2025-10-31_Salix_CD-70.pdf

PDF 14 MB Posted

Attached to
Construction Manager at Risk for new Salix Scale & Inspection Building
Solicitation number
645-RFP-2336-2026
Issued by
Warren County, Iowa

About this file

This is a comprehensive set of construction design documents for the Iowa Department of Transportation's new Salix Weigh Scale and Inspection Building project located in Woodbury County, Iowa near Interstate 29 southbound. The project encompasses complete architectural, structural, mechanical, plumbing, and electrical design plans at 70% construction document completion. The scope includes demolition of existing structures and utilities, construction of a new approximately 90-foot by 25-foot building with underground pit facilities, installation of mechanical systems including HVAC with gas-fired radiant heating and propane infrastructure, plumbing systems with duplex sewage ejector and sump pumps, septic system installation, and comprehensive electrical systems including lighting, power distribution, fire alarm, and data infrastructure. The site plan indicates development of pavement, sidewalks, parking areas, and utility coordination with existing I-29 infrastructure. A mandatory pre-proposal conference is scheduled for December 17, 2025, at 1:00 PM CT via Microsoft Teams, with proposals due January 22, 2026, at 1:00 PM CST. The procurement follows a Construction Manager at Risk (CMaR) qualification-based selection process.

The Iowa DOT seeks qualified construction management firms to provide preconstruction and construction management services with evaluation based on firm history, relevant project experience, team composition, project approach, location responsiveness, and presentation capability. Respondents must submit a single percentage fee for preconstruction and construction services, though cost will not factor into proposal selection. All bidders must register with the Iowa Department of Workforce Development Division of Labor and provide contractor certification. Financial documentation including three years of audited financials or equivalent, Dun & Bradstreet reports, and a minimum of three financial references are required. The Iowa DOT operates on 0% 0, Net 60 payment terms as a tax-exempt agency. The contract allows for potential renewal periods at the discretion of the DOT. Primary contact for inquiries is Teri Schulz at teri.schulz@iowadot.us or 515-239-1431.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

IG

N

L P

R T

E B

E B

U B

U B

T P

U B

U B

U B

U B

EXISTING PCC PAVING

REMOVE AND DISPOSE OF

SAWCUT FULL DEPTH,

EXISTING PCC RAMP PAVING

REMOVE AND DISPOSE OF

SAWCUT FULL DEPTH,

EXISTING PCC SIDEWALK

REMOVE AND DISPOSE OF

EXISTING PCC PARKING LOT

REMOVE AND DISPOSE OF

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE POLE AND REMOVE AND DISPOSE OF FOOTING

REMOVE AND SALVAGE EXISTING LIGHT

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

SUMP PIT AND SUMP PUMP

REMOVE AND DISPOSE OF HDPE RISER,

REMOVE 3 TREES

BE USED FOR STAGING

WITH ROAD PROJECT, CAN

PAVEMENT TO BE REMOVED

WITH ROAD PROJECT

PAVEMENT TO BE REMOVED

WITH ROAD PROJECT

PAVEMENT TO BE REMOVED

WITH ROAD PROJECT

PAVEMENT TO BE REMOVED

EXISTING CONCRETE BARRIERS

REMOVE AND DISPOSE OF

GAS LINE

PROPANE TANK AND

REMOVE AND DISPOSE OF

DISTRIBUTION BOX, AND SEPTIC TANK

REMOVE AND DISPOSE OF ABSORPTION FIELD,

COORDINATE WITH PREPASS

PREPASS HANDHOLE

REMOVE AND DISPOSE OF

PHONE LINE

WITH LONG LINES TO ABANDON

UTILITY PEDESTAL AND COORDINATE

REMOVE AND DISPOSE OF

OF RADIO TOWER

REMOVE AND DISPOSE

VENT AND ALL PIPING

REMOVE AND DISPOSE OF AIR

AIR CONDITIONER

REMOVE AND DISPOSE OF

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

ABANDON ELECTRIC LINE (TYP)

REMOVED WITH ROAD PROJECT

DRAINAGE TILE AND INTAKE TO BE

ROAD PROJECT

TO BE REMOVED WITH

DRAINAGE TILE AND INTAKE

OF EXISTING SHED

REMOVE AND DISPOSE

PROTECT EXISTING WELL

ABANDON ELECTRIC LINE (TYP)

ROAD PROJECT

TO BE REMOVED WITH

DRAINAGE TILE AND INTAKE

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

SCALE AND SCALE PIT

REMOVE AND DISPOSE OF

DRAINAGE TILE

REMOVE AND DISPOSE OF

AND DISPOSE OF FOOTING

SYSTEM POLE AND REMOVE

REMOVE AND SALVAGE PA

SIGN FACE LIGHT

SALVAGE SIGNAL AND

AND ELECTRICAL FITTINGS.

SIGN POSTS, SIGN FACE

REMOVE AND DISPOSE OF

MIDAMERICAN ENERGY.

TRANSFORMER. COORDINATE WITH

REMOVE AND DISPOSE OF EXISTING

TOWER AND FENCING

REMOVE AND DISPOSE OF RADIO

EXISTING BUILDING

REMOVE AND DISPOSE OF

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

CONCRETE TRASH RECEPTACLE

REMOVE AND DISPOSE OF

DISPOSE OF FOOTING

POLE AND REMOVE AND

EXISTING LIGHT

REMOVE AND SALVAGE

ABANDON ELECTRIC LINE (TYP)

EXISTING PCC RAMP PAVING

REMOVE AND DISPOSE OF

SAWCUT FULL DEPTH,

COORDINATE WITH PREPASS

PREPASS CONDUIT AS NEEDED

REMOVE AND DISPOSE OF

COORDINATE WITH MIDAMERICAN

PROTECT ELECTRIC SERVICE LINE

I-29 (SB)

ID

O

T

S a li x W e ig h S c a le

B u il d in g

Io w a D e p a rt m e n t o f T ra n s p o rt a ti o n

S a li x

IA

C D

B G

-9 A

(0

-8

-0

M A

M

M A

M

/3

/2 p w

\p ro je c tw is e .d o t.

in t.

la n

:P W

M a in

\D o c u m e n ts \P ro je c ts

\9

\D e s ig n \C

A D

D

F il e s \B

G -9

A

(0

-8

-0

\p la n s \C

D

-D e m o li ti o n P la n

.d g n M

M a n z e r

/2

/2

:5

:3

A

M

Io w a

I ll in o is n d ia n

N e b ra s k a

D R

A W

N

A P

P R

O V

E D

IS

S

U E

D F

O R

D A

T E

F

IE

L D

B O

O K

P R

O J E

C T

N O

C L

IE

N

T N

O

A B D E FC

A B D E FC

W e s to w n P k w y S u it e

W e s t

D e s M o in e s

IA

.2

.8 w w

.s h iv e -h a tt e ry

.c o m

Sheet

P L

A N

D E

M O

L

IT

IO

CD01

Scale In Feet

% C om ple te

N

L P

R T

E B

E B

U B

U B

U B

U B

U B

T P

U B

U B

U B

U B

U

BU

B

U B

U B

U B

SEE UTILITY PLAN FOR SEPTIC LOCATION.

AROUND PERIMETER OF NEW SEPTIC FIELD.

INSTALL TEMPORARY CONSTRUCTION FENCE

POLE AND REMOVE AND DISPOSE OF FOOTING

REMOVE AND SALVAGE EXISTING LIGHT

POLE AND REMOVE AND DISPOSE OF FOOTING

REMOVE AND SALVAGE EXISTING LIGHT

I-29 (SB)

COORDINATE WITH PREPASS

PREPASS CONDUIT AS NEEDED

REMOVE AND DISPOSE OF

ID

O

T

S a li x W e ig h S c a le

B u il d in g

Io w a D e p a rt m e n t o f T ra n s p o rt a ti o n

S a li x

IA

C D

B G

-9 A

(0

-8

-0

M A

M

M A

M

/3

/2 p w

\p ro je c tw is e .d o t.

in t.

la n

:P W

M a in

\D o c u m e n ts \P ro je c ts

\9

\D e s ig n \C

A D

D

F il e s \B

G -9

A

(0

-8

-0

\p la n s \C

D

-D e m o li ti o n P la n

.d g n M

M a n z e r

/2

/2

:0

:0

A

M

Io ll in n d ia e b ra s k a

D R

A W

N

A P

P R

O V

E D

IS

S

U E

D F

O R

D A

T E

F

IE

L D

B O

O K

P R

O J E

C T

N O

C L

IE

N

T N

O

A B D E FC

A B D E FC

W e s to w n P k w y S u it e

W e s t

D e s M o in e s

IA

.2

.8 w w

.s h iv e -h a tt e ry

.c o m

C302

CD02

P L

A N

D E

M O

L

IT

IO

Scale In Feet

% C om

L P

R T

E B

E B

U B

T P

U B

U B

STEEL PIPE BOLLARD (TYP)

31'-0"

6'-0"

E = 14106353.437

N = 8514854.038

BUILDING GRID LINE 1 AND C

FFE = 1085

FFE = 1085

FUTURE BARRIER

STEEL PIPE BOLLARD

STEEL PIPE BOLLARD

STEEL PIPE BOLLARD

STEEL PIPE BOLLARD

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF SIDEWALK

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF PAVEMENT

EXISTING EDGE OF PAVEMENT

EXISTING EDGE OF PAVEMENT

EXISTING EDGE OF SIDEWALK

EXISTING EDGE OF PAVEMENT

EXISTING EDGE OF PAVEMENT

EXISTING EDGE OF PAVEMENT

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF GRAVEL SHOULDER

FUTURE EDGE OF PAVEMENT

FUTURE EDGE OF GRAVEL SHOULDER

STRUCTURAL FOR DETAILS

PROPOSED SCALE PIT, SEE SEE STRUCTURAL FOR DETAILS

PROPOSED APPROACH SECTION

SEE STRUCTURAL FOR DETAILS

PROPOSED APPROACH SECTION

STRUCTURAL FOR DETAILS

PROPOSED SCALE DECK, SEE

BOLLARD (TYP)

FUTURE STEEL PIPE

10'-0" 10'-0"

1'-6" 90'-0" 1'-6"

20'-0"

E = 14106472.825

N = 8514880.866

E = 14106483.924

N = 8514889.400

E = 14106540.609

N = 8514815.672

E = 14106529.510

N = 8514807.138

EL = 1084.98

EL = 1084.98

FUTURE EDGE OF SIDEWALK

NOTES PRIOR TO PAVING

SEE SHEET C301 FOR CONDUIT

4" PCC PAD FOR PROPANE TANKS

E = 14106373.521

N = 8514869.479

BUILDING GRID LINE 1 AND B

E = 14106434.473

N = 8514790.202

BUILDING GRID LINE 6 AND B

E = 14106426.579

N = 8514758.905

BUILDING GRID LINE 7 AND C

E = 14106488.712

N = 8514831.903

BUILDING GRID LINE 6 AND A

E = 14106502.730

N = 8514813.669

BUILDING GRID LINE 8 AND A

ID

O

T

S a li x W e ig h S c a le

B u il d in g

Io w a D e p a rt m e n t o f T ra n s p o rt a ti o n

S a li x

IA

C D

B G

-9 A

(0

-8

-0

M A

M

M A

M

/3

/2 p w

\p ro je c tw is e .d o t.

in t.

la n :P

W M a in

\D o c u m e n ts

\P ro je c ts

\9 \D e s ig n \C

A D

D F il e s \B

G -9

A (0

-8 -0

\p la n s \C

-S it e P la n .d g n

M M a n z e r

/2

/2

:2

:2

A

M

Io ll in n d ia e b ra s k a

D R

A W

N

A P

P R

O V

E D

IS

S

U E

D F

O R

D A

T E

F

IE

L D

B O

O K

P R

O J E

C T

N O

C L

IE

N

T N

O

A B D E FC

A B D E FC

W e s to w n P k w y S u it e

W e s t

D e s M o in e s

IA

.2

.8 w w

.s h iv e -h a tt e ry

.c o m

S

IT

E P

L A

N

C101

Scale In Feet

T E

S T

% C om

L

R T

E B

E B

U B

T P

U B

U B

FFE = 1085

FFE = 1085

GRADING LIMIT (TYP.)

0.80% 0.80%

.5

.5

GRADE BREAK

GRADE BREAK

.0

.0

.0

.0

EL = 1084.98

EL = 1084.44

EL = 1084.44

EL = 1084.98

EL = 1084.44

EL = 1084.44

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.91

EL = 1084.91

EL = 1084.95

EL = 1084.91

EL = 1084.91

EL = 1084.91

EL = 1084.91

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.91

EL = 1084.91

EL = 1084.98

EL = 1084.98

EL = 1084.91

EL = 1084.91

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

EL = 1084.98

0.00% CROSS AND LONGITUDINAL

SLOPE ON DECK AND TOP OF PIT

ELEVATION = 1084.52

EL = 1084.31

EL = 1083.83

EL = 1083.71

EL = 1084.06

E =

N =

BUILDING GRID LINE 6 AND B

.0

1084.52 EL =

SCALE

1084.52 EL =

SCALE

1084.52 EL =

SCALE

1084.52 EL =

SCALE

GRADING LIMIT (TYP.)

GRADING LIMIT (TYP.)

GRADE BREAK

GRADE BREAK

G R

A D

E B

R E

A K

5.00%

5.00%

5.00%

2.00%

2.00%

2.00%

2.00%

.0

405.04

EL = 1082.65

EL = 1083.57

EL = 1084.48

EL = 1084.48

EL = 1084.48

EL = 1083.59

EL = 1082.70

:1

.0

.0

.0

.0

1084 (FUTURE)

1083 (FUTURE)

1084 (FUTURE)

1084 (FUTURE)

1084 (F

UTURE)

1083 (F

UTURE)

1082 (FUTURE)

1084 (FUTURE)

F

U T

U R

E

1.50%

1.50%

EL = 1084.48

EL = 1084.48

EL = 1084.48

10'-0"

10'-0"

GRADE BREAK GRADE BREAK

ID

O

T

S a li x W e ig h S c a le

B u il d in g

Io w a D e p a rt m e n t o f T ra n s p o rt a ti o n

S a li x

IA

C D

B G

-9 A

(0

-8

-0

M A

M

M A

M

/3

/2 p w

\p ro je c tw is e .d o t.

in t.

la n

:P W

M a in

\D o c u m e n ts \P ro je c ts

\9

\D e s ig n \C

A D

D

F il e s \B

G -9

A

(0

-8

-0

\p la n s \C

-G ra d in g

P la n M

M a n z e r

/2

/2

:0

:1

P

M

Io ll in n d ia e b ra s k a

D R

A W

N

A P

P R

O V

E D

IS

S

U E

D F

O R

D A

T E

F

IE

L D

B O

O K

P R

O J E

C T

N O

C L

IE

N

T N

O

A B D E FC

A B D E FC

W e s to w n P k w y S u it e

W e s t

D e s M o in e s

IA

.2

.8 w w

.s h iv e -h a tt e ry

.c o m

G R

A D

IN

G

P L

A N

C201

Scale In Feet

T E

S T

% C om

N

L P

R T

E B

E B

U B

U B

U B

T P

U B

U B

U B

U B

FFE = 1085

GRADING LIMIT (TYP.)

2.00%

:1

1083 (FUTURE)

1084 (FUTURE)

(F

UTURE)

1082 (FUTURE)

1081 (FUTURE)

1080 (FUTURE)

81 10

F U

T U

R E

F U

T U

R E

F U

T U

R E

1084 (FUTURE)

1083 (FUTURE)

1082 (FUTURE)

(FUTURE)

1083 (F

UTURE)

(FUTURE)

(F

UTURE)

(F

UTURE)

(F

UTURE)

(F

UTURE)

0 (F

UTURE)

(FUTURE)

1082 (FUTURE)

(FUTURE)

(FUTURE)

:1

:1

:1 4 :1

1.40% 1.40%

1.40%

1.0 0%

EL = 1078.93

EL = 1078.93

GRADING LIMIT (TYP.)

GRADING LIMIT (TYP.)

GRADING LIMIT (TYP.)

I-29 (SB)

ID

O

T

S a li x W e ig h S c a le

B u il d in g

Io w a D e p a rt m e n t o f T ra n s p o rt a ti o n

S a li x

IA

C D

B G

-9 A

(0

-8

-0

M A

M

M A

M

/3

/2 p w

\p ro je c tw is e .d o t.

in t.

la n

:P W

M a in

\D o c u m e n ts \P ro je c ts

\9

\D e s ig n \C

A D

D

F il e s \B

G -9

A

(0

-8

-0

\p la n s \C

-G ra d in g

P la n M

M a n z e r

/2

/2

:4

:0

P

M

Io ll in n d ia e b ra s k a

D R

A W

N

A P

P R

O V

E D

IS

S

U E

D F

O R

D A

T E

F

IE

L D

B O

O K

P R

O J E

C T

N O

C L

IE

N

T N

O

A B D E FC

A B D E FC

W e s to w n P k w y S u it e

W e s t

D e s M o in e s

IA

.2

.8 w w

.s h iv e -h a tt e ry

.c o m

C202

G R

A D

IN

G

P L

A N

Scale In Feet

% C om

HH

HH

T

HH

HHHH

HH

S

IG

N

L P

R T

E B

E B

U B

U B

U B

T P

U B

U B

U B

U B

SEE MECHANICAL PLANS

IE = 1081.00'

SUMP PUMP DRAIN CONNECTION

IE = 1082.16'

SEE MECHANICAL PLANS (TYP)

6" PVC ROOF DRAIN CONNECTION

8" PVC STORM DRAIN @ 0.90%

6" PVC STORM DRAIN @ 0.90%

CONNECT TO EXISTING WELL

87.8 LF PVC WATER LINE

SEE SHEET C501

10.0 LF 4" PVC SANITARY FORCE MAIN @ 2.00%

SANITARY @ 1.10%

25.1 LF 4" PVC

SEE SHEET C501

SEPTIC TANK, IE(IN) = 1080.42', IE(OUT) = 1080.17'

GAS LINE

SEE MECHANICAL PLANS

SANITARY CONNECTION, IE = 1080.22'

SEE SHEET C501

IE (IN) = 1077.11'

DISTRIBUTION BOX

SEE SHEET C501

ABSORPTION FIELD

(PROVIDE 1' MIN. COVER)

184.1 LF 4" PVC SANITARY @ 1.10%

(PROVIDE 1' MIN. COVER)

IE = 1077.76'

22.5° HORIZONTAL BENDIE = 1079.79'

45° HORIZONTAL BEND

IE = 1080.07'

45° HORIZONTAL BEND

SLAB TO 2' OUTSIDE OF SLAB, TEMPORARILY CAP ENDS

CONTRACTOR TO PROVIDE 4" CONDUIT FROM CENTER OF

IE(NE) = 1079.98'

IE(SE) = 1080.08'

IE(SW) = 1080.29'

RIM = 1084.00'

SW-401 48" MANHOLE

COUNTER INDUCTIVE LOOP

FUTURE TRAFFIC

TRAFFIC COUNTER

FUTURE HANDHOLE FOR

79.3 LF 15" RCP @ 0.50%

SUMP = SEE MECH. PLANS

IE(NE) = SEE MECH. PLANS

IE(NW) = 1081.48'

RIM = 1084.79'

SW-401 48" MANHOLE

LIFT STATION

FUTURE CONDUIT

FUTURE HANDHOLE

FUTURE CONDUIT

SEE ELECTRIC PLANS

4" PVC CONDUIT TO DATA CLOSET

SEE ELECTRICAL PLANS

PG = 1083.52'

NEW TRANSFORMER

LOCATION WITH PROVIDER

FINAL TANK AND SERVICE LINE

NEW PROPANE TANKS - COORDINATE

RIM = 1084.44'

PER ITS-101

48" X 30" HANDHOLE

RIM = 1083.70'

PER ITS-101

48" X 30" HANDHOLE

SEE ELECTRIC PLANS

ELECTRIC SERVICE

IE = 1082.68'

6" PVC RDC

IE = 1081.72'

6" PVC RDC

IE = 1081.42'

6" PVC RDC

IE = 1083.20'

6" PVC RDC

IE = 1083.02'

6X6X6 WYE

CAP END OF WYE

IE = 1082.50'

6X6X6 WYE

IE = 1081.98'

8X8X6 WYE

IE = 1081.95'

45° HORIZONTAL BEND

IE = 1081.87'

45° HORIZONTAL BEND

IE = 1081.54'

8X8X6 WYE

IE = 1081.24'

8X8X6 WYE

IE = 1080.92'

10X10X8 WYE

IE = 1081.03'

45° HORIZONTAL BEND

FFE = 1085

FFE =

IE = 1079.60'

15" RCP APRON PER DR-201

FUTURE BARRIER

PG = 1079.43'

E = 14106231.995

N = 8515055.209

PG = 1079.43'

E = 14106255.955

N = 8515096.801

PG = 1078.95'

E = 14106176.539

N = 8515087.156

PG = 1078.95'

E = 14106200.329

N = 8515128.453

RIM = 1083.55'

RIM = 1083.32'

SANITARY @ 1.10%

9.5 LF 4" PVC

(PROVIDE 1' MIN. COVER)

58.9 LF 4" PVC SANITARY @ 1.10%

STORM DRAIN @ 1.00%

71.3 LF 6" PVC

STORM DRAIN @ 0.90%

92.8 LF 10" PVC

DRAIN @ 1.00%

5.5 LF 4" PVC STORM

10"X4" ECCENTRIC REDUCER (MATCH CROWNS)

(MATCH INVERTS)

8X6 ECCENTRIC REDUCER

45° HORIZONTAL BEND45° HORIZONTAL BEND

BEND

45° HORIZONTAL

45° HORIZONTAL BEND

45° HORIZONTAL BEND

SEE ELECTRIC PLANS

4" PVC CONDUIT TO DATA CLOSET

I-29 (SB)

ID

O

T

S a li x W e ig h S c a le

B u il d in g

Io w a D e p a rt m e n t o f T ra n s p o rt a ti o n

S a li x

IA

C D

B G

-9 A

(0

-8

-0

M A

M

M A

M

/3

/2 p w

\p ro je c tw is e .d o t.

in t.

la n :P

W M a in

\D o c u m e n ts

\P ro je c ts

\9 \D e s ig n \C

A D

D F il e s \B

G -9

A (0

-8 -0

\p la n s \C

-U ti li ty P la n .d g n

M M a n z e r

/2

/2

:4

:2

P

M

Io ll in n d ia e b ra s k a

D R

A W

N

A P

P R

O V

E D

IS

S

U E

D F

O R

D A

T E

F

IE

L D

B O

O K

P R

O J E

C T

N O

C L

IE

N

T N

O

A B D E FC

A B D E FC

W e s to w n P k w y S u it e

W e s t

D e s M o in e s

IA

.2

.8 w w

.s h iv e -h a tt e ry

.c o m

U T

IL

IT

Y P

L A

N

C301

Scale In Feet

% C om

RISER, HEIGHT AS REQUIRED

TO EXTEND MANWAY ABOVE

FINISH GRADE

8" COMPACTED

BASE, IOWA DOT

GRADE 12 OR 14

UNDISTURBED EARTH

MECHANICAL

LINK SEAL

MECHANICAL

LINK SEAL

INFLUENT TEE

EFFLUENT

FILTER

4" PVC INLET, 2% SLOPE

TO SEPTIC TANK

4" PVC, SLOPE TO

DISTRIBUTION BOX

BUILDING

2" FROM SEWAGE

EJECTOR PUMP, SEE

MECHANICAL DETAILS

CAP

10'

3"

FINISH GRADE

LEAK PROOF PENETRATION;

MECHANICAL LINK SEAL.

COORDINATE WITH

CONTRACTOR AND

MECHANICAL CONTRACTOR.

3"

7-HOLE FLOW DISTRIBUTION BOX SET ON 8"

COMPACTED BASE, IOWA DOT GRADE 12 OR 14

4" PVC DISTRIBUTION PIPE (TYP.)

CHAMBER - SEE DETAIL D4

4" PVC FROM SEPTIC TANK

-SEE SHEET C301

3.

64' - SEE SHEET C301 FOR ABSORPTION FIELD LAYOUT

3.

8" INVERT

(36" WIDE TRENCH)

12" COVER H-10

SEE NOTE

12"

34" WIDE CHAMBER

6' SPACING

NATIVE BACKFILL

TOPSOIL

(CHAMBER SECTION) (END CAP VIEW)

TRENCH ELEV.

=1076.90

4" pvc

INLET

NOTES:

1. GENERAL: WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CURRENT STATEWIDE URBAN DESIGN AND SPECIFICATIONS (SUDAS), PROJECT SPECIFICATIONS, THE RECOMMENDED STANDARDS FOR SANITARY WORKS (COMMONLY KNOWN AS "THE TEN STATE STANDARDS"), THE IOWA

WASTEWATER FACILITIES DESIGN STANDARDS, AND IOWA CODE CHAPTER 69.

2. SEPTIC TANK: 1,500 GALLON (+/- 250 GAL), 2 COMPARTMENT PRECAST CONCRETE TANK MEETING REQUIREMENTS OF IOWA CODE CHAPTER 69.

3. LIFT STATION PRESSURE PIPING, FORCE MAIN, AND ABSORPTION FIELD MANIFOLDS AND LATERALS: SCHEDULE 40 PVC PIPE AND FITTINGS; WORKING PRESSURE RATING OF 280 PSI; MANUFACTURED FROM VIRGIN RIGID PVC COMPOUNDS WITH A CELL CLASS OF 12454 AS IDENTIFIED IN ASTM D 1784;

IPS CONFORMING TO ASTM D 1785; INJECTION MOLDED PVC SCHEDULE 40 FITTINGS SHALL CONFORM TO ASTM D 2466; RESTRAINED, CEMENT WELDED

JOINTS.

4. TRENCHING, BEDDING, AND BACKFILL: MEET REQUIREMENTS OF SUDAS SECTION 3010 - TRENCH EXCAVATION AND BACKFILL, INCLUDING DETAILS 3010.10, 3010.103, 3010.104. PROVIDE CLASS F-3 BEDDING FOR GRAVITY SANITARY SEWER PIPE AND CLASS P-3 FOR FORCE MAIN.

5. CLEANING, INSPECTION, AND TESTING OF SEWERS: PROVIDE FOR SANITARY SEWERS ACCORDANCE WITH SUDAS SECTION 4060 - CLEANING, INSPECTION, AND TESTING OF SEWERS.

6. CHAMBERS: CHAMBERS ARE TO BE INFILTRATOR QUICK4 STANDARD OR APPROVED EQUIVALENT. INSTALL CHAMBERS ACCORDING TO MANUFACTURER INSTRUCTIONS. TRENCHES AND CHAMBERS TO BE ON 9 FT CENTERS. CHAMBER BOTTOMS AND INLET INVERTS TO BE INSTALLED LEVEL. INSTALL ONE INSPECTION PORT PER CHAMBER LINE PER MANUFACTURER INSTRUCTIONS.

7. EFFLUENT FILTER: PROVIDE AND INSTALL EFFLUENT FILTER, NSF/ANSI APPROVED, BUILT GAS DEFLECTOR, SHUT-OFF BALL WHEN FILTER IS REMOVED, RATED FLOW OF 3,000 GPD, POLYLOK PL1-22.

8. DISTRIBUTION BOX: TUF-TITE 7-HOLE DISTRIBUTION BOX, OR EQUAL, PROVIDE AND INSTALL TUF-TITE SPEED LEVELERS FOR EACH DISTRIBUTION LINE

9. MODULAR MECHANICAL SEALS: PRESSURE RESISTANT TO 20 PSIG (40 FT. OF HEAD): EPDM RUBBER: SST BOLTS AND NUTS; LINK SEAL, OR EQUAL.

A1 SEPTIC TANK PLAN VIEW

A3 SEPTIC TANK SECTION VIEW

D3 SUBSURFACE CHAMBER AND DISTRIBUTION SYSTEM

D4 CHAMBER TYPICAL SECTION

NOTE:12" COVER MINIMUM. COVER CAN BE INCREASED TO A MAXIMUM OF 24" TO

FIT FINISHED GRADE ACROSS ABSORPTION FIELD IF NEEDED. HOWEVER,COVER

DEPTH (ABOVE 12") SHALL BE MINIMIZED TO THE GREATEST EXTENT POSSIBLE.

0.

8.

S

H

IV

E- H

AT

TE

R Y.

C O

M

A

B C D E F

A B C D E F

D R

AW

N

B Y

AP

PR

O

VE

D B

Y

IS

SU

ED

F

O R

IS

SU

E D

AT

E

C

LI

EN

T

PR

O

JE

C

T N

U M

BE

R

PR

O

JE

C

T N

U M

BE

R

Pr in te d: C501

C O

N

ST

R U

C

TI

O N

D

ET

AI

LS

M

AA

SD

O

C D

/3

1/

BG

-9

A0 0(

2)

--8 0-

Io w a

D ep ar tm en t o f T ra ns po rta tio n

ID

O

T

- S al ix

W ei gh S ca le

B ui ld in g

Sa lix

, I A

P:

\P ro je ct s\

\2

0\

De liv er ab le s\

Dr aw in gs

\1 _C ivi l\C

SE

PT

IC

S

YS

TE

M D

ET

AI

LS

.d wg

/2 7/

1:

:1

AM

% C om

ABBREVIATIONS

A

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

ALT ALTERNATE

APPROX APPROXIMATE (LY)

ARCH ARCHITECT (URAL)

B

B/ BOTTOM OF

BLDG BUILDING

BM BEAM

BOT BOTTOM

BP BASE PLATE

BRG BEARING

BSMT BASEMENT

BF BEAM FLANGE WIDTH

C

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CIP CAST-IN PLACE

CJ CONSTRUCTION/CONTROL JOINT

CL CENTER LINE

CLR CLEAR (ANCE)

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONN CONNECT (ION) (ED) (OR)

CONT CONTINUOUS

COORD COORDINATE

D

D DEPTH

DBE DECK BEARING ELEVATION

DBL DOUBLE

DEG DEGREE

DIM DIMENSION

DN DOWN

DTL DETAIL

DWG DRAWING

E E or EXST EXISTING

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

ELEC ELECTRIC / ELECTRICAL

ELEV or EL ELEVATION

EMBED EMBEDDED

EOR ENGINEER OR RECORD

EQ EQUAL

EQUIP EQUIPMENT

EW EACH WAY

F

F ISOLATED FOOTING

F'C CONCRETE COMPRESSIVE

STRENGTH

F/ FACE OF

FDN FOUNDATION

FFE FINISH (ED) FLOOR ELEVATION

FLR FLOOR (ING)

FRP FIBER REINFORCED POLYMER

FTG FOOTING

FV FIELD VERIFY

FY YIELD STRENGTH

G GA GAGE or GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

G or GL GRID LINE

H

HGR HANGER

HK HOOK

HORIZ HORIZONTAL

HWS HEADED WELDED STUDS

J

JBE JOIST BEARING ELEVATION

JST JOIST (S)

K

KO KNOCK-OUT

L L or LNTL LINTEL

LF LINEAR FOOT

LLBB LONG LEG BACK TO BACK

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LONG LONGITUDE (INAL)

LSL LONG SLOTTED (HOLES)

M

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEP MECHANICAL, ELECTRICAL,

PLUMBING

MEZZ MEZZANINE

MFR MANUFACTURER

MID MIDDLE

MIN MINIMUM

MISC MISCELLANEOUS

MTL METAL

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

O

O/O OUT TO OUT

OC ON CENTER

OF OUTSIDE FACE

OFCI OWNER FURNISHED-CONTRACTOR

INSTALLED

OFOI OWNER FURNISHED-OWNER

INSTALLED

OPNG OPENING (S)

ORIG ORIGINAL

OVHD OVERHEAD

P

PAF POWDER ACTUATED FASTENER

PC PRECAST CONCRETE or PILE CAP

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PH PHASE

PL PLATE

PREFAB PREFABRICATED

PRELIM PRELIMINARY

PVC POLYVINYL CHLORIDE

Q

QTY QUANTITY

R

R RADIUS

RD ROOF DRAIN

REF REFER (ENCE)

REINF REINFORCE (D) (ING) (MENT)

REQD REQUIRED

RF RETAINING FOUNDATION

RO ROUGH OPENING

RTU ROOF TOP UNIT

S

SC SLIP CRITICAL

SCH or SCHED SCHEDULE

SECT SECTION

SEOR STRUCTURAL ENGINEER OF RECORD

SIM SIMILAR

SJ SAW CUT JOINT or SLIP JOINT

SLBB SHORT LEG BACK TO BACK

SLOS SHORT LEG OUTSTANDING

SLP SLOPE

SOG SLAB ON GRADE

SPC SPACE (ING)

SPEC SPECIFICATIONS

SS STAINLESS STEEL

SSL SHORT SLOTTED (HOLES)

STA STATION

STAG STAGGERED

STD STANDARD

STIFF STIFFENER

STL STEEL

STRUC STRUCTURE (AL)

T

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

T/ TOP OF

TC TENSION CONTROLLED BOLT

TEMP TEMPORARY

TF TRENCHED FOUNDATION

THK THICK (NESS)

TOT TOTAL

TRANS TRANSVERSE

TYP TYPICAL

U

UNO UNLESS NOTED OTHERWISE

V

VERT VERTICAL

W

W/ WITH

W/O WITHOUT

WD WIDTH or WOOD

WF WALL FOOTING

WP WORKING POINT

WWR WELDED WIRE REINFORCEMENT

WWF WELDED WIRE FABRIC

NORTH ARROW

0A1 VIEW NAME

1/8" = 1'-0" 12" Contributor 1 / Contributor 2 / Contributor 3

VIEW NUMBER

DRAWING SCALE

TRUE NORTH

NORTH

PLAN

A1 A101

A1 A101

A101 A1

A00 KEYNOTE VALUE

RFI

REVISION NUMBER

REVISION TYPE

D.8 NEW GRID ID MARK

100'-0"

FIRST FLOOR

IDENTIFIED LEVEL NAME

ELEVATION MARK

SPOT ELEVATION MARK100'-0"

GENERAL SYMBOLS LEGEND

SHEET NUMBER

WALL SECTION MARK

VIEW NUMBER

SHEET NUMBER

ENLARGED DETAIL MARK

VIEW NUMBER

MATCHLINE

SHEET NUMBER

EXTERIOR ELEVATION MARK

VIEW NUMBER

A4/S104

VIEW NUMBER / SHEET NUMBER

OF CONTINUING VIEW

MASONRY

STEEL

CONCRETE

EARTH

GRANULAR FILL

GROUT

HIDDEN LINE

L(+100'-0") (+99'-0")

CHANGE IN SLAB ELEVATION MARK

W10 x4

9(E

BP2

STRUCTURAL COLUMN DESIGNATION

(E) - EXISTING

(D) - DEMOLISHED

BASE PLATE MARK

F # (+X'-X") P # (+X'-X")

FOOTING MARK (TOP ELEVATION)

BRICK LEDGE STEP MARK

PIER MARK (TOP ELEVATION)

SPAN DIRECTION MARK - ONE WAY

MOMENT FRAMING CONNECTION MARK

UPPER ELEVATION

LOWER ELEVATION

W(+100'-2")

(+100'-0") WALL STEP MARK

UPPER ELEVATION

LOWER ELEVATION

(+95'-0")

(+97'-0") FOUNDATION STEP MARK

UPPER ELEVATION

LOWER ELEVATION

GENERAL SYMBOLS LEGEND

DESIGN INFORMATION

1.

A.

B.

C.

D.

E.

F.

G.

H.

2.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

a.

b.

c.

3.

4.

CODES:

INTERNATIONAL BUILDING CODE (IBC) 20XX

AMERICAN CONCRETE INSTITUTE - BUILDING CODE REQUIREMENTS FOR STRUCTURAL

CONCRETE (ACI 318)

AMERICAN CONCRETE INSTITUTE - BUILDING CODE REQUIREMENTS FOR MASONRY

STRUCTURES (ACI 530)

AMERICAN INSTITUTE OF STEEL CONSTRUCTION - SPECIFICATION FOR STRUCTURAL

STEEL BUILDINGS (AISC 360)

ALLOWABLE STRENGTH DESIGN (ASD)

LOAD AND RESISTANCE FACTOR DESIGN (LRFD)

AMERICAN SOCIETY OF CIVIL ENGINEERS AND STRUCTURAL ENGINEERING INSTITUTE

(ASCE/SEI 7) - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

AMERICAN WELDING SOCIETY D1.1

AMERICAN IRON AND STEEL INSTITUTE (AISI S100) SPECIFICATION FOR THE DESIGN OF

COLD FORMED STEEL STRUCTURAL MEMBERS

AMERICAN FOREST & PAPER ASSOCIATION (AF&PA) NATIONAL DESIGN SPECIFICATION

FOR WOOD CONSTRUCTION (NDS)

DESIGN LOADS PER THE 2009 IBC (OCCUPANCY CATEGORY XXX) / DESIGN LOADS PER THE 2012

IBC (RISK CATEGORY XXX)

DEAD LOADS

STRUCTURE SELF WEIGHT AS SHOWN

CEILING, MEP & FP 10 PSF

ROOFING SYSTEM 10 PSF

MEP ABOVE MECHANICAL ROOM 20 PSF

LIVE LOADS

TYPICAL ROOF LIVE LOAD - 20 PSF

TYPICAL FLOOR LIVE LOADS (REDUCIBLE PER IBC 1607.10)

PARTITIONS 15 PSF

CORRIDORS 100 PSF

CORRIDORS ABOVE 1ST FLOOR 80 PSF

STAIRS STRUCTURE (UNREDUCIBLE) 100 PSF

STAIR TREADS 300 LBS OR 100 PSF

CLASSROOMS 40 PSF

OFFICE 50 PSF

MEDICAL PROCEDURE FLOORS 100 PSF

OPERATING ROOMS 60 PSF

PATIENT ROOMS 40 PSF

MECHANICAL ROOMS (UNREDUCIBLE) 150 PSF

LIGHT STORAGE (UNREDUCIBLE) 125 PSF

HEAVY STORAGE (UNREDUCIBLE) 250 PSF

PLATFORMS 60 PSF

CATWALKS 40 PSF

ROOF SNOW LOAD

GROUND SNOW LOAD, Pg XX PSF FLAT ROOF SNOW LOAD, Pf XX PSF SNOW EXPOSURE FACTOR, Ce XX SNOW IMPORTANCE FACTOR, Is XX THERMAL FACTOR, Ct XX RAIN ON SNOW (Pg<20 PSF) 5 PSF

SNOW DRIFT: REFER TO SNOW DRIFT DIAGRAM

WIND PRESSURE (ASCE 7-05)

BASIC WIND SPEED 90 MPH

WIND IMPORTANCE FACTOR XX

WIND EXPOSURE X

INTERNAL PRESSURE COEFFICIENT +/-0.18

MWFRS DESIGN WIND PRESSURE XX PSF

WIND PRESSURE (ASCE 7-10)

WIND SPEED, Vult XXX MPH NOMINAL DESIGN WIND SPEED, Vasd XXX MPH

WIND EXPOSURE X

INTERNAL PRESSURE COEFFICIENT +/-0.18

MWFRS DESIGN WIND LATERAL PRESSURE XX PSF

WIND PRESSURE - COMPONENTS AND CLADDING

PER ASCE 7 -XX FOR EACH REQUIRED COMPONENT

SEE SHEET S### FOR COMPONENTS AND CLADDING LOAD TABLE

SEISMIC DESIGN DATA

SEISMIC IMPORTANCE FACTOR XXX

MAPPED SPECTRAL RESPONSE ACCELERATIONS, Ss XXX

MAPPED SPECTRAL RESPONSE ACCELERATIONS, S1 XXX

SITE CLASS XXX

SPECTRAL RESPONSE COEFFICIENTS, Sds XXX SPECTRAL RESPONSE COEFFICIENTS, Sd1 XXX

SEISMIC DESIGN CATEGORY XXX

BASIC SEISMIC FORCE-RESISTING SYSTEM:

XXX

DESIGN BASE SHEAR, V = Cs x W XXX KIPS SEISMIC RESPONSE COEFFICIENT, Cs XXX

RESPONSE MODIFICATION FACTOR, R XX

ANALYSIS PROCEDURE: - EQUIVALENT LATERAL FORCE

LATERAL EARTH PRESSURES

ACTIVE PRESSURE XX PCF X DEPTH

AT-REST PRESSURE XX PCF X DEPTH

PASSIVE PRESSURE XX PCF X DEPTH

SPECIAL LOADING

DEFLECTION CRITERIA

FLOOR LIVE LOAD L/360

ROOF LIVE LOAD L/240

TOTAL LOAD ON MEMBERS SUPPORTING MASONRY L/600

SOILS INFORMATION BASED ON GEOTECHNICAL REPORT PREPARED BY XXXXXX, REPORT NO.

XXXXXXX, DATED XXXXXX.

NET ALLOWABLE SOIL BEARING PRESSURES:

SPREAD FOOTINGS XXXX PSF

CONTINUOUS WALL FOOTINGS XXXX PSF

DRILLED PIER END BEARING XXXX PSF

MINIMUM FROST PROTECTION DEPTH MEASURED FROM GRADE

EXTERIOR FOOTING ADJACENT TO HEATED AREA (-3'-6")

EXTERIOR FOOTING AT UNHEATED AREA (-4'-0")

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

A.

B.

C.

D.

10.

A.

B.

C.

11.

12.

13.

14.

15.

16.

17.

18.

THE GENERAL STRUCTURAL NOTES ARE INTENDED TO SUPPLEMENT THE DRAWINGS AND

SPECIFICATIONS. SHOULD CONFLICTS EXIST BETWEEN THESE DRAWINGS AND THE

SPECIFICATIONS NOTIFY THE ENGINEER OF ANY SUCH CONFLICTS.

STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ALL PROJECT DRAWINGS AND

SPECIFICATIONS. REFER TO ALL DRAWINGS FOR THE COORDINATION OF THE WORK IN THIS

PROJECT.

THE INTENT OF THESE PLANS AND NOTES IS TO PRESENT THE PROJECT REQUIREMENTS.

MAJOR DETAILS HAVE BEEN SHOWN ON THE DRAWINGS. HOWEVER, CERTAIN MINOR DETAILS

MUST BE WORKED OUT IN THE FIELD OR SHOP DRAWING PROCESS BY THE CONTRACTOR.

ELEVATIONS GIVEN ON PLANS ARE IN REFERENCE TO THE FINISHED FLOOR ELEVATION

(+100'-0") WHICH IS EQUAL TO THE CIVIL DATUM OF (XXX.XX').

UNLESS NOTED OTHERWISE, DETAILS SHOWN ON DRAWINGS ARE TO BE CONSIDERED TYPICAL

FOR ALL SIMILAR CONDITIONS.

THE STRUCTURE IS DESIGNED TO BE STABLE AND SELF-SUPPORTING AFTER THE BUILDING IS

FULLY ERECTED AND ALL CONNECTIONS ARE COMPLETED. UNLESS NOTED OTHERWISE, THE

DRAWINGS DO NOT INDICATE THE MEANS AND METHODS OF CONSTRUCTION. IT IS SOLELY THE

CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ERECTION PROCEDURE AND SEQUENCING

TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION.

THIS INCLUDES THE ADDITION TEMPORARY BRACING, GUYS AND TIE-DOWNS NECESSARY FOR

THE ERECTION PROCESS.

IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW THE APPLICABLE SAFETY CODES

AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.

CONTRACTOR'S CONSTRUCTION AND ERECTION SEQUENCE SHALL CONSIDER THE EFFECTS OF

THERMAL MOVEMENTS OF THE STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD.

EXISTING CONDITIONS:

THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL DIMENSIONS AND CONDITIONS

RELATING TO EXISTING CONSTRUCTION AND EXISTING SERVICES ON SITE. THE

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LOCATIONS OF EXISTING COLUMNS,

WALLS, OPENINGS, ETC, WITH THE ARCHITECTURAL DRAWINGS PRIOR TO PROCEEDING

WITH THE WORK. ANY DISCREPANCIES WITH THE CONTRACT DOCUMENTS SHALL BE

REPORTED TO THE ARCHITECT AND ENGINEER BEFORE PROCEEDING WITH THE AFFECTED

PART OF THE WORK.

DURING CONSTRUCTION THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS WHICH

ARE NOT KNOWN OR ARE AT VARIANCE WITH PROJECT DOCUMENTATION (DISCOVERY).

SUCH CONDITIONS MAY INTERFERE WITH THE NEW CONSTRUCTION OR REQUIRE

PROTECTION AND/OR SUPPORT OF EXISTING WORK DURING CONSTRUCTION. IT MAY ALSO

CONSIST OF DAMAGED OR DETERIORATION OF STRUCTURAL MATERIALS OR COMPONENTS

WHICH COULD JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING(S). THE

CONTRACTOR SHALL NOTIFY THE ENGINEER OF ALL DISCOVERIES WHICH MAY INTERFERE

WITH THE PROPER EXECUTION OF THE WORK OR JEOPARDIZE THE STRUCTURAL INTEGRITY

OF THE BUILDING(S) PRIOR TO PROCEEDING WITH THE WORK RELATED TO SUCH

DISCOVERIES.

DURING THE CONSTRUCTION PROCESS, IT SHALL BE SOLELY THE CONTRACTOR'S

RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF THE EXISTING STRUCTURE AND TO

PROTECT IT FROM DAMAGE ANY PORTIONS THAT ARE TO REMAIN.

CONTRACTOR SHALL INVESTIGATE THE SITE DURING EARTHWORK OPERATIONS FOR FILL

MATERIAL OR BURIED STRUCTURES. IMMEDIATELY, NOTIFY THE ENGINEER IF ANY SUCH

MATERIALS OR STRUCTURES ARE DISCOVERED.

STRUCTURAL COORDINATION

MECHANICAL, ELECTRICAL OR PLUMBING LOADS, OPENINGS AND SUPPORT FRAMING ARE

SHOWN FOR BIDDING PURPOSES ONLY. CONTRACTOR SHALL OBTAIN APPROVAL OF THE

MECHANICAL, ELECTRICAL OR PLUMBING CONTRACTOR BEFORE PROCEEDING WITH SUCH

PORTION OF THE WORK.

THE CONTRACTOR SHALL VERIFY THE SIZE AND LOCATION OF ALL OPENINGS, HOLES AND

SLEEVES THROUGH FOUNDATIONS AND OTHER STRUCTURAL ELEMENTS WITH THE

MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS. NO OPENINGS SHALL PASS

THROUGH STRUCTURAL MEMBERS UNLESS SHOWN ON THE DRAWINGS OR APPROVED BY

THE ENGINEER.

EXCESS COST DUE TO VARIATION IN THE STRUCTURE TO ACCOMMODATE A SUBSTITUTION

OR ALTERNATE MANUFACTURER(S) FROM THE LISTED BASIS OF DESIGN SHALL BE BORNE

BY THE CONTRACTOR.

BEFORE SUBMITTING A BID, EACH BIDDER SHALL VISIT THE SITE AND BECOME FULLY

ACQUAINTED WITH THE EXISTING CONDITIONS, CONSTRUCTION REQUIREMENTS,

RESTRICTIONS, QUANTITIES AND EQUIPMENT NECESSARY TO COMPLETE THE WORK. THE BID

SHALL INCLUDE ALL ITEMS REQUIRED TO COMPLETE THE WORK WITHIN THE EXISTING

CONDITIONS. DISRUPTION OF THE OWNERS NORMAL ACTIVITIES AROUND THE CONSTRUCTION

SITE SHALL BE KEPT TO A MINIMUM.

THE COST OF ADDITIONAL DESIGN WORK DUE TO ERRORS AND OMISSIONS BY THE

CONTRACTOR DURING CONSTRUCTION SHALL BE BORNE BY THE RESPONSIBLE CONTRACTOR.

ANY ENGINEERING DESIGN PROVIDED BY OTHER AND SUBMITTED FOR REVIEW OR RECORD

SHALL BEAR THE STAMP AND SIGNATURE OF A PROFESSIONAL STRUCTURAL ENGINEER

REGISTERED IN THE STATE WHERE THE PROJECT EXISTS.

CONTRACTOR SHALL COORDINATE WORK SCHEDULES WITH THE OWNER TO ESTABLISH

CONSTRUCTION SEQUENCING AROUND ANY OCCUPIED AREAS. CONTRACTOR SHALL NOT

PROCEED TO OCCUPIED AREAS UNTIL AUTHORIZED BY THE OWNER.

ALL ELEMENTS AND SURFACES DAMAGED BY DEMOLITION, BUT NOT SCHEDULED FOR REMOVAL

SHALL BE REPAIRED AND REFINISHED TO MATCH THE ADJACENT SURFACES AT NO ADDITIONAL

COST TO THE OWNER.

CONTRACTOR SHALL REMOVE ALL DEBRIS AND WASTE MATERIALS RESULTING FROM

CONSTRUCTION FROM THE SITE, UNLESS NOTED OTHERWISE.

CONTRACTOR SHALL MINIMIZE CREATION OF DUST, DIRT AND WINDBORNE DEBRIS FROM

BLOWING ACROSS THE SITE AND ONTO ADJACENT SITES.

CONTRACTOR SHALL COVER ANY EXTERIOR OPENING WITH TEMPORARY CLOSURES WHEN NOT

WORKING ON SITE TO PROTECT THE INTERIOR SPACES FROM WEATHER, INSECTS, RODENTS

AND INTRUDERS.

Pr in d:

Io a

Il lin oi s

In di an a

N eb ra sk a

PR

EL

IM

IN

AR

Y

- N O

T

FO

R

C O

N

ST

R U

C

TI

O N

D R

AW

N

AP

PR

O

VE

D

IS

SU

ED

F

O R

D

AT

E:

FI

EL

D B

O O

K:

PR

O

JE

C

T N

O

C

LI

EN

T

N O

A B D E FC

A B D E FC

W es to w n Pk w y, S ui te

W es t D es

M oi ne s, IA

5.

3.

w w w

.s hi ve -h at te ry .c om

Autodesk Revit 2020

/3

1/

:2 6:

A

M

C :\U se rs

\c m ar vi n\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \D

LW

JQ

6R Q

C 7D

Q \4 e4

1b 0-b5 b0

-4 c-b4 -5 f2

7c b7

8b e\ c7 c4 ef

-b 4d

1-

3b -8

0d 3-f7 3d f8 1d

3b 9d

.rv t

ID

O

T

- S al ix

W ei gh S ca le

B ui ld in g

Io w a D ep ar tm en t o f T ra ns po rta tio n

Sa lix

, I A

S000

ST

R

U C

TU

R

AL

G

EN

ER

AL

IN

FO

R

M

AT

IO

N

C D

Ap pr ov er

Au th or

/3

1/

MATERIAL CONFIGURATION REMARKS

LINTEL SCHEDULE

MARK

% C om

CAST-IN-PLACE CONCRETE

1.

2.

3.

4.

5.

A.

B.

a.

b.

C.

a.

b.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

ALL CONCRETE SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE AMERICAN

CONCRETE INSTITUTES PUBLICATIONS: ACI 301, ACI 305.1, ACI 306.1, ACI 315, AND ACI 318

UNLESS NOTED OTHERWISE.

CONCRETE COMPRESSIVE STRENGTH (28 DAY)(F'c)

FOOTINGS 4000 PSI

FOUNDATION WALLS AND PIERS 4000 PSI

SLAB ON GRADE 4000 PSI

GRADE BEAMS 4000 PSI

COLUMNS 5000 PSI

ELEVATED SLAB ON DECK 4000 PSI

ELEVATOR OR STAIR SHEAR WALLS 4000 PSI

ELEVATED BEAM, SLABS AND JOISTS 4000 PSI

DRILLED PIERS 4000 PSI

AUGER CAST PILES 4000 PSI

PILE CAPS 4000 PSI

CONCRETE REINFORCEMENT STANDARDS:

DEFORMED BARS ASTM A615 Fy = 60 KSI WELDED WIRE REINFORCEMENT (WWR) ASTM A1064 Fy = 65 KSI WELDABLE REINFORCING BARS ASTM A706 Fy = 60 KSI

SYNTHETIC MACRO FIBER REINFORCING ASTM C1116

EPOXY COATED REINFORCING ASTM A775 Fy = 60 KSI

ALL CONCRETE SHALL BE STONE AGGREGATE UNLESS NOTED OTHERWISE. SUBMIT MIX DESIGN

AND DOCUMENTATION FOR APPROVAL PER ACI 318.

REINFORCEMENT PROTECTION

CONCRETE PLACED AGAINST EARTH - 3"

CONCRETE PLACED IN FORMS BUT EXPOSED TO WEATHER OR EARTH:

BARS #5 AND SMALLER - 1 1/2"

BARS LARGER THAN #5 - 2"

CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:

SLABS, WALLS, AND JOISTS - 3/4"

BEAMS, COLUMNS - 1 1/2"

WHERE REQUIRED, DOWELS SHALL MATCH THE SIZE, NUMBER AND SPACING OF THE MAIN

REINFORCING UNLESS NOTED OTHERWISE.

ALL SPLICES, STANDARD HOOKS, AND DEVELOPMENT LENGTHS TO BE PER THE REFERENCED

EDITION OF ACI 318. MAKE BARS CONTINUOUS AROUND CORNERS. ALL SPLICES SHALL BE BY

CONTACT LAP.

ALL SPLICES SHALL BE A CLASS "B" TENSION SPLICE AS DEFINED IN ACI 318. PROVIDE LAP

SPLICES LENGTHS AS FOLLOWS:

LAP SPLICE LENGTHS GIVEN, ASSUME CLEAR SPACING BETWEEN BARS OF 2 BAR DIAMETERS,

AND A MINIMUM CLEAR COVER OF 1 BAR DIAMETER. TOP BARS ARE DEFINED AS HORIZONTAL

BARS WITH MORE THAN 12" ON FRESH CONCRETE BENEATH THE BARS.

WALLS AND GRADE BEAMS SHALL NOT HAVE JOINTS IN A HORIZONTAL PLANE, UNLESS

APPROVED BY THE ENGINEER.

CONSTRUCTION JOINTS IN STRUCTURAL CONCRETE WORK MUST BE MADE AT CENTER OF

SPAN OR AT CENTER OF SUPPORT WITH VERTICAL BULKHEADS AND HORIZONTAL KEYS,

UNLESS OTHERWISE SHOWN.

THERE SHALL BE NO ADDITIONAL OPENINGS LARGER THAN 10" IN CONCRETE WALLS AND SLABS

NOT SHOWN. REFER TO CONCRETE OPENING DETAIL FOR ADDITIONAL REINFORCEMENT

AROUND OPENINGS.

REINFORCING STEEL SHALL BE SECURELY FASTENED INTO FORMS PRIOR TO POURING

CONCRETE. WET SETTING OF REINFORCING STEEL WILL NOT BE ACCEPTED PER ACI.

CONCRETE MIX - FOOTINGS AND PILE CAPS

COARSE AGGREGATE 100% PASSING 1" SIEVE

FINE AGGREGATE 100% PASSING 3/8" SIEVE

WATER/CEMENT RATIO 0.45

SLUMP 4" +/- 1"

AIR CONTENT 6% +/- 1.5%

CONCRETE MIX - FOUNDATIONS

COARSE AGGREGATE 100% PASSING 1" SIEVE

FINE AGGREGATE 100% PASSING 3/8" SIEVE

WATER/CEMENT RATIO 0.45

SLUMP (NO WATER REDUCER) 4" +/- 1"

SLUMP (WITH WATER REDUCER) 4" TO 8"

AIR CONTENT 6% +/- 1.5%

CONCRETE MIX - SLAB ON GRADE - INTERIOR

COARSE AGGREGATE 100% PASSING 1" SIEVE

FINE AGGREGATE 100% PASSING 3/8" SIEVE

WATER/CEMENT RATIO 0.5

SLUMP (WITH WATER REDUCER) 4" TO 6"

AIR CONTENT LESS THAN 3%

CONCRETE MIX - TOPPING SLAB AND PAN STAIR FILL

COARSE AGGREGATE 100% PASSING 1/2" SIEVE

FINE AGGREGATE 100% PASSING NO.8 SIEVE

WATER/CEMENT RATIO 0.5

SLUMP (WITH WATER REDUCER) 5" TO 8"

AIR CONTENT LESS THAN 3%

BAR SIZE

#3 #4 #5 #6 #7 #8 #9 #10 #11

TYPICAL

22" 29" 36" 43" 63" 72" 81" 91" 101"

TOP BARS

28" 38" 47" 56" 81" 93" 105" 118" 131"

TYPICAL

19" 25" 31" 37" 54" 62" 70" 79" 87"

TOP BARS

25" 33" 41" 49" 71" 81" 91" 102" 114"

3000 PSI 4000 PSI

FOUNDATIONS

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED. DO NOT PLACE BACKFILL

BEHIND BASEMENT WALLS OR RETAINING WALLS UNTIL CONCRETE HAS ATTAINED THE

SPECIFIED COMPRESSIVE STRENGTH. BASEMENT WALLS SHALL NOT BE BACKFILLED UNTIL

SUPPORTING FLOOR IS COMPLETED AND ATTAINED FULL STRENGTH. CONTRACTOR SHALL

PROTECT ALL BELOW GRADE WALLS FROM LATERAL EARTH PRESSURES UNTIL SUPPORTING

FLOOR STRUCTURE IS COMPLETED. CONTRACTOR PROVIDE FOR DESIGN, PERMITS AND

INSTALLATION OF LATERAL SHORING TO BRACE WALLS IN LIEU OF WAITING FOR FLOOR SLAB

COMPLETION.

FOOTING SHALL BE CENTERED UNDER WALLS AND COLUMNS UNLESS NOTED OTHERWISE.

CONTRACTOR SHALL ACCOUNT FOR PUMPING OF WATER FROM THE EXCAVATION DUE TO

SURFACE WATER, GROUND WATER AND SEEPAGE.

CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF ALL SHEETING,

SHORING AND CRIBBING REQUIRED TO SAFELY RETAIN THE EARTH BANK AROUND THE

EXCAVATIONS.

ALL FOOTINGS SHALL BE PLACED ONTO FIRM UNDISTURBED SOIL OR ACCEPTABLE COMPACTED

BACKFILL AS OUTLINED IN THE SOIL REPORT AND PROJECT SPECIFICATIONS.

FOOTING ELEVATIONS SHOWN DESIGNATE THE MINIMUM DEPTH OF THE FOOTING WHERE THE

ALLOWABLE SOIL BEARING IS EXPECTED. LOCALIZED AREAS OF UNACCEPTABLE SOILS OR

POOR COMPACTION MAY BE DISCOVERED DURING THE EXCAVATION PROCESS REQUIRING

OVEREXCAVATION AND BACKFILL WITH ACCEPTABLE FILL. FOOTING EXCAVATIONS SHALL BE

LOWERED TO REACH SOIL MEETS THE DESIGN BEARING PRESSURE AND APPROVED BY THE

GEOTECHNICAL SPECIAL INSPECTION AGENCY.

ACCEPTABLE BACKFILL MATERIAL SHALL BE PLACED IN LIFTS NOT TO EXCEED EIGHT (8)

INCHES IN LOOSE THICKNESS.

FOR FOOTING AND FOUNDATIONS, THE SUBGRADE OR FILL MATERIAL SHALL BE COMPACTED

AND VERIFIED TO MEET 98% STANDARD PROCTOR MAXIMUM DRY DENSITY ACCORDANCE WITH

ASTM D698. FOR RELATIVELY COHESIONLESS GRANULAR FILL WHICH HAS A PERCENT PASSING

THE #200 SIEVE LESS THAN 10 PERCENT AND HAS ONLY A SLIGHT SENSITIVITY TO MOISTURE

CHANGES, COMPACTION SHALL BE 75 PERCENT RELATIVE DENSITY IN ACCORDANCE WITH

ASTM D4253 AND D4254. IF COMPACTION DOES NOT COMPLY, CONTRACTOR SHALL

RECOMPACT AREA AND UNTIL TEST RESULTS ARE PASSING. AN AREA EXHIBITING WEAKNESS

SUCH AS RUTTING OR PUMPING SHALL BE REMOVED AND REPLACED WITH COMPACTED

GRANULAR FILL.

FOOTING EXCAVATIONS SHALL BE INSPECTED AND APPROVED BY THE GEOTECHNICAL SPECIAL

INSPECTION AGENCY BEFORE CONCRETE IS PLACED. CONTRACTOR SHALL NOTIFY INSPECTION

AGENCY WHEN EXCAVATION IS READY FOR TESTING. INSPECTION AGENCY SHALL PROVIDE A

WRITTEN REPORT OF TEST RESULTS AND COMPLIANCE TO THE OWNER.

ACCEPTABLE SOIL SHALL BE DEFINED AS MEETING ASTM D2487 SOIL CLASSIFICATION GROUPS

GW, GP, GM, SW, SP, SM OR A COMBINATION OF THESE TYPES.

UNACCEPTABLE SOILS SHALL BE DEFINED AS MEETING ASTM D2487 SOIL CLASSIFICATION

GROUPS GC, SC, ML, MH, CL, CH, OL, OH, PT OR A COMBINATION OF THESE TYPES. GROUPS CL AND ML MAY BE ACCEPTABLE IF THE LIQUID LIMIT IS LESS THAN 45 AND THE PLASTICITY INDEX

IS LESS THAN 20.

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PREVENT ANY FROST OR

ICE FROM PENETRATING ANY FOOTING OR SLAB SUBGRADES BEFORE AND AFTER PLACING THE

CONCRETE AND UNTIL SUCH SUBGRADE IS FULLY PROTECTED BY THE PERMANENT BUILDING

ENCLOSURE AND THE SPACE IS CONDITIONED TO REMAIN ABOVE FREEZING.

CONCRETE FOOTINGS AND SLABS SHALL NOT BE PLACED ON OR AGAINST SUBGRADES

CONTAINING FROST, SNOW OR ICE. FROZEN SUBGRADES SHALL BE COMPLETELY THAWED AND

RECONDITIONED BEFORE CONCRETE MAY BE PLACED.

REPEATED HEAVY CONSTRUCTION TRAFFIC OVER EXPOSED SUBGRADE WILL CAUSE RUTTING

AND PUMPING WHEN SOIL IS ABOVE THE OPTIMUM MOISTURE CONTENT. AVOID EXCESS

CONSTRUCTION ACTIVITY ON WET SOILS. IF SUBGRADE IS ABOVE THE OPTIMUM MOISTURE

CONTENT DURING CONSTRUCTION, THEN DRYING OF THE SOIL SHALL BE CONDUCTED BY

DISKING, SCARIFICATION, AND AERATION.

SOILS WITH A MOISTURE CONTENT ABOVE THE OPTIMUM LEVEL SHALL BE REMOVED AND

REPLACED WITH COMPACTED GRANULAR FILL.

CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER OF ANY UNUSUAL SOIL

CONDITIONS THAT ARE IN VARIANCE WITH THE SOIL REPORT.

CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER IMMEDIATELY IF THE EXISTING

FOUNDATIONS VARY FROM THAT SHOWN ON THE DRAWINGS.

CONTRACTOR SHALL VERIFY OPENINGS AND SLEEVES THROUGH FOUNDATION WALLS WITH

THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL REQUIREMENTS. CHANGES IN SIZE,

LOCATION AND NUMBER SHALL NOT BE PERMITTED WITHOUT WRITTEN APPROVAL BY THE

ENGINEER.

CONTINUOUS WALL FOOTING REINFORCING SHALL EXTEND THROUGH COLUMN SPREAD

FOOTINGS UNLESS NOTED OTHERWISE.

GRADE BEAM TOP BARS SHALL BE CONTINUOUS OVER THE SUPPORTS. REINFORCEMENT

SHALL BE SPLICED WITH TOP BARS SPLICED AT MIDSPAN AND BOTTOM BARS SPLICED OVER

THE SUPPORT POINTS.

IF GRADE BEAM IS A SINGLE SIMPLE SPAN THEN TOP BARS SHALL BE CONTINUOUS FULL

LENGTH OF BEAM WITH STANDARD HOOKS AT EACH END AND BOTTOM BARS SHALL BE

CONTINUOUS BETWEEN SUPPORTS.

FOUNDATIONS - SLAB ON GRADE

1.

2.

3.

4.

5.

6.

7.

8.

9.

ALL ORGANIC MATERIAL AND UNACCEPTABLE FILL MATERIAL SHALL BE REMOVED FROM

BENEATH THE SLAB ON GRADE AS DIRECTED IN THE SOIL REPORT. EXPOSED SUBGRADE SHALL

BE PROOF ROLLED WITH A HEAVY WEIGHTED VEHICLE OF ROLLER IN THE PRESENCE OF THE

GEOTECHNICAL SPECIAL INSPECTION AGENCY. AREAS EXHIBITING RUTTING, PUMPING OR

WEAKNESS SHALL BE REMOVED AND REPLACED WITH COMPACTED ACCEPTABLE FILL

MATERIAL.

COMPACTION SHALL BE TESTED AND VERIFIED TO MEET 98% STANDARD PROCTOR MAXIMUM

DRY DENSITY ACCORDANCE WITH ASTM D698. FOR RELATIVELY COHESIONLESS GRANULAR FILL

WHICH HAS A PERCENT PASSING THE #200 SIEVE LESS THAN 10 PERCENT AND HAS ONLY A

SLIGHT SENSITIVITY TO MOISTURE CHANGES, COMPACTION SHALL BE 75 PERCENT RELATIVE

DENSITY IN ACCORDANCE WITH ASTM D4253 AND D4254. IF COMPACTION DOES NOT COMPLY,

CONTRACTOR SHALL RECOMPACT AREA AND UNTIL TEST RESULTS ARE PASSING. AN AREA

EXHIBITING WEAKNESS SUCH AS RUTTING OR PUMPING SHALL BE REMOVED AND REPLACED

WITH COMPACTED GRANULAR FILL.

CONCRETE SLAB ON GRADE SHALL BE PLACED ON A 6" WELL GRADED COMPACTED

GRANULAR FILL SUB-BASE.

PLACE ALL SLABS ON GRADE WITH AN APPROVED JOINT PATTERN SUBMITTED BY CONTRACTOR

AND APPROVED BY ENGINEER OR AS SHOWN ON DRAWINGS. SEQUENCE OF CONSTRUCTION

AND CONTROL JOINTS SHALL BE PLACED TO MINIMIZE SHRINKAGE CRACKS.

CONCRETE SLAB ON GRADES SHALL HAVE CONTROL JOINTS SAW CUT OR TOOLED . LOCATE

JOINT ALONG COLUMN CENTER LINES WITH INTERMEDIATE JOINTS AT A MAXIMUM SPACING OF

36 TIMES THE SLAB THICKNESS, UNLESS NOTED OTHERWISE. SLAB JOINT PANELS SHALL HAVE A MAXIMUM LENGTH TO WIDTH RATIO OF 1.5:1. DO NOT STAGGER OR OFFSET JOINTS. PROVIDE

ADDITIONAL JOINTS AT RE-ENTRANT CORNER. IF RE-ENTRANT CORNERS ARE UNAVOIDABLE,

THEN ADDITIONAL REINFORCING COMPRISED OF (2) #4 BARS x 3'-0" SHALL BE PLACED IN THE

CENTER OF THE SLAB DIAGONAL TO THE RE-ENTRANT CORNER CONDITION. PROVIDE SHOP

DRAWING OF CONTROL JOINT PATTERN AND CORNER REINFORCING.

SAWCUT JOINTS AS SOON AS SURFACE WILL ALLOW WITHOUT EDGES RAVELING BUT PRIOR TO

THE NEXT DAY AFTER THE POUR.

FLOOR FINISHES SHALL BE STEEL TROWELED FOR ALL INTERIORS AND BROOM FINISHED FOR

ALL EXTERIORS UNLESS NOTED OTHERWISE.

UTILITY TRENCH BACKFILL UNDER THE SLAB ON GRADE SHALL MEET THE SAME COMPACTION

REQUIREMENTS AS THE ORIGINAL SUBGRADE LISTED ABOVE.

SLOPE SLABS TO DRAINS TO CREATE POSITIVE DRAINAGE. PROVIDE DEPRESSIONS WHERE

INDICATED ON ARCHITECTURAL DRAWINGS, WHILE MAINTAINING THE THICKNESS OF THE

CONCRETE SLAB.

STRUCTURAL STEEL

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

STRUCTURAL STEEL SHALL CONFORM TO THE REFERENCED EDITION OF THE AISC

"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS".

STRUCTURAL STEEL MATERIAL STANDARDS

WIDE FLANGE SECTIONS ASTM A992 Fy = 50 KSI ANGLES, CHANNELS & PLATES ASTM A36 Fy = 36 KSI SQUARE AND RECTANGULAR HSS ASTM A500, GR C Fy = 50 KSI ROUND HSS ASTM A500, GR C Fy = 46 KSI STANDARD PIPE SECTIONS ASTM A53, GR B Fy = 35 KSI

STRUCTURAL STEEL CONNECTION STANDARDS:

HIGH STRENGTH BOLTS ASTM F3125 GRADE A325

HEAVY HEX NUT ASTM A563

WASHERS ASTM F436

ANCHOR RODS ASTM F1554 GRADE 36

HEADED WELDED STUDS ASTM A108 TYPE B

WELDING ELECTRODES (CARBON STEEL) AWS 5.1, E70XX

WELDING ELECTRODES (STAINLESS STEEL)

WELDING SHALL BE IN ACCORDANCE WITH STRUCTURAL WELDING CODE, AWS D1.1, LATEST

EDITION, AND SHALL BE PERFORMED BY CERTIFIED WELDERS ONLY USING PROPER

ELECTRODES FOR MATERIAL BEING WELDED. PROVIDE WELD SIZE IN ACCORDANCE WITH AISC

SPECIFICATIONS, BUT NOT LESS THAN 3/16" FILLET, CONTINUOUS UNLESS OTHERWISE NOTED.

ALL HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH RCSC -

"SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS." SEE DRAWINGS

FOR BOLTS SIZES. USE 3/4" DIAMETER, A325 BOLTS UNLESS NOTED OTHERWISE.

WHEN TENSION CONTROL BOLTS ARE INDICATED "TC" ON THE DRAWINGS, PROVIDE HIGH

STRENGTH "TENSION CONTROLLED" BOLTS MEETING ASTM F1852, TYPE 1.

ALL BOLTED CONNECTIONS ARE BEARING TYPE, UNLESS INDICATED AS TENSION CONTROLLED

(TC) OR SLIP CRITICAL (SC). PROVIDE STANDARD HOLES FOR BEARING TYPE CONNECTION

WHICH ARE 1/16" WIDER DIAMETER THAN THE BOLT.

ALL EXTERIOR EXPOSURE STEEL FRAMING, STEEL LINTEL ASSEMBLIES, BRICK RELIEF ANGLES

AND CONNECTORS SHALL BE HOT DIPPED GALVANIZED. ITEMS INDICATED TO BE GALVANIZED

SHALL BE HOT-DIP GALVANIZED IN COMPLIANCE WITH ASTM A123.

AFTER FABRICATION, ALL STEEL SHALL BE CLEANED OF ALL RUST, LOOSE MILL SCALE AND

OTHER FOREIGN MATERIALS. STEEL SHALL BE HAND TOOLED CLEANED (SSPC-SP2) OR

POWER TOOL CLEANED (SSPC-SP3).

ALL STRUCTURAL STEEL WILL HAVE ONE COAT OF FABRICATOR'S STANDARD LEAD AND

CHROMATE-FREE RUST INHIBITIVE PRIMER APPLIED PRIOR TO DELIVERY TO THE JOB SITE

UNLESS NOTED OTHERWISE. ALL AREAS OF STRUCTURAL STEEL MEMBERS IN WHICH THE

PRIMER COATED SURFACE IS DAMAGED DURING CONSTRUCTION SHALL BE TOUCHED UP WITH

MATCHING PRIMER.

THERE SHALL BE NO FIELD CUTTING OF STRUCTURAL STEEL MEMBERS FOR THE WORK OF

OTHER TRADES WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF

RECORD.

ALL MISCELLANEOUS STEEL AS SHOWN OR REFERENCED ON THE ARCHITECTURAL DRAWINGS

SHALL BE FABRICATED AND INSTALLED AS PART OF THE STRUCTURAL STEEL.

CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORES, GUYS, BRACES AND OTHER

SUPPORTS DURING ERECTION TO KEEP STRUCTURAL STEEL SECURE, PLUMB AND IN

ALIGNMENT AGAINST TEMPORARY CONSTRUCTION LOADS AND LOADS EQUAL TO DESIGN

LOADS. REMOVE ALL TEMPORARY SUPPORTS WHEN PERMANENT STRUCTURAL STEEL

FRAMING AND CONNECTIONS ARE COMPLETED.

MAINTAIN ERECTION TOLERANCES OF STRUCTURAL STEEL WITHIN AISC 303, "CODE OF

STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES."

DO NOT ENLARGE MISALIGNED BOLT HOLES BY BURNING OR THERMAL CUTTING. REAM HOLES

THAT MUST BE ENLARGED TO INSTALL BOLTS.

REINFORCED UNIT MASONRY

1.

2.

3.

4.

5.

6.

7.

A.

B.

C.

D.

E.

8.

9.

10.

11.

A.

B.

C.

D.

12.

13.

14.

15.

16.

CONCRETE MASONRY UNIT STANDARDS AND COMPRESSIVE STRENGTHS:

DESIGN ASSEMBLY STRENGTH, F'm , BY UNIT STRENGTH METHOD 2500 PSI

CONCRETE MASONRY UNITS (NORMAL WEIGHT) ASTM C90 3250 PSI

MASONRY GROUT ASTM C476 2500 PSI

MASONRY MORTAR, TYPE S ASTM C270 1800 PSI

REINFORCING FOR MASONRY ASTM A615 Fy = 60 KSI

PLATE AND BENT BAR ANCHORS ASTM A36

WIRE MESH TIES ASTM A185

JOINT REINFORCEMENT, LADDER TYPE, 1.7(9GA) ASTM A1064

ANCHOR RODS FOR MASONRY ASTM A307

THE LOAD BEARING CONCRETE MASONRY WALLS FOR THIS PROJECT WERE DESIGNED TO

SPAN VERTICALLY AND BE BRACED BY THE ROOF AND FLOOR FRAMING ELEMENTS OF THE

STRUCTURE. DURING CONSTRUCTION THE MASONRY CONTRACTOR SHALL PROVIDE LATERAL

BRACING UNTIL THE ROOF STRUCTURE IS INSTALLED AS RECOMMENDED BY ACI 530 AND THE

LATEST REVISION OF "STANDARD PRACTICE FOR BRACING MASONRY WALLS UNDER

CONSTRUCTION", PREPARED BY THE COUNCIL FOR MASONRY WALL BRACING. THIS BRACING IS

TO PREVENT UNNECESSARY STRESS OR DAMAGE TO THE MASONRY WALLS FROM LATERAL

LOADS, WHICH CAN OCCUR WHILE THE WALLS ARE NOT PROPERLY BRACED BY THE ROOF AND

FLOOR STRUCTURE.

SPLICE REINFORCING USING CONTACT LAPS TO THE LENGTHS INDICATED BELOW:

NP = NOT PERMITTED

NOTES TO SPECIFIER:

BASED ON 100% ALLOWABLE TENSILE STRESS IN REINFORCING (24,000 PSI)

LAP SPLICE CAN BE REDUCED (DIV BY 1.5) IF STRESS IS LESS THAN 80%

BARS GREATER THAN #9 ARE REQUIRED TO BE MECHANICALLY SPLICED

MASONRY MATERIALS AND CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF

“SPECIFICATION FOR MASONRY STRUCTURES AND RELATED COMMENTARIES (ACI 530/ASCE

6/TM 602) PUBLISHED BY AMERICAN CONCRETE INSTITUTE, EXCEPT WHERE REQUIREMENTS

ARE EXCEEDED BY THESE CONTRACT DOCUMENTS.

THOROUGHLY MIX MORTAR AND GROUT INGREDIENTS IN ACCORDANCE WITH THE

REFERENCED ASTM ABOVE IN QUANTITIES NEEDED FOR IMMEDIATE USE. DO NOT USE ANTI-

FREEZE COMPOUNDS TO LOWER THE FREEZE POINT.

ALL LOAD BEARING MASONRY WALLS SHALL BE HAVE FULL MORTAR BED, HEAD AND COLLAR

JOINTS. LAY HOLLOW MASONRY UNITS WITH FACE SHELL BEDDING ON HEAD AND BED JOINTS.

HORIZONTAL JOINT REINFORCEMENT: ALL LOAD BEARING MASONRY WALLS SHALL BE

CONSTRUCTED WITH LADDER TYPE JOINT REINFORCEMENT AS FOLLOWS:

SPACED AT A MAXIMUM OF 16" ON CENTER IN WALL CONSTRUCTION.

LAP JOINT REINFORCEMENT ENDS MINIMUM 6 INCHES.

PLACE HORIZONTAL JOINT REINFORCEMENT ONE ROW ABOVE AND ONE ROW BELOW ALL

WALL OPENINGS.

PLACE CONTINUOUS JOINT REINFORCEMENT IN FIRST JOINT BELOW THE TOP OF THE WALL.

DO NOT CONTINUE HORIZONTAL JOINT REINFORCEMENT ACROSS CONTROL OR EXPANSION

JOINTS.

ALL LOAD BEARING REINFORCED UNIT MASONRY WALLS SHALL HAVE (1) #5 BAR VERTICALLY IN

GROUTED CELL AT ALL CORNERS, ENDS OF WALLS, WALL INTERSECTIONS, AND IMMEDIATELY

ADJACENT TO EACH SIDE OF CONTROL JOINTS AND WALL OPENINGS.

CONCRETE MASONRY UNIT CORES SHALL BE PLACED WITH CELLS IN VERTICAL ALIGNMENT. ALL

CORES CONTAINING REINFORCEMENT AND ANCHORS SHALL BE FILLED SOLID WITH GROUT.

GROUT ALL CELLS TO RECEIVE ANCHORS.

PROVIDE A MINIMUM OF 1/2" OF GROUT BETWEEN THE MAIN REINFORCING AND THE MASONRY

UNITS. ALL VERTICAL REINFORCEMENT SHALL BE CENTERED IN THE WALL UNLESS NOTED

OTHERWISE.

ALL MASONRY WALLS SHALL HAVE VERTICAL CONTROL JOINTS AT A MAXIMUM SPACING OF 25

FEET AS FOLLOWS:

COORDINATE CONTROL JOINTS WITH LOCATIONS INDICATED ON ARCHITECTURAL

DRAWINGS.

CONTROL JOINTS SHALL NOT INTERFERE WITH BEAMS, JOISTS, OR LINTEL BEARING.

PROVIDE PREFORMED EXTRUDED RUBBER CONTROL JOINT DESIGNED FOR MASONRY

WALLS CONFORMING TO ASTM D2000 2AA-805.

SEAL JOINT WITH SINGLE COMPONENT ELASTERMERIC POLYURETHANE SEALANT. COLOR

TO MATCH MORTAR JOINTS.

DOWELS IN FOOTINGS SHALL BE PLACED TO ALIGN WITH CORES CONTAINING REINFORCING

STEEL. COORDINATE PLACEMENT BEFORE CONSTRUCTION OF FOOTING BEGINS.

GROUT SOLID ALL CMU CORES BELOW ADJACENT GRADE OR BELOW SLAB ON GRADE

CONSTRUCTION.

DURING CONSTRUCTION OF WALLS, COVER TOPS OF WALLS, PARTIALLY COMPLETED MASONRY

AND ANY OPEN WALL CAVITIES AT SILLS OR HEADERS WITH WATERPROOF SHEETING AT THE

END OF EACH DAY'S WORK.

REINFORCE ALL NON-LOAD BEARING MASONRY WALLS (SHOWN ON ARCHITECTURAL

DRAWINGS) WITH #5 BARS AT XX" OC UNLESS NOTED OTHERWISE.

BEAM BEARING CONDITIONS: FILL BLOCK CELLS SOLID WITH GROUT A DISTANCE OF 24"

BENEATH AND 12" EACH SIDE OF BEAM REACTIONS OR OTHER CONCENTRATED LOADS IF NOT

OTHERWISE REINFORCED. ALL BEAM AND JOIST POCKETS SHALL BE GROUTED SOLID OR

FILLED WITH CONCRETE MASONRY UNITS AFTER STEEL ERECTION IS COMPLETE.

BAR SIZE

#3 #4 #5 #6 #7 #8 #9

6" CMU

27" 36" 45" 54"

NP

NP

NP

8" CMU

27" 36" 45" 54" 63" 113"

NP

10" CMU

27" 36" 45" 54" 63" 72" 82"

12" CMU

27" 36" 45" 54" 63" 72" 82"

MINIMUM LAP SPLICE LENGTH

REINFORCED UNIT MASONRY - LINTELS

1.

2.

3.

4.

5.

6.

7.

8.

PROVIDE LINTELS ABOVE ALL WALL OPENINGS AND RECESSES GREATER THAN 12" WIDE AS

INDICATED IN THE PLANS AND LINTEL SCHEDULE.

OPENINGS NOT IDENTIFIED ON THE DOCUMENTS SHALL BE CONSTRUCTED IN A SIMILAR

MANNER TO THE SCHEDULED LOCATIONS THAT MATCH SPAN AND LOAD CONDITIONS. CONTACT

STRUCTURAL ENGINEER FOR CONFIRMATION.

LINTELS FOR 8" WIDE CMU NON-LOAD BEARING MASONRY PARTITION WALLS SHALL HAVE

LINTELS IN ACCORDANCE WITH THE FOLLOWING SCHEDULE:

ALL CMU BOND BEAM LINTELS SHALL HAVE A MINIMUM (2) #5 BARS PLACED 3" FROM THE

BOTTOM OF THE BLOCK AND GROUTED SOLID.

ALL STEEL ANGLE LINTELS ARE LONG LEG BACK TO BACK AND STITCH WELDED TOGETHER

TOP AND BOTTOM 3" LONG AT 12" ON CENTER MINIMUM.

ALL BOND BEAM LINTELS SHALL BE CONSTRUCTED USING BOND BEAM UNITS.

WALL OPENING JAMBS SHALL BE GROUTED SOLID FULL HEIGHT BELOW THE WIDTH OF THE

LINTEL BEARING, UNLESS NOTED OTHERWISE.

ALL LINTELS SHALL HAVE A MINIMUM OF 8" END BEARING, UNLESS NOTED OTHERWISE.

ALL STEEL LINTEL ASSEMBLIES IN EXTERIOR WALL CONSTRUCTION SHALL BE HOT-DIP

GALVANIZED PER ASTM A123, UNLESS NOTED OTHERWISE.

BEARING PLATES NOT REQUIRED FOR STEEL LINTELS, UNLESS NOTED OTHERWISE.

OPENING WIDTH MASONRY OPTION STEEL OPTION

1'-0 TO 2'-0"

>2'-0" TO 4'-0"

>4'-0" TO 6'-0"

>6'-0" TO 8'-0"

8" DEEP BOND BEAM 5/16"x7"PLATE (2)L3 1/2x3 1/2x1/4

(2)L4x3 1/2x5/16(LLV) (2)L5x3 1/2x5/16(LLV)

8" DEEP BOND BEAM

8" DEEP BOND BEAM

16" DEEP BOND BEAM

STEEL DECK

1.

2.

3.

4.

5.

6.

7.

A.

B.

8.

A.

B.

9.

10.

11.

12.

13.

ALL METAL DECK SHALL BE DESIGNED, MANUFACTURED, AND INSTALLED IN ACCORDANCE WITH

THE LATEST PROVISIONS OF THE STEEL DECK INSTITUTE - "DESIGN MANUAL FOR COMPOSITE

DECKS, FORM DECKS, ROOF DECKS AND CELLULAR METAL FLOOR DECK WITH ELECTRICAL

DISTRIBUTION" AND UNDERWRITER REQUIREMENTS (I.E. FACTORY MUTUAL).

STEEL DECK AND ACCESSORIES SHALL BE FABRICATED FROM STEEL SHEETS CONFORMING TO

THE FOLLOWING STANDARDS:

PAINTED STEEL ROOF DECK ASTM A1008, GR 33

GALVANIZED STEEL ROOF DECK ASTM A653, GR 33

GALVANIZED STEEL FLOOR DECK ASTM A653, GR 50 [33]

COMPOSITE STEEL FLOOR DECK ASTM A653, GR 50 [40]

PROVIDE METAL DECK MANUFACTURED BY A MEMBER OF THE STEEL DECK INSTITUTE OF THE

TYPE AND GAUGE INDICATED ON THE DRAWINGS.

GALVANIZED STEEL ROOF, FLOOR AND COMPOSITE DECK SHALL BE SHEET MATERIAL

CONFORMING TO ASTM A924 WITH A MINIMUM G60 COATING.

MINIMUM DECK BEARING ON STEEL MEMBERS SHALL BE 1 1/2". INSTALL DECK WITH A MINIMUM

2" END LAPS CENTERED OVER SUPPORT MEMBERS. COMPOSITE FLOOR DECK ENDS SHALL NOT

BE LAPPED.

DECK MANUFACTURER SHALL PROVIDE ALL RIDGE AND VALLEY PLATES, FLOOR DECK FILLERS,

AND COLUMN CLOSURES NECESSARY TO COMPLETE THE DECK INSTALLATION. ALL DECK AND

ACCESSORIES SHALL BE GALVANIZED, 20 GA. MINIMUM.

WHERE NOT INDICATED IN THE DRAWINGS, ATTACH ROOF DECK TO SUPPORTING STEEL

MEMBERS WITH EITHER PUDDLE WELDS OR POWDER ACTUATED FASTENERS:

(4) 5/8" DIAMETER PUDDLE WELDS PER 36 INCH WIDE SHEET (36/4 PATTERN). FASTEN

SIDELAPS CONDITIONS WITH #10 SELF DRILLING SCREWS, MINIMUM OF ONE SCREW AT

EACH MID SPAN OR AT 24" ON CENTER MAXIMUM . ATTACH DECK TO EDGES AT MEMBERS

PARALLEL TO CORRUGATIONS WITH 5/8" DIAMETER PUDDLE WELDS AT MINIMUM 6" ON

CENTER.

APPROVED EQUIVALENT POWDER ACTUATED…