This file is an electrical and instrumentation plan revision for the City of Pembroke Pines' Lift Station #64 Rehabilitation project located at 120 NW 108th Terrace, Pembroke Pines, Florida. The project scope includes the replacement of two existing 15-horsepower, 240-volt three-phase electrical pumps with two new 17-horsepower, 240-volt three-phase electrical pumps, demolition of the existing double throw panel (DTP), demolition of two existing control panels (CP and CP-2), and installation of a new 100-ampere, 240-volt electrical panel. The drawings are diagrammatical in nature representing existing conditions based on available documentation and site observations. A non-mandatory pre-bid meeting is scheduled for Tuesday, August 26, 2025, at 10:00 am, with proposal submissions required by Tuesday, September 23, 2025. The project timeline is 180 calendar days from the Notice to Proceed, with an estimated project cost of $560,000.
The electrical contractor is responsible for guaranteeing all electrical work, including parts and labor, for one year after final written acceptance by the City of Pembroke Pines. The contractor must obtain permits, procure certificates, conduct field visits prior to bidding, and coordinate with other trades while providing temporary power at the project site. The City of Pembroke Pines is responsible for all fees necessary to bring utility power to the site. All materials must be new and of specified types or approved equal, with wiring complying with the National Electrical Code Article 300. The contractor must coordinate all Florida Power and Light (FPL) service work with FPL Project Manager Daniel Robles at Daniel.Robles@fpl.com or (941) 202-9019. The project must comply with the Florida Building Code (8th Edition, 2023), Florida Fire Prevention Code (8th Edition, 2023), Florida Energy Conservation Code (8th Edition, 2023), NFPA 70 (National Electrical Code, 2020 Edition), NFPA 72 (National Fire Alarm Code, 2019 Edition), and NFPA 101 (Life Safety Code, 2021 Edition).
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
0 0
X X
X X
X X
X X
X X
X
XXXXXXX
X X
X X
X X
X X
X X
X X
X X
X X
X XX X X X X X X X X X X X X X
DTP
FPL
METER
CP
PUMP #1PUMP #2
CP-2
EXISTING FPL
TRANSFORMER
FPL METER TO BE
RELOCATED
4 5 6 7 8 9
A E-1
A' E-1
GATE
GATE
ELECTRICAL NOTES
1. CONTRACTOR SHALL GUARANTEE THE ENTIRE ELECTRICAL WORK, INCLUDING
PARTS AND LABOR, FOR A PERIOD OF ONE (1) YEAR AFTER FINAL WRITTEN
ACCEPTANCE BY CITY OF PEMBROKE PINES.
2. THE CONTRACTOR SHALL TAKE PERMITS AND PROCURE CERTIFICATES.
3. THE CONTRACTOR SHALL MAKE FIELD VISITS PRIOR TO BID AND BECOME
FAMILIAR WITH THE SCOPE OF WORK INVOLVED IN THIS JOB. EXTRAS SHALL NOT
BE ALLOWED FOR FAILURE ON THE CONTRACTOR'S PART TO COMPLY WITH THIS
REQUIREMENT.
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH
OTHER TRADES AS WELL PROVIDING TEMPORARY POWER AT PROJECT SITE FOR
ALL TRADES. THE OWNER SHALL BE RESPONSIBLE FOR ALL FEES NECESSARY TO
BRING UTILITY POWER TO PROJECT SITE.
5. ALL MATERIALS SHALL BE NEW, OF TYPES AND MAKES CALLED FOR, OR
APPROVED EQUAL.
6. GROUNDING SHALL COMPLY WITH THE NEC ART 250.
7. PROVIDE ENGRAVED PLASTIC LABELS FOR ALL NEW ELECTRICAL PANELS AND
JUNCTION BOXES.
8. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS PRIOR TO PROCEEDING WITH ANY WORK. WHERE DISCREPANCIES
OCCUR BETWEEN THESE DOCUMENTS AND EXISTING CONDITIONS, THE
DISCREPANCY SHALL BE REPORTED TO OWNER'S REPRESENTATIVE FOR
EXPEDITING AND RESOLUTION.
9. CONTRACTOR TO ASSURE THAT PROPER CLEARANCE (AS PER MANUFACTURER
RECOMMENDATIONS) IS PROVIDED AROUND ALL NEW EQUIPMENT FOR
SERVICING AND REPLACEMENT PURPOSES.
10. DISCONNECT SWITCHES SHALL BE H.P. RATED, QUICK-MAKEQUICK-BREAK
ENCLOSURES AS REQUIRED BY EXPOSURE.
11. ALL WIRING INSTALLATION SHALL BE MADE AS REQUIRED BY NEC ART. 300.
12. ALL CONDUCTORS SHALL BE COPPER WITH THW/THWN INSULATION. ALL
CONDUCTORS #10 AND SMALLER MAY BE SOLID. ALL CONDUCTORS #8 AND
LARGER SHALL BE STRANDED TYPE. ALL CONDUCTORS SHALL BE IN CONDUIT.
OUTDOOR UNDERGROUND CONDUITS SHALL BE IN PVC SCHEDULE-40., MINIMUM
COVER SHALL BE 18". OUTDOOR ABOVEGROUND CONDUITS SHALL BE RIGID.
INTERIOR EXPOSED OR CONCEALED CONDUIT SHALL BE EMT. STEEL
SET-SCREW FITTINGS. ALL WIRING INSTALLATION SHALL BE MADE AS REQUIRED
BY NEC Art. 300.
SCOPE OF WORK
THE SCOPE OF WORK OF THIS PROJECT CONSISTS OF:
- REPLACEMENT OF EXISTING TWO (2) 15HP, 240V-3PH ELECTRICAL PUMPS WITH
TWO (2) NEW 17HP, 240V-3PH ELECTRICAL PUMPS.
- DEMOLITION OF THE EXISTING DOUBLE THROW PANEL (DTP)
- DEMOLITION OF THE EXISTING CONTROL PANEL (CP).
- DEMOLITION OF THE EXISTING CONTROL PANEL (CP-2).
- INSTALLATION OF NEW 100A, 240V ELECTRICAL PANEL (CP).
ELECTRICAL PANEL.
ELECTRICAL SYMBOLS LEGEND
ELECTRICAL CLEARANCE.
P-X
BRANCH CIRCUIT HOMERUN TO PANEL BOARD NUMBER INDICATE
CIRCUIT DESIGNATION.
BUILDING CODE: FLORIDA BUILDING CODE - 8TH EDITION - 2023
FIRE/LIFE SAFETY CODE: FLORIDA FIRE PREVENTION CODE - 8TH EDITION -
ENERGY CODE: FLORIDA ENERGY CONSERVATION CODE - 8TH
EDITION-2023
NFPA 70: NATIONAL ELECTRICAL CODE - 2020 EDITION
NFPA 72: NATIONAL FIRE ALARM CODE - 2019 EDITION
NFPA 101: LIFE SAFETY CODE - 2021 EDITION
CODE REQUIREMENTS SHALL BE INCLUSIVE OF ALL ADDENDUMS AND
CLARIFICATIONS ISSUED UP TO THE TIME WHEN THE BUILDING PERMIT IS
GRANTED. THE LISTED CODES AND PERMIT STANDARDS SHALL NOT BE
CONSTRUED TO BE THE ONLY APPLICABLE CODES AND STANDARDS
GOVERNING THIS PROJECT. THE GENERAL CONTRACTOR, ALL
SUB-CONTRACTORS AND SUPPLIERS SHALL VERIFY AND ADHERE TO THE
REQUIREMENTS OF ALL OF THE CODES AND STANDARDS THAT GOVERN
AND PERTAIN TO THEIR PRESCRIBED SCOPE OF WORK.
APPLICABLE CODES
1 EXISTING 15HP, 240V-3PH, ELECTRICAL PUMP TO BE REPLACED.
2 EXISTING 150A / 120-240V, 3PH HIGH-LEG, DOUBLE THROW
ELECTRICAL PANEL TO BE DEMOLISHED.
3 EXISTING CONTROL PANEL TO BE DEMOLISHED.
4 ALL WORK SHALL BE COORDINATED WITH PROJECT MANAGER
BEFORE EXECUTION.
5 ELECTRICAL CONTRACTOR SHALL EXERCISE EXTRA CARE FOR ALL
DEMOLITION WORK. COORDINATE WITH PROJECT MANAGER WHERE
THE REMOVED EQUIPMENT SHALL BE PLACED.
6 ALL WORK SHALL BE PERFORMED IN A CLEAN MANNER. ALL WORK
SHALL BE COORDINATED WITH PROJECT MANAGER TO MINIMIZE ANY
DISTURBANCE TO OTHER AREAS OF THE BUILDING WHICH ARE TO
REMAIN IN OPERATION.
7 ALL REMOVED ITEMS SHALL BECOME PROPERTY OF THE OWNER
AND SHALL BE DISPOSED AS PER PROJECT MANAGER
INSTRUCTIONS, UNLESS INDICATED OTHERWISE. ALL ITEMS WHICH
WILL NOT BE KEPT BY THE OWNER, SHALL BE REMOVED AT
CONTRACTOR'S EXPENSE.
8 THESE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND
REPRESENT EXISTING CONDITIONS BASED ON AVAILABLE
DRAWINGS AND SITE OBSERVATIONS. CONTRACTOR IS
RESPONSIBLE FOR FIELD VERIFICATION OF ALL ACTUAL
CONDITIONS, FOR EXACT LOCATIONS AND SIZES OF PIPING,
CONDUIT, WIRES, EQUIPMENT, ETC.
9 EXISTING WORK TO REMAIN SHALL BE PROTECTED FROM DAMAGE.
WORK DAMAGED BY THE CONTRACTOR SHALL BE REPAIRED TO
MATCH EXISTING WORK.
10 ELECTRICAL POWERCORD - 3#8AWG + 1#10 - TYPE SOOW - EPDM
INSULATION - CPE JACKET. ELECTRICAL CONTRACTOR SHALL
COORDINATE WITH PUMP SUPPLIER. NO JUNCTION BOXES ALLOWED
BETWEEN WET WELL AND CONTROLPANEL.
11 ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FPL SERVICE
WORK WITH FPL PROJECT MANAGER:
DANIEL ROBLES
Daniel.Robles@fpl.com (941)202-9019
12 ELECTRICAL PANEL AND DISCONNECT ENCLOSURE SHALL BE
NEMA3R.
13 EXISTING CONDUIT AND WIRE FROM FPL TRANSFORMER TO BE
REUSED. ELECTRICAL CONTRACTOR SHALL EXTEND AND
RECONNECT EXISTING WIRE AS REQUIRED IF THEY ARE IN GOOD
CONDITION AND MATCH NEW REQUIREMENTS.
KEY ELECTRICAL NOTES
EXISTING
NEW ELECTRICAL EQUIPMENT
DEMOLITION
DTP DOUBLE THROW PANEL
0 0
X X
X X
X X
X X
X X
X
XXXXXXX
X X
X X
X X
X X
X X
X X
X X
X X
X XX X X X X X X X X X X X X X
B' E-1
CP
FPL
METER
MDS
MDS
GATE
GATE
PUMP #1PUMP #2
B E-1
7.00'
1.20'
-15.85'
0.00'
FROM
PANEL CP
2"C
CP
CPDTP
CP-2
FPL METER TO BE
RELOCATED
PUMP-1
15HP
+3.55'
+6.92'
15HP
PUMP-2
-14.22"
X X
X X
X X
XXXXXXX
X X
X X
X X
X X
X
X X X X X X X X X
X X
APPROVED:
DRAWN:
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
07-21-250 ISSUED FOR PERMIT
ELECTRICAL PLAN -
EXISTING - DEMOLITION
NEW
24-119-E1
E - 1
1 14
Pedro Arias, P.E.
Florida Registration. No. 63813
N.T.S.
LOCATION MAP
LIFT STATION LOCATION
ELECTRICAL PLAN -
EXISTING DEMOLITION SCALE: 1/4" = 1'-0"
N W th
S t
NW 108th Ave
SCALE: 1/4" = 1'-0"
ELEVATION B-B'ELECTRICAL PLAN - NEW
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
ELEVATION A-A'
SCOPE OF WORK
N.T.S.
SITE PLAN
N W th
S t
NW 108th Ave
DOUBLE THROW PANELDTP
NEW
DEMOLITION
LEVEL 3.55'
FPL
METER
CP
DTP
150A
240V-HIGH LEG
3PH
NEMA 3R
15HPPUMP #1
CP-2
15HP PUMP #2
L
NE
FROM FPL
TRANSFORMER
LEVEL (-) 15.85'
FPL
METER
17HPPUMP #1 17HP PUMP #2
FROM FPL
TRANSFORMER
CP
LIFT STATION
CONTROL PANEL
MCB
100A
240V-3PH
22KAIC
NEMA 3R-SS
LEVEL 7.00'
MDS
240V-3PH
HIGH-LEG
22KAIC
NEMA 3R-SS
LEVEL 9.23'
9 9
ELECTRICAL KEY NOTES
1 EXISTING FPL METER TO BE RELOCATED.
2 ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FPL SERVICE WORK WITH
FPL PROJECT MANAGER:
DANIEL ROBLES
Daniel.Robles@fpl.com (941)202-9019
3 EXISTING LIGHTING FIXTURE AND LIGHT SWITCH TO BE REPLACED.
4 NEW LIGHTING FIXTURE. LIGHTING FIXTURE SHALL BE PROTECTED BY A 20AMPS
FUSE. ELECTRICAL CONTRACTOR SHALL INSTALL AN IN-LINE FUSE ON PHASE-A
TO FEED THE EXISTING SERVICE LIGHT FIXTURE. USE POLARIS TAP INSIDE THE
DISCONNECT SWITCH.
5 NEW LIFT STATION PUMP PROVIDED AND INSTALLED BY CONTRACTOR.
6 ELECTRICAL POWER WIRING AND CONTROL WRING BETWEEN LIFT STATION
CONTROL PANEL AND LIFT STATION PUMPS TO BE PROVIDED AND COMPLETED
BY CONTRACTOR.
7 FINAL CONNECTIONS BETWEEN LIFT STATION CONTROL PANEL AND LIFT
STATION PUMPS AND START-UP BY CONTRACTOR.
8 ELECTRICAL POWERCORD - 3#8AWG + 1#10 - TYPE SOOW - EPDM INSULATION -
CPE JACKET. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH CITY OF
PEMBROKE PINES PROJECT MANAGER. NO JUNCTION BOXES ALLOWED
BETWEEN WET WELL AND CONTROL PANEL.
9 17HP IMMERSIBLE MOTOR. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
CITY OF PEMBROKE PINES PROJECT MANAGER.
10 EXISTING CONDUIT AND WIRE FROM FPL TRANSFORMER TO BE REUSED.
ELECTRICAL CONTRACTOR SHALL EXTEND AND RECONNECT EXISTING WIRE AS
REQUIRED IF THEY ARE IN GOOD CONDITION AND MATCH NEW REQUIREMENTS.
11 EYS EXPLOSION PROOF SEALING FITTING AS PER NEC ART 501.10.
12 NEW WATER LEVEL SENSORS TO BE PROVIDED AND COMPLETED
BY CONTRACTOR.
5 6 7
2"C 2"C
EXISTING GROUNDING SYSTEM
AS PER NEC ART 250.50
#8
PROVIDE AN INTERSYSTEM BONDING
TERMINATION AS PER NEC ART. 250.94
CONNECT TO TWO 5/8" x 10Ft LONG
COPPERCLAD STEEL GROUND DRIVEN RODS.
SPACE RODS MIN. 6Ft O.C.
NEC ART 250.66
GROUNDING SYSTEM
AS PER NEC ART 250.50
LS
2"C
CLASSIFIED AREA
CLASS 1, DIVISION 1, GROUP D
APPROVED:
DRAWN:
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
07-21-250 ISSUED FOR PERMIT
ELECTRICAL RISER
EXISTING-DEMOLITION
NEW
24-119-E2
E - 2
2 14
1 08-20-25 CONDUIT SEAL REV
Pedro Arias, P.E.
Florida Registration. No. 63813
ELECTRICAL RISER- NEW
N.T.S.
ELECTRICAL RISER / EXISTING - DEMOLITION
N.T.S.
AutoCAD SHX Text S
AutoCAD SHX Text S
DOUBLE THROW PANELDTP
NEW
DEMOLITION
APPROVED:
DRAWN:
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E3
E - 3
3 14
Pedro Arias, P.E.
Florida Registration. No. 63813
APPROVED:
DRAWN:
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
07-21-250 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E4
E - 4
4 14
1 08-20-25 CONDUIT SEAL REV
Pedro Arias, P.E.
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E5
E - 5
5 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E6
E - 6
6 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E7
E - 7
7 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E8
E - 8
8 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E9
E - 9
9 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E10
E - 10
10 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E11
E - 11
11 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E12
E - 12
12 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E13
E - 13
13 14
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
20871 Johnson Street, Suite 115 Phone: (954) 318-2264 Fax: (954) 450-7216
Pembroke Pines, Florida 33029
State of Florida CA No. 9113
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
06-18-240 ISSUED FOR PERMIT
CONTROL PANEL
24-119-E14
E - 14
14 14
| 24-119 E-1-R0 |
| Sheets and Views |
| E-1 |
| 24-119 E-2-R1 |
| Sheets and Views |
| E-2 |
| 24-119 E-3-R0 |
| Sheets and Views |
| E-3 |
| 24-119 E-4-R1 |
| Sheets and Views |
| E-4 |
| 24-119 E-5-R0 |
| Sheets and Views |
| E-5 |
| 24-119 E-6-R0 |
| Sheets and Views |
| E-6 |
| 24-119 E-7-R0 |
| Sheets and Views |
| E-7 |
| 24-119 E-8-R0 |
| Sheets and Views |
| E-8 |
| 24-119 E-9-R0 |
| Sheets and Views |
| E-9 |
| 24-119 E-10-R0 |
| Sheets and Views |
| E-10 |
| 24-119 E-11-R0 |
| Sheets and Views |
| E-11 |
| 24-119 E-12-R0 |
| Sheets and Views |
| E-12 |
| 24-119 E-13-R0 |
| Sheets and Views |
| E-13 |
| 24-119 E-14-R0 |
| Sheets and Views |
| E-14 |
File details come from the government source that posted it. Updated .