VICINITY MAP - (COLUMBIA, MO)

TRUE

NORTH

PLAN

NORTH

VICINITY MAP - (HARRY S. TRUMAN MEMORIAL VETERANS' HOSPITAL)

TRUE

NORTH

PLAN

NORTH

PROJECT

LOCATION

COVER IMAGE

ABBREVIATIONS

PROJ(D)

PLBG

PLYWD

PREFIN

RAD(R)

RESIL

REINF

REQ'D

SECT

SHWR

SPECS

REFRIG

GALVANIZEDGALVBMRK BENCHMARK

CONCRETE

MASONRY UNIT

CEILINGCLG

CLR

CMU

COL

CLO

CLEAR/CLEARANCE

COLUMN

CLOSET

CAB

CJ

CC

CB

BW

CL

BOC

BRZ

BRK

BO

BRG

BUR

BTM

BS

BUILT-UP ROOF

CENTER TO CENTER

CHALKBOARD

BOTTOM OF WALL

CENTER LINE

CONTROL JOINT/

CONSTRUCTION JOINT

CABINET

BACK OF CURB

BOTH SIDES

BOTTOM OF

BRONZE

BRICK

BEARING

BOTTOM

FOUNDATION

FLOOR DRAIN

FIRE EXTINGUISHER

FIRE

EXTINGUISHER

CABINET

FE

FEC

FDN

FD

EAST

EACH

EQUIPMENT

EXPOSED

EACH WAY

EXISTING

ELECTRICAL

EXTERIOR INSULATION

FINISH SYSTEM

ELEVATION/ELEVATOR

EXPANSION JOINT

EXISTING GRADE

ELECTRICAL CONTRACTOR

EXTERIOR

ETHYLENE PROPYLENE

DIENE TERPOLYMER

ELEV

EQUIP

EW

EPDM

EXP

EXIST

EXT

E

EA

EC

EG

EIFS

EJ

ELEC

INSULATION

INTERIOR

INSIDE DIAMETER

INSUL

IN(")

INT

ID

INCH

GRAB BAR

GENERAL CONTRACTOR

GYPSUM

GLASS/GLAZING

HOLLOW METAL

HIGH PRESSURE

DECORATIVE LAMINATE

HORIZONTAL

HARDWARE

HARDWOOD

HOSE BIB

HOT WATER

HEATING, VENTILATING

& AIR CONDITIONING

HDWR

HM

HORZ

HT

HPDL

HVAC

HW

HEIGHT

GB

GL

GRD

GYP

GC

HDWD

HB

GRADE

PART

PLAS

OVHD

PARTITION

PLASTER

OVERHEAD

SRT

SS

SQ

MISCELLANEOUS

MASONRY OPENING

NOT IN CONTRACT

NOT APPLICABLE

OUTSIDE DIAMETER

NUMBERNO(#)

NTS

OC

OA

NOM

OFF

OPNG

OD

ON CENTER

OVERALL

NOMINAL

NOT TO SCALE

OFFICE

OPENING

MISC

N

MO

MULL

MTL

NIC

NA

NORTH

MULLION

METAL

SHT

SF

SB

SND

SIM

S

RM

ROW

RO

SAT

SAN

ARCHITECT/

ARCHITECTURAL

AB ANCHOR BOLT

APPROX

BLDG

BD

ARCH

BM

BLK

ADJ

AFF

AC

ACCU

ALUM

ANOD

ALT

APPROXIMATE

BLOCK/BLOCKING

AT

BOARD

BEAM

BUILDING

AIR COOLED

CONDENSING UNIT

ABOVE FINISHED FLOOR

ADJUSTABLE

ALTERNATE

ANODIZED

ACOUSTICAL

ALUMINUM

A/C AIR CONDITIONING

PLUS OR MINUS

CONSTRUCTIONCONST

COURSE

CERAMIC TILE

CONTINUOUS

CARPET

CORRIDOR

DIAMETER

DOOR

DOWN

DITTO

DIMENSION

DOUBLE

DRINKING FOUNTAIN

DETAIL

DRAWING

DOWNSPOUT

DIA

DR

DS

DN

DO

DIM

DTL

DWG

CRS

CT

CONT

CORR

CPT

DBL

DF

CONFERENCE

CONCRETE

CONF

CONC

FINISHFIN

FLUORESCENT

FLOW LINE

FOLDING

FIELD VERIFY

FURNACE

FOOTING

FIRE RETARDANT

FOOT SCRAPER

FIBERGLASS

REINFORCED PLASTIC

FV

FT(')

FURR

FURN

FTG

G

GA

FOOT

FURRING

GAS

GAUGE

FRP

FLR

FLDG

FL

FRT

FS

FLUOR

FLOOR

FINISH GRADE

FINISH FLOOR

FG

FF

JOISTJST

LOW VOLUME CHANGE

MASONRYMAS

MANUF

MATL

MAX

MECH

MEMB

MH

MIN

MIRR

MANUFACTURER

MATERIAL

MECHANICAL

MEMBRANE

MAXIMUM

MINIMUM

MANHOLE

MIRROR

LDR

LF

LAV

LAM

LVC

LOCN

LINEAL FEET

LADDER

LAVATORY

LAMINATE

LOCATION

REF

R

RAG

RD

PT

PR

QT

PTD

JT

JAN JANITOR

JOINT

PL

UNDER CABINET LIGHTREQUIRED

PHYSICAL THERAPY

RESPIRATORY CARE

SURGICAL INTENSIVE CARE UNIT

STUDDED RUBBER TILE

STAINLESS STEEL

SQUARE

SPECIFICATIONS

YD

SUSPENDED

ACOUSTICAL TILE

SIMILAR

SANITARY NAPKIN

DISPENSER

SECTION

SHOWER

SHEET

SQUARE FEET

SPLASH BLOCK

RESILIENT

SOUTH

SANITARY

RIGHT OF WAY

ROUGH OPENING

ROOM

WD

WNDW

WH

WNSCT

WC

WT

WWF

WP

VCT

VWC

VEST

VERT

W W/ W/O

YARD

WATERPROOFING

/WATERPROOF

WELDED WIRE FABRIC

WATER HEATER

WATER CLOSET

WINDOW

WOOD

WAINSCOT

WEIGHT

VINYL COMPOSITION TILE

VINYL WALL COVERING

VERTICAL

VESTIBULE

WEST

WITH

WITH OUT

RC

SICU

CENTRAL STERILE

LONG TERM CARE

INTENSIVE CARE UNIT

OCCUPATIONAL THERAPY

MAGNETIC RESONANCE IMAGING

POST ANESTHETIC CARE UNIT

MEDICAL INTENSIVE CARE UNIT

LABOR-DELIVERY-RECOVERY-POST PARTUM

OPERATING ROOM

FOR MEDICAL

FACILITIES ONLY

EMERGENCY ROOM

COMPUTED TOMOGRAPHY

STORPLUMBING

PROJECT/(PROJECTED)

REFER/REFERENCE

ROOF DRAIN

RADIUS

RETURN AIR GRILLE

REINFORCING

REFRIGERATOR

RISER

PRESSURE TREATED

PAINTED

QUARRY TILE

PLYWOOD

PREFINISHED

PAIR

TLT

TV

TW

TOC

TPH

TO

TYP

UCL

T&B T

SUSP

STRUCT

TEL

TB

T&G

PLATE/PLASTIC/

PROPERTY LINE STL

STD

STORAGE

TOILET PAPER HOLDER

TOP OF CURB

TOILET

TELEVISION

TOP OF

TYPICAL

TOP OF WALL

TONGUE & GROOVE

TOP & BOTTOM

STRUCTURE/STRUCTURAL

TREAD

TELEPHONE

TACKBOARD

SUSPENDED

ICU

OR

LDRP

MRI

MICU

LTC

PT

PACU

OT

CS

CT

ER

STEEL

STANDARD

UNLESS NOTED OTHERWISEUNO

CUT STONE

STEEL

PLYWOOD

FINISH WOOD

CONT WD FRAMING

WOOD BLOCKING

MATERIAL SYMBOLS

LVC FILL

GRANULAR FILL

CONCRETE MASONRY

FACE BRICK

CONCRETE

EARTH

EXISTING CONSTRUCTION

ASPHALT

GLASS

RIGID OR TAPERED

INSULATION, EIFS

BATT INSULATION

GYPSUM BOARD

DRAWING SYMBOLS

95.00

TOC

98.5

TOC

98.5 E

B

NEW ELEVATION

ELEVATION DESCRIPTION

EXISTING CONTOUR

NEW CONTOUR

TEST BORING (SITE PLANS ONLY)

EXISTING ELEVATION

ELEVATION DESCRIPTION

PROPERTY LINE

/1 A101

/1 A101 MATCHLINE

SHT. REFERENCE

ELEVATION DATUM

(SECTIONS, ELEVATIONS ONLY)

BUILDING SECTION

WALL SECTION

DETAIL DRAWING

BUILDING ELEVATION

AI-201 INTERIOR ELEVATION

A100

WINDOW ID TAG

DOOR NUMBER

ROOM NAME

ROOM NAME & NUMBER

PARTITION SYMBOL

1 REVISION TAG

COLUMN LINE GRID

EQUIPMENT NUMBER

SITE PLAN NOTES

DEMOLITION PLAN NOTES

PRECAST CONCRETE

WALL PANEL TAG

XXX

AE-101

A-4 ALTERNATE TAG

PT-XX PAINT COLOR TAG

# PLAN NOTES &

ROOF PLAN NOTES

AE-201

AE-301

AE-310

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T (3

/8"

1' -0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T (1

/2"

1' -0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T

(3 /4"

1'

-0

6"

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

6"

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

6"

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

6"

32 4 5 61

MEP:

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :02

:55 P

M

GI000

COVER SHEET

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

HARRY S. TRUMAN MEMORIAL VETERANS' HOSPITAL

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

VA #589A4-24-103

06/25/2025

BID SET

SGA #231997

VA #589A4-24-103BID SET

SHEET INDEX - FEDERAL

01 - GENERAL INFORMATION

GI000 COVER SHEET

GI003 LIFE SAFETY CODE REVIEW

GI011 ACCESSIBILITY DETAILS

GI101 LIFE SAFETY PLAN - 1ST FLOOR

GI121 FACILITY PLAN

GI140 PHASING PLANS - BASEMENT FLOOR

GI141 PHASING PLANS - 1ST FLOOR

02 - HAZARDOUS MATERIALS

HA100 HAZARDOUS ASBESTOS PLAN - BASEMENT FLOOR

HA101 HAZARDOUS ASBESTOS PLAN - 1ST FLOOR

03 - STRUCTURAL

S000 DETAILS & PLANS

06 - ARCHITECTURAL DEMOLITION

AD100 DEMOLITION RCP - BASEMENT FLOOR - ABOVE CEILING

AD101 DEMOLITION PLAN - 1ST FLOOR

AD111 DEMOLITION RCP - 1ST FLOOR

07 - ARCHITECTURAL ELEMENTS

AE101 ARCHITECTURAL FLOOR PLAN - 1ST FLOOR

AE110 REFLECTED CEILING PLAN - BASEMENT FLOOR

AE111 REFLECTED CEILING PLAN - 1ST FLOOR

AE301 BUILDING SECTIONS

AE311 WALL SECTIONS

AE401 ENLARGED PLANS & ELEVATIONS

AE501 ARCHITECTURAL DETAILS

AE601 ARCHITECTURAL SCHEDULES & ASSEMBLIES

AE911 RENDERED IMAGES

08 - ARCHITECTURAL INTERIORS

AI101 FINISH PLAN & SCHEDULE - 1ST FLOOR

AI111 EQUIPMENT PLAN & SCHEDULE - 1ST FLOOR

AI121 WALL PROTECTION PLAN - 1ST FLOOR

AI131 SIGNAGE PLAN - 1ST FLOOR

AI401 INTERIOR ELEVATIONS

AI402 INTERIOR ELEVATIONS

AI511 CASEWORK DETAILS

09 - FIRE SUPPRESSION AND ALARM

FG101 FIRE SUPPRESSION SYMBOLS LEGEND AND GENERAL NOTES

FD101 FIRST FLOOR FIRE SUPPRESSION DEMOLITION PLAN

FA101 FIRST FLOOR FIRE ALARM PLAN

FX101 FIRST FLOOR FIRE SUPPRESSION PLAN

10 - PLUMBING

PD100 BASEMENT PLUMBING DEMOLITION PLAN

PD101 FIRST FLOOR PLUMBING DEMOLITION PLAN

PL100 BASEMENT PLUMBING PLAN

PL101 FIRST FLOOR PLUMBING PLAN

P-601 PLUMBING DIAGRAMS

P-701 PLUMBING SCHEDULES -FIXTURES - DETAILS

11 - MECHANICAL

MG101 MECHANICAL SYMBOLS LEGEND AND GENERAL NOTES

MD101 FIRST FLOOR MECHANICAL DEMOLITION PLAN

MH101 FIRST FLOOR HVAC PLAN

MP101 FIRST FLOOR PIPING PLAN

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-701 MECHANICAL SCHEDULES

12 - ELECTRICAL

EG101 ELECTRICAL SYMBOLS LEGEND AND GENERAL NOTES

ED101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

EL101 FIRST FLOOR LIGHTING PLAN

EN101 FIRST FLOOR NURSE CALL PLAN

EP101 FIRST FLOOR POWER PLAN

ET101 FIRST FLOOR SPECIAL SYSTEMS PLAN

ET102 OVERALL FIRST FLOOR SPECIAL SYSTEMS PLAN

E-501 ELECTRICAL DETAILS

E-701 ELECTRICAL SCHEDULES

TOTAL SHEET COUNT: 55

REVISION # DESCRIPTION DATE

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

ARCH I TEC

T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :02

:56 P

M

GI003

LIFE SAFETY CODE REVIEW

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

HORIZONTAL BUILDING SEPARATION ALLOWANCE NFPA CHAPTE...

INCIDENTAL USES SEPARATION IF REQUIRED N/A IBC TABLE 509

SEPARATION OF OCCUPANCIES IF REQUIRED B/A 1 HOUR NFPA CHAPTE...

ALLOWABLE AREA 112,500 IBC TABLE 506.2

SPRINKLER SYSTEM REQUIRED FULLY SPRINKLED NFPA 13

ALLOWABLE NUMBER OF STORIES ABOVE GRAD... 3 1 IBC TABLE 504.4

ALLOWABLE BUILDING HEIGHT IN FEET ABOVE... 85 IBC TABLE 504.3

BUILDING CONSTRUCTION TYPE N/A NFPA II (111) - IBC II-A NFPA TABLE

19.1.6.1 & IBC...

BUILDING HEIGHTS & AREAS

CODE

REFERENCE(S)

N/A N/A

SPECIALTY OCCUPANCY REQUIREMENTS (PARKING GARAGE INFORMATION?) IBC CHAPTER 4

BUSINESS HEALTHCARE (NFPA CHAPTER 19 EXISTING... NFPA...

OCCUPANCY GROUP

CODE

REFERENCES(S)

BUILDING CLASSIFICATION

HEIGHT N/A N/A

LOT FRONTAGE N/A N/A

STREET SIDE YARD N/A N/A

SIDE N/A N/A

REAR N/A N/A

FRONT N/A N/A

SETBACKS REQ

ZONING

CHAPTER

NUMBER OF VAN ACCESSIBLE STALLS REQUIRED N/A N/A

NUMBER OF ACCESSIBLE STALLS REQUIRED N/A N/A

NUMBER OF STALLS REQUIRED N/A N/A

PARKING REQ:

ZONING

CHAPTER

IBC REQUIRED/AHJ/ALLOWED ACTUAL PROVIDED 1/3

PERMIT REQ'D Y/N: NO

SEWAGE TREATMENT: CITY OF COLUMBIA

WATER SUPPLY CITY OF COLUMBIA

FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT

INSPECTION: ...

* PLUMBING DESIGN MANUAL

* PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL (PSDRM)

* SPACE AND EQUIPMENT PLANNING SYSTEM (SEPS)

* COST ESTIMATING MANUAL

* STRUCTURAL DESIGN MANUAL

* SIGNAGE DESIGN MANUAL

* EQUIPMENT GUIDE

* LIGHTING DESIGN MANUAL

* INTERIOR DESIGN DESIGN MANUAL

* HVAC DESIGN MANUAL

* FIRE PROTECTION MANUAL

* ELECTRICAL DESIGN MANUAL

SEE VA TIL * ARCHITECTURAL DESIGN MANUAL

VA GUIDES/MANUALS: * MEDICAL/SURGICAL INPATIENT UNITS & INTENSIVE CARE NURSING UNITS DESIGN GUIDE

SEE VA TIL * VA SEISMIC DESIGN REQUIREMENTS (H-18-8, ET AL)

VA ADDITIONAL REQ: * VA BARRIER FREE DESIGN STANDARD (PG-18-13)

* 2024 OSHA STANDARDS

* 2010 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS)

* NFPA 1: FIRE CODE 2024

* 2024 INTERNATIONAL PLUMBING CODE (IPC)

* 2024 NATIONAL FIRE PROTECTION AGENCY STANDARD DEVELOPMENT (NFPA 90A)

* NFPA 70 - 2023 NATIONAL ELECTRICAL CODE (NEC)

* 2024 INTERNATIONAL BUILDING CODE (IBC) - [Limited to where NFPA does not address.]

* 2024 NATIONAL FIRE PROTECTION AGENCY FIRE CODES (NFPA 5000 & 900 EXEMPT)

APPLICABLE CODES: * 2024 NATIONAL FIRE PROTECTION AGENCY 101 LIFE SAFETY (NFPA 101 LIFE SAFETY)

SITE ADDRESS: 800 HOSPITAL DRIVE COLUMBIA, MISSOURI 65201

PARCEL NO: N/A

CONSTRUCT WOMEN'S CLINIC

SGA PROJECT NO: 231997 / VA PROJECT NO: 589A4-24-103

CODE REVIEW

NUMBER OF FEC REQUIRED PER SPACE 1 1 TABLE 906.3

MAX TRAVEL DISTANCE TO FEC 75 FEET <75 FEET TABLE 906.3

MAXIMUM FLOOR AREA FOR EXTINGUISHER 11,250 SF <11,250 SF TABLE 906.3

MAXIMUM FLOOR AREA PER UNIT OF CLASS A 1,500 SF <1,500 SF TABLE 906.3

MINIMUM RATED SINGLE EXITNGUISHER REQUIRED 2-A TABLE 906.3

FIRE EXTINGUISHER REQUIREMENTS REQUIRED PROVIDED TABLE 906.1

FIRE DEPARTMENT COMMUNICATION COVERAGE REQUIRED PROVIDED 918.1

AUTOMATIC SPRINKLER SYSTEM REQUIRED PROVIDED TABLE 903.2.6

FIRE PROTECTION SYSTEMS REVIEW INTERNATIONAL FIRE CODE (IFC) IBC CHAPTER 9

WALLS & CEILINGS CLASS A MIN. 803

IBC CHAPTER 8

X ≥ 30 0 HR

10 ≤ X < 30 1 HR

5 ≤ X < 10 1 HR

FIRE SEPARATION DISTANCE PROTECTION X < 5 1 HR TABLE 705.5

DRAFT STOPS IN ATTIC NOT REQUIRED 718.4

DRAFT STOPS IN FLOORS NOT REQUIRED 718.3

FIRE WALL NOT REQUIRED 706.1

MAXIMUM AREA OF EXTERIOR WALL OPENINGS N/A TABLE 705.9

FIRE WALLS REQUIRED (Y/N) NOT REQUIRED 706

BUILDINGS ON THE SAME LOT (Y/N) N/A 705.3

5 FEET OR GREATER 40" TABLE 705.2

GREATER THAN 3 FEET TO LESS THAN 5 FEET 2/3 FSD TABLE 705.2

GREATER THAN 2 FEET TO 3 FEET 24" TABLE 705.2

O FEET TO 2 FEET NOT PERMITTED TABLE 705.2

EXTERIOR PROJECTIONS MIN. DISTANCE FROM LINE TO DETERMINE FSD TABLE 705.2

SYSTEM IN PLACE FULLY SPRINKLERED WITH FIRE EXTINGUISHERS FULLY SPRINKLERED WITH FIRE EXTINGUISHERS 703.2.1

FIRE & SMOKE PROTECTION IBC CHAPTER 7

SHAFT WALL 1 EXISTING TABLE 4.1.1/TABLE 601

ELEVATOR 1 EXISTING TABLE 4.1.1/TABLE 601

STAIRS 1 EXISTING TABLE 4.1.1/TABLE 601

ROOF CONSTRUCTION 1 EXISTING TABLE 4.1.1/TABLE 601

FLOOR CONSTRUCTION 1 EXISTING TABLE 4.1.1/TABLE 601

(SUPPORTING ONE FLOOR ONLY)

BEAMS, GIRDERS, TRUSSES, & ARCHES 1 EXISTING TABLE 4.1.1/TABLE 601

(SUPPORTING ONE FLOOR ONLY)

COLUMNS 1 EXISTING TABLE 4.1.1/TABLE 601

NON BEARING WALLS AND PARTITIONS - INT 0 0 TABLE 4.1.1/TABLE 601

NONBEARING WALLS AND PARTITIONS - EXT 0 EXISTING TABLE 4.1.1/TABLE 601

INTERIOR 1 EXISTING TABLE 4.1.1/TABLE 601

EXTERIOR 1 EXISTING TABLE 4.1.1/TABLE 601

BEARING WALLS 1 EXSITING TABLE 4.1.1/TABLE 601

PRIMARY STRUCTURE 1 EXISTING TABLE 4.1.1/TABLE 601

CONSTRUCTION TYPE:

NFPA 220 CHAPTER 4 &

IBC CHAPTER 6

NFPA/IBC REQUIRED ACTUAL PROVIDED 2/3

See Chapter 6 for Rated assemblies

UL-RATED SYSTEMS AND DESIGN NUMBER SEE WALL TYPE LEGEND / BUILDING SECTIONS

SOUND TRANSMISSION NOT REQUIRED SECTION 1207

LABELING FIRE WALLS LABEL ALL FIRE WALLS ABOVE ALL ACT CEILINGS. SECTION 703.7

MISCELLANEOUS INFORMATION

SPECIALTY REQUIREMENTS NONE

REQUIRED? YES EXISTING

ELEVATORS & CONVEYING SYSTEMS CHAPTER 30

SERVICE SINK 1 PER FLOOR EXISTING TABLE 2902.1

DRINKING FOUNTAINS 1 PER 100 EXISTING TABLE 2902.1

LAVATORIES - EMPLOYEES 1 PER 50 CARE ROOMS EXISTING

LAVATORIES - CARE RECIPIENTS 1 PER 50 CARE ROOMS = 1 2 TABLE 2902.1

WATER CLOSETS - EMPLOYEES 1 PER 25 EXISTING

WATER CLOSETS - CARE RECIPIENTS 1 PER 25 CARE ROOMS = 1 2 TABLE 2902.1

OCCUPANCY #

MINIMUM NUMBER OF REQUIRED PLUMBING

FIXTURES

REQUIRED TYPE OF FIXTURES PROVIDED TYPE OF FIXTURE TABLE 2902.1

PLUMBING SYSTEMS IBC CHAPTER 29

SPECIAL OCCUPANCIES N/A N/A 1108

ACCESSIBLE DWELLING UNITS & SLEEPING UNITS N/A N/A TABLE 1107.6.1.1

ACCESSIBLE ROUTES FOR DWELLINGS N/A N/A 1107.4

ACCESSIBLE PARKING SPACES N/A PROVIDED TABLE 1106.1

ACCESSIBLE ENTRANCES REQUIRED PROVIDED 1105

ACCESSIBLE ROUTE REQUIRED PROVIDED 1104

REQUIREMENTS REQUIRED PROVIDED 1103

ACCESSIBILITY IBC CHAPTER 11

DEAD END CORRIDOR LENGTH 30' MAXIMUM NFPA 101-19.2.5.3

MAX COMMON PATH OF TRAVEL 75'-0" SEE CODE PLANS NFPA 101-19.2.6 &

IBC 1006.2.1

ALLOWABLE EXIT ACCESS TRAVEL DISTANCE 200' NFPA 101-19.2.6.2.3

AREA OF REFUGE REQUIRED NO IBC 1009

SMOKE BARRIERS REQUIRED YES NFPA 101-19.3.7

MEANS OF EGRESS ILLUMINATION REQUIRED? YES NFPA 101-19.2.8 &...

MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS

PER STORY

2 EXISTING IBC TABLE 1006.3.1

SPECIAL EXCEPTIONS N/A

MINIMUM DOOR WIDTH, PATIENT ROOM 41 1/2" CLR NFPA 101-7.2.1

NUMBER OF EXITS & EXIT ACCESS DOORWAYS

REQUIRED

1 IBC TABLE 1006.2.1

MINIMUM CORRIDOR WIDTH 44" NFPA 101-19.2.3.4

DOOR SWINGS N/A

DOORS (multiply by 0.2 inches/occupant) 26 MIN NFPA 101-19.2.2.5.4 STAIRWAYS (multiply by 0.3 inches/occupant) N/A IBC 1005.3.1

MEANS OF EGRESS SIZING

STORAGE, MECHANICAL S SEE CODE PLANS NFPA 101 CHAPTER ...

CONCENTRATED BUSINESS B SEE CODE PLANS NFPA 101 CHAPTER ...

BUSINESS B SEE CODE PLANS NFPA 101 CHAPTER ...

LIST TYPE TOTAL OCCUPANTS NFPA 101 TABLE...

OCCUPANCY LOAD - FUNCTION OF SPACE (LIST

BELOW)

OCCUPANT LOAD FACTOR

MEANS OF EGRESS CODE REFERENCES

IBC REQUIRED/AHJ/ALLOWED ACTUAL PROVIDED 3/3

REVISION # DESCRIPTION DATE

01 BID SET 00/00/0000

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

GENERAL ACCESSIBILITY NOTES

A.

B.

C.

D.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

ALL CONSTRUCTION AND RENOVATION SHALL MEET THE ARCHITECTURAL BARRIERS ACT

ACCESSIBILITY STANDARD (ABAAS).

SUPPLEMENTAL TO THE (ABAAS), CONSTRUCTION & RENOVATION IN HEALTH FACILITIES OF THE

DEPARTMENT OF VETERAN AFFAIRS (VA) SHALL COMPLY WITH THE VA BARRIER FREE DESIGN

STANDARD: A SUPPLEMENT TO THE ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS

(PG-18-13).

VA BARRIER FREE DESIGN STANDARDS THAT ARE

MORE RESTRICTIVE THAN ABAAS & IBC REQUIREMENTS

MINIMUM REQUIREMENTS

SITES - PARKING SPACES ACCESSIBLE 1% GREATER THAN ABAAS

SPINAL CORD INJURY/DISORDER (SCI/D) FACILITIES: 0.2

ACCESSIBLE SPACES PER INPATIENT BED; 0.5 PER

LONG-TERM CARE BED; 5.6 PER OUTPATIENT EXAM ROOM.

DEDICATED FOR SCI/D PATIENTS

HOSPITAL OUTPATIENT FACILITIES 10% OF TOTAL SPACES

REHABILITATION AND OUTPATIENT

PHYSICAL THERAPY FACILITIES 20% OF TOTAL SPACES

BUILDING-ACCESSIBLE SEATING, ASSEMBLY AREAS 1% GREATER THAN ABAAS

ACCESSIBLE ROUTE

WIDTH, MIN. PATIENT CARE AREAS 6'-0"

WIDTH, MIN. ADMINISTRATIVE AREA 5'-0"

SLOPE, MAXIMUM (INCLUDING PARKING SPACES) 1:50 (2%)

MINIMUM GRADIENT OF WALK REQUIRING REST

AREAS EVERY 200' 1:50 (2%)

TURNING RADIUS 5'-6"

TURNING RADIUS, BARIATRIC 6'-0"

T-SHAPED TURNING SPACE 5'-6" x 5'-6" T-SHAPED TURNING SPACE, BARIATRIC 6'-0" x 6'-0"

FLOOR SURFACES

CHANGES IN LEVEL NOT PERMITTED ON SCI/D FLOORS

CARPET CUSHION OR PADDING NOT PERMITTED

PARKING & PASSENGER LOADING ZONES

ACCESS AISLE REQUIREMENT FOR ACCESSIBLE

PARKING SPACES 5'-0" EACH SIDE

PASSENGER LOADING AREA

"COMMUNICATION SYSTEM" FOR ASSISTANCE AT SCI UNITS YES

CURB RAMPS

WIDTH, MINIMUM 4'-0"

RAMPS

MAXIMUM SLOPE 1:20

MAXIMUM LENGTH, WITHIN RANGE OF 1:33 - 1:26 40'

MAXIMUM LENGTH, WITHIN RANGE OF 1:25 - 1:20 35'

MINIMUM CLEAR WIDTH 4'-0"

MINIMUM SIZE LEVEL LANDING, WHERE DOORS

SWING INTO LANDING 6'-0" X 6'-0"

STAIRS

HANDRAIL HEIGHT 34"

ELEVATOR (PASSENGER)

MINIMUM WIDTH OF ELEVATOR DOORS 4'-0"

MINIMUM CAR SIZE 8'-0" X 6'-2" PLATFORM SIZE

DOUBLE SET OF HANDRAILS YES

WINDOWS

SILL HEIGHT IN PATIENT BEDROOMS 24" MAXIMUM

DOORS & DOORWAYS

PATIENT CARE DELIVERY AREAS WITH PATIENT BED,

STRETCHER OR GURNEY ACCESS, MINIMUM WIDTH 5'-0" SLIDER TYPE

PATIENT CARE DELIVERY AREAS WITH PATIENT BED, 5'-6" (4'-0" + 1'-6")

STRETCHER OR GURNEY ACCESS, MINIMUM WIDTH,

BARIATRIC 6'-0"

PATIENT CARE BUILDING ENTRY, EXIT, AND DEPARTMENT

ENTRY DOORS MINIMUM WIDTH. 4'-0"

WATER CLOSETS - INPATIENT NURSING UNITS

GRAB BAR CONFIGURATION: DOUBLE SWING-UP BARS FOR

ALL PATIENT TOILETS/SHOWER ROOMS ON NURSING UNITS

W/ INTEGRAL TOILET PAPER DISPENSER.

DISTANCE FROM TOILET CENTERLINE TO SIDE WALL 3'-0"

DISTANCE FROM EDGE OF TOILET TO SIDE WALL, BARIATRIC 3'-0"

TOILET STALLS

MINIMUM ACCESSIBLE STALL SIZE 5'-6" X 6'-0"

MINIMUM SIZE WHEELCHAIR "FRONT-TRANSFER" STALL 3'-6" X 6'-0"

GRAB BARS REQUIRED IN ALL STALLS

SHOWER STALLS (PATIENT)

MINIMUM STALL DIMENSIONS 4'-0" X 4'-0"

MINIMUM BARIATRIC STALL DIMENSIONS 4'-0" X 6'-0"

GRAB BARS HORIZONTAL PLUS VERTICAL BARS

TOILET ROOMS

INPATIENT BEDROOM TOILET ROOMS,

MINIMUM WIDTH OF TOILET ROOM ENTRANCE DOORS 48"

CAFETERIAS

KNEE CLEARANCE, FOR MINIMUM 5% TABLES 2'-3" & 2'-5" FOR AT LEAST 5%

CUTLERY AND SUPPLY HEIGHT 40" - 48"

HEALTH CARE FACILITIES

MEDICAL/SURGICAL NURSING UNITS,

PERCENT OF PATIENT BEDROOMS ACCESSIBLE 100%

MEDICAL/SURGICAL NURSING UNITS,

Figure 302.2 Carpet Pile Height

Figure 303.2 Vertical Change in Level

1/2 " m ax 1/4

" m ax

Figure 303.3 Beveled Change in Level

1/2 1/4

1/4 1/2

Figure 304.3.1.2 Circular Turning Space - Existing

Buildings Size and Overlap

Overlap of knee and toe clearance

6.2

.2

2'

- 1

" m ax

P er ø 5'-0" min

Figure 304.3.2.2 T-Shaped Turning Space New Buildings - Size and Overlap ar m ar m base

60" min min 12" min 36" min 12"

" m in36 " m in

" m in

Figure 305.3.2 Clear Floor or Ground

Space- Existing Buildings

Figure 305.5 Position of Clear Floor or Ground Space

Figure 305.7.1 Maneuvering Clearance in an

Alcove, Forward Approach

Figure 305.7.2 Maneuvering Clearance in an

Alcove, Parallel Approach

(a) forward

(b) parallel

48" min

" m in

30" min

" m in

48" min

" m in

36" min

X > 2

4"

60" min

X > 1

5"

Figure 306.2 Toe Clearance

Figure 306.3 Knee Clearance

(b) plan

(a) elevation

9"

6" max

" m in

17"- 25"

(b) plan

(a) elevation

" m in

25" max

11" min

8" min

" m in

Figure 307.2 Limits of Protruding Objects

4" max

X > 2

7"

X

Figure 307.3 Post-Mounted Protruding Objects

(b)(a)

" 12" max 12" max

" m ax X > 12"

X > 12"

" m in

Figure 307.4 Vertical Clearance

" M ax

X < 8

Figure 308.3.1 Unobstructed Side Reach

Figure 308.3.2 Unobstructed High Side Reach

Figure 308.2.2 Obstructed High Forward Reach

Figure 308.2.1 Unobstructed

Forward Reach

(a) (b) (b)(a) m in15

" m ax

" m ax

20" max

" m ax

20"- 25" max

10" max m in15

" m ax

10" max 10" - 24" max

" m ax

" m ax

" m ax

" m ax

BU

IL

DI

NG

B

LO

CK

S

Figure 403.5.2 Clear Width at Turn Existing Buildings

Figure 403.5.1 Clear Width of an Accessible Route

(a) 180 degree turn

(b) 180 degree turn

(Exception)

Figure 403.5.3.2 Clear Width At 90-Degree Turn

Existing Buildings

36" min

" m in

Figure 403.5.3.1 Clear Width At 90-Degree Turn

Existing Buildings

36" min

" m in

" m in

" m in

42" min

X<48"

42" min 36" min

X<48"

36" min

32" min

36" min

32" min

36" min

" m ax

" m in

" m ax

AC

CE

SS

IB

LE

R

OU

TE

S

Figure 404.2.4.3 Maneuvering Clearance at Recessed Doors and Gates

Figure 404.2.4.1 Maneuvering Clearance at Manual Swinging Doors and Gates

Figure 404.2.3 Clear Width of Doorways

Figure 404.2.6 Doors in Series and Gates in Series

(e) hinge approach, pull side

(j) latch approach, push side

(k) latch approach, push side

*48 min if door provided with closer

(i) latch approach, pull side

*54 min if door provided with closer

(h) latch approach, pull side

(f) hinge approach, push side

(g) hinge approach, push side

*if door provided with both closer and latch ** 48 min if both closer and latch provided

(b) front approach, push side

(c) front approach, push side

*if door provided with both closer and latch

(a) front approach, pull side

(a) hinged door

(b) sliding door

(c) folding door

(d) doorways without doors

(a) pull side

(b) push side

(c) push side, door provided with both closer and latch

(d) hinge approach, pull side

(a)

(c)

(b)

(d)

90.0 0°

32" min

32" min

32" min

>2 4"

36" min

18" min

" m in 48 " m in

*12" min

36" min 60 " m in

42" min

" m in

" m in

22" min* 12" min

* 4 8" m in

24" min

24" min

* 4 2" m in

" m in

18" min

X> 8"

X> 8" 48

" m in

" m in

12" min

X> 8"

48" min

48" min

48" min

" m in

66" min

DO

OR

S

AN

D

GA

TE

S

Figure 605.2 Height and Depth of Urinals

(a) wall hung type

Figure 604.2 Water Closet

Location

(a) wheelchair accessible water closets

(b) ambulatory accessible

Water closets Figure 604.3.1

Size of Clearance at Water Closets

Figure 604.5.1 Side Wall Grab Bar at

Water Closets

Figure 604.5.2 Rear Wall Grab Bar at Water Closets

Figure 604.7 Dispenser Outlet Location

Figure 604.9.5 Wheelchair Accessible Toilet Compartment Toe Clearance

Transfer Side comply with section 609.3

(a) elevation children

(b) plan

8" m in

8" min

" m in8" min

Partition

" m in

" m ax7" - 9"

36" min

24" min min 12"12" max 42" min

54" min

42" m in18

39" - 41" m in18

" m in

60" min 16" - 18" 17" - 19"

PL

UM

BI

NG

E

LE

ME

NT

S

AN

D

FA

CI

LI

TI

ES

TO

IL

ET

S

AN

D

UR

IN

AL

S

" m ax

13 1/2" min

(b) stall type

13 1/2" min

Figure 903.3 Bench Size And Clear Space

42" min

Figure 903.4 Bench Back Support

(a) (b) m in18

2" m ax 2 1/2" max

Figure 904.4.1 Sales And Service Counters - Parallel Approach

Figure 904.4.2 Sales And Service Counters - Forward Approach

Elevation

Plan

30" min

" m ax

" m ax

Elevation

Plan

36" min

" m ax

" m ax

BU

IL

T-

IN

E

LE

ME

NT

S

Figure 703.6.1 Pictogram Field

MEN not in pictogram field

6" M in

Figure 705.1 Size and Spacing of Truncated Domes base diameter of 0.9"-1.4" top diameter of 50%-65% of the base diameter

(a) elevation (enlarged)

(b) plan

.65 " M in 1.6" - 2.4"

1.6

2.

4"

Figure 707.6.2 Numeric Key Layout

(a) 12-key ascending

(b) 12-key descending

1 2 3 4 5 6

7 8 9

* 0 #

7 8 9

4 5 6

1 2 3

* 0 #

Figure 703.2.5 Height of Raised

Characters

LIBRARY

5/8

2"0.2

Figure 703.3.1 Braille Measurement single braille cell blank cell space between words raised dot no raised dot

Figure 703.3.2 Position of Braille

AREA OF

REFUGE

3/8 " m in 3/8

" m in

Figure 703.7.2.1 International Symbol of Accessibility

Figure 703.7.2.2 International TTY Symbol

Figure 703.7.2.3 Volume-Controlled Telephone

Figure 703.7.2.4 International Symbol of Access for

Hearing Loss

Figure 704.2.1.1 Parallel Approach to

Telephone

Figure 704.2.1.2 Forward Approach to

Telephone

Figure 703.4.1 Height of Tactile Characters

Above Floor or Ground

Figure 703.4.2 Location of Tactile Signs at Doors

AREA OF

REFUGE

centered on tactile characters

AREA OF

REFUGE

45.

00°

" M ax

" M ax

" M in

" M ax

18" Min

" M in di st an ce b et we en co rre sp on di ng d ot s fro m o ne ce ll d ire ct ly be lo w di st an ce b et we en d ot s in th e s am e c ell distance between corresponding dots in adjacent cells distance between dots in the same cell ba se d iam et er

CO

MM

UN

IC

AT

IO

N

EL

EM

EN

TS

A

ND

F

EA

TU

RE

S

Sanitary Napkin Disposal

Sanitary Napkin Dispenser

" m ax

Soap Dispenser

Paper Towel Dispenser

T.

O.

d isp en se r O

PG

" m ax

Coat/Robe Hook

4'- 0"

A

CC

5'- 4"

T

YP

Mirror Height

" t o gl as s

Fire Extinguisher Cabinet

" m ax to th e h an dl e

" m ax

Hand Dryer

Trash Receptacle

" m ax

Toilet Seat Cover Dispenser

MO

UN

TI

NG

H

EI

GH

TS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :02

:57 P

M

GI011

ACCESSIBILITY DETAILS

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

REVISION # DESCRIPTION DATE

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

JT

JT

JT

JT

FE

C

CRJT

GENERAL CODE NOTES

H. SMOKE SEALS TO BE INSTALLED AT ALL RATED DOORS.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

BUILDING & LIFE SAFETY REQUIREMENT LEGEND

DESCRIPTIONWALL

RATINGPARTITION KEY NFPA 101-2024

IBC 2024

OPENINGS

RATING REFERENCE

90 MINFIRE BARRIER:

OCCUPANCY/AREA SEPARATION

FIRE BARRIER:

HORIZONTAL EXIT & REFUGE AREA

90 MINNFPA 7.1.3.2 NFPA 8.3.3.2.2

2 HOUR

FIRE BARRIER

VERTICAL EXIT ENCLOSURE/SHAFT

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES) 60 MIN

90 MINNFPA 8.6

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

SMOKE PARTITIONS

(SPRINKLERED)

HAZARDOUS/INCIDENTAL USE

NR

SMOKE BARRIER

SUBDIVIDING SPACES

20 MIN

SMOKE PARTITION

SUITE SEPARATION

EXIT ACCESS CORRIDORS

(SPRINKLERED) CORRIDOR WALLS

NR

NFPA 8.5

IBC 716.1

NFPA 8.4.2

IBC 710.3

NFPA 8.4.2

IBC 407.3

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 19.3.7.8

IBC 716.1

NFPA 8.7.1.2

NFPA 8.3.3.2.2, 8.4

NFPA 8.4.3

1 HOUR

NR

NR

NR NR

2 HR

NFPA 8.2.1.3

IBC 716.1

NFPA 8.3.3.2.2

IBC 716.1

DAMPERS

TYPE REFERENCE

FIRE

90 MIN

FIRE

90 MIN

NFPA 8.3.4.3, 9.2.1

NFPA 8.3.4.3, 9.2.1

SMOKE

90 MIN

NFPA 8.5.5.3

VARIES NFPA 8.4.4

VARIES NFPA 8.4.4, 8.4.6.2

VARIES NFPA 8.4.4, 8.4.6.2

NOT ALLOWED

UNLESS SERVING

STAIR ONLY

N/A

1 HR

FIRE BARRIER 45 MINNFPA 8.7.1.1

IBC 716.1

NFPA 8.3.3.2.2, 8.7.1.1

IBC 716.11 HOUR N/A N/A

CONSTRUCTION LEGEND

SHADED AREA NOT IN SCOPE OF WORK

NEW COMPONENTS

TRUE

NORTH

PLAN

NORTH

4.0" 48.0"

0.4" 48.0"

LENGTH OF TRAVEL: 76'-9"

110 SF

A119

CLEAN

141 SF

A121

EXAM/TELEHEALTH/CONSULT

66 SF

A123

RESTROOM

121 SF

A125

ENTRY/WAITING

387 SF

C1A3

CORRIDOR

9 SF

A124B

INTAKE

38 SF

A127

MSA

CHECK-IN

105 SF

A120

SOILED 165 SF

A122

PROCEDURE2

72 SF

A124

RESTROOM

187 SF

A126

PROCEDURE1

183 SF

A128

SWAMP

22 SF

A128A

NURSE

STATION25 SF

A124A

NURSE

STATION

C1E33

CORR.

C1E34

CORRIDOR

A129B

ELEC./

TELE./

MECH.

13 SF

10.44

10.48 10.45

10.45

10.47

10.40

10.40

55'-0"

0.0" 0.0"

OCCUPANTS

REQUIRED WIDTH

PROVIDED WIDTH

OCCUPANT LOAD

CODE & EGRESS SYMBOL LEGEND

FEC FIRE EXTINGUISHER CABINET

FE FIRE EXTINGUISHER

FPS FIRE PULL STATION

FACP FIRE ALARM CONTROL PANEL

FSA FIRE SYSTEM ANNUNCIATOR ALARM

FSP FIRE SYSTEM ANNUNCIATOR PANEL

DIRECTION OF EGRESS

DIRECTION OF EGRESSPATH OF TRAVEL

START OF PATH TRAVEL DISTANCE (TD)

TD = X'-X"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :02

:58 P

M

GI101

LIFE SAFETY PLAN - 1ST FLOOR

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

KEYNOTES

KEY VALUE KEYNOTE TEXT

10.40 RECESSED MOUNTED F.E.C.

10.44 LABEL ABOVE CEILING IN EACH ROOM DESIGNATING WALL AS "SMOKE BARRIER". REMOVE ANY

INCORRECT LABELING THAT MAY REMAIN.

10.45 LABEL ABOVE CEILING IN EACH ROOM DESIGNATING WALL AS "SMOKE PARTITION".

10.47 VERIFY EXISTING SEALS AND PROVIDE NEW WHERE EXISTING DOES NOT MEET REQUIREMENTS

OF FIRE SEALANT FOR 1-HOUR FIRE BARRIER.

10.48 VERIFY EXISTING SEALS AND PROVIDE NEW WHERE EXISTING DOES NOT MEET REQUIREMENTS

OF SEALANT FOR SMOKE BARRIER.

1/4" = 1'-0"D2 LIFE SAFETY PLAN - 1ST FLOOR

FIRST LEVEL KEY PLAN

N

REVISION # DESCRIPTION DATE

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

OVEN

GENERAL FACILITY NOTES

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

H. FOR CLARITY, ONLY SMOKE COMPARTMENTS MODIFIED BY THE WORK ARE SHOWN ON THIS PLAN.

CONSTRUCTION LEGEND

SHADED AREA NOT IN SCOPE OF WORK

NEW COMPONENTS

TRUE

NORTH

PLAN

NORTH

PROJECT LOCATION

CONSTRUCTION ACCESS

REVISION TO SMOKE

COMPARTMENT #1-3

21062 SF

REVISION TO SMOKE

COMPARTMENT #1-1

15700 SF

S.C. 1-1, SUITE 1

PATIENT CARE NON-SLEEPING SUITE

1858 SF

CONSTRUCTION ACCESS ROUTE

SMOKE

COMPARTMENT #1-4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :03

:03 P

M

GI121

FACILITY PLAN

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

KEYNOTES

KEY VALUE KEYNOTE TEXT

1" = 20'-0"D1 CAMPUS / FACILITY PLAN

REVISION # DESCRIPTION DATE

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

FE

FEC

FP

FE

FE

FEC

FP

FE

GENERAL PHASING NOTES

H. IN EXISTING AND/OR OCCUPIED BUILDINGS, ALL TEMPORARY CONSTRUCTION BARRIERS SHALL BE

MINIMUM 1 HOUR RATED FIRE BARRIER ASSEMBLIES UNO.

I. WHERE ABOVE CEILING WORK IS REQUIRED IN OCCUPIED SPACES, THE CONTRACTOR SHALL

COORDINATE AND CONFIRM DATE & TIME WITH THE OWNER.

J. ALL CEILINGS DISTURBED IN OCCUPIED SPACES DURING AFTER-HOURS WORK SHALL BE

REINSTALLED, CLEANED UP, AND OPERATIONAL PRIOR TO THE END OF EACH WORK SHIFT UNO.

K. IN EXISTING AND/OR OCCUPIED BUILDINGS, ALL OPENINGS THROUGH RATED CONCRETE FLOOR

ASSEMBLIES MUST BE FIRESTOPPED OF INFILLED PRIOR TO THE END OF EACH WORK SHIFT.

L. MODIFICATIONS TO EXISTING WALLS MAY BE NECESSARY TO CREATE A TEMPORARY RATED

ASSEMBLY DURING PROJECT CONSTRUCTION. REFERENCE PHASING AND/OR ARCHITECTURAL

DEMOLITION PLANS.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

NOTE

A. AFFECTED AREAS AND BARRIER LOCATIONS SHOWN ARE APPROXIMATE UNO.

PHASING LEGEND

EXISTING AREA

NEW OR RENOVATED AREA

EXISTING PARTITION

NEW PARTITION

DEMOLISHED PARTITION

TEMPORARY CONSTRUCTION BARRIER (1 HOUR FIRE RATED ASSEMBLY UNO)

TEMPORARY WALL MODIFICATION (1 HOUR FIRE RATED ASSEMBLY UNO)

AREA AFFECTED BY PHASE

AREA AFFECTED BY PHASE AFTER-

HOURS

TEMPORARY WALL MODIFICATION (WEATHER PROOFING)

TRUE

NORTH

PLAN

NORTH

A027AA026

A025BA025

A024A

A024

A022

A020A

A020A019A010

A010A

A009A

E001FE001E

CBA4 CBA5 CBA7

A028

A030

A031

A029

A023A

A023A021A018

A011

A014

CBA6

A012

A013

A015

1.06

1.05

1.05

TRUE

NORTH

PLAN

NORTH

A027AA026

A025BA025

A024A

A024

A022

A020A

A020A019A010

A010A

A009A

E001FE001E

CBA4 CBA5 CBA7

A028

A030

A031

A029

A023A

A023A021A018

A011

A014

CBA6

A012

A013

A015

1.05

1.05

1.06

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :03

:04 P

M

GI140

PHASING PLANS - BASEMENT FLOOR

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

KEYNOTES

KEY VALUE KEYNOTE TEXT

1.05 REFER TO DEMOLITION PLAN(S) FOR EXTENT OF WORK.

1.06 MAINTAIN 6 FT MIN. CLEAR CORRIDOR FOR THE ENTIRE LENGTH OF CONSTRUCTION.

FIRST LEVEL KEY PLAN

N

3/16" = 1'-0"D2 PHASING PLAN - BASEMENT FLOOR PHASE 2

3/16" = 1'-0"B1 PHASING PLAN - BASEMENT FLOOR PHASE 1

REVISION # DESCRIPTION DATE

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

FP

FE

FE

C

FP

FP

FE

FE

C

GENERAL PHASING NOTES

H. IN EXISTING AND/OR OCCUPIED BUILDINGS, ALL TEMPORARY CONSTRUCTION BARRIERS SHALL BE

MINIMUM 1 HOUR RATED FIRE BARRIER ASSEMBLIES UNO.

I. WHERE ABOVE CEILING WORK IS REQUIRED IN OCCUPIED SPACES, THE CONTRACTOR SHALL

COORDINATE AND CONFIRM DATE & TIME WITH THE OWNER.

J. ALL CEILINGS DISTURBED IN OCCUPIED SPACES DURING AFTER-HOURS WORK SHALL BE

REINSTALLED, CLEANED UP, AND OPERATIONAL PRIOR TO THE END OF EACH WORK SHIFT UNO.

K. IN EXISTING AND/OR OCCUPIED BUILDINGS, ALL OPENINGS THROUGH RATED CONCRETE FLOOR

ASSEMBLIES MUST BE FIRESTOPPED OF INFILLED PRIOR TO THE END OF EACH WORK SHIFT.

L. MODIFICATIONS TO EXISTING WALLS MAY BE NECESSARY TO CREATE A TEMPORARY RATED

ASSEMBLY DURING PROJECT CONSTRUCTION. REFERENCE PHASING AND/OR ARCHITECTURAL

DEMOLITION PLANS.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

NOTE

A. AFFECTED AREAS AND BARRIER LOCATIONS SHOWN ARE APPROXIMATE UNO.

PHASING LEGEND

EXISTING AREA

NEW OR RENOVATED AREA

EXISTING PARTITION

NEW PARTITION

DEMOLISHED PARTITION

TEMPORARY CONSTRUCTION BARRIER (1 HOUR FIRE RATED ASSEMBLY UNO)

TEMPORARY WALL MODIFICATION (1 HOUR FIRE RATED ASSEMBLY UNO)

AREA AFFECTED BY PHASE

AREA AFFECTED BY PHASE AFTER-

HOURS

TEMPORARY WALL MODIFICATION (WEATHER PROOFING)

TRUE

NORTH

PLAN

NORTH

1.06

1.04

TRUE

NORTH

PLAN

NORTH

CONSTRUCTION

ACCESS

1.04

1.06

1.04

1.27

1.26

1.04

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :03

:05 P

M

GI141

PHASING PLANS - 1ST FLOOR

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

KEYNOTES

KEY VALUE KEYNOTE TEXT

1.04 MAINTAIN WIDTH OF CASED OPENING CLEAR FOR THE ENTIRE LENGTH OF CONSTRUCTION.

1.06 MAINTAIN 6 FT MIN. CLEAR CORRIDOR FOR THE ENTIRE LENGTH OF CONSTRUCTION.

1.26 PROVIDE TEMPORARY BARRIER FOR WORK IN THIS AREA. (COORDINATE WORK WITH OWNER.)

REMOVE AND REPLACE DOOR FRAME KEEPING EXIT CORRIDOR OPERATIONAL. INFILL NEW

RATED FRAME

1.27 PROVIDE TEMPORARY BARRIER FOR WORK IN THIS AREA. (COORDINATE WORK WITH OWNER.)

INFILL NEW RATED FRAME TO CREATE 1-HOUR RATED TEMPORARY BARRIER UNTIL DOORS ARE

READY

FIRST LEVEL KEY PLAN

N

3/16" = 1'-0"B2 PHASING PLAN - 1ST FLOOR PHASE 1

3/16" = 1'-0"D2 PHASING PLAN - 1ST FLOOR PHASE 2

REVISION # DESCRIPTION DATE

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

GENERAL DEMOLITION NOTES

H. PROTECT ALL EXISTING UTILITIES UNO.

I. PATCHING AND/OR INFILL TO MATCH EXISTING CONSTRUCTION AND FINISHES UNO.

J. EXISTING ITEMS TO REMAIN ARE SHOWN IN GRAY.

K. EXISTING ITEMS TO BE DEMOED ARE SHOWN WHITE WITH DASHED LINES.

L. INFILL OF FIRE PARTITION PENETRATIONS/OPENINGS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

M. CONTRACTOR TO COORDINATE RELOCATION AND/OR STORAGE OF SALVAGED ITEMS WITH THE

OWNER UNO.

N. REFERENCE MECHANICAL DEMOLITION, AND/OR PLUMBING DEMOLITION SHEETS FOR INFORMATION

REGARDING DEMOLITION OF HAZARDOUS MATERIALS.

O. SEE STRUCTURAL DETAILS FOR INFORMATION REGARDING INFILL OF EXISTING STRUCTURAL FLOOR

PENETRATIONS.

P. ALL CONSTRUCTION WASTE PRODUCED BY DEMOLITION TO BE PROPERTY OF CONTRACTOR UNO.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

GENERAL HAZARDOUS MATERIAL NOTES

H. REFERENCE ASBESTOS SURVEY FOR A LIST OF MATERIALS THAT CONTAIN 1% ASBESTOS OR LESS

WHICH WILL ENABLE THE RENOVATION / DEMOLITION CONTRACTOR TO MAKE APPROPRIATE

DECISIONS CONCERNING COMPLIANCE ISSUES WITH APPLICABLE OSHA REGULATIONS.

I. REFERENCE ARCHITECTURAL DEMOLITION SHEETS FOR INFORMATION REGARDING DEMOLITION OF

NON HAZARDOUS MATERIALS.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

NOTE

A. AFFECTED AREAS & BARRIER LOCATIONS SHOWN ARE APPROXIMATE UNO.

B. ASBESTOS LOCATIONS & QUANTITIES ARE APPROXIMATE.

C. HAZARDOUS MATERIALS MAY EXTEND BEYOND SCOPE OF WORK.

HAZARDOUS MATERIAL LEGEND

EXISTING AREA

NEW OR RENOVATED AREA

EXISTING PARTITION

NEW PARTITION

DEMOLISHED PARTITION

1 HR RATED TEMPORARY CONSTRUCTION

BARRIER

TEMPORARY WALL MODIFICATION

ASBESTOS MATERIALS - MEP ITEMS

ASBESTOS MATERIALS - ARCH ITEMS

APPROXIMATE DEMO QUANTITIES

ASBESTOS INSULATED PIPE:

1ST FLOOR - 300 LF

ASBESTOS FITTINGS:

BASEMENT FLOOR - 30 FITTINGS

1ST FLOOR - 20

ASBESTOS JOINT COMPOUND:

BASEMENT FLOOR - 600 SF

1ST FLOOR - 400 SF

CONSTRUCTION LEGEND

SHADED AREA NOT IN SCOPE OF WORK

NEW COMPONENTS

TRUE

NORTH

PLAN

NORTH

A027A

A026

A025BA025

A024A

A024

A022

A020A

A020A019A010

A010A

A009A

E001FE001E

CBA4 CBA5 CBA7

A028

A030 A031

A029

A023A

A023A021A018

A011

A014

CBA6

A012

A013

2.58

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :03

:06 P

M

HA100

HAZARDOUS ASBESTOS PLAN - BASEMENT

FLOOR

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA #589A4-24-103BID SET

1/4" = 1'-0"D2

HAZARDOUS ASBESTOS PLAN - BASEMENT

FLOOR FIRST LEVEL KEY PLAN

N

REVISION # DESCRIPTION DATE

01 BID SET 00/00/0000

KEYNOTES

KEY VALUE KEYNOTE TEXT

2.58 REMOVE EXISTING GYP CEILING AS NECESSARY FOR DEMO/INSTALL OF MEP ELEMENTS (SEE

MEP PLANS); REPLACE, PATCH AND PAINT CEILING WHERE AFFFECTED BY CONSTRUCTION. ADD

ACCESS PANELS AS REQUIRED TO SERVICE NEW MEP ELEMENTS.

TODD RANDALL

STONE

NUMBER

A−2018027172

*S T A

T E

OF MISSO

U R I

3 3 G

G

S

J

J J

G

G

G

G

JJ

J

JJ J

G

J

J

G

G

S

J

J J J

G

J J

J J

J

J J

J

J

JG

G

JJ J

J

S

J J J

J J

J J

J

J

J W,1 F

F

CR

K K

J

E

GENERAL DEMOLITION NOTES

H. PROTECT ALL EXISTING UTILITIES UNO.

I. PATCHING AND/OR INFILL TO MATCH EXISTING CONSTRUCTION AND FINISHES UNO.

J. EXISTING ITEMS TO REMAIN ARE SHOWN IN GRAY.

K. EXISTING ITEMS TO BE DEMOED ARE SHOWN WHITE WITH DASHED LINES.

L. INFILL OF FIRE PARTITION PENETRATIONS/OPENINGS SHALL MAINTAIN THE INTEGRITY OF THE

RATING.

M. CONTRACTOR TO COORDINATE RELOCATION AND/OR STORAGE OF SALVAGED ITEMS WITH THE

OWNER UNO.

N. REFERENCE MECHANICAL DEMOLITION, AND/OR PLUMBING DEMOLITION SHEETS FOR INFORMATION

REGARDING DEMOLITION OF HAZARDOUS MATERIALS.

O. SEE STRUCTURAL DETAILS FOR INFORMATION REGARDING INFILL OF EXISTING STRUCTURAL FLOOR

PENETRATIONS.

P. ALL CONSTRUCTION WASTE PRODUCED BY DEMOLITION TO BE PROPERTY OF CONTRACTOR UNO.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

GENERAL HAZARDOUS MATERIAL NOTES

H. REFERENCE ASBESTOS SURVEY FOR A LIST OF MATERIALS THAT CONTAIN 1% ASBESTOS OR LESS

WHICH WILL ENABLE THE RENOVATION / DEMOLITION CONTRACTOR TO MAKE APPROPRIATE

DECISIONS CONCERNING COMPLIANCE ISSUES WITH APPLICABLE OSHA REGULATIONS.

I. REFERENCE ARCHITECTURAL DEMOLITION SHEETS FOR INFORMATION REGARDING DEMOLITION OF

NON HAZARDOUS MATERIALS.

A.

B.

C.

D.

E.

F.

G.

ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION

DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE

PROCEEDING WITH THE WORK.

WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS. DO NOT SCALE THE

DRAWINGS.

CONTRACTOR & SUBCONTRACTORS TO VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.

ALL MATERIALS & EQUIPMENT SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTIONS.

DETAILS SHOWN ARE TYPICAL UNO. SIMILAR DETAILS APPLY IN SIMILAR CONDITIONS.

SEE STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

DIMENSIONS ARE TO FACE OF FRAMING, CENTERLINE OF EQUIPMENT, CENTERLINE OF FIXTURE, OR GRID UNO. DIMENSIONS ARE TO FACE OF FINISH ON INTERIOR ELEVATIONS AND/OR WHERE THE

ABBREVIATION "CLR" IS USED UNO.

NOTE

A. AFFECTED AREAS & BARRIER LOCATIONS SHOWN ARE APPROXIMATE UNO.

B. ASBESTOS LOCATIONS & QUANTITIES ARE APPROXIMATE.

C. HAZARDOUS MATERIALS MAY EXTEND BEYOND SCOPE OF WORK.

HAZARDOUS MATERIAL LEGEND

EXISTING AREA

NEW OR RENOVATED AREA

EXISTING PARTITION

NEW PARTITION

DEMOLISHED PARTITION

1 HR RATED TEMPORARY CONSTRUCTION

BARRIER

TEMPORARY WALL MODIFICATION

ASBESTOS MATERIALS - MEP ITEMS

ASBESTOS MATERIALS - ARCH ITEMS

APPROXIMATE DEMO QUANTITIES

ASBESTOS INSULATED PIPE:

1ST FLOOR - 300 LF

ASBESTOS FITTINGS:

BASEMENT FLOOR - 30 FITTINGS

1ST FLOOR - 20

ASBESTOS JOINT COMPOUND:

BASEMENT FLOOR - 600 SF

1ST FLOOR - 400 SF

CONSTRUCTION LEGEND

SHADED AREA NOT IN SCOPE OF WORK

NEW COMPONENTS

TRUE

NORTH

PLAN

NORTH

C1E33

ST

R

#4

A129B A129A

A129

A130

A1

A128A

A128B

A144

C1 E6

C1 A6

A119

A119A

A121 A123 A125

C1A3

A118 A120 A120A A122

A124 A126

A127 A128

1.04

1.04

1.04

ANTE

ROOM

2.66

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

A

B

C

D

2 4 5

PhaseDESIGNER OF RECORD A/E:

STAMPCONSULTANTS

MEP:

FARRIS ENGINEERING

12700 WEST DODGE ROAD

OMAHA, NE 68154

402.330.5900

STRUCTURAL:

ERA STRUCTURAL ENGINEERING

110N. ANKENY BLVD. SUITE 200

ANKENY, IA 50023

515.384.1001

6"

6"

6"

6"

ON

E

EI

GH

TH

IN

CH

O

NE

F

OO

T (1

/8"

1' -0

ON

E

QU

AR

TE

R

IN

CH

O

NE

F

OO

T (1

/4"

1' -0

TH

RE

E

EI

GH

TH

S

IN

CH

O

NE

F

OO

T

(3 /8"

1'

-0

ON

E

HA

LF

IN

CH

O

NE

F

OO

T

(1 /2"

1'

-0

TH

RE

E

QU

AR

TE

RS

IN

CH

O

NE

F

OO

T (3

/4"

1' -0

ON

E

IN

CH

O

NE

F

OO

T (1

1'

-0

ON

E

AN

D

ON

E

HA

LF

IN

CH

ES

O

NE

F

OO

T (1

1/ 2"

1'

-0

TH

RE

E

IN

CH

ES

O

NE

F

OO

T

(3

1' -0

32 4 5 61

C:

\U se rs\

A.

Sc hlo me r\D oc um en ts\

W

OM

EN

S

CL

IN

IC

_a utu mn sR

AF

.rv t 6/2

5/2

5 5 :03

:07 P

M

HA101

HAZARDOUS ASBESTOS PLAN - 1ST FLOOR

STONE GROUP ARCHITECTS

117 PIERCE STREET, SUITE 110

SIOUX CITY, IA 51101

(712)252-4014

CONSTRUCT WOMEN'S CLINIC

800 HOSPITAL DRIVE COLUMBIA, MO 65201

06/25/2025 BF/TM IN/LY

SGA #231997

VA…