This document is a combined synopsis/solicitation for the replacement of an influent magnetic flow meter at the Nogales International Wastewater Treatment Plant (NIWTP) operated by the International Boundary and Water Commission (IBWC). The solicitation is a 100% Small Business Set-Aside request for quote (RFQ) with a NAICS code of 221320 Sewage Treatment Facilities. The requirement is for the replacement of the current inflow magnetic flow meter per the plant's maintenance and repair manuals. The solicitation provides details on the site visit, submission of questions, quote due date, and evaluation criteria, which include technical acceptability, technical approach, past performance, and price. Award will be made to the responsible offeror whose offer represents the best value to the Government. Attachments include a CLIN structure, Performance Work Statement, Quality Assurance Surveillance Plan, and Wage Determination.

View the file

Other files for this federal contract opportunity

Other files attached to Influent Magnetic Meter Replacement, newest first.
File Type Posted
AP Model 10D1435A.pdf PDF
AscherPorter MagMeter specs (002).pdf PDF
Questions and Responses - 8.16.pdf PDF
Site image-Magmeter and Potential Bypass Points.pdf PDF
S4.pdf PDF
FY24 PWS Replace Influent MAG Meter 4 17 2024 rev.pdf PDF
QASP NIWTP Replace MAG Meter 4 17 2024.pdf PDF
CLIN Structure - Replace Mag Meters.pdf PDF
WD 20105-5481 REV 23.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 MAGNETIC FLOW MEASURING SYSTEMS

A. Magnetic Flowmeter Systems: Magnetic flowmeter systems shall be of the low frequency electromagnetic induction type and produce a DC pulsed signal directly proportional to and linear with the liquid flow rate. Complete zero stability shall be an inherent characteristic of the flowmeter system. Each magnetic flow metering system shall include a metering tube, signal cable, transmitter and flowmeter grounding rings.

B. Metering Tube: The metering tube shall have the following attributes:

1. Be constructed of ASTM A 316 stainless steel with flanged connections

2. Utilize a minimum of 2 bullet-nosed, self-cleaning electrodes

3. Include a liner in conformance with the manufacturer's recommendation for the intended service

4. Have electrodes constructed of materials which are in conformance with the manufacturer's recommendation for the intended service

5. Have housing rated for NEMA 6 submergence conditions and be coated with epoxy paint

C. Ground Rings: Magnetic flow meters shall have 2 grounding rings which are in conformance with the manufacturer's bore and material recommendation for the intended service. Grounding rings shall be designed to protect and shield from process abrasion the liner edge interface at the metering tube end.

D. Transmitter: The microprocessor-based signal converter/transmitter shall have the following attributes:

1. Utilize DC pulse technique to drive flux-producing coils

2. Convert DC pulse signal from the tube to a standardized 4-20 mA signal into a minimum

700 ohms

3. Include a 6 digit LCD display for flowrate, percent of span, and totalizer

4. Include an operator interface consisting of keypads which respond to English text entry

5. Feature an integral zero return to provide a consistent zero output signal in response to an external dry contact closure

6. Be capable of measuring flow in both directions

7. Integral low flow cutoff and zero return

8. Automatic range change

9. Programmable parameters including meter size, full scale Q. magnetic field frequency, primary constant, time constant

10. Data retention for a minimum of 5 years without line or battery power

11. Self diagnostics and automatic data checking

12. Protected terminals and fuses in a separate compartment which isolates field connection from electronics

13. [Utilize "Smart" technology which employs a hand-held configuration terminal and outputs a digital flow signal superimposed on 4-20 mA signal that complies with the HART protocol.]

14. [Produce a scaleable frequency output, O to 100 Hz, transistor switch closure up to 5.75

W externally powered, 5 to 24 V DC]

15. Can tolerate ambient temperature operating limits of -20 to 140 degrees Fahrenheit (-

29 to 60 degrees C)

E. Signal Cable: Signal cable shall be the manufacturer's standard cable for the intended application.

F. Performance: The flow metering system shall conform to the following technical specifications: Time constant= 0.5 to 1000 seconds; galvanic or optic isolation: Accuracy:

0.25% of flow rate from 10 to 100% full scale for velocities over 3 fps: Repeatability: 0.25% full Scale: Power consumption: 30 watts or less: Power Requirements: 120 VAC, ± 10%:

2.0 CALIBRATION

A. Each flow metering system shall be hydraulically calibrated at a facility which is traceable to the National Institute of Standards and Technologies. The calibration procedure shall conform to the requirements of MIL-STD-45662A. A real-time computer generated printout of the actual calibration data indicating apparent and actual flows at 20 percent, 40 percent, 60 percent, 80 percent, and 100 percent of the calibrated range shall be submitted to the CONSTRUCTION MANAGER at least thirty (30) days prior to shipment of the meters to the project site.

2.1 MANUFACTURERS

A. Meters shall be manufactured by one of the following (or equal):

1. Fischer & Porter

2. Foxboro

3. Johnson Yokagawa

4. Krohne

PART 3 -- EXECUTION

3.1 INSTALLATION

A. Magnetic flow meters shall be installed in accordance with the manufacturer's installation instructions and Section 15150.

B. Meters shall be properly grounded to the adjacent pipe where indicated to ensure full pipe grounding.