2025_06-12_PRMIT_E25-4776_AKRailroadAOC_34x22.pdf
PDF 157 KB Posted
- Attached to
- 25-49 ARRC UPS Replacement 825 E. Whitney Road
- Solicitation number
- 25-49-213520 ARRC UPS Replacement 825 E. Whitney R
- Issued by
- Aleutians East Borough, Alaska
About this file
The document is an electrical design and specification set for the Alaska Railroad AOC (Airport Office Complex) UPS Replacement project located at 825 E Whitney Road in Anchorage, Alaska. The project involves replacing an existing Uninterruptible Power Supply (UPS) system, specifically a Mitsubishi 80-KVA UPS, with a new system that will connect to the existing electrical infrastructure with no load change. The design includes detailed electrical specifications, one-line diagrams, and room layout plans for demolition and new work, with the project dated for completion in June 2025.
The replacement UPS system is specified to have 480V input and 208Y/120V 3-phase 4-wire output, with a 3-breaker wrap-around bypass switch, step-down transformer, output breaker distribution, static internal bypass, remote annunciator, communication package with network connection, seismic support, and batteries sized for 120 minutes of capacity at 14-kW load. The project involves removing the existing 65kVA UPS and installing a new UPS system with associated infrastructure modifications, including upgrades to electrical panels and feeders. The electrical design ensures compliance with National Electric Code (NEC) standards and includes detailed specifications for conduit, wiring, grounding, and supporting electrical infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 25-49 ARRC UPS Replacement 825 E. Whitney Road.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL LEGEND
METERING DEVICE
POWER PANELBOARD
T TRANSFORMER: APPROX. PHYSICAL SIZE AS SCALED
LINETYPE/LINEWEIGHT DENOTING CONTROL WIRING
LINETYPE/LINEWEIGHT DENOTING BELOW GRADE CONDUIT
LINETYPE/LINEWEIGHT DENOTING NEW ONE-LINE CONNECTIONS
LINETYPE/LINEWEIGHT DENOTING NEW WORK
LINETYPE/LINEWEIGHT DENOTING EXISTING WORK TO REMAIN
LINETYPE/LINEWEIGHT DENOTING DEMO WORK
LINETYPE/LINEWEIGHT DENOTING FUTURE WORK
a
LOWER CASE LETTER DENOTES
SWITCH LEG FOR CORRESPONDING
LUMINAIRE CONTROL
CONTROL
SWITCHES
UPPERCASE LETTER OR NUMBER
DENOTES SWITCH CONFIGURATION
2A-15a
RT13
LUMINAIRES
LUMINAIRE TYPE (UNDERLINED)
CIRCUIT AND SWITCHLEG
PANEL
RECEPTACLES
PANEL
+48" 2A-5,7
NOTE 1: DIMENSIONS (WHEN GIVEN ARE AFF). TRIANGLE DENOTES
46" AFF IN OPEN AREAS OR AT CASEWORK LOCATIONS TO BE 4"
ABOVE COUNTERTOP (BACKSPLASH WHEN PRESENT). COORDINATE
WITH ARCHITECTURE. THIS APPLIES TO ALL ELECTRICAL DEVICES.
TRIANGLE.
SEE NOTE 1.
MOUNTING HEIGHT (SEE NOTE 1)
CIRCUIT NUMBER(S)
EQUIPMENT
CONNECTIONS
PANEL
2A-1,3,5
AHU-1
CIRCUIT NUMBER(S)
EQUIPMENT ID (UNDERLINED)
EQUIPMENT TAG LEGEND
RE
E
TIG S
R
ED ALEP OR F OSS I N
49TH
E
NEIGNE
R
S ATA
TE OF ALASK
EE - 9773
ERIC D. COWLING
SHEET NO.
JOB NO.
DATE
DRAWN
REVIEWED
REVISIONS
E
IC
E N
G
IN
E E
R S
IN
C
E
IC
J O
B N
O
W W
W .E
IC
E
N G
.C O
M
.3
.9
A
N C
H O
R A
G E
A
K
O L D
S E
W A
R D
H W
Y S
T E
E L E
C T
R I C
A L
E
N G
I N
E E
R S
C O
R P
O R
A T
IO
N
L
IC
E N
S E
A
E C
C
T H
IS
S
H E
E T
I S
F U
L L S
IZ
E
A T
"x
A C
T U
A L
/1
/2
:0
:5
P M
C
U se rs \E ri cC o w li n g \E
IC
E n g in e e rs
\D e si g n
F il e s\
P ro je ct s\ E
\E
-4
A
K R a il ro a d A
O C
\D E
S \E
-4
E
S h t2
A
K R a il ro a d A
O C
.r v t
E0.1
LEGEND AND
SPECIFICATIONS
E25-4776
06/11/2025
KRR
EDC
A L
A S
K A
R A
IL
R
O A
D A
O C
U P
S R
E P
L A
C E
M E
N T
E
W H
IT
N
E Y
R D
A N
C H
O R
A G
E A
K
E
-4
6/12/25 q c:
/1
/2
:0
:4 f c-vi sO n
S h t
.0
;0 .0
:0 .0
/0
ELECTRICAL SHEET LIST
NUM REV# SHEET TITLE
E0.1 LEGEND AND SPECIFICATIONS
E1.1 ONE-LINE DIAGRAMS, DETAILS, AND SCHEDULES
TOTAL SHEETS: 2
INDUSTRY STANDARD ABBREVIATIONS SHALL ALSO BE APPLICABLE.
ABBREVIATIONS
Key Name FullWord
(#) DENOTES TYPICAL IN LIGHT FIXTURE TYPES
(D) DEMOLISH
(E) EXISTING
(R) RELOCATED
AER ARC ENERGY REDUCTION
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
BJ BONDING JUMPER
CB CIRCUIT BREAKER
CO, C.O. CONDUIT ONLY
CT CURRENT TRANSFORMER
CU COPPER
EECP ELEVATOR EMERGENCY COMMUNICATION PANEL
EECS ELEVATOR EMERGENCY COMMUNICATION STATION
EGC EQUIPMENT GROUNDING CONDUCTOR
FAA FIRE ALARM ANNUCIATOR
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE ILLUMINATION
FHP FRACTIONAL HORSEPOWER
FLA FULL LOAD AMPS
FSD FIRE SMOKE DAMPER
G, GFCI GROUND FAULT CIRCUIT INTERRUPTER
GEC GROUNDING ELECTRODE CONDUCTOR
GES GROUNDING ELECTRODE SYSTEM
GFPE GROUND FAULT PROTECTION OF EQUIPMENT
MCA MINIMUM CIRCUIT AMPACITY
MFS MAXIMUM FUSE SIZE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT (NOT IN SCOPE)
NO NORMALLY OPEN
P POLES
PC PHOTO CELL
PH, Ø PHASE
PNL PANEL
RIB RELAY IN A BOX (MOTOR RATED)
SCA SHORT CIRCUIT AMPS
SCCR SHORT CIRCUIT CURRENT RATING
SE SERVICE ENTRANCE RATED
SPD SURGE PROTECTION DEVICE
SSBJ SUPPLY SIDE BONDING JUMPER
SSEBJ SUPPLY SIDE EQUIPMENT BONDING JUMPER
TGB TELECOMMUNICATION GROUNDING BUSBAR
TMGB TELECOMMUNICATION MAIN GROUNDING BUSBAR
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VFD VARIABLE FREQUENCY DRIVE
W WATTS OR WIRE
WG WIRE GUARD
WP WEATHERPROOF
XFMR TRANSFORMER
MOUNTING HEIGHT SCHEDULE
EQUIPMENT (TO CENTER UON) HEIGHT (UON)
CONTACTORS, MOTOR STARTERS, DISCONNECT (TOP) 66"
ELECTRIC RANGE RECEPTACLES (TOP) 7" MAX
INDICATING DEVICES (BOTTOM) 80"
PANELBOARDS - POWER; SPECIAL SYSTEMS (TOP) 72"
POWER METER BASE (CENTER LINE OF SOCKET) PER UTILITY
PULL STATIONS, PUSH BUTTONS 46"
REC FULL HEIGHT REFRIGERATOR OR REACH-IN UNITS 46"
REC IN FINISHED AREAS 18"
REC IN NON-FINISHED, WAREHOUSE, MECH AND SHOPS 46"
REC LOCATED IN HAZARDOUS OR S-2 OCCUPANCIES 24" MINIMUM
TELECOMMUNICATION OUTLETS 18"
WALL MOUNTED SWITCHES 46"
WASHING MACHINES AND DRYER RECEPTACLE 43"
MOA PLAN REVIEW PROJECT SUMMARY
REPLACEMENT OF EXISTING UPS SYSTEM CONNECTING TO EXISTING
ELECTRICAL SYSTEM. NO LOAD CHANGE.
"X" = PROVIDE SUBMITTAL
ELECTRICAL SPECIFICATIONS
26 00 00 - GENERAL REQUIREMENTS: ALL ELECTRICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE (NEC), STATE, MUNICIPAL, FEDERAL LAWS, AND AMENDMENTS GOVERNING THE PROJECT. ALL WORK SHALL BE PERFORMED UNDER THE SUPERVISION OF A CERTIFIED ADMINISTRATOR
JOURNEYMAN ELECTRICIAN.
ALL ELECTRICAL EQUIPMENT SHALL BE NEW COMMERCIAL GRADE AND INCLUDE THE SEAL OF A NATIONALLY RECOGNIZED TESTING LABORATORY FOR THE PURPOSE IT IS INSTALLED AS A COMPLETE ASSEMBLY. THE CONTRACTOR SHALL SUBMIT A REQUEST FOR ANY SUBSTITUTION OR DEVIATION FROM THE DESIGN IN WRITING TO THE ENGINEER. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED CONSTRUCTION PERMITS, SCHEDULE INSPECTIONS, AND PAY ALL ASSOCIATED FEES UNLESS
DIRECTED OTHERWISE.
WORKING CLEARANCES: THE CONTRACTOR IS REQUIRED TO COORDINATE THE MINIMUM WORKING CLEARANCES AND DEDICATED EQUIPMENT REQUIRED BY THE NEC. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH ALL
SUBCONTRACTORS SO THAT ENCROACHMENTS INTO THE RESTRICTED SPACE ARE PREVENTED.
PROVIDE ALL CUTTING, CORING, AND PATCHING REQUIRED FOR ELECTRICAL INSTALLATION. REGISTERED STRUCTURAL ENGINEER APPROVAL IS REQUIRED WHEN CORING OR CUTTING OF STRUCTURAL MEMBERS IS REQUIRED.
PLENUM RATING: ALL CABLING, RACEWAYS, CABLE TIES AND COMPONENTS LOCATED IN CEILING SPACES THAT ARE PLENUMS
SHALL BE PLENUM RATED.
COORDINATE WITH ARCHITECTURAL PLANS, SHOP DRAWINGS, AND OTHER TRADES PRIOR ROUGH-IN FOR FOR DEVICE AND
EQUIPMENT LOCATIONS AND REQUIREMENTS.
BARRIER RATINGS: ALL ELECTRICAL PENETRATIONS THROUGH FIRE RATED BARRIERS SHALL BE SEALED IN ACCORDANCE WITH NEC ARTICLE 300.21. PROVIDE FIRE PUTTY OR SHEET ROCK CONFIGURED FOR UL FIRE RATING WRAPPING ALL BOXES AND PANELS MATCHING WALL AND CEILING FIRE RATING. CONTRACTOR TO PROVIDE SUBMITTAL OF ALL FIRE RATING SYSTEMS TO BE USED. VAPOR BARRIERS: SEAL ALL VAPOR BARRIER PENETRATIONS TO MAINTAIN SYSTEM INTEGRITY.
RACEWAYS EXPOSED TO DIFFERENT TEMPERATURES SHALL BE FILLED WITH AN APPROVED MATERIAL IN ACCORDANCE WITH
NEC TO STOP AIR FLOW..
ACCESS PANELS: PROVIDE ACCESS PANELS FOR ALL LOCATIONS NECESSARY TO ACCESS ELECTRICAL EQUIPMENT AND JUNCTION BOXES. ACCESS PANELS SHALL BE FIRE RATED EQUAL TO OR EXCEEDING THE ADJACENT WALL OR CEILING
CONSTRUCTION AND PAINTED TO MATCH.
REMODEL: TRACE OUT EXISTING CIRCUIT CONFIGURATIONS IMPACTED BY REMODEL REQUIREMENTS. PROVIDE CIRCUIT CONTINUITY FOR ALL CIRCUITS THAT ARE MODIFIED DURING CONSTRUCTION AND PROVIDE TEMPORARY POWER AND LIGHTING FOR ALL AREAS OF THE BUILDING DURING THE RENOVATION WHERE REQUIRED. DEMOLISH ALL ABANDONED CONTROL, SIGNAL AND POWER WIRING BACK TO SOURCE. UPDATE ALL PANEL SCHEDULES TO REFLECT CURRENT CIRCUIT DESCRIPTIONS. REMOVE, RE-INSTALL, CLEAN AND TEST EXISTING EQUIPMENT, DEVICES, FIXTURES ETC WHERE WALLS OR CEILINGS ARE MODIFIED REQUIRING SYSTEM MODIFICATION. EXISTING/REMODEL WIRING THAT CANNOT BE CONCEALED DUE TO EXISTING SOLID CORE OR CONCRETE CONSTRUCTION SHALL BE INSTALLED USING WIREMOLD SURFACE MOUNTED RACEWAY AND BOXES IN FINISHED AREAS AND EXPOSED CONDUIT IN NON-FINISHED AREAS. CIRCUITS POWERING EMERGENCY LIGHTING MUST BE RECONFIGURED TO NOT BE PART OF A MULTI-WIRE (SHARED NEUTRAL) CIRCUIT.
ELECTRICAL DEVICES SHOWN ON THE PLANS AS EXISTING ARE TO BE REPLACED WITH NEW DEVICES AND DEVICE PLATES TO
MATCH THE NEW WORK.
26 01 10 - SUBMITTALS: PROVIDE MATERIAL AND EQUIPMENT SUBMITTAL FOR EACH SPECIFICATION SECTION DENOTED AS REQUIRED AT MINIMUM. SUBMITTALS SHALL BE SUBMITTED ELECTRONICALLY IN PDF FORMAT (UNLESS HARD COPY IS REQUIRED BY OTHER CONTRACT APPLYING TO THE ENTIRE PROJECT). SUBMIT ALL REQUIRED SECTIONS IN A SINGLE SUBMITTAL OR BROKEN INTO NO MORE THAN THE FOLLOWING SEPARATE SECTIONS: “LIGHTING”, “EQUIPMENT”, “WIRING/DEVICES”, AND “SPECIAL SYSTEMS”. ORGANIZE SUBMITTAL AND/OR EACH SECTION BY SPECIFICATION NUMBER FOLLOWED BY ANY MAJOR EQUIPMENT REFERENCE ON THE DRAWINGS WITH ALL OPTIONS AND SELECTIONS HIGHLIGHTED TO DENOTE THE SPECIFIC EQUIPMENT PROPOSED. SUBMITTAL REVIEW IS FOR GENERAL DESIGN AND CONFIGURATION AND DOES NOT RELIEVE THE CONTRACTOR FROM PROVIDING A COMPLETE OPERATIONAL SYSTEM COMPLIANT WITH THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
26 01 21 - RECORD DRAWINGS: MARK UP A SET OF DRAWINGS (REDLINES) SHOWING ALL ELECTRICAL WORK. SHOW DIAGRAMMATIC ROUTING MODIFICATIONS, SIZING, AND CIRCUIT REVISIONS TO THE CONTRACT PLANS. RECORD DRAWINGS SHALL BE KEPT ON SITE AVAILABLE FOR REVIEW DURING THE ENTIRE CONSTRUCTION PERIOD. SUBMIT FINAL REDLINE SET
FOR APPROVAL PRIOR TO FINAL INSPECTION.
26 01 22 - WARRANTY: THE CONTRACTOR SHALL GUARANTEE ALL WORK EXECUTED UNDER THIS CONTRACT TO BE FREE FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM SUBSTANTIAL COMPLETION. ANY FAULTY MATERIALS OR WORKMANSHIP SHALL BE REPAIRED DURING THE GUARANTEE PERIOD AT NO ADDITIONAL COST TO
THE OWNER.
26 05 15 - POWER AND LIGHTING CONDUCTORS: STRANDED COPPER ROUTED IN CONDUIT UNLESS NOTED OTHERWISE.
INSULATION TO BE THHN-2 90 DEGREE C FOR INDOOR APPLICATIONS AND XHHW-2 90 DEGREE C FOR OUTDOOR LOCATIONS, IN UNHEATED SPACES, OR INSTALLED WHILE THE AMBIENT TEMPERATURE IS LESS THAN -7C (20F). ALL CONDUCTORS SHALL BE INSTALLED IN ACCORDANCE WITH NEC REQUIREMENTS FOR AMBIENT TEMPERATURE DERATING, CONDUIT FILL DERATING, AND BOX FILL. PROVIDE UNSHARED DEDICATED NEUTRAL FOR EACH CIRCUIT. BRANCH CIRCUIT WIRING MAY BE INSTALLED IN CABLES WHERE ROUTED CONCEALED AND SUPPORTED BY NEC REQUIREMENTS AND TYPE TYPE W OR EQUAL CORDS WHERE INSTALLED IN ACCORDANCE WITH THE NEC REQUIREMENTS SIZED AS DENOTED IN THE NEC TABLES 400.5(A)(2) AND 400.5(A)(3).
"X" = PROVIDE SUBMITTAL
ELECTRICAL SPECIFICATIONS
480V/277V CONDUCTORS: COLOR CODE CONDUCTORS BROWN, ORANGE, YELLOW, GRAY AND GREEN WITH YELLOW STRIPE.
MINIMUM SIZE CONDUCTORS FOR 15 AND 20 AMP BRANCH CIRCUITS MEASURED FROM THE PANELBOARD TO THE FURTHEST DEVICE ON THE CIRCUIT UNLESS OTHERWISE NOTED ON THE DRAWINGS: 12 AWG UP TO 120 FT, 10 AWG 120 FT TO 200 FT, GREATER THAN 200 FT SIZE CONDUCTORS TO LIMIT VOLTAGE DROP TO 5% OR LESS.
208V/120V CONDUCTORS: COLOR CODE CONDUCTORS BLACK, RED, BLUE, WHITE, AND GREEN. MINIMUM SIZE CONDUCTORS FOR 15 AND 20 AMP BRANCH CIRCUITS MEASURED FROM THE PANELBOARD TO THE FURTHEST DEVICE ON THE CIRCUIT UNLESS OTHERWISE NOTED ON THE DRAWINGS: 12 AWG UP TO 75 FT, 10 AWG 75 FT TO 140 FT, GREATER THAN 140 FT SIZE
CONDUCTORS TO LIMIT VOLTAGE DROP TO 5% OR LESS.
26 05 19 - MC CABLES: METALCLAD (MC) CABLE WITH STEEL OUTER SHEATH. ALLOWED USES DRY WHERE ROUTED
CONCEALED AND PROTECTED.
26 05 29 - HANGARS AND SUPPORTS FOR ELECTRICAL SYSTEMS: SUPPORT ALL ELECTRICAL EQUIPMENT INCLUDING, BUT NOT LIMITED TO, LIGHT FIXTURES, PANELBOARDS, BOXES, CONDUIT, ETC. PER NEC AND IBC SEISMIC REQUIREMENTS. PROVIDE SEISMIC SUPPORT AND DESIGN SEALED BY A LICENSED STRUCTURAL ENGINEER AS A DEFERRED SUBMITTAL TO THE AHJ FOR ALL EQUIPMENT OVER 400 LBS AND, EQUIPMENT OVER 20 LBS MOUNTED GREATER THAN 4FT AFF, CONDUIT 2.5”C OR GREATER AND ALL TRAPEZE OR WALL SUPPORTED RACEWAY 10 LBS/LF OR GREATER. SUPPORT STRUT AND MOUNTING HARDWARE TO
BE GALVANIZED
26 05 30 - RACEWAY: ALL POWER, LIGHTING, CLASS 1, CLASS 2/3 CIRCUITS INSTALLED IN CONDUIT SHALL BE CONCEALED RACEWAY EXCEPT WHERE SPECIFICALLY INDICATED ELSEWHERE IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS.
ELECTRICAL EQUIPMENT AND WIRING CAN BE EXPOSED IN MECHANICAL/ELECTRICAL ROOMS, COOLER/FREEZERS, TELECOMMUNICATION ROOMS, OPEN CEILING SPACES, OR WHERE SPECIFICALLY NOTED. DO NOT ROUTE RACEWAYS ON THE EXTERIOR SURFACE OF THE BUILDING OR THE ROOF UNLESS SPECIFICALLY NOTED OTHERWISE. RACEWAYS CROSSING BUILDING SEISMIC JOINTS OR CONNECTING TO EQUIPMENT WHICH MOVES OR VIBRATES REQUIRE TRANSITION TO FLEXIBLE RACEWAY ACROSS JOINT WITH ENOUGH SLACK TO ALLOW BUILDING MOVEMENT IN ALL DIRECTIONS WITHOUT DAMAGE.
26 05 33 – RIGID METAL CONDUIT (RMC): ANSI C80.1, UL 6. WITH BUSHINGS AT ALL TERMINATIONS. FITTINGS: GALVANIZED MALLEABLE IRON WITH THREADED HUBS FOR ALL CONDUIT ENTRIES AND COUPLINGS. SET SCREW OR RUNNING THREAD FITTINGS ARE NOT PERMITTED. USES: WET OR DRY WHERE INSTALLED BELOW GRADE, IN CONCRETE, STUB UPS, CONCEALED, WHERE EXPOSED TO PHYSICAL DAMAGE, ROUTED ON BUILDING ROOF, SERVICE RISERS, OR WITHIN 10FT OF RACEWAY ROUTED INTO FIXED FOUNDATIONS SUCH AS LIGHT POLE BASE OR STRUCTURE. MUST USE THREADED FITTINGS.
MYERS HUBS WITH GROUNDING LOCKNUTS ARE REQUIRED FOR SERVICE RACEWAYS TO CT'S, METERS AND MAIN
DISCONNECTS.
26 05 34 - ELECTRICAL METALLIC TUBING (EMT): ANSI C80.3, UL 797; GALVANIZED STEEL TUBING. FITTINGS: NEMA FB 1;
GALVANIZED STEEL OR MALLEABLE IRON SET SCREW OR COMPRESSION. DIE CAST OR PRESSURE CAST FITTINGS OR LOCKNUTS ARE NOT PERMITTED. USES: WET OR DRY CONCEALED OR EXPOSED WHERE NOT SUBJECT TO PHYSICAL DAMAGE. WET OR DAMP LOCATIONS REQUIRE RAINTIGHT WET RATED GLAND COMPRESSION COUPLINGS AND CONNECTORS.
NOT PERMITTED FOR SERVICE ENTRANCE RACEWAY, IN CONTACT WITH EARTH, OR IN CONTACT WITH CONCRETE.
26 05 35 - FLEXIBLE METAL CONDUIT (FMC): GALVANIZED OR ZINC COATED FLEXIBLE STEEL CONSTRUCTION. FMC FITTINGS:
GALVANIZED MALLEABLE IRON OR STEEL WITH INSULATED THROATS. USES: DRY SPACES LENGTHS LESS THAN 6FT FOR
CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER MOVABLE OR VIBRATING EQUIPMENT.
LIQUIDTIGHT FLEXIBLE CONDUIT (LTMC): GALVANIZED OR ZINC COATED FLEXIBLE STEEL CONSTRUCTION WITH PVC OUTER JACKET. USES: DRY, DAMP, OR WET LOCATIONS LENGTHS LESS THAN 6FT FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER MOVABLE OR VIBRATING EQUIPMENT.
X 26 30 00 - UPS: DESIGN BASIS: MITSUBISHI 80-KVA 9900 AEGIS UPS. 480V INPUT:208Y/120V 3 PHASE 4 WIRE OUTPUT. UNIT TO INCLUDE 3 BREAKER WRAP AROUND BYPASS SWITCH, STEP DOWN TRANSFORMER, OUTPUT BREAKER DISTRIBUTION, STATIC INTERNAL BY-PASS, REMOTE ANNUNCIATOR, CS141 COMMUNICATION PACKAGE WITH DATA CONNECTION TO BUILDING NETWORK, SEISMIC SUPPORT, AND BATTERY SIZED FOR 120 MINUTE CAPACITY AT 14-KW OF LOAD.
NUM DESCRIPTION
M
G
80/3
80/3
/3
150/3
250/3
'SDP-H'
'UPA'
(E)'UPC'
'CT' 'MD'
'MB'
150/3
40/3
150/3
TO: (E) RTU-1
TO: (E) ELEVATOR
TO: (E) TRANSFORMER FEEDING PNL 'SDP/P'
TO: (E) LIGHTING PNL 'SHA'
TO: (E) LIGHTING PNL 'SHB'
80/3
50/3
(E)'UPB' (E)'UPD'
(D) 65KVA UPS
52KW, 92%
EFFICIENT
'MDP'
30/3
225/3
(E) PNL 'NHA'
225/3
(E)'GDP'
70/3
(E)'EHA'
TO: (E) TRANSFORMER
FEEDING DISCONNECT
WPSE
80KVA
125/3
MANUAL
TRANSFER
SWITCH
(E)480V/150KW
GENERATOR
/3
400/3
/3
/3 4
/3
/3
'ATSS'
200/3
216 DISPATCH
BREAKROOM
(N) BATT
SEE DETAIL 4/E1.1
'MTS'
(E)'ATSE'
125/3
/3
/3
(N)COMBINATION MAINTENANCE
BY-PASS & TRANSFORMER
'(N) UPS'
(N)OUTPUT DISTRIBUTION
(D)'UPS' (D)'BYPASS' (D)BATTERY CABINET
'ATSS'
(E)1/0CU OUTPUT
(E)4 AWG CU INPUTS
11' - 9"
'SDP-H' 'SDP-H'
(N)BATTERY CABINET
'ATSS'
(N)200 AMP 208V OUTPUT
UPS DISTRIBUTION 003
(N)COMBINATION
MAINTENANCE
BY-PASS &
TRANSFORMER
(N) UPS
PRIMARY
WINDINGS
N
G
PRIMARY EQUIPMENT GROUND
CONDUCTOR (EGC) PER INCOMING
FEEDER. SEE FEEDER SCHEDULE.
PROVIDE GROUNDING ELECTRODE CONDUCTOR TO BUILDING STEEL
BONDED WITH EXOTHERMIC OR IRREVERSIBLE CRIMP LUG. WHEN BUILDING
STEEL IS NOT AVAILABLE OR NOT ELECTRICALLY CONTINUOUS TO
ELECTRICAL SERVICE, PROVIDE BOND CONDUCTOR ROUTED TO SERVICE
EQUIPMENT. WHEN MULTIPLE TRANSFORMERS ARE BONDED TO A SHARED
CONDUCTOR PROVIDE 3/0 AWG CU (250 KCMIL AL WHEN APPROVED) IN
ACCORDANCE WITH NEC FOR MULTIPLE SEPARATELY DERIVED SYSTEMS.
SECONDARY BONDING JUMPER (BJ).
SEE FEEDER SCHEDULE.
PRIMARY RACEWAY AND
CONDUCTORS PER DRAWINGS
SECONDARY RACEWAY AND
CONDUCTORS PER DRAWINGS
TYPICAL LIQUID TIGHT FLEXIBLE
CONDUIT CONNECTION FOR PRIMARY
AND SECONDARY CONNECTIONS
TYPICAL GROUNDING BUSHING
BONDED TO THE GROUND LUG
PROVIDE ADDITIONAL GROUND LUGS AS REQUIRED
FOR TERMINATION BONDED TO ENCLOSURE
PROVIDE BOND AT THE NEAREST POINT AVAILABLE
TO METALLIC WATER PIPING SYSTEMS IN THE AREA
SERVED BY THE SEPARATELY DERIVED SYSTEM.
(CONNECTIONS MUST BE ACCESSIBLE)
TRANSFORMER ENCLOSURE
1 AWG - 1/0 AWG
2/0 AWG - 3/0 AWG
> 3/0 AWG - 350 KCMIL
> 350 KCMIL - 600 KCMIL
> 600 KCMIL - 1100 KCMIL
> 1100 KCMIL
XFMR SECONDARY
6 AWG
4 AWG
2 AWG
1/0 AWG
2/0 AWG
12.5% * XFMR SECONDARY
JUMPER OR ELECTRODE
2/0 AWG - 3/0 AWG
> 500 KCMIL - 900 KCMIL
> 900 KCMIL - 1750 KCMIL
> 1750 KCMIL
XFMR SECONDARY
4 AWG
2 AWG
1/0 AWG
3/0 AWG
4/0 AWG
12.5% * XFMR SECONDARY
> 3/0 AWG - 250 KCMIL
> 250 KCMIL - 500 KCMIL
COPPER CONDUCTORS ALUMINUM OR COPPER-CLAD CONDUCTORS
"XFMR SECONDARY" DENOTES THE AREA OF THE LARGEST
UNGROUNDED SECONDARY CONDUCTOR OR EQUIVALENT
AREA FOR PARALLEL SECONDARY CONDUCTORS.
">" DENOTES GREATER THAN.
REQUIRED MINIMUM CONDUCTOR SIZE
JUMPER OR ELECTRODE
REQUIRED MINIMUM CONDUCTOR SIZE
2 AWG OR SMALLER 8 AWG 1/0 AWG OR SMALLER 6 AWG
SYSTEM BONDING JUMPER. SEE MINIMUM
CONDUCTOR SIZE TABLE ABOVE.
GROUNDING ELECTRODE CONDUCTOR. SEE
MINIMUM CONDUCTOR SIZE TABLE ABOVE.
X0
SECONDARY
WINDINGS
"X0" DENOTES GROUND BOND POINT
OF SECONDARY WINDINGS
RE
E
TIG S
R
ED ALEP OR F OSS I N
49TH
E
NEIGNE
R
S ATA
TE OF ALASK
EE - 9773
ERIC D. COWLING
SHEET NO.
JOB NO.
DATE
DRAWN
REVIEWED
REVISIONS
E
IC
E N
G
IN
E E
R S
IN
C
E
IC
J O
B N
O
W W
W .E
IC
E
N G
.C O
M
.3
.9
A
N C
H O
R A
G E
A
K
O L D
S E
W A
R D
H W
Y S
T E
E L E
C T
R I C
A L
E
N G
I N
E E
R S
C O
R P
O R
A T
IO
N
L
IC
E N
S E
A
E C
C
T H
IS
S
H E
E T
I S
F U
L L S
IZ
E
A T
"x
A C
T U
A L
/1
/2
:0
:5
P M
C
U se rs \E ri cC o w li n g \E
IC
E n g in e e rs
\D e si g n
F il e s\
P ro je ct s\ E
\E
-4
A
K R a il ro a d A
O C
\D E
S \E
-4
E
S h t2
A
K R a il ro a d A
O C
.r v t
E1.1
ONE-LINE
DIAGRAMS, DETAILS,
AND SCHEDULES
E25-4776
06/11/2025
KRR
EDC
A L
A S
K A
R A
IL
R
O A
D A
O C
U P
S R
E P
L A
C E
M E
N T
E
W H
IT
N
E Y
R D
A N
C H
O R
A G
E A
K
E
-4
6/12/25 q c:
/1
/2
:0
:4 f c-vi sO n
S h t
.0
;0 .0
:0 .0
/0
FEEDER SCHEDULE
ID AMPERAGE FEEDER (MINIMUM) CU UON
UPA 200 2"C, (4)3/0 AWG, (1)4 AWG BJ
UPS 125 1.5"C, (3)1 AWG, (1)6 AWG EGC
REF NOTE
001 DEMOLISH THE EXISTING 80 AMP, 3 POLE CIRCUIT BREAKERS TO MAKE ROOM
FOR THE NEW BREAKER.
002 PROVIDE NEW 125 AMP, 3 POLE SQUARE D KA36125 CIRCUIT BREAKER.
003 UPGRADE FEEDER TO EXISTING 200 AMP RATED PANEL 'UPA'. CONTRACTOR
MAY EXTEND AND REUSE EXISTING 2" RACEWAY FOR NEW CONDUCTORS
WHERE FEASIBLE. LENGTH OF THE FEEDER IS APPROXIMATELY 120FT.
004 NEW FEEDER TO BE ROUTED OVERHEAD. EXISTING UPS INPUT FEEDERS TO
BE ABANDONED IN PLACE.
# REFERENCED SHEET NOTES
CONTRACTOR TO VERIFY EQUIPMENT TO BE PROVIDED
WITH SERVING UTILITY PRIOR TO PROCUREMENT. ANY
DECREASE OF TRANSFORMER %Z, CONDUCTOR
LENGTHS, OR INCREASE IN TRANSFORMER KVA OR
CABLE SIZES TO BE REPORTED TO CONTRACT OFFICER
FOR RECALCULATION OF SCA PRIOR TO PROCUREMENT.
DISTRIBUTION SCCR SCHEDULE
EQUIPMENT SHALL HAVE AN SCCR EXCEEDING THE
SHORT CIRCUIT AMPS "SCA" OR MINIMUM SCCR, WHICH
EVER IS GREATER. EQUIPMENT SHALL BE FULLY
RATED. BRANCH CIRCUIT PANELS RATED 225 AMPS OR
LESS MAY USE MANUFACTURER TESTED
COMBINATIONS PER NEC 240.86(B) WHERE THE MOTOR
LOAD DO NOT EXCEED 1% OF THE LOWEST AIC RATED
DEVICE IN THE PANEL PER NEC 240.86(C).
THE "MIN FT" COLUMN DENOTES DISTANCE USED FOR
'SCA' CALCULATION. ACTUAL DISTANCE IS EXPECTED
TO BE LONGER. IF CONDUCTOR LENGTH IS LESS THAN
"MIN FT", CONTRACTOR SHALL SUBMIT A VARIATION
REQUEST FOR RECALCULATION. THIS MAY REQUIRE
ASSOCIATATED EQUIPMENT MODIFICATIONS.
(BASIS FOR CALCULATION)
ASSUMED UTILITY SYSTEM CONFIGURATION
SERVICE TRANSFORMER
KVA %Z
SCA SECONDARY
LINE-LINE LINE-NEUTRAL
150 1.20 15,027 15,027
AMPS
- FOR CALCULATION ONLY -
SERVICE LATERAL MIN FT
600 2EA: (4)350 KCMIL 86
EQUIP ID OPD SCA MIN SCCR XR MIN FT
SDP-H 400 A 11,780 14,000 2.07 26
UPA 200 A 3,928 10,000 1.17 96
UPS 10,636 0.00 27
SCALE: NONEE1.1
3 REVISED PARTIAL POWER ONE-LINE DIAGRAM
SCALE: 1/2" = 1'-0"E1.1
1 DEMOLITION PLAN - ELECTRICAL ROOM
SCALE: 1/2" = 1'-0"E1.1
2 NEW WORK - ELECTRICAL ROOM
SCALE: NONEE1.1
4 TYPICAL TRANSFORMER GROUNDING ONE-LINE DIAGRAM
NUM DESCRIPTION
| Sheets |
| E0.1 - LEGEND AND SPECIFICATIONS |
| E1.1 - ONE-LINE DIAGRAMS, DETAILS, AND SCHEDULES |
File details come from the government source that posted it. Updated .