This document is a set of structural design drawings and general notes for the Valdosta Water Treatment Plant (WTP) No. 2 and Production Wells project issued for bid by the City of Valdosta, Georgia. The project comprises multiple structures including two production wells, a degasification complex, ground storage tank, chemical injection vault, high service pump station, operations building, chemical storage area, carbon dioxide storage and feed system, and a sanitary grinder pump station. The drawings are prepared by CDM Smith (COA No. PEF000106; Expiration Date 06/30/2026) and include detailed mechanical, structural, and architectural plans with specifications for concrete, masonry, structural steel, and aluminum construction. The document establishes design criteria, load requirements, material specifications, and standard construction details necessary for contractors to execute the work.
The design incorporates comprehensive structural requirements including concrete with 4,500 PSI 28-day compressive strength for structural elements, ASTM A992 structural steel, ASTM A500 hollow structural sections, and masonry with 2,000 PSI design compressive strength. Foundation designs accommodate varying soil bearing pressures ranging from 1,000 PSF for mat foundations to 2,700 PSF for the high service pump station. Wind design specifications reference ASCE 7-16 with ultimate design wind speeds of 122 mph and nominal speeds of 95 mph for Risk Category III structures. Seismic design criteria establish a Seismic Design Category B with response modification factors specified for reinforced concrete and masonry shear wall systems. All delegated submittals, including equipment anchorage, railing systems, tank restraints, and pre-engineered structural components, must be signed and sealed by Georgia-registered professional engineers and submitted for engineer review prior to fabrication and construction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VALVE TAGEQUIPMENT TAG
MISCELLANEOUS SYMBOLS
PIPE AND FITTING SYMBOLSPROCESS PIPE IDENTIFICATION
PROCESS VALVE LOOP IDENTIFICATION PIPE TAG
GENERAL NOTES
M-1
MECHANICAL GENERAL NOTES
AND LEGEND
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
M-2
WELL NO. 1
PLAN AND SECTION
SECTION 1PLAN
N
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-3
WELL NO. 2
PLAN AND SECTION
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
SECTION 1 PLAN
N
M-4
DEGASIFICATION COMPLEX NO. 1
PLAN
PLAN
N
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-5
SECTIONS I
SECTION 1 SECTION 2
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-6
SECTIONS II
SECTION 1
SECTION 2
SECTION 3
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-7
ISOMETRIC
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
M-8
GROUND STORAGE TANK PLAN
DOME PLAN
FLOOR PLAN
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
M-9
GROUND STORAGE TANK
SECTION AND DETAILS
DETAIL A
DETAIL B DETAIL C DETAIL D
SECTION 1
M-10
GROUND STORAGE TANK
SECTIONS AND DETAILS
DETAIL D
SECTION 3
DETAIL ASECTION 2SECTION 1
DETAIL E
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-11
GROUND STORAGE TANK
DETAILS
DETAIL A
DETAIL B
DETAIL E
DETAIL D
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-12
CHEMICAL INJECTION VAULT
PLAN AND SECTION
PLAN
SECTION 1
N
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
PLAN
M-13
HIGH SERVICE PUMP STATION PLAN
N
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-14
HIGH SERVICE PUMP STATION SECTION
AND FLOW METER PAD PLAN AND SECTION
SECTION 1
SECTION 1
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
N
3'-0" CONC
ENCASEMENT
3'-0" CONC
ENCASEMENT
M-15
CHEMICAL STORAGE AREA
PLAN
N
PLAN
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-16
SECTIONS I
SECTION 1
SECTION 2 SECTION 3
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-17
SECTIONS II
SECTION 4 SECTION 5
DETAIL A
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
M-18
ISOMETRIC
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
M-19
CARBON DIOXIDE STORAGE AND FEED SYSTEM
PLAN
N
SECTION 1 DETAIL ADETAIL B
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
M-20
CARBON DIOXIDE STORAGE AND FEED SYSTEM
SECTIONS
SECTION 2 SECTION 3 SECTION 4
SECTION 1
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
M-21
SANITARY GRINDER PUMP STATION
PLAN AND SECTION
DETAIL A
N
DETAIL B
DETAIL EDETAIL D
DETAIL C
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
MD-1
MISCELLANEOUS MECHANICAL DETAILS I
DETAIL B
DETAIL D
DETAIL F
DETAIL C
DETAIL A
DETAIL G DETAIL H
DETAIL E
DETAIL JDETAIL
DETAIL A
MD-2
MISCELLANEOUS MECHANICAL DETAILS II
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
DETAIL B DETAIL C DETAIL D
DETAIL E
DETAIL F
DETAIL G
DETAIL H
DETAIL I
1'
PLAN
ELEVATION
MD-3
MISCELLANEOUS MECHANICAL DETAILS III
CITY OF VALDOSTA, GA
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
DETAIL A DETAIL B
3" FLOW METER6" MIN ABOVE
GRADE
15" 9"
3" GATE VALVE
(TYP)
MIN MIN
AB
ADDL
ALUM/AL
ALT
APPROX
BOT
BRG
B/W
CJ
CL
CLJ
CLR
CMU
COL
CONC
CONN
CONT
DET
DIA
DIAG
DL
DWG
DWL
EA
EB
EF
EL
EMBED
EQ
EQUIP
ES
EW
EXST
EXP JT
EXT
f'c f'm
FAB
FDN
FT
FH
FL
FRP
FTG
GALV
GR
GRTG
H
HAS.
HDR
HOR/HORIZ
HP
IDE
I.E.
NUMBER
AND
AT
ANCHOR BOLT
ADDITIONAL
ALUMINUM
ALTERNATE (ING)
APPROXIMATELY
BOTTOM
BEARING
BETWEEN
CONSTRUCTION JOINT
CENTERLINE
CONTROL JOINT
CLEAR
CONCRETE MASONRY UNITS
COLUMN
CONCRETE
CONNECTION
CONTINUOUS
DETAIL
DIAMETER
DIAGONAL
DEAD LOAD
DRAWING
DOWEL
EACH
EXPANSION BOLT
EACH FACE
ELEVATION
EMBEDMENT
EQUAL (LY)
EQUIPMENT
EACH SIDE
EACH WAY
EXISTING
EXPANSION JOINT
EXTERIOR
CONCRETE COMPRESSION STRESS
MASONRY PRISM STRESS
FABRICATE (OR, ED)
FOUNDATION
FEET
FLATHEAD
FLOOR
FIBERGLASS REINFORCED PLASTIC
FOOTING
GALVANIZED
GRADE
GRATING
HIGH
HEADED ANCHOR STUD
HEADER
HORIZONTAL
HIGH POINT
INSIDE
INVERT ELEVATION
JT
LG
LLH
LLV
LOC(S)
LP
MAS
MAX
MFR
m/s
MPH
MIN
MO
NS
NTS
OC
OH
OPNG
PCJ
PREFAB
PROJ
PLG
PSF
R
REF
REINF
REQD
REV
SECT
SIM
SP
SQ
SS
STD
STIF
STIR
STL
SYM
T T/ T&B
TF
THD
TOC
TRNSV
TYP
UNO
VB
VERT
VIF
W/ W/O
WD
WP
WSTP
WWF
JOINT
LENGTH
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LOCATION(S)/LOCATED
LOW POINT
MASONRY
MAXIMUM
MANUFACTURER
METERS PER SECOND
MILES PER HOUR
MINIMUM
MASONRY OPENING
NON-SHRINK
NOT TO SCALE
ON CENTER
OVERHEAD
OPENING
PARTIAL CONTRACTION JOINT
PREFABRICATED
PROJECTION
POUNDS PER LINEAR FOOT/FEET
POUNDS PER SQUARE FOOT/FEET
RISER(S)
REFERENCE/REFER
REINFORCE (D, ING)
REQUIRED
REVISION
SECTION
SIMILAR
SPACE (S, ED)
SQUARE
STAINLESS STEEL
STANDARD
STIFFENER
STIRRUP (S)
STEEL
SYMMETRICAL
TREAD(S)
TOP OF
TOP AND BOTTOM
TOP FACE
THREADED
TOP OF CONCRETE
TRANSVERSE
TYPICAL
UNLESS NOTED OTHERWISE
VAPOR BARRIER
VERTICAL
VERIFY IN FIELD
WITH
WITHOUT
DRIFT WIDTH
WORKING POINT
WATERSTOP
WELDED WIRE FABRIC
DESIGN CRITERIA:
CODES:
• INTERNATIONAL BUILDING CODE, 2018 EDITION WITH GEORGIA
AMENDMENTS
• ENVIRONMENTAL STRUCTURES: ACI 350-06 "CODE REQUIREMENTS
FOR ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES"
• OTHER STRUCTURES: ACI 318-14 "BUILDING CODE REQUIREMENTS
FOR STRUCTURAL CONCRETE"
• AISC STEEL CONSTRUCTION MANUAL, FIFTEENTH EDITION
• AISC 360-10 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS
• TMS 402-2016 "BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES"
CONCRETE:
ALL MATERIALS AND METHODS OF CONSTRUCTION SHALL BE IN ACCORDANCE
WITH ACI 318 REQUIREMENTS.
ALL CONCRETE SHALL BE AIR-ENTRAINED.
WATER REDUCING AGENT SHALL BE IN ACCORDANCE WITH ASTM C494.
ALL CONCRETE SURFACES EXPOSED TO AIR, UNLESS OTHERWISE NOTED IN
SPECIFICATIONS, SHALL BE TREATED WITH AN APPROPRIATE CURING COMPOUND
AS SOON AS CEMENT FINISHING IS COMPLETED OR FORMS ARE REMOVED.
ALL EXPOSED CORNERS OF CONCRETE SHALL HAVE A MINIMUM CHAMFER OF 3/4"
UNLESS OTHERWISE NOTED.
THE CONTRACTOR SHALL OBTAIN ENGINEER'S APPROVAL FOR THE LOCATION OF
CONSTRUCTION JOINTS THAT ARE NOT SHOWN ON THE DRAWING.
DESIGN LOADS:
LIVE LOADS:
• STAIRWAYS 100 PSF
• WALKWAYS 100 PSF
• PROCESS SLABS ON GRADE 300 PSF
• ELEVATED SLABS 200 PSF
• STORAGE AREAS AND ELECTRICAL ROOM 300 PSF
• GRATING AND COVER PLATE 100 PSF
ROOF SNOW LOAD:
• GROUND SNOW LOAD, Pg 0 PSF
• FLAT SNOW LOAD, PF 0 PSF
• SNOW EXPOSURE FACTOR, CE 1.0
• SNOW LOAD IMPORTANCE FACTOR, Is 1.10
• THERMAL FACTOR, CT SEE DRAWINGS
SUPERIMPOSED DEADLOADS:
• ROOFS AS NOTED
• FLOORS AS NOTED
WIND DESIGN DATA: ASCE 7-16
• ULTIMATE DESIGN WIND SPEED, Vult (3 SECOND GUST) 122 MPH
• NOMINAL DESIGN WIND SPEED, Vasd 95 MPH
• RISK CATEGORY III
• WIND EXPOSURE CATEGORY C
• ENCLOSURE CLASSIFICATION SEE DESIGN DRAWINGS
• INTERNAL PRESSURE COEFFICIENT SEE DESIGN DRAWINGS
FLOOD DESIGN DATA:
• PER NFIP FIRM MAP NO. 13185C0220E, PANEL 220 OF 400, DATED SEPTEMBER 26,
2008, NOT IN A FLOOD ZONE
EARTHQUAKE:
• RISK CATEGORY III
• SITE CLASS D
• SEISMIC DESIGN CATEGORY B
• SEISMIC IMPORTANCE FACTOR, IE 1.25
• MAPPED SPECTRAL RESPONSE ACC, SS 0.09
• MAPPED SPECTRAL RESPONSE ACC, S1 0.055
• SPECTRAL RESPONSE COEFFICIENT, SDS 0.096
• SPECTRAL RESPONSE COEFFICIENT, SD1 0.087
• SEISMIC-FORCE-RESISTING SYSTEM SEE DESIGN DRAWINGS
• DESIGN BASE SHEAR SEE DESIGN DRAWINGS
• SEISMIC RESPONSE COEFFICIENT, CS SEE DESIGN DRAWINGS
• RESPONSE MODIFICATION FACTOR, R SEE DESIGN DRAWINGS
• ANALYSIS PROCEDURE USED SEE DESIGN DRAWINGS
CONCRETE 28-DAY STRENGTH:
• STRUCTURAL CONCRETE 4500 PSI
• MASONRY FILLED CELL GROUT 2500 PSI
• CONCRETE FILL AND ENCASEMENT 2500 PSI
FOUNDATIONS:
• ALLOWABLE BEARING PRESSURE FOR STRIP AND MAT FOUNDATIONS OVER
SUBSURFACE PREPARED AS PER DRAWINGS AND SPECIFICATIONS:
• MAT FOUNDATION 1,000 PSF
• STRUCTURAL FILL 3,000 PSF
• STRIP FOOTINGS 2,000 PSF
• DEGASIFICATION COMPLEX NO. 1 2,000 PSF
• OPERATIONS BUILDING 2,000 PSF
• HIGH SERVICE PUMP STATION 2,700 PSF
• CHEMICAL STORAGE AREA 2,000 PSF
• CHEMICAL INJECTION VAULT 2,000 PSF
• MISCELLANEOUS SLABS-ON-GRADE 2,000 PSF
GENERAL CONDITIONS:
ALL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE
ARCHITECTURAL, MECHANICAL, CIVIL, ELECTRICAL AND SHOP DRAWINGS AND
SPECIFICATIONS.
THE CONTRACTOR SHALL REVIEW AND VERIFY DIMENSIONS SHOWN IN ALL PLANS
AND REVIEW ALL FIELD CONDITIONS THAT MAY AFFECT THE INSTALLATION OF THE
FACILITY, SHOULD DISCREPANCIES APPEAR, THE CONTRACTOR SHALL NOTIFY THE
ENGINEER IN WRITING TO OBTAIN ENGINEER'S CLARIFICATION BEFORE COMMENCING
WITH THE WORK.
FOR ALL ITEMS EMBEDDED IN OR PASSED THROUGH CONCRETE, THE CONTRACTOR
SHALL INITIALLY REFER TO ARCHITECTURAL, ELECTRICAL, MECHANICAL, HEATING AND
VENTILATION DRAWINGS AND APPROVED SHOP DRAWINGS FOR TYPE, SIZE, LOCATION
AND SPECIAL INSTALLATION REQUIREMENTS FOR THESE ITEMS.
THE CONTRACTOR SHALL TAKE ANY AND ALL NECESSARY MEASURES TO PROTECT
EXISTING STRUCTURES FROM DAMAGE WHEN WORKING IN AND AROUND EXISTING
STRUCTURES PERFORMING WORK SUCH AS DEMOLITION, FOUNDATION EXCAVATION
AND OTHERS.
SIZE AND LOCATION OF EQUIPMENT PADS AND ANCHOR BOLTS SHALL BE PER
EQUIPMENT MANUFACTURER'S REQUIREMENTS.
ANY EQUIPMENT THAT MAY INDUCE VIBRATION TO THE STRUCTURE SHALL BE
ADEQUATELY ISOLATED FROM THE STRUCTURES.
ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE
TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSE-
WHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
STANDARD DETAILS APPLY TO ALL SIMILAR SITUATIONS ON THE PROJECT, EXCEPT
WHERE A DIFFERENT DETAIL IS SHOWN.
ALL PIPES UNDER SOIL SUPPORTED STRUCTURE SLABS AND FOOTINGS SHALL BE
ENCASED IN CONCRETE AS SHOWN ON THE STRUCTURAL DRAWINGS. PIPES SHALL
BE PRESSURE TESTED BEFORE ENCASING.
ELECTRICAL CONDUIT, PIPING, WASH HOSE STATIONS, HOSE RACKS, CONTROL PANELS,
LIGHT FIXTURES, ENCLOSURES OR ANY OTHER APPURTENANCE, SHALL NOT BE DIRECTLY
SUPPORTED OFF OF GUARDRAIL UNLESS EXPLICITLY ALLOWED BY THE STRUCTURAL
ENGINEER OF RECORD.
REINFORCING STEEL:
REINFORCEMENT SHALL CONFORM TO ASTM A615, GRADE 60 REQUIREMENTS.
ALL ACCESSORIES SHALL BE IN CONFORMANCE WITH ACI 315 REQUIREMENTS.
REINFORCING STEEL SHALL HAVE THE FOLLOWING CLEAR COVER UNLESS
OTHERWISE NOTED:
• CONCRETE CAST AGAINST EARTH 3"
• FORMED SURFACES IN CONTACT WITH SOIL,
SEWAGE, WATER OR EXPOSED TO WEATHER 2"
• FORMED SURFACES NOT EXPOSED TO WEATHER OR
IN CONTACT WITH SOIL:
SLABS, WALLS AND JOISTS 3/4"
BEAMS AND COLUMNS 1-1/2"
LAP SPLICES SHALL BE AS SHOWN ON THE DRAWINGS. FOR LAP SPLICES NOT
SHOWN ON THE DRAWINGS, THE CONTRACTOR SHALL OBTAIN ENGINEER'S
APPROVAL.
THE CONTRACTOR SHALL PREPARE PLACING DRAWINGS AND SCHEDULES IN
CONFORMANCE WITH ACI 315 REQUIREMENTS.
STRUCTURAL STEEL:
DESIGN, FABRICATION, ERECTION MATERIALS AND WORKMANSHIP SHALL BE IN
ACCORDANCE WITH THE LATEST AISC SPECIFICATIONS AND DESIGN DRAWINGS.
ALL STRUCTURAL STEEL:
• W SHAPES - ASTM A992
• M, S AND HP SHAPES - ASTM A36
• CHANNELS AND ANGLES - ASTM A36
• HSS (SQUARE, RECTANGULAR AND ROUND) - ASTM A500
• PLATES - ASTM A36
• HIGH-STRENGTH BOLTS - ASTM F3125
• TENSION CONTROL BOLTS - ASTM F1852
• NUTS - ASTM A563
• HARDENED STEEL WASHER - ASTM F436
• ANCHOR RODS - ASTM F1554
• THREADED RODS - ASTM A36
ALL PIPE: ASTM A53, GRADE B.
THE FABRICATOR SHALL DESIGN AND DETAIL ALL PARTS OF CONNECTIONS NOT
FULLY DETAILED ON THE DESIGN DRAWINGS. THE NUMBER OF BOLTS AND OTHER
SIMILAR ELEMENTS SHOWN ON THE DRAWING ARE PICTORIAL ONLY.
SHOP AND ERECTION DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER FOR
REVIEW.
WELDED CONNECTIONS SHALL BE IN ACCORDANCE WITH THE LATEST AWS
STRUCTURAL WELDING CODE REQUIREMENTS. ELECTRODES SHALL BE E-70XX.
STRUCTURAL ALUMINUM:
DESIGN, FABRICATION, ERECTION MATERIALS AND WORKMANSHIP SHALL BE IN
ACCORDANCE WITH THE LATEST "ALUMINUM DESIGN MANUAL" (ADM) SPECIFICATIONS
AND DESIGN DRAWINGS.
ALL STRUCTURAL ALUMINUM:
• ALUMINUM EXTRUDED PIPE - ASTM B429, ALLOY 6063-T6
OR ALLOY 6061-T6
• ALUMINUM EXTRUDED SHAPE - ASTM B221, ALLOY 6061-T6
• ALUMINUM SHEET AND PLATE - ASTM B209, ALLOY 6061-T6
• ALUMINUM ALLOY ROLLED THREAD PLATE - ASTM B632, ALLOY 6061-T6
• ALUMINUM CASTING - ASTM B26/B26M, ALLOY A350.6-T6
SHOP AND ERECTION DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER FOR
REVIEW.
WELDED CONNECTIONS SHALL BE IN ACCORDANCE WITH THE LATEST AWS D1.2/D1.2M
"STRUCTURAL WELDING CODE - ALUMINUM".
WHERE ALUMINUM CONTACTS A DISSIMILAR METAL, APPLY TO THE DISSIMILAR METAL
A HEAVY BRUSH COAT OF ZINC-CHROMATE PRIMER FOLLOWED BY TWO COATS OF
ALUMINUM METAL PAINT.
WHERE ALUMINUM CONTACTS MASONRY OR CONCRETE, APPLY A HEAVY COAT OF
BITUMASTIC OR EPOXY PAINT.
FLOTATION CONSIDERATION:
STRUCTURES WERE DESIGNED TO BE NON-BUOYANT AFTER THE STRUCTURE IS
PLACED INTO SERVICE. THEREFORE, THE STRUCTURE MAY BE BUOYANT DURING
CONSTRUCTION. THE GENERAL CONTRACTOR SHALL PROTECT ALL STRUCTURES
(NEW AND EXISTING) FROM FLOTATION DURING CONSTRUCTION, REGARDLESS OF
GROUNDWATER LEVELS, UNTIL STRUCTURES ARE PLACED IN OPERATION.
WATERSTOP
GRATING
SPAN
DIRECTION
EARTH FILL
UNDISTURBED
EARTH
CONCRETE
CONCRETE
MASONRY
STRUCTURAL
FILL
ALUMINUM
AL GRATING
CHECKERED
PLATE
SAND
GRANULAR FILL
DEMOLITION
FRP
GRATING
HOUSEKEEPING
PAD SEE A/SD-2
CONCRETE MASONRY:
DESIGN CRITERIA:
• DESIGN COMPRESSIVE STRENGTH OF MASONRY AT 28 DAYS f'm = 2,000 PSI
• ALLOWABLE STEEL STRESS fs = 25,600 PSI
CONTINUOUS INSPECTION IS REQUIRED FOR ALL MASONRY WORK.
ALL MATERIALS AND METHODS OF CONSTRUCTION SHALL BE IN ACCORDANCE WITH
DRAWINGS AND SPECIFICATIONS AND:
• TMS 402-16 "BUILDING CODE FOR MASONRY STRUCTURES."
• SPECIFICATION 042200
MATERIALS:
• BLOCK: CONFORM TO ASTM C90 - LOAD BEARING, NORMAL WEIGHT TWO CELL,
8"x8"x16" AND 12"x8"x16" (COMPRESSIVE STRENGTH, NET AREA 2,000 PSI)
• MORTAR: CONFORM TO ASTM C270, TYPE S. MINIMUM COMPRESSIVE STRENGTH AT
28 DAYS - 2,000 PSI. UTILIZE TYPE II CEMENT AND TYPE S LIME.
• STEEL: LADDER TYPE JOINT REINFORCEMENT AT EVERY
SECOND COURSE (16" OC). BOND BEAM AND FILLED CELL REINFORCEMENT AS PER
DRAWINGS. (ASTM A615, GRADE 60).
CONSTRUCTION:
• ALL FILLED CELLS AND COLUMNS SHALL BE POURED AT LEAST (2) HOURS PRIOR TO
POURING LINTEL BLOCK OR TIE BEAMS.
• MAXIMUM CONSTRUCTION HEIGHT OF MASONRY WALLS WITHOUT FILLED CELL OR
COLUMN POURS IS TO BE 8'-0". THE CONCRETE FOR FILLED CELLS SHALL BE
RODDED OR PUDDLED DURING PLACEMENT TO ENSURE COMPLETE FILLING TO THE
BLOCK CORE.
• SEE STANDARD DETAILS AND ARCHITECTURAL DRAWINGS FOR LINTEL
REQUIREMENTS OVER OPENINGS.
• PROVIDE CLEAN OUT AND INSPECTION BLOCK OUTS IN CELLS CONTAINING
REINFORCEMENT.
GEOTECHNICAL REPORT:
GEOTECHNICAL ENGINEERING REPORT ENTITLED, "VALDOSTA WATER TREATMENT PLANT,"
BY TTL, INC, DATED JUNE 5, 2024. GEOTECHNICAL REPORT AVAILABLE UPON REQUEST.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
GENERAL STRUCTURAL NOTES
S-1
S000STNT.RVT
ABBREVIATIONS
GENERAL NOTES
LEGEND AND SYMBOLS
WATERTIGHTNESS TESTING REQUIREMENTS:
• THE WATER-CONTAINING STRUCTURES SHALL BE FILLED WITH POTABLE WATER
AND TESTED FOR WATERTIGHTNESS PER SPECIFICATION SECTION 018819.
• PERFORM WATERTIGHTNESS TESTING PRIOR TO WATERPROOFING AND
DAMPPROOFING, INSTALLATION OF COATINGS AND LININGS, AND PRIOR TO
PLACING BACKFILL AROUND STRUCTURES.
• ALL SEEPING CRACKS SHALL BE INJECTED WITH WATER ACTIVATED
HYDROPHILIC POLYURETHANE GROUT UNTIL SEEPAGE STOPS.
ABBREVIATION NOTES:
1.ABBREVIATIONS AND DESIGNATIONS FOR STEEL MEMBERS MAY BE FOUND IN THE CURRENT
MANUAL OF STEEL CONSTRUCTION BY AISC.
2.ABBREVIATIONS OF TECHNICAL SOCIETIES AND TRADE ASSOCIATIONS MAY BE FOUND IN THE
SPECIFICATIONS.
3.WELDING SYMBOLS AND ABBREVIATIONS MAY BE FOUND IN AWS 2.4.
DELEGATED SUBMITTALS:
1. THE FOLLOWING PORTIONS OF THE PROJECT ARE DELEGATED SUBMITTAL ITEMS
AND HAVE NOT BEEN DESIGNED BY THE ENGINEER OF RECORD:
a. EQUIPMENT, TANK AND PIPE SUPPORT ANCHORAGE
b. RAILING SYSTEMS
c. TANK RESTRAINTS
d. PRE-ENGINEERED CANOPY
e. PRESTRESSED WIRE-WRAPPED GROUND STORAGE TANK
f. FRP COMPONENTS
g. WALL MOUNTED CANOPY
h. PRE-ENGINEERED COLD FORMED STEEL TRUSS
1. DELEGATED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE ENGINEER FOR
REVIEW DURING THE CONSTRUCTION PHASE OF THE PROJECT.
2. DELEGATED SUBMITTAL ITEMS SHALL BE SIGNED AND SEALED BY A STRUCTURAL
ENGINEER REGISTERED IN THE STATE OF GEORGIA.
3. DELEGATED SUBMITTAL ITEMS SHALL NOT BE ERECTED OR INSTALLED UNTIL THE
ENGINEER OF RECORD HAS REVIEWED THE SUBMITTAL DOCUMENTS AND
INDICATED THAT THEY HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
CONFORMANCE WITH THE DESIGN OF THE STRUCTURE.
FOUNDATION PREPARATION:
ALL CONCRETE FOUNDATIONS AND SLAB-ON-GRADE SHALL BE PLACED ON GRADED AGGREGATE
BASE OR COMPACTED STRUCTURAL FILL MEETING STRUCTURAL FILL CRITERIA. INSTALL
6oz NON-WOVEN GEOTEXTILE FABRIC BETWEEN AGGREGATE AND NATIVE SOIL OR STRUCTURAL FILL.
REFER TO SPECIFICATION SECTION 312000 FOR STRUCTURAL FILL REQUIREMENTS.
UNSUITABLE SOILS SHALL BE REMOVED TO THE LIMITS SHOWN OR AS ENCOUNTERED AND
REPLACED WITH STRUCTURAL FILL COMPACTED TO AT LEAST 98% OF THE STANDARD PROCTOR
MAXIMUM DRY DENSITY PER ASTM 698.
STRUCTURAL FILL SHOULD EXTEND 5-FEET BEYOND THE EDGE OF THE FOOTING, THEN AT A SLOPE OF ONE HORIZONTAL TO ONE VERTICAL TO SUITABLE BEARING SOILS, AS SHOWN ON THE DRAWINGS.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
ST I N S . BOGG
S
UP
S-4
S-4
45' - 0" 35' - 0"
1' - 0" 15' - 0" 1' - 0" 5' - 0" 1' - 0" 11' - 0" 1' - 0"
1' - 6" 1' - 6"
PIPE SUPPORT SEE
"M" DRAWINGS (TYP)
S-4
O P
N G
B E
L O
W
O P
N G
B E
L O
W
1/2" EXPANSION JOINT
MATERIAL W/ SEALANT
1/2" EXPANSION JOINT
MATERIAL W/ SEALANT
AL LADDER (TYP)
S L O
P E
/8
HP EL 198.79
LP EL 198.50
SLOPE 1/8" / 12"
LP EL 198.50
HP EL 198.58
EL 196.00
T/CONC
6"x6" OPENING
BELOW (TYP OF 2)
A
SD-2
(TYP)
10' - 0"
1/2" EXP JT
1/2" EXP JT
NOTE:
INDICATES HOUSEKEEPING OR EQUIPMENT PAD. SEE DETAILS A/SD-2 AND B/SD-2.
COORDINATE SIZE WITH SUPPLIED EQUIPMENT.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
DEGASIFICATION COMPLEX NO. 1
FOUNDATION PLAN S-2
SWZ000CW.RVT
1/4" = 1'-0"
FOUNDATION PLAN (EL 198.50)
N structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
S-4
S-4
S-4
SIDE MOUNTED AL GUARDRAIL (TYP)
35' - 0"
S-4
(T Y
P
(TYP)
3' - 6" *
AL FLOOR DOOR W/ LADDER
(TYP OF 3)
E
SD-5
S L O
P E
/8
S
L O
P E
/8
LP EL 208.00
LP EL 208.00
B
SD-2
A
SD-4
TYPE "T-1" STAIR
A
SD-5
A
SD-2
A
S-4
(TYP)
HP EL 208.08
OPNG FOR 16" PIPE
PIPE OPENING
REFER TO
PROCESS
DRAWINGS
HINGED SIDE (TYP)
EQUIP PAD
3' - 0" 2' - 0" 3' - 0" 2' - 0" 3' - 0"
DESIGN LOAD DATA - DEGASIFICATION COMPLEX NO. 1
SEISMIC:
BASIC SEISMIC-FORCE-RESISTING SYSTEM: ORDINARY REINFORCED CONCRETE SHEAR WALLS
DESIGN BASE SHEAR: Cs*W
SEISMIC RESPONSE COEFFICIENT: Cs: 0.005
RESPONSE MODIFICATION FACTOR: R: 4
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE PROCEDURE
REFER TO SHEET S-1 FOR DESIGN LOAD DATA THAT IS THE SAME FOR ALL STRUCTURES.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
DEGASIFICATION COMPLEX NO. 1
TOP PLAN S-3
SWZ000CW.RVT
1/4" = 1'-0"
TOP PLAN (EL 208.00)
N
NOTE:
1. * INDICATES DIMENSION AND/OR INFORMATION TO BE
COORDINATED BY THE CONTRACTOR WITH THE
MANUFACTURER OF THE APPROVED EQUIPMENT PRIOR
TO FABRICATION AND CONSTRUCTION.
NOTE:
INDICATES HOUSEKEEPING OR EQUIPMENT PAD.
SEE DETAILS A/SD-2 AND B/SD-2.
COORDINATE SIZE WITH SUPPLIED EQUIPMENT.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
EL 200.50
1/2" EXPANSION JOINT
MATERIAL W/ SEALANT
CJ (TYP)
CJ W/ WS (TYP)
(TYP)
5' - 0"1' - 6"
1/2" EXPANSION JOINT
MATERIAL W/ SEALANT
LP EL 198.50
HP EL 198.58
SIDE MOUNTED AL
GUARDRAIL (TYP)
EL 196.00
BAFFLE WALL
CONCRETE COATING REFER
TO SPECIFICATION 099673.23
A
SD-4
#6@12" OC EW EF
#6@12" EF VERT WITH
MATCHING (DOWELS)
S-4
A
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1.
EQUIP PADB
SD-2
1' - 0" 4' - 3" 4' - 0" 3' - 6" 4' - 0" 4' - 3" 1' - 0"
1' - 0" (TYP)WALL
OPNG
AL LADDER
SIDE MOUNTED AL
GUARDRAIL (TYP)
EL 196.00
T/CONC
LP EL 208.00
D
SD-1
A
SD-4
12" MIN GRADED AGGREGATE
BASE. SEE FOUNDATION
PREPARATION NOTES, S-1.
(TYP)
5' - 0"
AL GUARDRAIL
W/ HANDRAIL
CS12 STRINGER
(TYP)
B
SD-5
B
SD-4
E
SD-5
E Q
U A
L R
IS
E
R S
/4
17 TREADS @ 11" = 15' - 7"3' - 0"
(M
IN
T/CONC
EL VARIES
T/CONC
EL 196.00
G
SD-2
CONC CURB
W
IT
H M
A T
C H
IN
G
C O
R N
E R
B A
R S
T
Y P
E F
H O
R
IZ
(M
IN
E
F H
O R
IZ
T/CONC
EL VARIES
#6@12 VERT
WITH MATCHING
DOWELS
EL 196.00
T/CONC
#6@8" OC EW T&B
#6@6" OC EW T&B
W
IT
H M
A T
C H
IN
G
C
O R
N E
R B
A R
S
T Y
P
12" MIN GRADED AGGREGATE BASE. SEE
FOUNDATION PREPARATION NOTES, S-1.
5' - 0"
C L A
S S
B L
A P
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
DEGASIFICATION COMPLEX NO. 1
SECTIONS AND DETAILS S-4
SWZ000CW.RVT
1/4" = 1'-0"S-2
1 SECTION
1/4" = 1'-0"S-2
2 SECTION
1/4" = 1'-0"S-3
3 SECTION
1/4" = 1'-0"S-2
4 SECTION
DETAIL
1/2" = 1'-0"
A
TYPICAL EXTERIOR WALL AND SLAB REINFORCEMENT
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
S-7
64' - 0"
S-7
(TYP)
1' - 0" 62' - 0" 1' - 0"
30' - 0"
CJ
C J
T/SLAB
EL 199.00
FLOOR DRAIN
(TYP 4 LOCATIONS)
SEE "P" DRAWINGS
HP EL 199.00 (TYP)
LP EL 198.94 (TYP)
L O
P E
O
SLOPE
SLOPE SLOPE
SLOPE
O
O P
E
MCJ
MCJ
MCJMCJ
MCJMCJMCJ MCJ
MCJMCJMCJ MCJ
(T Y
P
NOTE:
INDICATES HOUSEKEEPING OR EQUIPMENT PAD. SEE DETAILS A/SD-2 AND B/SD-2.
COORDINATE SIZE WITH SUPPLIED EQUIPMENT.
5 4
(TYP)
a = 4' - 5"
2e3e
3r
2n
2r 3r
(TYP)
a = 4' - 5" a 3e
2n
2e3e
3r
2n
2r 3r
3e
2n
DESIGN LOAD DATA - OPERATIONS BUILDING
SEISMIC:
BASIC SEISMIC-FORCE-RESISTING SYSTEM: INTERMEDIATE REINFORCED MASONRY SHEAR WALLS
DESIGN BASE SHEAR: Cs*W
SEISMIC RESPONSE COEFFICIENT: Cs: 0.035
RESPONSE MODIFICATION FACTOR: R: 3.5
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE PROCEDURE
WIND DESIGN DATA:
ENCLOSURE CLASSIFICATION: PARTIALLY OPEN
INTERNAL PRESSURE COEFFICIENT: +/- 0.18
REFER TO SHEET S-1 FOR DESIGN LOAD DATA THAT IS THE SAME FOR ALL STRUCTURES.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
OPERATIONS BUILDING
FOUNDATION PLAN S-5
SWZ000OB.RVT
1/4" = 1'-0"
FOUNDATION PLAN
N
NTS
C&C WALL PRESSURE ELEVATION
NTS
C&C ROOF PRESSURE PLAN
WIND PRESSURE (PSF) FOR COMPONENT AND CLADDING (Vult)
EFFECTIVE
WIND AREA
(SQ. FT.)
PRESSURE (+) / SUCTION (-) PRESSURE (+) / SUCTION (-) PRESSURE (+) / SUCTION (-) PRESSURE (+) / SUCTION (-) PRESSURE (+) / SUCTION (-) PRESSURE (+) / SUCTION (-) PRESSURE (+) / SUCTION (-)
ROOF (PSF) ROOF (PSF) ROOF (PSF) ROOF (PSF) ROOF (PSF) ROOF (PSF) WALL (PSF)
ZONE 1 ZONE 2e ZONE 2n ZONE 2r ZONE 3e ZONE 3r ZONE 4 ZONE 5
OH OH OH OH OH OH
< 10.00 24.2 -59.9 -68.7 24.2 -59.9 -68.7 24.2 -87.4 -96.2 24.2 -87.4 -96.2 24.2 -87.4 -113.0 24.2 -104.0 -132.0 29.7 -32.1 29.7 -39.6
10 TO 20 19.8 -59.9 -68.7 19.8 -59.9 -68.7 19.8 -87.4 -96.2 19.8 -87.4 -96.2 19.8 -87.4 -113.0 19.8 -104.0 -132.0 29.7 -32.1 29.7 -39.6
20 TO 50 17.8 -59.9 -68.7 17.8 -59.9 -68.7 17.8 -75.6 -83.8 17.8 -75.6 -83.8 17.8 -75.6 -97.3 17.8 -89.0 -111.0 28.4 -30.8 28.4 -36.9
50 TO 100 15.2 -36.4 -59.5 15.2 -36.4 -59.5 15.2 -59.9 -67.4 15.2 -59.9 -67.4 15.2 -59.9 -77.0 15.2 -69.3 -83.9 26.6 -29.1 26.6 -33.5
>= 100 13.2 -18.7 -52.3 13.2 -18.7 -52.3 13.2 -48.1 -55.0 13.2 -48.1 -55.0 13.2 -48.1 -61.6 13.2 -54.4 -63.2 25.3 -27.8 25.3 -30.8
TABLE NOTES:
1. TO CONVERT ULTIMATE WIND PRESSURES TO NOMINAL WIND PRESSURES, MULTIPLY THE VALUES BY 0.6.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
STEEL ROOF TRUSS
(TYP)
12" CMU WALL
(TYP)
METAL DECK
NOTE 2
S L O
P E
:1
S
L O
P E
:1
69' - 0"
O H
O H
2' - 6" 1' - 0" 62' - 0" 1' - 0"
OH
2' - 6"
1' - 0" TRUSSES @ 4'-0" = 60' - 0" 1' - 0"
8" CMU PARTITION
WALL (TYP)
SEE NOTE 7
SEE NOTE 7
12"x16" MIN CONCRETE
TIE BEAM
STEEL ROOF DECK
MASONRY WALL
TYPICAL VERTICAL
FILLED CELL
REINFORCING WITH
STANDARD HOOK AT
TOP END
TYPICAL BOND
BEAM REINFORCING
GROUT-FILLED
U-BLOCKS (TYP)
M
IN1
LAP SPLICE
CLASS 'B' TENSION
A
S-7
STEEL ROOF DECK
GALV L7x4x3/8 LLV CONT WITH 1/2"ø BENT BAR ANCHOR
BOLTS @ 24"OC WITH 2 3/4"
MINIMUM EMBED (2)-#5 (TYP)
GROUT FILLED
U-BLOCKS (TYP)
M
IN
DECK FASTENER
PER NOTES
EXTERIOR MASONRY WALL
T/MASONRY WALL
EL VARIES
(2)-#5 T&B
#4 TIES @12" OC
PRE-ENGINEERED COLD FORM STEEL TRUSS NOTES:
TRUSS MANUFACTURER TO DESIGN TRUSS IN CONFORMANCE WITH INTERNATIONAL BUILDING
CODE, 2018, WITH GEORGIA AMENDMENTS
1. ROOF SYSTEM:
ROOF SUPERIMPOSED LOADS (ASD):
DL (SUPERIMPOSED) = 10 PSF
DL (DECK + SUPERIMPOSED) = 20 PSF
SUPERIMPOSED LL (NON-REDUCIBLE) = 20 PSF
NET WIND UPLIFT = -28 PSF
SNOW LOAD = 0 PSF
2. ROOF DECK:
A. GALVANIZED DECK: 1.5B, 20 GAGE, G60 BY VULCRAFT OR APPROVED EQUAL.
B. SUPPORT FASTENERS:
#12 SCREWS** 36/4 PATTERN OR APPROVED EQUAL.
C. SIDELAP FASTENERS:
(3)-#12 SCREWS SIDELAP CONNECTOR PER SPAN OR APPROVED EQUAL.
** COORDINATE FASTENER MODEL WITH TRUSS CHORD THICKNESS.
ROOF FRAMING:
PRE-ENGINEERED COLD FORM STEEL TRUSSES BASED ON 4 FT SPACING.
TOP CHORD SUPERIMPOSED DL (ASD) 80 PLF
TOP CHORD SUPERIMPOSED LL (ASD) 80 PLF
BOTTOM CHORD SUPERIMPOSED DL (ASD) 40 PLF
3. PRE-ENGINEERED COLD FORMED STEEL TRUSS CALCULATIONS (INCLUDING CONNECTIONS
TO STRUCTURE) AND SHOP DRAWINGS, SHOWING ALL TEMPORARY AND PERMANENT
BRACING, AND SHEAR BRACES/TRUSSES/BLOCKING TO TRANSFER DIAPHRAGM LOADS
SHALL BE SIGNED AND SEALED BY A GEORGIA REGISTERED PROFESSIONAL ENGINEER AND
SUBMITTED TO ENGINEER FOR REVIEW.
4. REFER TO ARCHITECTURAL, HVAC, PLUMBING AND ELECTRICAL DRAWINGS FOR
ADDITIONAL EQUIPMENT TO BE SUPPORTED BY THE TRUSSES. TRUSS DESIGNER TO
USE ACTUAL WEIGHT OF EQUIPMENT PROVIDED.
5. COORDINATE LOCATION AND SIZE OF ROOF OPENINGS WITH ARCHITECTURAL,
HVAC AND PLUMBING DRAWINGS. FRAME ALL OPENINGS LARGER THAN 12" WITH
COLD FORM STEEL FRAMING DESIGNED BY TRUSS MANUFACTURER.
6. SEE DESIGN DRAWINGS AND STANDARD DETAILS FOR FURTHER DESIGN AND LOAD
REQUIREMENTS.
7. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATION SECTION 107316 FOR OVERHEAD
CANOPY AT ENTRANCE. CANOPY SHALL NOT BE CONSTRUCTED UNTIL DRAWINGS AND
REACTIONS HAVE BEEN SUBMITTED TO, REVIEWED AND APPROVED BY THE ENGINEER.
PROVIDE CONTINUOUS BOND BEAM OR VERTICAL FILLED CELL AT LOCATIONS OF
CANOPY ANCHORAGE. CANOPY'S ENGINEER SHALL PROVIDE ANCHORAGE
DESIGN. SUBMIT DESIGN CALCULATIONS, SIGNED AND SEALED BY PROFESSIONAL
ENGINEER REGISTERED IN GEORGIA.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
OPERATIONS BUILDING
ROOF PLAN S-6
SWZ000OB.RVT
1/4" = 1'-0"
ROOF PLAN
DETAIL
1/2" = 1'-0"
A
TYPICAL EXTERIOR WALL CAP BEAM
DETAIL
1" = 1'-0"
B
EXTERIOR WALL CONNECTION
N
NOTE:
1. REFER TO SD-3 FOR STANDARD MASONRY DETAILS
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
A
GRADE EL SEE CIVIL
T/ BEAM
EL 213.67
T/SLAB
EL 199.00 1
T/FOOTING
EL 196.00
METAL DECK
(T Y
P
(TYP)
3' - 0"
EL 211.67
T/ WALL
5' - 0"
1' - 9" 1' - 0" 1' - 9"
4' - 6"
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1
#5@12" OC, EW, T&B
(TYP)
#5@12" OC EW T&B
(TYP)
VAPOR BARRIER
SEE SPECIFICATION
SECTION 031000
#5@12" OC, EW, EF
(TYP)
1/2" EXPANSION JOINT
MATERIAL WITH SEALANT
TYPICAL VERTICAL
WALL REINFORCING
DAMPPROOFING
SEE SPECIFICATION
SECTION 071113
T/ SLAB
GRADE EL SEE CIVIL
4" GDOT #57 STONE
6oz NON-WOVEN
GEOTEXTILE FABRIC
EL 199.00
(2)-1/2"ø HEADED STUD ANCHORS x 8" LONG @8" OC, CENTERED IN CONC BEAM
1/2" THICK STEEL PLATE
COLD-FORMED STEEL TRUSS
AND CONNECTION TO PLATE BY
DELEGATE ENGINEER
2" 8" 2"
1' - 0"
C
O N
C B
E A
M 6
CONCRETE TIE BEAM
COLD-FORMED STEEL
TRUSS AND CONNECTION
BY DELEGATE ENGINEER
V2
PY
V1
NOTES:
1. TRUSS TO WALL CONNECTIONS TO BE DESIGNED FOR THE FOLLOWING
SIMULTANEOUS SERVICE LOADS:
LOAD COMB 1: V1=0.42 kip, V2=0.92 kip, PY=2.5 kip
2. LOADS FOR TYPICAL TRUSS @ 4' - 0" OC
3. TRUSS SYSTEM SHALL BE CAPABLE OF TRANSFERRING VERTICAL AND
HORIZONTAL LOADS ABOVE FROM DECK TO CMU WALL. TRUSS SYSTEM
BY DELEGATE ENGINEER SHALL INCLUDE SHEAR BRACES/TRUSSES TO
TRANSFER DIAPHRAGM LOADS.
4. TRUSS TO BEARING CONNECTION AS DETAILED ON THESE DRAWINGS
IS PRELIMINARY UNTIL FINAL REACTIONS FROM DELEGATE ENGINEER
ARE REVIEWED AND APPROVED BY THE ENGINEER OF RECORD.
B
2-#5 T&B
#4 TIES @ 12" OC
1'-4"H x 1'-0"W
CONC BEAM
VERTICAL FILLED
CELL REINFORCING
T/ CONC
HEEL HEIGHT ±8",
COORDINATE
WITH TRUSS MFR
EL 213.67
NOTE:
CONCRETE TIE BEAM CONSTRUCTION JOINTS TO MATCH
MASONRY CONTROL JOINT (MCJ) LOCATIONS.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
OPERATIONS BUILDING
SECTIONS AND DETAILS S-7
SWZ000OB.RVT
1/4" = 1'-0"S-5
1 SECTION
1/2" = 1'-0"S-5
2 SECTION
DETAIL
1 1/2" = 1'-0"
B
TYPICAL TRUSS BEARING AND ANCHORAGE
DETAIL
1" = 1'-0"
C
TRUSS CONNECTOR DESIGN FORCES
DETAIL
1" = 1'-0"
A
CONCRETE TIE BEAM
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
15' - 4"
MO
3' - 4" 16' - 4"
MO
6' - 4" 2' - 8"
TOP OF RIDGE 218.32
TOC EL 199.67
L1 L2
J2 J2M O
M O
J2 J2
FILLED CELL W/ #5@40"
OC VERTICAL
REINFORCING (TYP)
TYP VERTICAL
REINFORCING @
CORNERS (TYP)
12"X16" MIN
CONCRETE CAP BEAM
T/ FOOTING 196.00
GRADE EL SEE CIVIL
GROUT BOND BEAM W/ 2-#5
@48" OC MAX (TYP)
METAL DECK
MCJ
22' - 2"
BOND BEAM TO SUPPORT
CANOPY
L1
26' - 0"
MO
3' - 4" 34' - 8"
METAL DECK 12"X16" MIN
CONCRETE CAP BEAM
STEEL JOIST
T/ BEAM EL 213.67
GRADE EL SEE CIVIL
TOC EL 199.67
T/ FOOTING 196.00
M O
TYP VERTICAL
REINFORCING @
CORNERS (TYP)
FILLED CELL W/ #5@40"
OC VERTICAL
REINFORCING (TYP)
GROUT BOND BEAM W/ 2-#5
@48" OC MAX (TYP)
J1 J1
MCJ MCJ MCJ
MCJ
4' - 0" 19' - 4" 17' - 4" 19' - 4" 4' - 0"
METAL DECK
12"X16" MIN
CONCRETE CAP BEAMSTEEL JOIST
GRADE EL SEE CIVIL
TYP VERTICAL
REINFORCING @
CORNERS (TYP)
FILLED CELL W/ #5@40"
OC VERTICAL
REINFORCING (TYP)
GROUT BOND
BEAM W/ 2-#5@
48" OC MAX (TYP)
4' - 0"
MO
8' - 0"
SOLID GROUTED
4' - 0"
MO
7' - 4"
SOLID GROUTED
6' - 8"
MO
8' - 0" 26' - 0"
T/ BEAM EL 213.67
TOC EL 199.67
T/ FOOTING 196.00
M O
M O
L2
J2 J2
L2 L2
J2 J2
J2 J2
4' - 0" 19' - 4" 17' - 4" 19' - 4" 4' - 0"
BOND BEAM TO
SUPPORT CANOPY
WALL, SEE NOTE 1 WALL, SEE NOTE 1
L2
J2 J2
L2
J2 J2
FILLED CELL W/ #5@40"
OC VERTICAL
REINFORCING (TYP)
TYP VERTICAL
REINFORCING @
CORNERS (TYP)
12"X16" MIN
CONCRETE CAP BEAM
GRADE EL SEE CIVIL
GROUT BOND BEAM W/ 2-#5
@48" OC MAX (TYP)
METAL DECK
M O
M O
9' - 4"
MO
6' - 4" 19' - 0"
MO
5' - 4" 4' - 0"
TOC EL 199.67
TOP OF RIDGE 218.36
T/ FOOTING 196.00
MCJ
22'-2"
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
OPERATIONS BUILDING
MASONRY ELEVATIONS S-8
SWZ000OB.RVT
3/16" = 1'-0"
NORTH ELEVATION FOR MAIN BUILDING
3/16" = 1'-0"
WEST ELEVATION FOR MAIN BUILDING
3/16" = 1'-0"
EAST ELEVATION FOR MAIN BUILDING
3/16" = 1'-0"
SOUTH ELEVATION FOR MAIN BUILDING
NOTE:
1. PROVIDE FULLY GROUTED CELLS AND VERTICAL REINFORCEMENT
FOR ALL CELLS ON THIS WALL ONLY. JAMB, LINTEL, OPENING
REINFORCEMENT IS STILL REQUIRED PER DETAILS ON SD -3
LEGEND
LINTEL TYPE, DETAL F/SD-3
JAMB TYPE, DETAIL H/SD-3 & K/SD-3
OPENING LABEL
LX
JX
X structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
S-9
CONCRETE
ENCASEMENT
(TYP)
1/2" EXPANSION
JOINT MATERIAL
WITH SEALANT (TYP)
C
SD-2
(TYP)
3' - 8" *
(T Y
P
S L O
P E
HP 198.57
LP 198.40
CONCRETE
PUMP CAN
1/2" EXPANSION
JOINT MATERIAL
WITH SEALANT (TYP)
1' - 0" 1' - 0" * 1' - 8" * 1' - 0" *
1' - 0"
GRADE
EL SEE CIVIL
T/SLAB
EL VARIES
T/SLAB
PIPE ENCASEMENT
C
SD-2
F
SD-2
#5@12" TOP MAT, EW
#5@12" EF, EW
#5@12" T&B, EW
5' - 8"
M
IN
5' - 0"
EL 188.28 *
(M
IN
T/CONC
EL 200.45 *
12" MIN GRADE AGGREGATE
BASE. SEE FOUNDATION
PREPARATION NOTES, S-1
12" MIN GRADE AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
HIGH SERVICE PUMP STATION
PLAN AND SECTION S-9
SWZ000HS.RVT
1/4" = 1'-0"
PLAN
N
_ 3/8" = 1'-0"
1 SECTION
NOTES:
1. * INDICATES DIMENSIONS AND/OR INFORMATION TO BE COORDINATED BY THE CONTRACTOR
WITH AN APPROVED EQUIPMENT MANUFACTURER PRIOR TO FABRICATION AND
CONSTRUCTION.
2. PUMP ANCHORAGE SHALL BE DESIGNED BY A DELEGATE ENGINEER REGISTERED IN THE
STATED OF GEORGIA.
3. CONCRETE PIPE SUPPORTS NOT SHOWN. REFER TO MECHANICAL DRAWINGS.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
S-12
S-12
4' - 6" 11' - 2" 6' - 0" 11' - 2" 6' - 0" 6' - 11" 1' - 6" 3' - 0" 1' - 6" 6' - 11" 6' - 0" 4' - 8" 13' - 8"
1' - 2" 23' - 0" 20' - 0" 20' - 0" 20' - 0" 1' - 2"
BOT OF TRENCH
HP EL 197.74 (TYP)
BOT OF TRENCH
LP EL 197.26 (TYP)
CURB AROUND PERIMETER
T/ CURB
FRP GRTG (TYP)
85' - 4"
1 2 3 5
A
B
2' - 5" 6"
8" 6" 83' - 0" 6" 8"
(TYP)
2' - 6"
(T Y
P
(TYP)
2' - 6"
EL 200.00 (TYP)
CHEMICAL RESISTANT COATING
@ TRENCH (TYP)
S-12
S-12
C
S-12
A
SLOPE
3' - 6"
HP EL 199.67
LP EL 199.50
HP EL 199.67
LP EL 199.50 LP EL 199.50
HP EL 199.67
LP EL 199.50
LP EL 199.50
HP EL 199.67
LP EL 199.50
SLOPE SLOPESLOPE SLOPE
SLOPE SLOPE
3' - 0" 2' - 10" 10' - 0" 4' - 3" 3' - 0" 3' - 0" 7' - 10" 3' - 0"
2'-0" THK SLAB
(AT LP EL 199.5)
(TYP)
(TYP)
S-12
B
(TYP OF 4)
BRACED BAY BRACED BAY
NOTE:
INDICATES HOUSEKEEPING OR EQUIPMENT PAD. SEE DETAILS A/SD-2 AND B/SD-2.
COORDINATE SIZE WITH SUPPLIED EQUIPMENT.
DESIGN LOAD DATA - CHEMICAL CANOPY
SUPERIMPOSED DEAD LOAD: 10 PSF
ALL LOADS FROM EQUIPMENT, PIPING AND PIPE SUPPORTS, CONDUIT AND MISCELLANEOUS ITEMS LOCATED ON THE CANOPY OR SUSPENDED FROM THE ROOF ARE TO BE VERIFIED WITH APPROVED LAYOUTS AND SUBMITTALS BY THE CONTRACTOR AND PROVIDED TO THE CANOPY MANUFACTURER. THE
REQUIRED LOADS SHALL BE SUBMITTED WITH THE CANOPY CALCULATIONS.
ROOF LIVE LOAD: 20 PSF
WIND DESIGN DATA:
ENCLOSURE CLASSIFICATION: OPEN
INTERNAL PRESSURE COEFFICIENT: NOT APPLICABLE
REFER TO SHEET S-1 FOR DESIGN LOAD DATA THAT IS THE SAME FOR ALL STRUCTURES.
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282N. SHEKAR
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
CHEMICAL STORAGE AREA
FOUNDATION PLAN S-10
SWZ001CH.rvt
1/4" = 1'-0"
FOUNDATION PLAN
N
NOTES:
1. * INDICATES DIMENSIONS AND/OR INFORMATION TO BE COORDINATED BY THE CONTRACTOR WITH THE
MANUFACTURER OF THE APPROVED EQUIPMENT PRIOR TO FABRICATION AND CONSTRUCTION.
2. PRE ENGINEERED STRUCTURAL STEEL FOR CANOPY SHALL BE GALVANIZED UNO.
3. STRUCTURE SHALL NOT BE FABRICATED OR CONSTRUCTED UNTIL THE SUBMITTAL OF THE PRE- ENGINEERED BUILDING ANCHOR BOLT LOCATIONS AND FOUNDATION REACTIONS HAVE BEEN REVIEWED AND ADJUSTMENTS TO THE STRUCTURE HAVE BEEN COMPLETED IF REQUIRED, BY THE ENGINEER.
4. THE STEEL CANOPY COMPONENTS SHALL BE DESIGNED BY A DELEGATE ENGINEER. SEE SPECIFICATION 133419.
5. PRIOR TO SUBMITTING SHOP DRAWINGS TO ENGINEER FOR REVIEW AND APPROVAL, COORDINATE THE FRP TANK SIZE AND STEEL CANOPY VERTICAL AND HORIZONTAL CLEARANCES WITH THE RESPECTIVE
MANUFACTURERS TO FACILITATE INSTALLATION AND REMOVAL OF THE TANKS.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
S-12
S-12
1 2 3 5
A
B
ROOF PURLINS PER
MANUFACTURER NOT
SHOWN FOR CLARITY
S L O
P E
85' - 0"
1' - 0" 23' - 0" 20' - 0" 40' - 0" 1' - 0"
ROOF EDGE (TYP)
STEEL FRAME BY METAL
BUILDING MANUFACTURER
METAL DECK BY METAL
BUILDING MANUFACTURER.
CROSS BRACING, SIZE
AND LOCATION BY
METAL BUILDING
MANUFACTURER.
1 2 3123 a a a a= 3' - 0" (TYP)
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282N. SHEKAR
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
CHEMICAL STORAGE AREA
ROOF PLAN S-11
SWZ001CH.rvt
1/4" = 1'-0"
ROOF PLAN
N
NTS
C&C WIND PRESSURE DIAGRAM
WIND PRESSURE (PSF) FOR COMPONENT AND CLADDING (Vult)
EFFECTIVE WIND
AREA (SQ. FT.)
PRESSURE (+) /SUCTION (-)
ROOF (PSF)
1 (Clear) 1 (Obst.) 2 (Clear) 2 (Obst.) 3 (Clear) 3 (Obst.)
< 10.00 38.5 -34.2 18.3 -40.2 57.7 -51.7 27.9 -61.1 77.0 -102.0 36.5 -120.0
10 TO 20 38.5 -34.2 18.3 -40.2 57.7 -51.7 27.9 -61.1 57.7 -51.7 27.9 -61.1
20 TO 50 38.5 -34.2 18.3 -40.2 57.7 -51.7 27.9 -61.1 57.7 -51.7 27.9 -61.1
50 TO 100 38.5 -34.2 18.3 -40.2 38.5 -34.2 18.3 -40.2 38.5 -34.2 18.3 -40.2
>= 100 38.5 -34.2 18.3 -40.2 38.5 -34.2 18.3 -40.2 38.5 -34.2 18.3 -40.2
TABLE NOTES:
1. FOR ASD PRESSURES, APPLY A FACTOR OF 0.6 TO THE LISTED PRESSURES CORRESPONDING TO Vult.
2. Obst. - OBSTRUCTURED WIND FLOW.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
8"
8"
C L
R
GALV STEEL FRAME AND BASE
PLATE BY METAL BUILDING
MANUFACTURER
ROOF PURLINS BY METAL
BUILDING MANUFACTURER
(TYP)
METAL DECK BY METAL
BUILDING MANUFACTURER
SODIUM HYPOCHLORITE TANK
(SEE "M" DRAWINGS)
PROVIDE VAPOR RETARDER
PER SPECIFICATION 033000
(TYP)
A B
#6@12” T&B, EW
EL 200.00
T/CURB
T/GRATING
EL 199.50
HP EL 197.74
LP EL 197.26
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1.
(TYP)
5' - 0"
TOS EL 222.50
BOC EL 196.25
T/EQUIP PAD EL 200.17
1 2 3 54
CONCRETE COATING
REFER TO SPECIFICATION 099673.33
T/CURB
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1.
(TYP)
5' - 0"
EL 200.00
LP EL 199.50
LP EL 199.50
#6@12" T&B, EW
LP EL 199.50
LP EL 199.50 LP EL 199.50
LP EL 199.50
(T Y
P
M
IN
HP EL 199.67 HP EL 199.67
HP EL 199.67 HP EL 199.67
(M
IN
L
P
(TYP)
1' - 0"
PEDESTAL
COLUMN
2-#4@ TIE
SETS IN TOP 6"
2'' NON-SHRINK
GROUT
REFER SECTION 1 FOR
SLAB REINF
8-#7
COL
B 3 "3
3"3"
CONCRETE
BASEPLATE BY
CANOPY ENGINEER
(4)-3/4” ⌀ F1554, GR36 STANDARD
HEX HEAD ANCHOR BOLTS WITH
HEX NUTS AND GRADE A WASHERS
EMBEDDED 12” MINIMUM INTO
CONCRETE SET IN STANDARD HOLE
IN BASEPLATE (TYP)
COL
COL
B
1' - 3" 1' - 3"
WALL
REINFORCING
(8)-#7 SET OF 3-#4 TIES. ALTERNATE
POSITION OF HOOKS FOR
SUCCESSIVE CROSS TIE SETS
COL
COL
B
(8)-#7
WALL
REINFORCING
SET OF 3-#4 TIES. ALTERNATE
POSITION OF HOOKS FOR
SUCCESSIVE CROSS TIE SETS
2' - 0" 1' - 2"
COL
COL
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282N. SHEKAR
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
CHEMICAL STORAGE AREA
SECTIONS AND DETAILS S-12
SWZ001CH.rvt
1/4" = 1'-0"S-10
2 SECTION
1/4" = 1'-0"S-10
1 SECTION
3/4" = 1'-0"S-10
3 SECTION
DETAIL
1/2" = 1'-0"
C
COLUMN ANCHOR BOLTS
DETAIL
1/2" = 1'-0"
A
PIERS
NOTES:
1. * COORDINATE CANOPY HEIGHT WITH SELECTED STORAGE TANKS.
DETAIL
1/2" = 1'-0"
B
CORNER PIERS
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
S-13
1' - 6" 20' - 0" 1' - 6"
23' - 0"
1' - 0" 18' - 0" 1' - 0"
1'-6"X1'X6"X1'-6" SUMP
AL LADDER
SLOPE
S L O
P E
PIPE OPENING REFER
TO PROCESS DRAWINGS
T/SLAB
EL VARIES
LP EL 191.33
HP EL 191.50
4' - 0"
M
IN
GRADE EL
SEE CIVIL
T/WALL
EL 198.00
PIPE OPENING REFER TO
PROCESS DRAWINGS
#6@12” T&B
D
SD-1
#6@12” EW, EF WITH
MATCHING DOWELS
AND CORNER BARS (TYP)
L A
P S
P L
IC
E
C L A
S S
B T
E N
S
IO
N
T/SLAB
EL VARIES
3/8" THK AL STIFFENED
COVER PLATE
HP EL 191.50
LP EL 191.33
1'-4"X1'X4"X1'-4" SUMP
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1
S-13
1' - 0" 18' - 0" 1' - 0"
4' - 6" 4' - 6" 4' - 6" 4' - 6"
A W x .3
A W x .3
A W x .3
3/8" THICK AL STIFFENED
COVER PLATE
F
SD-4
EL 198.00
T /A
L E
L
.9
T /A
L E
L
.9
T /A
L E
L
.9
T/COVER PLATE
(TYP, UNO)
AW8x7.08
A W x .0
3'-0" SQ REMOVABLE AL
STIFFENED COVER PLATE
(TYP OF 2 LOCATIONS)
F
SD-5
SIM (TYP)
A
- (TYP)
A W x .0
AW8x7.08
/4
/2
"AW9X8.36
(2)-5/8" DIA BOLTS
TOP OF
CONC
L4X4X 3/8 CLIP ANGLE
EITHER SIDE, SAME
MATERIAL AS BEAM
DRILL AND EPOXY (2)-5/8" DIA 316 SS
THREADED RODS WITH HILTI HIT-RE
500 V3 AND 6" EMBED.
COVER PLATE
3/4"
2 1/2"
CUT BOTTOM FLANGE
WHERE REQUIRED
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282Y. MOHAMMED
M. TRAPP
K. FRANCOFORTE
R. KEEFE
J. BOGGS
CHEMICAL INJECTION VAULT
PLANS AND SECTION S-13
SWZ000CV.RVT
3/8" = 1'-0"
FOUNDATION PLAN
N
_ 1/2" = 1'-0"
1 SECTION
3/8" = 1'-0"
TOP PLAN
N
_ 3/4" = 1'-0"
3 DETAIL
NOTES:
1. AW: INDICATES ALUMINUM ASSOCIATION STANDARD
W-SHAPES (FORMERLY I SHAPES).
2. CONCRETE PIPE SUPPORTS NOT SHOWN. REFER TO
MECHANICAL DRAWINGS.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
* 68' - 6"
T/14" CONC SLAB
EL 199.00
REINF: #6@12" EW, T&B
S-14
T/30" CONC SLAB
EL 198.50
REINF: #6@12" OC EW T&B
* 29' - 2"
S-14
S-14
F
SD-2
16' - 3"
T/12" CONC SLAB
EL 197.50
REINF: #6@12" EW, T&B
D
SD-1
(SIM)
1/2" EXPANSION
JOINT MATERIAL
WITH SEALANT
S-14
F
SD-2
16' - 3"
T/12" CONC SLAB
EL 201.80
REINF: #6@12" EW, T&B
D
SD-1
(SIM)
1/2" EXPANSION
JOINT MATERIAL
WITH SEALANT
GRADE EL
SEE CIVIL
B
SD-2
F
SD-2
(TYP)
(M
IN
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1
PIPE PENETRATION
SEE "M" DRAWINGS
D
SD-1 (TYP)
F
SD-2
T/12" CONC SLAB
EL 199.00
REINF: #6@12" EW, T&B
T/30" CONC SLAB
7' - 0"
EL 199.00
REINF: #6@12" EW, T&B
S-14
(SIM)
GRADE EL
SEE CIVIL
(M
IN
12" MIN GRADED AGGREGATE BASE.
SEE FOUNDATION PREPARATION
NOTES, S-1
A B C D E F G H
C
D M
S M
IT
H
A L
L R
IG
H
T S
R E
S E
R V
E D
R
E U
S E
O F
D O
C U
M E
N T
S T
H E
E S
E D
O C
U M
E N
T S
A N
D D
E S
IG
N
S P
R O
V
ID
E D
B Y
P R
O F
E S
S
IO
N A
L S
E R
V
IC
E
IN
C O
R P
O R
A T
E D
H E
R E
IN
A
R E
T H
E P
R O
P E
R T
Y O
F C
D M
S M
IT
H
A N
D A
R E
N O
T T
O B
E U
S E
R
IN
W H
O L
E O
R P
A R
T F
O R
A N
Y O
T H
E R
P R
O J E
C T
W
IT
H O
U T
T H
E W
R
IT
T E
N A
U T
H O
R
IZ
A T
IO
N
O F
C D
M S
M
IT
H
DATE:
APPROVED BY:
CROSS CHK'D BY:
SHEET CHK'D BY:
DRAWN BY:
DESIGNED BY:
JULY 2025
4651 Salsbury Road, Suite 420 Jacksonville, FL 32256 Tel: (904) 731-7109 COA No. PEF000106; EXP. DATE 06/30/2026
PROJECT NO.
FILE NAME:
SHEET NO.
REMARKSCHKDDRWNDATE
REV.
NO.
CITY OF VALDOSTA, GA
VALDOSTA WTP NO. 2
AND PRODUCTION WELLS
ISSUED FOR BID
20790-289282M. TRAPP
B. BENNETT
K. FRANCOFORTE
R. KEEFE
J. BOGGS
MISCELLANEOUS SLAB
PLANS, SECTIONS AND DETAILS S-14
SWZ000CP.RVT
1/4" = 1'-0"
CARBON DIOXIDE STORAGE SLAB
1/4" = 1'-0"
GENERATOR PAD
1/4" = 1'-0"
WELL NO. 1 PAD
1/4" = 1'-0"
WELL NO. 2 PAD
NN
NOTE:
* INDICATED DIMENSIONS AND/OR INFORMATION IS PRELIMINARY
AND IS TO BE COORDINATED BY THE CONTRACTOR WITH THE
MANUFACTURER OF THE APPROVED EQUIPMENT PRIOR TO
FABRICATION AND CONSTRUCTION.
_ 3/8" = 1'-0"
1 SECTION
1/4" = 1'-0"
FLOW METER PAD
N
N
N
1" = 1'-0"
PRESSURIZED SOLUTION FEED SYSTEM
_ 1/4" = 1'-0"
2 SECTION
N
NOTE:
CONCRETE PIPE SUPPORTS NOT SHOWN.
REFER TO MECHANICAL DRAWINGS.
structural
No. 001701
RE
G I STERED
ENG I NEER
G
EO
RG IA
J U
STANDARD DETAIL NOTES:
1. BASIC SLAB/WALL/BEAM REINFORCEMENT AS SHOWN ON DESIGN DRAWINGS.
2. SIZE AND SPACING OF BAR TO MATCH WALL/BEAM REINFORCEMENT AS SHOWN ON DESIGN DRAWINGS.
3. FOR ADDITIONAL BARS AT CORNERS AND INTERSECTIONS, SEE DESIGN DRAWINGS.
4. FOR DOWEL SIZE AND SPACING, SEE DESIGN DRAWINGS.
5. FOR WALLS, TERMINATE WATERSTOP AND KEYWAY 8" BELOW TOP OF WALL.
6. FOR SLABS-ON-GRADE, OMIT SEALANT ON BOTTOM OF SLAB AND EXTEND PRE-MOLDED JOINT MATERIAL
TO BOTTOM.
SEE NOTE 1
TENSION LAP
NOTE: SECOND POUR SHALL BE 24 HOURS MINIMUM AFTER INITIAL POUR.
CONTINUOUS
REINFORCING
OR LAP AS SHOWN
T
6" PVC WATERSTOP. BOND TO
INTERSECTING WATERSTOP.
TERMINATE WATERSTOP 8"
BELOW TOP OF WALL
(TYP)
3" CLEAR
INITIAL CAST
ROUGHEN JOINT
1/4" FULL AMPLITUDE
AS SPECIFIED
CASE 1
CLASS "B"
T /2
T /2
S E
E T
A B
L
E SEE NOTES 2 AND 3
SEE NOTE 1SEE NOTES 2 AND 3 SEE NOTE 1
SEE NOTES 2 AND 3
S E
E T
A B
L E
#5 3'-0"
#6 3'-8"
#7 4'-6"
#8 6'-0"
#9 7'-6"
CORNER REINFORCING INTERSECTION REINFORCING
BAR
SIZE
LAP
LENGTH
NOTES:
1. SAWCUT WIDTH 1/8" MIN - 1/4" MAX.
2. SAWCUT DEPTH 1" MIN - 1-1/2" MAX.
3. FILL JOINT TO FULL DEPTH WITH SELF-
LEVELING SEALANT. USE BACKER ROD OR
BOND BREAKER TAPE PER MANUFACTURER.
SKEWED CORNERCORNER INTERSECTION
12" EXTENSION
UNO
SEE NOTE 1
SEE NOTES
2 AND 3
SEE NOTES
2 AND 3
SEE NOTE 1
TENSION LAP SPLICE
CLASS "B"
L A
P S
P L
IC
E
C L
A S
S
B
T E
N S
IO
N
TENSION LAP SPLICE
CLASS "B"
L A
P S
P L
IC
E
C L
A S
S
B
T E
N S
IO
N
U N
O O
N D
E S
IG
D
A
W
IN
G S
U N
O O
N D
E S
IG
A
W
IN
G S
8"
SEE NOTE 3
SEE NOTE 1
SEE NOTES 2 AND 3
ROUGHEN JOINT
1/4" FULL AMPLITUDE
AS SPECIFIED
6" PVC WATERSTOP
SEE NOTE 4
4" STARTER
WALL
C L A
S S
B
D O
W E
L P
R O
J E
C T
IO
N
T E
N S
IO
N
L A
P S
P L
IC
E U
N O
ROUGHEN JOINT
1/4" FULL AMPLITUDE
AS SPECIFIED
SEE NOTE 4
C L A
S S
B
D O
W E
L P
R O
J E
C T
IO
N
T E
N S
IO
N
L A
P S
P L
IC
E U
N O
WITHOUT WATERSTOP WITH WATERSTOP
SEE NOTE 1 SEE NOTE 1
NOTES:
1. STARTER WALL MAY BE ELIMINATED AT JOINTS WITHOUT WATERSTOP AT CONTRACTOR'S OPTION.
2. PROVIDE…