2025-05-23_-_UNIT_1_REHABILITATION_PLANS-_BID_SET.pdf

PDF 7 MB Posted

Attached to
Wastewater Treatment Plant Unit 1 Rehabilitation
Solicitation number
PSUT-25-07
Issued by
Broward County, Florida

About this file

This is a comprehensive bid set document for the City of Pembroke Pines Utilities Department for the Wastewater Treatment Plant Unit 1 Rehabilitation project located at 13955 Pembroke Road, Pembroke Pines, Florida 33027. The project scope includes complete renovation and painting of Treatment Unit 1, with major components including removal and replacement of the fine bubble diffuser system, clarifier drive, Return Activated Sludge (RAS) box and valve, installation of a new spray wash system for the effluent trough, grit cleaning and removal, renovation and painting of the entire unit, installation of a closed-loop air header system with process air piping, and comprehensive electrical and instrumentation control modifications. The bid set includes detailed construction documents with electrical plans (sheets E-1 through E-7) covering demolition, site plans, one-line and riser diagrams, electrical details, and instrumentation plans (sheets I-1 through I-3) with P&ID diagrams and installation details. The mandatory pre-bid meeting is scheduled for Monday, July 14, 2025, at 9:00 am at the treatment plant facility, with written questions due by Tuesday, July 29, 2025, and sealed bids due by Tuesday, August 12, 2025, at 2:00 pm. The project is expected to be completed within 365 calendar days from the Notice to Proceed, with liquidated damages assessed at $1,500 per day for project delays.

The estimated project cost is approximately $2,400,000, requiring bidders to submit proposal security of 5% of the total cumulative base amount and obtain both Payment and Performance Bonds for 100% of the contract price. The project is locally funded and not supported by federal grants or funding sources. Contractors must comply with E-Verify system registration, background screening requirements, and provide comprehensive insurance coverage including general liability, workers' compensation, and auto liability. Successful bidders must submit detailed shop drawings, technical manuals, and documentation of previous experience on comparable wastewater treatment plant rehabilitation projects. Contract compensation will be provided through monthly payments based on unit pricing, with payment not to exceed a specified maximum annual amount. The City of Pembroke Pines will evaluate bids based on compliance with specifications, contractor qualifications, and adherence to local requirements including public entity crime certifications, equal benefits provisions, and drug-free workplace compliance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET

PEMBROKE PINES COMMISSION

SCOPE OF WORKC-1

UTILITIES DEPARTMENT

8300 SOUTH PALM DRIVE

PEMBROKE PINES, FL 33025

CITY OF PEMBROKE PINES

C-0

DATENO. BY DESCRIPTION

SHEET No.

CITY OF PEMBROKE PINES

WWTP UNIT 1 REHABILITATION PLAN

13995 PEMBROKE RD, PEMBROKE PINES, FL 33027

COVER SHEET

RENOVATION AND PAINTINGC-2

ELECTRICAL LEGEND AND NOTESE-1

PHOTOS AND EAST ELECTRICAL BUILDINGE-3

ELECTRICAL SITE PLAN -DEMOLITIONE-2

E-4

E-5

E-6

E-7 I-1

I-2

I-3

ONE LINE AND RISER DIAGRAM

MODIFIED TREATMENT UNIT ELECTRIC PLAN

ELECTRICAL DETAILS - SHEET 1

ELECTRICAL DETAILS- SHEET 2

INSTRUMENTATION LEGEND AND NOTES

P&ID - TREATMENT UNIT NO. 1

INSTRUMENTATION DETAILS

C-3 CLOSED LOOP AIR HEADER SYSTEM

VICE MAYOR - DISTRICT 4

DISTRICT 2

DISTRICT 1

DISTRICT 3

MAYOR

THOMAS GOOD Jr.

MARIA RODRIGUEZ

ANGELO CASTILLO

JAY D. SCHWARTZ

CITY MANAGERCHARLES F. DODGE

MICHAEL A. HERNANDEZ

SEAL:R E V I S I O N S

C

ITY O

F P .P

. P

LA

N S

U B

M

ITTA

L:

DATENO. BY DESCRIPTION

O F

S H

E E

T:

R

S H

E E

T N

U M

B E

R

S U

B M

ITTA

L D

A

TE

S C

A

LE

: WASTEWATER TREATMENT PLANT

UNIT 1 REHABILITATION

13955 Pembroke Rd, Pembroke Pines, FL 33029

RENOVATION AND PAINTING

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

C L

O S

E D

L O

O P

A

IR

H E

A D

E R

S Y

S T

E M

SEAL:R E V I S I O N S

C

ITY O

F P .P

. P

LA

N S

U B

M

ITTA

L:

DATENO. BY DESCRIPTION

O F

S H

E E

T:

R

S H

E E

T N

U M

B E

R

S U

B M

ITTA

L D

A

TE

S C

A

LE

WASTEWATER TREATMENT PLANT

UNIT 1 REHABILITATION

13955 Pembroke Rd, Pembroke Pines, FL 33029

SCOPE OF WORK

l l

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

E-1 N.T.S.

E

LE

C

TR

IC

A

L

LE

G E

N D

A N

D N

O

TE

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

N.T.S.

E-2

E

LE

C

TR

IC

A

L S

IT

E

P

LA

N

D E

M O

LI

TI

O N

ELECTRICAL SITE PLAN - DEMOLITION

SCALE: 1" = 20'-0"

PHOTO E1: STAIRWAY TO TU-1

NOT TO SCALE

PHOTO E2: EXPOSED CONDUITS

NOT TO SCALE

PHOTO E3: EXPOSED CONDUITS

NOT TO SCALE

CONTRACTOR SHALL REMOVE THE

EXISTING PANELS, DISCONNECTS, ETC.

DURING REHAB OF TREATMENT UNIT NO.1

REMOVE ALL EXPOSED CONDUITS ON

TREATMENT UNIT NO.1, INDICATED OR

NOT BACK TO SOURCE. CUT CONDUITS

TO THE GROUND ENTRY POINTS AND

REMOVE WIRES BACK TO SOURCE.

REMOVE ALL EXPOSED CONDUITS ON

TREATMENT UNIT NO.1, INDICATED OR NOT

BACK TO SOURCE. CUT CONDUITS

TO THE GROUND ENTRY POINTS AND REMOVE

WIRES BACK TO SOURCE.

REMOVE ALL EXISTING JUNCTION

BOXES DURING REMOVAL OF

EXISTING EXPOSED CONDUITS (TYPICAL).

REMOVE EXISTING PHOTOCELL

REFER TO OTHER DISCIPLINE DRAWINGS

FOR REMOVAL OF THE EXISTING HANDRAIL,

WALKWAY, GRATING, TREATMENT UNIT

WALL, MECHANISM, ETC. AND PERFORM

REMOVAL OF EXISTING CONDUITS AS WELL

AS INSTALLATION OF NEW CONDUITS

ACCORDINGLY.

REMOVE EXISTING LIMIT SWITCH. NEW LIMIT SWITCH

SHALL BE INSTALLED SIMILARLY AT THE SAME LOCATION.

DEMOLITION NOTES

CONTRACTOR SHALL COORDINATE WITH ALL OTHER

DISCIPLINES FOR REHABILITATION OF THE EXISTING

TREATMENT UNIT NO.1 AND ASSOCIATED STAIRWAY,

WALKWAY, ETC. DISCONNECT POWER WIRES BEFORE

DEMOLITION BEGINS. DISCONNECT ALL OTHER WIRES AND

REMOVE BACK TO SOURCE. REMOVE ALL PANELS AND

INSTRUMENTS BEFORE DEMOLITION BEGINS. COORDINATE

WITH OWNER FOR EQUIPMENT TO BE SALVAGE AND TURN

OVER TO THE OWNER. OTHERWISE, DISPOSE ALL OTHER

ITEMS ACCORDINGLY. REMOVE ALL EXPOSED CONDUITS

COMPLETELY. CUT UNDERGROUND CONDUITS FLUSH WITH

FLOOR OR WALL OR GRADE AND CAP.

REMOVE THE EXISTING LIGHT POLES LOCATED ON WALKWAY

OF TREATMENT UNIT NO.1 AND TURN OVER TO THE OWNER.

DISPOSE THEM IF NOT WANTED BY OWNER. CONTRACTOR

SHALL FIELD DETERMINE THE EXISTING LIGHTING CIRCUIT AT

TREATMENT UNIT NO.1 LIGHT POLES THAT WILL BE REMOVED.

MODIFY EXISTING LIGHTING CIRCUIT AS NEEDED TO KEEP THE

REMAINING LIGHT POLES AT REMAINING LIGHTS, INCLUDING

LIGHT POLES AT THE TREATMENT UNIT NO.2 FUNCTIONAL.

1.

2.

REMOVE EXISTING LIGHT POLES

AT TREATMENT UNIT NO.1 DURING

REHABILITATION. TOTAL OF 6.

EXISTING LIGHT POLE AT

TREATMENT UNIT NO.2 SHALL

REMAIN.

REFER TO DRAWING E-03

FOR ENLARGED EAST

ELECTRICAL BUILDING

REFER TO DEMOLITION NOTE NO.1 AND NO.2

FOR TREATMENT UNIT NO.1.

REPLACE EXISTING MAGNETIC

FLOWMETER AND PANEL

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

E-3 N.T.S.

P H

O

TO

S A

N D

E A

S T

E

LE

C

TR

IC

A

L B

U

IL

D

IN

G

PHOTO E5: INSTRUMENT PANELS

NOT TO SCALE

PHOTO E4: TREATMENT UNIT NO.1

NOT TO SCALE PHOTO E6: FLOWMETER AND PANEL

NOT TO SCALE

EAST ELECTRICAL AND BLOWER BUILDING

SCALE: 1/4" = 1'-0"

EXISTING PLC-2A PANEL

EXISTING LIGHT POLE AT TREATMENT UNIT NO.1

SHALL BE REMOVED AND TURN OVER TO THE OWNER.

TYPICAL

CONTRACTOR SHALL REMOVE THE

EXISTING PANELS, DISCONNECTS, ETC.

DURING REHAB OF TREATMENT UNIT NO.1

REMOVE ALL EXPOSED CONDUITS ON

TREATMENT UNIT NO.1, INDICATED OR

NOT BACK TO SOURCE. CUT CONDUITS

TO THE GROUND ENTRY POINTS AND

REMOVE WIRES BACK TO SOURCE.

REPLACE EXISTING MAGNETIC FLOWMETER

AS SHOWN ON I-DRAWINGS

REPLACE EXISTING FLOWMETER

DISPLAY PANEL AS SHOWN ON

I-DRAWINGS

REMOVE EXISTING CLARIFIER

NO.1 DRIVE STARTER

EXISTING EMDP-2

EXISTING EMDP-1

EXISTING BLOWER#6

STARTER

EXISTING CLARIFIER

NO.2 DRIVE STARTER (ABOVE)

EXISTING FROTH SPRAY#2

STARTER (BELOW)

EXISTING PANEL ELP1EXISTING TRANSFORMER

EXISTING 120V SUB-PANEL

AND LIGHTING CONTACTOR FOR TU#1 AND TU#2

EXISTING EAST

SWITCHBOARD

CONTINUED ON DRAWING E-5

CONTINUED ON DRAWING E-5

SAW CUT EXISTING CONCRETE SLAB

FOR NEW CONDUITS INSTALLATION.

(TYPICAL)

NEW NEMA 4X

316 S.S. J-BOX

NEW NEMA 4X 316 S.S. J-BOX

(FIELD ADJUST LOCATION TO

AVOID CONFLICT WITH DOOR)

SAW CUT EXISTING CONCRETE SLAB

FOR NEW CONDUITS INSTALLATION.

(TYPICAL)

LOCATION: EAST BLOWER ROOM EMDP-2

3P-250A

MCP

3P-250A

MCP

3P-15A

MLO 600A, 3 PHASE, 4 WIRE,65 KAIC

VFD

VFD

BLOWER

#1

BLOWER

#2

CLARIFIER

DRIVE UNIT #1

AT

TREATMENT

UNIT #1

2P-50A

PANEL "ELP1"

XFMR

25 KVA

480-120/240, 1Ø, 3W

3P-15A

LIFT STATION

CONTROL PANEL

EXISTING EAST

MAIN SWBD

NOT TO SCALE

EXISTING EAST BLOWER DISTRIBUTION PANEL NO.2 (EMDP-2) ONE LINE

LOCATION: EAST BLOWER ROOM EMDP-2

3P-250A

MCP

3P-250A

MCP

3P-15A

MLO 600A, 3 PHASE, 4 WIRE,65 KAIC

VFD

VFD

BLOWER

#1

BLOWER

#2

CLARIF.

DRIVE

(RACK

DRIVE)

2P-50A

PANEL "ELP1"

XFMR

25 KVA

480-120/240, 1Ø, 3W

3P-15A

LIFT STATION

CONTROL PANEL

EXISTING EAST

MAIN SWBD

NOT TO SCALE

MODIFIED EAST BLOWER DISTRIBUTION PANEL NO.2 (EMDP-2) ONE LINE

TREATMENT UNIT#1

CONTROL PANEL

(LCP-TU1)

3/4"C, 3#12, 1#12G

3/4"C, 3#12, 1#12G

EXISTING PANEL "ELP1"

3/4

EXISTING

SUBMERSIBLE

SPRAY PUMP

AT TREATMENT

UNIT #1

EXST. EXST.

EXISTING LIGHT POLES

AT TREATMENT UNIT NO.1

TO NEXT

LIGHT POLE

IN TU#2

FROTH

SPRAY

PUMP

3/4

MOTORIZED

VALVE

(TU1-CV1)

MOV

1"C, 10#14, 1#14G

J

4X SS

3/4"C, 2#14, 1#14G

(TYP.)

EXISTING LIGHTING

CONTACTOR

1 CONTRACTOR SHALL REMOVE THE EXISTING STARTER, CONDUITS/WIRES, ETC.

ASSOCIATED WITH THE TREATMENT UNIT NO.1 DRIVE. TURN OVER STARTER,

DISCONNECT, ETC. TO THE OWNER, DISPOSE THEM IF NOT WANTED BY THE OWNER.

EXISTING BREAKER AT EMDP-2 SHALL BE REUSED TO POWER THE PROPOSED

TREATMENT UNIT NO.1 CONTROL PANEL.

CONTRACTOR SHALL FIELD VERIFY THE EXISTING TU#1 AND TU#2 LIGHTING CIRCUIT

FROM THE EXISTING LP PANEL THRU EXISTING LIGHTING CONTRACTOR/TIME CLOCK

LOCATED IN THE EAST ELECTRICAL BUILDING - EAST BLOWER ROOM. DISCONNECT

AND REMOVE EXISTING LIGHT POLES ON TOP OF TU#1 AND MODIFY THE LIGHTING

CIRCUIT SO THAT TU#2 LIGHTING WILL STILL FUNCTIONAL. IF NEEDED, PROVIDE AND

INSTALL NEW 3/4", 2#10, 1#10G FROM THE EXISTING LIGHTING CONTACTOR TO THE

NEAREST LIGHT POLE AT TU#2 WALKWAY BEFORE DISCONNECTING LIGHTING

CIRCUIT AT TU#1.

CONTRACTOR SHALL COORDINATE WITH PACKAGED SYSTEM SUPPLIER FOR EACH

INDIVIDUAL COMPONENT LOCATION AND INSTALL CONDUITS/WIRES ACCORDINGLY.

KEYED NOTES:

3P-15A

SPD

3P-15A 3P-30A 3P-30A

SPARE SPARE SPARE

3P-30A 3P-30A

SPARE SPARE

3P-15A

4X SS

3/4"C, 3#12, 1#12G

3/4"C, 3#12, 1#12G

EATON PANEL (PRL4B)EATON PANEL (PRL4B)

3/4"C, MSC

(8x8x6)

EXISTING

PLC-2A

PANEL

LE-TU1SB1 FIT-TU1SB1

AE- TU1DO1

FUTURE

AIT-TU1DO1

FUTURE

FE-TU1IF1 FIT-TU1IF1

M

RAS/WAS

MOTORIZED

VALVE

(TU1-CV1)

LEVEL

TO FLOW

MEASUREMENTFIT-TU1EF1LE-TU1EF1

AE-TU1DO1

FUTURE

AIT-TU1DO1

FUTURE

3/4"C, 1#TSP

3/4"C, 1#TSP

3/4"C, 1#TSP

3/4"C, 2#TSP

1"C, 20#14, 1#14GSPARE 3/4"C

PLC-2A PANEL RISER DIAGRAM

SPARE 3/4"C

NOT TO SCALE

EXISTING PANEL ELP-1

EXISTING PANEL "ELP1"

NOT TO SCALE

MODIFIED PANEL ELP-1

LEVEL

TO FLOW

MEASUREMENT

3/4"C, 2#12, 1#12G

J

4X SS

FIT-TU1IF1

3/4"C, 2#12, 1#12G

FIT-TU1SB1 FIT-TU1EF1

NEW LIGHT POLES

AT TREATMENT UNIT NO.1

EXISTING LIGHTING

CONTACTOR

3/4"C, 2#12, 1#12G

3/4"C, 2#12, 1#12G

NEW

JBOX-I1

(4X SS)

LOCATION:

NEAR THE

STAIR

LANDING

OF TU#1

MINIMUM

DIMENSION:

12"x12"x8"

LOCATION:

EAST

ELECTRICAL

ROOM

2"C, 8#TSP

YC03

4X SS

ZS

-T

U 1L

S1

ZS

-T

U 1L

S2

TS

-T

U 1T

S1

SV

-T

U 1S

V1

LIMIT SWITCHES,

SV, TORQUE

SWITCH

NEW

JBOX-C2

NEW JBOX-P1

4X SS

(10x10x8) 4X SS

SEE DWG E-5

SEE DWG E-5

YC01

YC02

YC04

SPARE 1"C

4X

SS

YC05

NEW JBOX-P1

(10x10x8) 4X SS

TREATMENT UNIT #1

CONTROL PANEL

1"C, 20#14, 1#14G

YC06

SPARE 1"C

LOCATION:

NEAR THE

STAIR

LANDING

OF TU#1

LOCATION:

NEAR THE

STAIR

LANDING

OF TU#1

LOAD SUMMARY: THIS IS A LOAD REPLACEMENT ONLY.

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

E-4 N.T.S.

O N

E L

IN

E

A N

D R

IS

E

R D

IA

G

R A

M

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

E-5 N.T.S.

M O

D

IF

IE

D

T R

E A

TM

E

N T

U N

IT

E

LE

C

TR

IC

P

LA

N

MODIFIED TREATMENT UNIT NO.1 - ELECTRICAL PLAN

SCALE: 1" = 10'-0"

NEW LIGHT POLE WITH

BRACKET (MOUNT TO

THE SIDE OF WALKWAY)

TYPICAL OF SIX NEW LIGHT

POLES FOR TU#1 (SEE DETAIL)

EXISTING LIGHT POLE AT

TREATMENT UNIT#2

(TO REMAIN)

FE

TU1IF1

NEW FLOW TRANSMITTER

WITH PIPE STAND AND SUNSHIELD

FIT

TU1IF1

CLARIFIER DRIVE

NEW TREATMENT UNIT

NO.1 CONTROL PANEL

FUTURE INSTRUMENT

(STUB-OUT AND CAP)

FOR FUTURE USE

NEW ULTRASONIC

LEVEL SENSOR AND

TRANSMITTER FOR

RAS/WAS FLOW (ON

SPLITTER BOX)

NEW DISCONNECT

FOR MOV

(TU1CV1)

ZS

TU1LS1

ZS

TU1LS2

NEW ULTRASONIC LEVEL

SENSOR FOR EFFLUENT

FLOW MEASUREMENT

FROTH SPRAY WATER

FIELD ROUTE EXPOSED CONDUITS

ALONG THE WALKWAY SUPPORTS.

SUPPORT EXPOSED CONDUITS AS

PER NEC REQUIREMENTS. TYPICAL

CONDUIT CROSSING WALKWAY

SHALL BE UNDER THE WALKWAY,

INDICATED OR NOT, TYPICAL.

AERATION

ZONE

AERATION

ZONE

CLARIFIER

ZONE

CHLORINE

CONTACT

DIGESTER

ZONE

FIT

TU1EF1

V-NOTCH WEIRS

LEVEL TRANSMITTER

WITH PIPE STAND.

TS

TU1TS1

TORQUE

SWITCH

E-7

1 CONTRACTOR SHALL PROVIDE AND INSTALL NEW LIGHT POLES WITH SUPPORT

BRACKETS AS PER ELECTRICAL DETAIL DRAWING. FIELD ROUTE EXPOSED

CONDUITS TO AVOID CONFLICT AND ADJUST ACCORDINGLY. ROUTE EXPOSED

CONDUITS EITHER BELOW THE WALKWAY OR SIDE OF THE HANDRAIL AS DIRECTED

BY THE FIELD ENGINEER DURING CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH APPROVED SHOP DRAWINGS OF THE

CONTROL PANEL AND ADJUST THE MOUNTING BASED ON THE ACTUAL DIMENSION

OF THE PANEL TO MEET THE NEC CODE CLEARANCES. IF NEEDED, OFFSET PANEL

OUTSIDE THE HANDRAIL AS NEEDED TO HAVE CLEARANCE IN FRONT OF THE PANEL.

PROVIDE AND INSTALL ALL NECESSARY "316 STAINLESS STEEL L" BRACKETS AND

316 STAINLESS STEEL HARDWARE FOR MOUNTING OF THE PANEL.

RECONNECT EXISTING GROUND WIRES TO THE TANK AFTER REHABILITATION OF THE

TREATMENT UNIT. EXTEND GROUND WIRES AS NEEDED. THERE ARE 3 EXISTING

CONNECTIONS AT THE EXISTING TANK.

ONLY INFLUENT FLOWMETER WILL BE INSTALLED AT THE GROUND LEVEL USING

ELECTRICAL RACK. OTHER EQUIPMENT AND PANELS ARE LOCATED ON THE UPPER

LEVEL OF THE TREATMENT UNIT. SEE OTHER DISCIPLINE DRAWINGS FOR ELEVATION

VIEWS.

CONTRACTOR SHALL PROVIDE AND INSTALL TWO NEW GROUND ROD NEXT TO THE

EXISTING GROUND WIRE OF THE TREATMENT UNIT NO.1 TANK AND BOND THEM

TOGETHER USING MECHANICAL LUG CONNECTION. FIELD LOCATE ACTUAL

LOCATION TO INSTALL GROUND RODS AND INSTALL ACCORDINGLY.

KEYED NOTES:

MOUNT NEW JUNCTION BOXES

ON THE BACK SIDE OF STAIR

LANDING. FIELD ROUTE UNDERGROUND

CONDUITS. (JBOX-P1, JBOX-C1, JBOX-I1)

FIELD ROUTE UNDERGROUND

CONDUITS TO NEW JUNCTION

BOXES AND ADJUST TO AVOID

CONFLICTS WITH EXISTING

CONDITIONS. (TYPICAL)

SAW CUT EXISTING CONCRETE SLAB

FOR NEW CONDUITS INSTALLATION.

(TYPICAL)

FIELD ROUTE EXPOSED CONDUITS UNDER

THE STAIR USING UNISTRUT TO OFFSET.

EXPOSED CONDUITS SHALL NOT OBSTRUCT

TO THE STAIR STEPS.

APPROXIMATE LOCATION

OF EXISTING GROUND WIRE

CONNECTION TO TANK

(TYPICAL OF THREE LOCATIONS

AROUND THE TANK). BOND

NEW GROUND WIRE TO

EXISTING GROUND WIRE.

ELECTRICAL NOTES

ELECTRICAL CONDUIT ROUTING IS SHOWN FOR ILLUSTRATION PURPOSES ONLY.

CONTRACTOR SHALL FIELD VERIFY THE CONDUIT ROUTING WITH EXISTING

CONDITIONS AND PROPOSED PIPING, DRAINAGE, ETC. TO AVOID CONFLICTS AND

ADJUST ACCORDINGLY. CONTRACTOR SHALL VISIT THE SITE AND DETERMINE

CONDITIONS AT THE EXISTING SITE BEFORE SUBMITTING HIS/HER BID. SOME

CONDUIT ROUTINGS REQUIRE FIELD DETERMINATION OF THE ROUTINGS TO AVOID

CONFLICTS WITH EXISTING CONDITIONS.

CONTRACTOR SHALL SAW CUT EXISTING SIDEWALK, ROADWAY, CONCRETE SLAB,

ETC. FOR CONDUIT CROSSING AND REPAIR/RESTORE TO MATCH EXISTING

CONDITION.

NO CONDUIT SHALL PENETRATE AN OUTDOOR ELECTRICAL PANEL FROM TOP. FOR

OUTDOOR ELECTRICAL PANELS, ALL CONDUIT PENETRATIONS SHALL BE FROM THE

BOTTOM OR SIDE. PROVIDE NEMA 4X 316 STAINLESS STEEL J-BOX AS NECESSARY

TO ASSIST CONDUITS ENTERING OUTDOOR ELECTRICAL PANEL. OUTDOOR PANEL

SHALL BE PROVIDED WITH HOFFMAN VENT DRAIN OR EQUAL.

CONTRACTOR SHALL KEEP THE SEPARATION BETWEEN POWER AND

INSTRUMENTATION YARD CONDUITS AS PER DRAWING E-1, NOTE 17.

1.

2.

3.

4.

NEW GROUND ROD

(TYPICAL)

CONTINUED ON DRAWING E-3

LE

TU1EF1

FIT

TU1SB1

LE

TU1SB1

YC01

YC02

YC03

YC04

YC05

YC06

YC01-06

DISCONNECT ON

HANDRAIL (TYP.)

DISCONNECT ON

HANDRAIL (TYP.)

CHANNEL-GLOBE STRUT,

UNISTRUT OR EQUAL

ANCHOR TO WALL WITH 1/2" DIA. X 4"

STAINLESS STEEL CONCRETE ANCHORS,

WITH SUPPORTS AT 5"-0" MAXIMUM.

MOUNTING DETAILS

CONDUIT PIPE STRAP

TRAPEZE ASSEMBLY

NOTES:

CONDUIT SUPPORT

NOT TO SCALE

STAGGER JOINTS

USE QUEEN CITY PLASTIC SPACERS

APPLIES TO CONCRETE ENCASED CONDUIT.

NOT TO SCALE

HORIZONTAL STAGGERING OF SPACERS AND JOINTS

9"

OR EQUAL.

9"

SPACER REQUIREMENTS.

OF CONDUIT AS PER NEC

DISTANCE DEPENDS ON SIZE

MIN

9"

CONDUIT GROUNDING

(GROUND ONE

ONLY)

END OF CONDUIT

ENCLOSURE

EQUIPMENT

GROUND WIRE

GROUNDING BUSHINGS

NOT TO SCALE

CONDUIT

RIGID

LOCKNUTS

ALL CONDUIT SHALL BE GROUNDED

WITH "O-Z/GEDNEY" TYPE BLG

316 STAINLESS STEEL THREADED ROD SUPPORT

FROM BUILDING STRUCTURE. MINIMUM 38" DIA.

1 1/2" X 1 1/2" STAINLESS

STEEL CHANNEL

316 STAINLESS STEEL CONDUIT

CLAMP

1. THIS DETAIL TYPICAL FOR BOTH VERTICAL AND HORIZONTAL

MOUNTING

2. CHANNEL AND ALL SUPPORT DEVICES TO BE 316 STAINLESS

STEEL.

3. CHANNELS TO BE SPACED 5' MAXIMUM.

TYP

TYP TYP

5 6

TYP

CONDUIT ENTRANCE

WALL

OLB CONDULETS

EXISTING BUILDING

NOT TO SCALE

FINISH GRADE

TYP

WALL PENETRATION

ON WALL E-6

INSTRUMENTATION GROUNDING & SURGE PROTECTION

TVSS

GROUND WIRE FROM

INSTRUMENT CASE TO

NEW GROUND ROD

AND NEAREST

GROUND GRID

INSTRUMENT CABLE.

TWISTED SHIELDED 4-20 MA

GROUND WIRE

TO NEAREST

GROUND ROD.

GROUND CABLE SHIELD

AT THIS END ONLY

CONTROL PANEL LOCATED AT BUILDING.

FIELD MOUNTED

INSTRUMENT

TYP NOTE: SEE SPEC. SECTIONS

NOT TO SCALE

WALL OR SLAB

WALL OR SLAB

CORE DRILL OPENING

CONDUIT

TYPICAL BOTH SIDES

CAULK ENDS ALL AROUND

CONDUIT PENETRATION AT

U.L APPROVED FIRE

RATED JOINT FILLER

CONDUIT MOUNTED TO HANDRAIL

DISCONNECT MOUNTD

ON HANDRAIL DETAIL

TYPICAL FOR ALL CONDUIT ENTRANCES INTO

NEMA 3R, NEMA 4, OR NEMA 4X ENCLOSURES.

CONDUIT HUB

NOT TO SCALE

MIN. 12" STRAIGHT

CONTROL CABINET

SECTION

BONDING

LUG

SPACE-MAKER HUB

WITH INSULATED

THROAT

OZ/GEDNEY RAINTIGHT

NEOPRENE "O" RING

INSULATED THROAT

BUSHING

TYP

TYP

TYP

TYP

GROUND CABLE CONNECTION

GROUND ROD DETAIL

TYP

TYP

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

E-6 N.T.S.

E

LE

C

TR

IC

A

L D

E

TA

IL

S

S

H E

E T

(12 FEET POLE).

WALKWAY

TO NEXT LIGHT FIXTURE

DETAIL

1/2" ALUM. PL.

TYPICAL MIN.

120V CIRCUIT

TYPICAL MIN.

S.S NUTS & BOLTS

1"

HANDRAIL

ON WALKWAY

LIGHT FIXTURE MOUNTING

WITH NYLON ISOLATION WASHERS. ADJUST

SIZE 316 SS BOLTS & BOLT PATTERN

STRUCTURE. COORDINATE WTIH

ATTACK TO THE WALKWAY

1"

4" DIA. ALUMINUM POLE

TYP

NOT TO SCALE

STRUCTURAL ENGINEER.

4X SS

JB

1/2" ALUM. PL.

9" M

IN

ALL POLE INSTALLATIONS MUST MEET FLORIDA

BUILDING CODE WIND LOADING REQUIREMENT

WITH APPROPRIATE WIND GUST FACTOR FOR

THE LOCATION OF INSTALLATION. THE

CONTRACTOR SHALL INCLUDE WITH THE SHOP

DRAWING SUBMITTAL, A POLE WIND LOADING

CALCULATION SIGNED & SEALED BY A

STRUCTURAL ENGINEER REGISTERED IN THE

STATE OF FLORIDA SHOWING THAT THE

PROPOSED POLE AND INSTALLATIONS WILL MEET

THE GIVEN WIND LOADING REQUIREMENT.

WINDLOADING NOTE:

1.

(DO NOT MOUNT

DEVICE ON HANDRAIL)

WP/GFI RECEPTACLE

1/

2"

4-WAY DUCTBANK

3" 3"

3" 7 1/2" 3"

NOT TO SCALE

10-WAY DUCTBANK

1/

2"

3" AT 12" ON CENTER.

U-SHAPED TIES MIN.,

ALL AROUND. 2 #3

2" MINIMUM COVER

BOTTOM

7 1/2"3"

3"

7 1/2" 3"7 1/2" 7 1/2"

#4 TOP AND

7 1/2"

3-WAY CONCRETE

ENCASED DUCTBANK

3" 3"

7 1/2"3" 3"

#4 TOP AND

BOTTOM

2" MINIMUM COVER

ALL AROUND. 2 #3

U-SHAPED TIES MIN.,

6" OVERLAP AT 12"

ON CENTER.

#4 TOP AND

BOTTOM

2" MINIMUM COVER

ALL AROUND. 2 #3

U-SHAPED TIES MIN.,

AT 12" ON CENTER.

TYP

TYP

TYP

NOT TO SCALE

NOT TO SCALE

FOR DUCTBANK WITH DIFFERENT QUANTITY OF CONDUITS SHOWN, HORIZONTAL STAGGER THE ARRANGEMENT USING

ABOVE DETAIL WITH REBAR, SPACING, AND POUR CONCRETE SIMILARLY.

KEEP MINIMUM DISTANCE SEPARATION ALLOWED BETWEEN POWER CONDUITS AND INSTRUMENTATION CONDUITS AS PER

NOTE 17 (DRAWING E-1).

NOTES:

FINISH GRADE

QUAZITE PULL BOX W/BASE,

EXPENSE AND INSTALL PER

FOR DRAINAGE

MANUFACTURER'S RECOMMENDATIONS.

SEE PLAN FOR CONDUIT

8" CRUSHED STONE OR GRAVEL

CONTRACTOR SHALL ENLARGE SIZE TO

MEET NEC WHEN NEEDED AT HIS OWN

17"X30" I.D. MINIMUM SIZE,

M

IN

IM

U

M

AND WIRE REQUIREMENTS

HEAVY DUTY, SKID RESISTANT &

NONMETALLIC TRAFFIC RATED COVER,

MARKED "ELECTRICAL" AND BOLTED

DOWN WITH STAINLESS STEEL HARDWARE

NOT TO SCALE

ELECTRICAL PULL BOX DETAIL

TYP

EXISTING PANEL ELP1 SCHEDULE (EAST BLOWER ROOM)

BUS AMPS

BA

LOADPOLESBUSAMPSPOLES AMPS

A B

LOAD

BUS AMPS

A B

21 22

EAST BLOWER ROOM

NEMA 4X STAINLESS STEELNEMA 4X

LOCATION:

FLUSH

SURFACE

BRANCH POLES

NEMA 1

COPPER BUSSES

TO BE GFI BREAKERS

HINGED DOOR

CABINET:400

277/480 1 PHASE, 3 WIRE

SPD

200%150%

___ BREAKER

ENCLOSURE TYPE

GROUND BUS

MAIN LUGS ________ SETS SIZE: _________

KEYED DOOR LATCH

NEMA 3R

RATED VOLTAGE:

RATED AMPS:

100%

MAIN LUGS ONLY

NEUTRAL BUS

PANELBOARD MUST BE RATED TO INTERRUPT A SHORT CIRCUIT ISC OF ___10,000 AMPS SYMMETRICAL.

MF'RS. EATON (CUTLER-HAMMER)

CIRCUIT BREAKER (BOLT-IN) BRANCH DEVICES

MEASURED AMPS: BUS A____ BUS B_____ CONNECTED Kva____

MAIN AMPS

120/240

HEMS PUMP-

TREATMENT UNIT #1 FLOW TRANSMITTERS

UNKNOWN

UNKNOWN

UNKNOWN

UNKNOWN

UNKNOWN

UNKNOWN

BATT. CHRG

DAY TANK

FAN ATS

EXISTING PANEL LP1 - A SCHEDULE

BUS AMPS

BA

LOADPOLESBUSAMPSPOLES AMPS

A B

LOAD

BUS AMPS

A B

EAST BLOWER ROOM

NEMA 4X STAINLESS STEELNEMA 4X

LOCATION:

FLUSH

SURFACE

BRANCH POLES

NEMA 1

COPPER BUSSES

TO BE GFI BREAKERS

HINGED DOOR

CABINET:400

277/480 1 PHASE, 3 WIRE

SPD

200%

150%

___ BREAKER

ENCLOSURE TYPE

GROUND BUS

MAIN LUGS ________ SETS SIZE: _________

KEYED DOOR LATCH

NEMA 3R

RATED VOLTAGE:

RATED AMPS:

100%

MAIN LUGS ONLY

NEUTRAL BUS

PANELBOARD MUST BE RATED TO INTERRUPT A SHORT CIRCUIT ISC OF ___10,000 AMPS SYMMETRICAL.

MF'RS. SQUARE D

CIRCUIT BREAKER (BOLT-IN) BRANCH DEVICES

MEASURED AMPS: BUS A____ BUS B_____ CONNECTED Kva____

MAIN AMPS

120/240

0.2

1.0

3.4

0.2

3.4

3.0 3.4

0.1 1.5

12.0

12.0SPACE

GEN ROOM RECEPS

GEN ROOM EXHAUST FAN

PLC # 2

EAST SWITCH KWH METER PANEL

PLANT LIGHT

OUTLETS

PLANT 2 LIGHT

FA

PUMP

MOV 905

FUEL SYSTEM

GAS TANK

MOV 907

LIFT STATION

POST TOP

RADPTLED-P2-40K-SYM-MVOLT-

REMARKSMOUNTINGCATALOG NODESCRIPTION MANUFACTURER

LUMINAIRE SCHEDULE

LITHONIA120

LAMPS

5000 LUM.1

TYPETYPE VOLTS

POST TOP AREA LUMINAIRE, RADEAN FAMILY LED

39 WATTS

POLE W/ COORDINATE WITH 4" POLE

SUPPLIER FOR POST TOP

MOUNTING OPTION AND

PROVIDE ACCORDINGLY.

LIGHTING

(OR)

COOPER

LIGHTING

LXS-VA-2-840-U-SYM-S-GM-F- 5000 LUM.

48 WATTSPOST TOP AREA LUMINAIRE, INVUE LUXESCAPE LED

RADPT20-SF-DNAXD

MA1036-XX

(SEE DETAIL)

PUMP

UNKNOWN

UNKNOWN

UNKNOWN

UNKNOWN

NOTE: INSTALL TWO NEW BREAKERS IN EXISTING PANEL AS SHOWN.

3.0 TREATMENT UNIT #1 LIGHTING20 1 3.0

AS NEEDED FOR INSTALLATION AS PER LIGHT

POLE MANUFACTURERS RECOMMENDATION

POWER, SEE DWG E-4

POWER, SEE DWG E-4

SIGNAL, SEE DWG E-4

SPARE SIGNAL, SEE DWG E-4

TU#1 CONTROL PANEL (LCP-TU1) VIA JBOX-P1

TU#1 CONTROL PANEL (LCP-TU1) VIA JBOX-P1

JBOX-I1 LOCATED NEAR TU#1 STAIR LANDING

JBOX-I1 LOCATED NEAR TU#1 STAIR LANDING

EXISTING EMDP-2 PANEL

EXISTING EMDP-2 PANEL

EXISTING PLC-2A PANEL

EXISTING PLC-2A PANEL

REMARKSTO

YARD CONDUIT SCHEDULE (SEE NOTE 1 THRU 3)

FROM NO.

YC04

YC03

YC02

YC01

CONTROL, SEE DWG E-4

SPARE CONTROL , SEE DWG E-4JBOX-I1 LOCATED NEAR TU#1 STAIR LANDING

JBOX-C1 LOCATED NEAR TU#1 STAIR LANDINGEXISTING PLC-2A PANEL

EXISTING PLC-2A PANELYC06

YC05

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

E-7 N.T.S.

E

LE

C

TR

IC

A

L D

E

TA

IL

S

S

H E

E T

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

I-1 N.T.S.

IN

S

TR

U

M E

N

TA

TI

O

N L

E G

E N

D A

N D

N O

TE

EXISTING PLANT

SCADA SYSTEM

EXISTING PLC-2A PANEL

(EAST MAIN ELECTRICAL

BUILDING - ELECTRICAL ROOM)

M

INFLUENT FLOW

(PUMPED RAW)

FE

TU1IF1

FIT

TU1IF1

120V, 1Ø

10" DIA.

M

M

EXISTING I/O POINTS ADDRESS FOR TU#1 AT PLC-2 PANEL:

PLC2:R1/S3/DI10: WWTU NO.1 CLARIFIER DRIVE ON/OFF

PLC2:R1/S3/DI11: WWTU NO.1 CLARIFIER DRIVE FAIL

PLC2:R1/S3/DI12: SPARE INPUT

PLC2:R1/S3/DI13: SPARE INPUT

PLC2:R1/S3/DI14: SPARE INPUT

PLC2:R1/S3/DI15: SPARE INPUT

PLC2:R1/S4/DI10: SPARE INPUT

PLC2:R1/S4/DI11: SPARE INPUT

PLC2:R1/S4/DI12: SPARE INPUT

PLC2:R1/S4/DI13: SPARE INPUT

PLC2:R1/S4/DI14: SPARE INPUT

PLC2:R1/S4/DI15: SPARE INPUT

PLC2:R1/S7/AO02: SPARE ANALOG OUTPUT

PLC2:R1/S7/AO03: SPARE ANALOG OUTPUT

PLC2:R1/S7/AO04: SPARE ANALOG OUTPUT

PLC2:R1/S7/AO05: SPARE ANALOG OUTPUT

PLC2:R1/S7/AO06: SPARE ANALOG OUTPUT

PLC2:R1/S7/AO07: SPARE ANALOG OUTPUT

V-NOTCH

WEIR

120V, 1Ø

LEVEL

TO FLOW

MEASUREMENT

QALQIL

RUNNING

STARTER-TU1-AP1

QI QA

QAQI

RUNNING FAULT

FAIL

HS

SPRAY

WATER

SUBMERSIBLE

PUMP

(TU1-SP1)

FI

FI

TREATMENT

UNIT#1

INFLUENT

FLOW

TU1IF1

TU1IF1

A

QA

QA

TREATMENT

UNIT#1

EFFLUENT

FLOW

TU1EF1

TU1EF1

A

TU#1 SPRAY WATER PUMP

QALQIL

RUNNING

480V, 3Ø

FAIL

4X SS POWDER COATED

WHITE WITH SUNSHIELD

ON TOP AND SIDES

TU1RK1 TU1RK1 TU1SP1 TU1SP1TU1SP1

TU1SP1 TU1SP1

TU1SP1TU1SP1

RETURN

SLUDGE

AIRLIFT

ASSEMBLY

EXISTING AIR SUPPLY

CONNECTION

QI QA

QAQI

RUNNING FAULT

TU#1 CLARIFIER DRIVE

CONTROL PANEL LCP-TU1

TU1RK1 TU1RK1

TU1RK1TU1RK1

FIT

TU1EF1

LE

TU1EF1

STARTER-TU1-RK1 **

HS

RESET

TU1B

LIMIT

SWITCH

RAS/WAS

MOTORIZED

VALVE

(TU1-CV1)

HS

TU1RK1

HOA

TREATMENT UNIT CONTROL

PANEL LCP-TU1

ZS

TU1LS2

LIMIT

SWITCH

ZS

TU1LS1

TIMER

SV**

SPRAY

NOZZLE

SPRAY

NOZZLE

QI

QA

TU#1

TORQUE

ALARM

TU1RK1A

TU1RK1A

V-NOTCH

WEIR

LE

TU1SB1

120V, 1Ø

LEVEL

TO FLOW

MEASUREMENT

FIT

TU1SB1

FI

FI

TREATMENT

UNIT#1

RAS OR

WAS

FLOW

TU1SB1

TU1SB1

A

AE

TU1DO1

AE

TU1DO1

FUTUREFUTURE

AIT

TU1DO1

FUTURE

AIT

TU1DO1

FUTURE

AI

AI

TREATMENT

UNIT#1

RE-AIR

DO

TU1DO1

TU1DO1

A

AI

AI

TREATMENT

UNIT#1

EFFLUENT

DO

TU1DO2

TU1DO2

A

R 1/

S3 /D

I1

R 1/

S3 /D

I1

R 1/

S3 /D

I1

R 1/

S3 /D

I1

EXISTING I/O POINTS ADDRESS FOR TU#1 AT PLC-5 PANEL:

(NOTE: PLC-5 PANEL IS LOCATED IN EFFLUENT ELECTRICAL ROOM)

PLC5:R1/S5/AI00: WWTU NO.1 RE-AIR DO (0-10 PPM)

PLC5:R1/S5/AI01: WWTU NO.1 CHLORINE CONTACT DO (0-10 PPM)

PLC5:R1/S5/AI03: WWTU NO.1 INFLUENT FLOW (0-4 MGD)

PLC5:R1/S5/AI05: WWTU NO.1 EFFLUENT FLOW (0-3 MGD)

PLC5:R1/S5/AI06: WWTU NO.1 AIR FLOW (0-6000 SCFM)

PLC5:R1/S9/AO04: WWTU NO.1 SPLITTER BOX ACTUATOR VALVE (0-100%)

R 1/

S4 /D

I1

R 1/

S8 /A

I0

R 1/

S8 /A

I0

R 1/

S8 /A

I0

CLARIFIER

DRIVE

TS

TU1TS1

TORQUE

SWITCH

1 CONTRACTOR SHALL PROVIDE AND INSTALL NEW

LOCAL CONTROL PANEL FOR TREATMENT UNIT NO.1

LOCAL CONTROL PANEL, INCLUDING STARTER, SPD,

BREAKERS, TIMER, RELAY, LED PUSH TO TEST

INDICATION LIGHTS, ETC. IN A NEMA 4X 316

STAINLESS STEEL CONTROL PANEL. NEW PANEL

SHALL BE POWDER COATED WHITE WITH

SUNSHIELD ON TOP AND SIDES. CONNECT LCP TO

PLC-2 PANEL AS SHOWN AND AS REQUIRED. THERE

ARE EXISTING SPARE I/O POINTS IN THE PLC-2

PANEL AND CONTRACTOR SHALL FIELD VERIFY AND

ADJUST THE I/O POINTS AS NEEDED.

CONTRACTOR SHALL PROVIDE AND INSTALL ALL

NECESSARY RELAYS, TERMINAL BLOCKS, SURGE

ARRESTORS, WIRING, ETC. AS NEEDED FOR NEW

SIGNALS AT THE PLC-2 PANEL. MAKE ALL

NECESSARY CONNECTIONS, TERMINATIONS,

MODIFICATIONS, ETC. FOR A COMPLETE AND

FUNCTIONAL PLC SYSTEM IN PLACE.

EXISTING ANALOG SIGNALS ASSOCIATED WITH THE

EXISTING TREATMENT UNIT NO.1 (TU#1) AT THE

PLC-5 PANEL (EFFLUENT ELECTRICAL BUILDING)

SHALL BE DISCONNECTED DURING THE

REHABILITATION OF THE TU#1. UPDATE THE I/O

LOOP DIAGRAMS AND LABEL THEM AS SPARE. ALL

NEW SIGNALS ASSOCIATED WITH THE

REHABILITATED TU#1 SHALL BE CONNECTED TO THE

PLC#2 PANEL AS SHOWN ON DRAWINGS AND AS PER

SPECIFICATIONS.

CONTRACTOR SHALL PROVIDE AND INSTALL ONE

NEW ANALOG INPUT MODULE (8 CHANNEL) IN THE

EXISTING PLC-2 RACK SPARE SLOT LOCATION.

EXISTING PLC IS CONTROLLOGIX (1756-L61) MODEL.

PROVIDE AND INSTALL NEW SURGE ARRESTORS,

TERMINAL BLOCKS, WIRING, ETC. FOR A COMPLETE

AND FUNCTIONAL PLC SYSTEM IN PLACE.

PROVIDE AND INSTALL SUNSHIELD AND PIPE STAND,

SPD, ETC. FOR ALL FLOW AND LEVEL TRANSMITTER.

TYPICAL.

COORDINATE WITH SPLITTER BOX SUPPLIER FOR

THE ACTUAL DIMENSIONS OF SPLITTER BOX AND

V-NOTCH WEIR LAYOUT TO DETERMINE THE

LOCATION TO INSTALL THE FLOW/LEVEL SENSOR.

REQUEST ALL NECESSARY PARAMETERS OF THE

V-NOTCH WEIR FOR FLOW CALCULATION AND

SETUP THE FLOWMETER ACCORDINGLY.

FIELD OBTAIN AND COPY THE EXISTING V-NOTCH

WEIR PARAMETERS FROM THE EXISTING

FLOWMETER BEFORE REPLACEMENT AND SETUP

NEW FLOWMETER ACCORDINGLY.

KEYED NOTES:

DIFFUSERSDIFFUSERS

STILLING

WELL

MOD.

ZC

ZC

TU#1

SPLITTER

BOX VALVE

POSITION

CONTROL

TU1CV1

TU1CV1

A

R 1/

SX

/A

I0

R 1/

S8 /A

I0

R 1/

S8 /A

I0

FUTUREFUTURE

ZI

ZI

TU#1

SPLITTER

BOX VALVE

POSITION

INDICATION

TU1CV1

TU1CV1

A

R 1/

S8 /A

I0

480V, 3Ø

QI

QA

TU#1

TORQUE

SHUTDOWN

R 1/

S4 /D

I1

QIL

TORQUE

ALARM

TU1RK1A

QIL

TORQUE

SHUTDOWN

TU1RK1B

OO

TU1RK1B

TU1RK1B

SPD

SV-TU1SV1

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

I-2 N.T.S.

P

ID

TR

E

A

TM

E N

T U

N

IT

N O

.1

NOTES:

ROUND OFF ALL EXPOSED EDGES AND CORNERS. ALL S.S. SHALL

BE 316 STAINLESS STEEL.

SEE SPECIFICATIONS FOR SPD INFORMATION

1" NONSHRINK

GROUT

SECURE TO SLAB WITH 4-1/2"

SS CONCRETE ANCHORS

1/2 "x12"x12" S.S. PLATE

4" SCH 40 S.S. PIPE

4"x2" S.S. REDUCER

2" SCH 40 S.S. PIPE

L 2 1/2 "x2"x 1/4 " S.S. LENGTH TO

SUIT INSTRUMENT

INSTRUMENT

L 2 1/2 "x2"x 1/4 " S.S.

LENGTH TO SUIT

INSTRUMENT

MOUNTING HOLES TO SUIT INSTRUMENT SECURE

INSTRUMENT TO STANCHION W/316 S.S. BOLTS, NUTS

& WASHERS

NOT TO SCALE

2'-6"

4'6"

TO SUIT

INSTRUMENT

3/16

3/16 G

3/16

L

1.

STANCHION SUPPORT FOR

CASE MOUNTED INSTRUMENTS

L

RAIN HOOD REQUIRED

FOR OUTDOOR APPLICATION

UV PROTECTIVE

FLEXIBLE

SUN SHIELD

INSTALLATION DETAIL

MAGNETIC FLOWMETER

NOT TO SCALE

SPD

SPD

2.

VAR.

VAR.

HANDRAIL

RIGID

CONDUIT

PIPE

SUPPORT

LEVEL TRANSMITTER

4'-6"

INSTALLATION DETAIL

ULTRASONIC LEVEL TRANSMITTER

VAR.

WALL

FLEXIBLE CONDUIT

WITH MSC

SONIC SENSOR

MAX. LEVEL

MIN. 1 FT. FOR EVERY

10 FT. LEVEL DEEP

NEW HINGED TRANSDUCER

BRACKET (PULSAR MODEL:

dBA003) OR EQUAL.

EXISTING

GRATING

LEVEL TRANSDUCER WITH

CABLE LENGTH AS

NECESSARY (FIELD ADJUST

MOUNTING LOCATION AS

NEEDED INSIDE CLARIFIER

COLLECTION BOX)

PIPE STAND WITH

SUNSHIELD

SPD

4 WIRE INSTRUMENT

4 WIRE INSTRUMENT

PANEL LP"X"

120VAC

4-20MA OUTPUT

PANEL LP"X"

120VAC

1 2

7 6

SURGE SUPRESSOR

EDCO SLAC

4-20MA OUTPUT+

(TYP)

FIELD PANEL

(TYP)

SURGE SUPRESSOR

EDCO PC642

9 8

PLC I/O

TYPICAL 4 WIRE INSTRUMENT ISOLATOR

NOT TO SCALE

VAR.

TREATMENT UNIT NO.1CONTROL SCHEMATIC

COORDINATE WITH

TREATMENT UNIT NO.1

SYSTEM SUPPLIER FOR

SPRAY WATER AND

CLARIFIER DRIVE TORQUE

SWITCH INTERLOCKING

REQUIREMENTS. ADJUST

SCHEMATIC AS NEEDED TO

COMPLY WITH THE

FUNCTION REQUIRED BY

THE SYSTEM SUPPLIER

DURING SHOP DRAWING

PHASE.

S E

A L:

R E

V I

S I

O N

S

CITY OF P.P. PLAN SUBMITTAL:

D A

TE

N

O

B Y

D E

S C

R

IP

TI

O

N

OFSHEET:

PE

M

BR

O

KE

P

IN

ES

, F

LO

R

ID

A

C

IT

Y O

F

PE

M

BR

O

KE

P

IN

ES

S O

U

TH

P

AL

M D

R

IV

E

KNOW WHAT'S BELOW

ALWAYS CALL 811

BEFORE YOU DIG

It's fast. It's free. It's the law.

www.callsunshine.com

R

SHEET NUMBER:

SUBMITTAL DATE:

SCALE:

U

TI

LI

TI

ES

D

EP

AR

TM

EN

T

MARCH 2025

X X

W A

S

TE

W A

TE

R

T R

E A

TM

E

N T

P

LA

N T

U N

IT

R E

H A

B

IL

IT

A

TI

O

N

P em br ok e

R d, P em br ok e P in es

, F L

100% SET

I-3 N.T.S.

IN

S

TR

U

M E

N

TA

TI

O

N D

E

TA

IL

cover.pdf
P2.pdf
P3.pdf
P1.pdf
202503 100% Electrial and Instrumentation.pdf
Sheets and Views
E-1 ELECTRICAL LEGEND AND NOTES
E-2 ELECTRICAL SITE PLAN - DEMOLITION
E-3 PHOTOS AND EAST ELECTRICAL BUILDING
E-4 ONE LINE AND RISER DIAGRAM
E-5 MODIFIED TREATMENT UNIT 1 ELECTRIC PLAN
E-6 ELECTRICAL DETAILS - SHEET 1
E-7 ELECTRICAL DETAILS - SHEET 2
I-1 INSTRUMENTATION LEGEND AND NOTES
I-2 P&ID - TREATMENT UNIT NO.1
I-3 INSTRUMENTATION DETAILS

File details come from the government source that posted it. Updated .