2025.06.13 SC VMS_Addendum 01.pdf
PDF 1 MB Posted
- Attached to
- Sioux City Vehicle Maintenance Shop
- Solicitation number
- C385X3152RFB
- Issued by
- Scott County, Iowa
About this file
Addendum 001 for Sioux City Vehicle Maintenance Shop
This is Addendum 001, issued June 13, 2025, for the Sioux City Vehicle Maintenance Shop project being constructed for the Iowa National Guard by the design firm Farnsworth Group, Inc. The addendum modifies the construction drawings and specifications for the approximately 24,805 square foot facility located at 6400 Harbor Drive, Sioux City, Iowa. Key modifications include specifications for three 26'-0" x 10'-0" hazardous material storage buildings, revision of sectional door sizes and electric motor specifications (including 22'-0"x16'-0" and 8'-0"x10'-0" doors with ControlHoist Standard 1/2 HP motors), updates to blast-resistant glazing requirements for windows per ASTM F 2248, revisions to locker room benches and accessories with specified manufacturer models including Penco hardwood benches and Robinson Steel Co. stainless steel pedestals, and modifications to 3-hour fire-rated door specifications for the hazardous materials storage buildings. The addendum also includes revisions to hollow metal frames and doors, aluminum frame entrances, toilet and office accessories, and mechanical piping details. Drawing revisions correct detail reference numbers (changing references from Detail 15/A3.2 to Detail 1/A3.2), update room layouts for locker rooms, latrine elevations, janitor rooms, and bulk storage areas, and add a new mechanical piping plan sheet (MP0.2) for underfloor radiant heating circuits. Pre-approved product substitutions include Royale Concrete for polished concrete, MuleHide PVC for roofing, Spaceguard Beast Wire Partitions for wire mesh, and Royal Lockers for plastic lockers. Bids are due July 1, 2025, at 1:00 PM local time via IMPACS online submission.
Bidders must acknowledge receipt of this addendum on the bid form, with failure to do so potentially resulting in disqualification. The addendum does not specify pricing information, set-asides, incumbents, or funding sources, as these details are contained in the primary bid solicitation documents. All specification and drawing modifications outlined in the addendum are incorporated into the contract documents and supersede previous versions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Advertisement for Bids.pdf | ||
| Sioux City VMS Pre-Bid Transcript.docx | DOCX document | |
| Construction Set_Specs_6-6-2025.pdf | ||
| 1320565-event.pdf | ||
| Construction Set_Drawings_6-6-2025.pdf | ||
| 1322462-event.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum
14225 University Avenue, Suite 110 | Waukee, IA 50263 | p 515.225.3469 | www.f-w.com
ENGINEERS | ARCHITECTS | SURVEYORS | SCIENTISTS
Addendum Number: 001
Addendum Issue Date: June 13, 2025 Owner: Iowa National Guard
Project Name: Sioux City Vehicle Maintenance Shop
A/E Project Number: 0230434.00
Owner Contract Number: C385X3152 Owner Project Number: 190137
Containing: 7 Pages; 0 Documents; 2 Drawings; 0 Specifications
This addendum amends the drawings and specifications of the above reference project and is hereby incorporated into the contract documents as part thereof. Bidders must acknowledge receipt of this Addendum in the space provided on the Bid Form. FAILURE TO DO SO MAY SUBJECT BIDDER TO DISQUALIFICATION.
General:
Item No. 1 Hazardous Material Storage Buildings:
A. Quantity of three (3) 26’-0” x 10’-0” storage buildings. Refer to specification section 13 34 25
Hazardous Material Storage Buildings and drawings C2.1, C3.3, and S3.1.
Item No. 2 Suppliers shall provide Substitution Request Forms completed in their entirety. The General Contractor shall be responsible for any unchecked certifications.
Specifications:
Section 00 01 10 – Table of Contents Item No. 3 Remove specification section 07 42 13 Insulated Core Metal Wall Panels.
Item No. 4 Add Division 33 – Utilities
Section 08 12 13 – Hollow Metal Frames
Item No. 5 Revise section: 1.4.A.1 Provide at Exterior Entrance Doors to read as follows:
Building Category: Primary Gathering Level of Protection: Low Stand-Off Distance:
All Plan East Facing Doors: No Doors on Plan East 0 feet x Charge Weight II 0 feet x Charge Weight I All Plan South Facing Doors:
627 feet x Charge Weight II (Fencing 226 feet x Charge Weight I (Parking) All Plan West Facing Doors:
670 feet x Charge Weight II (Fencing 303 feet x Charge Weight I (Parking) All Plan North Facing Doors:
Farnsworth Group, Inc.
114 feet x Charge Weight II (Fencing) 78 feet x Charge Weight I (Parking)
Section 08 13 13 – Hollow Metal Doors Item No. 6 Revise section: 1.6.A.1 Provide at Exterior Entrance Doors to read as follows:
Building Category: Primary Gathering Level of Protection: Low Stand-Off Distance:
All Plan East Facing Doors: No Doors on Plan East 0 feet x Charge Weight II 0 feet x Charge Weight I All Plan South Facing Doors:
627 feet x Charge Weight II (Fencing 226 feet x Charge Weight I (Parking) All Plan West Facing Doors:
670 feet x Charge Weight II (Fencing 303 feet x Charge Weight I (Parking) All Plan North Facing Doors:
Section 08 36 13 – Sectional Doors Item No. 7 Revise 2.2.A. to read as follows: Provide 22’-0”x16’-0” doors designed for electric motor and hand chain operation.
Item No. 8 Add 2.2.B. to read as follows:
B. Provide 8’-0”x10’-0” doors designed for electric motor and hand chain operation.
1. Provide with floor operated disconnect for use with chain hoist and electric operator combination.
Electric operator, Jackshaft type, Model: ControlHoist Standard 1/2 HP, mounted at exterior wall.
a. Motor: continuous duty capacitor start NEMA Type 1 faced flanged motor; 120V single phase.
Motor shall be separate from reduction mechanism for ease of maintenance.
b. Reduction: worm gear drive running in oil with additional reduction by chain and sprockets.
c. Roller Chain Drive: Door shaft shall be driven by roller chain to provide door travel of 6" to 12" per second.
d. Starter-Reversing Contactor Type: standard duty across the line reversing type with mechanical interlock. Automatic reversing controls are not to be used.
e. Adjustable Friction Clutch: shall be provided to protect door and operator if door movement is obstructed.
f. Limit Switches: positive chain drive screw type limit switch, enclosed in electrical control box, accessible for precision setting. Limit switches will remain in time when emergency chain hoist is used and door is operated manually.
g. Control Wiring: Control voltage shall be 24 volts. Control wiring shall be RC: Three button momentary contact on OPEN and STOP, constant pressure on CLOSE.
h. Overload Protection: provide manual reset for overload protection.
i. Electrical Enclosure: all electrical components shall be in NEMA Type 1 enclosure.
j. Emergency Operation: supply a chain hoist, which may be engaged from the floor for mechanical operation. An electrical interlock disconnects power when chain hoist is engaged.
k. Magnetic Brake: furnish magnetic solenoid brake for positive stop.
Section 08 41 13 Aluminum Frames Entrances & Storefront
Item No. 9 Revise 1.2.D.2. to read as follows:
Provide glazed window capable of resisting loads of an “Equivalent 3-second Duration Design Loading” per ASTM F 2248 for blast resistant glazing fabricated with laminated glazing. Uniform load acting on the window frame shall be 2.0 times the Equivalent 3-second Duration Design Loading.
Building Category: Primary Gathering Level of Protection: Low Stand-Off Distance:
All Plan East Facing Doors: No Doors on Plan East 0 feet x Charge Weight II 0 feet x Charge Weight I All Plan South Facing Doors:
627 feet x Charge Weight II (Fencing 226 feet x Charge Weight I (Parking) All Plan West Facing Doors:
670 feet x Charge Weight II (Fencing 303 feet x Charge Weight I (Parking) All Plan North Facing Doors:
Section 10 28 00 – Toilet, Bath, & Office Accessories Item No. 10 Revise section: 2.1-B.13 Locker Benches to read as follows:
Locker Benches: hardwood bench top, clear lacquer finish as manufactured by Penco;
www.pencoproducts.com or approved equal. Pedestals: heavy duty, 304 stainless steel pedestals, Model #RSCSSP304 as manufactured by Robinson Steel Co.; www.rsclockers.com/.
a. 20” x 42”, ADA
1) Restroom 104 – 1 total
2) Restroom 106 – 1 total
b. 9-1/2” x 24”,
1) Restroom 104 – 2 total
2) Restroom 106 – 2 total
c. Anchor benches to concrete with stainless steel sidewalk bolts or button head socket screws in expansion anchors.
Section 13 34 25 – Hazardous Materials Storage Building
Item No. 11 Revise section: 2.2-C.6 to read as follows.
6. Door, Single:
a. UL Classified and labeled, 3-hour fire-rated swinging type door (48”W x 80”H) located on front of building, centered on short side. UL Listed and labeled door frame and hardware: panic exit rim device on active leaf, self-closer, and an exterior keyed security lock. Door hold open device on active leaf; fuse-linked for automatic closure.
b. Provide one door per building.
c. Provide rain shield or overhang over door opening for rain deflection.
http://www.rsclockers.com/
Drawings:
Architectural
Sheets A1.2 – Floor Plan Area A Item No. 12 Revise note “BOLLARD – SEE DETAIL 15/A3.2” to “BOLLARD – SEE DETAIL 1/A3.2”.
Item No. 13 Add leader to “Metal Wall Shelving” note in room 110 Battery.
Sheet A1.3 – Floor Plan Area B Item No. 14 Revise note “Vinyl Number – See Detail 15/A3.2 – Coordinate placement with O.H. Door Controls
(Typical)” to read as follows “Vinyl Number – See Detail 1/A3.2 – Coordinate placement with O.H. Door Controls (Typical)” Sheets A3.1 – Overall Exterior Elevations
Item No. 15 Revise note “BOLLARD – SEE DETAIL 15/A3.2” to “BOLLARD – SEE DETAIL 1/A3.2”.
Sheet A4.1 – Building Sections
Item No. 16 Revise note “Vinyl Number – See Detail 15/A3.2 – Coordinate placement with O.H. Door Controls (Typical)” to read as follows “Vinyl Number – See Detail 1/A3.2 – Coordinate placement with O.H. Door Controls (Typical)” Sheets A7.2 – Door Schedule, Room Finish Schedule, Glazing & Door Elevations
Item No. 17 Revise all HM Door and Frame Finish to “P” in lieu of “PF”.
Sheets A8.1 – Interior Elevations and Enlarged Plans (Revised Drawing Sheet Attached)
Item No. 18 Revise Detail 1- 104 Men’s and 106 Women’s Locker rooms – Enlarged Floor Plan as indicated on attached drawing.
Item No. 19 Revise Detail 2 – 106 – Women’s Latrines North Elevation as indicated on attached drawing.
Item No. 20 Revise Detail 6 – RM 104 – Men’s Latrines South Elevation as indicated on attached drawing.
Sheets A8.3 – Interior Elevations Item No. 21 Rename detail 4 “Elevation 4-a” to “Corridor 101B – Drinking Fountain”
Mechanical Piping
Sheet MP0.2 – Underfloor Mechanical Piping Plan – Area B (Drawing Sheet Attached) Item No. 22 Add sheet in its entirety.
Product Pre-Approvals:
Item No. 23 The following manufacturers shall be substituted as equal to the named Base Bid manufacturer(s) specified. Approval is contingent upon manufacturers fulfilling all specification requirements, tangible and intangible, set forth in the Drawings and Project Manual. Mechanical and Electrical Contractors shall verify that pre-approved vendors meet specifications and installation requirements based upon the project’s available space. This approval does not waive any requirements or conditions of the Contract Documents for any material, system or manufacturer.
Section Item Approved Equal 03 35 43 Polished Concrete Royale Concrete (Approved Applicator) 07 54 19.11 Fully Adhered Polyvinyl Chloride Roofing MuleHide PVC FRS 10 22 13 Wire Mesh Partitions Spaceguard Beast Wire Partitions 10 51 26 Plastic Lockers Royal Lockers
Bids are Due: July 1, 2025 / 1:00 PM local time, bids due online only via IMPACS.
END OF ADDENDUM 01
Issued By:
FARNSWORTH GROUP, INC.
Kara N. Garside, Associate AIA Architectural Associate II
Attachments:
Documents: None
Drawings Dated 06/13/2025:
Sheet A8.1 Sheet MP0.2
Specifications: None
A. SEE G0.1 FOR STANDARD MOUNTING HEIGHTS.
B. CONTROL JOINTS SHOWN ARE DESIGNATED FOR AESTHETIC PURPOSES. WHERE
CONTROL JOINTS ARE NOT SHOWN, COMPLY WITH REQUIREMENTS AS DICTATED
IN THE PARTITION GENERAL NOTES.
INTERIOR ELEVATION GENERAL NOTES
T18 T18
T7T7
T13T14
T20T20
W A
L L
T
IL
E
T
Y P
2'-8"2'-8"2'-2"
T7
A9.1
_____ GYP. BD. BULKHEAD
- SEE REFLECTED CEILING
PLAN - TYPICAL
T5T5
T16
T16
W A
L L
T
IL
E
T
Y P
12x24 CERAMIC TILE TYPICAL
T6T6
WOOD LOCKER BENCH -
SEE SPECS
T8
T8
T4T4
T3 T2
T1
W A
L L
T
IL
E
T
Y P
T16
12x24 CERAMIC TILE TYPICAL
ADA BENCH
PROVIDE LOCKER w/ ADA
COMPLIANT FEATURERS
T18
3'-0" 3'-0" 2'-7 1/2"
W A
L L
T
IL
E
T
Y P
3'-0" 4'-2" T10
T4
T4
T2
T3
T1
ADA BENCH
W A
L L
T
IL
E
T
Y P
T16
DOUBLE TIER SOLID
PLASTIC LOCKERS w/
SLOPED TOP - SEE SPEC.
- NORTH WALL
PROVIDE LOCKER w/ ADA
COMPLIANT FEATURERS
T7 T7
T18T18
T14
T13
W A
L L
T
IL
E
T
Y P
12x24 CERAMIC TILE TYPICAL
T7
T6T6
2'-2"2'-8"2'-8"
A9.1
GYP. BD. BULKHEAD
- SEE REFLECTED
CEILING PLAN - TYPICAL
T5 T5
T16 T16
WOOD LOCKER BENCH -
SEE SPECS
SLOPE FLOOR 1/4" PER
- FOOT DOWN FROM EACH
SIDE TO DRAIN
CERAMIC WALL TILE
- FIELD COLOR
3'-4"
0.25
S T
A L L S
/2
S
T A
N D
A R
D
PROVIDE ACCENT TILE COLOR
AT FLOOR TRANSITION
12x24 CERAMIC
TILE TYPICAL
PROVIDE T-SHAPED
WATER STOP @ ADA
STALLS - SEE SPEC.
ADA STALLS: FLOOR
TRANSITION SHALL BE
A MAX DEPTH OF 1/2"
WASH FOUNTAIN
- SEE PLUMBING DWGS.
T5T5
4" RUBBER BASE - TYPICAL
CMU - PAINT
GYPSUM WALL BOARD - PAINT
DRINKING FOUNTAIN w/
BOTTLE FILLER
- SEE PLUMBING DWGS.
EYE-WASH STATION
- SEE PLUMBING DWGS.
T22
7'-4"8'-0"1'-5"
A8.1
A8.1
MENS
WOMENS
9'-2 3/8" 9'-0" 5'-4" 8'-8" 6'-0" 9'-0" 9'-4"
1'-10" 6" 3'-4" 3'-0" 1'-6" 3'-4" 1'-2"
3'-8" 5'-8" 22'-10" 15'-0" 5'-8" 3'-8"
2'-0" 1'-10" 6'-10" 6'-0" 1'-4"
P6
P6
P7
P7
T8 T8
T4T4
T18 T18
T7 T7 T14
T18T18
T7T7
3'-2 1/2" 5'-0"3'-2 1/2"
/2
T13T13
T14
T4 T4
T3 T3
T20 T20
P6
P2
T2
T1
T2
T1
5'-0"
2'-2" 2'-8" 2'-8" 2'-8" 2'-8" 2'-2"
T7
56'-6 3/8"
A5.5
1'-4" 6'-0"
A5.5
P C
C T
P C
C T
DISPLAY CASE
FEC
LOCKER ROOM
BENCH - TYPICAL
T7
P2
P2
P2
P2
P2
P7
25'-4 3/8" 12'-10" 18'-4"
P2
P7
T5 T6 T6 T5 T5
T6 T6 T5
T10T10
P2
P6 P7
P2 P2
T16
T16
T16
T16
T16
T16
T16T16
T16T16
T17
T17
T17 T17
T15T16
T15
T15
2X2 ACCESS PANEL -
TYPICAL
1'-8"
P7
T10T10
T20 T20
T15
T15
S.S. CG TYP.
1'-8"
WOOD LOCKER BENCH -
SEE SPECS
WOOD LOCKER BENCH -
SEE SPECS
DOUBLE TIER SOLID
PLASTIC LOCKERS w/
SLOPED TOP - SEE SPEC.
- NORTH WALL
2'-3 1/2"
PROVIDE LOCKER w/ ADA
COMPLIANT FEATURERS
SOLID PLASTIC LOCKERS
w/ SLOPED TOP - SEE
SPEC.
PROVIDE LOCKER w/ ADA
COMPLIANT FEATURERS
SOLID PLASTIC LOCKERS
w/ SLOPED TOP - SEE
SPEC.
F F
E E
115-2
115-1
33'-6"
2'-8" 8'-0" 22'-10"
P3
P3
T Y
P
3'-10"
FEB
10'-8" 4'-0"
DN DN
DN
FF - ( -4" )
CONCRETE RAMP
CONCRETE RAMP
P6
GALV. STEEL PIPE BOLLARDS
w/ POLYETHYLENE COVER
- SEE DETAIL TYPICAL
CONCEP
55 GAL
GFGI
250 GAL
15/40
CFCI
280 GAL
ATF
GFGI
250 GAL
10WT
GFGI
17 GAL
GAA
CFGI
FF - ( 0" )
A5.2
_____ 2
A5.3
SIM.
BULK POL
A5.2
4'-0"
"6
STAINLESS STEEL AT
4'-0" FROM FF (2 SIDES)
T21
4" RUBBER BASE -
TYPICAL
MOP SINK
- SEE PLUMBING
DWGS.
JANITOR
A8.1
2'-0"
4" RUBBER BASE -
TYPICAL
STAINLESS STEEL
WALL SHELVES
A8.4
WALL BRACKETS
CMU - PAINT
10" INSULATED
PRECAST WALL
PANEL (TYPICAL)
11'-0"
COORDINATE
SHELVES WITH MEP
DUCT PLACEMENT
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
IAARNG PROJECT #:
CONTRACT #:
/1
/2
:2 :3
P
M A8.1
INTERIOR
ELEVATIONS AND
ENLARGED PLANS
KNG/SH
0230434.00
SIOUX CITY VEHICLE
MAINTENANCE SHOP
IOWA NATIONAL GUARD
6400 HARBOR DR.
SIOUX CITY, IA 51111
06/6/2025
06/6/2025
100% CONSTRUCTION SET
LS
190137
C385X3152
SCALE: 1/4" = 1'-0"
106 - WOMENS LATRINES SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
106 - WOMENS LATRINES NORTH ELEVATION
SCALE: 1/4" = 1'-0"
RM 104 - MENS LATRINES WEST ELEVATION
SCALE: 1/4" = 1'-0"
RM 104 - MENS LATRINES SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
RM 104 - MENS LATRINES NORTH ELEVATION
SCALE: 1/4" = 1'-0"
104 MENS AND 106 WOMENS LOCKER ROOMS - ENLARGED FLOOR PLAN
TOILET ACCESSORY SCHEDULE
MARK DESCRIPTION REMARKS
T1 GRAB BAR (42")
T2 GRAB BAR (36")
T3 GRAB BAR (18")
T4 TOILET TISSUE DISPENSER
T5 PAPER TOWEL DISPENSER
T6 SOAP DISPENSER
T7 24" x 36" FRAMED MIRROR w/ SHELF
T8 SANITARY NAPKIN DISPOSAL
T10 24" x 60" FRAMED MIRROR
T13 ADA SHOWER BENCH
T14 SHOWER GRAB BAR
T15 18"W x 6"D SHOWER SHELF
T16 ROBE HOOK
T17 SOAP DISH
T18 ELECTRIC HAND DRYER
T20 SHOWER ROD & CURTAIN
T21 MOP HOLDER
T22 60" x 20" STAINLESS STEEL SHELF
SCALE: 1/2" = 1'-0"
TYPICAL SHOWER BASIN SECTION
SCALE: 1/4" = 1'-0"
RM 108 - SOUTH ELEVATION
SCALE: 1/4" = 1'-0"
115 BULK POL - ENLARGED FLOOR PLAN
SCALE: 1/4" = 1'-0"
RM 120 - NORTH ELEVATION
SCALE: 1/4" = 1'-0"
120 JANITOR
SCALE: 1/4" = 1'-0"
RM 110 - WEST ELEVATION
1 06/16/2025 ADD 0106/13/2025
F
E
D
C
B
A
5 6 7 8 9 10 11 12
WARM UP/ WASH BAY
WORK BAY
WORK BAY
WORK BAY
BULK POL
TOOL ROOM
PRODUCTION CONTROLLER
SUPPLY ROOM
ALCOVE
BULKY EQUIPMENT STORAGE
6" SPACING 6" SPACING 6" SPACING 6" SPACING
6" SPACING
6" SPACING 6" SPACING 6" SPACING 6" SPACING
6" SPACING
9" SPACING9" SPACING9" SPACING
9" SPACING
CIRCUIT A-1
349 FT @ 12 IN.
FLOW: 1.29 GPM
ΔT: 20° F
CIRCUIT A-2
349 FT @ 12 IN.
FLOW: 1.31 GPM
ΔT: 20° F
CIRCUIT A-3
349 FT @ 12 IN.
FLOW: 1.31 GPM
ΔT: 20° F
CIRCUIT A-4
349 FT @ 12 IN.
FLOW: 1.30 GPM
ΔT: 20° F
CIRCUIT A-5
298 FT @ 12 IN.
FLOW: 1.10 GPM
ΔT: 20° F
CIRCUIT A-6
298 FT @ 12 IN.
FLOW: 1.10 GPM
ΔT: 20° F
CIRCUIT A-7
298 FT @ 12 IN.
FLOW: 1.10 GPM
ΔT: 20° F
CIRCUIT A-8
297 FT @ 12 IN.
FLOW: 1.08 GPM
ΔT: 20° F
CIRCUIT A-9
330 FT @ 12 IN.
FLOW: 1.22 GPM
ΔT: 20° F
CIRCUIT A-10
335 FT @ 12 IN.
FLOW: 1.25 GPM
ΔT: 20° F
CIRCUIT A-11
333 FT @ 12 IN.
FLOW: 1.25 GPM
ΔT: 20° F
CIRCUIT A-12
329 FT @ 12 IN.
FLOW: 1.22 GPM
ΔT: 20° F CIRCUIT A-13
373 FT @ 12 IN.
FLOW: 1.33 GPM
ΔT: 20° F
CIRCUIT A-14
372 FT @ 12 IN.
FLOW: 1.33 GPM
ΔT: 20° F
CIRCUIT A-15
369 FT @ 12 IN.
FLOW: 1.32 GPM
ΔT: 20° F
CIRCUIT A-16
369 FT @ 12 IN.
FLOW: 1.32 GPM
ΔT: 20° F
CIRCUIT A-17
380 FT @ 12 IN.
FLOW: 1.33 GPM
ΔT: 20° F
CIRCUIT A-18
379 FT @ 12 IN.
FLOW: 1.32 GPM
ΔT: 20° F
CIRCUIT A-19
383 FT @ 12 IN.
FLOW: 1.34 GPM
ΔT: 20° F
CIRCUIT A-20
374 FT @ 12 IN.
FLOW: 1.34 GPM
ΔT: 20° F
CIRCUIT A-21
356 FT @ 12 IN.
FLOW: 1.23 GPM
ΔT: 20° F
CIRCUIT A-22
357 FT @ 12 IN.
FLOW: 1.24 GPM
ΔT: 20° FCIRCUIT A-23
357 FT @ 12 IN.
FLOW: 1.23 GPM
ΔT: 20° F
CIRCUIT A-24
357 FT @ 12 IN.
FLOW: 1.23 GPM
ΔT: 20° F
CIRCUIT A-25
322 FT @ 12 IN.
FLOW: 1.11 GPM
ΔT: 20° F
CIRCUIT A-26
318 FT @ 12 IN.
FLOW: 1.10 GPM
ΔT: 20° F
CIRCUIT A-27
316 FT @ 12 IN.
FLOW: 1.09 GPM
ΔT: 20° F
CIRCUIT A-28
315 FT @ 12 IN.
FLOW: 1.09 GPM
ΔT: 20° F
CIRCUIT A-29
372 FT @ 12 IN.
FLOW: 1.28 GPM
ΔT: 20° F
CIRCUIT A-30
380 FT @ 12 IN.
FLOW: 1.32 GPM
ΔT: 20° F
CIRCUIT A-31
380 FT @ 12 IN.
FLOW: 1.32 GPM
ΔT: 20° F
CIRCUIT A-32
377 FT @ 12 IN.
FLOW: 1.30 GPM
ΔT: 20° F
T T T T
T T T T bluestone engineering
5518 NW 88th Street Johnston, IA 50131 515-727-0700 www.bluestonemep.com/ Project #:
BLUESTONE ENGINEERING, LLC RESERVES PROPRIETARY RIGHTS, INCLUDING
COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID
DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF BLUESTONE
ENGINEERING, LLC AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER
PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
BLUESTONE ENGINEERING, LLC. © 2024 BLUESTONE ENGINEERING, LLC
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
IAARNG PROJECT #:
CONTRACT #:
123-053
/6
/2
:4 :5
P
M MP0.2
UNDERFLOOR
MECHANICAL PIPING
PLAN - AREA B
CPJ
JRS
0230434.00
SIOUX CITY VEHICLE
MAINTENANCE SHOP
IOWA NATIONAL GUARD
6400 HARBOR DR.
SIOUX CITY, IA 51111
06/06/2025
06/06/2025
100% CONSTRUCTION SET
CPJ
190137
C385X3152
N
1/8" = 1'-0"
UNDERFLOOR MECHANICAL PIPING PLAN - AREA B
A B
GENERAL NOTES:
1. ALL VALVES TO BE LOCATED IN ACCESSIBLE LOCATIONS. COORDINATE WITH ARCHITECTURAL DRAWINGS.
2. REFER TO RADIATION SCHEDULE (IN-FLOOR) FOR TUBING INFORMATION.
3. RADIANT IN-FLOOR TUBING TO BE SPACED 12" ON CENTER UNLESS OTHERWISE NOTED ON PLAN.
4. RADIANT IN-FLOOR TUBING TO BE SPACED 6" ON CENTER FOR THE TWO PIPING PASSES IMMEDIATALY ADJACENT TO
THE BUILDING EXTERIOR WALLS.
5. REFER TO MP5 AND M7 SERIES DRAWINGS FOR THE FOLLOWING REFERENCED DETAILS:
A. RADIANT IN-FLOOR HEAT TUBING
B. WATER SOURCE HEAT PUMP CONTROL DIAGRAM
C. RADIANT IN-FLOOR HEATING ZONE CONTROL DIAGRAM
THIS SHEET MUST BE PRINTED IN COLOR
N
PLAN NORTH
1 06/16/2025 ADD 0106/13/2025