2026-0508 59125413.JLM - Plainwell Garage Generator - ADDENDUM 1 DRAWING.pdf
PDF 938 KB Posted
- Attached to
- 591/25413. JLM; Plainwell Garage Generator
- Solicitation number
- RFQ 171 260000000250 3
- Issued by
- Allegan County, Michigan
About this file
This is an Addendum 1 Drawing document for the Plainwell Garage Generator project issued by the Michigan Department of Technology, Management and Budget, Facilities and Business Services Administration, Design and Construction Division, in coordination with Century Facilities Design (CAE). The project involves the addition of a 125-kilowatt generator to the M.D.O.T. Plainwell Garage located at 596 11th Street, Plainwell, Michigan 49080, in Allegan County. The electrical plan drawing (Sheet E2.0) was issued for bid and construction on April 10, 2026, with Addendum 1 issued on May 8, 2026. The drawing provides detailed specifications for the generator equipment pad installation, natural gas line routing and connections, electrical interconnections, and auxiliary systems including an automatic transfer switch (ATS), annunciator panel, emergency stop, and surge protection device (SPD).
The technical specifications require an 8-inch concrete pad with reinforced #5 bars at 12-inch on-center spacing, 4,000 PSI minimum compressive strength, and compliance with ACI 318 and ACI 301 standards. The natural gas supply infrastructure includes a 1-1/2 inch natural gas line routed along the building with gas pressure regulation equipment (Pietro Fiorentini regulator rated at 2 PSIG inlet, 7 inches W.C. outlet), a gas meter upgrade to accommodate 4,361 CFH connected load, and a dirt leg sediment trap. The generator requires coordination with the utility to increase gas service capacity and pressure as necessary. Contractors must submit concrete mix designs from an approved independent testing firm at least 10 working days prior to construction commencement and coordinate engineer inspection of the prepared site before concrete pouring. All exposed gas piping must be painted and supported with stainless steel unistrut supports.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C ra he n
A ve nu e
N E
- G ra nd R ap id s, M
I 4
Te le ph on e:
(6
) 4
-5
F ax
6)
-5
W eb : w w w
.c en tu ry ae .c om
EN
T U R Y
Fa ci lit ie s D es ig n C
A E
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ADAM P. LACH, RA, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
M.D.O.T. PLAINWELL GARAGE
PLAINWELL, MICHIGAN
GENERATOR ADDITION
Know what's below.
before you dig.Call
R
M.D.O.T. PLAINWELL GARAGE
596 11TH STREET
PLAINWELL, MICHIGAN 49080
ALLEGAN COUNTY
SHEET NO.
PROJECT NO:
DWG. SCALE:
DESIGN BY:
DRAWN BY:
NO
DA
TE
RE
VI
SI
ON
S
BY
C ra he n
A ve nu e
N E
- G ra nd R ap id s, M
I 4
Te le ph on e:
(6
) 4
-5
F ax
6)
-5
W eb : w w w
.c en tu ry ae .c om
E N T U R Y
Fa ci lit ie s D es ig n C
A E
MIS032.13
IS
SU
E
FO
R
R
EV
IE
W
AT
H
/ 0
6 /
P L U R I B U E
S U N U M
C I R C U M S P I C E
S I Q U ERE I S PENI NSULAM AMOENA
M
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ADAM P. LACH, RA, DIRECTOR
FACILITIES AND BUSINESS SERVICES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION
P
LA
IN
W
E
LL
, M
IC
H
IG
A N
G E
N E
R A
T O
R A
D D
IT
IO
N
FI
LE
N
O . 5
/2
.J
LM
M D
O T
P
LA
IN
W
E
LL
G A
R A
G E
IS
SU
E
FO
R
R
EV
IE
W
AT
H
/ 1
3 /
IS
SU
E
FO
R
BI
D
CO
NS
TR
UC
TI
ON
AT
H
/ 1
0 /
IS
SU
E
FO
R
BI
D
CO
NS
TR
UC
TI
ON
A
DD
EN
DU
M
AT
H
/ 8 / 2
A. HOLLAND
M. TIPPING
E2.0
AS NOTED
EL
EC
TR
IC
AL
P
LA
N
AutoCAD SHX Text 400A M.F.D
AutoCAD SHX Text
MDP
AutoCAD SHX Text
LP-C
AutoCAD SHX Text
LP-F
AutoCAD SHX Text
RADIATOR ON WEST SIDE
AutoCAD SHX Text
ANNUNCIATOR PANEL
AutoCAD SHX Text
EMERGENCY STOP
AutoCAD SHX Text
ATS
AutoCAD SHX Text
EX. ELECTRICAL METER
AutoCAD SHX Text
PROPOSED GENERATOR LOCATION, 125KW
AutoCAD SHX Text
GENERATOR EQUIPMENT PAD. SEE DETAIL THIS SHEET
AutoCAD SHX Text
ANNUNCIATOR PANEL
AutoCAD SHX Text
ATS
AutoCAD SHX Text
LP-F (AUX. POWER)
AutoCAD SHX Text
EMERGENCY STOP
AutoCAD SHX Text M
AutoCAD SHX Text
EX. OVER HEAD RISER
AutoCAD SHX Text
EX. UTILITY OVERHEAD LINES
AutoCAD SHX Text
AutoCAD SHX Text
ATS
AutoCAD SHX Text
MDP
AutoCAD SHX Text
BOILER ROOM
AutoCAD SHX Text
MENS LOCKERS
AutoCAD SHX Text
STORAGE #3
AutoCAD SHX Text
PARKING GARAGE
AutoCAD SHX Text
1-1/2" NG LINE TO GENERATOR ROUTE NATURAL GAS ALONG BUILDING
AutoCAD SHX Text M
AutoCAD SHX Text
EX. GAS UTILITY SUPPLY
AutoCAD SHX Text
TO EX. UTILITY POLE
AutoCAD SHX Text
UPGRADE GAS METER BY GAS SERVICE SEE DETAILS
AutoCAD SHX Text
EXISTING STAIR COLUMN
AutoCAD SHX Text
GAS PRESSURE REGULATOR EQUAL TO PIETRO FIORENTINI 2 PSIG INLET, 7" W.C. OUTLET
AutoCAD SHX Text
1-1/2" UG NG TO GENERATOR SEE DETAIL
AutoCAD SHX Text
AutoCAD SHX Text GENERAL NOTES: : 1. SEE SINGLE LINE DIAGRAM AND GENERATOR INTERCONNECTION RISER DIAGRAM ON SEE SINGLE LINE DIAGRAM AND GENERATOR INTERCONNECTION RISER DIAGRAM ON SHEET E6.0 FOR CONDUIT AND WIRE SIZES AND QUANTITIES.
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text PLAN NOTES: - (SYMBOL DENOTES PLAN NOTE) : - (SYMBOL DENOTES PLAN NOTE) - (SYMBOL DENOTES PLAN NOTE) 1. MOUNT SPD ABOVE EXISTING MAIN FUSED DISCONNECT. MOUNT SPD ABOVE EXISTING MAIN FUSED DISCONNECT. 2. COORDINATE ENGINEER INSPECTION OF PREPARED SITE BEFORE POUR OF CONCRETE. COORDINATE ENGINEER INSPECTION OF PREPARED SITE BEFORE POUR OF CONCRETE.
AutoCAD SHX Text
1. PROVIDE PVC SLEEVES FOR ALL PENETRATIONS THROUGH GENERATOR EQUIPMENT PAD. SEE PROVIDE PVC SLEEVES FOR ALL PENETRATIONS THROUGH GENERATOR EQUIPMENT PAD. SEE ELECTRICAL FOR CONDUIT SIZES AND QUANTITIES. CONFIRM GENERATOR EQUIPMENT PAD SIZE AND SLEEVE LOCATIONS WITH ENGINEER BASED ON GENERATOR SUBMITTAL DRAWINGS.
AutoCAD SHX Text
NOTES
AutoCAD SHX Text 10"
AutoCAD SHX Text 8"
AutoCAD SHX Text 8"
AutoCAD SHX Text 8"
AutoCAD SHX Text
GENERATOR + 12" (TYP.)
AutoCAD SHX Text
3" CLR.
AutoCAD SHX Text #5 BARS @ 12" o.c.
AutoCAD SHX Text
#5 BARS CONTINUOUS, T. & B. AT SLAB PERIMETER
AutoCAD SHX Text
3/4" CHAMFER (TYP.)
AutoCAD SHX Text 6"
AutoCAD SHX Text
GRADE
AutoCAD SHX Text
T/PAD EL.
AutoCAD SHX Text
%%USECTION VIEW
AutoCAD SHX Text CONCRETE SPECIFICATIONS: 1. THE FOLLOWING REFERENCE DOCUMENTS, THEIR COMMENTARIES, AND THE STANDARDS REFERENCED THEREIN, APPLY TO THE FOLLOWING REFERENCE DOCUMENTS, THEIR COMMENTARIES, AND THE STANDARDS REFERENCED THEREIN, APPLY TO DESIGN, FABRICATION, AND CONSTRUCTION PRACTICES TO BE ADHERED TO WITH REGARD TO THE WORK SHOWN ON THE DRAWINGS: A. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318, LATEST EDITION). B. SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301, LATEST EDITION). 2. COLD WEATHER PROTECTION SHALL BE IN ACCORDANCE WITH ACI 306, IN HOT WEATHER, COMPLY WITH ACI 305. COLD WEATHER PROTECTION SHALL BE IN ACCORDANCE WITH ACI 306, IN HOT WEATHER, COMPLY WITH ACI 305. 3. SUBMIT (4) COPIES OF THE PROPOSED MIX DESIGN PREPARED BY AN APPROVED INDEPENDENT TESTING FIRM AT LEAST SUBMIT (4) COPIES OF THE PROPOSED MIX DESIGN PREPARED BY AN APPROVED INDEPENDENT TESTING FIRM AT LEAST (10) WORKING DAYS PRIOR TO THE PROPOSED START OF CONSTRUCTION. SELECT PROPORTIONS ACCORDING TO ACI 301, SECTION 3.9. APPROVAL OF THE MIX IS REQUIRED PRIOR TO PLACEMENT OF CONCRETE. 4. PROVIDE (3/4) INCH BEVELS ON ALL PERMANENTLY EXPOSED EDGES OF CONCRETE SURFACES. PROVIDE (3/4) INCH BEVELS ON ALL PERMANENTLY EXPOSED EDGES OF CONCRETE SURFACES. 5. MINIMUM COMPRESSIVE STRENGTH (F'c): 4,000 PSI. MINIMUM COMPRESSIVE STRENGTH (F'c): 4,000 PSI. 6. MINIMUM CEMENT CONTENT: MINIMUM CEMENT CONTENT: (6.0) SACKS PER CUBIC YARD FOR 4,000 PSI CONCRETE. CEMENT PER ASTM STANDARD C-150 OR ASTM STANDARD C-595. USE 20% MAXIMUM FLY ASH BY WEIGHT. 7. MAXIMUM WATER TO CEMENT RATIO: MAXIMUM WATER TO CEMENT RATIO: (5) GALLONS PER SACK (0.44). 8. ENTRAINED AIR: 5% TO 7% ENTRAINED AIR: 5% TO 7% 9. AGGREGATES: AGGREGATES: COARSE ASTM STANDARD C-33 MDOT 6A OR 6AA; FINE ASTM STANDARD C-33 MDOT SAND 2NS. 10. WELDED WIRE FABRIC (FLAT SHEET) SHALL CONFORM TO ASTM STANDARD A-496 AND A-497 REQUIREMENTS. WELDED WIRE FABRIC (FLAT SHEET) SHALL CONFORM TO ASTM STANDARD A-496 AND A-497 REQUIREMENTS. 11. AIR ENTRAINING ADMIXTURES: AIR ENTRAINING ADMIXTURES: ASTM C260 NEUTRALIZED VINSOL RESIN COMPATIBLE WITH SUPERPLASTICIZER (IF USED). 12. SUPERPLASTICIZER ADMIXTURES: ASTM C494 TYPE F OR G. SUPERPLASTICIZER ADMIXTURES: ASTM C494 TYPE F OR G. 13. WATER REDUCER/RETAINERS CONFORMING TO C-494, TYPE A OR D. WATER REDUCER/RETAINERS CONFORMING TO C-494, TYPE A OR D. 14. POZZOLONIC ADMIXTURES: ASTM C618, TYPE F, LOSS ON IGNITION LIMITED TO 4%. POZZOLONIC ADMIXTURES: ASTM C618, TYPE F, LOSS ON IGNITION LIMITED TO 4%. 15. CONCRETE CURING: CONCRETE CURING: WET BURLAP CURE FOR 7 DAYS PER ACI RECOMMENDED PRACTICE. 16. ALL HORIZONTAL SURFACES TO BE BROOM FINISHED. ALL VERTICAL SURFACES TO BE SMOOTH FORM FINISH. PATCH ALL HORIZONTAL SURFACES TO BE BROOM FINISHED. ALL VERTICAL SURFACES TO BE SMOOTH FORM FINISH. PATCH HOLIDAYS AND REMOVE FINS. SNAP FORM TIES AND PATCH TIE HOLES WITH GROUT ON ALL EXPOSED SURFACES.
AutoCAD SHX Text
GENERATOR + 12" (TYP.)
AutoCAD SHX Text
GENERATOR + 12" (TYP.)
AutoCAD SHX Text
3" CLR. (TYP.)
AutoCAD SHX Text #5 BARS @ 12" o.c., E.W.
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
%%UPLAN VIEW
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
SLAB
AutoCAD SHX Text
12" MIN COMPACTED GRANULAR FILL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
8" CONCRETE PAD
AutoCAD SHX Text
AutoCAD SHX Text
CONC. PAD
AutoCAD SHX Text GAS PRESSURE REGULATOR EQUAL TO PIETRO FIORENTINI 2 PSIG INLET, 10" W.C. OUTLET 1665 CFH
AutoCAD SHX Text PROVIDE STAINLESS STEEL UNISTRUT SUPPORTS AS NEEDED TO SUPPORT AND PROTECT PIPE. PAINT EXPOSED GAS PIPING
AutoCAD SHX Text
1-1/2" NG (2 PSIG) FROM METER
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
FLEXIBLE CONNECTION
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
GENERATOR PIPING DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
GAS METER DETAIL
AutoCAD SHX Text DIRT LEG (SEDIMENT TRAP) INSTALLED IN BOTTOM RUN OPENING OF TEE AS SHOWN. MINIMUM 6" ABOVE GRADE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GAS METER
AutoCAD SHX Text
4361 CFH CONNECTED LOAD
AutoCAD SHX Text
ROUTE 1-1/2" NATURAL GAS LINE ALONG BUILDING
AutoCAD SHX Text
1-1/2" NG (2 PSIG) TO GENERATOR
AutoCAD SHX Text
NG TO BUILDING
AutoCAD SHX Text
2" NG (2 PSIG)
AutoCAD SHX Text
GAS SERVICE CAPACITY AND PRESSURE TO BE INCREASED AS NECESSARY BY UTILITY
AutoCAD SHX Text GAS PRESSURE REGULATOR EQUAL TO PIETRO FIORENTINI 2 PSIG INLET, 7" W.C. OUTLET APPROX. 2700 CFH CAPACITY
AutoCAD SHX Text
BALL VALVE (TYPICAL)
AutoCAD SHX Text
GAS SUPPLY BY UTILITY
AutoCAD SHX Text
3" FLG (VIF)
AutoCAD SHX Text
GAS COCK (TYPICAL)
AutoCAD SHX Text
NOTES: PAINT EXPOSED GAS PIPING PER SPECIFICATIONS
AutoCAD SHX Text
SCALE: NO SCALE
AutoCAD SHX Text
EQUIPMENT PAD DETAIL
| CS |
| Sheets and Views |
| CS |
| E1.0 |
| Sheets and Views |
| E1.0 |
| E2.0 |
| Sheets and Views |
| E2.0 |
| E6.0 |
| Sheets and Views |
| E6.0 |
PLAINWELL SITE PLAN - REFERANCE DRAWING