About this file
This construction document set consists of electrical design specifications and plans for the Kellogg Elementary School gymnasium lighting and air conditioning project, prepared by KingScott Associates Inc. for Gull Lake Community Schools located in Richland, Michigan. The project encompasses the demolition of existing light fixtures and associated electrical infrastructure within the gymnasium (Room 1131) and installation of new LED high-bay lighting fixtures with integrated 0-10V dimming drivers. The scope includes new electrical service coordination with Consumers Energy, installation of conduit, conductors, wiring devices, panelboards, surge protection devices, lighting control systems compliant with ASHRAE 90.1-2013 with Michigan amendments, and fire alarm system integration. The construction documents indicate an estimation status of "on hold" with issuance dates of December 19, 2025, January 20, 2026, and April 9, 2026.
The electrical specifications require the contractor to procure all building permits and inspections while performing work in accordance with the Michigan Electrical Code and National Electrical Code standards. New LED high-bay fixtures are specified as Lithonia IBE-L24-15000LM-ATC-MD-MVOLT fixtures with exit signage by the same manufacturer. The project utilizes a 400-amp main distribution panel (MDP) fed from utility service at 208Y/120V, 3-phase, 4-wire configuration, with multiple distribution panels and branch panels throughout the facility. Lighting control devices are mandated to be manufactured by N-Light unless otherwise noted, and all panelboards must be fully rated square D NQOD units for 208/120V applications. The contractor must provide shop drawings, operation manuals, and closeout documentation including software licenses and maintenance materials upon completion of work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2026_04_09 GLCS Richland Gym A_C.pdf | ||
| Bid Advertisement Apr 2026 Sink Fund.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
400500
200100
KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC
JOB NO.
SHEET TITLE
SHEET NO.
ISSUANCES DATE
N
P L
E A
S E
R E
C Y
C L
E
T H
E S
E D
R A
W
IN
G S
A N
D T
H E
W O
R K
R E
P R
E S
E N
T E
D T
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F A
N D
C
O P
Y R
IG
H
T
K
IN
G
S C
O T
T A
S S
O C
IA
T
E S
A
D
M A
Y N
O T
B E
U S
E D
O R
R E
P R
O D
U C
W
IT
H
O U
T P
E R
M
IS
S
IO
N
L A
S T
P R
IN
T
E D ljh
CLIENT:
GULL LAKE COMMUNITY SCHOOLS
10100 EAST 'D' AVE.
RICHLAND, MI 49083
P. (269) 548-3400
ARCHITECT & CIVIL ENGINEER:
KINGSCOTT ASSOCIATES INC.
950 TRADE CENTRE WAY, SUITE 130
PORTAGE, MI 49002
P. (800) 632-7815
CONSTRUCTION MANAGER:
MEP ENGINEER:
IGNYTE
38 COMMERCE AVE. SW
SUITE 450
GRAND RAPIDS, MI 49503
DIRECTORY
MILLER DAVIS
1029 PORTAGE ST.
KALAMAZOO, MI 49001
P. (269) 345-3561
PORTAGE | CHELSEA | GRAND RAPIDS | DETROIT
Gull Lake Community Schools
/9
/2
:0
:2
A
M
A u to d e s k D o c s
/G L C
S
S in k in g F u n d /G
L C
S K
E L L O
G G
E le m A rc h r2
.r v t 2288.77
TITLE SHEET
G1
N . 4
0t h
St re et H ic ko ry C or ne rs , M
I 4
G ul l L a ke C o m m un ity S ch o o ls
K E L L O
G G
S
IN
K
IN
G
F U
N D
Gull Lake Community Schools
KELLOGG 2026 SINKING FUND
CONSTRUCTION DOCUMENTS
KELLOGG ELEMENTARY
9594 N. 40th STREET
APRIL 09, 2026
SHEET INDEX
GENERAL
G1 TITLE SHEET
ARCHITECTURAL
A0.1 COMPOSITE PLAN
ELECTRICAL
E000 ELECTRICAL SYMBOLS AND GENERAL NOTES
ED110 FIRST FLOOR ELECTRICAL DEMOLITION PLAN
E001 ELECTRICAL SPECIFICATIONS
E210 FIRST FLOOR LIGHTING PLAN
E401 ELECTRICAL ONE-LINE DIAGRAM
CONSTRUCTION DOCUMENTS 04/09/2026
CG
SPEECH
MECHANICAL
RECEIVING
CAFETERIA
SERVERY
KITCHEN
GYMNASIUM
CLASSROOM
BAND
CORRIDOR
MEN
WOMEN
CLASSROOM
CONFERENCE
AUX. GYM
OFFICE
WOMEN
CORRIDOR
CLASSROOM
CLASSROOM
MEN
CLASSROOM
STAFF ROOM
STORAGE
STORAGE
ITIN. OFFICE
CONFERENCE
PRINCIPAL
210 RECEPTIONIST
HEALTH
WKRM
CORRIDOR
STEAM
STORAGE
SPEECH
STORAGE
CORRIDOR
STORAGE
MUSIC
YOUNG 5's
YOUNG 5's
KINDERGARTEN
KINDERGARTEN
ART
ECSE
KINDERGARTEN
KINDERGARTEN
KINDERGARTEN
CORRIDOR
CORRIDOR
CORRIDOR
SPEECH
ITIN OFFICE
CORRIDOR
CORRIDOR
RESOURCE
1st GRADE
1st GRADE
419 1st GRADE
2nd GRADE
2nd GRADE
2nd GRADE
2nd GRADE
1st GRADE
1st GRADE
SPANISH
TITLE ONE
TITLE ONE
CORR
WKRM
T.
MEDIA CENTER
OFFICE
OFFICE
2nd GRADE
CORRIDOR
STORAGE
1. INDICATES CONSTRUCTION DOCUMENT ROOM NUMBERS.XX
COMPOSITE PLAN GENERAL NOTES:
AREA OF WORK
400500
200100
KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC
JOB NO.
SHEET TITLE
SHEET NO.
ISSUANCES DATE
N
P L
E A
S E
R E
C Y
C L
E
T H
E S
E D
R A
W
IN
G S
A N
D T
H E
W O
R K
R E
P R
E S
E N
T E
D T
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F A
P
Y R
IG
H
T
K
IN
G
S C
O T
T A
S S
O C
IA
T
D
M A
Y N
O T
B E
U S
E D
O R
R E
P R
O D
U C
H
O U
T P
E R
M
IS
S
IO
N
L A
S T
P R
IN
T
E D ljh
PORTAGE | CHELSEA | GRAND RAPIDS | DETROIT
Gull Lake Community Schools
/9
/2
:0
:3
A
M
A u to d e s k D o c s
/G L C
S
S in k in g F u n d /G
L C
S K
E L L O
G G
E le m A rc h r2
.r v t 2288.77
COMPOSITE PLAN
A0.1
N . 4
0t h
St re et H ic ko ry C or ne rs , M
I 4
G ul l L a ke C o m m un ity S ch o o ls
K E L L O
G G
S
IN
K
IN
G
F U
N D
1/16" = 1'-0"
COMPOSITE PLAN
CONSTRUCTION DOCUMENTS 04/09/2026
ELECTRICAL ABBREVIATION LIST
ABBREVIATION DESCRIPTION
A
AF
AFCI
A.F.F.
AIC
AL
AR
AT
ATS
AUX
BKR
BPS
C
CB
CKT
CT
DEMO
DIM
DISC
DP
DS
DWG
EBU
EC
ELEC
EM/ EMERG
EMT
EO
EPO
EWC
EXIST
EXT
FA
FLA
FLR
FOH
FSEC
FU
G/GRD/EG
GFCI
GFP
HOA
HP
HV
HZ
IG
JB
KV
KVA
KW
KWH
LA
LP
LDP
AMPERES
AMPERES FRAME (BREAKER RATING)
ARC FAULT CIRCUIT INTERRUPTER
ABOVE FINISH FLOOR
AMPS INTERRUPTING CAPACITY
AUDIENCE LEFT
AUDIENCE RIGHT
AMPERS TRIP (BREAKER SETTING)
AUTOMATIC TRANSFER SWITCH
AUXILIARY
BREAKER
BOLTED PRESSURE SWITCH
CONDUIT
CIRCUIT BREAKER
CIRCUIT
CURRENT TRANSFORMER
DEMOLITION
DIMENSION
DISCONNECT
DISTRIBUTION PANEL
DOWNSTAGE
DRAWING
EMERGENCY BATTERY UNIT
ELECTRICAL CONTRACTOR
ELECTRICAL
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICALY OPERATED
EMERGENCY POWER OFF
ELECTRIC WATER COOLER
EXISTING
EXTERIOR
FIRE ALARM
FULL LOAD AMPS
FLOOR
FRONT OF HOUSE
FOOD SERVICE EQUIPMENT
FUSE
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
HAND-OFF-AUTO
HORSEPOWER
HIGH VOLTAGE
HERTZ
ISOLATED GROUND
JUNCTION BOX
KILOVOLT
KILOVOLT - AMPERES
KILOWATT
KILOWATT - HOURS
LIGHTING ARRESTOR
LIGHTING PANEL
LIGHTING DISTRIBUTION PANEL
MAX
MCB
MCC
MDP
MECH
MIN
MISC.
MLO
MTD
MTG
MTR
N
NC
NEC
NF
NIC
NL
NO
NTS
OC
OFCI
OFOI
P
PB
PH
PT
PDP
RECEPT.
RCP
RDP
RP
RSC
SCHED
SW
SWBD
SWGR
TB
TELECOM
TR
TTP
TYP
UNO
US
V
W
WG
WP
XFMR
XP
(E)
(R)
MAXIMUM
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MECHANICAL
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MOUNTED
MOUNTING
MOTOR
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NON-FUSIBLE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OWNER FURNISHED,
CONTRACTOR INSTALLED
OWNER FURNISHED,
OWNER INSTALLED
POLE
PUSHBUTTON STATION
PHASE
POTENTIAL TRANSFORMER
POWER DISTRIBUTION PANEL
RECEPTACLE
RECEPTACLE
RECEPTACLE DISTRIBUTION PANEL
RECEPTACLE PANEL
RIGID STEEL CONDUIT
SCHEDULE
SWITCH
SWITCHBOARD
SWITCHGEAR
TERMINAL BOX
TELECOMMUNICATIONS
TAMPER RESISTANT
TELEPHONE TERMINAL BACKBOARD
TYPICAL
UNLESS OTHERWISE NOTED
UPSTAGE
VOLTS
WIRE OR WATTS
WIRE GUARD
WEATHERPROOF
TRANSFORMER
EXPLOSION PROOF
EXISTING
RELOCATED
ELECTRICAL SYMBOL LIST
SYMBOL DESCRIPTION
LIGHTING FIXTURE - ARCHITECTURAL TROFFER
EMERGENCY LIGHTING FIXTURE
LIGHTING FIXTURE - PENDANT
WALL MOUNTED LIGHTING FIXTURE
LIGHTING FIXTURE
LIGHTING TRACK OR ROPE LIGHT
TRACK LIGHTING FIXTURE
EMERGENCY LIGHTING UNIT
POLE MOUNTED LIGHTING FIXTURE
POLE MOUNTED LIGHTING FIXTURE - POST TOP
BOLLARD LIGHTING FIXTURE
EXIT LIGHTING FIXTURE WITH DIRECTIONAL
ARROWS (SHADED AREA INDICATES FACE)
EXIT LIGHTING FIXTURE WITH DIRECTIONAL
ARROWS (SHADED AREA INDICATES FACE)
EXIT LIGHTING FIXTURE - WALL MOUNTED
SINGLE POLE TOGGLE SWITCH
TWO POLE TOGGLE SWITCH
3 WAY TOGGLE SWITCH
4 WAY TOGGLE SWITCH
KEY OPERATED SWITCH
DIMMER SWITCH
PILOT SWITCH
OCCUPANCY SENSOR DEVICE - CEILING
SIMPLEX / DUPLEX RECEPTACLE
SIMPLEX / DUPLEX RECEPTACLE CONTROLLED BY
AUTOMATIC CONTROL DEVICE / SYSTEM
QUAD RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE (SIMILAR FOR
TAMPER RESISTANT, QUADS, EMERGENCY AND GFI
RECEPTACLES)
DUPLEX RECEPTACLE-GROUND FAULT CIRCUIT
INTERRUPTER
DUPLEX EMERGENCY RECEPTACLE
CEILING MOUNTED
DUPLEX RECEPTACLE
SPECIAL RECEPTACLE - REFER TO ELECTRICAL
STANDARD SCHEDULES
MULTI-OUTLET RACEWAY - LEGRAND AL3300 OR EQUAL
POKE-THROUGH ASSEMBLY - LEGRAND
EVOLUTION SERIES OR EQUAL
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONTROL PANEL
VARIABLE FREQUENCY DRIVE
MOTOR
MANUAL CONTROLLER
MAGNETIC CONTROLLER
COMBINATION MAGNETIC CONTROLLER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
PUSH BUTTON STATION
AUTOMATIC DOOR CONTROLLER
AUTOMATIC DOOR PUSH PAD OPERATOR
GROUND ROD
GROUND CONNECTION
CONDUIT SLEEVE WITH BUSHINGS; LENGTH AS REQUIRED
"X" INDICATES CONDUIT SIZE
CONDUIT STUB - UP/DOWN
EMPTY BOX FOR FUTURE
TELECOMMUNICATION OUTLET
EMPTY BOX FOR FUTURE TELECOMMUNICATION
OUTLET MOUNTED 4" ABOVE COUNTERTOP
EMPTY BOX FOR FUTURE CEILING MOUNTED
TELECOMMUNICATION OUTLET
TELECOMMUNICATION OUTLET
"X" INDICATES TYPE
SPEAKER
SPEAKER - WALL MOUNTED
MICROPHONE
VOLUME CONTROL
SIGNALING BELL
SINGLE FACE CLOCK - CEILING MOUNTED
SINGLE FACE CLOCK - WALL MOUNTED
DOUBLE FACE CLOCK - CEILING MOUNTED
DOUBLE FACE CLOCK - WALL MOUNTED
P
PT
FB
CP
VFD
CB
DP
PP
X
X
S
S
MIC
VC
B
USB RECEPTACLE
GENERATOR TRANSFER DEVICEGTD
REMOTE GENERATOR ANNUNCIATOR PANELRGP
AUTOMATIC TRANSFER SWITCHATS
SWITCHBOARD
BRANCH CIRCUIT PANEL BOARD - 208/120V
TRANSFORMER
DISTRIBUTION PANEL - 208/120V
SECURITY CAMERA
MOTION DETECTOR
SECURITY KEY SWITCH
DOOR CONTACT
KEY PAD
CARD READER
CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
MANUALLY/ OPERATED
SWITCH
AUTOMATIC OR MANUAL TRANSFER
SWITCH
FUSE
TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
LIGHTNING ARRESTOR
PANELBOARD
"X" INDICATES PANELBOARD NAME
GROUND
SECURITY KEY INTERLOCK
ENGINE GENERATOR
UTILITY METER
AMMETER
VOLTMETER
AMMETER SWITCH
VOLTMETER SWITCH
SURGE PROTECTIVE DEVICE
TIME DELAY RELAY
THERMAL OVERLOAD RELAY
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
N.O. PUSH BUTTON SINGLE CIRCUIT
N.C. PUSH BUTTON SINGLE CIRCUIT
GROUND BUS
MD
K
DC
KP
CR
X
K
G
M
A
V
AS
VS
SPD
TDR
GB
DURESS PUSH BUTTON STATION
DELAYED EGRESS
DB
DE
REQUEST TO EXIT STATIONREX
MANUAL FIRE ALARM PULL STATION
SMOKE DETECTOR
REMOTE TEST STATION (FOR DUCT DETECTOR)
FIRE ALARM BELL
NOTIFICATION APPLIANCE - WALL MOUNT SPEAKER/STROBE
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
F
SD
RT
F
F
TS
FS
FACP
FAA
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANELNAC
R E
F E
R T
O E
L E
C T
R
IC
L
T
A N
D A
R D
S C
H E
D U
L E
S
DIMMER OCCUPANCY SENSOR SWITCH
LOW VOLTAGE DIMMER SWITCH
POWER POLE - WIREMOLD TYPE
F NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER/STROBE
LIGHTING CONTROL DEVICE - REFER TO LIGHTING
CONTROL SCHEDULE
LC
K
D
OS
LV
GFI
USB
CLG
FLOOR BOX ASSEMBLY - LEGRAND
EVOLUTION SERIES OR EQUAL
TOUCH SCREEN SWITCHTS
OS
OCCUPANCY SENSOR DEVICE - WALLOS
PC PHOTOCELL DEVICE - REFER TO ZONES SHOWN ON
PLANS
EQ
EQUIPMENT CONNECTION - REFER TO ELECTRICAL
FEEDER AND PANEL SCHEDULE FOR BREAKER AND
CONDUCTOR SIZE/QUANTITY
J JUNCTION BOX
EMERGENCY POWER OFF BUTTON
V NOTIFICATION APPLIANCE - CEILING MOUNT STROBE
NOTIFICATION APPLIANCE - WALL MOUNT STROBEV
BRANCH CIRCUIT PANEL BOARD - 480/277V
DISTRIBUTION PANEL - 480/277V
CARBON MONOXIDE DETECTORCO
HEAT DETECTORHD
BEAM DETECTORBD
DUCT DETECTORDD
SMOKE DETECTOR - ELEVATOR TYPE; CONNECT TO FIRE ALARM
SYSTEM AND ELEVATOR CONTROL PANEL
SD
E
SPRINKLER VALVE MONITOR SWITCHOSY
SMOKE DAMPERSD
MAGNETIC DOOR HOLDERDH
S NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER
NOTIFICATION APPLIANCE - WALL MOUNT SPEAKERS
FIRE ALARM BATTERY CABINETBATT
EXIT FIXTURE-BACK
MOUNTED BOTTOM OF EXIT
SIGN TO BE 4" ABOVE TOP OF
DOOR FRAME
EXIT
EXIT
1' -6
EXIT
A/C SUPPLY
DIFFUSER
90" MAX (IBC)
4' -0
5"
8' -6
EXIT-CEILING MOUNTED
EXIT-FIXTURE END
MOUNTED
NFPA 72 AUDIBLE APPLIANCE 6" MIN
BELOW FINISHED CEILING
EMERGENCY
BATTERY
FIXTURE
ABOVE FINISHED FLOOR
AUDIBLE 80" MIN (IBC)
CEILING HEIGHTS LESS THEN 86" VISUAL
LENS MOUNTING HEIGHT WILL BE WITHIN 6"
OF THE CEILING
FINISHED CEILING
AUDIO/VISUAL &
VISUAL ONLY
DEVICES
SYNCHRONIZE MORE THAN
TWO APPLIANCES IN ANY
FIELD OF VIEW
MANUAL PULL STATION
AUDIBLE
ONLY
'-8
DOOR WIDTH LESS THEN 3'-0"
(MODIFY FOR DIFFERENT
DOOR WIDTHS)
FINISHED FLOOR
O R
A P
P R
O V
E D
F R
O M
A H
J
M
IN
B
O V
E F
IN
IS
H E
D F
L O
O R
CEILING MOUNTED SMOKE/HEAT
DETECTOR
3'-0" MIN 4"
NOTES:
1. INSTALL ELECTRICAL DEVICES AT MOUNTING HEIGHTS NOTED ABOVE UNLESS OTHERWISE NOTED ON PLANS. COORDINATE WITH ALL OTHER DISCIPLINES PRIOR TO INSTALL.
2. VISUAL MOUNTING APPLIANCE MOUNTING HEIGHT IN SLEEPING ROOMS:
A. MINIMUM DISTANCE IN SLEEPING ROOMS IS 24" FROM CEILING TO THE TOP OF LENS FOR 110cd STROBES WITHIN 16' OF PILLOW
B. 177cd STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING, THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER
7' -6
(M
IN
(M
A X
1' -0
"4"
M A
X
DO NOT INSTALL HEAT DETECTOR IN
SHADED AREA
WALL MOUNTED
SMOKE/HEAT
DETECTOR
MAGNETIC
DOOR
HOLDER
FINISHED WALL
SWITCHBANK
AUTOMATIC DOOR OPERATOR PUSH
BUTTON
RECEPTACLE, DATA JACK OR
TELEPHONE JACK
3'-0"
5' MAX TO EXIT DOOR
4' -0
4"
7' -6
ELECTRICAL DEVICE TYPICAL MOUNTING HEIGHTS
6' -6
BRANCH CIRCUIT PANELBOARDS
DISCONNECT SWITCH
5' -0
KINGSCOTT ASSOCIATES INC. PORTAGE, CC
JOB
SHEET
TITLE
SHEET
NO.
ISSUANCE DATE
N
P L
E A
S E
R E
C Y
C L
E
T H
E S
E D
R A
W
IN
G S
A N
D T
H E
W O
R K
R E
P R
E S
E N
T E
D T
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F A
P
Y R
IG
H
T
K
IN
G
S C
O T
T A
S S
O C
IA
T
D
M A
Y N
O T
B E
U S
E D
O R
R E
P R
O D
U C
H
O U
T P
E R
M
IS
S
IO
N
L A
S T
P R
IN
T
E D ljh
PORTAGE | CHELSEA | GRAND RAPIDS |
Gull Lake Community Schools
/8
/2
:5
:0
A
M
A u to d e s k D o c s
/G L C
S
S in k in g F u n d /2
.1
K
G A
G
U L L L
A K
E K
E L L O
G G
E L E
M E
N T
A R
Y G
Y M
C O
O L
IN
G M
E P
.r v t
2288.77
ELECTRICAL SYMBOLS AND
GENERAL NOTES
E000
N th S tr e e t
H ic ko ry
C o rn e rs
M
I
G u ll
L a k e
C o m m u n it y S c h o o ls
K E
L L
O G
G
S
IN
K
IN
G
F U
N D
ESTIMATION
ON HOLD
CONSTRUCTION DOCUMENTS
12/19/2025
01/20/2026
04/09/2026
NOTE: SOME SYMBOLS AND ABBREVIATIONS SHOWN
MAY NOT APPLY TO THIS PROJECT.
ELECTRICAL SPECIFICATION
1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.
2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.
3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY FUNCTIONAL ELECTRICAL SERVICE.
4. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.
5. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.
6. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:
A. CONDUIT.
B. CONDUCTORS.
C. WIRING DEVICES INCLUDING COVERPLATES.
D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.
E. PANELBOARDS. AND SWITCHBOARDS
F. TRANSFORMERS.
G. SURGE PROTECTION DEVICES
H. POWER METERS.
I. INTERIOR LIGHT FIXTURES.
J. EXTERIOR LIGHT FIXTURES INCLUDING SITE POLES.
K. LIGHTING CONTROL SYSTEM AND DEVICES.
L. FIRE ALARM SYSTEM.
7. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.
8. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.
9. PROVIDE LAMACOID LABELS FOR:
A. PANELBOARDS AND SWITCHBOARDS.
B. TRANSFORMERS.
C. DISCONNECT SWITCHES.
D. VARIABLE FREQUENCY DRIVES.
E. LIGHTING CONTROL PANELS. LABEL SHALL INDICATE ROOMS CONTROLLED.
10. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.
11. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:
A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.
B. OUTDOORS: RIGID GALVANIZED STEEL.
C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.
D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.
12. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.
13. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.
14. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS.
15. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING.
16. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.
17. EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-EMERGNECY CIRCUITS.
18. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUITS OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR VOLTAGE DROP.
19. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.
20. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.
21. PANELBOARDS SHALL BE FULLY RATED, SERIES RATED PANELS ARE NOT ACCEPTABLE. HAVE HINGED SWING DOOR-IN-DOOR. LOAD CENTERS ARE NOT ACCEPTABLE. SQUARE D NQOD OR EQUAL FOR
208/120V BRANCH PANELBOARDS. SQUARE D NF OR EQUAL FOR 480/277V PANELBOARDS. PROVIDE TYPED PANELBOARD CIRCUIT LABEL CARDS. UPDATE ALL EXISTING LABEL CARDS AS REQUIRED.
22. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.
23. ALL FLOOR MOUNTED EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PAD.
24. RECEPTACLES SHALL BE TAMPER-RESISTANT EXTRA HEAVY DUTY GRADE, 20AMP MINIMUM. WHITE IN COLOR UNLESS NOTED OTHERWISE.
25. ALL DEVICE COVERS SHALL MATCH DEVICE COLOR UNLESS STAINLESS STEEL COVERS ARE SPECIFIED.
26. WEATHERPROOF RECEPTACLE COVERS SHALL BE METAL, WHILE-IN-USE TYPE.
27. SWITCHES SHALL BE HEAVY DUTY GRADE, 20 AMP, QUIET TYPE, WHITE UNLESS NOTED OTHERWISE.
28. LIGHTING CONTROL DEVICES SHALL BE MANUFACTURED BY N-LIGHT, UNLESS NOTED OTHERWISE.
29. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013 WITH MICHIGAN AMENDMENTS.
30. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED.
INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL
INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND
LOCAL CODES.
MIF CO H E IGT AAT NS
No.
6201060604
JONATHAN
RUMOHR
ENGINEER
PART 1 - GENERAL
1. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM
INVOLVED IS NOT PARTICULARLY MENTIONED. INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK
INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE
AND LOCAL CODES.
2. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.
3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.
4. DO NOT INTERRUPT EXISTING ELECTRICAL SERVICE TO FACILITIES WITHOUT WRITTEN PERMISSION BY OWNER. COORDINATE WORK WITH EXISTING
ELECTRICAL SERVICES WITH OWNER AND UTILITY COMPANY.
5. ARRANGE TO PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR SCOPE OF WORK.
6. PROVIDE NEW ELECTRICAL SERVICES FROM UTILITY COMPANY AS DIRECTED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A
FULLY FUNCTIONAL ELECTRICAL SERVICE.
7. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:
A. CONDUIT
B. CONDUCTORS
C. WIRING DEVICES, INCLUDING COVER PLATES
D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES
E. PANELBOARDS AND SWITCHBOARDS
F. SURGE PROTECTION DEVICES
G. INTERIOR AND EXTERIOR LIGHTING FIXTURES, INCLUDING SITE POLES
H. LIGHTING CONTROL SYSTEM AND DEVICES
I. FIRE ALARM SYSTEM
PART 2 - EXECUTION
1. PROVIDE SCHEDULE FOR ELECTRICAL INSTALLATION WORK TO OWNER AND ARCHITECT FOR MAJOR MILESTONE DATES.
2. COORDINATION DRAWINGS; PROVIDE COORDINATION DRAWINGS FOR FOLLOWING INSTALLATIONS:
A. LARGE INDOOR EQUIPMENT INSTALLATIONS.
B. LARGE OUTDOOR EQUIPMENT INSTALLATIONS.
3. DEMOLITION WORK
A. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC., ASSOCIATED WITH DEMOLISHED EQUIPMENT.
B. REMOVE ALL ABANDONED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.
C. PATCH, REPAIR AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS OR FLOORS TO MATCH EXISTING CONDITION. MAINTAIN ALL FIRE
RATINGS OF WALLS AND DOORS.
D. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.
4. CLOSEOUT ACTIVITIES
A. PROVIDE NORMAL OPERATION, EMERGENCY OPERATION AND PREVENTIVE MAINTENANCE MANUALS FOR EACH SYSTEM, EQUIPMENT AND DEVICE.
B. PROVIDE SOFTWARE AND FIRMWARE OPERATION DOCUMENTATION FOR SYSTEM INSTALLED.
C. PROVIDE BACKUP, UPGRADES AND UNRESTRICTED LICENSES FOR INSTALLED SOFTWARE, INCLUDING OPERATING SYSTEMS AND PROGRAMMING
TOOLS REQUIRED FOR MAINTENANCE AND OPERATION.
SECTION 26 0010
SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUCTORS AND CABLES INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. COPPER BUILDING WIRE
A. FLEXIBLE, INSULATED, DRAWN COPPER WITH AN INSULATION JACKET, RATED 600V OR LESS.
B. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.
C. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUIT(S) OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR
VOLTAGE DROP.
D. PROVIDE COLOR CODED WIRE WITH DIFFERENT COLOR FOR EACH PHASE, NEUTRAL AND GROUND, BASED ON ELECTRICAL SYSTEM TYPE.
2. CONNECTORS AND SPLICES
A. FACTORY-FABRICATED CONNECTORS, SPLICES, AND LUGS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE
INDICATED.
B. SHALL BE MARKED FOR INTENDED LOCATION AND USE.
PART 3 - EXECUTION
1. INSTALLATION
A. CONCEAL CABLES IN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE NOTED.
B. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE WIRE/CABLE GRIPS, THAT WILL NOT DAMAGE CABLES OR RACEWAY.
USE MANUFACTURER APPROVED PULLING COMPOUND OR LUBRICANT WHEN NECESSARY.
C. INSTALL CONDUCTORS AT EACH OUTLET, WITH AT LEAST 12" OF SLACK.
D. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.
2. CONNECTIONS
A. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES.
B. SPLICES, TERMINATIONS, AND TAPS SHALL BE COMPATIBLE WITH CONDUCTOR MATERIAL.
C. CONDUCTORS SHALL BE CONTINUOUS FROM ORIGIN TO PANEL OR EQUIPMENT TERMINATION WHERE POSSIBLE. SPLICES AND TAPS, WHERE
REQUIRED, SHALL BE MADE IN JUNCTION BOXES WITH SUITABLE CONNECTORS.
3. ACCEPTANCE
A. ALL CONDUCTORS AND CONNECTIONS SHALL TEST FREE OF GROUNDS, SHORTS, AND OPENS PRIOR TO ENERGIZING CIRCUIT.
SECTION 26 0519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUIT AND RACEWAY PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. ALL PRODUCTS SHALL BE UL LISTED AND LABELED.
2. EMT - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).
3. RMC - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).
4. FMC - FLEXIBLE, STEEL. PROVIDE AT TERMINATION POINT FOR EQUIPMENT SUBJECT TO MOTION AND VIBRATION.
5. MC CABLE - COLOR-CODED COPPER CONDUCTORS WITH INTERLOCKING GALVANIZED STEEL SHEATHING.
6. PVC - SCHEDULE 40, SCHEDULE 80, FOR USE WITH MAXIMUM 90 DEG C WIRE.
7. FITTINGS
A. SHALL BE LISTED FOR USE WITH RACEWAY SYSTEM TO BE INSTALLED.
PART 3 - EXECUTION
1. CONDUIT TYPE SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH IT IS LOCATED:
A. INDOORS - EMT, AND/OR RMC, WITH SET-SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.
B. OUTDOORS - RIGID GALVANIZED STEEL.
C. UNDERGROUND - RIGID, NON-METALLIC SCHEDULE 80 PVC.
a. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED ABOVE GROUND.
2. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.
3. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.
4. USE LARGE RADIUS ELLS FOR ALL CONDUIT BENDS.
5. CONDUITS SHALL BE CONCEALED WITHIN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED. CONDUITS SHALL BE
SUPPORTED WITHIN 12" OF ENCLOSURES TO WHICH ATTACHED.
6. INSTALL RACEWAY SEALS AND FITTINGS AT ACCESSIBLE LOCATIONS.
7. DO NOT INSTALL CONDUITS WITHIN 2" OF THE BOTTOM SIDE OF METAL DECK ROOF.
8. KEEP CONDUITS AT LEAST 6" AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES.
9. INSTALL PULL WIRES IN EMPTY RACEWAYS FOR FUTURE USE. PROVIDE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN
200lb TENSILE STRENGTH. LEAVE AT LEAST 12" OF SLACK AT BOTH ENDS OF CONDUIT.
10. CAP AND SEAL UNDERGROUND RACEWAYS DESIGNATED AS SPARE ABOVE GRADE ALONGSIDE DUCT RACEWAYS IN USE.
11. PROVIDE SEPARATE RACEWAY SYSTEM FOR EMERGENCY CIRCUIT(S). EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-
EMERGENCY CIRCUITS.
SECTION 26 0533.13
CONDUITS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL GROUNDING AND BONDING PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. GROUNDING AND BONDING CONDUCTORS
A. PROVIDE THHN/THWN-2, TINNED-COPPER WIRE OR CABLE, GREEN COLOR. CABLE SHALL BE RATED 600V.
2. GROUNDING AND BONDING CLAMPS
A. CLAMPS SUITABLE FOR ATTACHMENT OF GROUNDING AND BONDING CONDUCTORS TO ELECTRODES, PIPES, TUBING, AND REBAR. SUITABLE TYPES
SHALL BE:
a. STRAP-TYPE PIPE AND ROD CLAMPS
b. BEAM GROUNDING CLAMPS
c. EXOTHERMICALLY WELDED CONNECTIONS
3. GROUNDING (EARTHING) ELECTRODES
A. COPPER CLAD STEEL
B. 3/4" DIAMETER BY 10' LENGTH
PART 3 - EXECUTION
1. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.
2. GROUNDING AND BONDING CONDUCTORS
A. PROVIDE SOLID CONDUCTOR FOR 8 AWG AND SMALLER, AND STRANDED CONDUCTORS FOR 6 AWG AND LARGER, UNLESS OTHERWISE NOTED.
B. ROUTE CONDUCTORS ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE. AVOID OBSTRUCTING ACCESS TO OR PLACING CONDUCTORS WHERE
THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE.
C. PROVIDE GROUNDING AND BONDING BUSBARS IN ELECTRICAL EQUIPMENT ROOMS, ROOMS HOUSING SERVICE EQUIPMENT, AND ELSEWHERE
INDICATED ON DRAWINGS.
3. CONNECTIONS
A. MAKE CONNECTIONS SO POSSIBILITY OF GALVANIC ACTION OR ELECTROLYSIS IS MINIMIZED.
B. USE EXOTHERMIC WELDS FOR ALL BELOW GRADE CONNECTIONS.
4. GROUNDING ELECTRODES
A. DRIVE GROUND RODS UNTIL TOPS ARE 2" BELOW FINISHED FLOOR OR GRADE.
B. INSTALL AT LEAST (3) RODS SPACED AT LEAST ONE-ROD LENGTH FROM EACH OTHER AND CONNECT TO SERVICE GROUNDING ELECTRODE
CONDUCTOR.
C. FOR CONCRETE-ENCASED ELECTRODE (UFER GROUND), USE MINIMUM 20' OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG.
a. IF FOUNDATION IS LESS THAN 20' LONG, COIL EXCESS CONDUCTOR WITHIN BASE OF FOUNDATION.
b. BOND GROUNDING CONDUCTOR TO REINFORCING STEEL IN AT LEAST (4) LOCATIONS AND TO ANCHOR BOLTS. EXTEND GROUNDING CONDUCTOR
BELOW GRADE AND CONNECT TO GROUNDING GRID OR GROUNDING ELECTRODE EXTERNAL TO CONCRETE.
5. EQUIPMENT GROUNDING AND BONDING
A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH THE FOLLOWING ITEMS:
a. FEEDERS AND BRANCH CIRCUITS
b. LIGHTING CIRCUITS
c. RECEPTACLE CIRCUITS
d. SINGLE, AND THREE-PHASE MOTOR AND APPLIANCE BRANCH CIRCUITS
e. FLEXIBLE RACEWAY, ARMORED, AND METAL-CLAD CABLE RUNS
B. ALL CORRUGATED STAINLESS STEEL TUBING FOR GAS PIPING SYSTEM IN KITCHENS SHALL BE BONDING TO THE GROUNDING ELECTRODE SYSTEM.
BONDING JUMPER SHALL NOT BE SMALLER THAN 6 AWG.
SECTION 26 0526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SUPPORT, ANCHORAGE, AND ATTACHMENT PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
A. STEEL HANGERS, CLAMPS, AND ASSOCIATED FITTINGS SHALL BE DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED.
B. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS FOR FASTENING ELECTRICAL ITEMS OR SUPPORTS TO BUILDING SURFACES:
a. POWDER-ACTUATED FASTENERS
b. MECHANICAL-EXPANSION ANCHORS
c. CONCRETE INSERTS
d. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS
e. THROUGH BOLTS AND TOGGLE BOLTS
f. HANGER RODS
PART 3 - EXECUTION
A. SUPPORT INSTALLATION
a. PROVIDE SIZES OF COMPONENTS SO STRENGTH WILL BE ADEQUATE TO CARRY PRESENT AND FUTURE STATIC LOADS WITHIN SPECIFIED LIMITS.
b. CUT, FIT, AND PLACE MISCELLANEOUS METAL SUPPORTS ACCURATELY IN LOCATION, ALIGNMENT, AND ELEVATION TO SUPPORT AND ANCHOR
ELECTRICAL MATERIALS AND EQUIPMENT.
B. CONCRETE BASES
a. ALL FLOOR MOUNT ELECTRICAL EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PADS. PADS SHALL BE NOT LESS THAN 4" LARGER IN BOTH
DIRECTIONS OF ELECTRICAL EQUIPMENT TO BE SUPPORTED.
C. TOUCHUP
a. CLEAN WELDS AND ABRADED AREAS OF SHOP PAINT. PAINT EXPOSED AREAS IMMEDIATELY AFTER ERECTING HANGERS AND SUPPORTS.
SECTION 26 0529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SURGE PROTECTIVE DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. MANUFACTURER
A. RAYCAP
a. TYPE 1, SERVICE ENTRANCE - RAYVOSS
b. TYPE 2, BRANCH PANEL - RSE2
2. GENERAL CHARACTERISTICS
A. MCOV: NOT LESS THAN 125% OF NOMINAL SYSTEM VOLTAGE FOR 208Y/120V AND 120/240V SYSTEMS. NOT LESS THAN 115% OF NOMINAL
SYSTEM VOLTAGE FOR 480Y/277V SYSTEMS.
B. PEAK SURGE CURRENT RATING: MINIMUM SINGLE-PULSE SURGE CURRENT WITHSTAND RATING PER PHASE SHALL BE NOT LESS THAN -
a. TYPE 1: 160, OR 240 kA.
b. TYPE 2: 50, 100, 150, OR 200 kA.
C. PROTECTION MODES: DEVICE SHALL HAVE PROTECTION MODES FOR LINE-TO-NEUTRAL, AND LINE-TO-LINE, FOR TYPE 1 DEVICES, AND LINE-TO-
NEUTRAL, LINE-TO-GROUND, NEUTRAL-TO-GROUND, AND LINE-TO-LINE, FOR TYPE 2 DEVICES.
3. OPTIONS
A. INTERNAL THERMAL PROTECTION TO DISCONNECT SPD BEFORE DAMAGING INTERNAL SUPPRESSOR COMPONENTS.
B. INDICATOR LIGHT DISPLAY FOR PROTECTION STATUS.
C. AUDIBLE ALARM.
D. NEMA ICS 5, DRY FORM-C CONTACTS RATED AT 1 A AND 120 VAC FOR REMOTE MONITORING OF PROTECTION STATUS.
E. TYPE 2 DEVICES: TOV AND SURGE COUNTER WITH TIME AND DATE STAMP.
PART 3 - EXECUTION
1. INSTALLATION
A. PROVIDE OCPD AND DISCONNECT FOR INSTALLATION OF SPD IN ACCORDANCE WITH UL 1449 AND MANUFACTURER INSTRUCTIONS.
B. INSTALL LEADS BETWEEN DISCONNECT(S) AND SPD(S) IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.
a. DO NOT SPLICE AND EXTEND SPD LEADS UNLESS PERMITTED BY MANUFACTURER.
b. DO NOT EXCEED MANUFACTURER RECOMMENDED LEAD LENGTH.
c. DO NOT BOND NEUTRAL AND GROUND.
d. USE CRIMPED CONNECTORS AND SPLICES ONLY. WIRE NUTS ARE NOT ACCEPTABLE.
C. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.
SECTION 26 4313
SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL BOX AND COVER PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. METALLIC OUTLET BOXES
A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.
B. MATERIAL SHALL BE SHEET METAL GALVANIZED STEEL, WITH A MINIMUM DEPTH OF 2.5".
C. BOXES SHALL HAVE PRYOUT OPENINGS, KNOCKOUTS, THREADED ENTRIES, OR HUBS IN EITHER SIDES OR BACK FOR CONDUITS OR CONDUIT
FITTINGS. SHALL HAVE PROVISIONS FOR MOUNTING OUTLET BOX COVER.
D. EXTENSION RINGS SHALL BE PROVIDED WHERE REQUIRED OR INDICATED ON DRAWINGS, TO EXTEND DEVICE BOX TO INCREASE DEPTH.
EXTENSION RINGS SHALL BE SUITABLE FOR USE WITH ASSOCIATED DEVICE BOX.
2. NONMETALLIC OUTLET BOXES
A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.
3. COVER PLATES
A. LISTED AND LABELED FOR INTENDED LOCATION AND USE WITH ASSOCIATED OUTLET BOX TYPE.
B. FOR USE IN FINISHED LOCATIONS: .032" THICK, TYPE 302/304 NON-MAGNETIC STAINLESS STEEL.
a. ALL DEVICE COVERS SHALL BE BRUSHED STAINLESS STEEL, UNLESS SPECIFIC DEVICE COLOR IS SPECIFIED.
C. PROVIDE GASKETS FOR WALLPLATES IN DAMP OR WET LOCATIONS.
D. WEATHERPROOF COVERS
a. SHALL BE METAL, "WHILE-IN-USE" TYPE. COVER SHALL BE GRAY COLOR.
PART 3 - EXECUTION
1. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.
A. CUT, PATCH, REPAIR AND PAINT GYPSUM AND/OR MASONRY WALLS TO RECESS NEW BOXES WHERE INDICATED.
B. HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY ARE NOT IN THE SAME VERTICAL CHANNEL.
2. PROVIDE NEMA 1 BOXES AND COVERS FOR INDOOR LOCATIONS, UNLESS OTHERWISE NOTED.
3. PROVIDE NEMA 3R BOXES AND COVERS FOR OUTDOOR LOCATIONS, UNLESS OTHERWISE NOTED.
4. SUPPORT
A. SUPPORT BOXES IN RECESSED CEILINGS INDEPENDENT OF CEILING TILES OR GRID.
B. SUPPORT JUNCTION OR PULL BOXES FROM BUILDING STRUCTURE. DO NOT SUPPORT BOXES BY CONDUIT(S).
5. ALL BOXES USED FOR LOW VOLTAGE DATA CABLING SHALL BE DOUBLE GANG, 3-1/2" DEEP WITH SINGLE GANG MUD RING. PROVIDE 1" CONDUIT TO
ABOVE ACCESSIBLE CEILING FOR DATA CABLING.
SECTION 26 0533.16
BOXES AND COVERS ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LABEL AND IDENTIFICATION PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. LABELS
A. LISTED AND LABELED FOR INTENDED LOCATION AND APPLICATION.
B. VINYL WRAPAROUND LABELS - PREPRINTED, FLEXIBLE LABELS LAMINATED WITH CLEAR, WEATHER AND CHEMICAL-RESISTANT COATING.
C. SELF-ADHESIVE WRAPAROUND LABELS - PREPRINTED, VINYL FLEXIBLE LABEL WITH ACRYLIC PRESSURE-SENSITIVE ADHESIVE.
D. SELF-ADHESIVE LABELS - POLYESTER VINYL, THERMAL, TRANSFER PRINTED, MULTI-COLOR, WEATHER AND UV-RESISTANT, PRESSURE-
SENSITIVE ADHESIVE.
E. SIZE
a. 1-1/2" BY 6" FOR RACEWAYS AND CONDUCTORS.
b. 3-1/2" BY 5" FOR EQUIPMENT.
2. SIGNS
A. LAMINATED ACRYLIC OR MELAMINE PLASTIC.
a. 1/16" THICK FOR SIGNS UP TO 20 SQ. IN.
b. 1/8" THICK FOR SIGNS GREATER THAN 20 SQ. IN.
c. ENGRAVED LEGEND WITH BLACK LETTERS ON WHITE FACE.
d. PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4" GROMMETS IN CORNERS FOR MOUNTING.
3. UNDERGROUND-LINE WARNING TAPE
A. SUITABLE TO IDENTIFY AND LOCATE UNDERGROUND ELECTRICAL AND COMMUNICATIONS UTILITY LINES.
B. PRINTING ON TAPE MUST BE PERMANENT AND NOT DAMAGED BY BURIAL OPERATIONS.
C. INSCRIPTIONS SHALL READ "CAUTION BURIED ELECTRIC LINE BELOW" OR "CAUTION BURIED COMMUNICATION LINE BELOW".
D. DETECTABLE WARNING TAPE
a. REINFORCED, DETECTABLE THREE-LAYER LAMINATE, CONSISTING OF ALUMINUM-FOIL CORE AND CLEAR PROTECTIVE FILM.
PART 3 - EXECUTION
1. PROVIDE BAKED ENAMEL SIGNS FOR:
A. PANELBOARDS AND SWITCHBOARDS
B. TRANSFORMERS
C. DISCONNECT SWITCHES
D. VARIABLE FREQUENCY DRIVES
E. LIGHTING CONTROL PANELS. LABELS SHALL INDICATED ROOMS CONTROLLED
2. IDENTIFY CONDUCTORS, CABLES, AND TERMINALS IN ENCLOSURES AND AT JUNCTIONS, TERMINALS, PULL POINTS, AND LOCATIONS OF HIGH
VISIBILITY. IDENTIFY BY SYSTEM AND CIRCUIT DESIGNATION.
3. PROVIDE UNDERGROUND-LINE WARNING TAPE FOR POWER, LIGHTING, AND COMMUNICATIONS CABLING.
4. LABEL INDIVIDUAL COVER PLATES WITH SELF-ADHESIVE LABELS. LABEL TO INDICATE CIRCUIT WHICH DEVICE IS FED FROM WITH THE FOLLOWING
INFORMATION:
A. PANELBOARD DESIGNATION - BRANCH CIRCUIT NUMBER.
5. INSTALL IDENTIFICATION MATERIALS AT LOCATIONS FOR MOST CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND
MAINTENANCE OF EQUIPMENT.
6. PROVIDE FLOOR MARKING TAPE TO INDICATE WORKING CLEARANCE OF ELECTRICAL EQUIPMENT. FLOOR MARKING TAPE SHALL NOT BE USED FOR
SURFACE OR FLUSH-MOUNTED PANELBOARDS AND SIMILAR EQUIPMENT IN FINISHED SPACES.
SECTION 26 0553
IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LIGHTING CONTROL PRODUCTS INSTALLED DURING COURSE OF WORK.
A. PROVIDE SUBMITTALS THAT INCLUDE INTERCONNECTION DIAGRAMS AND DIAGRAMS FOR POWER, SIGNAL, AND CONTROL WIRING.
PART 2 - PRODUCTS
1. ELECTROMECHANICAL DIAL-TIME SWITCHES
A. MANUFACTURER
a. INTERMATIC, INC.
b. LEVITON MANUFACTURING CO., INC.
c. NSI INDUSTRIES LLC
B. ASTRONOMICAL TIME DIAL.
C. SPST CONTACT, RATED FOR 20A BALLAST LOAD, 120/240 VAC.
D. ALLOW FOR CONNECTION OF A PHOTOELECTRIC RELAY AS A SUBSTITUTE FOR ON/OFF FUNCTION OF A PROGRAM.
E. EIGHT-DAY PROGRAM - UNIQUELY PROGRAMMABLE FOR EACH WEEKDAY OR HOLIDAY.
2. INDOOR OCCUPANCY AND VACANCY SENSORS
A. MANUFACTURER
a. N-LIGHT, UNLESS NOTED OTHERWISE.
B. WALL OR CEILING MOUNTED.
C. DUAL TECHNOLOGY, SEPARATE POWER PACK.
D. OCCUPANCY MODE - TURN LIGHTS ON WHEN AREA IS OCCUPIED AND OFF WHEN UNOCCUPIED. PROVIDE TIME DELAY FOR TURNING LIGHTS OFF
WITH ADJUSTABLE RANGE OF 1 TO 15 MINUTES.
E. VACANCY MODE - LIGHTS TO BE TURNED ON MANUALLY AND SENSOR TO TURN LIGHTS OFF WHEN AREA IS UNOCCUPIED. PROVIDE TIME DELAY
FOR TURNING LIGHTS OFF WITH ADJUSTABLE RANGE OF 1 TO 15 MINUTES.
F. POWER PACK - LINE VOLTAGE. DRY CONTACTS RATED FOR A 20A LED LOAD AT 120VAC AND 277VAC. POWER PACK TO CONTAIN AUXILIARY DRY
CONTACT FOR SPARE CONNECTION TO OTHER BUILDING SYSTEM(S).
3. SWITCHBOX-MOUNTED OCCUPANCY SENSORS
A. MANUFACTURER
a. N-LIGHT, UNLESS OTHERWISE NOTED.
B. OPERATION - TURN LIGHTS ON WHEN AREA IS OCCUPIED AND OFF WHEN UNOCCUPIED. PROVIDE TIME DELAY FOR TURNING LIGHTS OFF WITH
ADJUSTABLE RANGE OF 1 TO 15 MINUTES.
C. SWITCH RATING - NOT LESS THAN 800 VA LED LOAD AT 120 VAC, 1200 VA LED LOAD AT 277 VAC, AND 800 W INCANDESCENT.
D. SENSOR TECHNOLOGY - DUAL TECHNOLOGY - PIR AND ULTRASONIC.
E. VOLTAGE TO MATCH THE CIRCUIT VOLTAGE.
F. COLOR TO MATCH WIRING DEVICE FINISHES. FACEPLATE FINISH TO BE BRUSHED STAINLESS STEEL, UNLESS OTHERWISE INDICATED.
PART 3 - EXECUTION
1. INSTALLATION
A. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013, WITH MICHIGAN AMENDMENTS.
B. COORDINATE LAYOUT AND INSTALLATION OF CEILING-MOUNTED DEVICES WITH OTHER BUILDING SYSTEMS THAT PENETRATE CEILINGS.
C. INSTALL AND AIM SENSORS IN LOCATIONS TO ACHIEVE NOT LESS THAN 90% COVERAGE OF AREAS INDICATED.
D. MOUNT ELECTRICALLY HELD LIGHTING CONTACTORS WITH ELASTOMER ISOLATOR PADS TO ELIMINATE VIBRATION.
E. SIZE CONDUCTORS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
F. ALL EXPOSED WIRING AREAS SHALL BE INSTALLED IN CONDUIT. NO EXPOSED LOW VOLTAGE WIRING WILL BE ALLOWED.
2. IDENTIFICATION
A. IDENTIFY CONTROLLED CIRCUITS IN LIGHTING CONTRACTORS.
B. IDENTIFY CIRCUITS OR LUMINAIRES CONTROLLED BY PHOTOELECTRIC AND OCCUPANCY SENSORS AT EACH SENSOR.
SECTION 26 0923
LIGHTING CONTROL DEVICES
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL PANELBOARD PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. MANUFACTURER
A. SQUARE D - NQOD FOR 208/120V BRANCH PANELBOARDS, NF FOR 480/277V BRANCH PANELBOARDS.
B. OR EQUAL BY:
a. EATON CORP.
b. SIEMENS
2. ELECTRICAL COMPONENTS, DEVICES, AND EQUIPMENT SHALL BE UL LABELED.
3. ENCLOSURES
A. RATED FOR ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION
a. INDOOR, DRY AND CLEAN LOCATIONS - NEMA 1
b. OUTDOOR LOCATIONS - NEMA 3R
c. KITCHEN LOCATIONS - NEMA 4X, STAINLESS STEEL
d. OTHER WET AND DAMP INDOOR LOCATIONS - NEMA 4
B. FRONT - SECURE TO BOX WITH CONCEALED TRIM CLAMPS. FOR SURFACE-MOUNTED FRONTS, MATCH DIMENSIONS; FOR FLUSH-MOUNTED
FRONTS, OVERLAP BOX. TRIMS MUST COVER LIVE PARTS AND MAY HAVE NO EXPOSED HARDWARE.
4. BUSES
A. TIN-PLATED ALUMINUM FOR 400A OR LESS.
B. HARD DRAWN COPPER FOR ABOVE 400A.
5. CONDUCTOR CONNECTORS
A. TIN-PLATED ALUMINUM OR HARD DRAWN COPPER, 98% CONDUCTIVITY.
B. MAIN AND NEUTRAL LUGS - MECHANICAL TYPE, WITH LUG ON NEUTRAL BAR FOR EACH POLE IN PANELBOARD.
C. GROUND LUGS AND BUS-CONFIGURED TERMINATORS - MECHANICAL TYPE, WITH LUG ON BAR FOR EACH POLE IN PANELBOARD.
D. SUBFEED LUGS - MECHANICAL TYPE, SUITABLE FOR USE WITH CONDUCTOR MATERIAL. LOCATE AT SAME END OF BUS AS INCOMING LUGS OR
MAIN DEVICE.
6. SHORT-CIRCUIT CURRENT RATING
A. FULLY RATED TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS. SERIES RATED PANELS ARE NOT
ACCEPTABLE.
7. OVERCURRENT PROTECTIVE DEVICES
A. THERMAL-MAGNETIC CIRCUIT BREAKERS
a. INVERSE TIME CURRENT ELEMENT FOR LOW-LEVEL OVERLOADS.
b. INSTANTANEOUS MAGNETIC TRIP ELEMENT FOR SHORT CIRCUITS.
c. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT-BREAKER FRAME SIZES 250A AND LARGER.
B. ELECTRONIC TRIP CIRCUIT BREAKERS
a. RMS SENSING.
b. FIELD-REPLACEABLE RATING PLUG OR ELECTRONIC TRIP.
c. FIELD ADJUSTABLE SETTINGS FOR: INSTANTANEOUS TRIP, LONG AND SHORT TIME PICKUP LEVELS, LONG AND SHORT TIME ADJUSTMENTS, AND GROUND FAULT PICKUP LEVEL, TIME DELAY AND I
T RESPONSE.
C. SUBFEED CIRCUIT BREAKERS SHALL BE VERTICALLY ARRANGED ON PHASE BUSBARS.
PART 3 - EXECUTION
1. INSTALLATION
A. MOUNT TOP OF PANELBOARD TRIP 7.5' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED.
B. MOUNT PANELBOARD CABINET PLUMB AND RIGID WITHOUT DISTORTION OF BOX.
C. MOUNT RECESSED PANELBOARDS WITH FRONT UNIFORMLY FLUSH WITH WALL FINISH.
a. FOR RECESSED PANELBOARDS, STUB (4) 1" EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED
TO BE CEILING SPACE IN FUTURE.
D. MAKE GROUNDING CONNECTIONS AND BOND NEUTRAL FOR SERVICES AND SEPARATELY DERIVED SYSTEMS TO GROUND. MAKE CONNECTIONS
TO GROUNDING ELECTRODES, SEPARATE GROUNDS FOR ISOLATED GROUND BARS, AND CONNECTIONS TO SEPARATE GROUND BARS.
2. IDENTIFICATION
A. PANELBOARD LABEL MUST LIST MANUFACTURER NAME, TRADEMARK, VOLTAGE, AMPERAGE, NUMBER OF PHASES, AND NUMBER OF POLES AND
MUST BE LOCATED ON INTERIOR OF PANELBOARD DOOR.
B. CIRCUIT BREAKER LABELS MUST LIST CURRENT RATING, UL AND IEC CERTIFICATION STANDARDS, AND AIC RATING.
C. CIRCUIT DIRECTORY
a. PROVIDE CIRCUIT DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTED IN TRANSPARENT CARD HOLDER.
b. PANELBOARD DIRECTORY SHALL BE TYPE-WRITTEN, AND PROVIDE DETAILED INFORMATION SHOWN ON ASSOCIATED PANELBOARD LOAD
SCHEDULE.
c. UPDATE ALL EXISTING CIRCUIT DIRECTORY CARDS AS REQUIRED.
SECTION 26 2416
PANELBOARDS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL WIRING DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. GENERAL USE SWITCHES
A. MANUFACTURER
a. ARROW HART, WIRING DEVICES
b. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.
c. LEVITON MANUFACTURING CO., INC.
d. PASS & SEYMOUR, LEGRAND NORTH AMERICA, LLC
B. GENERAL CHARACTERISTICS
a. HEAVY DUTY GRADE, QUIET TYPE, 120/277 VAC, RATED 20A MINIMUM.
b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.
c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.
2. STRAIGHT-BLADE RECEPTACLES
A. MANUFACTURER
a. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.
B. GENERAL CHARACTERISTICS
a. EXTRA HEAVY DUTY GRADE, TAMPER-RESISTANT, RATED 20A MINIMUM.
b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.
c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.
PART 3 - EXECUTION
1. INSTALLATION
A. UNLESS OTHERWISE INDICATED, INSTALL SWITCHES, RECEPTACLES, AND OTHER WIRING DEVICES, AT MOUNTING HEIGHTS RECOMMENDED IN
NECA NEIS 1.
B. ORIENT RECEPTACLES TO MATCH CONFIGURATION DIAGRAM IN NEMA WD 6.
a. RECEPTACLES ORIENTED HORIZONTALLY SHALL BE MOUNTED WITH NEUTRAL BLADE FACING UP.
2. IDENTIFICATION
A. MARK INSIDE OF COVER OR COVER PLATE OF WIRING DEVICE(S) WITH PANELBOARD AND CIRCUIT NUMBER FEEDING WIRING DEVICE(S).
SECTION 26 2726
WIRING DEVICES
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LED LIGHTING PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. GENERAL CHARACTERISTICS
A. PROVIDE ALL INTERIOR AND EXTERIOR LUMINAIRES AS INDICATED ON THE LIGHT FIXTURE SCHEDULE.
B. ELECTRICAL COMPONENTS, DEVICES AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING
AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.
C. METAL PARTS SHALL BE FREE OF BURRS AND SHARP CORNERS AND EDGES. SHEET METAL COMPONENTS SHALL BE STEEL UNLESS
OTHERWISE INDICATED. FORM AND SUPPORT SHALL PREVENT WARPING AND SAGGING.
D. LUMINAIRE FINISHES SHALL BE FACTORY APPLIED AND RATED FOR THE INTENDED LOCATION AND APPLICATION.
E. LUMINAIRE SUPPORT
a. SINGLE-STEM HANGARS: 1/2" STEEL TUBING WITH SWIVEL BALL FITTINGS AND CEILING CANOPY. FINISH SAME AS LUMINAIRE.
b. WIRES: 12 GAUGE, CLASS 3, SOFT TEMPER, ZINC-COATED STEEL.
c. ROD HANGERS: 3/16" MINIMUM DIAMETER, CADMIUM-PLATED, THREADED STEEL ROD.
d. HOOK HANGERS: INTEGRATED ASSEMBLY MATCHED TO LUMINAIRE.
e. JUNCTION BOX CANOPY COVERS SHALL MATCH COLOR OF THE CEILING THEY ARE ATTACHED TO.
f. CONCRETE BASES SHALL BE PROVIDED FOR ALL POLE MOUNTED LUMINAIRES. CONDUIT(S) SHALL BE CAST INTO BASE.
F. INTEGRAL EMERGENCY BATTERY PACKS
a. WHERE SPECIFIED, BATTERY PACKS SHALL PROVIDE MINIMUM 90 MINUTES OF LIGHT AT RATED OUTPUT OF BATTERY PACK.
PART 3 - EXECUTION
1. INSTALLATION
A. LUMINAIRES SHALL BE INSTALLED LEVEL, PLUMB, AND SQUARE WITH CEILINGS AND WALLS UNLESS OTHERWISE INDICATED.
B. LUMINAIRE SUPPORTS SHALL BE SIZED AND RATED FOR LUMINAIRE WEIGHT WITHOUT CAUSING DEFLECTION OF CEILING OR WALL.
C. INSTALL ACCESSORIES FURNISHED WITH EACH LUMINAIRE.
D. AIM DIRECTIONAL LUMINAIRES AS INDICATED ON DRAWINGS.
2. IDENTIFICATION
A. JUNCTION BOXES SERVING BRANCH CIRCUIT WIRING FOR LUMINAIRES SHALL BE LABELED WITH ASSOCIATED PANELBOARD AND CIRCUIT
NUMBER.
SECTION 26 5119
LED LIGHTING
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL FIRE ALARM SYSTEM PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. GENERAL CHARACTERISTICS
A. FINISHED SYSTEM SHALL BE NON-CODED, UL-CERTIFIED ADDRESSABLE SYSTEM, WITH MULTIPLEXED SIGNAL TRANSMISSION AND VOICE AND
STROBE NOTIFICATION FOR EVACUATION. SYSTEM SHALL BE FIELD PROGRAMMABLE, MICROPROCESSOR-BASED, AND MODULAR.
B. FIRE ALARM COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED BY AN NRTL IN ACCORDANCE WITH NFPA 70 FOR USE
WITH SELECTED FIRE-ALARM SYSTEM AND MARKED FOR INTENDED LOCATION AND APPLICATION.
C. FIRE-ALARM SIGNAL INITIATION MUST BE BY ONE OF THE FOLLOWING DEVICES AND/OR SYSTEMS:
a. MANUAL PULL STATIONS
b. DETECTORS: HEAT, FLAME, SMOKE, DUCT, CARBON MONOXIDE, ETC.
c. AUTOMATIC SPRINKLER SYSTEM WATER FLOW
d. PREACTION SYSTEM
e. DRY-TYPE SYSTEM PRESSURE FLOW SWITCH
f. FIRE PUMP OR FIRE STANDPIPE SYSTEM
D. FIRE ALARM SIGNAL INITIATION MUST INITIATE THE FOLLOWING:
a. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES, INCLUDING VOICE EVACUATION NOTICES
b. IDENTIFY ALARM AND SPECIFIC INITIATING DEVICE AT FACU, CONNECTED NETWORK CONTROL PANELS, REMOTE ANNUNCIATORS, AND OFF-
PREMISES NETWORK CONTROL PANELS
c. TRANSMIT ALARM SIGNAL TO REMOTE ALARM RECEIVING STATION
d. UNLOCK ELECTRIC DOOR LOCKS IN DESIGNATED EGRESS PATHS
e. RELEASE FIRE AND SMOKE DOORS HELD OPEN BY MAGNETIC DOOR HOLDERS
f. ACTIVATE VOICE/ALARM COMMUNICATION SYSTEM
g. SWITCH HVAC EQUIPMENT CONTROLS TO FIRE-ALARM MODE
h. ACTIVE SMOKE CONTROL SYSTEM AT FIRE FIGHTERS SMOKE CONTROL STATION (WHERE APPLICABLE)
i. CLOSE SMOKE DAMPERS IN AIR DUCTS OF DESIGNATED HVAC DUCT SYSTEMS
j. RECALL ELEVATOR(S) TO PRIMARY OR ALTERNATE RECALL FLOORS
k. ACTIVATE EMERGENCY LIGHTING CONTROL
l. ACTIVATE EMERGENCY SHUTOFFS FOR GAS AND FUEL SUPPLIES, EXCEPT FOR SHUTOFFS SERVING LEGALLY REQUIRED LIFE SAFETY
SYSTEMS SUCH AS EMERGENCY GENERATORS AND FIRE PUMPS
m. RECORD EVENTS IN SYSTEM MEMORY
E. PROVIDE NETWORK COMMUNICATIONS IN ACCORDANCE WITH MANUFACTURER WRITTEN INSTRUCTIONS.
F. DEVICE GUARDS SHALL BE WELDED WIRE MESH OF SIZE AND SHAPE REQUIRED FOR PROTECTED DEVICE. PAINT COLOR SHALL MATCH
PROTECTED DEVICE.
PART 3 - EXECUTION
1. INSTALLATION
A. IF APPLICABLE, VERIFY FUNCTIONALITY OF INSTALLED COMPONENTS OF EXISTING SYSTEM PRIOR TO STARTING WORK. DOCUMENT EQUIPMENT
OR COMPONENTS NOT FUNCTIONING AS DESIGNED.
a. DO NOT INTERRUPT FIRE-ALARM SERVICE TO FACILITIES OCCUPIED BY OWNER OR OTHERS UNLESS PERMITTED WITH CONSTRUCTION
MANAGERS WRITTEN PERMISSION. NOTIFY CONSTRUCTION MANAGER NO FEWER THAN (7) DAYS IN ADVANCE OF PROPOSED INTERRUPTION
OF FIRE-ALARM SERVICE.
b. CONNECT NEW EQUIPMENT TO EXISTING CONTROL PANEL, OR MONITORING EQUIPMENT AT SUPERVISING STATION.
c. EXPAND, MODIFY, AND SUPPLEMENT EXISTING CONTROL EQUIPMENT AS NECESSARY TO EXTEND CONTROL FUNCTIONS TO NEW POINTS.
NEW COMPONENTS MUST BE CAPABLE OF MERGING WITH EXISTING CONFIGURATION WITHOUT DEGRADING PERFORMANCE OF EITHER
SYSTEM.
B. INSTALL WALL MOUNTED EQUIPMENT WITH TOPS OF CABINETS NOT MORE THAN 78" ABOVE FINISHED FLOOR.
C. INSTALL MANUAL FIRE-ALARM BOXES IN NORMAL PATH OF EGRESS WITHIN 60" OF EXIT DOORWAY. MANUAL BOXES MUST BE INSTALLED ON
BACKGROUND OF CONTRASTING COLOR. OPERABLE PART OF MANUAL BOXES MUST BE BETWEEN 42" AND 48" ABOVE FINISHED FLOOR.
D. INSTALL DETECTORS WITH SPACING AS REQUIRED BY NFPA 72. DUCT DETECTORS SHALL HAVE SAMPLING TUBES THAT EXTEND FULL WIDTH OF
DUCT.
E. EXPOSED PATHWAYS LOCATED LESS THAN 96" ABOVE FINISHED FLOOR MUST BE INSTALLED IN EMT. EXPOSED EMT MUST BE PAINTED RED.
2. IDENTIFICATION
A. INSTALL NAMEPLATE FOR EACH ELECTRICAL CONNECTION, INDICATING ELECTRICAL EQUIPMENT DESIGNATION AND CIRCUIT NUMBER FEEDING
CONNECTION.
B. INSTALL FRAMED INSTRUCTIONS IN LOCATION VISIBLE FROM FACU.
C. IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, AND TERMINALS.
SECTION 28 4621
ADDRESSABLE FIRE ALARM SYSTEMS
KINGSCOTT ASSOCIATES INC. PORTAGE, CC
JOB
SHEET
TITLE
SHEET
NO.
ISSUANCE DATE
N
P L
E A
S E
R E
C Y
C L
E
T H
E S
E D
R A
W
IN
G S
A N
D T
H E
W O
R K
R E
P R
E S
E N
T E
D T
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F A
P
Y R
IG
H
T
K
IN
G
S C
O T
T A
S S
O C
IA
T
D
M A
Y N
O T
B E
U S
E D
O R
R E
P R
O D
U C
H
O U
T P
E R
M
IS
S
IO
N
L A
S T
P R
IN
T
E D ljh
PORTAGE | CHELSEA | GRAND RAPIDS |
Gull Lake Community Schools
/8
/2
:5
:0
A
M
A u to d e s k D o c s
/G L C
S
S in k in g F u n d /2
.1
K
G A
G
U L L L
A K
E K
E L L O
G G
E L E
M E
N T
A R
Y G
Y M
C O
O L
IN
G M
E P
.r v t
2288.77
ELECTRICAL SPECIFICATIONS
E001
N th S tr e e t
H ic ko ry
C o rn e rs
M
I
G u ll
L a k e
C o m m u n it y S c h o o ls
K E
L L
O G
G
S
IN
K
IN
G
F U
N D
ESTIMATION
ON HOLD
CONSTRUCTION DOCUMENTS
12/19/2025
01/20/2026
04/09/2026
MIF CO H E IGT AAT NS
No.
6201060604
JONATHAN
SS
SS
SS
D D
D D
D D
D D
C.3
2.1
3.2
2.4
3.3
G1
G2
KINGSCOTT ASSOCIATES INC. PORTAGE, CC
JOB
SHEET
TITLE
SHEET
NO.
ISSUANCE DATE
N
P L
E A
S E
R E
C Y
C L
E
T H
E S
E D
R A
W
IN
G S
A N
D T
H E
W O
R K
R E
P R
E S
E N
T E
D T
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F A
P
Y R
IG
H
T
K
IN
G
S C
O T
T A
S S
O C
IA
T
D
M A
Y N
O T
B E
U S
E D
O R
R E
P R
O D
U C
H
O U
T P
E R
M
IS
S
IO
N
L A
S T
P R
IN
T
E D ljh
PORTAGE | CHELSEA | GRAND RAPIDS |
Gull Lake Community Schools
/8
/2
:5
:0
A
M
A u to d e s k D o c s
/G L C
S
S in k in g F u n d /2
.1
K
G A
G
U L L L
A K
E K
E L L O
G G
E L E
M E
N T
A R
Y G
Y M
C O
O L
IN
G M
E P
.r v t
2288.77
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
ED110
N th S tr e e t
H ic ko ry
C o rn e rs
M
I
G u ll
L a k e
C o m m u n it y S c h o o ls
K E
L L
O G
G
S
IN
K
IN
G
F U
N D
ESTIMATION
ON HOLD
CONSTRUCTION DOCUMENTS
12/19/2025
01/20/2026
04/09/2026
1/8" = 1'-0"ED110
1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN
ELECTRICAL DEMOLITION KEYED NOTES
1 DEMOLISH ALL LIGHT FIXTURES AND ASSOSIATED CONDUIT AND
WIRING.
MIF CO H E IGT AAT NS
No.
6201060604
JONATHAN
G2
G1
A
BB-64
A
BB-64
A
BB-64
A
BB-64
A
BB-64
AE
BB-64
A
BB-64
A
BB-64
AE
BB-64
A
BB-64
A
BB-64
A
BB-64
A
BB-64
A
BB-64
A
BB-64
A
BB-64
A
BB-66
A
BB-66
A
BB-66
A
BB-66
A
BB-66
A
BB-66
A
BB-66
A
BB-66
AE
BB-66
A
BB-66
A
BB-66
A
BB-66
AE
BB-66
A
BB-66
A
BB-66
A
BB-66
A
BB-66
X1 X1
X1X1
KINGSCOTT ASSOCIATES INC. PORTAGE, CC
JOB
SHEET
TITLE
SHEET
NO.
ISSUANCE DATE
N
P L
E A
S E
R E
C Y
C L
E
T H
E S
E D
R A
W
IN
G S
A N
D T
H E
W O
R K
R E
P R
E S
E N
T E
D T
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F A
P
Y R
IG
H
T
K
IN
G
S C
O T
T A
S S
O C
IA
T
D
M A
Y N
O T
B E
U S
E D
O R
R E
P R
O D
U C
H
O U
T P
E R
M
IS
S
IO
N
L A
S T
P R
IN
T
E D ljh
PORTAGE | CHELSEA | GRAND RAPIDS |
Gull Lake Community Schools
/8
/2
:5
:0
A
M
A u to d e s k D o c s
/G L C
S
S in k in g F u n d /2
.1
K
G A
G
U L L L
A K
E K
E L L O
G G
E L E
M E
N T
A R
Y G
Y M
C O
O L
IN
G M
E P
.r v t
2288.77
FIRST FLOOR LIGHTING PLAN
E210
N th S tr e e t
H ic ko ry
C o rn e rs
M
I
G u ll
L a k e
C o m m u n it y S c h o o ls
K E
L L
O G
G
S
IN
K
IN
G
F U
N D
ESTIMATION
ON HOLD
CONSTRUCTION DOCUMENTS
12/19/2025
01/20/2026
04/09/2026
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING DRIVER LOAD MANUFACTURER NOTES
A HIGH BAY SURFACE 0-10V 38 VA LITHONIA: #IBE-L24-15000LM-ATC-MD-MVOLT-GZ10-40K-80CRI-DWH
AE HIGH BAY SURFACE 0-10V 39 VA LITHONIA: #IBE-L24-15000LM-ATC-MD-MVOLT-GZ10-40K-80CRI-DWH-E15WCP
X1 EXIT SIGN, RED LETTERING, 1-SIDED SURFACE 0-10V 5 VA LITHONIA: #LQC-1-R-ELN
1/8" = 1'-0"E210
1 FIRST FLOOR LIGHTING PLAN
ELECTRICAL LIGHTING KEYED NOTES
1 <ELECTRICAL LIGHTING KEYED NOTE>
2 <ELECTRICAL LIGHTING KEYED NOTE>
3 <ELECTRICAL LIGHTING KEYED NOTE>
EXISTING PANEL
Notes:
Demand Current: 163 A
Demand Load: 59 kVA
Connected Current: 162 A
Connected Load: 58 kVA
LIGHTING - INTERIOR 1251 VA 125.00% 1564 VA
Load Classification Connected Factor Demand
Current: 162 A 172 A 155 A
Connecte... 19 kVA 21 kVA 19 kVA
83 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 84
81 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 82
79 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 80
77 SPARE 20 1 -- -- 0 500 -- -- 1 20 EXERIOR WAL LTS 78
75 SPARE 20 1 -- -- 0 500 -- -- 1 20 GYM 1131 CAN LTS 76
73 SPARE 20 1 -- -- 0 500 -- -- 1 20 GYM 1114 EMERGENCY LTS 74
71 SPARE 20 1 -- -- 0 1000 -- -- 1 20 LCP1 CONTROL 72
69 CU/FC RM 1137 20 1 -- -- 1000 70
67 CU/FC RM 1137 20 1 -- -- 1000 68
65 CU/FC RM 1139 20 1 -- -- 1000 644 1 20 LIGHTING - INTERIOR 66
63 CU/FC RM 1139 20 1 -- -- 1000 607 1 20 LIGHTING - INTERIOR 64
61 CU/FC RM 1135 20 1 -- -- 1000 0 -- -- 1 20 SPARE 62
59 CU/FC RM 1135 20 1 -- -- 1000 0 -- -- 1 20 SPARE 60
57 CU/FC RM 1132 20 1 -- -- 1000 0 -- -- 1 20 SPARE 58
55 CU/FC RM 1132 20 1 -- -- 1000 0 -- -- 1 20 SPARE 56
53 SPARE 20 1 -- -- 0 500 -- -- 1 20 FLAG POLE LTS 54
51 SPARE 20 1 -- -- 0 0 -- -- 1 20 SITE POLE LTS 52
49 SPARE 20 1 -- -- 0 0 -- -- 1 20 SITE POLE LTS 50
47 10000 0 -- -- 1 20 SPARE 48
45 10000 500 -- -- 1 20 GYM 1131 MH LTS 46
PANEL EA 100 3 -- --
10000 500 -- -- 1 20 GYM 1131 MH LTS 44
41 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 42
39 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 40
37 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 38
35 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 36
33 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 34
31 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 32
29 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 30
27 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 28
25 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 26
23 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 24
21 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 22
19 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 20
17 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 18
15 SPARE 20 1 -- -- 0 0 -- -- 1…