PIPE CONDENSATE FROM ALL TEMPORARY AHUS AND TEMPORARY COOLING EQUIPMENT TO AN APPROVED SANITARY DRAIN OR INDIRECT RECEPTOR USING RIGID PIPING
OR HOSE WITH CONTINUOUS POSITIVE SLOPE. DO NOT DISCHARGE CONDENSATE TO GRADE, WALKWAYS, OR LANDSCAPED AREAS. PROVIDE TEMPORARY SUPPORTS, AIR GAP AS REQUIRED, AND SECURE PIPING TO PREVENT LEAKS, EROSION, OR NUISANCE CONDITIONS. COORDINATE DISCHARGE LOCATION WITH THE BUILDING OWNER
PRIOR TO INSTALLATION.
6. PIPING ISOLATION
• USE STOPPLE OR PIPE-FREEZE ISOLATION METHODS TO AVOID DRAINING THE CHILLED AND HEATING WATER SYSTEMS WHEN REPLACING ISOLATION VALVES. WHERE THIS
METHOD IS NOT POSSIBLE, COORDINATE WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
7. POST-CONSTRUCTION CLEANING
• UPON COMPLETION OF WORK IN EACH MECHANICAL ROOM, CLEAN ALL DUST, DEBRIS, AND MATERIALS GENERATED BY CONSTRUCTION ACTIVITIES. REPAIR ANY DUCT, PIPE, OR EQUIPMENT INSULATION DAMAGED DURING CONSTRUCTION.
• DISTURBED LANDSCAPING:
1. ALL DENUDED AREAS SHALL RECEIVE TEMPORARY OR PERMANENT STABILIZATION IN ACCORDANCE WITH THE VIRGINIA EROSION AND SEDIMENT CONTROL REGULATIONS
AND THE VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK, LATEST EDITION. PERMANENT VEGETATION SHALL BE CONSIDERED ESTABLISHED ONLY WHEN A UNIFORM, MATURE VEGETATIVE COVER IS ACHIEVED THAT IS SUFFICIENT TO INHIBIT EROSION.
2. CONTRACTOR SHALL TOPSOIL, LIME, FERTILIZE, AND SEED ALL DISTURBED LAWN AND GRASS AREAS IN ACCORDANCE WITH THE VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK, LATEST EDITION, INCLUDING SPECIFIED PERMANENT AND TEMPORARY SEEDING MIXTURES, SOIL PREPARATION, AND APPLICATION RATES
APPROPRIATE TO THE PROJECT LOCATION AND SEASON.
8. HOT WATER CONVECTORS
• MAINTAIN OPERATION OF ALL PERIMETER HOT WATER CONVECTORS DURING CONSTRUCTION. COORDINATE ANY TEMPORARY SHUTDOWNS OF THE HOT WATER SYSTEM
WITH THE OWNER.
9. TEMPORARY SYSTEMS RESPONSIBILITY
• THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK AND COMPONENTS NECESSARY TO OPERATE THE FOLLOWING TEMPORARY SYSTEMS, INCLUDING PIPING, DUCTWORK, AND ASSOCIATED CONTROLS. THE CONTRACTOR MUST OPERATE AND MAINTAIN THE TEMPORARY HEATING/COOLING EQUIPMENT AND RESPOND TO ANY REPORTED ISSUES WITHIN FOUR (4) HOURS. EMERGENCY TEMPORARY HEATING/COOLING OUTAGES MUST NOT EXCEED TWELVE (12) HOURS.
SCALE: 1" = 40'-0"
FIRST FLOOR OVERALL PHASING PLAN
PHASING NOTES:
PLAN
NORTH
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
• UPON STARTUP, ACTIVATE THE TEMPORARY AHU, THEN AFTER 10 SECONDS
ENERGIZE (TDH-#A), IF NEEDED. WAIT AN ADDITIONAL 10 SECONDS BEFORE
ENERGIZING (TDH-#B), IF NEEDED.
• WHEN IN OCCUPIED MODE, THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY.
THE TEMPORARY CONTROLLER SHALL MODULATE THE SUPPLY FAN VFD TO
MAINTAIN THE EXISTING STATIC PRESSURE SETPOINT OF THE EXISTING COLD
DECK STATIC PRESSURE SENSOR. MAINTAIN THE EXISTING STATIC PRESSURE
SENSOR SETPOINT; CONFIRM THE EXISTING SETPOINT WITH THE OWNER.
• THE TEMPORARY AHU SHALL MODULATE THE COMPRESSORS TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE COOLING SETPOINT (55°F ADJ). IF THE
DISCHARGE AIR TEMPERATURE DROPS BELOW 55°F ADJ, THE TEMPORARY
ELECTRIC DUCT HEATER (TDH-#A) SHALL TURN ON AND MAINTAIN A DISCHARGE
AIR TEMPERATURE OF 55°F ADJ.
• TDH-#B SHALL MODULATE TO MAINTAIN A HOT DUCT TEMPERATURE OF 90°F
ADJ.
• SPACE TEMPERATURES SHALL BE CONTINUOUSLY MONITORED. AN ALARM
SHALL BE GENERATED IF THE SPACE TEMPERATURE EXCEEDS 78 °F OR FALLS
BELOW 70 °F.
TEMPORARY SEQUENCE OF OPERATIONS:
09/30/2026
/3
/2
E
FO
R
B
/2
AFMS
FS
S
F
M
HVAC AND MECHANICAL PIPING LEGEND
CONSTRUCTION PHASING
DUCT SYSTEMS
AIR TERMINAL TAGS
S2C
NUMBER: UNIT DESIGNATION
NUMBER: AIRFLOW
R-1
WxH
SIZE: WIDTH x HEIGHT
T
H
SD
CO
CO2
SENSORS
TEMPERATURE
HUMIDITY
SMOKE
CARBON MONOXIDE
CARBON DIOXIDE
P
DP
SP
OCC
PRESSURE
DIFFERENTIAL PRESSURE
STATIC PRESSURE
OCCUPANCY
CHILLED WATER RETURN
PIPING SYSTEMS
PIPE ACCESSORIES & FITTINGS
CHR
CHS
CD
CWR
CWS
HWR
HWS
CHILLED WATER SUPPLY
CONDENSATE DRAIN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
ROUND DUCT
RECTANGULAR12"x10"
12"ø
SUPPLY DUCT
RETURN DUCT
EXHAUST DUCT
OVAL DUCT23"/10"
ESS EMERGENCY STOP SWITCH
MECHANICAL ABBREVIATIONS
DOWN UP
DUCT DIMENSIONS
MECHANICAL GENERAL NOTES
GENERAL
1. REFER TO EACH DRAWING FOR NOTES SPECIFIC TO THAT DRAWING SHEET.
2. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND INDICATE THE GENERAL AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING AND
DUCTWORK. DO NOT SCALE DRAWINGS. THEY ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. A COMPLETE HEATING, VENTILATING AND AIR CONDITIONING SYSTEM (HVAC) WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS MUST BE PROVIDED. THE CONTRACTOR MUST CAREFULLY REVIEW ALL THE CONTRACT DOCUMENTS AND COORDINATE BETWEEN ALL TRADES PRIOR TO SUBMITTING SHOP DRAWINGS. THE CONTRACTOR MUST VERIFY ALL SIZES, MATERIALS, TEMPERATURE AND PRESSURE RATINGS BEFORE ORDERING OR INSTALLING ANY MATERIALS OR EQUIPMENT. THE CONTRACTOR MUST PREPARE INSTALLATION INSTRUCTIONS AND
FABRICATION DRAWINGS PRIOR TO ACTUAL INSTALLATION.
3. ALL MECHANICAL EQUIPMENT AND ACCESSORIES MUST BE INSTALLED IN STRICT ACCORDANCE WITH THE CURRENT APPROVED EDITION OF THE INTERNATIONAL MECHANICAL CODE (IMC) AND ALL OTHER APPLICABLE LOCAL CODES AND BUILDING STANDARDS, UNLESS DRAWINGS
AND/OR SPECIFICATIONS INDICATE WORK OVER AND ABOVE CODE REQUIREMENTS.
4. FURNISH ALL MATERIALS AND LABOR NECESSARY FOR THE COMPLETION OF WORK UNLESS NOTED OTHERWISE.
5. ALL MISCELLANEOUS MATERIAL REQUIRED TO ENSURE PROPER INSTALLATION MUST BE PROVIDED.
6. ALL MECHANICAL EQUIPMENT AND SYSTEMS MUST BE INSTALLED IN A MANNER WHICH MINIMIZES NOISE AND VIBRATION.
7. ALL MATERIALS REQUIRED FOR PROPER INSTALLATION MUST BE NEW UNLESS THE ITEM IS INDICATED AS EXISTING TO REMAIN OR
RELOCATED ON THE DRAWINGS.
COORDINATION
1. COORDINATE THE INSTALLATION OF ALL WORK WITH THE WORK OF OTHER TRADES. MINOR DEVIATIONS FROM THE PLANS, TO INCLUDE OFFSETS AND TRANSITIONS, MAY BE MADE TO AVOID CONFLICTS. MAJOR CONFLICTS MUST BE BROUGHT TO THE ATTENTION OF THE
ENGINEER PRIOR TO COMMENCEMENT OF THE WORK.
2. EQUIPMENT SIZES SHOWN ARE BASED UPON TYPICAL MANUFACTURED EQUIPMENT AVAILABLE. SHOP DRAWINGS MUST BE PROVIDED FOR REVIEW AND APPROVAL, SHOWING SPACE FOR ACCESS, EGRESS, MAINTENANCE, AND REQUIRED CODE CLEARANCES PRIOR TO ANY
PROCUREMENT, FABRICATION, OR INSTALLATION.
3. COORDINATE THE ELECTRICAL REQUIREMENTS OF EACH PIECE OF EQUIPMENT WITH THE ELECTRICAL CONTRACT DOCUMENTS PRIOR TO
ORDERING.
4. DO NOT PENETRATE STRUCTURAL MEMBERS WITHOUT PRIOR APPROVAL.
5. DO NOT PLACE PIPING ABOVE ELECTRICAL, COMMUNICATIONS, DATA EQUIPMENT OR PANELS.
6. INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL EQUIPMENT
A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE WITH A QUALIFIED
SPRINKLER SYSTEM INSTALLER FOR RESOLUTION.
DUCTWORK
1. DUCT SIZES ARE SHOWN AS INSIDE CLEAR DIMENSIONS. WHERE INTERNAL INSULATION IS CALLED FOR, DIMENSIONS MUST BE INCREASED
FOR THE THICKNESS OF THE INSULATION.
2. ALL BRANCH DUCTWORK MUST BE SIZED TO MATCH THE TERMINAL CONNECTION SERVED UNLESS NOTED OTHERWISE. FLEXIBLE DUCT TO DIFFUSERS MUST BE INSTALLED FREE OF KINKS AND SAGS. MAXIMUM LENGTH OF FLEXIBLE DUCT MUST BE 5'-0". ALL RUNOUT AND BRANCH
DUCTS MUST CONTAIN A MANUAL VOLUME DAMPER FOR BALANCING.
3. ALL DUCT TRANSITIONS FROM SQUARE TO ROUND MUST BE SMOOTH SQUARE TO ROUND TRANSITIONS.
4. ALL DIFFUSERS MUST HAVE FOUR-WAY BLOW UNLESS NOTED OTHERWISE..
5. ALL DAMPERS, DAMPER OPERATORS, AND FANS MUST BE ACCESSIBLE. LOCATE ALL EQUIPMENT OR APPURTENANCES IN AREAS WITH
ACCESSIBLE CEILINGS. THE CONTRACTOR MAY UTILIZE ACCESS PANELS FOR THOSE AREAS NOT EASILY ACCESSIBLE. ALL ACCESS PANEL LOCATIONS MUST BE COORDINATED WITH THE CONTRACT DOCUMENTS AND APPROVED BY THE OWNER PRIOR TO INSTALLATION OF
EQUIPMENT.
6. PROVIDE UL LISTED FIRESTOPPING ASSEMBLIES FOR EACH PENETRATION OF RATED ASSEMBLIES.
7. ALL DUCTWORK MUST BE SLEEVED THROUGH WALL PENETRATIONS EXCEPT INTERIOR PARTITIONS. ALL WALL PENETRATIONS OF
DUCTWORK MUST BE SEALED.
8. PROVIDE TURNING VANES IN MITERED 90 DEGREE BENDS EXCEPT TRANSFER DUCTS OR OTHERWISE NOTED.
9. PROVIDE CONICAL TEES FOR TAKE-OFFS FROM ROUND AND FLAT OVAL DUCTWORK. PROVIDE TAPS WITH 45 DEGREE DUCT HEEL FOR TAKE-
OFFS FROM RECTANGULAR DUCTWORK.
PIPING
1. SLOPE CONDENSATE DRAINS AT 1/8" PER FOOT MINIMUM IN THE DIRECTION OF FLOW. PROVIDE FITTINGS TO ALLOW CLEANING OF ENTIRE
SYSTEM.
2. ALL PIPING MUST HAVE ITS SLOPE AND INVERT ESTABLISHED PRIOR TO THE INSTALLATION OF ANY PIPING.
3. ALL PIPING SYSTEMS THAT ARE NOT OPEN TO ATMOSPHERE MUST BE PROVIDED WITH VALVED DRAINS AT LOW POINTS AND MANUAL AIR
VENTS AT HIGH POINTS.
4. PROVIDE UL LISTED FIRESTOPPING ASSEMBLIES FOR EACH PENETRATION OF RATED ASSEMBLIES.
5. ALL PIPING MUST BE SLEEVED THROUGH MASONRY WALL PENETRATIONS. ALL PARTITION PENETRATIONS MUST BE ACOUSTICALLY SEALED.
6. SIZE AND ROUTE REFRIGERANT PIPING PER EQUIPMENT MANUFACTURER'S WRITTEN INSTRUCTIONS.
7. CONNECTIONS BETWEEN DISSIMILAR METALS MUST BE MADE WITH DIELECTRIC FITTINGS.
EQUIPMENT
1. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
2. ALL MECHANICAL EQUIPMENT MUST BE INSTALLED IN SUCH A MANNER SO THAT ALL FILTERS, VALVES, MOTORS, DAMPERS, ETC., ARE
COMPLETELY ACCESSIBLE AND SERVICEABLE, INCLUDING ACCESS DOORS IF REQUIRED.
3. COMPLETE AND PROPER INSTALLATION OF THERMOSTATS AND ALL OTHER NECESSARY FIELD MOUNTED CONTROL COMPONENTS MUST BE THE RESPONSIBILITY OF THE MECHANICAL OR CONTROLS CONTRACTOR. THE EQUIPMENT MANUFACTURER MUST FURNISH COMPLETE WIRING CONTROLS. ALL CONTROL WIRING IN MECHANICAL ROOMS OR AREAS SUBJECT TO DAMAGE MUST BE IN CONDUIT AND INSTALLED
PER ELECTRICAL CONTRACT DOCUMENTS.
4. PROVIDE FLEXIBLE CONNECTIONS BETWEEN HVAC EQUIPMENT AND SHEET METAL DUCTWORK.
RENOVATION WORK
1. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY, AND PREVIOUS RECORD DRAWINGS FORM THE BASIS FOR MANY OF THESE DRAWINGS. FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. THERE MAY EXIST FIELD CONDITIONS WHICH DIFFER FROM THOSE SHOWN ON THESE DRAWINGS. ANY SUCH DEVIATIONS MUST BE BROUGHT TO THE ATTENTION OF THE ENGINEER FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR
MATERIAL/EQUIPMENT PURCHASE WHICH WOULD BE UNUSABLE UNDER THOSE CIRCUMSTANCES.
2. MINIMIZE THE DESTRUCTION OR DEMOLITION OF EXISTING CEILING OR FLOOR TILES. REPLACE ALL TILES DEMOLISHED OR DAMAGED, COORDINATE THE TILE SELECTION WITH OWNER REPRESENTATIVE.
OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS
1. REMOVE ANY LARGE DEBRIS OR OBSTRUCTIONS FROM THE PLENUMS MANUALLY OR WITH APPROPRIATE TOOLS.
2. UTILIZE INDUSTRIAL-GRADE CLEANING SOLUTIONS AND EQUIPMENT TO THOROUGHLY CLEAN THE INTERIOR SURFACES OF THE PLENUMS.
THIS MAY INCLUDE PRESSURE WASHING, VACUUMING, AND THE USE OF CHEMICAL AGENTS TO ELIMINATE MOLD, DUST, AND OTHER
CONTAMINANTS.
3. ENSURE THAT ALL CLEANING AGENTS USED ARE APPROVED FOR USE IN HVAC SYSTEMS AND DO NOT LEAVE HARMFUL RESIDUES THAT
COULD AFFECT AIR QUALITY.
4. PAY SPECIAL ATTENTION TO CORNERS, JOINTS, AND ANY OTHER AREAS WHERE DIRT AND DEBRIS MAY ACCUMULATE.
5. CONDUCT A POST-CLEANING INSPECTION TO VERIFY THAT ALL AREAS OF THE PLENUMS ARE THOROUGHLY CLEANED AND FREE OF
CONTAMINANTS.
6. DOCUMENT THE CLEANING PROCESS, INCLUDING BEFORE AND AFTER PHOTOGRAPHS, AND PROVIDE A DETAILED REPORT TO THE BUILDING
OWNER.
S=SUPPLY
R=RETURN
NECK SIZE:
A=6" B=8" C=10"
E=EXHAUST
T=TRANSFER
D=12" E=14" F=16"
S=SUPPLY
R=RETURN
E=EXHAUST
T=TRANSFER
NUMBER: UNIT DESIGNATION
NUMBER: AIRFLOW
EXISTING TO REMAIN
DEMOLITION
WORK IN THIS PHASE
# KEYNOTE
POINT OF
CONNECTION
POINT OF
DISCONNECTION
DEMO EXISTING
TO REMAIN
WORK IN
THIS PHASE
EXISTING
TO REMAIN
DUCT ACCESSORIES & FITTINGS
ACCESSORIES
DAMPER,
MANUAL
BALANCING
DAMPER,
BACKDRAFT
DAMPER,
CONTROL
DAMPER,
FIRE
DAMPER,
SMOKE
DAMPER,
FIRE & SMOKE
SECURITY
BARS
AIRFLOW
MONITORING
STATION
FLEXIBLE
DUCT UP
DOWN
45 DEG
BEND
90 DEG
BEND
GORED MITERED
DOWN UP
90 DEG
BEND
45 DEG
BEND
DOWN
UP
90 DEG
BEND
45 DEG
BEND
RECTANGULAR DUCTWORK
MITERED RADIUS
ROUND DUCTWORK
OVAL DUCTWORK
TEE
TEE UP
TEE DN
90 DEG
ELBOW
ELBOW
PIPE UP
PIPE DN
REDUCER,
CONCENTRIC
REDUCER,
ECCENTRIC
FLANGE
JOINT
BLIND
FLANGE
PIPE
CAP
VALVE, GLOBE
VALVE, GATE
VALVE, CHECK
VALVE, BUTTERFLY, CONTROL
VALVE, BUTTERFLY, MANUAL
VALVE, BALL, CONTROL
VALVE, BALL, MANUAL
VALVE, BALANCING
WYE STRAINER
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
LEGEND, ABBREVIATIONS
& GENERAL NOTES
SWL
MKD
9/30/2026
240020
M-001
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
(D) DEMOLISH
(E) EXISTING ELEMENT TO REMAIN
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASUREMENT STATION
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AO ANALOG OUTPUT
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
ARCH ARCHITECTURE
AS AIR SEPARATOR
BEL BELLMOUTH FITTING
CD CONDENSATE DRAIN
CDW CONDENSER WATER
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CLG COOLING OR CEILING
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDENSATE OR CONDENSER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DDC DIRECT DIGITAL CONTROL
DEG DEGREES
DI DIGITAL INPUT
DN DOWN
DO DIGITAL OUTPUT
DP DIFFERENTIAL PRESSURE
EA EXHAUST AIR OR EACH
EL ELEVATION
EXH EXHAUST
F OR °F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FS FLOW SWITCH
FT FOOT OR FEET
FZ FREEZESTAT
GA GAUGE
GAL GALLON (U.S.)
GALV GALVANIZED
H HUMIDITY
HP HORSEPOWER
HWP HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
L LOUVER
MCA MAXIMUM CURRENT AMPACITY
MOP
MAXIMUM OVERCURRENT
PROTECTION
NC
NOISE CRITERIA OR NORMALLY
CLOSED
NG NATURAL GAS
NO NUMBER OR NORMALLY OPEN
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OCC OCCUPANCY
P PRESSURE
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RA RETURN AIR
RH RELATIVE HUMIDITY
RLF RELIEF AIR
SA SUPPLY AIR
SD
SMOKE DAMPER OR SMOKE
DETECTOR
SF SQUARE FEET
SP STATIC PRESSURE
STD STANDARD
T TEMPERATURE
TSTAT THERMOSTAT
TYP TYPICAL
UH UNIT HEATER
VFD VARIABLE FREQUENCY DRIVE
VLV VALVE
W/ WITH
W/O WITHOUT
WG WATER GAUGE
XFER TRANSFER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
MD401
MD401
M-401
M-401
MD402
M-402
M-402
MD402
MD403
M-403
MD403
M-403
MD404
MD404
M-404
M-404
RM K400
RM F400
RM I400
RM L400
P
P
P
P
P
P
FOR AHU-9
FOR AHU-7
FOR AHU-6
FOR AHU-35
FOR AHU-34
FOR AHU-33
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
FIRST FLOOR OVERALL
SWL
MKD
9/30/2026
240020
M-101
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
SCALE: 1" = 20'-0"
FIRST FLOOR OVERALL
1" = 20'-0" 0" 20' 40' 80'
PLAN
NORTH
GRAPHIC SCALE:
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
1. SPACE PRESSURE SENSORS SERVING PATIENT CORRIDORS MUST BE CONSIDERED
PATIENT-ACCESSIBLE. PROVIDE AN ANTI-LIGATURE, TAMPER-RESISTANT, FLUSH-
MOUNTED ENCLOSURE. COORDINATE FINAL LOCATIONS AND ENCLOSURE DETAILS
WITH THE OWNER.
GENERAL NOTES:
09/30/2026
/3
/2
E
FO
R
B
/2
MD405
MD405
M-405
M-405
MD406
MD406
M-406
M-406
PENTHOUSE
PENTHOUSE
(E) ROOF ACCESS HATCH
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
ROOF OVERALL
SWL
MKD
9/30/2026
240020
M-102
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
SCALE: 1" = 20'-0"
ROOF OVERALL
1" = 20'-0" 0" 20' 40' 80'
PLAN
NORTH
GRAPHIC SCALE:
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
(E) OA LOUVER
(E) 45"x12" SA
(E) 30"x12" SA
(E) 45"x12" RA
(E
"x
R A
(E) 18"/12" SA
(E) 25"/12" SA
(E) 42"x22" RLF
84"x8" SA
12"x72" SA
72"x24" OA
(E) AHU-6
PLENUM
(D) AHU-6
RM L400
(E) FD
(D) 1" CD(D) AHU-6
(E) 2" HWS
(E) 2" CHR
(E) 2" CHS
(E) 2" HWR
(D) P-40
RM L400
(E) 1 1/2" HWS
(E) 2" CHR
(E) 2" CHS
(E) 1 1/2" HWR
(E) 2" HWS
(E) 2" HWR
(E) 3/4" HWR
(E) 3/4" HWS
(D) 3/4" HWS
(D) 3/4" HWR
(D) 1 1/2" HWS
(D) 1 1/2" HWR
(E) 2" HWR
(D) 2" CHS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
DEMOLITION - FIRST
FLOOR - AHU-6
SWL
MKD
9/30/2026
240020
MD401
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
DEMOLITION NOTES
1 (E) 8" HOUSEKEEPING PAD.
2 DEMOLISH AIR HANDLER.
3 DUCT UP TO (E) 42" x 42" ROOF VENTILATOR.
SCALE: 1/4" = 1'-0"
AHU-6 DUCTWORK DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
AHU-6 PIPING DEMOLITION PLAN
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
F
F S
(E
"x
R A
(E) 24"x108" OA
(D) AHU-7
(E) 40"x14" RA
(E) 23"/12" SA
(E) LOUVER
RM F400
(E) 16"x102" OA
(D) 22"x56" OA
(D) 17"/12" SA
(D) 23"/12" SA
(D) 23"/12" SA
(D) 17"/12" SA
(E) 17"/12" SA
(E) 23"/12" SA
(E) 17"/12" SA
(D) 22"x56" OA
(E) 36"x72" RLF
(D) 16"x102" OA
(E) LOUVER
(E) 3" CHR
(E) 3" CHS
(E) 2 1/2" HWS
(E) 2 1/2" HWR
(E) FD (D) 1" CD
(D) AHU-7
(D) 3" CHS
(D) 3" CHR
(E) 1 1/2" HWR
(E) 1 1/2" HWS
(D) P-41
RM F400
(D) 1 1/2" HWR
(D) 1 1/2" HWS
(D) 1 1/2" HWS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
DEMOLITION - FIRST
FLOOR - AHU-7
SWL
MKD
9/30/2026
240020
MD402
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
DEMOLITION NOTES
1 (E) 8" HOUSEKEEPING PAD.
2 DEMOLISH AIR HANDLER.
3 DUCT UP TO (E) 36 x 72" ROOF VENTILATOR.
4 EXISTING CUTOUT IN HOUSEKEEPING PAD FOR EXISTING FLOOR
DRAIN.
5 PATCH/REPAIR DAMAGED PLENUM SECTION TO MATCH EXISTING
CONSTRUCTION; PROVIDE SEAL CLASS A CONSTRUCTION ON ALL
NEW DUCTWORK.
6 DEMOLISH INDICATED OA PLENUM. DO NOT DISTURB OR
DISCONNECT EXISTING TO-REMAIN PANEL, UPS EQUIPMENT,
CONDUIT, OR UNISTRUT SUPPORTING PANEL. PROTECT EXISTING
EQUIPMENT FROM DAMAGE DURING DEMOLITION.
SCALE: 1/4" = 1'-0"
AHU-7 DUCTWORK DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
AHU-7 PIPING DEMOLITION PLAN
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
(E) 40"x14" RA
(E) 15"/12" SA
(E) 20"/12" SA
(D) AHU-9
RM I400
(E) OA LOUVER
(E) 20"/12" SA
(E) 42"x12" RA
(E) 15"/12" SA
(D) 15"/12" SA
(D) 20"/12" SA
(D) 20"/12" SA
(D) 15"/12" SA
(E) SMOKE DETECTOR
(D) 1" CD
(E) FD
(E) 3" CHS
(E) 3" CHR (E) 2 1/2" HWS
(E) 2 1/2" HWR
(D) AHU-09
(D) 1 1/2" HWR
(D) 1 1/2" HWS
(E) 2" HWS
(E) 2" HWR
(E) 2 1/2" HWS
(E) 2 1/2" HWR
(D) P-42
(E) 1 1/2" HWR
(E) 1 1/2" HWS
RM I400
(D) 2" HWR
(D) 2" HWS
(D) 3" CHR
(D) 3" CHS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:1
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
DEMOLITION - FIRST
FLOOR - AHU-9
SWL
MKD
9/30/2026
240020
MD403
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
DEMOLITION NOTES
1 DUCT UP TO ROOF VENTILATOR.
2 (E) 8" HOUSEKEEPING PAD.
3 DEMOLISH AIR HANDLER.
4 PATCH/REPAIR DAMAGED PLENUM SECTION TO MATCH EXISTING
CONSTRUCTION; PROVIDE SEAL CLASS A CONSTRUCTION ON ALL
NEW DUCTWORK.
5 DEMOLISH INDICATED OA PLENUM. DO NOT DISTURB OR
DISCONNECT EXISTING TO-REMAIN PANEL, UPS EQUIPMENT,
CONDUIT, OR UNISTRUT SUPPORTING PANEL. PROTECT EXISTING
EQUIPMENT FROM DAMAGE DURING DEMOLITION.
SCALE: 1/4" = 1'-0"
AHU-9 DUCTWORK DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
AHU-9 PIPING DEMOLITION PLAN
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
M
(D) AHU-35
(E) 46"x20" RA
(E) 46"x20" RA
(D) 36"x18" SA
(D) 22"/12" SA
(D) 11"ø SA
(D) 13"ø SA
(E) 11"ø SA
(E) 13"ø SA
(E) 36"x18" SA
(E) 22"/12" SA
(E) 40"x22" RLF
(E) 18"x12" RA
(E) UNIT
HEATER
RM K400
BELOW
BELOW
(E) MOTORIZED
DAMPER INTERLOCKED
WITH (E) EF
(E) OA LOUVER
AND PLENUM
BELOW
BELOW
42"x42" RLF
(D) AHU-35
(E) 1 1/2" HWR
(E) 1 1/2" HWS
(D) 1 1/2" HWR
(D) 1 1/2" HWS (D) 2" HWR
(D) 2" HWS
(E) 3/4" HWS
(E) 3/4" HWR
(E) FD
(D) P-39
(E) UNIT
HEATER
RM K400
(D) 1" CD
(E) 3" CHS
(E) 3" CHR
(E) 2 1/2" HWS
(E) 2 1/2" HWR
(D) 3" CHR
(D) 3" CHS
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:2
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
DEMOLITION - FIRST
FLOOR - AHU-35
SWL
MKD
9/30/2026
240020
MD404
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
DEMOLITION NOTES
1 (E) 4" HOUSEKEEPING PAD.
2 DEMOLISH AIR HANDLER.
SCALE: 1/4" = 1'-0"
AHU-35 DUCTWORK DEMOLITON PLAN
SCALE: 1/4" = 1'-0"
AHU-35 PIPING DEMOLITION PLAN
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
(E) 28"x24" RLF
(E
"x
R A
(E) 32"x36" OA
(E) 34"x24" RA
(D) AHU-33
(D) 9"ø SA
(D) 11"ø SA
(E) 12"x30" SA
(E) 16"x16" SA
PENTHOUSE
(E) RELIEF LOUVER
(E) OA LOUVER
(E) ROOM OA
DAMPER
(E) UNIT
HEATER
(D) AHU-33
(E) 3" CHS
(E) 3" CHR (E) 2" HWR
(E) 2" HWS
(E) 1 1/2" HWR
(E) 1 1/2" HWS
(E) 3" CHR
(E) 3" CHS
(D) 2" HWR
(E) 2" HWS
(E) 3/4" HWS
(E) 3/4" HWR
(E) 2" HWS
(E) 2" HWR
(E) FD
(D) P-37
7 7
PENTHOUSE
(D) 1" CD
(D) 1 1/2" HWS
(D) 1 1/2" HWR
(E) UNIT HEATER
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:2
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
DEMOLITION - ROOF -
AHU-33
SWL
MKD
9/30/2026
240020
MD405
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
DEMOLITION NOTES
1 (E) 4" HOUSEKEEPING PAD.
2 (E) 30"x30" RA DOWN.
3 (E) 12"x30" SA DOWN.
4 (E) 16"x16" SA DOWN.
5 (E) 11" SA DOWN. DISCONNECT DUCTWORK ABOVE FLOOR.
6 (E) 9" SA DOWN. DISCONNECT DUCTWORK ABOVE FLOOR.
7 (E) 6" HOUSEKEEPING PAD.
8 REUSE EXISTING FLOOR PENETRATION.
9 DEMOLISH AIR HANDLER.
SCALE: 1/4" = 1'-0"
AHU-33 DUCTWORK DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
AHU-33 PIPING DEMOLITION PLAN
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
(E) OA DAMPER
(E) 30"x38" RA
(E
"x
R A
(E) 44"x24" RLF
(E) 40"x36" OA
(D) AHU-34
(D) 16"x16" SA
(D) 16"x30" SA
(D) 12"ø SA
(D) 15"ø SA
PENTHOUSE
(E) RELIEF
LOUVER
(E) OA LOUVER
(D) 16"x30" SA DOWN
(D) 24"x68" RA
(D) 24"x68" OA
(D) 28"x68" OA
(D) 48"x22" SA
(D) 48"x22" SA
(D) 24"x22" SA(D) 24"x22" SA
(E) UNIT HEATER
(D) AHU-34
(E) 3/4" HWS
(E) 3/4" HWR
(E) 2" HWR
(E) 2" HWS
(E) 2" HWR
(D) 2" HWR
(D) 1 1/2" HWS
(E) 3" CHS
(E) 3" CHR
(E) 2" HWS
(E) 2" HWR
(D) 1 1/2" HWS
(E) 1 1/2" HWS
(D) 1 1/2" HWR
(E) FD
(D) P-38
PENTHOUSE
(D) 1" CD
(D) 3" CHS
(D) 3" CHR
(E) 1 1/2" HWR
(E) UNIT HEATER
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:2
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
DEMOLITION - ROOF -
AHU-34
SWL
MKD
9/30/2026
240020
MD406
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
DEMOLITION NOTES
1 (E) 4" HOUSEKEEPING PAD.
2 (E) 30"x38" RA DOWN.
3 (E) 16"x16" SA DOWN.
4 (E) 15" SA DOWN.
5 (E) 12" SA DOWN.
6 (E) 6" HOUSEKEEPING PAD.
7 PATCH AND SEAL FLOOR PENETRATION.
8 DEMOLISH AIR HANDLER.
SCALE: 1/4" = 1'-0"
AHU-34 DUCTWORK DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
AHU-34 PIPING DEMOLITION PLAN
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
V
D V
F D
V F
D V
F D
(E) 45"x12" SA
(E) 30"x12" SA
(E) 45"x12" RA
(E
"x
R A
(E) 42"x22" RLF
22"x42" RLF
(E) 25"/12" SA
(E) 18"/12" SA
M-401
37"x15" OA
RM L400
SD
(E) OA LOUVER
(E) AHU-6 PLENUM
(E) FD
(E) 1 1/2" HWS
(E) 2" CHR
(E) 2" CHS
(E) 1 1/2" HWR
P-40
M-401
(E) 2" HWR
(E) 2" HWS
(E) 2" CHR
(E) 2" CHS
(E) 2" HWR
RM L400
2" CHS
2" CHR
1 1/2" HWR
1 1/2" HWR
3/4" HWR
(E) 3/4" HWS
1" CD
(E) 3/4" HWS
(E) FD
AHU-6
P-40
16"x30" RA22"x42" RLF
(E) 3/4" HWR
1" CD
45"x12" SA
30"x12" SA
(E) 45"x12" SA
(E) 22"x42" RLF
(E) 2" HWR
(E) 2" HWS
(E) 2" CHS
(E) 2" CHR
2" CHR
2" CHS
1 1/2" HWS
1 1/2" HWR
(E) 3/4" HWS
3/4" HWR
(E) 1 1/2" HWS
(E) 45"x12" RA
15"x37" OA
(E) SD
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2
.7 w ile y w ils o n .c o m
E m p lo y e e -O w n e d
KEY PLAN
N V
M H
I A
H U
R E
P L A
C E
M E
N T
P
H A
S E
-1
-2
-1
/2
/2
:1
:2
P
M
C U s e rs
\m d e la n o
\O n e
D ri v e
W ile y
W ils o n In c \D o c u m e n ts \2
R
M
C e n m d e la n o Z
Q G
.r v t
FIRST FLOOR - AHU-6
ENLARGED PLANS
SWL
MKD
9/30/2026
240020
M-401
MKD
D B
H D
S N
O R
T H
E R
N V
IR
G
IN
IA
M E
N T
A L
H E
A L T
H I N
S T
IT
U
T E
F A
L L S
C H
U R
C H
V
A
2' 4' 8'0' 1/4" =1'-0"
SCALE: 1/4" = 1'-0"
AHU-6 DUCTWORK PLAN
SCALE: 1/4" = 1'-0"
AHU-6 PIPING PLAN
WORK NOTES
1 (E) 8" HOUSEKEEPING PAD.
2 DDC PANEL. PROVIDE 120 V POWER. LOCATE PANEL ON EXISTING
UNISTRUT.
3 DUCT UP TO (E) 42" x 42" ROOF VENTILATOR.
4 EXISTING OUTSIDE AIR PLENUM AND DUCTWORK TO REMAIN.
THOROUGHLY CLEAN AND REMOVE ALL DUST, DEBRIS, AND
CONTAMINANTS FROM INTERIOR SURFACES PRIOR TO REUSE.
REFER TO OUTSIDE AIR PLENUM CLEANING INSTRUCTION NOTES
ON M-001.
5 PROVIDE AIRFLOW MEASURING STATION.
6 VFD, SEE ELECTRICAL PLANS.
GENERAL NOTES
1. DUCT, PIPING, AND EQUIPMENT LOCATIONS ARE APPROXIMATE
BASED ON EXISTING DRAWINGS AND SITE SURVEY. LOCATIONS
MUST BE VERIFIED IN FIELD AS NECESSARY.
2 PATCH AND SEAL TO MATCH EXISTING ALL BUILDING
PENETRATIONS CREATED DURING DEMOLITION AND NOT
RE-USED.
3 EQUIPMENT, DUCTWORK, AND PIPING IDENTIFIED FOR
DEMOLITION SHALL BE REMOVED TO THE EXTENTS SHOWN
INCLUDING ALL ACCESSORIES AND CONTROLS UNLESS NOTED
OTHERWISE.
4 PROVIDE MANUFACTURER RECOMMENDED CLEARANCE AROUND
ALL EQUIPMENT.
5 MAINTAIN A CLEAR WALKING PATH 3' WIDE BY 80" TALL THROUGH
MECHANICAL ROOM.
6 HOUSEKEEPING PADS UNDER AHUS ARE EXISTING TO REMAIN.
PADS SHALL BE MODIFIED AS NECESSARY TO ACCOMMODATE
NEW UNIT FOOTPRINTS.
7 AHU, DUCT, AND PIPING MUST BE BROKEN DOWN INTO SECTIONS
AND COMPONENTS THAT CAN BE REMOVED THROUGH EXISTING
BUILDING PATHWAYS.
8 USE STOPPLE OR PIPE FREEZE ISOLATION SYSTEM TO PREVENT
HAVING TO DRAIN THE SYSTEM WHEN REPLACING ISOLATION
VALVES. WHERE THIS METHOD IS NOT POSSIBLE, COORDINATE
WITH OWNER FOR SHUTDOWN AND DRAINING OF SYSTEM.
9 THOROUGHLY CLEAN ALL EXISTING TO REMAIN OUTDOOR AIR
PLENUMS THAT ARE SERVING REPLACED AIR HANDLERS.REFER
TO OUTSIDE AIR PLENUM CLEANING INSTRUCTIONS NOTES ON
GENERAL NOTES SHEET M-0#1.
10 INSTALL DUCTWORK A MINIMUM OF THREE TIMES THE MAXIMUM
DIMENSION AWAY FROM EXISTING SPRINKLER HEADS. INSTALL
EQUIPMENT A MINIMUM OF 18 INCHES BELOW SPRINKLERS. IF
DUCTWORK MUST ENCROACH ON THIS DISTANCE, COORDINATE
WITH A QUALIFIED SPRINKLER SYSTEM INSTALLER FOR
RESOLUTION.
11 EQUIPMENT PATHWAYS INTO BUILDING MUST BE APPROVED BY
BUILDING OWNER
SCALE: 1/2" = 1'-0"
AHU-6 SECTION VIEW
GRAPHIC SCALE:
1' 2' 4'0' 1/2" =1'-0"
(E) OA PLENUM
M R
K D
A T
E R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
09/30/2026
/3
/2
E
FO
R
B
/2
F S
VFDVFD VFDVFD
M-402
(E
"x
R A
(E) 36"x72" RLF
(E) 24"x108" OA
(E) 40"x14" RA
(E) 23"/12" SA
22"x56" OA
RM F400
AHU-7
SD 17"/12" SA
23"/12" SA
17"x12" SA
23"/12" SA
(E) 17"/12" SA
(E) 23"/12" SA
(E) 17"/12" SA
(E) OA LOUVER
(E) 3" CHR
(E) 3" CHS
(E) 2 1/2" HWS
(E) 2 1/2" HWR
M-402
(E) FD
AHU-7
(E) 1 1/2" HWR
(E) 1 1/2" HWS
1 1/2" HWR
1 1/2" HWS
P-41
2 1/2" HWR
2 1/2" HWS
3" CHR
3" CHS
RM F400
1" CD
AHU-7
TRANSITION TO (E) OA
PLENUM 24"x108"
36"x72" RLF
(E) 36"x72" RLF
56"x22" OA
(E) 14"x40" RA(E) 40"x20" RA
12"x66" RA
8"x66" RLF
6"x66" OA
(E) 12"/23" SA (E) 1 1/2" HWR
(E) 2 1/2" HWR
1 1/2" HWS
1 1/2" HWR
(E) 1 1/2" HWS
(E) 3" CHS
(E) 3" CHR
3" CHS
3" CHR 2 1/2" HWS
2 1/2" HWR
P-41
(E) FD
(E) ROOM EXHAUST,
550 CFM
1" CD
(E) 1 1/2" HWR
23"/12" SA
12"/23" SA
17"/12" SA17"x12" SA
DRAWN:
CHECK:
SHT. NO.
SHEET TITLE
REV. NO.
DESIGN:
DATE:
COMM NO:
123456
E
D
A
B
C
123456
P a ra g o n P la c e S u it e
R ic h m o n d V
A
.2