2026_04_09 GLCS Kellogg Gym Lighting.pdf

PDF 2 MB Posted

Attached to
Sinking Fund - Gym Lighting and AC
Solicitation number
RFP GLCS 260000001849 1
Issued by
Michigan

About this file

This construction document set consists of electrical design specifications and plans for the Kellogg Elementary School gymnasium lighting and air conditioning project, prepared by KingScott Associates Inc. for Gull Lake Community Schools located in Richland, Michigan. The project encompasses the demolition of existing light fixtures and associated electrical infrastructure within the gymnasium (Room 1131) and installation of new LED high-bay lighting fixtures with integrated 0-10V dimming drivers. The scope includes new electrical service coordination with Consumers Energy, installation of conduit, conductors, wiring devices, panelboards, surge protection devices, lighting control systems compliant with ASHRAE 90.1-2013 with Michigan amendments, and fire alarm system integration. The construction documents indicate an estimation status of "on hold" with issuance dates of December 19, 2025, January 20, 2026, and April 9, 2026.

The electrical specifications require the contractor to procure all building permits and inspections while performing work in accordance with the Michigan Electrical Code and National Electrical Code standards. New LED high-bay fixtures are specified as Lithonia IBE-L24-15000LM-ATC-MD-MVOLT fixtures with exit signage by the same manufacturer. The project utilizes a 400-amp main distribution panel (MDP) fed from utility service at 208Y/120V, 3-phase, 4-wire configuration, with multiple distribution panels and branch panels throughout the facility. Lighting control devices are mandated to be manufactured by N-Light unless otherwise noted, and all panelboards must be fully rated square D NQOD units for 208/120V applications. The contractor must provide shop drawings, operation manuals, and closeout documentation including software licenses and maintenance materials upon completion of work.

View the file

Other files

File Type Posted
2026_04_09 GLCS Richland Gym A_C.pdf PDF
Bid Advertisement Apr 2026 Sink Fund.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOCATION MAP

400500

200100

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB NO.

SHEET TITLE

SHEET NO.

ISSUANCES DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

N D

C

O P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

E S

A

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

W

IT

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

CLIENT:

GULL LAKE COMMUNITY SCHOOLS

10100 EAST 'D' AVE.

RICHLAND, MI 49083

P. (269) 548-3400

ARCHITECT & CIVIL ENGINEER:

KINGSCOTT ASSOCIATES INC.

950 TRADE CENTRE WAY, SUITE 130

PORTAGE, MI 49002

P. (800) 632-7815

CONSTRUCTION MANAGER:

MEP ENGINEER:

IGNYTE

38 COMMERCE AVE. SW

SUITE 450

GRAND RAPIDS, MI 49503

DIRECTORY

MILLER DAVIS

1029 PORTAGE ST.

KALAMAZOO, MI 49001

P. (269) 345-3561

PORTAGE | CHELSEA | GRAND RAPIDS | DETROIT

Gull Lake Community Schools

/9

/2

:0

:2

A

M

A u to d e s k D o c s

/G L C

S

S in k in g F u n d /G

L C

S K

E L L O

G G

E le m A rc h r2

.r v t 2288.77

TITLE SHEET

G1

N . 4

0t h

St re et H ic ko ry C or ne rs , M

I 4

G ul l L a ke C o m m un ity S ch o o ls

K E L L O

G G

S

IN

K

IN

G

F U

N D

Gull Lake Community Schools

KELLOGG 2026 SINKING FUND

CONSTRUCTION DOCUMENTS

KELLOGG ELEMENTARY

9594 N. 40th STREET

APRIL 09, 2026

SHEET INDEX

GENERAL

G1 TITLE SHEET

ARCHITECTURAL

A0.1 COMPOSITE PLAN

ELECTRICAL

E000 ELECTRICAL SYMBOLS AND GENERAL NOTES

ED110 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

E001 ELECTRICAL SPECIFICATIONS

E210 FIRST FLOOR LIGHTING PLAN

E401 ELECTRICAL ONE-LINE DIAGRAM

CONSTRUCTION DOCUMENTS 04/09/2026

CG

SPEECH

MECHANICAL

RECEIVING

CAFETERIA

SERVERY

KITCHEN

GYMNASIUM

CLASSROOM

BAND

CORRIDOR

MEN

WOMEN

CLASSROOM

CONFERENCE

AUX. GYM

OFFICE

WOMEN

CORRIDOR

CLASSROOM

CLASSROOM

MEN

CLASSROOM

STAFF ROOM

STORAGE

STORAGE

ITIN. OFFICE

CONFERENCE

PRINCIPAL

210 RECEPTIONIST

HEALTH

WKRM

CORRIDOR

STEAM

STORAGE

SPEECH

STORAGE

CORRIDOR

STORAGE

MUSIC

YOUNG 5's

YOUNG 5's

KINDERGARTEN

KINDERGARTEN

ART

ECSE

KINDERGARTEN

KINDERGARTEN

KINDERGARTEN

CORRIDOR

CORRIDOR

CORRIDOR

SPEECH

ITIN OFFICE

CORRIDOR

CORRIDOR

RESOURCE

1st GRADE

1st GRADE

419 1st GRADE

2nd GRADE

2nd GRADE

2nd GRADE

2nd GRADE

1st GRADE

1st GRADE

SPANISH

TITLE ONE

TITLE ONE

CORR

WKRM

T.

MEDIA CENTER

OFFICE

OFFICE

2nd GRADE

CORRIDOR

STORAGE

1. INDICATES CONSTRUCTION DOCUMENT ROOM NUMBERS.XX

COMPOSITE PLAN GENERAL NOTES:

AREA OF WORK

400500

200100

KINGSCOTT ASSOCIATES INC. PORTAGE, MICHIGANCC

JOB NO.

SHEET TITLE

SHEET NO.

ISSUANCES DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS | DETROIT

Gull Lake Community Schools

/9

/2

:0

:3

A

M

A u to d e s k D o c s

/G L C

S

S in k in g F u n d /G

L C

S K

E L L O

G G

E le m A rc h r2

.r v t 2288.77

COMPOSITE PLAN

A0.1

N . 4

0t h

St re et H ic ko ry C or ne rs , M

I 4

G ul l L a ke C o m m un ity S ch o o ls

K E L L O

G G

S

IN

K

IN

G

F U

N D

1/16" = 1'-0"

COMPOSITE PLAN

CONSTRUCTION DOCUMENTS 04/09/2026

ELECTRICAL ABBREVIATION LIST

ABBREVIATION DESCRIPTION

A

AF

AFCI

A.F.F.

AIC

AL

AR

AT

ATS

AUX

BKR

BPS

C

CB

CKT

CT

DEMO

DIM

DISC

DP

DS

DWG

EBU

EC

ELEC

EM/ EMERG

EMT

EO

EPO

EWC

EXIST

EXT

FA

FLA

FLR

FOH

FSEC

FU

G/GRD/EG

GFCI

GFP

HOA

HP

HV

HZ

IG

JB

KV

KVA

KW

KWH

LA

LP

LDP

AMPERES

AMPERES FRAME (BREAKER RATING)

ARC FAULT CIRCUIT INTERRUPTER

ABOVE FINISH FLOOR

AMPS INTERRUPTING CAPACITY

AUDIENCE LEFT

AUDIENCE RIGHT

AMPERS TRIP (BREAKER SETTING)

AUTOMATIC TRANSFER SWITCH

AUXILIARY

BREAKER

BOLTED PRESSURE SWITCH

CONDUIT

CIRCUIT BREAKER

CIRCUIT

CURRENT TRANSFORMER

DEMOLITION

DIMENSION

DISCONNECT

DISTRIBUTION PANEL

DOWNSTAGE

DRAWING

EMERGENCY BATTERY UNIT

ELECTRICAL CONTRACTOR

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

ELECTRICALY OPERATED

EMERGENCY POWER OFF

ELECTRIC WATER COOLER

EXISTING

EXTERIOR

FIRE ALARM

FULL LOAD AMPS

FLOOR

FRONT OF HOUSE

FOOD SERVICE EQUIPMENT

FUSE

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

HAND-OFF-AUTO

HORSEPOWER

HIGH VOLTAGE

HERTZ

ISOLATED GROUND

JUNCTION BOX

KILOVOLT

KILOVOLT - AMPERES

KILOWATT

KILOWATT - HOURS

LIGHTING ARRESTOR

LIGHTING PANEL

LIGHTING DISTRIBUTION PANEL

MAX

MCB

MCC

MDP

MECH

MIN

MISC.

MLO

MTD

MTG

MTR

N

NC

NEC

NF

NIC

NL

NO

NTS

OC

OFCI

OFOI

P

PB

PH

PT

PDP

RECEPT.

RCP

RDP

RP

RSC

SCHED

SW

SWBD

SWGR

TB

TELECOM

TR

TTP

TYP

UNO

US

V

W

WG

WP

XFMR

XP

(E)

(R)

MAXIMUM

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MECHANICAL

MINIMUM

MISCELLANEOUS

MAIN LUGS ONLY

MOUNTED

MOUNTING

MOTOR

NEUTRAL

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NON-FUSIBLE

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

ON CENTER

OWNER FURNISHED,

CONTRACTOR INSTALLED

OWNER FURNISHED,

OWNER INSTALLED

POLE

PUSHBUTTON STATION

PHASE

POTENTIAL TRANSFORMER

POWER DISTRIBUTION PANEL

RECEPTACLE

RECEPTACLE

RECEPTACLE DISTRIBUTION PANEL

RECEPTACLE PANEL

RIGID STEEL CONDUIT

SCHEDULE

SWITCH

SWITCHBOARD

SWITCHGEAR

TERMINAL BOX

TELECOMMUNICATIONS

TAMPER RESISTANT

TELEPHONE TERMINAL BACKBOARD

TYPICAL

UNLESS OTHERWISE NOTED

UPSTAGE

VOLTS

WIRE OR WATTS

WIRE GUARD

WEATHERPROOF

TRANSFORMER

EXPLOSION PROOF

EXISTING

RELOCATED

ELECTRICAL SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE - ARCHITECTURAL TROFFER

EMERGENCY LIGHTING FIXTURE

LIGHTING FIXTURE - PENDANT

WALL MOUNTED LIGHTING FIXTURE

LIGHTING FIXTURE

LIGHTING TRACK OR ROPE LIGHT

TRACK LIGHTING FIXTURE

EMERGENCY LIGHTING UNIT

POLE MOUNTED LIGHTING FIXTURE

POLE MOUNTED LIGHTING FIXTURE - POST TOP

BOLLARD LIGHTING FIXTURE

EXIT LIGHTING FIXTURE WITH DIRECTIONAL

ARROWS (SHADED AREA INDICATES FACE)

EXIT LIGHTING FIXTURE WITH DIRECTIONAL

ARROWS (SHADED AREA INDICATES FACE)

EXIT LIGHTING FIXTURE - WALL MOUNTED

SINGLE POLE TOGGLE SWITCH

TWO POLE TOGGLE SWITCH

3 WAY TOGGLE SWITCH

4 WAY TOGGLE SWITCH

KEY OPERATED SWITCH

DIMMER SWITCH

PILOT SWITCH

OCCUPANCY SENSOR DEVICE - CEILING

SIMPLEX / DUPLEX RECEPTACLE

SIMPLEX / DUPLEX RECEPTACLE CONTROLLED BY

AUTOMATIC CONTROL DEVICE / SYSTEM

QUAD RECEPTACLE

ABOVE COUNTER DUPLEX RECEPTACLE (SIMILAR FOR

TAMPER RESISTANT, QUADS, EMERGENCY AND GFI

RECEPTACLES)

DUPLEX RECEPTACLE-GROUND FAULT CIRCUIT

INTERRUPTER

DUPLEX EMERGENCY RECEPTACLE

CEILING MOUNTED

DUPLEX RECEPTACLE

SPECIAL RECEPTACLE - REFER TO ELECTRICAL

STANDARD SCHEDULES

MULTI-OUTLET RACEWAY - LEGRAND AL3300 OR EQUAL

POKE-THROUGH ASSEMBLY - LEGRAND

EVOLUTION SERIES OR EQUAL

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

CONTROL PANEL

VARIABLE FREQUENCY DRIVE

MOTOR

MANUAL CONTROLLER

MAGNETIC CONTROLLER

COMBINATION MAGNETIC CONTROLLER

NON-FUSIBLE DISCONNECT SWITCH

FUSIBLE DISCONNECT SWITCH

ENCLOSED CIRCUIT BREAKER

PUSH BUTTON STATION

AUTOMATIC DOOR CONTROLLER

AUTOMATIC DOOR PUSH PAD OPERATOR

GROUND ROD

GROUND CONNECTION

CONDUIT SLEEVE WITH BUSHINGS; LENGTH AS REQUIRED

"X" INDICATES CONDUIT SIZE

CONDUIT STUB - UP/DOWN

EMPTY BOX FOR FUTURE

TELECOMMUNICATION OUTLET

EMPTY BOX FOR FUTURE TELECOMMUNICATION

OUTLET MOUNTED 4" ABOVE COUNTERTOP

EMPTY BOX FOR FUTURE CEILING MOUNTED

TELECOMMUNICATION OUTLET

TELECOMMUNICATION OUTLET

"X" INDICATES TYPE

SPEAKER

SPEAKER - WALL MOUNTED

MICROPHONE

VOLUME CONTROL

SIGNALING BELL

SINGLE FACE CLOCK - CEILING MOUNTED

SINGLE FACE CLOCK - WALL MOUNTED

DOUBLE FACE CLOCK - CEILING MOUNTED

DOUBLE FACE CLOCK - WALL MOUNTED

P

PT

FB

CP

VFD

CB

DP

PP

X

X

S

S

MIC

VC

B

USB RECEPTACLE

GENERATOR TRANSFER DEVICEGTD

REMOTE GENERATOR ANNUNCIATOR PANELRGP

AUTOMATIC TRANSFER SWITCHATS

SWITCHBOARD

BRANCH CIRCUIT PANEL BOARD - 208/120V

TRANSFORMER

DISTRIBUTION PANEL - 208/120V

SECURITY CAMERA

MOTION DETECTOR

SECURITY KEY SWITCH

DOOR CONTACT

KEY PAD

CARD READER

CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER

MANUALLY/ OPERATED

SWITCH

AUTOMATIC OR MANUAL TRANSFER

SWITCH

FUSE

TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

LIGHTNING ARRESTOR

PANELBOARD

"X" INDICATES PANELBOARD NAME

GROUND

SECURITY KEY INTERLOCK

ENGINE GENERATOR

UTILITY METER

AMMETER

VOLTMETER

AMMETER SWITCH

VOLTMETER SWITCH

SURGE PROTECTIVE DEVICE

TIME DELAY RELAY

THERMAL OVERLOAD RELAY

NORMALLY OPEN CONTACTS

NORMALLY CLOSED CONTACTS

N.O. PUSH BUTTON SINGLE CIRCUIT

N.C. PUSH BUTTON SINGLE CIRCUIT

GROUND BUS

MD

K

DC

KP

CR

X

K

G

M

A

V

AS

VS

SPD

TDR

GB

DURESS PUSH BUTTON STATION

DELAYED EGRESS

DB

DE

REQUEST TO EXIT STATIONREX

MANUAL FIRE ALARM PULL STATION

SMOKE DETECTOR

REMOTE TEST STATION (FOR DUCT DETECTOR)

FIRE ALARM BELL

NOTIFICATION APPLIANCE - WALL MOUNT SPEAKER/STROBE

TAMPER SWITCH

FLOW SWITCH

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

F

SD

RT

F

F

TS

FS

FACP

FAA

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANELNAC

R E

F E

R T

O E

L E

C T

R

IC

L

T

A N

D A

R D

S C

H E

D U

L E

S

DIMMER OCCUPANCY SENSOR SWITCH

LOW VOLTAGE DIMMER SWITCH

POWER POLE - WIREMOLD TYPE

F NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER/STROBE

LIGHTING CONTROL DEVICE - REFER TO LIGHTING

CONTROL SCHEDULE

LC

K

D

OS

LV

GFI

USB

CLG

FLOOR BOX ASSEMBLY - LEGRAND

EVOLUTION SERIES OR EQUAL

TOUCH SCREEN SWITCHTS

OS

OCCUPANCY SENSOR DEVICE - WALLOS

PC PHOTOCELL DEVICE - REFER TO ZONES SHOWN ON

PLANS

EQ

EQUIPMENT CONNECTION - REFER TO ELECTRICAL

FEEDER AND PANEL SCHEDULE FOR BREAKER AND

CONDUCTOR SIZE/QUANTITY

J JUNCTION BOX

EMERGENCY POWER OFF BUTTON

V NOTIFICATION APPLIANCE - CEILING MOUNT STROBE

NOTIFICATION APPLIANCE - WALL MOUNT STROBEV

BRANCH CIRCUIT PANEL BOARD - 480/277V

DISTRIBUTION PANEL - 480/277V

CARBON MONOXIDE DETECTORCO

HEAT DETECTORHD

BEAM DETECTORBD

DUCT DETECTORDD

SMOKE DETECTOR - ELEVATOR TYPE; CONNECT TO FIRE ALARM

SYSTEM AND ELEVATOR CONTROL PANEL

SD

E

SPRINKLER VALVE MONITOR SWITCHOSY

SMOKE DAMPERSD

MAGNETIC DOOR HOLDERDH

S NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER

NOTIFICATION APPLIANCE - WALL MOUNT SPEAKERS

FIRE ALARM BATTERY CABINETBATT

EXIT FIXTURE-BACK

MOUNTED BOTTOM OF EXIT

SIGN TO BE 4" ABOVE TOP OF

DOOR FRAME

EXIT

EXIT

1' -6

EXIT

A/C SUPPLY

DIFFUSER

90" MAX (IBC)

4' -0

5"

8' -6

EXIT-CEILING MOUNTED

EXIT-FIXTURE END

MOUNTED

NFPA 72 AUDIBLE APPLIANCE 6" MIN

BELOW FINISHED CEILING

EMERGENCY

BATTERY

FIXTURE

ABOVE FINISHED FLOOR

AUDIBLE 80" MIN (IBC)

CEILING HEIGHTS LESS THEN 86" VISUAL

LENS MOUNTING HEIGHT WILL BE WITHIN 6"

OF THE CEILING

FINISHED CEILING

AUDIO/VISUAL &

VISUAL ONLY

DEVICES

SYNCHRONIZE MORE THAN

TWO APPLIANCES IN ANY

FIELD OF VIEW

MANUAL PULL STATION

AUDIBLE

ONLY

'-8

DOOR WIDTH LESS THEN 3'-0"

(MODIFY FOR DIFFERENT

DOOR WIDTHS)

FINISHED FLOOR

O R

A P

P R

O V

E D

F R

O M

A H

J

M

IN

B

O V

E F

IN

IS

H E

D F

L O

O R

CEILING MOUNTED SMOKE/HEAT

DETECTOR

3'-0" MIN 4"

NOTES:

1. INSTALL ELECTRICAL DEVICES AT MOUNTING HEIGHTS NOTED ABOVE UNLESS OTHERWISE NOTED ON PLANS. COORDINATE WITH ALL OTHER DISCIPLINES PRIOR TO INSTALL.

2. VISUAL MOUNTING APPLIANCE MOUNTING HEIGHT IN SLEEPING ROOMS:

A. MINIMUM DISTANCE IN SLEEPING ROOMS IS 24" FROM CEILING TO THE TOP OF LENS FOR 110cd STROBES WITHIN 16' OF PILLOW

B. 177cd STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING, THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER

7' -6

(M

IN

(M

A X

1' -0

"4"

M A

X

DO NOT INSTALL HEAT DETECTOR IN

SHADED AREA

WALL MOUNTED

SMOKE/HEAT

DETECTOR

MAGNETIC

DOOR

HOLDER

FINISHED WALL

SWITCHBANK

AUTOMATIC DOOR OPERATOR PUSH

BUTTON

RECEPTACLE, DATA JACK OR

TELEPHONE JACK

3'-0"

5' MAX TO EXIT DOOR

4' -0

4"

7' -6

ELECTRICAL DEVICE TYPICAL MOUNTING HEIGHTS

6' -6

BRANCH CIRCUIT PANELBOARDS

DISCONNECT SWITCH

5' -0

KINGSCOTT ASSOCIATES INC. PORTAGE, CC

JOB

SHEET

TITLE

SHEET

NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS |

Gull Lake Community Schools

/8

/2

:5

:0

A

M

A u to d e s k D o c s

/G L C

S

S in k in g F u n d /2

.1

K

G A

G

U L L L

A K

E K

E L L O

G G

E L E

M E

N T

A R

Y G

Y M

C O

O L

IN

G M

E P

.r v t

2288.77

ELECTRICAL SYMBOLS AND

GENERAL NOTES

E000

N th S tr e e t

H ic ko ry

C o rn e rs

M

I

G u ll

L a k e

C o m m u n it y S c h o o ls

K E

L L

O G

G

S

IN

K

IN

G

F U

N D

ESTIMATION

ON HOLD

CONSTRUCTION DOCUMENTS

12/19/2025

01/20/2026

04/09/2026

NOTE: SOME SYMBOLS AND ABBREVIATIONS SHOWN

MAY NOT APPLY TO THIS PROJECT.

ELECTRICAL SPECIFICATION

1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.

2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.

3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY FUNCTIONAL ELECTRICAL SERVICE.

4. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.

5. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.

6. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:

A. CONDUIT.

B. CONDUCTORS.

C. WIRING DEVICES INCLUDING COVERPLATES.

D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.

E. PANELBOARDS. AND SWITCHBOARDS

F. TRANSFORMERS.

G. SURGE PROTECTION DEVICES

H. POWER METERS.

I. INTERIOR LIGHT FIXTURES.

J. EXTERIOR LIGHT FIXTURES INCLUDING SITE POLES.

K. LIGHTING CONTROL SYSTEM AND DEVICES.

L. FIRE ALARM SYSTEM.

7. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.

8. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.

9. PROVIDE LAMACOID LABELS FOR:

A. PANELBOARDS AND SWITCHBOARDS.

B. TRANSFORMERS.

C. DISCONNECT SWITCHES.

D. VARIABLE FREQUENCY DRIVES.

E. LIGHTING CONTROL PANELS. LABEL SHALL INDICATE ROOMS CONTROLLED.

10. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.

11. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:

A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.

B. OUTDOORS: RIGID GALVANIZED STEEL.

C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.

D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.

12. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.

13. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.

14. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS.

15. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING.

16. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.

17. EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-EMERGNECY CIRCUITS.

18. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUITS OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR VOLTAGE DROP.

19. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.

20. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.

21. PANELBOARDS SHALL BE FULLY RATED, SERIES RATED PANELS ARE NOT ACCEPTABLE. HAVE HINGED SWING DOOR-IN-DOOR. LOAD CENTERS ARE NOT ACCEPTABLE. SQUARE D NQOD OR EQUAL FOR

208/120V BRANCH PANELBOARDS. SQUARE D NF OR EQUAL FOR 480/277V PANELBOARDS. PROVIDE TYPED PANELBOARD CIRCUIT LABEL CARDS. UPDATE ALL EXISTING LABEL CARDS AS REQUIRED.

22. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.

23. ALL FLOOR MOUNTED EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PAD.

24. RECEPTACLES SHALL BE TAMPER-RESISTANT EXTRA HEAVY DUTY GRADE, 20AMP MINIMUM. WHITE IN COLOR UNLESS NOTED OTHERWISE.

25. ALL DEVICE COVERS SHALL MATCH DEVICE COLOR UNLESS STAINLESS STEEL COVERS ARE SPECIFIED.

26. WEATHERPROOF RECEPTACLE COVERS SHALL BE METAL, WHILE-IN-USE TYPE.

27. SWITCHES SHALL BE HEAVY DUTY GRADE, 20 AMP, QUIET TYPE, WHITE UNLESS NOTED OTHERWISE.

28. LIGHTING CONTROL DEVICES SHALL BE MANUFACTURED BY N-LIGHT, UNLESS NOTED OTHERWISE.

29. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013 WITH MICHIGAN AMENDMENTS.

30. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED.

INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL

INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND

LOCAL CODES.

MIF CO H E IGT AAT NS

No.

6201060604

JONATHAN

RUMOHR

ENGINEER

PART 1 - GENERAL

1. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM

INVOLVED IS NOT PARTICULARLY MENTIONED. INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK

INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE

AND LOCAL CODES.

2. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.

3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.

4. DO NOT INTERRUPT EXISTING ELECTRICAL SERVICE TO FACILITIES WITHOUT WRITTEN PERMISSION BY OWNER. COORDINATE WORK WITH EXISTING

ELECTRICAL SERVICES WITH OWNER AND UTILITY COMPANY.

5. ARRANGE TO PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR SCOPE OF WORK.

6. PROVIDE NEW ELECTRICAL SERVICES FROM UTILITY COMPANY AS DIRECTED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A

FULLY FUNCTIONAL ELECTRICAL SERVICE.

7. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:

A. CONDUIT

B. CONDUCTORS

C. WIRING DEVICES, INCLUDING COVER PLATES

D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES

E. PANELBOARDS AND SWITCHBOARDS

F. SURGE PROTECTION DEVICES

G. INTERIOR AND EXTERIOR LIGHTING FIXTURES, INCLUDING SITE POLES

H. LIGHTING CONTROL SYSTEM AND DEVICES

I. FIRE ALARM SYSTEM

PART 2 - EXECUTION

1. PROVIDE SCHEDULE FOR ELECTRICAL INSTALLATION WORK TO OWNER AND ARCHITECT FOR MAJOR MILESTONE DATES.

2. COORDINATION DRAWINGS; PROVIDE COORDINATION DRAWINGS FOR FOLLOWING INSTALLATIONS:

A. LARGE INDOOR EQUIPMENT INSTALLATIONS.

B. LARGE OUTDOOR EQUIPMENT INSTALLATIONS.

3. DEMOLITION WORK

A. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC., ASSOCIATED WITH DEMOLISHED EQUIPMENT.

B. REMOVE ALL ABANDONED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.

C. PATCH, REPAIR AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS OR FLOORS TO MATCH EXISTING CONDITION. MAINTAIN ALL FIRE

RATINGS OF WALLS AND DOORS.

D. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.

4. CLOSEOUT ACTIVITIES

A. PROVIDE NORMAL OPERATION, EMERGENCY OPERATION AND PREVENTIVE MAINTENANCE MANUALS FOR EACH SYSTEM, EQUIPMENT AND DEVICE.

B. PROVIDE SOFTWARE AND FIRMWARE OPERATION DOCUMENTATION FOR SYSTEM INSTALLED.

C. PROVIDE BACKUP, UPGRADES AND UNRESTRICTED LICENSES FOR INSTALLED SOFTWARE, INCLUDING OPERATING SYSTEMS AND PROGRAMMING

TOOLS REQUIRED FOR MAINTENANCE AND OPERATION.

SECTION 26 0010

SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUCTORS AND CABLES INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. COPPER BUILDING WIRE

A. FLEXIBLE, INSULATED, DRAWN COPPER WITH AN INSULATION JACKET, RATED 600V OR LESS.

B. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.

C. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUIT(S) OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR

VOLTAGE DROP.

D. PROVIDE COLOR CODED WIRE WITH DIFFERENT COLOR FOR EACH PHASE, NEUTRAL AND GROUND, BASED ON ELECTRICAL SYSTEM TYPE.

2. CONNECTORS AND SPLICES

A. FACTORY-FABRICATED CONNECTORS, SPLICES, AND LUGS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE

INDICATED.

B. SHALL BE MARKED FOR INTENDED LOCATION AND USE.

PART 3 - EXECUTION

1. INSTALLATION

A. CONCEAL CABLES IN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE NOTED.

B. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE WIRE/CABLE GRIPS, THAT WILL NOT DAMAGE CABLES OR RACEWAY.

USE MANUFACTURER APPROVED PULLING COMPOUND OR LUBRICANT WHEN NECESSARY.

C. INSTALL CONDUCTORS AT EACH OUTLET, WITH AT LEAST 12" OF SLACK.

D. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.

2. CONNECTIONS

A. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES.

B. SPLICES, TERMINATIONS, AND TAPS SHALL BE COMPATIBLE WITH CONDUCTOR MATERIAL.

C. CONDUCTORS SHALL BE CONTINUOUS FROM ORIGIN TO PANEL OR EQUIPMENT TERMINATION WHERE POSSIBLE. SPLICES AND TAPS, WHERE

REQUIRED, SHALL BE MADE IN JUNCTION BOXES WITH SUITABLE CONNECTORS.

3. ACCEPTANCE

A. ALL CONDUCTORS AND CONNECTIONS SHALL TEST FREE OF GROUNDS, SHORTS, AND OPENS PRIOR TO ENERGIZING CIRCUIT.

SECTION 26 0519

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUIT AND RACEWAY PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. ALL PRODUCTS SHALL BE UL LISTED AND LABELED.

2. EMT - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).

3. RMC - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).

4. FMC - FLEXIBLE, STEEL. PROVIDE AT TERMINATION POINT FOR EQUIPMENT SUBJECT TO MOTION AND VIBRATION.

5. MC CABLE - COLOR-CODED COPPER CONDUCTORS WITH INTERLOCKING GALVANIZED STEEL SHEATHING.

6. PVC - SCHEDULE 40, SCHEDULE 80, FOR USE WITH MAXIMUM 90 DEG C WIRE.

7. FITTINGS

A. SHALL BE LISTED FOR USE WITH RACEWAY SYSTEM TO BE INSTALLED.

PART 3 - EXECUTION

1. CONDUIT TYPE SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH IT IS LOCATED:

A. INDOORS - EMT, AND/OR RMC, WITH SET-SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.

B. OUTDOORS - RIGID GALVANIZED STEEL.

C. UNDERGROUND - RIGID, NON-METALLIC SCHEDULE 80 PVC.

a. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED ABOVE GROUND.

2. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.

3. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.

4. USE LARGE RADIUS ELLS FOR ALL CONDUIT BENDS.

5. CONDUITS SHALL BE CONCEALED WITHIN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED. CONDUITS SHALL BE

SUPPORTED WITHIN 12" OF ENCLOSURES TO WHICH ATTACHED.

6. INSTALL RACEWAY SEALS AND FITTINGS AT ACCESSIBLE LOCATIONS.

7. DO NOT INSTALL CONDUITS WITHIN 2" OF THE BOTTOM SIDE OF METAL DECK ROOF.

8. KEEP CONDUITS AT LEAST 6" AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES.

9. INSTALL PULL WIRES IN EMPTY RACEWAYS FOR FUTURE USE. PROVIDE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN

200lb TENSILE STRENGTH. LEAVE AT LEAST 12" OF SLACK AT BOTH ENDS OF CONDUIT.

10. CAP AND SEAL UNDERGROUND RACEWAYS DESIGNATED AS SPARE ABOVE GRADE ALONGSIDE DUCT RACEWAYS IN USE.

11. PROVIDE SEPARATE RACEWAY SYSTEM FOR EMERGENCY CIRCUIT(S). EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-

EMERGENCY CIRCUITS.

SECTION 26 0533.13

CONDUITS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL GROUNDING AND BONDING PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. GROUNDING AND BONDING CONDUCTORS

A. PROVIDE THHN/THWN-2, TINNED-COPPER WIRE OR CABLE, GREEN COLOR. CABLE SHALL BE RATED 600V.

2. GROUNDING AND BONDING CLAMPS

A. CLAMPS SUITABLE FOR ATTACHMENT OF GROUNDING AND BONDING CONDUCTORS TO ELECTRODES, PIPES, TUBING, AND REBAR. SUITABLE TYPES

SHALL BE:

a. STRAP-TYPE PIPE AND ROD CLAMPS

b. BEAM GROUNDING CLAMPS

c. EXOTHERMICALLY WELDED CONNECTIONS

3. GROUNDING (EARTHING) ELECTRODES

A. COPPER CLAD STEEL

B. 3/4" DIAMETER BY 10' LENGTH

PART 3 - EXECUTION

1. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.

2. GROUNDING AND BONDING CONDUCTORS

A. PROVIDE SOLID CONDUCTOR FOR 8 AWG AND SMALLER, AND STRANDED CONDUCTORS FOR 6 AWG AND LARGER, UNLESS OTHERWISE NOTED.

B. ROUTE CONDUCTORS ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE. AVOID OBSTRUCTING ACCESS TO OR PLACING CONDUCTORS WHERE

THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE.

C. PROVIDE GROUNDING AND BONDING BUSBARS IN ELECTRICAL EQUIPMENT ROOMS, ROOMS HOUSING SERVICE EQUIPMENT, AND ELSEWHERE

INDICATED ON DRAWINGS.

3. CONNECTIONS

A. MAKE CONNECTIONS SO POSSIBILITY OF GALVANIC ACTION OR ELECTROLYSIS IS MINIMIZED.

B. USE EXOTHERMIC WELDS FOR ALL BELOW GRADE CONNECTIONS.

4. GROUNDING ELECTRODES

A. DRIVE GROUND RODS UNTIL TOPS ARE 2" BELOW FINISHED FLOOR OR GRADE.

B. INSTALL AT LEAST (3) RODS SPACED AT LEAST ONE-ROD LENGTH FROM EACH OTHER AND CONNECT TO SERVICE GROUNDING ELECTRODE

CONDUCTOR.

C. FOR CONCRETE-ENCASED ELECTRODE (UFER GROUND), USE MINIMUM 20' OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG.

a. IF FOUNDATION IS LESS THAN 20' LONG, COIL EXCESS CONDUCTOR WITHIN BASE OF FOUNDATION.

b. BOND GROUNDING CONDUCTOR TO REINFORCING STEEL IN AT LEAST (4) LOCATIONS AND TO ANCHOR BOLTS. EXTEND GROUNDING CONDUCTOR

BELOW GRADE AND CONNECT TO GROUNDING GRID OR GROUNDING ELECTRODE EXTERNAL TO CONCRETE.

5. EQUIPMENT GROUNDING AND BONDING

A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH THE FOLLOWING ITEMS:

a. FEEDERS AND BRANCH CIRCUITS

b. LIGHTING CIRCUITS

c. RECEPTACLE CIRCUITS

d. SINGLE, AND THREE-PHASE MOTOR AND APPLIANCE BRANCH CIRCUITS

e. FLEXIBLE RACEWAY, ARMORED, AND METAL-CLAD CABLE RUNS

B. ALL CORRUGATED STAINLESS STEEL TUBING FOR GAS PIPING SYSTEM IN KITCHENS SHALL BE BONDING TO THE GROUNDING ELECTRODE SYSTEM.

BONDING JUMPER SHALL NOT BE SMALLER THAN 6 AWG.

SECTION 26 0526

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SUPPORT, ANCHORAGE, AND ATTACHMENT PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

A. STEEL HANGERS, CLAMPS, AND ASSOCIATED FITTINGS SHALL BE DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED.

B. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS FOR FASTENING ELECTRICAL ITEMS OR SUPPORTS TO BUILDING SURFACES:

a. POWDER-ACTUATED FASTENERS

b. MECHANICAL-EXPANSION ANCHORS

c. CONCRETE INSERTS

d. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS

e. THROUGH BOLTS AND TOGGLE BOLTS

f. HANGER RODS

PART 3 - EXECUTION

A. SUPPORT INSTALLATION

a. PROVIDE SIZES OF COMPONENTS SO STRENGTH WILL BE ADEQUATE TO CARRY PRESENT AND FUTURE STATIC LOADS WITHIN SPECIFIED LIMITS.

b. CUT, FIT, AND PLACE MISCELLANEOUS METAL SUPPORTS ACCURATELY IN LOCATION, ALIGNMENT, AND ELEVATION TO SUPPORT AND ANCHOR

ELECTRICAL MATERIALS AND EQUIPMENT.

B. CONCRETE BASES

a. ALL FLOOR MOUNT ELECTRICAL EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PADS. PADS SHALL BE NOT LESS THAN 4" LARGER IN BOTH

DIRECTIONS OF ELECTRICAL EQUIPMENT TO BE SUPPORTED.

C. TOUCHUP

a. CLEAN WELDS AND ABRADED AREAS OF SHOP PAINT. PAINT EXPOSED AREAS IMMEDIATELY AFTER ERECTING HANGERS AND SUPPORTS.

SECTION 26 0529

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SURGE PROTECTIVE DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. MANUFACTURER

A. RAYCAP

a. TYPE 1, SERVICE ENTRANCE - RAYVOSS

b. TYPE 2, BRANCH PANEL - RSE2

2. GENERAL CHARACTERISTICS

A. MCOV: NOT LESS THAN 125% OF NOMINAL SYSTEM VOLTAGE FOR 208Y/120V AND 120/240V SYSTEMS. NOT LESS THAN 115% OF NOMINAL

SYSTEM VOLTAGE FOR 480Y/277V SYSTEMS.

B. PEAK SURGE CURRENT RATING: MINIMUM SINGLE-PULSE SURGE CURRENT WITHSTAND RATING PER PHASE SHALL BE NOT LESS THAN -

a. TYPE 1: 160, OR 240 kA.

b. TYPE 2: 50, 100, 150, OR 200 kA.

C. PROTECTION MODES: DEVICE SHALL HAVE PROTECTION MODES FOR LINE-TO-NEUTRAL, AND LINE-TO-LINE, FOR TYPE 1 DEVICES, AND LINE-TO-

NEUTRAL, LINE-TO-GROUND, NEUTRAL-TO-GROUND, AND LINE-TO-LINE, FOR TYPE 2 DEVICES.

3. OPTIONS

A. INTERNAL THERMAL PROTECTION TO DISCONNECT SPD BEFORE DAMAGING INTERNAL SUPPRESSOR COMPONENTS.

B. INDICATOR LIGHT DISPLAY FOR PROTECTION STATUS.

C. AUDIBLE ALARM.

D. NEMA ICS 5, DRY FORM-C CONTACTS RATED AT 1 A AND 120 VAC FOR REMOTE MONITORING OF PROTECTION STATUS.

E. TYPE 2 DEVICES: TOV AND SURGE COUNTER WITH TIME AND DATE STAMP.

PART 3 - EXECUTION

1. INSTALLATION

A. PROVIDE OCPD AND DISCONNECT FOR INSTALLATION OF SPD IN ACCORDANCE WITH UL 1449 AND MANUFACTURER INSTRUCTIONS.

B. INSTALL LEADS BETWEEN DISCONNECT(S) AND SPD(S) IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.

a. DO NOT SPLICE AND EXTEND SPD LEADS UNLESS PERMITTED BY MANUFACTURER.

b. DO NOT EXCEED MANUFACTURER RECOMMENDED LEAD LENGTH.

c. DO NOT BOND NEUTRAL AND GROUND.

d. USE CRIMPED CONNECTORS AND SPLICES ONLY. WIRE NUTS ARE NOT ACCEPTABLE.

C. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.

SECTION 26 4313

SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL BOX AND COVER PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. METALLIC OUTLET BOXES

A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.

B. MATERIAL SHALL BE SHEET METAL GALVANIZED STEEL, WITH A MINIMUM DEPTH OF 2.5".

C. BOXES SHALL HAVE PRYOUT OPENINGS, KNOCKOUTS, THREADED ENTRIES, OR HUBS IN EITHER SIDES OR BACK FOR CONDUITS OR CONDUIT

FITTINGS. SHALL HAVE PROVISIONS FOR MOUNTING OUTLET BOX COVER.

D. EXTENSION RINGS SHALL BE PROVIDED WHERE REQUIRED OR INDICATED ON DRAWINGS, TO EXTEND DEVICE BOX TO INCREASE DEPTH.

EXTENSION RINGS SHALL BE SUITABLE FOR USE WITH ASSOCIATED DEVICE BOX.

2. NONMETALLIC OUTLET BOXES

A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.

3. COVER PLATES

A. LISTED AND LABELED FOR INTENDED LOCATION AND USE WITH ASSOCIATED OUTLET BOX TYPE.

B. FOR USE IN FINISHED LOCATIONS: .032" THICK, TYPE 302/304 NON-MAGNETIC STAINLESS STEEL.

a. ALL DEVICE COVERS SHALL BE BRUSHED STAINLESS STEEL, UNLESS SPECIFIC DEVICE COLOR IS SPECIFIED.

C. PROVIDE GASKETS FOR WALLPLATES IN DAMP OR WET LOCATIONS.

D. WEATHERPROOF COVERS

a. SHALL BE METAL, "WHILE-IN-USE" TYPE. COVER SHALL BE GRAY COLOR.

PART 3 - EXECUTION

1. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.

A. CUT, PATCH, REPAIR AND PAINT GYPSUM AND/OR MASONRY WALLS TO RECESS NEW BOXES WHERE INDICATED.

B. HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY ARE NOT IN THE SAME VERTICAL CHANNEL.

2. PROVIDE NEMA 1 BOXES AND COVERS FOR INDOOR LOCATIONS, UNLESS OTHERWISE NOTED.

3. PROVIDE NEMA 3R BOXES AND COVERS FOR OUTDOOR LOCATIONS, UNLESS OTHERWISE NOTED.

4. SUPPORT

A. SUPPORT BOXES IN RECESSED CEILINGS INDEPENDENT OF CEILING TILES OR GRID.

B. SUPPORT JUNCTION OR PULL BOXES FROM BUILDING STRUCTURE. DO NOT SUPPORT BOXES BY CONDUIT(S).

5. ALL BOXES USED FOR LOW VOLTAGE DATA CABLING SHALL BE DOUBLE GANG, 3-1/2" DEEP WITH SINGLE GANG MUD RING. PROVIDE 1" CONDUIT TO

ABOVE ACCESSIBLE CEILING FOR DATA CABLING.

SECTION 26 0533.16

BOXES AND COVERS ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LABEL AND IDENTIFICATION PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. LABELS

A. LISTED AND LABELED FOR INTENDED LOCATION AND APPLICATION.

B. VINYL WRAPAROUND LABELS - PREPRINTED, FLEXIBLE LABELS LAMINATED WITH CLEAR, WEATHER AND CHEMICAL-RESISTANT COATING.

C. SELF-ADHESIVE WRAPAROUND LABELS - PREPRINTED, VINYL FLEXIBLE LABEL WITH ACRYLIC PRESSURE-SENSITIVE ADHESIVE.

D. SELF-ADHESIVE LABELS - POLYESTER VINYL, THERMAL, TRANSFER PRINTED, MULTI-COLOR, WEATHER AND UV-RESISTANT, PRESSURE-

SENSITIVE ADHESIVE.

E. SIZE

a. 1-1/2" BY 6" FOR RACEWAYS AND CONDUCTORS.

b. 3-1/2" BY 5" FOR EQUIPMENT.

2. SIGNS

A. LAMINATED ACRYLIC OR MELAMINE PLASTIC.

a. 1/16" THICK FOR SIGNS UP TO 20 SQ. IN.

b. 1/8" THICK FOR SIGNS GREATER THAN 20 SQ. IN.

c. ENGRAVED LEGEND WITH BLACK LETTERS ON WHITE FACE.

d. PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4" GROMMETS IN CORNERS FOR MOUNTING.

3. UNDERGROUND-LINE WARNING TAPE

A. SUITABLE TO IDENTIFY AND LOCATE UNDERGROUND ELECTRICAL AND COMMUNICATIONS UTILITY LINES.

B. PRINTING ON TAPE MUST BE PERMANENT AND NOT DAMAGED BY BURIAL OPERATIONS.

C. INSCRIPTIONS SHALL READ "CAUTION BURIED ELECTRIC LINE BELOW" OR "CAUTION BURIED COMMUNICATION LINE BELOW".

D. DETECTABLE WARNING TAPE

a. REINFORCED, DETECTABLE THREE-LAYER LAMINATE, CONSISTING OF ALUMINUM-FOIL CORE AND CLEAR PROTECTIVE FILM.

PART 3 - EXECUTION

1. PROVIDE BAKED ENAMEL SIGNS FOR:

A. PANELBOARDS AND SWITCHBOARDS

B. TRANSFORMERS

C. DISCONNECT SWITCHES

D. VARIABLE FREQUENCY DRIVES

E. LIGHTING CONTROL PANELS. LABELS SHALL INDICATED ROOMS CONTROLLED

2. IDENTIFY CONDUCTORS, CABLES, AND TERMINALS IN ENCLOSURES AND AT JUNCTIONS, TERMINALS, PULL POINTS, AND LOCATIONS OF HIGH

VISIBILITY. IDENTIFY BY SYSTEM AND CIRCUIT DESIGNATION.

3. PROVIDE UNDERGROUND-LINE WARNING TAPE FOR POWER, LIGHTING, AND COMMUNICATIONS CABLING.

4. LABEL INDIVIDUAL COVER PLATES WITH SELF-ADHESIVE LABELS. LABEL TO INDICATE CIRCUIT WHICH DEVICE IS FED FROM WITH THE FOLLOWING

INFORMATION:

A. PANELBOARD DESIGNATION - BRANCH CIRCUIT NUMBER.

5. INSTALL IDENTIFICATION MATERIALS AT LOCATIONS FOR MOST CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND

MAINTENANCE OF EQUIPMENT.

6. PROVIDE FLOOR MARKING TAPE TO INDICATE WORKING CLEARANCE OF ELECTRICAL EQUIPMENT. FLOOR MARKING TAPE SHALL NOT BE USED FOR

SURFACE OR FLUSH-MOUNTED PANELBOARDS AND SIMILAR EQUIPMENT IN FINISHED SPACES.

SECTION 26 0553

IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LIGHTING CONTROL PRODUCTS INSTALLED DURING COURSE OF WORK.

A. PROVIDE SUBMITTALS THAT INCLUDE INTERCONNECTION DIAGRAMS AND DIAGRAMS FOR POWER, SIGNAL, AND CONTROL WIRING.

PART 2 - PRODUCTS

1. ELECTROMECHANICAL DIAL-TIME SWITCHES

A. MANUFACTURER

a. INTERMATIC, INC.

b. LEVITON MANUFACTURING CO., INC.

c. NSI INDUSTRIES LLC

B. ASTRONOMICAL TIME DIAL.

C. SPST CONTACT, RATED FOR 20A BALLAST LOAD, 120/240 VAC.

D. ALLOW FOR CONNECTION OF A PHOTOELECTRIC RELAY AS A SUBSTITUTE FOR ON/OFF FUNCTION OF A PROGRAM.

E. EIGHT-DAY PROGRAM - UNIQUELY PROGRAMMABLE FOR EACH WEEKDAY OR HOLIDAY.

2. INDOOR OCCUPANCY AND VACANCY SENSORS

A. MANUFACTURER

a. N-LIGHT, UNLESS NOTED OTHERWISE.

B. WALL OR CEILING MOUNTED.

C. DUAL TECHNOLOGY, SEPARATE POWER PACK.

D. OCCUPANCY MODE - TURN LIGHTS ON WHEN AREA IS OCCUPIED AND OFF WHEN UNOCCUPIED. PROVIDE TIME DELAY FOR TURNING LIGHTS OFF

WITH ADJUSTABLE RANGE OF 1 TO 15 MINUTES.

E. VACANCY MODE - LIGHTS TO BE TURNED ON MANUALLY AND SENSOR TO TURN LIGHTS OFF WHEN AREA IS UNOCCUPIED. PROVIDE TIME DELAY

FOR TURNING LIGHTS OFF WITH ADJUSTABLE RANGE OF 1 TO 15 MINUTES.

F. POWER PACK - LINE VOLTAGE. DRY CONTACTS RATED FOR A 20A LED LOAD AT 120VAC AND 277VAC. POWER PACK TO CONTAIN AUXILIARY DRY

CONTACT FOR SPARE CONNECTION TO OTHER BUILDING SYSTEM(S).

3. SWITCHBOX-MOUNTED OCCUPANCY SENSORS

A. MANUFACTURER

a. N-LIGHT, UNLESS OTHERWISE NOTED.

B. OPERATION - TURN LIGHTS ON WHEN AREA IS OCCUPIED AND OFF WHEN UNOCCUPIED. PROVIDE TIME DELAY FOR TURNING LIGHTS OFF WITH

ADJUSTABLE RANGE OF 1 TO 15 MINUTES.

C. SWITCH RATING - NOT LESS THAN 800 VA LED LOAD AT 120 VAC, 1200 VA LED LOAD AT 277 VAC, AND 800 W INCANDESCENT.

D. SENSOR TECHNOLOGY - DUAL TECHNOLOGY - PIR AND ULTRASONIC.

E. VOLTAGE TO MATCH THE CIRCUIT VOLTAGE.

F. COLOR TO MATCH WIRING DEVICE FINISHES. FACEPLATE FINISH TO BE BRUSHED STAINLESS STEEL, UNLESS OTHERWISE INDICATED.

PART 3 - EXECUTION

1. INSTALLATION

A. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013, WITH MICHIGAN AMENDMENTS.

B. COORDINATE LAYOUT AND INSTALLATION OF CEILING-MOUNTED DEVICES WITH OTHER BUILDING SYSTEMS THAT PENETRATE CEILINGS.

C. INSTALL AND AIM SENSORS IN LOCATIONS TO ACHIEVE NOT LESS THAN 90% COVERAGE OF AREAS INDICATED.

D. MOUNT ELECTRICALLY HELD LIGHTING CONTACTORS WITH ELASTOMER ISOLATOR PADS TO ELIMINATE VIBRATION.

E. SIZE CONDUCTORS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.

F. ALL EXPOSED WIRING AREAS SHALL BE INSTALLED IN CONDUIT. NO EXPOSED LOW VOLTAGE WIRING WILL BE ALLOWED.

2. IDENTIFICATION

A. IDENTIFY CONTROLLED CIRCUITS IN LIGHTING CONTRACTORS.

B. IDENTIFY CIRCUITS OR LUMINAIRES CONTROLLED BY PHOTOELECTRIC AND OCCUPANCY SENSORS AT EACH SENSOR.

SECTION 26 0923

LIGHTING CONTROL DEVICES

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL PANELBOARD PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. MANUFACTURER

A. SQUARE D - NQOD FOR 208/120V BRANCH PANELBOARDS, NF FOR 480/277V BRANCH PANELBOARDS.

B. OR EQUAL BY:

a. EATON CORP.

b. SIEMENS

2. ELECTRICAL COMPONENTS, DEVICES, AND EQUIPMENT SHALL BE UL LABELED.

3. ENCLOSURES

A. RATED FOR ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION

a. INDOOR, DRY AND CLEAN LOCATIONS - NEMA 1

b. OUTDOOR LOCATIONS - NEMA 3R

c. KITCHEN LOCATIONS - NEMA 4X, STAINLESS STEEL

d. OTHER WET AND DAMP INDOOR LOCATIONS - NEMA 4

B. FRONT - SECURE TO BOX WITH CONCEALED TRIM CLAMPS. FOR SURFACE-MOUNTED FRONTS, MATCH DIMENSIONS; FOR FLUSH-MOUNTED

FRONTS, OVERLAP BOX. TRIMS MUST COVER LIVE PARTS AND MAY HAVE NO EXPOSED HARDWARE.

4. BUSES

A. TIN-PLATED ALUMINUM FOR 400A OR LESS.

B. HARD DRAWN COPPER FOR ABOVE 400A.

5. CONDUCTOR CONNECTORS

A. TIN-PLATED ALUMINUM OR HARD DRAWN COPPER, 98% CONDUCTIVITY.

B. MAIN AND NEUTRAL LUGS - MECHANICAL TYPE, WITH LUG ON NEUTRAL BAR FOR EACH POLE IN PANELBOARD.

C. GROUND LUGS AND BUS-CONFIGURED TERMINATORS - MECHANICAL TYPE, WITH LUG ON BAR FOR EACH POLE IN PANELBOARD.

D. SUBFEED LUGS - MECHANICAL TYPE, SUITABLE FOR USE WITH CONDUCTOR MATERIAL. LOCATE AT SAME END OF BUS AS INCOMING LUGS OR

MAIN DEVICE.

6. SHORT-CIRCUIT CURRENT RATING

A. FULLY RATED TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS. SERIES RATED PANELS ARE NOT

ACCEPTABLE.

7. OVERCURRENT PROTECTIVE DEVICES

A. THERMAL-MAGNETIC CIRCUIT BREAKERS

a. INVERSE TIME CURRENT ELEMENT FOR LOW-LEVEL OVERLOADS.

b. INSTANTANEOUS MAGNETIC TRIP ELEMENT FOR SHORT CIRCUITS.

c. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT-BREAKER FRAME SIZES 250A AND LARGER.

B. ELECTRONIC TRIP CIRCUIT BREAKERS

a. RMS SENSING.

b. FIELD-REPLACEABLE RATING PLUG OR ELECTRONIC TRIP.

c. FIELD ADJUSTABLE SETTINGS FOR: INSTANTANEOUS TRIP, LONG AND SHORT TIME PICKUP LEVELS, LONG AND SHORT TIME ADJUSTMENTS, AND GROUND FAULT PICKUP LEVEL, TIME DELAY AND I

T RESPONSE.

C. SUBFEED CIRCUIT BREAKERS SHALL BE VERTICALLY ARRANGED ON PHASE BUSBARS.

PART 3 - EXECUTION

1. INSTALLATION

A. MOUNT TOP OF PANELBOARD TRIP 7.5' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED.

B. MOUNT PANELBOARD CABINET PLUMB AND RIGID WITHOUT DISTORTION OF BOX.

C. MOUNT RECESSED PANELBOARDS WITH FRONT UNIFORMLY FLUSH WITH WALL FINISH.

a. FOR RECESSED PANELBOARDS, STUB (4) 1" EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED

TO BE CEILING SPACE IN FUTURE.

D. MAKE GROUNDING CONNECTIONS AND BOND NEUTRAL FOR SERVICES AND SEPARATELY DERIVED SYSTEMS TO GROUND. MAKE CONNECTIONS

TO GROUNDING ELECTRODES, SEPARATE GROUNDS FOR ISOLATED GROUND BARS, AND CONNECTIONS TO SEPARATE GROUND BARS.

2. IDENTIFICATION

A. PANELBOARD LABEL MUST LIST MANUFACTURER NAME, TRADEMARK, VOLTAGE, AMPERAGE, NUMBER OF PHASES, AND NUMBER OF POLES AND

MUST BE LOCATED ON INTERIOR OF PANELBOARD DOOR.

B. CIRCUIT BREAKER LABELS MUST LIST CURRENT RATING, UL AND IEC CERTIFICATION STANDARDS, AND AIC RATING.

C. CIRCUIT DIRECTORY

a. PROVIDE CIRCUIT DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTED IN TRANSPARENT CARD HOLDER.

b. PANELBOARD DIRECTORY SHALL BE TYPE-WRITTEN, AND PROVIDE DETAILED INFORMATION SHOWN ON ASSOCIATED PANELBOARD LOAD

SCHEDULE.

c. UPDATE ALL EXISTING CIRCUIT DIRECTORY CARDS AS REQUIRED.

SECTION 26 2416

PANELBOARDS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL WIRING DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. GENERAL USE SWITCHES

A. MANUFACTURER

a. ARROW HART, WIRING DEVICES

b. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.

c. LEVITON MANUFACTURING CO., INC.

d. PASS & SEYMOUR, LEGRAND NORTH AMERICA, LLC

B. GENERAL CHARACTERISTICS

a. HEAVY DUTY GRADE, QUIET TYPE, 120/277 VAC, RATED 20A MINIMUM.

b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.

c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.

2. STRAIGHT-BLADE RECEPTACLES

A. MANUFACTURER

a. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.

B. GENERAL CHARACTERISTICS

a. EXTRA HEAVY DUTY GRADE, TAMPER-RESISTANT, RATED 20A MINIMUM.

b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.

c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.

PART 3 - EXECUTION

1. INSTALLATION

A. UNLESS OTHERWISE INDICATED, INSTALL SWITCHES, RECEPTACLES, AND OTHER WIRING DEVICES, AT MOUNTING HEIGHTS RECOMMENDED IN

NECA NEIS 1.

B. ORIENT RECEPTACLES TO MATCH CONFIGURATION DIAGRAM IN NEMA WD 6.

a. RECEPTACLES ORIENTED HORIZONTALLY SHALL BE MOUNTED WITH NEUTRAL BLADE FACING UP.

2. IDENTIFICATION

A. MARK INSIDE OF COVER OR COVER PLATE OF WIRING DEVICE(S) WITH PANELBOARD AND CIRCUIT NUMBER FEEDING WIRING DEVICE(S).

SECTION 26 2726

WIRING DEVICES

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LED LIGHTING PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. GENERAL CHARACTERISTICS

A. PROVIDE ALL INTERIOR AND EXTERIOR LUMINAIRES AS INDICATED ON THE LIGHT FIXTURE SCHEDULE.

B. ELECTRICAL COMPONENTS, DEVICES AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING

AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.

C. METAL PARTS SHALL BE FREE OF BURRS AND SHARP CORNERS AND EDGES. SHEET METAL COMPONENTS SHALL BE STEEL UNLESS

OTHERWISE INDICATED. FORM AND SUPPORT SHALL PREVENT WARPING AND SAGGING.

D. LUMINAIRE FINISHES SHALL BE FACTORY APPLIED AND RATED FOR THE INTENDED LOCATION AND APPLICATION.

E. LUMINAIRE SUPPORT

a. SINGLE-STEM HANGARS: 1/2" STEEL TUBING WITH SWIVEL BALL FITTINGS AND CEILING CANOPY. FINISH SAME AS LUMINAIRE.

b. WIRES: 12 GAUGE, CLASS 3, SOFT TEMPER, ZINC-COATED STEEL.

c. ROD HANGERS: 3/16" MINIMUM DIAMETER, CADMIUM-PLATED, THREADED STEEL ROD.

d. HOOK HANGERS: INTEGRATED ASSEMBLY MATCHED TO LUMINAIRE.

e. JUNCTION BOX CANOPY COVERS SHALL MATCH COLOR OF THE CEILING THEY ARE ATTACHED TO.

f. CONCRETE BASES SHALL BE PROVIDED FOR ALL POLE MOUNTED LUMINAIRES. CONDUIT(S) SHALL BE CAST INTO BASE.

F. INTEGRAL EMERGENCY BATTERY PACKS

a. WHERE SPECIFIED, BATTERY PACKS SHALL PROVIDE MINIMUM 90 MINUTES OF LIGHT AT RATED OUTPUT OF BATTERY PACK.

PART 3 - EXECUTION

1. INSTALLATION

A. LUMINAIRES SHALL BE INSTALLED LEVEL, PLUMB, AND SQUARE WITH CEILINGS AND WALLS UNLESS OTHERWISE INDICATED.

B. LUMINAIRE SUPPORTS SHALL BE SIZED AND RATED FOR LUMINAIRE WEIGHT WITHOUT CAUSING DEFLECTION OF CEILING OR WALL.

C. INSTALL ACCESSORIES FURNISHED WITH EACH LUMINAIRE.

D. AIM DIRECTIONAL LUMINAIRES AS INDICATED ON DRAWINGS.

2. IDENTIFICATION

A. JUNCTION BOXES SERVING BRANCH CIRCUIT WIRING FOR LUMINAIRES SHALL BE LABELED WITH ASSOCIATED PANELBOARD AND CIRCUIT

NUMBER.

SECTION 26 5119

LED LIGHTING

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL FIRE ALARM SYSTEM PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. GENERAL CHARACTERISTICS

A. FINISHED SYSTEM SHALL BE NON-CODED, UL-CERTIFIED ADDRESSABLE SYSTEM, WITH MULTIPLEXED SIGNAL TRANSMISSION AND VOICE AND

STROBE NOTIFICATION FOR EVACUATION. SYSTEM SHALL BE FIELD PROGRAMMABLE, MICROPROCESSOR-BASED, AND MODULAR.

B. FIRE ALARM COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED BY AN NRTL IN ACCORDANCE WITH NFPA 70 FOR USE

WITH SELECTED FIRE-ALARM SYSTEM AND MARKED FOR INTENDED LOCATION AND APPLICATION.

C. FIRE-ALARM SIGNAL INITIATION MUST BE BY ONE OF THE FOLLOWING DEVICES AND/OR SYSTEMS:

a. MANUAL PULL STATIONS

b. DETECTORS: HEAT, FLAME, SMOKE, DUCT, CARBON MONOXIDE, ETC.

c. AUTOMATIC SPRINKLER SYSTEM WATER FLOW

d. PREACTION SYSTEM

e. DRY-TYPE SYSTEM PRESSURE FLOW SWITCH

f. FIRE PUMP OR FIRE STANDPIPE SYSTEM

D. FIRE ALARM SIGNAL INITIATION MUST INITIATE THE FOLLOWING:

a. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES, INCLUDING VOICE EVACUATION NOTICES

b. IDENTIFY ALARM AND SPECIFIC INITIATING DEVICE AT FACU, CONNECTED NETWORK CONTROL PANELS, REMOTE ANNUNCIATORS, AND OFF-

PREMISES NETWORK CONTROL PANELS

c. TRANSMIT ALARM SIGNAL TO REMOTE ALARM RECEIVING STATION

d. UNLOCK ELECTRIC DOOR LOCKS IN DESIGNATED EGRESS PATHS

e. RELEASE FIRE AND SMOKE DOORS HELD OPEN BY MAGNETIC DOOR HOLDERS

f. ACTIVATE VOICE/ALARM COMMUNICATION SYSTEM

g. SWITCH HVAC EQUIPMENT CONTROLS TO FIRE-ALARM MODE

h. ACTIVE SMOKE CONTROL SYSTEM AT FIRE FIGHTERS SMOKE CONTROL STATION (WHERE APPLICABLE)

i. CLOSE SMOKE DAMPERS IN AIR DUCTS OF DESIGNATED HVAC DUCT SYSTEMS

j. RECALL ELEVATOR(S) TO PRIMARY OR ALTERNATE RECALL FLOORS

k. ACTIVATE EMERGENCY LIGHTING CONTROL

l. ACTIVATE EMERGENCY SHUTOFFS FOR GAS AND FUEL SUPPLIES, EXCEPT FOR SHUTOFFS SERVING LEGALLY REQUIRED LIFE SAFETY

SYSTEMS SUCH AS EMERGENCY GENERATORS AND FIRE PUMPS

m. RECORD EVENTS IN SYSTEM MEMORY

E. PROVIDE NETWORK COMMUNICATIONS IN ACCORDANCE WITH MANUFACTURER WRITTEN INSTRUCTIONS.

F. DEVICE GUARDS SHALL BE WELDED WIRE MESH OF SIZE AND SHAPE REQUIRED FOR PROTECTED DEVICE. PAINT COLOR SHALL MATCH

PROTECTED DEVICE.

PART 3 - EXECUTION

1. INSTALLATION

A. IF APPLICABLE, VERIFY FUNCTIONALITY OF INSTALLED COMPONENTS OF EXISTING SYSTEM PRIOR TO STARTING WORK. DOCUMENT EQUIPMENT

OR COMPONENTS NOT FUNCTIONING AS DESIGNED.

a. DO NOT INTERRUPT FIRE-ALARM SERVICE TO FACILITIES OCCUPIED BY OWNER OR OTHERS UNLESS PERMITTED WITH CONSTRUCTION

MANAGERS WRITTEN PERMISSION. NOTIFY CONSTRUCTION MANAGER NO FEWER THAN (7) DAYS IN ADVANCE OF PROPOSED INTERRUPTION

OF FIRE-ALARM SERVICE.

b. CONNECT NEW EQUIPMENT TO EXISTING CONTROL PANEL, OR MONITORING EQUIPMENT AT SUPERVISING STATION.

c. EXPAND, MODIFY, AND SUPPLEMENT EXISTING CONTROL EQUIPMENT AS NECESSARY TO EXTEND CONTROL FUNCTIONS TO NEW POINTS.

NEW COMPONENTS MUST BE CAPABLE OF MERGING WITH EXISTING CONFIGURATION WITHOUT DEGRADING PERFORMANCE OF EITHER

SYSTEM.

B. INSTALL WALL MOUNTED EQUIPMENT WITH TOPS OF CABINETS NOT MORE THAN 78" ABOVE FINISHED FLOOR.

C. INSTALL MANUAL FIRE-ALARM BOXES IN NORMAL PATH OF EGRESS WITHIN 60" OF EXIT DOORWAY. MANUAL BOXES MUST BE INSTALLED ON

BACKGROUND OF CONTRASTING COLOR. OPERABLE PART OF MANUAL BOXES MUST BE BETWEEN 42" AND 48" ABOVE FINISHED FLOOR.

D. INSTALL DETECTORS WITH SPACING AS REQUIRED BY NFPA 72. DUCT DETECTORS SHALL HAVE SAMPLING TUBES THAT EXTEND FULL WIDTH OF

DUCT.

E. EXPOSED PATHWAYS LOCATED LESS THAN 96" ABOVE FINISHED FLOOR MUST BE INSTALLED IN EMT. EXPOSED EMT MUST BE PAINTED RED.

2. IDENTIFICATION

A. INSTALL NAMEPLATE FOR EACH ELECTRICAL CONNECTION, INDICATING ELECTRICAL EQUIPMENT DESIGNATION AND CIRCUIT NUMBER FEEDING

CONNECTION.

B. INSTALL FRAMED INSTRUCTIONS IN LOCATION VISIBLE FROM FACU.

C. IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, AND TERMINALS.

SECTION 28 4621

ADDRESSABLE FIRE ALARM SYSTEMS

KINGSCOTT ASSOCIATES INC. PORTAGE, CC

JOB

SHEET

TITLE

SHEET

NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS |

Gull Lake Community Schools

/8

/2

:5

:0

A

M

A u to d e s k D o c s

/G L C

S

S in k in g F u n d /2

.1

K

G A

G

U L L L

A K

E K

E L L O

G G

E L E

M E

N T

A R

Y G

Y M

C O

O L

IN

G M

E P

.r v t

2288.77

ELECTRICAL SPECIFICATIONS

E001

N th S tr e e t

H ic ko ry

C o rn e rs

M

I

G u ll

L a k e

C o m m u n it y S c h o o ls

K E

L L

O G

G

S

IN

K

IN

G

F U

N D

ESTIMATION

ON HOLD

CONSTRUCTION DOCUMENTS

12/19/2025

01/20/2026

04/09/2026

MIF CO H E IGT AAT NS

No.

6201060604

JONATHAN

SS

SS

SS

D D

D D

D D

D D

C.3

2.1

3.2

2.4

3.3

G1

G2

KINGSCOTT ASSOCIATES INC. PORTAGE, CC

JOB

SHEET

TITLE

SHEET

NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS |

Gull Lake Community Schools

/8

/2

:5

:0

A

M

A u to d e s k D o c s

/G L C

S

S in k in g F u n d /2

.1

K

G A

G

U L L L

A K

E K

E L L O

G G

E L E

M E

N T

A R

Y G

Y M

C O

O L

IN

G M

E P

.r v t

2288.77

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN

ED110

N th S tr e e t

H ic ko ry

C o rn e rs

M

I

G u ll

L a k e

C o m m u n it y S c h o o ls

K E

L L

O G

G

S

IN

K

IN

G

F U

N D

ESTIMATION

ON HOLD

CONSTRUCTION DOCUMENTS

12/19/2025

01/20/2026

04/09/2026

1/8" = 1'-0"ED110

1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

ELECTRICAL DEMOLITION KEYED NOTES

1 DEMOLISH ALL LIGHT FIXTURES AND ASSOSIATED CONDUIT AND

WIRING.

MIF CO H E IGT AAT NS

No.

6201060604

JONATHAN

G2

G1

A

BB-64

A

BB-64

A

BB-64

A

BB-64

A

BB-64

AE

BB-64

A

BB-64

A

BB-64

AE

BB-64

A

BB-64

A

BB-64

A

BB-64

A

BB-64

A

BB-64

A

BB-64

A

BB-64

A

BB-66

A

BB-66

A

BB-66

A

BB-66

A

BB-66

A

BB-66

A

BB-66

A

BB-66

AE

BB-66

A

BB-66

A

BB-66

A

BB-66

AE

BB-66

A

BB-66

A

BB-66

A

BB-66

A

BB-66

X1 X1

X1X1

KINGSCOTT ASSOCIATES INC. PORTAGE, CC

JOB

SHEET

TITLE

SHEET

NO.

ISSUANCE DATE

N

P L

E A

S E

R E

C Y

C L

E

T H

E S

E D

R A

W

IN

G S

A N

D T

H E

W O

R K

R E

P R

E S

E N

T E

D T

H E

R E

IN

A

R E

T H

E P

R O

P E

R T

Y O

F A

P

Y R

IG

H

T

K

IN

G

S C

O T

T A

S S

O C

IA

T

D

M A

Y N

O T

B E

U S

E D

O R

R E

P R

O D

U C

H

O U

T P

E R

M

IS

S

IO

N

L A

S T

P R

IN

T

E D ljh

PORTAGE | CHELSEA | GRAND RAPIDS |

Gull Lake Community Schools

/8

/2

:5

:0

A

M

A u to d e s k D o c s

/G L C

S

S in k in g F u n d /2

.1

K

G A

G

U L L L

A K

E K

E L L O

G G

E L E

M E

N T

A R

Y G

Y M

C O

O L

IN

G M

E P

.r v t

2288.77

FIRST FLOOR LIGHTING PLAN

E210

N th S tr e e t

H ic ko ry

C o rn e rs

M

I

G u ll

L a k e

C o m m u n it y S c h o o ls

K E

L L

O G

G

S

IN

K

IN

G

F U

N D

ESTIMATION

ON HOLD

CONSTRUCTION DOCUMENTS

12/19/2025

01/20/2026

04/09/2026

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION MOUNTING DRIVER LOAD MANUFACTURER NOTES

A HIGH BAY SURFACE 0-10V 38 VA LITHONIA: #IBE-L24-15000LM-ATC-MD-MVOLT-GZ10-40K-80CRI-DWH

AE HIGH BAY SURFACE 0-10V 39 VA LITHONIA: #IBE-L24-15000LM-ATC-MD-MVOLT-GZ10-40K-80CRI-DWH-E15WCP

X1 EXIT SIGN, RED LETTERING, 1-SIDED SURFACE 0-10V 5 VA LITHONIA: #LQC-1-R-ELN

1/8" = 1'-0"E210

1 FIRST FLOOR LIGHTING PLAN

ELECTRICAL LIGHTING KEYED NOTES

1 <ELECTRICAL LIGHTING KEYED NOTE>

2 <ELECTRICAL LIGHTING KEYED NOTE>

3 <ELECTRICAL LIGHTING KEYED NOTE>

EXISTING PANEL

Notes:

Demand Current: 163 A

Demand Load: 59 kVA

Connected Current: 162 A

Connected Load: 58 kVA

LIGHTING - INTERIOR 1251 VA 125.00% 1564 VA

Load Classification Connected Factor Demand

Current: 162 A 172 A 155 A

Connecte... 19 kVA 21 kVA 19 kVA

83 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 84

81 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 82

79 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 80

77 SPARE 20 1 -- -- 0 500 -- -- 1 20 EXERIOR WAL LTS 78

75 SPARE 20 1 -- -- 0 500 -- -- 1 20 GYM 1131 CAN LTS 76

73 SPARE 20 1 -- -- 0 500 -- -- 1 20 GYM 1114 EMERGENCY LTS 74

71 SPARE 20 1 -- -- 0 1000 -- -- 1 20 LCP1 CONTROL 72

69 CU/FC RM 1137 20 1 -- -- 1000 70

67 CU/FC RM 1137 20 1 -- -- 1000 68

65 CU/FC RM 1139 20 1 -- -- 1000 644 1 20 LIGHTING - INTERIOR 66

63 CU/FC RM 1139 20 1 -- -- 1000 607 1 20 LIGHTING - INTERIOR 64

61 CU/FC RM 1135 20 1 -- -- 1000 0 -- -- 1 20 SPARE 62

59 CU/FC RM 1135 20 1 -- -- 1000 0 -- -- 1 20 SPARE 60

57 CU/FC RM 1132 20 1 -- -- 1000 0 -- -- 1 20 SPARE 58

55 CU/FC RM 1132 20 1 -- -- 1000 0 -- -- 1 20 SPARE 56

53 SPARE 20 1 -- -- 0 500 -- -- 1 20 FLAG POLE LTS 54

51 SPARE 20 1 -- -- 0 0 -- -- 1 20 SITE POLE LTS 52

49 SPARE 20 1 -- -- 0 0 -- -- 1 20 SITE POLE LTS 50

47 10000 0 -- -- 1 20 SPARE 48

45 10000 500 -- -- 1 20 GYM 1131 MH LTS 46

PANEL EA 100 3 -- --

10000 500 -- -- 1 20 GYM 1131 MH LTS 44

41 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 42

39 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 40

37 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 38

35 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 36

33 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 34

31 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 32

29 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 30

27 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 28

25 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 26

23 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 24

21 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 22

19 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 20

17 SPARE 20 1 -- -- 0 0 -- -- 1 20 SPARE 18

15 SPARE 20 1 -- -- 0 0 -- -- 1…

This is the start of the file's text. The full file is on GovTribe.