2025-05-23_-_UNIT_1_REHABILITATION_PLANS-_BID_SET.pdf
PDF 7 MB Posted
- Attached to
- Wastewater Treatment Plant Unit 1 Rehabilitation
- Solicitation number
- PSUT-25-07
- Issued by
- Broward County, Florida
About this file
This is a comprehensive bid set document for the City of Pembroke Pines Utilities Department for the Wastewater Treatment Plant Unit 1 Rehabilitation project located at 13955 Pembroke Road, Pembroke Pines, Florida 33027. The project scope includes complete renovation and painting of Treatment Unit 1, with major components including removal and replacement of the fine bubble diffuser system, clarifier drive, Return Activated Sludge (RAS) box and valve, installation of a new spray wash system for the effluent trough, grit cleaning and removal, renovation and painting of the entire unit, installation of a closed-loop air header system with process air piping, and comprehensive electrical and instrumentation control modifications. The bid set includes detailed construction documents with electrical plans (sheets E-1 through E-7) covering demolition, site plans, one-line and riser diagrams, electrical details, and instrumentation plans (sheets I-1 through I-3) with P&ID diagrams and installation details. The mandatory pre-bid meeting is scheduled for Monday, July 14, 2025, at 9:00 am at the treatment plant facility, with written questions due by Tuesday, July 29, 2025, and sealed bids due by Tuesday, August 12, 2025, at 2:00 pm. The project is expected to be completed within 365 calendar days from the Notice to Proceed, with liquidated damages assessed at $1,500 per day for project delays.
The estimated project cost is approximately $2,400,000, requiring bidders to submit proposal security of 5% of the total cumulative base amount and obtain both Payment and Performance Bonds for 100% of the contract price. The project is locally funded and not supported by federal grants or funding sources. Contractors must comply with E-Verify system registration, background screening requirements, and provide comprehensive insurance coverage including general liability, workers' compensation, and auto liability. Successful bidders must submit detailed shop drawings, technical manuals, and documentation of previous experience on comparable wastewater treatment plant rehabilitation projects. Contract compensation will be provided through monthly payments based on unit pricing, with payment not to exceed a specified maximum annual amount. The City of Pembroke Pines will evaluate bids based on compliance with specifications, contractor qualifications, and adherence to local requirements including public entity crime certifications, equal benefits provisions, and drug-free workplace compliance.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET
PEMBROKE PINES COMMISSION
SCOPE OF WORKC-1
UTILITIES DEPARTMENT
8300 SOUTH PALM DRIVE
PEMBROKE PINES, FL 33025
CITY OF PEMBROKE PINES
C-0
DATENO. BY DESCRIPTION
SHEET No.
CITY OF PEMBROKE PINES
WWTP UNIT 1 REHABILITATION PLAN
13995 PEMBROKE RD, PEMBROKE PINES, FL 33027
COVER SHEET
RENOVATION AND PAINTINGC-2
ELECTRICAL LEGEND AND NOTESE-1
PHOTOS AND EAST ELECTRICAL BUILDINGE-3
ELECTRICAL SITE PLAN -DEMOLITIONE-2
E-4
E-5
E-6
E-7 I-1
I-2
I-3
ONE LINE AND RISER DIAGRAM
MODIFIED TREATMENT UNIT ELECTRIC PLAN
ELECTRICAL DETAILS - SHEET 1
ELECTRICAL DETAILS- SHEET 2
INSTRUMENTATION LEGEND AND NOTES
P&ID - TREATMENT UNIT NO. 1
INSTRUMENTATION DETAILS
C-3 CLOSED LOOP AIR HEADER SYSTEM
VICE MAYOR - DISTRICT 4
DISTRICT 2
DISTRICT 1
DISTRICT 3
MAYOR
THOMAS GOOD Jr.
MARIA RODRIGUEZ
ANGELO CASTILLO
JAY D. SCHWARTZ
CITY MANAGERCHARLES F. DODGE
MICHAEL A. HERNANDEZ
SEAL:R E V I S I O N S
C
ITY O
F P .P
. P
LA
N S
U B
M
ITTA
L:
DATENO. BY DESCRIPTION
O F
S H
E E
T:
R
S H
E E
T N
U M
B E
R
S U
B M
ITTA
L D
A
TE
S C
A
LE
: WASTEWATER TREATMENT PLANT
UNIT 1 REHABILITATION
13955 Pembroke Rd, Pembroke Pines, FL 33029
RENOVATION AND PAINTING
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
C L
O S
E D
L O
O P
A
IR
H E
A D
E R
S Y
S T
E M
SEAL:R E V I S I O N S
C
ITY O
F P .P
. P
LA
N S
U B
M
ITTA
L:
DATENO. BY DESCRIPTION
O F
S H
E E
T:
R
S H
E E
T N
U M
B E
R
S U
B M
ITTA
L D
A
TE
S C
A
LE
WASTEWATER TREATMENT PLANT
UNIT 1 REHABILITATION
13955 Pembroke Rd, Pembroke Pines, FL 33029
SCOPE OF WORK
l l
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
E-1 N.T.S.
E
LE
C
TR
IC
A
L
LE
G E
N D
A N
D N
O
TE
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
N.T.S.
E-2
E
LE
C
TR
IC
A
L S
IT
E
P
LA
N
D E
M O
LI
TI
O N
ELECTRICAL SITE PLAN - DEMOLITION
SCALE: 1" = 20'-0"
PHOTO E1: STAIRWAY TO TU-1
NOT TO SCALE
PHOTO E2: EXPOSED CONDUITS
NOT TO SCALE
PHOTO E3: EXPOSED CONDUITS
NOT TO SCALE
CONTRACTOR SHALL REMOVE THE
EXISTING PANELS, DISCONNECTS, ETC.
DURING REHAB OF TREATMENT UNIT NO.1
REMOVE ALL EXPOSED CONDUITS ON
TREATMENT UNIT NO.1, INDICATED OR
NOT BACK TO SOURCE. CUT CONDUITS
TO THE GROUND ENTRY POINTS AND
REMOVE WIRES BACK TO SOURCE.
REMOVE ALL EXPOSED CONDUITS ON
TREATMENT UNIT NO.1, INDICATED OR NOT
BACK TO SOURCE. CUT CONDUITS
TO THE GROUND ENTRY POINTS AND REMOVE
WIRES BACK TO SOURCE.
REMOVE ALL EXISTING JUNCTION
BOXES DURING REMOVAL OF
EXISTING EXPOSED CONDUITS (TYPICAL).
REMOVE EXISTING PHOTOCELL
REFER TO OTHER DISCIPLINE DRAWINGS
FOR REMOVAL OF THE EXISTING HANDRAIL,
WALKWAY, GRATING, TREATMENT UNIT
WALL, MECHANISM, ETC. AND PERFORM
REMOVAL OF EXISTING CONDUITS AS WELL
AS INSTALLATION OF NEW CONDUITS
ACCORDINGLY.
REMOVE EXISTING LIMIT SWITCH. NEW LIMIT SWITCH
SHALL BE INSTALLED SIMILARLY AT THE SAME LOCATION.
DEMOLITION NOTES
CONTRACTOR SHALL COORDINATE WITH ALL OTHER
DISCIPLINES FOR REHABILITATION OF THE EXISTING
TREATMENT UNIT NO.1 AND ASSOCIATED STAIRWAY,
WALKWAY, ETC. DISCONNECT POWER WIRES BEFORE
DEMOLITION BEGINS. DISCONNECT ALL OTHER WIRES AND
REMOVE BACK TO SOURCE. REMOVE ALL PANELS AND
INSTRUMENTS BEFORE DEMOLITION BEGINS. COORDINATE
WITH OWNER FOR EQUIPMENT TO BE SALVAGE AND TURN
OVER TO THE OWNER. OTHERWISE, DISPOSE ALL OTHER
ITEMS ACCORDINGLY. REMOVE ALL EXPOSED CONDUITS
COMPLETELY. CUT UNDERGROUND CONDUITS FLUSH WITH
FLOOR OR WALL OR GRADE AND CAP.
REMOVE THE EXISTING LIGHT POLES LOCATED ON WALKWAY
OF TREATMENT UNIT NO.1 AND TURN OVER TO THE OWNER.
DISPOSE THEM IF NOT WANTED BY OWNER. CONTRACTOR
SHALL FIELD DETERMINE THE EXISTING LIGHTING CIRCUIT AT
TREATMENT UNIT NO.1 LIGHT POLES THAT WILL BE REMOVED.
MODIFY EXISTING LIGHTING CIRCUIT AS NEEDED TO KEEP THE
REMAINING LIGHT POLES AT REMAINING LIGHTS, INCLUDING
LIGHT POLES AT THE TREATMENT UNIT NO.2 FUNCTIONAL.
1.
2.
REMOVE EXISTING LIGHT POLES
AT TREATMENT UNIT NO.1 DURING
REHABILITATION. TOTAL OF 6.
EXISTING LIGHT POLE AT
TREATMENT UNIT NO.2 SHALL
REMAIN.
REFER TO DRAWING E-03
FOR ENLARGED EAST
ELECTRICAL BUILDING
REFER TO DEMOLITION NOTE NO.1 AND NO.2
FOR TREATMENT UNIT NO.1.
REPLACE EXISTING MAGNETIC
FLOWMETER AND PANEL
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
E-3 N.T.S.
P H
O
TO
S A
N D
E A
S T
E
LE
C
TR
IC
A
L B
U
IL
D
IN
G
PHOTO E5: INSTRUMENT PANELS
NOT TO SCALE
PHOTO E4: TREATMENT UNIT NO.1
NOT TO SCALE PHOTO E6: FLOWMETER AND PANEL
NOT TO SCALE
EAST ELECTRICAL AND BLOWER BUILDING
SCALE: 1/4" = 1'-0"
EXISTING PLC-2A PANEL
EXISTING LIGHT POLE AT TREATMENT UNIT NO.1
SHALL BE REMOVED AND TURN OVER TO THE OWNER.
TYPICAL
CONTRACTOR SHALL REMOVE THE
EXISTING PANELS, DISCONNECTS, ETC.
DURING REHAB OF TREATMENT UNIT NO.1
REMOVE ALL EXPOSED CONDUITS ON
TREATMENT UNIT NO.1, INDICATED OR
NOT BACK TO SOURCE. CUT CONDUITS
TO THE GROUND ENTRY POINTS AND
REMOVE WIRES BACK TO SOURCE.
REPLACE EXISTING MAGNETIC FLOWMETER
AS SHOWN ON I-DRAWINGS
REPLACE EXISTING FLOWMETER
DISPLAY PANEL AS SHOWN ON
I-DRAWINGS
REMOVE EXISTING CLARIFIER
NO.1 DRIVE STARTER
EXISTING EMDP-2
EXISTING EMDP-1
EXISTING BLOWER#6
STARTER
EXISTING CLARIFIER
NO.2 DRIVE STARTER (ABOVE)
EXISTING FROTH SPRAY#2
STARTER (BELOW)
EXISTING PANEL ELP1EXISTING TRANSFORMER
EXISTING 120V SUB-PANEL
AND LIGHTING CONTACTOR FOR TU#1 AND TU#2
EXISTING EAST
SWITCHBOARD
CONTINUED ON DRAWING E-5
CONTINUED ON DRAWING E-5
SAW CUT EXISTING CONCRETE SLAB
FOR NEW CONDUITS INSTALLATION.
(TYPICAL)
NEW NEMA 4X
316 S.S. J-BOX
NEW NEMA 4X 316 S.S. J-BOX
(FIELD ADJUST LOCATION TO
AVOID CONFLICT WITH DOOR)
SAW CUT EXISTING CONCRETE SLAB
FOR NEW CONDUITS INSTALLATION.
(TYPICAL)
LOCATION: EAST BLOWER ROOM EMDP-2
3P-250A
MCP
3P-250A
MCP
3P-15A
MLO 600A, 3 PHASE, 4 WIRE,65 KAIC
VFD
VFD
BLOWER
#1
BLOWER
#2
CLARIFIER
DRIVE UNIT #1
AT
TREATMENT
UNIT #1
2P-50A
PANEL "ELP1"
XFMR
25 KVA
480-120/240, 1Ø, 3W
3P-15A
LIFT STATION
CONTROL PANEL
EXISTING EAST
MAIN SWBD
NOT TO SCALE
EXISTING EAST BLOWER DISTRIBUTION PANEL NO.2 (EMDP-2) ONE LINE
LOCATION: EAST BLOWER ROOM EMDP-2
3P-250A
MCP
3P-250A
MCP
3P-15A
MLO 600A, 3 PHASE, 4 WIRE,65 KAIC
VFD
VFD
BLOWER
#1
BLOWER
#2
CLARIF.
DRIVE
(RACK
DRIVE)
2P-50A
PANEL "ELP1"
XFMR
25 KVA
480-120/240, 1Ø, 3W
3P-15A
LIFT STATION
CONTROL PANEL
EXISTING EAST
MAIN SWBD
NOT TO SCALE
MODIFIED EAST BLOWER DISTRIBUTION PANEL NO.2 (EMDP-2) ONE LINE
TREATMENT UNIT#1
CONTROL PANEL
(LCP-TU1)
3/4"C, 3#12, 1#12G
3/4"C, 3#12, 1#12G
EXISTING PANEL "ELP1"
3/4
EXISTING
SUBMERSIBLE
SPRAY PUMP
AT TREATMENT
UNIT #1
EXST. EXST.
EXISTING LIGHT POLES
AT TREATMENT UNIT NO.1
TO NEXT
LIGHT POLE
IN TU#2
FROTH
SPRAY
PUMP
3/4
MOTORIZED
VALVE
(TU1-CV1)
MOV
1"C, 10#14, 1#14G
J
4X SS
3/4"C, 2#14, 1#14G
(TYP.)
EXISTING LIGHTING
CONTACTOR
1 CONTRACTOR SHALL REMOVE THE EXISTING STARTER, CONDUITS/WIRES, ETC.
ASSOCIATED WITH THE TREATMENT UNIT NO.1 DRIVE. TURN OVER STARTER,
DISCONNECT, ETC. TO THE OWNER, DISPOSE THEM IF NOT WANTED BY THE OWNER.
EXISTING BREAKER AT EMDP-2 SHALL BE REUSED TO POWER THE PROPOSED
TREATMENT UNIT NO.1 CONTROL PANEL.
CONTRACTOR SHALL FIELD VERIFY THE EXISTING TU#1 AND TU#2 LIGHTING CIRCUIT
FROM THE EXISTING LP PANEL THRU EXISTING LIGHTING CONTRACTOR/TIME CLOCK
LOCATED IN THE EAST ELECTRICAL BUILDING - EAST BLOWER ROOM. DISCONNECT
AND REMOVE EXISTING LIGHT POLES ON TOP OF TU#1 AND MODIFY THE LIGHTING
CIRCUIT SO THAT TU#2 LIGHTING WILL STILL FUNCTIONAL. IF NEEDED, PROVIDE AND
INSTALL NEW 3/4", 2#10, 1#10G FROM THE EXISTING LIGHTING CONTACTOR TO THE
NEAREST LIGHT POLE AT TU#2 WALKWAY BEFORE DISCONNECTING LIGHTING
CIRCUIT AT TU#1.
CONTRACTOR SHALL COORDINATE WITH PACKAGED SYSTEM SUPPLIER FOR EACH
INDIVIDUAL COMPONENT LOCATION AND INSTALL CONDUITS/WIRES ACCORDINGLY.
KEYED NOTES:
3P-15A
SPD
3P-15A 3P-30A 3P-30A
SPARE SPARE SPARE
3P-30A 3P-30A
SPARE SPARE
3P-15A
4X SS
3/4"C, 3#12, 1#12G
3/4"C, 3#12, 1#12G
EATON PANEL (PRL4B)EATON PANEL (PRL4B)
3/4"C, MSC
(8x8x6)
EXISTING
PLC-2A
PANEL
LE-TU1SB1 FIT-TU1SB1
AE- TU1DO1
FUTURE
AIT-TU1DO1
FUTURE
FE-TU1IF1 FIT-TU1IF1
M
RAS/WAS
MOTORIZED
VALVE
(TU1-CV1)
LEVEL
TO FLOW
MEASUREMENTFIT-TU1EF1LE-TU1EF1
AE-TU1DO1
FUTURE
AIT-TU1DO1
FUTURE
3/4"C, 1#TSP
3/4"C, 1#TSP
3/4"C, 1#TSP
3/4"C, 2#TSP
1"C, 20#14, 1#14GSPARE 3/4"C
PLC-2A PANEL RISER DIAGRAM
SPARE 3/4"C
NOT TO SCALE
EXISTING PANEL ELP-1
EXISTING PANEL "ELP1"
NOT TO SCALE
MODIFIED PANEL ELP-1
LEVEL
TO FLOW
MEASUREMENT
3/4"C, 2#12, 1#12G
J
4X SS
FIT-TU1IF1
3/4"C, 2#12, 1#12G
FIT-TU1SB1 FIT-TU1EF1
NEW LIGHT POLES
AT TREATMENT UNIT NO.1
EXISTING LIGHTING
CONTACTOR
3/4"C, 2#12, 1#12G
3/4"C, 2#12, 1#12G
NEW
JBOX-I1
(4X SS)
LOCATION:
NEAR THE
STAIR
LANDING
OF TU#1
MINIMUM
DIMENSION:
12"x12"x8"
LOCATION:
EAST
ELECTRICAL
ROOM
2"C, 8#TSP
YC03
4X SS
ZS
-T
U 1L
S1
ZS
-T
U 1L
S2
TS
-T
U 1T
S1
SV
-T
U 1S
V1
LIMIT SWITCHES,
SV, TORQUE
SWITCH
NEW
JBOX-C2
NEW JBOX-P1
4X SS
(10x10x8) 4X SS
SEE DWG E-5
SEE DWG E-5
YC01
YC02
YC04
SPARE 1"C
4X
SS
YC05
NEW JBOX-P1
(10x10x8) 4X SS
TREATMENT UNIT #1
CONTROL PANEL
1"C, 20#14, 1#14G
YC06
SPARE 1"C
LOCATION:
NEAR THE
STAIR
LANDING
OF TU#1
LOCATION:
NEAR THE
STAIR
LANDING
OF TU#1
LOAD SUMMARY: THIS IS A LOAD REPLACEMENT ONLY.
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
E-4 N.T.S.
O N
E L
IN
E
A N
D R
IS
E
R D
IA
G
R A
M
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
E-5 N.T.S.
M O
D
IF
IE
D
T R
E A
TM
E
N T
U N
IT
E
LE
C
TR
IC
P
LA
N
MODIFIED TREATMENT UNIT NO.1 - ELECTRICAL PLAN
SCALE: 1" = 10'-0"
NEW LIGHT POLE WITH
BRACKET (MOUNT TO
THE SIDE OF WALKWAY)
TYPICAL OF SIX NEW LIGHT
POLES FOR TU#1 (SEE DETAIL)
EXISTING LIGHT POLE AT
TREATMENT UNIT#2
(TO REMAIN)
FE
TU1IF1
NEW FLOW TRANSMITTER
WITH PIPE STAND AND SUNSHIELD
FIT
TU1IF1
CLARIFIER DRIVE
NEW TREATMENT UNIT
NO.1 CONTROL PANEL
FUTURE INSTRUMENT
(STUB-OUT AND CAP)
FOR FUTURE USE
NEW ULTRASONIC
LEVEL SENSOR AND
TRANSMITTER FOR
RAS/WAS FLOW (ON
SPLITTER BOX)
NEW DISCONNECT
FOR MOV
(TU1CV1)
ZS
TU1LS1
ZS
TU1LS2
NEW ULTRASONIC LEVEL
SENSOR FOR EFFLUENT
FLOW MEASUREMENT
FROTH SPRAY WATER
FIELD ROUTE EXPOSED CONDUITS
ALONG THE WALKWAY SUPPORTS.
SUPPORT EXPOSED CONDUITS AS
PER NEC REQUIREMENTS. TYPICAL
CONDUIT CROSSING WALKWAY
SHALL BE UNDER THE WALKWAY,
INDICATED OR NOT, TYPICAL.
AERATION
ZONE
AERATION
ZONE
CLARIFIER
ZONE
CHLORINE
CONTACT
DIGESTER
ZONE
FIT
TU1EF1
V-NOTCH WEIRS
LEVEL TRANSMITTER
WITH PIPE STAND.
TS
TU1TS1
TORQUE
SWITCH
E-7
1 CONTRACTOR SHALL PROVIDE AND INSTALL NEW LIGHT POLES WITH SUPPORT
BRACKETS AS PER ELECTRICAL DETAIL DRAWING. FIELD ROUTE EXPOSED
CONDUITS TO AVOID CONFLICT AND ADJUST ACCORDINGLY. ROUTE EXPOSED
CONDUITS EITHER BELOW THE WALKWAY OR SIDE OF THE HANDRAIL AS DIRECTED
BY THE FIELD ENGINEER DURING CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH APPROVED SHOP DRAWINGS OF THE
CONTROL PANEL AND ADJUST THE MOUNTING BASED ON THE ACTUAL DIMENSION
OF THE PANEL TO MEET THE NEC CODE CLEARANCES. IF NEEDED, OFFSET PANEL
OUTSIDE THE HANDRAIL AS NEEDED TO HAVE CLEARANCE IN FRONT OF THE PANEL.
PROVIDE AND INSTALL ALL NECESSARY "316 STAINLESS STEEL L" BRACKETS AND
316 STAINLESS STEEL HARDWARE FOR MOUNTING OF THE PANEL.
RECONNECT EXISTING GROUND WIRES TO THE TANK AFTER REHABILITATION OF THE
TREATMENT UNIT. EXTEND GROUND WIRES AS NEEDED. THERE ARE 3 EXISTING
CONNECTIONS AT THE EXISTING TANK.
ONLY INFLUENT FLOWMETER WILL BE INSTALLED AT THE GROUND LEVEL USING
ELECTRICAL RACK. OTHER EQUIPMENT AND PANELS ARE LOCATED ON THE UPPER
LEVEL OF THE TREATMENT UNIT. SEE OTHER DISCIPLINE DRAWINGS FOR ELEVATION
VIEWS.
CONTRACTOR SHALL PROVIDE AND INSTALL TWO NEW GROUND ROD NEXT TO THE
EXISTING GROUND WIRE OF THE TREATMENT UNIT NO.1 TANK AND BOND THEM
TOGETHER USING MECHANICAL LUG CONNECTION. FIELD LOCATE ACTUAL
LOCATION TO INSTALL GROUND RODS AND INSTALL ACCORDINGLY.
KEYED NOTES:
MOUNT NEW JUNCTION BOXES
ON THE BACK SIDE OF STAIR
LANDING. FIELD ROUTE UNDERGROUND
CONDUITS. (JBOX-P1, JBOX-C1, JBOX-I1)
FIELD ROUTE UNDERGROUND
CONDUITS TO NEW JUNCTION
BOXES AND ADJUST TO AVOID
CONFLICTS WITH EXISTING
CONDITIONS. (TYPICAL)
SAW CUT EXISTING CONCRETE SLAB
FOR NEW CONDUITS INSTALLATION.
(TYPICAL)
FIELD ROUTE EXPOSED CONDUITS UNDER
THE STAIR USING UNISTRUT TO OFFSET.
EXPOSED CONDUITS SHALL NOT OBSTRUCT
TO THE STAIR STEPS.
APPROXIMATE LOCATION
OF EXISTING GROUND WIRE
CONNECTION TO TANK
(TYPICAL OF THREE LOCATIONS
AROUND THE TANK). BOND
NEW GROUND WIRE TO
EXISTING GROUND WIRE.
ELECTRICAL NOTES
ELECTRICAL CONDUIT ROUTING IS SHOWN FOR ILLUSTRATION PURPOSES ONLY.
CONTRACTOR SHALL FIELD VERIFY THE CONDUIT ROUTING WITH EXISTING
CONDITIONS AND PROPOSED PIPING, DRAINAGE, ETC. TO AVOID CONFLICTS AND
ADJUST ACCORDINGLY. CONTRACTOR SHALL VISIT THE SITE AND DETERMINE
CONDITIONS AT THE EXISTING SITE BEFORE SUBMITTING HIS/HER BID. SOME
CONDUIT ROUTINGS REQUIRE FIELD DETERMINATION OF THE ROUTINGS TO AVOID
CONFLICTS WITH EXISTING CONDITIONS.
CONTRACTOR SHALL SAW CUT EXISTING SIDEWALK, ROADWAY, CONCRETE SLAB,
ETC. FOR CONDUIT CROSSING AND REPAIR/RESTORE TO MATCH EXISTING
CONDITION.
NO CONDUIT SHALL PENETRATE AN OUTDOOR ELECTRICAL PANEL FROM TOP. FOR
OUTDOOR ELECTRICAL PANELS, ALL CONDUIT PENETRATIONS SHALL BE FROM THE
BOTTOM OR SIDE. PROVIDE NEMA 4X 316 STAINLESS STEEL J-BOX AS NECESSARY
TO ASSIST CONDUITS ENTERING OUTDOOR ELECTRICAL PANEL. OUTDOOR PANEL
SHALL BE PROVIDED WITH HOFFMAN VENT DRAIN OR EQUAL.
CONTRACTOR SHALL KEEP THE SEPARATION BETWEEN POWER AND
INSTRUMENTATION YARD CONDUITS AS PER DRAWING E-1, NOTE 17.
1.
2.
3.
4.
NEW GROUND ROD
(TYPICAL)
CONTINUED ON DRAWING E-3
LE
TU1EF1
FIT
TU1SB1
LE
TU1SB1
YC01
YC02
YC03
YC04
YC05
YC06
YC01-06
DISCONNECT ON
HANDRAIL (TYP.)
DISCONNECT ON
HANDRAIL (TYP.)
CHANNEL-GLOBE STRUT,
UNISTRUT OR EQUAL
ANCHOR TO WALL WITH 1/2" DIA. X 4"
STAINLESS STEEL CONCRETE ANCHORS,
WITH SUPPORTS AT 5"-0" MAXIMUM.
MOUNTING DETAILS
CONDUIT PIPE STRAP
TRAPEZE ASSEMBLY
NOTES:
CONDUIT SUPPORT
NOT TO SCALE
STAGGER JOINTS
USE QUEEN CITY PLASTIC SPACERS
APPLIES TO CONCRETE ENCASED CONDUIT.
NOT TO SCALE
HORIZONTAL STAGGERING OF SPACERS AND JOINTS
9"
OR EQUAL.
9"
SPACER REQUIREMENTS.
OF CONDUIT AS PER NEC
DISTANCE DEPENDS ON SIZE
MIN
9"
CONDUIT GROUNDING
(GROUND ONE
ONLY)
END OF CONDUIT
ENCLOSURE
EQUIPMENT
GROUND WIRE
GROUNDING BUSHINGS
NOT TO SCALE
CONDUIT
RIGID
LOCKNUTS
ALL CONDUIT SHALL BE GROUNDED
WITH "O-Z/GEDNEY" TYPE BLG
316 STAINLESS STEEL THREADED ROD SUPPORT
FROM BUILDING STRUCTURE. MINIMUM 38" DIA.
1 1/2" X 1 1/2" STAINLESS
STEEL CHANNEL
316 STAINLESS STEEL CONDUIT
CLAMP
1. THIS DETAIL TYPICAL FOR BOTH VERTICAL AND HORIZONTAL
MOUNTING
2. CHANNEL AND ALL SUPPORT DEVICES TO BE 316 STAINLESS
STEEL.
3. CHANNELS TO BE SPACED 5' MAXIMUM.
TYP
TYP TYP
5 6
TYP
CONDUIT ENTRANCE
WALL
OLB CONDULETS
EXISTING BUILDING
NOT TO SCALE
FINISH GRADE
TYP
WALL PENETRATION
ON WALL E-6
INSTRUMENTATION GROUNDING & SURGE PROTECTION
TVSS
GROUND WIRE FROM
INSTRUMENT CASE TO
NEW GROUND ROD
AND NEAREST
GROUND GRID
INSTRUMENT CABLE.
TWISTED SHIELDED 4-20 MA
GROUND WIRE
TO NEAREST
GROUND ROD.
GROUND CABLE SHIELD
AT THIS END ONLY
CONTROL PANEL LOCATED AT BUILDING.
FIELD MOUNTED
INSTRUMENT
TYP NOTE: SEE SPEC. SECTIONS
NOT TO SCALE
WALL OR SLAB
WALL OR SLAB
CORE DRILL OPENING
CONDUIT
TYPICAL BOTH SIDES
CAULK ENDS ALL AROUND
CONDUIT PENETRATION AT
U.L APPROVED FIRE
RATED JOINT FILLER
CONDUIT MOUNTED TO HANDRAIL
DISCONNECT MOUNTD
ON HANDRAIL DETAIL
TYPICAL FOR ALL CONDUIT ENTRANCES INTO
NEMA 3R, NEMA 4, OR NEMA 4X ENCLOSURES.
CONDUIT HUB
NOT TO SCALE
MIN. 12" STRAIGHT
CONTROL CABINET
SECTION
BONDING
LUG
SPACE-MAKER HUB
WITH INSULATED
THROAT
OZ/GEDNEY RAINTIGHT
NEOPRENE "O" RING
INSULATED THROAT
BUSHING
TYP
TYP
TYP
TYP
GROUND CABLE CONNECTION
GROUND ROD DETAIL
TYP
TYP
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
E-6 N.T.S.
E
LE
C
TR
IC
A
L D
E
TA
IL
S
S
H E
E T
(12 FEET POLE).
WALKWAY
TO NEXT LIGHT FIXTURE
DETAIL
1/2" ALUM. PL.
TYPICAL MIN.
120V CIRCUIT
TYPICAL MIN.
S.S NUTS & BOLTS
1"
HANDRAIL
ON WALKWAY
LIGHT FIXTURE MOUNTING
WITH NYLON ISOLATION WASHERS. ADJUST
SIZE 316 SS BOLTS & BOLT PATTERN
STRUCTURE. COORDINATE WTIH
ATTACK TO THE WALKWAY
1"
4" DIA. ALUMINUM POLE
TYP
NOT TO SCALE
STRUCTURAL ENGINEER.
4X SS
JB
1/2" ALUM. PL.
9" M
IN
ALL POLE INSTALLATIONS MUST MEET FLORIDA
BUILDING CODE WIND LOADING REQUIREMENT
WITH APPROPRIATE WIND GUST FACTOR FOR
THE LOCATION OF INSTALLATION. THE
CONTRACTOR SHALL INCLUDE WITH THE SHOP
DRAWING SUBMITTAL, A POLE WIND LOADING
CALCULATION SIGNED & SEALED BY A
STRUCTURAL ENGINEER REGISTERED IN THE
STATE OF FLORIDA SHOWING THAT THE
PROPOSED POLE AND INSTALLATIONS WILL MEET
THE GIVEN WIND LOADING REQUIREMENT.
WINDLOADING NOTE:
1.
(DO NOT MOUNT
DEVICE ON HANDRAIL)
WP/GFI RECEPTACLE
1/
2"
4-WAY DUCTBANK
3" 3"
3" 7 1/2" 3"
NOT TO SCALE
10-WAY DUCTBANK
1/
2"
3" AT 12" ON CENTER.
U-SHAPED TIES MIN.,
ALL AROUND. 2 #3
2" MINIMUM COVER
BOTTOM
7 1/2"3"
3"
7 1/2" 3"7 1/2" 7 1/2"
#4 TOP AND
7 1/2"
3-WAY CONCRETE
ENCASED DUCTBANK
3" 3"
7 1/2"3" 3"
#4 TOP AND
BOTTOM
2" MINIMUM COVER
ALL AROUND. 2 #3
U-SHAPED TIES MIN.,
6" OVERLAP AT 12"
ON CENTER.
#4 TOP AND
BOTTOM
2" MINIMUM COVER
ALL AROUND. 2 #3
U-SHAPED TIES MIN.,
AT 12" ON CENTER.
TYP
TYP
TYP
NOT TO SCALE
NOT TO SCALE
FOR DUCTBANK WITH DIFFERENT QUANTITY OF CONDUITS SHOWN, HORIZONTAL STAGGER THE ARRANGEMENT USING
ABOVE DETAIL WITH REBAR, SPACING, AND POUR CONCRETE SIMILARLY.
KEEP MINIMUM DISTANCE SEPARATION ALLOWED BETWEEN POWER CONDUITS AND INSTRUMENTATION CONDUITS AS PER
NOTE 17 (DRAWING E-1).
NOTES:
FINISH GRADE
QUAZITE PULL BOX W/BASE,
EXPENSE AND INSTALL PER
FOR DRAINAGE
MANUFACTURER'S RECOMMENDATIONS.
SEE PLAN FOR CONDUIT
8" CRUSHED STONE OR GRAVEL
CONTRACTOR SHALL ENLARGE SIZE TO
MEET NEC WHEN NEEDED AT HIS OWN
17"X30" I.D. MINIMUM SIZE,
M
IN
IM
U
M
AND WIRE REQUIREMENTS
HEAVY DUTY, SKID RESISTANT &
NONMETALLIC TRAFFIC RATED COVER,
MARKED "ELECTRICAL" AND BOLTED
DOWN WITH STAINLESS STEEL HARDWARE
NOT TO SCALE
ELECTRICAL PULL BOX DETAIL
TYP
EXISTING PANEL ELP1 SCHEDULE (EAST BLOWER ROOM)
BUS AMPS
BA
LOADPOLESBUSAMPSPOLES AMPS
A B
LOAD
BUS AMPS
A B
21 22
EAST BLOWER ROOM
NEMA 4X STAINLESS STEELNEMA 4X
LOCATION:
FLUSH
SURFACE
BRANCH POLES
NEMA 1
COPPER BUSSES
TO BE GFI BREAKERS
HINGED DOOR
CABINET:400
277/480 1 PHASE, 3 WIRE
SPD
200%150%
___ BREAKER
ENCLOSURE TYPE
GROUND BUS
MAIN LUGS ________ SETS SIZE: _________
KEYED DOOR LATCH
NEMA 3R
RATED VOLTAGE:
RATED AMPS:
100%
MAIN LUGS ONLY
NEUTRAL BUS
PANELBOARD MUST BE RATED TO INTERRUPT A SHORT CIRCUIT ISC OF ___10,000 AMPS SYMMETRICAL.
MF'RS. EATON (CUTLER-HAMMER)
CIRCUIT BREAKER (BOLT-IN) BRANCH DEVICES
MEASURED AMPS: BUS A____ BUS B_____ CONNECTED Kva____
MAIN AMPS
120/240
HEMS PUMP-
TREATMENT UNIT #1 FLOW TRANSMITTERS
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
BATT. CHRG
DAY TANK
FAN ATS
EXISTING PANEL LP1 - A SCHEDULE
BUS AMPS
BA
LOADPOLESBUSAMPSPOLES AMPS
A B
LOAD
BUS AMPS
A B
EAST BLOWER ROOM
NEMA 4X STAINLESS STEELNEMA 4X
LOCATION:
FLUSH
SURFACE
BRANCH POLES
NEMA 1
COPPER BUSSES
TO BE GFI BREAKERS
HINGED DOOR
CABINET:400
277/480 1 PHASE, 3 WIRE
SPD
200%
150%
___ BREAKER
ENCLOSURE TYPE
GROUND BUS
MAIN LUGS ________ SETS SIZE: _________
KEYED DOOR LATCH
NEMA 3R
RATED VOLTAGE:
RATED AMPS:
100%
MAIN LUGS ONLY
NEUTRAL BUS
PANELBOARD MUST BE RATED TO INTERRUPT A SHORT CIRCUIT ISC OF ___10,000 AMPS SYMMETRICAL.
MF'RS. SQUARE D
CIRCUIT BREAKER (BOLT-IN) BRANCH DEVICES
MEASURED AMPS: BUS A____ BUS B_____ CONNECTED Kva____
MAIN AMPS
120/240
0.2
1.0
3.4
0.2
3.4
3.0 3.4
0.1 1.5
12.0
12.0SPACE
GEN ROOM RECEPS
GEN ROOM EXHAUST FAN
PLC # 2
EAST SWITCH KWH METER PANEL
PLANT LIGHT
OUTLETS
PLANT 2 LIGHT
FA
PUMP
MOV 905
FUEL SYSTEM
GAS TANK
MOV 907
LIFT STATION
POST TOP
RADPTLED-P2-40K-SYM-MVOLT-
REMARKSMOUNTINGCATALOG NODESCRIPTION MANUFACTURER
LUMINAIRE SCHEDULE
LITHONIA120
LAMPS
5000 LUM.1
TYPETYPE VOLTS
POST TOP AREA LUMINAIRE, RADEAN FAMILY LED
39 WATTS
POLE W/ COORDINATE WITH 4" POLE
SUPPLIER FOR POST TOP
MOUNTING OPTION AND
PROVIDE ACCORDINGLY.
LIGHTING
(OR)
COOPER
LIGHTING
LXS-VA-2-840-U-SYM-S-GM-F- 5000 LUM.
48 WATTSPOST TOP AREA LUMINAIRE, INVUE LUXESCAPE LED
RADPT20-SF-DNAXD
MA1036-XX
(SEE DETAIL)
PUMP
UNKNOWN
UNKNOWN
UNKNOWN
UNKNOWN
NOTE: INSTALL TWO NEW BREAKERS IN EXISTING PANEL AS SHOWN.
3.0 TREATMENT UNIT #1 LIGHTING20 1 3.0
AS NEEDED FOR INSTALLATION AS PER LIGHT
POLE MANUFACTURERS RECOMMENDATION
POWER, SEE DWG E-4
POWER, SEE DWG E-4
SIGNAL, SEE DWG E-4
SPARE SIGNAL, SEE DWG E-4
TU#1 CONTROL PANEL (LCP-TU1) VIA JBOX-P1
TU#1 CONTROL PANEL (LCP-TU1) VIA JBOX-P1
JBOX-I1 LOCATED NEAR TU#1 STAIR LANDING
JBOX-I1 LOCATED NEAR TU#1 STAIR LANDING
EXISTING EMDP-2 PANEL
EXISTING EMDP-2 PANEL
EXISTING PLC-2A PANEL
EXISTING PLC-2A PANEL
REMARKSTO
YARD CONDUIT SCHEDULE (SEE NOTE 1 THRU 3)
FROM NO.
YC04
YC03
YC02
YC01
CONTROL, SEE DWG E-4
SPARE CONTROL , SEE DWG E-4JBOX-I1 LOCATED NEAR TU#1 STAIR LANDING
JBOX-C1 LOCATED NEAR TU#1 STAIR LANDINGEXISTING PLC-2A PANEL
EXISTING PLC-2A PANELYC06
YC05
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
E-7 N.T.S.
E
LE
C
TR
IC
A
L D
E
TA
IL
S
S
H E
E T
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
I-1 N.T.S.
IN
S
TR
U
M E
N
TA
TI
O
N L
E G
E N
D A
N D
N O
TE
EXISTING PLANT
SCADA SYSTEM
EXISTING PLC-2A PANEL
(EAST MAIN ELECTRICAL
BUILDING - ELECTRICAL ROOM)
M
INFLUENT FLOW
(PUMPED RAW)
FE
TU1IF1
FIT
TU1IF1
120V, 1Ø
10" DIA.
M
M
EXISTING I/O POINTS ADDRESS FOR TU#1 AT PLC-2 PANEL:
PLC2:R1/S3/DI10: WWTU NO.1 CLARIFIER DRIVE ON/OFF
PLC2:R1/S3/DI11: WWTU NO.1 CLARIFIER DRIVE FAIL
PLC2:R1/S3/DI12: SPARE INPUT
PLC2:R1/S3/DI13: SPARE INPUT
PLC2:R1/S3/DI14: SPARE INPUT
PLC2:R1/S3/DI15: SPARE INPUT
PLC2:R1/S4/DI10: SPARE INPUT
PLC2:R1/S4/DI11: SPARE INPUT
PLC2:R1/S4/DI12: SPARE INPUT
PLC2:R1/S4/DI13: SPARE INPUT
PLC2:R1/S4/DI14: SPARE INPUT
PLC2:R1/S4/DI15: SPARE INPUT
PLC2:R1/S7/AO02: SPARE ANALOG OUTPUT
PLC2:R1/S7/AO03: SPARE ANALOG OUTPUT
PLC2:R1/S7/AO04: SPARE ANALOG OUTPUT
PLC2:R1/S7/AO05: SPARE ANALOG OUTPUT
PLC2:R1/S7/AO06: SPARE ANALOG OUTPUT
PLC2:R1/S7/AO07: SPARE ANALOG OUTPUT
V-NOTCH
WEIR
120V, 1Ø
LEVEL
TO FLOW
MEASUREMENT
QALQIL
RUNNING
STARTER-TU1-AP1
QI QA
QAQI
RUNNING FAULT
FAIL
HS
SPRAY
WATER
SUBMERSIBLE
PUMP
(TU1-SP1)
FI
FI
TREATMENT
UNIT#1
INFLUENT
FLOW
TU1IF1
TU1IF1
A
QA
QA
TREATMENT
UNIT#1
EFFLUENT
FLOW
TU1EF1
TU1EF1
A
TU#1 SPRAY WATER PUMP
QALQIL
RUNNING
480V, 3Ø
FAIL
4X SS POWDER COATED
WHITE WITH SUNSHIELD
ON TOP AND SIDES
TU1RK1 TU1RK1 TU1SP1 TU1SP1TU1SP1
TU1SP1 TU1SP1
TU1SP1TU1SP1
RETURN
SLUDGE
AIRLIFT
ASSEMBLY
EXISTING AIR SUPPLY
CONNECTION
QI QA
QAQI
RUNNING FAULT
TU#1 CLARIFIER DRIVE
CONTROL PANEL LCP-TU1
TU1RK1 TU1RK1
TU1RK1TU1RK1
FIT
TU1EF1
LE
TU1EF1
STARTER-TU1-RK1 **
HS
RESET
TU1B
LIMIT
SWITCH
RAS/WAS
MOTORIZED
VALVE
(TU1-CV1)
HS
TU1RK1
HOA
TREATMENT UNIT CONTROL
PANEL LCP-TU1
ZS
TU1LS2
LIMIT
SWITCH
ZS
TU1LS1
TIMER
SV**
SPRAY
NOZZLE
SPRAY
NOZZLE
QI
QA
TU#1
TORQUE
ALARM
TU1RK1A
TU1RK1A
V-NOTCH
WEIR
LE
TU1SB1
120V, 1Ø
LEVEL
TO FLOW
MEASUREMENT
FIT
TU1SB1
FI
FI
TREATMENT
UNIT#1
RAS OR
WAS
FLOW
TU1SB1
TU1SB1
A
AE
TU1DO1
AE
TU1DO1
FUTUREFUTURE
AIT
TU1DO1
FUTURE
AIT
TU1DO1
FUTURE
AI
AI
TREATMENT
UNIT#1
RE-AIR
DO
TU1DO1
TU1DO1
A
AI
AI
TREATMENT
UNIT#1
EFFLUENT
DO
TU1DO2
TU1DO2
A
R 1/
S3 /D
I1
R 1/
S3 /D
I1
R 1/
S3 /D
I1
R 1/
S3 /D
I1
EXISTING I/O POINTS ADDRESS FOR TU#1 AT PLC-5 PANEL:
(NOTE: PLC-5 PANEL IS LOCATED IN EFFLUENT ELECTRICAL ROOM)
PLC5:R1/S5/AI00: WWTU NO.1 RE-AIR DO (0-10 PPM)
PLC5:R1/S5/AI01: WWTU NO.1 CHLORINE CONTACT DO (0-10 PPM)
PLC5:R1/S5/AI03: WWTU NO.1 INFLUENT FLOW (0-4 MGD)
PLC5:R1/S5/AI05: WWTU NO.1 EFFLUENT FLOW (0-3 MGD)
PLC5:R1/S5/AI06: WWTU NO.1 AIR FLOW (0-6000 SCFM)
PLC5:R1/S9/AO04: WWTU NO.1 SPLITTER BOX ACTUATOR VALVE (0-100%)
R 1/
S4 /D
I1
R 1/
S8 /A
I0
R 1/
S8 /A
I0
R 1/
S8 /A
I0
CLARIFIER
DRIVE
TS
TU1TS1
TORQUE
SWITCH
1 CONTRACTOR SHALL PROVIDE AND INSTALL NEW
LOCAL CONTROL PANEL FOR TREATMENT UNIT NO.1
LOCAL CONTROL PANEL, INCLUDING STARTER, SPD,
BREAKERS, TIMER, RELAY, LED PUSH TO TEST
INDICATION LIGHTS, ETC. IN A NEMA 4X 316
STAINLESS STEEL CONTROL PANEL. NEW PANEL
SHALL BE POWDER COATED WHITE WITH
SUNSHIELD ON TOP AND SIDES. CONNECT LCP TO
PLC-2 PANEL AS SHOWN AND AS REQUIRED. THERE
ARE EXISTING SPARE I/O POINTS IN THE PLC-2
PANEL AND CONTRACTOR SHALL FIELD VERIFY AND
ADJUST THE I/O POINTS AS NEEDED.
CONTRACTOR SHALL PROVIDE AND INSTALL ALL
NECESSARY RELAYS, TERMINAL BLOCKS, SURGE
ARRESTORS, WIRING, ETC. AS NEEDED FOR NEW
SIGNALS AT THE PLC-2 PANEL. MAKE ALL
NECESSARY CONNECTIONS, TERMINATIONS,
MODIFICATIONS, ETC. FOR A COMPLETE AND
FUNCTIONAL PLC SYSTEM IN PLACE.
EXISTING ANALOG SIGNALS ASSOCIATED WITH THE
EXISTING TREATMENT UNIT NO.1 (TU#1) AT THE
PLC-5 PANEL (EFFLUENT ELECTRICAL BUILDING)
SHALL BE DISCONNECTED DURING THE
REHABILITATION OF THE TU#1. UPDATE THE I/O
LOOP DIAGRAMS AND LABEL THEM AS SPARE. ALL
NEW SIGNALS ASSOCIATED WITH THE
REHABILITATED TU#1 SHALL BE CONNECTED TO THE
PLC#2 PANEL AS SHOWN ON DRAWINGS AND AS PER
SPECIFICATIONS.
CONTRACTOR SHALL PROVIDE AND INSTALL ONE
NEW ANALOG INPUT MODULE (8 CHANNEL) IN THE
EXISTING PLC-2 RACK SPARE SLOT LOCATION.
EXISTING PLC IS CONTROLLOGIX (1756-L61) MODEL.
PROVIDE AND INSTALL NEW SURGE ARRESTORS,
TERMINAL BLOCKS, WIRING, ETC. FOR A COMPLETE
AND FUNCTIONAL PLC SYSTEM IN PLACE.
PROVIDE AND INSTALL SUNSHIELD AND PIPE STAND,
SPD, ETC. FOR ALL FLOW AND LEVEL TRANSMITTER.
TYPICAL.
COORDINATE WITH SPLITTER BOX SUPPLIER FOR
THE ACTUAL DIMENSIONS OF SPLITTER BOX AND
V-NOTCH WEIR LAYOUT TO DETERMINE THE
LOCATION TO INSTALL THE FLOW/LEVEL SENSOR.
REQUEST ALL NECESSARY PARAMETERS OF THE
V-NOTCH WEIR FOR FLOW CALCULATION AND
SETUP THE FLOWMETER ACCORDINGLY.
FIELD OBTAIN AND COPY THE EXISTING V-NOTCH
WEIR PARAMETERS FROM THE EXISTING
FLOWMETER BEFORE REPLACEMENT AND SETUP
NEW FLOWMETER ACCORDINGLY.
KEYED NOTES:
DIFFUSERSDIFFUSERS
STILLING
WELL
MOD.
ZC
ZC
TU#1
SPLITTER
BOX VALVE
POSITION
CONTROL
TU1CV1
TU1CV1
A
R 1/
SX
/A
I0
R 1/
S8 /A
I0
R 1/
S8 /A
I0
FUTUREFUTURE
ZI
ZI
TU#1
SPLITTER
BOX VALVE
POSITION
INDICATION
TU1CV1
TU1CV1
A
R 1/
S8 /A
I0
480V, 3Ø
QI
QA
TU#1
TORQUE
SHUTDOWN
R 1/
S4 /D
I1
QIL
TORQUE
ALARM
TU1RK1A
QIL
TORQUE
SHUTDOWN
TU1RK1B
OO
TU1RK1B
TU1RK1B
SPD
SV-TU1SV1
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
I-2 N.T.S.
P
ID
TR
E
A
TM
E N
T U
N
IT
N O
.1
NOTES:
ROUND OFF ALL EXPOSED EDGES AND CORNERS. ALL S.S. SHALL
BE 316 STAINLESS STEEL.
SEE SPECIFICATIONS FOR SPD INFORMATION
1" NONSHRINK
GROUT
SECURE TO SLAB WITH 4-1/2"
SS CONCRETE ANCHORS
1/2 "x12"x12" S.S. PLATE
4" SCH 40 S.S. PIPE
4"x2" S.S. REDUCER
2" SCH 40 S.S. PIPE
L 2 1/2 "x2"x 1/4 " S.S. LENGTH TO
SUIT INSTRUMENT
INSTRUMENT
L 2 1/2 "x2"x 1/4 " S.S.
LENGTH TO SUIT
INSTRUMENT
MOUNTING HOLES TO SUIT INSTRUMENT SECURE
INSTRUMENT TO STANCHION W/316 S.S. BOLTS, NUTS
& WASHERS
NOT TO SCALE
2'-6"
4'6"
TO SUIT
INSTRUMENT
3/16
3/16 G
3/16
L
1.
STANCHION SUPPORT FOR
CASE MOUNTED INSTRUMENTS
L
RAIN HOOD REQUIRED
FOR OUTDOOR APPLICATION
UV PROTECTIVE
FLEXIBLE
SUN SHIELD
INSTALLATION DETAIL
MAGNETIC FLOWMETER
NOT TO SCALE
SPD
SPD
2.
VAR.
VAR.
HANDRAIL
RIGID
CONDUIT
PIPE
SUPPORT
LEVEL TRANSMITTER
4'-6"
INSTALLATION DETAIL
ULTRASONIC LEVEL TRANSMITTER
VAR.
WALL
FLEXIBLE CONDUIT
WITH MSC
SONIC SENSOR
MAX. LEVEL
MIN. 1 FT. FOR EVERY
10 FT. LEVEL DEEP
NEW HINGED TRANSDUCER
BRACKET (PULSAR MODEL:
dBA003) OR EQUAL.
EXISTING
GRATING
LEVEL TRANSDUCER WITH
CABLE LENGTH AS
NECESSARY (FIELD ADJUST
MOUNTING LOCATION AS
NEEDED INSIDE CLARIFIER
COLLECTION BOX)
PIPE STAND WITH
SUNSHIELD
SPD
4 WIRE INSTRUMENT
4 WIRE INSTRUMENT
PANEL LP"X"
120VAC
4-20MA OUTPUT
PANEL LP"X"
120VAC
1 2
7 6
SURGE SUPRESSOR
EDCO SLAC
4-20MA OUTPUT+
(TYP)
FIELD PANEL
(TYP)
SURGE SUPRESSOR
EDCO PC642
9 8
PLC I/O
TYPICAL 4 WIRE INSTRUMENT ISOLATOR
NOT TO SCALE
VAR.
TREATMENT UNIT NO.1CONTROL SCHEMATIC
COORDINATE WITH
TREATMENT UNIT NO.1
SYSTEM SUPPLIER FOR
SPRAY WATER AND
CLARIFIER DRIVE TORQUE
SWITCH INTERLOCKING
REQUIREMENTS. ADJUST
SCHEMATIC AS NEEDED TO
COMPLY WITH THE
FUNCTION REQUIRED BY
THE SYSTEM SUPPLIER
DURING SHOP DRAWING
PHASE.
S E
A L:
R E
V I
S I
O N
S
CITY OF P.P. PLAN SUBMITTAL:
D A
TE
N
O
B Y
D E
S C
R
IP
TI
O
N
OFSHEET:
PE
M
BR
O
KE
P
IN
ES
, F
LO
R
ID
A
C
IT
Y O
F
PE
M
BR
O
KE
P
IN
ES
S O
U
TH
P
AL
M D
R
IV
E
KNOW WHAT'S BELOW
ALWAYS CALL 811
BEFORE YOU DIG
It's fast. It's free. It's the law.
www.callsunshine.com
R
SHEET NUMBER:
SUBMITTAL DATE:
SCALE:
U
TI
LI
TI
ES
D
EP
AR
TM
EN
T
MARCH 2025
X X
W A
S
TE
W A
TE
R
T R
E A
TM
E
N T
P
LA
N T
U N
IT
R E
H A
B
IL
IT
A
TI
O
N
P em br ok e
R d, P em br ok e P in es
, F L
100% SET
I-3 N.T.S.
IN
S
TR
U
M E
N
TA
TI
O
N D
E
TA
IL
| cover.pdf |
| P2.pdf |
| P3.pdf |
| P1.pdf |
| 202503 100% Electrial and Instrumentation.pdf |
| Sheets and Views |
| E-1 ELECTRICAL LEGEND AND NOTES |
| E-2 ELECTRICAL SITE PLAN - DEMOLITION |
| E-3 PHOTOS AND EAST ELECTRICAL BUILDING |
| E-4 ONE LINE AND RISER DIAGRAM |
| E-5 MODIFIED TREATMENT UNIT 1 ELECTRIC PLAN |
| E-6 ELECTRICAL DETAILS - SHEET 1 |
| E-7 ELECTRICAL DETAILS - SHEET 2 |
| I-1 INSTRUMENTATION LEGEND AND NOTES |
| I-2 P&ID - TREATMENT UNIT NO.1 |
| I-3 INSTRUMENTATION DETAILS |
File details come from the government source that posted it. Updated .