20220503 - BLDG 10 - PermPumpPack - Drawings - Combined.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24723Q0344
About this file
This federal solicitation is for the procurement of a permanent fire pump for the W.J.B. Dorn VA Medical Center in Columbia, South Carolina. Key requirements include furnishing a new diesel-driven fire pump, prefabricated house, day tank, and all necessary accessories. The fire pump must be UL listed and FM approved and meet NFPA 20, NFPA 37, NFPA 70, and seismic protection standards. The contractor must test and commission the system at the manufacturer's facility and on site, and advise the VA of testing dates with 10 days' notice. Related specifications cover general requirements, commissioning, wet and dry pipe sprinkler systems, diesel fire pumps, low-voltage power, raceways, fire detection and alarms, and grounding and bonding. The contractor must comply fully with all specification sections.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S01-RFQ 36C24723Q0344_1 02-24-2023-.docx | DOCX document | |
| S01-RFQ 36C24723Q03441-02-23-2023---.docx | DOCX document | |
| 20220505 - BLDG 10 - PermPumpPack - Specifications - Combined.pdf | ||
| 36C24723Q0344.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Architects/Engineers/Planners
KMG
1201 Main Street, Suite 2100
Columbia, South Carolina 29201 tel. 803-256-0000 fax 803-255-7243
A S S O C I A T E S, I N C.
Prepared by:
W.J.B. DORN VA MEDICAL CENTER
COLUMBIA, SOUTH CAROLINA
DEPARTMENT OF VETERAN'S AFFAIRS
DRAWING INDEX
CIVIL (NOT USED)
ARCHITECTURAL (NOT USED)
FIRE PROTECTION
MECHANICAL (NOT USED)
ELECTRICAL
STRUCTURAL (NOT USED)
PLUMBING (NOT USED)
VA PROJECT #544-21-119
05/03/2022
ISSUED FOR
BID SET
B10 Permanent Pump Acquisition Package
FA001 FIRE DETECTION - LEGEND, NOTES, AND DRAWING INDEX
FA002 FIRE DETECTION DETAILS
FA003 FIRE DETECTION - FIRESTOP DETAILS
FA004 FIRE DETECTION - RISER DIAGRAMS AND I/O MATRIX
FA201 FIRE DETECTION - FIRST FLOOR - FIRE PUMP
FA202 FIRE DETECTION - FIRE PUMP LOCATIONS EXISTING CONDITIONS
FX001 PERMNANENT FIRE SUPPRESSION - LEGENDS, NOTES AND DRAWING INDEX
FX002 PERMNANENT FIRE SUPPRESSION - FIRESTOP DETAILS
FX003 PERMNANENT FIRE SUPPRESSION - DETAILS
FX005 PERMNANENT FIRE SUPPRESSION - FIRE, JOCKEY PUMP SCHEDULE
FX201 PERMNANENT FIRE SUPPRESSION - FIRE PUMP HOUSE PLAN
FX202 PERMNANENT FIRE SUPPRESSION - EXISITING CONDITIONS
(NOT USED)
FIRE EXTINGUISHER SCHEDULE
FIRE EXTINGUISHER MUST BE ENGAUGE ENABLED INTELLIGENT
FIRE EXTINGUISHER WITH MONITORING CAPABILITY. THE FIRE
EXTINGUISHER WILL BE A 20 LB (120B:C) DRY CHEMICAL FOR
USE AT THE FIRE PUMP HOUSE FOR EXTINGUISHMENT OF
ELECTRICAL AND FLAMMABLE LIQUID INCIPIENT FIRES.
FE3
DESIGN CODES, STANDARDS & PARTIES OF REFERENCE
THE FOLLOWING PUBLICATIONS AND AUTHORITIES HAVING JURISDICTION SHALL BE
REFERENCED FOR THE DESIGN OF THE FIRE PROTECTION SYSTEM ON THIS PROJECT:
1. ANSI, A117.1 STANDARD, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES. 2017
EDITION
2. ASCE 7 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, 2022
EDITION
3. ASME A17.1 - SAFETY CODE FOR ELEVATORS AND ESCALATORS INCLUDES
REQUIREMENTS FOR ELEVATORS, ESCALATORS, DUMBWAITERS, MOVING WALKS,
MATERIAL LIFTS AND DUMBWAITERS WITH AUTOMATIC TRANSFER SWITCHES, 2019
EDITION
4. INTERNATIONAL BUILDING CODE 2021 EDITION
5. NFPA 1 - FIRE CODE, 2021 EDITION
6. NFPA 10 - STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2022 EDITION
7. NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION
8. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE
PROTECTION, 2022 EDITION
9. NFPA 70 - NATIONAL ELECTRIC CODE, 2020 EDITION
10. NFPA 72 - NATIONAL FIRE ALARM & SIGNALING CODE, 2022 EDITION
11. NFPA 101 - LIFE SAFETY CODE. 2021 EDITION
12. NFPA 241 - STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERNATION AND
DEMOLITION OPERATIONS, 2019 EDITION
13. VA FIRE PROTECTION DESIGN MANUAL, JUNE 1, 2021 EDITION
14. VA SEISMIC DESIGN REQUIREMENTS, REVISED MAY 1, 2020 EDITION
15. VA FIRE SAFETY
16. ALL AUTHORITIES HAVING JURISDICTION
TS
FIRE ALARM SYMBOLS
FIRE SUPPRESSION TAMPER SWITCH TO
SPRINKLER SYSTEM; FIRE ALARM INTERFACE
REQUIRED
FIRE EXTINGUISHER, DRY CHEMICAL FOR ALL TYPES OF FIRES
(EXCEPT METALS) ABC TYPE
WF FIRE SUPPRESSION WATER FLOW SWITCH TO
SPRINKLER SYSTEM; FIRE ALARM INTERFACE
REQUIRED
COMBINATION SPEAKER / VISIBLE - CEILING MOUNT.
CD = CANDELA RATING/ SETTING
FIRE ALARM TERMINAL CABINET
FIRE EXTINGUISHER STATION MODULE
M
CD
EVM
1. THE CONTRACTOR WILL BE HELD RESPONSIBLE TO HAVE EXAMINED THE EXISTING SITE
CONDITIONS FOR THE WORK INCLUDED UNDER THIS CONTRACT. NO ALLOWANCE WILL BE MADE
SUBSEQUENTLY IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR
NEGLIGENCE ON THEIR PART.
2. NO FIRE ALARM DOCUMENTS/PLANS SHALL BE USED FOR DEMOLITION AND INSTALLATION OF
THIS SYSTEM UNLESS THEY CONTAIN A REVIEW AND APPROVAL STAMP FROM THE VA FIRE
SAFETY AND A COMPLETED REVIEW BY THE ARCHITECT/ENGINEER. THE VA FIRE SAFETY OR
ARCHITECT/ENGINEER HAS THE AUTHORITY TO STOP ANY WORK UNTIL SUCH PLANS ARE ON
SITE AND IN USE.
3. ALL FIRE ALARM DEVICE LOCATIONS SHALL BE COORDINATED WITH PLUMBING PIPING,
MECHANICAL PIPING, MECHANICAL EQUIPMENT, SIGNS, AND OTHER MEP TRADES PRIOR TO
CONSTRUCTION.
4. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN OF THE
LAYOUTS, DEVICES COUNTS, CONDUCTOR TYPES, WIRING DIAGRAMS, I/O MATRIX, RISER
DIAGRAMS, AND BATTERY CALCULATIONS SHALL BE SEALED BY AN PROFESSIONAL ENGINEER
REGISTERED IN THE STATE OF SOUTH CAROLINA OR A NICET LEVEL III OR LEVEL IV FIRE ALARM
DESIGNER.
5. FLOOR/WALL PENETRATIONS THROUGH RATED SEPARATIONS SHALL BE SEALED WITH AN FM
APPROVED FIRE RATED MATERIAL AND METHODS.
6. WALL PENETRATIONS THROUGH NON-RATED PARTITIONS SHALL BE PROVIDED WITH A NON-
SHRINKING GROUT OR CAULKING MATERIAL AND APPROVED ASSEMBLY.
7. THE FIRE ALARM PLANS ARE FOR COORDINATION AND BIDDING PURPOSES ONLY. THE FIRE
ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN.
8. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF
WALLS AND CEILING REQUIRED FOR THE INSTALLATION OF THE NEW FIRE SUPPRESSION
SYSTEM.
9. THE CIRCUIT WIRING SHALL BE SIZED AS FOLLOWS:
A. NOTIFICATION APPLIANCE CIRCUITS SHALL BE A MINIMUM OF #14 AWG.
10. B. SIGNAL LINE CIRCUITS SHALL BE MINIMUM OF #18 AWG AND MAXIMUM OF #14 AWG.
11. THE FIRE ALARM SYSTEM SHALL BE AN ADDRESSABLE SYSTEM INCLUDING INDIVIDUALLY
ADDRESSED DEVICES.
12. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING EXISTING
CONDITIONS PRIOR TO CONSTRUCTION. THE EXISTING FIRE ALARM EQUIPMENT AT BUILDING
B10, PROTECTED PREMISE FIRE ALARM CONTROL PANEL AND THE MAIN FIRE ALARM CONTROL
PANEL AT BUILDING 100, EMERGENCY COMMUNICATION CENTER NEEDS TO BE FIELD VERIFIED
TO DETERMINE INTERFACE POINTS AND IF EXISTING TWO FIRE ALARM CONTROL PANEL(S)
REQUIRES TO BE EXPANDED DUE TO THIS BUILDING CONSTRUCTION. THIS CONTRACTOR SHALL
INCLUDE EXPANSION AND UPGRADE OF BATTERIES, IF EXISTING CONDITIONS WILL NOT MEET
NFPA 72 WITH THE NEW ADDITION INTO THIS SCOPE OF WORK.
13. FURNISH AND INSTALL END-OF-LINE RESISTORS AND CLEARLY MARK THE LOCATION OF THIS
DEVICE.
14. ALL FIRE ALARM SYSTEM COMPONENTS SHALL BE UL LISTED.
15. FIRE ALARM SYSTEM SHALL INTERFACE WITH THE FIRE SUPPRESSION SYSTEM WHERE ZONING
SHALL BE ON A PER FLOOR BASIS (E.G., ONE ZONE PER FLOOR).
16. NATIONALLY RECOGNIZED CODES, AND THE VA DESIGN MANUAL REQUIREMENTS MUST USE
THE REQUIREMENTS OF NFPA FOR CONFLICTS AND NOT THE MOST STRINGENT CODE OR VA
DESIGN MANUALS.
17. FOLLOWING THE FIRE ALARM SYSTEM INSTALLATION, A 100% FIRE ALARM SYSTEM ACCEPTANCE
TEST SHALL BE CONDUCTED BY THE FIRE ALARM CONTRACTOR FOR THE SCOPE OF WORK
SHOWN ON THESE DOCUMENTS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT, ENGINEER,
OWNER AND ALL AUTHORITIES HAVING JURISDICTION WITHIN FOUR(4) WORKING DAYS OF THE
TEST FOR SCHEDULING.
18. ALL FIRE ALARM DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 20, NFPA 70, NFPA
72, NFPA 101, VA FIRE PROTECTION DESIGN MANUAL AND PROJECT SPECIFICATION
REQUIREMENTS.
19. ALL INSTALLED FIRE ALARM DEVICES SHALL BE UL LISTED AND APPROVED FOR INSTALLATION
WITH THE EXISTING TWO FIRE ALARM CONTROL PANELS, E.G., ONE IN THE FIRST FLOOR
VESTIBULE AREA OF BUILDING B10 AND THE OTHER MAIN FIRE ALARM CONTROL PANEL IS
LOCATED IN THE EMERGENCY COMMUNICATION CENTER OF BUILDING 100.
20. ALL FIRE ALARM DEVICES SHALL BE ACCESSIBLE FOR PERIODIC INSPECTIONS, MAINTENANCE
AND TESTING PURPOSES.
21. ALL FIRE ALARM DEVICES SUBJECT TO MECHANICAL DAMAGE SHALL BE PROTECTED BY A
MANUFACTURER'S APPROVED PROTECTIVE COVER/GUARD.
22. THE FIRE ALARM CONTRACTOR SHALL PREPARE AS-BUILT DRAWINGS DURING THE
INSTALLATION OF THE FIRE ALARM SYSTEM.
23. A FIRE ALARM SYSTEM RECORD OF COMPLETION SHALL BE PRESENTED TO THE ARCHITECT, ENGINEER, AND VA FIRE SAFETY AT THE CONCLUSION OF THIS FIRE ALARM SYSTEM
INSTALLATION.
24. THE CONTRACTOR SHALL PROVIDE THE VA REPRESENTATIVE WITH OPERATING, TESTING,
MAINTENANCE INSTRUCTION, SITE SPECIFIC SOFTWARE CHANGES/ADDITIONS, AND AS-BUILT
DRAWINGS AT THE CONCLUSION OF THIS FIRE ALARM INSTALLATION.
25. THE CONTRACTOR SHALL PROVIDE THE VA REPRESENTATIVE WITH MAINTENANCE AND
TESTING SCHEDULE FOR ALL EQUIPMENT FURNISH/INSTALLED UNDER THIS SCOPE OF WORK IN
ACCORDANCE WITH NFPA 72 GUIDELINES.
26. ALL FIRE ALARM CABLE SHALL BE INSTALLED WITHIN A CONDUIT AND PER NFPA 70
REQUIREMENT.
27. ALL FIRE ALARM CABLE SHALL BE MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 70
AND NFPA 72 REQUIREMENTS.
28. NATIONALLY RECOGNIZED CODES, AND THE VA DESIGN MANUAL REQUIREMENTS MUST USE
THE REQUIREMENTS OF NFPA FOR CONFLICTS AND NOT THE MOST STRINGENT CODE OR VA
DESIGN MANUALS.
29. ALL FIRE ALARM CIRCUITS SHALL BE DURABLY MARKED AND LABELED WHERE THE
IDENTIFICATION SHALL BE CLEARLY VISIBLE.
30. ALL FIRE ALARM CABLE SHALL BE INSTALLED IN A CONDUIT IN A NEAT, WORKMAN LIKE MANNER.
31. ALL FIRE ALARM CABLES SHALL BE INSTALLED IN A CONDUIT OR METALIC RACEWAY AND BE
INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE. FIRE ALARM CABLE SHALL NOT
BE STRAPPED, TAPED OR ATTACHED BY ANY MEANS TO THE EXTERIOR OF ANY CONDUCTOR
OTHER RACEWAY AS A MEANS OF SUPPORT.
32. ALL FIRE ALARM CABLE INSTALLED IN A CONDUIT SHALL BE SUPPORTED BY STRAPS, HANGERS
OR SIMILAR FITTING DESIGNED AND INSTALLED SO AS NOT TO DAMAGE THE CABLE.
33. ALL FIRE ALARM CABLES INSTALLED IN A CONDUIT SHALL BE ACCESSIBLE; WHERE, BUILDING FEATURES DO NOT PROVIDE ACCESSIBILITY, OR THE FIRE ALARM CABLE SHALL BE INSTALLED IN
AN APPROVED CONDUIT/METAL RACEWAY.
34. ALL WIRING SHALL BE SECURED TO THE STRUCTURE AS SPECIFIED IN NFPA 70.
35. ALL CONDUIT/RACEWAY SHALL BE SECURED TO THE STRUCTURE AS SPECIFIED IN NFPA 70.
36. THE FIRE ALARM SYSTEM SHALL BE TEST FREE OF GROUNDS.
37. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR DETERMINING CABLE FILL/CONDUIT SIZING PER NFPA 70 REQUIREMENTS (ALL FIRE ALARM CONDUIT SHALL BE A MINIMUM SIZE OF 3/4 -
INCH).
38. A VOLTAGE DROP CALCULATION SHALL BE PERFORMED AND SUBMITTED BY THE FIRE ALARM
CONTRACTOR FOR POWER CONSUMING CIRCUITS; IN ORDER TO VALIDATE THAT THE SYSTEM
HAS BEEN DESIGNED WITHIN NFPA TOLERABLE LIMITS. NOTIFICATION APPLIANCE DEVICE
CIRCUITS VOLTAGE DROP CALCULATIONS SHALL HAVE A MAXIMUM VOLTAGE DROP OF 15%
AND A PREFERRED VOLTAGE DROP OF 10% MEETING NFPA 72, SECTION 10.3.5.
FIRE ALARM GENERAL NOTES FIRE ALARM AND DETECTION NOTE
FIRE ALARM AND DETECTION PLANS ARE SHOWN FOR BIDDING PURPOSES. FIRE
ALARM AND DETECTION CONTRACTOR IS TO SUBMIT SHOP DRAWING. FIRE ALARM
CALCULATIONS MEETING NFPA 72 AND VA FIRE PROTECTION DESIGN MANUAL, ALL
SHOP DRAWINGS AND CALCULATION ARE TO BE SIGNED. STAMPED AND SEALED BY
EITHER A LICENSED FIRE PROTECTION ENGINEER IN THE STATE WHERE WORK WILL
BE PERFORMED OR A NICET LEVEL III OR IV CERTIFICATION IN FIRE ALARM SYSTEM
LAYOUT. ALL WORK IS TO BE DONE IN ACCORDANCE WITH THE VA REQUIREMENTS
AND APPLICABLE CODES.
39. ALL FIRE ALARM WIRING SHALL BE INSTALLED IN A CONDUIT/RACEWAYS SEPARATE FROM
ALL OTHER SYSTEMS.
40. MAINTAINABILITY:
1. EXTERNAL AND INTERNAL PARTS SHALL BE ARRANGED SO THAT, WHEN INSTALLED,
ALL PARTS REQUIRING MANIPULATION, OBSERVATION, AND/OR MAINTENANCE ARE
READILY ACCESSIBLE AND SAFE FOR OPERATION AND MAINTENANCE PERSONNEL.
SPECIFY ANY MAINTENANCE ENVELOPES AND CLEARANCES AROUND INSTALLED
EQUIPMENT. WHEREVER PRACTICAL, VALVES AND INSTRUMENTS SHALL BE
LOCATED SUCH THAT THEY CAN BE OPERATED AND EASILY ACCESSED FROM
GRADE LEVEL.
2. MAINTAINABILITY SHALL BE INCORPORATED INTO THE DESIGN OF ALL CONTRACTOR
SUPPLIED EQUIPMENT. THE PRIMARY MAINTAINABILITY OBJECTIVE SHALL BE TO
MINIMIZE THE COMPLEXITY AND TIME REQUIRED FOR MAINTENANCE. THE
FOLLOWING GENERAL CRITERIA SHALL BE OF A LOW MAINTENANCE DESIGN AND
SHALL BE EASILY MAINTAINABLE.
A. CONTRACTOR SUPPLIED EQUIPMENT SHALL BE OF LOW MAINTENANCE
DESIGN AND SHALL BE EASILY MAINTAINABLE.
B. CONTRACTOR SUPPLIED EQUIPMENT SHALL BE DESIGNED TO BE
MAINTAINED IN PLACE, IF POSSIBLE, WITH MINIMUM DISASSEMBLY OF
SURROUNDING EQUIPMENT AND MINIMUM USAGE OF TEMPORARY
SCAFFOLDING AND HANDLING EQUIPMENT.
41. WIRING INSTALLED IN METAL RACEWAYS WITHIN BUILDINGS THAT ARE PROTECTED WITH
100% COMPLETE SPRINKLER COVERAGE SHALL BE CONSIDERED TO MEET THE
REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN ACCORDANCE WITH NFPA 72 AS
A 2-HOUR PERFORMANCE ALTERNATIVE THAT HAS BEEN APPROVED BY THE AUTHORITY
HAVING JURISDICTION AND SHALL BE PERMITTED FOR VOICE COMMUNICATION SYSTEMS IN
VA FACILITIES.
42. WIRING FOR BUILDING FIRE ALARM SYSTEMS SHALL BE SPECIFIED AS DEFINED IN NFPA 72
AND AS FOLLOWS:
1. SIGNALING LINE CIRCUITS (SLC): CLASS B.
2. INITIATING DEVICE CIRCUITS (IDC): CLASS B
3. COMMUNICATION BETWEEN BUILDING FIRE ALARM CONTROL UNITS (E.G.., SUCH AS
BETWEEN THE FIRE PUMP HOUSE AND BUILDING B10 LOCAL FIRE ALARM CONTROL
PANEL: CLASS X
1. WHERE SIGNALING LINE CIRCUITS ARE RUN BETWEEN FIRE ALARM
CONTROL UNITS IN SEPARATE BUILDING, FIBER OPTIC CIRCUITS SHALL BE
FURNISHED/INSTALLEd.
2. WHERE CLASS X COPPER CIRCUITS ARE INSTALLED, PROVIDE ISOLATION
MODULES THAT WILL ENSURE THAT ONLY ONE BUILDING, E.G., THE FIRE
PUMP HOUSE, BUILDING B10 OR BUILDING 100 WILL BE LOST (E.G., WILL NOT
RESPOND) DURING ANY TYPE OF FAULT. IT IS REQUIRED THAT THE
INSTALLATION OF CLASS X CIRCUITS BE RUN IN SEPARATE CONDUITS FROM
EACH OTHER.
43. COORDINATE FIRE ALARM ZONES WITH THE SPRINKLER ZONES ON A PER FLOOR BASIS..
44. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH OTHER TRADES
TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK INSTALLED BY THIS
CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER WITHOUT
ADDITIONAL COMPENSATION TO THE CONTRACTOR.
45. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR PROVIDING DESIGN SHOP DRAWINGS,
CALCULATIONS, ETC., INCLUDING BUT NOT LIMITED TO ALL ITEMS WHICH APPLY AS
OUTLINED IN NFPA 72 SECTIONS 7.2, 7.4 AND 7.5, TITLED, "MINIMUM REQUIRED
DOCUMENTATION", "SHOP DRAWINGS (INSTALLATION DOCUMENTATION)," AND
"COMPLETION DOCUMENTATION".
46. ALL FIRE ALARM POWER CIRCUITS SHALL BE FED TO/FROM A LIFE SAFETY PANEL MEETING
THE REQUIREMENTS OF NFPA 70 SECTION 517.45(B) AND SECTION 517.32(C) WHERE A
DEDICATED LIFE SAFETY BRANCH CIRCUIT SHALL SUPPLY POWER FOR FIRE ALARM
PANELS, EXTENDER PANELS, ETC. FIRE ALARM SYSTEM SHALL NOT BE FED FROM A
NORMAL POWER PANEL.
47. THE FIRE ALARM CIRCUIT BREAKER IDENTIFICATION AND ACCESSIBILITY SHALL MEET THE
REQUIREMENTS OF NFPA 72, SECTION 10.6.5.2 AND FIRE ALARM CIRCUIT BREAKER LOCK
REQUIREMENTS STATED IN SECTION 10.6.5.4 & 10.6.5.5.
48. ALL ALARM, SUPERVISORY, AND DETECTION SYSTEMS SHALL BE CONNECTED TO THE
EXISTING BUILDING B10 PROTECTED PREMISE FIRE ALARM CONTROL PANEL AND
INTERFACED WITH THE MAIN FIRE ALARM CONTROL PANEL LOCATED IN BUILDING 100,
EMERGENCY COMMUNICATION CENTER. ALL INTERFACES BETWEEN BUILDING B10 AND
BUILDING 100 ARE EXISTING.
49. 12 MULTIMODE FOR FIRE ALARM SYSTEM COMMUNICATIONS, TYPE OM1 ONLY.
50. DISRUPTIONS TO FIRE ALARM AND SPRINKLER SYSTEMS SHALL BE KEPT TO A MINIMUM OR
AVOIDED. DELINEATE PHASING OF CONSTRUCTION TO ENSURE THAT INSTALLATIONS OF
NEW SYSTEMS ARE EXPEDITED, AND EXISTING SYSTEMS ARE KEPT IN SERVICE UNTIL THE
REPLACEMENT SYSTEM IS OPERATIONAL. IF FIRE PROTECTION SYSTEMS ARE TO BE
DISRUPTED, PROCEDURES SHALL BE INCORPORATED INTO THE DESIGN TO MAINTAIN
EQUIVALENT LEVELS OF FIRE PROTECTION AND PROVIDE FORMAL NOTIFICATION TO THE
FACILITY WHILE SYSTEMS ARE DOWN. FOR EXAMPLE, THE PROVISION OF A 24 HOUR FIRE
WATCH BY QUALIFIED INDIVIDUALS PROVIDED BY THE CONTRACTOR MAY PROVIDE AN
EQUIVALENT LEVEL OF FIRE PROTECTION DURING SYSTEM DISRUPTION IN SOME
CIRCUMSTANCES.
51. ACTIVATE FIRE PROTECTION AS IT IS INSTALLED .
52. FIRE ALARM SYSTEM INSTALLATION SHOULD BE COORDINATED AND PLACED IN SERVICE
PRIOR TO FINAL INSPECTION.
53. MEANS OF NOTIFICATION REQUIRED THROUGHOUT CONSTRUCTION AREAS (NFPA 241
REQUIREMENT)
54. TEMPORARY SYSTEM MAY BE DESIRED IF NEW SYSTEM CANNOT BE INSTALLED AS
CONSTRUCTION PROGRESSES ONCE INSTALLED, SYSTEM SHOULD BE ON EVEN IF PENDING
ACCEPTANCE.
55. EXISTING FA SYSTEM SHOULD ALWAYS STAY ONLINE FOR DURATION OF PROJECT UNLESS:
1. TEMP FA SYSTEM INSTALLED
2. FIRE WATCH IMPLEMENTED THIS ALLOWS BUILDING TO BE PROTECTED WHILE NEW
SYSTEM, DEVICES, WIRING, CONDUIT AND ALARM PANEL, ETC., IS INSTALLED.
56. FIRE ALARM LIFE SAFETY SYSTEM TO BE FURNISHED/INSTALLED BY THIS CONTRACTOR
SHALL BE MAINTAINED AS SOON AS REASONABLY PRACTICAL. COORDINATION WITH VA
FIRE MARSHAL IS REQUIRED.
FIRE ALARM GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ACQUISITION
DRAWINGS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Jerome K. Simons, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Name Address City, State Zip Phone number Contact
W.J.B. Dorn VA Medical Center B10
Permanent Diesel Fire Pump
Acquisition Package
B
IM
/B
O w n e r
R e q u e s te d C h a n g e s /4
C E
C e n tr a l M o d e l.
rv t
/3 /2
:0
:4
P M
FA-001
FIRE DETECTION - LEGEND,
NOTES, AND DWG. INDEX
COLUMBIA, SC
544-22-130
BUILDING 10
05/03/22 JRC
BID SET
GAT
FIRE DETECTION - DRAWING INDEX
SHEET
NUMBER SHEET NAME
FA-001 FIRE DETECTION - LEGEND, NOTES, AND DWG. INDEX
FA-002 FIRE DETECTION - FIRE DETECTION DETAILS
FA-003 FIRE DETECTION - FIRESTOP DETAILS
FA-004 FIRE DETECTION - RISER DIAGRAMS AND I/O MATRIX
FA-200 FIRE DETECTION - BASEMENT SPACE RENOVATION PLAN
FA-201 FIRE DETECTION - FIRST FLOOR / FIRE PUMP
FA-202 FIRE DETECTION - FIRE PUMP LOCATION EXISTING CONDITIONS
FA-203 FIRE DETECTION - FIRST, SECOND AND THIRD FLOOR PART PLANS
Rev. No. Revisions: Date:
NTS
TO
NEXT
DEVICE
FROM
FCP
OR
PREVIOUS
DEVICE
DATA
OUT(+)
DATA
OUT(-)
DAT
A
IN(+)
DAT
A
IN(-)
34 2 1
ALARM/
ACTIVE
NORMAL
RED
LED
GRN
LED
SIGA-CT1
TB2
TB1
TYP.N.O.
INITIATING
DEVICE
EOL
47K
OHM
NTS
ALARM
HORN
JUNCTION
BOX
MOUNTING
PLATE
XENON
STROBE
ALARM LAMP
SINGLE INPUT MODULE 2
FIRE ALARM HORN/STROBE LIGHT
MOUNTING DETAIL 3
STANDARD C-CLAMP PIPE HANGER 5
NTS
DESIGN DATA FOR C-CLAMP HANGER
A
C R
1-1/8" or Bar Joist
6. Steel Beam
Ring
5. Adjustable Hanger
4. Hanger Rod
3. Lock Nut
2. Set Screw
1. C-Clamp
Components:
1/2-69 1/48
1/2-4 1/27 3/46
1/2-3 3/46 3/45
3/8-364
3/8-2 1/25 1/23
3/8-2 1/452 1/2
3/8-1 3/44 1/42
3/8-1 1/241 1/2
3/8-1 1/23 3/41 1/4
3/8-1 1/43 1/21
3/8-1 1/43 1/23/4
3/8-1 1/43 1/21/2
Diameter
Rod
Takeout
Hanger
A Dimension
Minimum
Size
Pipe
Nominal inchesinchesinches
NTS
MOUNTING
BASE
ASSY.
ADAPTER
STRAP
(PART OF BASE ASSY.)
4"X 4"X 2-1/8"
JUNCTION
BOX
NTS
6" MIN
80" MIN
AND
96" MAX
FINISHED FLOOR
CEILING
MANUAL FIRE
ALARM
STATION
5'-0" MAX
TYPICAL EXIT DOORWAY
48" MAX
42" MAX
4" MIN
12" MAX
20" MAX
WALL MOUNTED
HEAT
DETECTOR
WALL MOUNTED
SMOKE DETECTOR
TYPICAL SMOKE DETECTOR MOUNTING DETAIL 4
1MOUNTING HEIGHTS OF DEVICES
GENERAL DETAIL NOTES:
A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF
DEVICES. WHEREVER DEVICES, ON THIS SHEET OR OTHER SHEETS,
ARE SHOWN AT GIVEN LOCATION WITH DIFFERENT MOUNTING HEIGHTS
THEY SHALL BE ALIGNED VERTICALLY (TO THE CENTER LINE). IF THEY
ARE SHOWN AT THE SAME MOUNTING HEIGHT THEY SHALL BE ALIGNED
HORIZONTALLY (TO THE TOP OF COVERPLATE). REFER TO THE
ARCHITECTURAL PLANS, ELEVATIONS AND DETAILS. COORDINATE
WITH ARCHITECT PRIOR TO ROUGH-IN.
B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS
INDICATED OTHERWISE.
C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN,
COORDINATE WITH ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS.
IF A CONFLICT OCCURS, REQUEST CLARIFICATION FROM ARCHITECT/
ENGINEER PRIOR TO ROUGH-IN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ACQUISITION
DRAWINGS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Jerome K. Simons, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Name Address City, State Zip Phone number Contact
W.J.B. Dorn VA Medical Center B10
Permanent Diesel Fire Pump
Acquisition Package
B
IM
/B
O w n e r
R e q u e s te d C h a n g e s /4
C E
C e n tr a l M o d e l.
rv t
/3 /2
:0
:3
P M
FA-002
FIRE DETECTION - FIRE
DETECTION DETAILS
COLUMBIA, SC
544-22-130
BUILDING 10
05/03/22 JRC
BID SET
GATRev. No. Revisions: Date:
FIRE ALARM UL NOTES
1. REFER TO SECTION 078416 OF THE SPECIFICATIONS. FOR QUALITY CONTROL REQUIREMENTS, REFER
TO THE QUALITY CONTROL PORTION OF THE SPECIFICATION NOTED ABOVE.
2. DETAILS SHOWN ARE TYPICAL DETAILS, IF FIELD CONDITIONS DO NOT MATCH THE REQUIREMENTS OF THE TYPICAL DETAILS, APPROVED ALTERNATE DETAIL SHALL BE UTILIZED. FIELD CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR COMPLIANCE WITH THE DETAIL(S), INCLUDING BUT NOT
LIMITED TO THE FOLLOWING:
A. MINIMUM AND MAXIMUM WIDTH OF JOINTS.
B. TYPE AND THICKNESS OF FIRE-RATED CONSTRUCTION. THE MINIMUM ASSEMBLY RATING OF
THE FIRE STOP ASSEMBLY SHALL MEET OR EXCEED THE HIGHEST RATING OF ADJACENT
CONSTRUCTION.
3. IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS ARE NOT AVAILABLE, MANUFACTURER'S
ENGINEERED JUDGEMENT DRAWINGS ARE ACCEPTABLE. DRAWINGS SHALL FOLLOW THE
INTERNATIONAL FIRESTOP COUNCIL (IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEM
ENGINEERED JUDGEMENT AND THE ENGINEERED JUDGEMENT MUST BE SUBMITTED TO THE VA COR
AND ENGINEER FOR REVIEW AND COMMENT PRIOR TO ITS USE.
4. REFERENCES:
A. 2013 UNDERWRITER'S LABORATORIES FIRE RESISTANCE DIRECTORY, VOLUME 2
B. NFPA 101, LIFE SAFETY CODE, 2021 EDITION
C. ALL GOVERNING LOCAL AND VA FIRE PROTECTION DESIGN MANUAL
5. FIRESTOP SYSTEM MUST MEET THE REQUIREMENTS OF ASTM E-814 (UL 1479) TESTED ASSEMBLIES
THAT PROVIDE A FIRE RATING EQUAL TO THAT OF THE CONSTRUCTION BEING PENETRATED.
6. ALL RATED THROUGH-PENETRATION SHALL BE PROMINENTLY LABELED WITH THE FOLLOWING
INFORMATION.
A. ATTENTION: FIRE RATED ASSEMBLY
B. UL SYSTEM #
C. PRODUCT(S) USED
D. HOURLY RATING (F-RATING)
E. INSTALLATION DATE
NOT TO SCALE
THROUGH PENETRATION FIRESTOP SYSTEM
(PROVIDE UL LISTED SYSTEM)
A
A
Section A-A
1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR PARTITION
TYPE & RATING ENCOUNTERED.
2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE & MATERIAL OF
THROUGH PENETRATION UTILIZED.
3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL ASSEMBLY &
THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR CAVITY ACCORDING TO
THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM UTILIZED.
ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED FIRE
STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION PENETRATED AND THE
THROUGH PENETRATION MATERIAL.
DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT THE
PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED TO THE
BUILDING OWNER AT THE PROJECT COMPLETION.
PROVIDE WALL OR FLOOR LABLES INDICATING THE SYSTEM MANUFACTURER AND UL LISTED
ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM IS INSTALLED.
PIPE SLEEVE THROUGH WALL DETAIL
NTS
PIPE
NOTES:
1. FOR INTERIOR WALLS
AND BELOW GRADE
GROUND TO GROUND
WALLS
CUT OPENING IN
EXISTING MASONRY
WALL LARGER THAN
SLEEVE AND FORM &
FILL WITH
EXPANSIVE
TYPE GROUT
FIRE
RESISTANT
SILICONE FOAM
SEALER
ESCUTCHEON PLATE
ON ONE OR BOTH
SIDES WHERE PIPING
IS EXPOSED
PIPE SLEEVE
EXISTING POURED
CONCRETE OR
C.M.U. WALL.
ANCHOR
LUGS
(MIN. 3 REQ'D)
PIPE
INSULATION
(WHERE REQ'D)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ACQUISITION
DRAWINGS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Jerome K. Simons, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Name Address City, State Zip Phone number Contact
W.J.B. Dorn VA Medical Center B10
Permanent Diesel Fire Pump
Acquisition Package
B
IM
/B
O w n e r
R e q u e s te d C h a n g e s /4
C E
C e n tr a l M o d e l.
rv t
/3 /2
:0
:2
P M
FA-003
FIRE DETECTION - FIRESTOP
DETAILS
COLUMBIA, SC
544-22-130
BUILDING 10
05/03/22 JRC
FIRE DETECTION INPUT/OUTPUT MATRIX 2
NOTES:
1. DEVICES SHOWN ARE TYPICAL. REFER TO FIRE DETECTION SHEETS FOR DEVICE LOCATIONS AND QUANTITIES.
2. PROVIDE END OF LINE RESISTORS AS REQUIRED.
3. ANNUNCIATION SHALL BE THREE TEMPORAL BEEPS.
4. DUCT SMOKE DETECTORS AND DAMPERS SHALL BE PROVIDED AND WIRED TO FACP AND POWER BY ELECTRICAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL
INSTALL THEM.
5. FOR LARGER DUCTS, PROVIDE ADDITIONAL DUCT DETECTORS AS REQUIRED BY NFPA 72.
6. EQUIPMENT MUST BE COMPATIBLE WITH THE FIRE ALARM CONTROL PANEL SOFTWARE.
NTS
A U
D
IB
L E
A L A
R M
S A
C T
IV
A
T
IO
N
AREA SMOKE DETECTOR - FIRST FLOOR
AREA SMOKE DETECTOR - SECOND FLOOR
A
SYSTEM INPUTS
SYSTEM
OUTPUTS
D
IS
P L A
Y A
L A
R M
S
IG
N A
L
D
IS
P L A
Y S
U P
E R
V
IS
O R
Y S
IG
N
A L
D
IS
P L A
Y T
R O
U B
L E
S
IG
N A
L
T R
A N
S M
IT
S
U P
E R
V
IS
O R
Y S
IG
N
A L
T O
S U
P E
R V
IS
O
R Y
S T
A T
IO
N
T R
A N
S M
IT
T
R O
U B
L E
S
IG
N A
L
S U
P E
R V
IS
O
R Y
S T
A T
IO
N
T R
A N
S M
IT
A
L A
R M
S
IG
N A
L
P E
R V
IS
O
R Y
S T
A T
IO
N
C L O
S E
D A
M P
E R
S O
N F
A N
S P
R O
X
IM
A
E
D E
T E
C T
O R
R E
C O
R D
S E
V E
N T
A T
F A
C P
S O
U N
D S
G E
N E
R A
L B
U
IL
D
IN
G A
L A
R M
S H
U T
D O
W N
A
IR
H A
N D
L E
R S
E R
V E
D B
Y
D
T E
C T
O R
AREA SMOKE DETECTOR - THIRD FLOOR
DUCT SMOKE DETECTOR - FIRST FLOOR
DUCT SMOKE DETECTOR - ATTIC LEVEL
DOOR RELEASE SMOKE DETECTOR18
B C
DRY PIPE VALVE ROOM TEMPERATURE ALARM
FIRE SPRINKLER WATER FLOW/PRESSURE SWITCH
FIRE ALARM AC POWER FAILURE
FIRE ALARM LOW BATTERY
FIRE ALARM OPEN CIRCUIT
FIRE ALARM GROUND FAULT
MANUAL PULL BOXES - BASEMENT
MANUAL PULL BOXES - FIRST FLOOR
MANUAL PULL BOXES - SECOND FLOOR
MANUAL PULL BOXES - THIRD FLOOR
MANUAL PULL BOXES - ATTIC
WATER CONTROL VALVE TAMPER SWITCH6
7 HIGH/LOW PRESSURE DRY-PIPE SPRINKLER SYSTEM
IN
IT
IA
T
E E
L E
V A
T O
R S
H U
T T
R
IP
A N
IS
C O
N N
E C
T E
L E
V A
T O
R P
O W
E R
E L E
V A
T O
R R
E C
A L L
ELEVATOR LOBBY SMOKE DETECTORS
ELEVATOR INTERFACE CIRCUIT SUPERVISORY
A B C D E F G H I J K L M
FIRE ALARM SEQUENCE OF OPERATION
THE FIRE ALARM NOTIFICATION SYSTEM SHALL GO INTO ALARM UPON ACTIVATION OF A MANUAL PULL STATION, AREA SMOKE DETECTOR, OR FLOW SWITCH. THE ALARM SHALL BE DISPLAYED BY AUDIBLE AND VISUAL NOTIFICATION APPLIANCES. THE ELEVATOR(S) SHALL BE RECALLED UPON ACTIVATION THE EACH INDEPENDENT FLOOR ELEVATOR LOBBY SMOKE DETECTOR AND THE AIR HANDLING UNITS SHALL BE SHUT DOWN UPON ACTIVATION OF AIR HANDLER(S) DUCT SMOKE DETECTOR. THE FIRE ALARM SYSTEM SHALL DISPLAY A TROUBLE CONDITION UNDER LOSS OF POWER, OR IF A SMOKE DETECTOR IS REMOVED FROM THE BASE. THE FIRE ALARM SYSTEM SHALL DISPLAY A
SUPERVISORY CONDITION UPON ACTIVATION OF A TAMPER SWITCH OR DUCT SMOKE DETECTOR.
O P
E N
S L
O C
K E
D E
G R
E S
S D
O O
R S
F
L O
O R
O F
F
IR
E O
R
IG
IN
N
FIRE EXTINGUISHER MONITORING SYSTEM
D E F G H I J K L M N
7. ALL NOTIFICATIONS TO THE FIRE DEPARTMENT SHALL OCCUR BY THE EMERGENCY COMMUNICATION CENTER AT THE MAIN HOSPITAL, BUILDING 100; WHERE, THIS BUILDING'S FIRE ALARM CONTROL PANEL SHALL REPORT ALL ALARM INDICATION.
R E
C A
L L E
L E
V A
T O
R S
T O
P R
IM
A
R Y
C
A L L F
L O
O R
O
R E
C A
L L E
L E
V A
T O
R S
T O
A L T
E R
N A
C
A L L F
L O
O R
P
O P
ELEVATOR LOBBY SMOKE DETECTOR - 1ST FLR23
C L O
S E
A S
S O
C
IA
T E
S M
O K
E B
A R
R
IE
R D
O
T H
E F
L O
O R
Q
Q
FIRE PUMP RUNNING
FIRE PUMP FAILURE - PHASE REVERSAL
DOUBLE CHECK VALVE TAMPER SWITCH
27 FIRE PUMP HOUSE TEMPERATURE ALARM
28 POST INDICATOR VALVE TAMPER SWITCH
29 ELEVATOR LOBBY SMOKE DETECTOR - 1ST 2ND,
3RD AND ATTIC/ROOF LEVELS
HEAT TRACE LOSS OF CONTROL POWER
F
IR
E
A L R
M H
E A
T T
R A
C E
S U
P E
R V
IS
P
E R
V
IS
IO
N
R
R
HEAT TRACE LOSS OF CURRENT
HEAT TRACE LOW INDUCED VOLTAGE
HEAT TRACE HIGH/LOW TEMPERATURE INDICATION
HEAT TRACE SWITCH FAILURE
FIRE PUMP - FAILURE TO START
FIRE PUMP - CONTROLLER OFF OR IN MANUAL
POSITION
TS WF DD
CD CD CD
BUILDING B10
ADDRESSABLE
FIRE ALARM
CONTROL PANEL
EVAC DACT
EVAC
BATT
M M M M
M M M M
RI
P
CM CM CD CM
CD CD CD CM
P
EXISTING
FIRST
FLOOR
BASEMENT
CONDUCTORS PER MANUFACTURER'S
PUBLISHED RECOMMENDATIONS IN
3/4" C MINIMUM TYPICAL
NEW MAIN FIRE ALARM
CONTROL PANEL / VOICE
COMMUNICATOR PANEL TO
BE INTERFACED WITH
SPEAKER / STROBES, SMOKE
DETECTORS,
STROBES, ETC.
DIGITAL VOICE COMMAND
(DV) FOR FIRE / VOICE TO
BE LOCATED IN THE
VESTIBULE AREA OF
BUILDING, B10
TO BE LOCATED WITHIN
THE COMMUNICATION
ROOM WITH ROOM
DESIGNATION "T103."
VOIP
VOIP
POWER CONNECTOR
POWER CONNECTOR
BUILDING 100, ROOM LA104
EMERGENCY COMMAND
CENTER / TELEPHONE
OPERATOR STATION
UNDERGROUND CLASS X
CIRCUIT AND PATHWAY
NETWORK
BUILDING B10, FIRE ALARM NETWORK
FIRE DETECTION AND FIRE EXTINGUISHER MONITORING RISER DIAGRAM
1NTS
EXISTING
FIRST
FLOOR
EVM EVM EVM EVM EVM
ADDRESSABLE
FIRE EXTINGUISHER
MONITORING PANEL
POWER CONNECTOR
ADDRESSABLE
FACP
FURNISHED / INSTALLED BY THIS CONTRACTOR
INCLUDING ALL INTERFACES BETWEEN THE
BUILDING, B10 FIRE / DIGITAL VOICE PANEL AND
MAIN HOSPITAL, BUILDING 100 FIRE / DIGITAL
VOICE PANEL.
EXISTING NOTIFIER
FIRE / DIGITAL VOICE
PANEL MODEL NFS2-3030
PROGRAMMING / UPDATES FOR REMOTE MONITORING
OF BUILDING, B10 FIRE / DIGITAL VOICE PANEL BY THIS
CONTRACTOR AT THE MAIN HOSPITAL, BUILDING 100,
EMERGENCY COMMUNICATION SYSTEM, FIRE DIGITAL
VOICE ALARM PANEL
M M M M
CD CD CD CM
SECOND
FLOOR
M M M M
CD CD CD CM
THIRD
FLOOR
M M M M
CD CD CD CM
ATTIC
EXISTING
EVM EVM EVM
EVM EVM EVM
EVM EVM EVM
EVM EVM EVM EVM
SECOND
FLOOR
BASEMENT
THIRD
FLOOR
ATTIC
REFER TO TELECOMMUNICATION DRAWINGS
FOR ALL NETWORKING BETWEEN BUILDING 10
DACT AND BUILDING 100, EMERGENCY
COMMUNICATION CENTER'S FIRE ALARM
CONTROL PANEL/INTERFACE POINT
(ABOVEGROUND AND BELOWGROUND
INSTALLATIONS).
GAP
BATT
POWER CONNECTOR
GRAPHIC ANNUNCIATOR
PANEL TO BE LOCATED AT THE
FRONT VESTIBULE.
CLASS B CIRCUIT AND
PATHWAY, REFER TO NFPA 72.
CLASS B CIRCUIT AND PATHWAY, REFER TO NFPA 72
(TYPICAL).
CLASS B CIRCUIT AND
PATHWAY, REFER TO
NFPA 72.
CLASS X CIRCUIT AND PATHWAY,
REFER TO NFPA 72.
NOTE:
1. ALL INITIATING DEVICES (IDC), SIGNALING LINE CIRCUITS (SLC) AND NOTIFICATION APPLIANCE CIRCUITS SHALL BE A CLASS B
CIRCUIT AND PATHWAY CIRCUIT INTERFACE BETWEEN THE INDIVIDUAL DEVICES AND THE ADDRESSABLE FACP.
2. CLASS X CIRCUIT AND PATHWAY BETWEEN THE ADDRESSABLE FIRE EXTINGUISHER MONITORING PANEL AND THE ADDRESSABLE
FIRE ALARM SYSTEM PANEL WITHIN BUILDING 10.
3. CLASS X CIRCUIT AND PATHWAY CIRCUITS BETWEEN BUILDING 10 ADDRESSABLE FIRE ALARM CONTROL PANEL AND BUILDING 100, EMERGENCY COMMUNICATION CENTER'S FIRE ALARM CONTROL PANEL.
4. PATHWAY SURVIVABILITY BETWEEN THE GRAPHIC ANNUNCIATOR PANEL AND THE FIRE EXTINGUISHER MONITORING AND
INTERFACE WITH THE ADDRESSABLE FIRE ALARM CONTROL SYSTEM SHALL MEET THE REQUIREMENTS STATED IN DIVISION 28 SPECIFICATION AND NFPA 72, E.G., SPECIFICALLY MONITORING FOR INTEGRITY AND CIRCUIT PERFORMANCE.
FIRE PUMP FIRE
ALARM TERMIANL
CABINET
CLASS X CIRCUIT AND
PATHWAY, REFER TO NFPA 72.
CLASS X CIRCUIT AND
PATHWAY, REFER TO NFPA 72.
EVM NEW EXTERIOR
FIRE PUMP HOUSE
EXISTING
M
CD
M
CD
EXTERIOR
FIRE PUMP
NEW
HEAT TRACE DIGITAL ELECTRONIC
CONTROLLER (PROPOSED
LOCATION BASEMENT MECHANICAL
EQUIPMENT ROOM)
TS WF
NEW
M
EVM
FIRE ALARM GENERAL NOTES AND REQUIREMENTS:
A. THE FIRE EXTINGUISHER MONITORING SYSTEM SHALL HAVE THE CAPABILITY TO
MONITOR INDIVIDUAL HAND PORTABLE FIRE EXTINGUISHERS FOR PRESENCE, OFF
NORMAL PRESSURE, LOSS OF MONITORING SYSTEM INTERFACE POWER AND ANY
OBSTRUCTION THAT COULD POSSIBLY BLOCK ACCESS TO EACH INDIVIDUAL
PORTABLE EXTINGUISHER.
B. REFER TO TELECOMMUNICATION DRAWINGS Ts003, ts002 AND TS003 FOR ALL
INTERFACED BETWEEN THE FIRE ALARM CONTROL SYSTEM DIGITAL TRANSMITTER
(DACT) AT THE NEW BUILDING B10 FIRE ALARM CONTROL PANEL AND THE MAIN FIRE
ALARM CONTROL PANEL LOCATED IN BUILDING 100 EMERGENCY COMMUNICATION
CENTER. THE FIBER OPTICS INSTALLATIONS SHOWN ON THE TELECOMMUNICATION
DRAWINGS INCLUDE ABOVE GROUND AND BELOW GROUND NETWORK
INSTALLATIONS.
C. THE MAIN FIRE ALARM CONTROL PANEL LOCATED IN BUILDING 100 EMERGENCY
COMMUNICATION CENTER SERVES AT THE 24-HOUR MANNED LOCATION FOR
MONITORING OF THE VA CAMPUS. BUILDING 100 EMERGENCY COMMUNICATION
CENTER’S FIRE ALARM CONTROL PANEL SHALL NOT NOTIFY THE COLUMBIA, SOUTH
CAROLINA FIRE DEPARTMENT, AS INDICATED THIS IS THE VA COLUMBIA, EMERGENCY
COMMUNICATION CENTER’S RESPONSIBILITY. BUILDING B10, FIRE ALARM CONTROL
PANEL SHALL NOT UNDER ANY CIRCUMSTANCES SEND SIGNALS FROM THE BUILDING
B10 TO THE COLUMBIA, SOUTH CAROLINA FIRE DEPARTMENT.
D. THE MAIN FIRE ALARM CONTROL PANEL LOCATED AT BUILDING 100 SHALL RECEIVE
SPECIFIC INPUTS FROM BUILDING B10 FIRE ALARM CONTROL PANEL FOR ALARM,
TROUBLE AND SUPERVISORY INDICATION. THE INPUTS RECEIVED FROM THE
BUILDING B10FIRE ALARM CONTROL PANEL SHALL PROVIDE THE LOCATION, DEVICE,
FLOOR/ROOM AND AREA OF WHERE THE ALARM INDICATION HAS OCCURRED WITHIN
BUILDING B10.
E. THE REQUIRED FORMAT FOR ALARM, TROUBLE AND SUPERVISORY THAT ACTIVATES
AT BUILDING B10 LOCAL FIRE ALARM CONTROL PANEL SHALL BE TRANSMITTED TO
BUILDING 100, EMERGENCY COMMUNICATION CENTER’S MAIN FIRE ALARM CONTROL
PANEL. THE SIGNAL FORMAT AT BUILDING B10 FIRE ALARM CONTROL PANEL / MODEM
COMMUNICATOR SHALL BE COMPATIBLE WITH THE EXISTING FIRE ALARM CONTROL
PANEL LOCATED AT BUILDING 100, EMERGENCY COMMUNICATION CENTER’S FIRE
ALARM CONTROL PANEL IS A PROJECT SCOPE OF WORK REQUIREMENT. BOTH FIRE
ALARM CONTROL PANEL S SHALL BE ABLE TO TRANSMIT AND RECEIPT OF SIGNALS
BOTH WAYS, E.G., MULTIMODE COMMUNICATION AND BE 100% COMPATIBLE.
F. A SINGLE FAULT ON A PATHWAY CONNECTED TO THE ADDRESSABLE DEVICE SHALL
NOT CAUSE THE LOSS OF DEVICES IN MORE THAN ONE ZONE/FLOOR (NFPA 72,
PARAGRAPH 23.6.1.1). FOR PURPOSES ON THIS PROJECT, EACH FLOOR OF THE
BUILDING SHALL BE CONSIDERED A SEPARATE ZONE [NFPA 72, PARAGRAPH 23.6.1.1].
FIRE ALARM GENERAL NOTES AND REQUIREMENTS CONTINUED:
E. THE REQUIRED FORMAT FOR ALARM, TROUBLE AND SUPERVISORY THAT ACTIVATES AT BUILDING B10 LOCAL FIRE ALARM CONTROL PANEL SHALL BE TRANSMITTED TO BUILDING 100, EMERGENCY COMMUNICATION CENTER’S MAIN FIRE ALARM CONTROL PANEL. THE SIGNAL FORMAT AT BUILDING
B10 FIRE ALARM CONTROL PANEL / MODEM COMMUNICATOR SHALL BE COMPATIBLE WITH THE
EXISTING FIRE ALARM CONTROL PANEL LOCATED AT BUILDING 100, EMERGENCY COMMUNICATION CENTER’S FIRE ALARM CONTROL PANEL IS A PROJECT SCOPE OF WORK REQUIREMENT. BOTH FIRE ALARM CONTROL PANEL S SHALL BE ABLE TO TRANSMIT AND RECEIPT OF SIGNALS BOTH WAYS, E.G., MULTIMODE COMMUNICATION AND BE 100% COMPATIBLE.
F. A SINGLE FAULT ON A PATHWAY CONNECTED TO THE ADDRESSABLE DEVICE SHALL NOT CAUSE THE LOSS OF DEVICES IN MORE THAN ONE ZONE/FLOOR (NFPA 72, PARAGRAPH 23.6.1.1). FOR PURPOSES ON THIS PROJECT, EACH FLOOR OF THE BUILDING SHALL BE CONSIDERED A SEPARATE ZONE [NFPA
72, PARAGRAPH 23.6.1.1].
G. REFER TO DIVISION 28 SPECIFICATIONS AND FA-001 FOR CIRCUIT AND PATHWAY REQUIREMENTS
FOR THIS SCOPE OF WORK BETWEEN THE NEW REHABILITATION CENTER'S AND THE MAIN FIRE
ALARM CONTROL PANE AS WELL AS INITIATING DEVICE CIRCUITS (IDCS), SIGNALING LINE CIRCUITS (SLCS) AND NOTIFICATION APPLIANCE CIRCUITS (NACS) BETWEEN BUILDING B10 INDIVIDUAL FIRE
ALARM DEVICES AND THIS BUILDING'S ADDRESSABLE FIRE ALARM CONTROL PANEL (FACP).
H. REFER TO THE INPUT/OUTPUT MATRIX FOR ALL SIGNAL INPUTS TO BE RECEIVED AT BUILDING B10 NEW LOCAL FIRE ALARM CONTROL PANEL AND THE MAIN FIRE ALARM CONTROL PANEL AT BUILDING
100, EMERGENCY COMMUNICATION CENTER’S HAS DIRECT RESPONSIBILITY FOR THE 24-HOUR
MANNED LOCATION FOR ALARM MONITORING PURPOSES TO MEET NFPA 72 REQUIREMENTS.
ELEVATOR MANUFACTURER WRITTEN ELEVATOR SMOKE DETECTION REQUIREMENTS:
A. FOR EACH ELEVATOR PROVIDE A NORMALLY CLOSED CONTRACT REPRESENTING THE SMOKE
DETECTOR AT THE DESIGNATED RETURN LANDING.
B. REQUIREMENTS FOR INTERMITTENTLY ILLUMINATING FIRE HAT VISUAL SIGNAL IN THE CAR
OPERATING WITH EITHER (B) OR (C) BELOW:
C. FOR A SINGLE UNIT OR FOR A GROUP OF ELEVATORS HAVING ONE COMMON MACHINE
ROOM/MACHINE SPACE AND ONE COMMON HOISTWAY, PROVIDE ONE ADDITIONAL NORMALLY
CLOSED CONTACT REPRESENTING THE MACHINE ROOM/MACHINE SPACE AND HOISTWAY SMOKE
DETECTORS.
D. IF THE GROUP CONTAINS MORE THAN ONE HOISTWAY AND HOISTWAY SMOKE DETECTORS ARE
INSTALLED, PROVIDE ONE NORMALLY CLOSE CONTACT FOR EACH ELEVATOR. THE CONTACT IS TO
REPRESENT THE SMOKE DETECTOR IN THE MACHINE SPACE FOR THAT PARTICULAR ELEVATOR,
AND ANY SMOKE DETECTOR IN THE HOISTWAY CONTAINING THAT PARTICULAR ELEVATOR.
E. FIRE SUPPRESSION (E.G., SPRINKLER PROTECTION) SHALL BE FURNISHED/INSTALLED IN THE
HOISTWAY AND ELEVATOR MACHINE ROOM / MACHINE SPACE(S) AN AUTOMATIC MEANS TO
DISCONNECT THE MAINLINE POWER SUPPLY TO THE AFFECTED ELEVATOR AND ANY OTHER POWER
SUPPLIES USED TO MOVE THE ELEVATOR, UPON OR PRIOR TO THE APPLICATION OF WATER IS
REQUIRED. SMOKE DETECTORS SHALL NOT BE USED TO ACTIVATE FIRE SUPPRESSION (E.G.,
SPRINKLER PROTECTION) IN THE HOISTWAYS OR MACHINE ROOMS / MACHINE SPACE OR TO
DISCONNECT THE MAIN POWER LINE.
DEFINITIONS:
A. ACTIVE COMMUNICATION: REFERS TO A METHOD OF SIGNAL TRANSMISSION TO A 24-
HOUR MANNED EMERGENCY COMMUNICATION CENTER IN WHICH COMMUNICATION
BETWEEN THE PROTECTED PREMISE FIRE ALARM COMMUNICATOR AND THE STATION
RECEIVER IS CONTINUOUSLY SUPERVISED. LOSS OF COMMUNICATION WILL RESULT IN
A TROUBLE CONDITION AT BOTH THE COMMUNICATOR AND THE RECEIVER AND WILL
TRIGGER A PREDETERMINED RESPONSE BY PERSONNEL AT THE 24-HOUR MANNED
MONITORING STATION.
B. ALARM VERIFICATION: A METHOD BY WHICH AS ALARM (OR SUPERVISORY) EVENT
MUST UNDERGO ANOTHER PROCESS IN ORDER TO CONFIRM AN ACTUAL CONDITION
EXISTS WHICH REQUIRES THE ACTIVATION OF AN OUTPUT DEVICE. THIS MAY INCLUDE
THE REQUIREMENT FOR ANOTHER INDEPENDENT DEVICE MONITORING THE SAME
PROTECTED AREA TO ENTER AN ALARM STATE. IT MAY ALSO INVOLVE PROGRAMMING
SOFTWARE OR FIRMWARE THAT REQUIRES ONE EVENT TRIGGER TO FOLLOW
ANOTHER WITHIN A SPECIFIED AND USUALLY PROGRAMMABLE TIMEFRAME.
C. DIGITAL ALARM COMMUNICATOR TRANSMITTER (DACT): A SYSTEM COMPONENT AT
THE PROTECTED PREMISE FIRE ALARM CONTROL PANEL (E.G., NEW REHABILITATION
BUILDING) TO WHICH INITIATING DEVICES, SIGNALING LINE CIRCUIT AND NOTIFICATION
APPLIANCE CIRCUITS ARE CONNECTED. THE DACT SEIZES THE CONNECTED
TELEPHONE LINE OR OTHER TRANSMISSION MEDIA, DIALS A PRESELECTED NUMBER
TO CONNECT TO A DACR, AND TRANSMIT SIGNALS INDICATING A STATUS CHANGE OF
THE LOCAL FIRE ALARM DEVICE.
D. DIGITAL ALARM COMMUNICATOR RECEIVER (DACR): A SYSTEM COMPONENT THAT
ACCEPTS AND DISPLAYS SIGNAL FROM THE DIGITAL ALARM COMMUNICATOR
TRANSMITTER (DACT) LOCATED AT A PROTECTED PREMISE THROUGH THE PUBLIC-
SWITCH TELEPHONE NETWORK OR A DIGITAL ALARM COMMUNICATOR RECEIVER
(DACR).
E. DIGITAL COMMUNICATOR: THIS IS AN OUTPUT DEVICE UTILIZE BY THE FIRE ALARM
SYSTEM TO COMMUNICATE ALARM, TROUBLE OR SUPERVISORY SIGNAL TO A 24-HOUR
MANNED EMERGENCY COMMUNICATION CENTER. IT USED THE PREMISE NORMAL
TELEPHONE LINE OR OTHER COMMUNICATION MEDIA TO TRANSMIT THE SIGNAL AT
THE NEW REHABILITATION BUILDING FOR ACTION BY THE MAIN HOSPITAL'S
EMERGENCY COMMUNICATION CENTER.
F. ABBREVIATION EVM MEANS FIRE EXTINGUISHER STATION MODULE.
G. CLASS B CIRCUIT AND PATHWAY: REFER TO NFPA 72, SECTION 12.3 FOR DEFINITION
AND REQUIREMENT OF PATHWAY DESIGNATION.
H. CLASS X CIRCUIT AND PATHWAY: REFER TO NFPA 72, SECTION 12.3 FOR DEFINITION
AND REQUIREMENTS OF THE PATHWAY DESIGNATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ACQUISITION
DRAWINGS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Jerome K. Simons, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Name Address City, State Zip Phone number Contact
W.J.B. Dorn VA Medical Center B10
Permanent Diesel Fire Pump
Acquisition Package
B
IM
/B
O w n e r
R e q u e s te d C h a n g e s /4
C E
C e n tr a l M o d e l.
rv t
/3 /2
:0
:0
P M
FA-004
FIRE DETECTION - RISER
DIAGRAMS AND I/O MATRIX
COLUMBIA, SC
544-22-130
BUILDING 10
05/03/22 JRC
CG CG
CGCG
CG CG
CG
CG
CG CG
CG CG
CG
CG
CG
CG
CG
CG CG CG
CG
CG
CG
CG CG
CG
CG
CG CG CG
CG
CG
CG
CG CG CG
CG
CG
CG
CG
CG
CG CG
CG
CG
CG
CG
CG
CG
CG CG
CG
CG
CG
CG CG CG
CG
CG
CG
CG
CG
CG
CGCG
CG
CG CG
CG
CG
CG
CG CG
CG CG
CG
CG
CG
CG
CGCG
CG
CGCG
CG
CG CG CG
CG
CGCG
CG
CG CG
CG
CG
CG
CG
CG
CG
CG
CG
CG CG
CG
CG
CG
CG
CG
CG
CG CG
CG
CG
CG
TS
MM
TS
TS
TS
TS
WF
TS TS
F A
C P
TS
TS
2 HOUR FIRE RESISTIVE CONSTRUCTION & SMOKE BARRIER
2 HOUR FIRE RESISTIVE CONSTRUCTION
1 HOUR FIRE RESISTIVE CONSTRUCTION & SMOKE BARRIER
1 HOUR FIRE RESISTIVE CONSTRUCTION
SMOKE TIGHT PARTITION (BUT NOT SMOKE RATED.)
WALL RATING LEGEND:
FIRE EXTINGUISHER SCHEDULE
FIRE EXTINGUISHER, 20 LB (40B:C) CARBON DIOXIDE FOR
FIRE PUMP ROOMFE3
CONTRACTOR SHALL PROVIDE FIRE ALARM TERMINAL CABINET
THAT SHALL INTERFACE ALL TAMPER/WATER FLOW SWITCHES,
FIRE PUMP MONITORING DEVICES AND THE FIRE EXTINGUISHER
MONITORING SYSTEM. THIS FIRE ALARM TERMINAL CABINET
SHALL BE NETWORKED WITH THE LOCAL FIRE ALARM CONTROL
PANEL LOCATED ON THE FIRST FLOOR OF BUILDING B10. THIS
SCOPE OF WORK SHALL INCLUDE ALL EQUIPMENT AND
PROGRAMING AT THE LOCAL FIRE ALARM CONTROL PANEL WITHIN
THE FIRE PUMP HOUSE, LOCAL FIRE ALARM CONTROL PANEL AT
BUILDING B10 AND THE MAIN FIRE ALARM CONTROL PANEL
LOCATED WITHIN BUILDING 100, EMERGENCY COMMUNICATION
CENTER. THE DESIGN BASIS FOR THE FIRE ALARM TERMINAL
CABINET WOULD BE EQUAL TO ACER BOX IF SERIES FIRE ALARM
TERMINAL CABINET, PART NUMBER SSU00660, 32 TERMINATION
POINTS, SIZE 14" X 14" X 3-1/4" WITH KEY LOCK.
FIRE EXTINGUISHER MONITORING SYSTEM WIRING/CABLING;
ROUTE CABLING FROM THE FIRE PUMP HOUSE TO ADDRESSABLE
FIRE EXTINGUISHER MONITORING PANEL LOCATED ON THE FIRST
FLOOR OF BUILDING B10.
FIRE DETECTION SHALL NOT BE REQUIRED IN HOISTWAYS OF
TRACTION ELEVATORS COMPLYING WITH THE REQUIREMENTS OF
NFPA 13, SECTION 9.3.6.3 AND THE REQUIREMENTS OF NFPA 72,
SECTION 21.4
EXTERIOR SPEAKER-STROBE TO BE WEATHER PROOF MEETING
NEMA 4 X REQUIREMENTS.
TEMPORARY FIRE PUMP LOCATION; FINAL LOCATION TO BE
COORDINATED WITH THE VA COR.
FIRE ALARM CONTROL PANEL
KEYED NOTES
GENERAL NOTES
A. REFER TO DRAWING FA-001 FOR FIRE ALARM GENERAL NOTES,
ABBREVIATIONS AND SYMBOLS.
B. REFER TO DRAWING FA-001 FOR TEMPORARY FIRE ALARM, FIRE
EXTINGUISHER AND FIRE SUPPRESSION REQUIREMENTS DURING AN
IMPAIRMENT TO EXISTING SYSTEM INSTALLED UNDER A PRIOR
PROJECT PHASE.
C. REFER TO FA-004 FOR FIRE ALARM INPUT / OUTPUT MATRIX. ALL NEW
TAMPER SWITCHES SHALL BE INTERFACED WITH THE FIRE ALARM
SYSTEM AT BOTH BUILDING B10, LOCAL FIRE ALARM CONTROL PANEL
AND BUILDING 100, EMERGENCY COMMUNICATION CENTER'S MAIN
FIRE ALARM CONTROL PANEL.
D. REFER TO DRAWING FX-004 FOR IMPAIRMENT AND TEMPORARY FIRE
ALARM/DETECTION AND FIRE SUPPRESSION REQUIREMENTS.
THE INFORMATION GIVEN HEREIN IS AS EXACT AS COULD BE
SECURED FOR BIDDING PURPOSES AND ITS ACCURACY IS NOT
GUARANTEED. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR
EXAMINING NEW JOB CONDITIONS AND VERIFYING ALL
MEASUREMENTS, DISTANCES, ELEVATIONS, CLEARANCES, PIPE
SIZES, ETC., BEFORE STARTING THE DEMOLITION OR NEW WORK.
E. THE DRAWING SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES. THE SCALE WHEN INDICATED FOR GENERAL REFERENCE
ONLY.
F. ALL VALVES CONTROLLING FIRE PROTECTION EQUIPMENT AND FIRE
PROTECTION MAINS SHALL BE PROVIDED WITH A
TAMPER/SUPERVISORY SWITCHES WIRED TO THE FIRE ALARM
CONTROL PANEL.
G. EXACT LOCATIONS AND QUANTITIES OF WATERFLOW AND TAMPER
SWITCHES SHALL BE VERIFIED BY THE CONTRACTOR. ALL FIRE
SPRINKLER SYSTEM SHALL HAVE THESE DEVICES, CONTRACTOR
PRICING SHALL INCLUDE CONNECTION OF THESE DEVICES WHETHER
SHOWN OR LOCATED ON THE DESIGN DOCUMENT DRAWINGS.
H. FIRE DETECTION CONTRACTOR SHALL PROVIDE COVERAGE ABOVE
AND BELOW ALL OBSTRUCTIONS COMPLYING WITH NFPA 72.
I. FIRE ALARM SYSTEM WIRING/CABLING WITHIN THE FIRE PUMP HOUSE
AND TO/FROM TO/FROM THE EXTERIOR FIRE PUMP HOUSE TO
BUILDING B10, LOCAL FIRE ALARM CONTROL PANEL IS A NOTIFIER
FIRE ALARM SYSTEM. THEREFORE, THE NEW LOCAL FIRE ALARM
CONTROL PANEL WITHIN THE FIRE PUMP HOUSE SHALL BE NOTIFIER
FIRE ALARM PANEL AND HAVE THE CAPACITY TO INTERFACE, SEND
AND RECEIVE ALARMS, DIGITAL VOICE COMMUNICATION, ETC., FOR
THIS SCOPE OF WORK. REFER TO SPECIFICATION 28 05 13,
"CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY" AND SPECIFICATION 28 05 28.33, "CONDUITS AND
BACKBOXES FOR ELECTRONIC SAFETY AND SECURITY."
J. FINAL LOCATION OF THE LOCAL FIRE ALARM TERMINAL CABINET
WITHIN THE FIRE PUMP HOUSE SHALL BE LOCATED IN AN APPROVED
LOCATION AND ELEVATION BY THE FIRE PUMP / PUMP HOUSE
MANUFACTURER, LOCAL VA AND CITY OF COLUMBIA LOCAL
JURISDICTION HAVING AUTHORITY(E.G., VA FIRE MARSHAL AND/OR
LOCAL FIRE DEPARTMENT FIRE MARSHAL). REFER TO NFPA 101,
PARAGRAPH 9.6.6, TITLED "LOCATION OF CONTROL."
K. THIS CONTRACTOR SHALL COORDINATE WITH THE GENERAL
CONTRACTOR ON THE POURING OF THE CONCRETE PAD SINCE
EXISTING CONDITIONS AT THE SITE THERE ARE TWO UTILITY BOXES,
E.G., ONE ELECTRICAL BOX W/COVER AND ONE PLUMBING
CLEANOUT. THE CONSTRUCTION OF THE FIRE PUMP HOUSE, FIRE
PUMP ASSEMBLY AND ALL COMPONENTS MUST WITHIN THE FINAL
FIRE PUMP HOUSE/EQUIPMENT DESIGN PROVIDE ACCESSIBILITY TO
BOTH OF THE ABOVE UTILITY CONNECTION, NO EXCEPTIONS WILL BE
ACCEPTED. THIS IS A CONDITION OF PROCUREMENT WITH THE VA
DORN COR AND ENGINEER OF RECORD.
L. FURNISH/INSTALL HEAT TRACE SYSTEM FOR PROTECTION OF THE
UNDERGROUND AND ABOVEGROUND PIPING. REFER TO FX-201 FOR
PIPING CONFIGURATION. THE HEAT TRACING SYSTEM SHALL BE UL
LISTED AND SHALL PROTECT FIRE SUPPRESSION DISTRIBUTION LINES
AS SHOWN ON FX-201 WHERE THE HEAT TRACING SYSTEM SHALL BE
SPECIFICALLY LISTED FOR USE ON DISTRIBUTION LINES. ELECTRONIC
SUPERVISION WITH AN INTELLIGENT ELECTRONIC CONTROLLER
SHALL BE PROVIDED CAPABLE OF MONITORING THE FOLLOWING
CONDITIONS WITH INTERFACE TO THE FIRE ALARM SYSTEM:
a. LOSS OF SUPPLY VOLTAGE
b. GROUND FAULT
c. LOSS OF CONTROL POWER
d. INDUCED LOW VOLTAGE
e. TEMPERATURE
f. SWITCH FAILURE
2345 18 7 6910 011
G
F
D
H
A
B
C
12131415
E
B.4 B.1
C.4 C.4
12.8 12.512.412.212.1 11.1
SP
SP
(ON LOW
ROOF)
EVM
FE3
GENERATOR (E)
CHILLER (E)
FIRE ALARM SYMBOLS
FIRE SUPPRESSION TAMPER SWITCH TO SPRINKLER SYSTEM;
FIRE ALARM INTERFACE REQUIRED
TS
FIRE SUPPRESSION WATER FLOW SWITCH TO SPRINKLER SYSTEM;
FIRE ALARM INTERFACE REQUIRED
WF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ACQUISITION
DRAWINGS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Jerome K. Simons, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Name Address City, State Zip Phone number Contact
W.J.B. Dorn VA Medical Center B10
Permanent Diesel Fire Pump
Acquisition Package
B
IM
/B
O w n e r
R e q u e s te d C h a n g e s /4
C E
C e n tr a l M o d e l.
rv t
/3 /2
:0
:0
P M
FA-201
FIRE DETECTION - FIRST FLOOR /
FIRE PUMP
COLUMBIA, SC
544-22-130
BUILDING 10
05/03/22 JRC
BID SET
GAT
1/8" = 1'-0"
FIRST FLOOR PLAN - FIRE DETECTION PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ACQUISITION
DRAWINGS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Jerome K. Simons, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Name Address City, State Zip Phone number Contact
W.J.B. Dorn VA Medical Center B10
Permanent Diesel Fire Pump
Acquisition Package
B
IM
/B
O w n e r
R e q u e s te d C h a n g e s /4
C E
C e n tr a l M o d e l.
rv t
/3 /2
:1
:3
P M
FA-202
FIRE DETECTION - FIRE PUMP
LOCATION EXISTING CONDITIONS
COLUMBIA, SC
544-22-130
BUILDING 10
05/03/22 JRC
BID SET
GAT
PLUMBING CLEANOUT WHERE THE
FIRE PUMP HOUSE INTERNAL CONFIGURATION
MUST PROVIDE ACCESS TO THIS BOX WITHIN
THE FIRE PUMP HOUSE AND COORDINATE
ACCESSIBILITY WITHIN THE FIRE PUMP
HOUSE & EQUIPMENT.
ELECTRICAL BOX W/COVER WHERE WHERE THE
FIRE PUMP HOUSE INTERNAL CONFIGURATION
MUST PROVIDE ACCESS TO THIS BOX WITHIN
THE FIRE PUMP HOUSE AND COORDINATE
ACCESSIBILITY WITHIN THE FIRE PUMP
HOUSE & EQUIPMENT
Rev. No. Revisions: Date:
NOTE: THE FIRE PUMP PACKAGE FOOTPRINT IS FIXED AT 11' (WIDE) X 16'
(LONG), NO DEVIATIONS ALLOWED.
FIRE PROTECTION DESIGN CRITERIA
ORDINARY HAZARD GROUP 2 - FIRE PUMP HOUSE; NFPA 13,
SECTION 26.27.1.8
DESIGN DENSITY: 0.25GPM/SQ.FT
HYDRAULICALLY MOST DEMANDING AREA:OVER ENTIRE ROOM AREA
SPRINKLER ORIFICE: 3/4INCH
MAXIMUM COVERAGE/SPRINKLER HEAD: 130SQ.FT.
HOSE STREAM ALLOWANCE INSIDE/OUTSIDE: 250GPM
K FACTOR: 8.0GPM/(PSI)½
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
52.
53.
54.
THE NEW FIRE PUMP ASSEMBLY COMPLETE SHALL BE SIZED IN ACCORDANCE WITH THE VA FIRE PROTECTION MANUAL, AND SHALL BE HYDRAULICALLY CALCULATED TO MEET THE REQUIREMENTS OF NFPA 13 AND
APPROVED BY VA FIRE SAFETY OFFICIAL HAVING JURISDICTION, THE CONTRACTOR
SHALL BE RESPONSIBLE FOR OBTAINING THEIR FLOW TEST DATA FROM THE CITY OF COLUMBIA MEETING THE REQUIREMENTS OF NFPA 291 AND NFPA 13, SECTION 23.2.1 INCLUDING ANY FEES.
THE SYSTEM SHALL BE DESIGNED AND BUILT IN A WORKMANLIKE MANNER, IN ACCORDANCE WITH
DETAILED DRAWINGS TO BE SUBMITTED FOR APPROVAL. THE WORK SHALL INCLUDE ALL
COMPONENTS REQUIRED TO PROVIDE A COMPLETE SYSTEM.
THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE A SET OF SHOP DRAWINGS THAT INCLUDE ALL PIPE SIZES, ELEVATIONS, HEAD LOCATIONS, DIMENSIONS, VALVES, INSPECTOR TESTS, FLOW SWITCHES, TAMPER SWITCHES, ETC.
FIRE PROTECTION MAIN/BRANCH PIPING SHALL BE PROVIDED AND LOCATED IN ACCORDANCE WITH
NFPA 13 AND THE VA FIRE PROTECTION DESIGN MANUAL. IT IS THE CONTRACTOR’S
RESPONSIBILITY TO CONFIRM LOCATIONS FOR COMPLIANCE WITH THE CODE REQUIREMENTS.
THE FIRE PROTECTION CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AT THE PROJECT SITE.
FIRE SUPPRESSION PIPING SHOULD BE ROUTED AS HIGH AS POSSIBLE WHILE STILL COORDINATING WITH OTHER TRADES. ELEVATION OF SPRINKLER PIPING MUST BE DETERMINED BY PROPOSED SPACE IN THE
BASEMENT CRAWL SPACE AND BASEMENT MECHANICAL EQUIPMENT ROOM.
FIRE SUPPRESSION PIPING SHALL NOT BE INSTALLED IN ANY AREAS SUBJECT TO FREEZING
CONDITIONS WITHOUT PROPER FREEZE PROTECTION, THAT SHALL INCLUDE INSULATION, FREEZE
PROTECTION AND EXTERIOR METAL JACKET.
ALL MATERIAL AND ITS INSTALLATION SHALL BE IN COMPLETE COMPLIANCE WITH ALL APPLICABLE
SECTIONS OF THE LATEST EDITION OF NFPA FACTORY MUTUAL GUIDELINES AND VA FIRE
PROTECTION DESIGN MANUAL GUIDELINES.
THE FIRE PROTECTION CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT; AND, PERFORM ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF A COMPLETE FIRE PROTECTION SYSTEM THAT IS READY FOR USE WITHIN THE INTENT OF AND AS INDICATED ON THE DRAWINGS, SPECIFICATIONS AND AS HEREIN SPECIFIED.
SMALL ITEMS NOT SHOWN OR SPECIFIED, BUT OBVIOUSLY REQUIRED BY GOOD GENERAL PRACTICE TO
COMPLETE THE WORK SHALL BE FURNISHED AND INSTALLED THE SAME AS IF BOTH SHOWN AND
SPECIFIED.
BY SUBMITTING A PROPOSAL FOR THIS WORK, THE CONTRACTOR WILL BE HELD TO…