2021-07-06 VA 538-20-207 Improve Fleet Parking - Addendum 1.pdf
PDF 2 MB Posted
- Attached to
- Y1LZ--CONSTRUCTION | Improve Fleet Parking Area & Add Vehicle Charging Stations; Project 538-20-207
- Solicitation number
- A001
About this file
This addendum addresses a federal construction project to improve a fleet parking area and add vehicle charging stations at a Department of Veterans Affairs medical center. Key details include:
- The addendum provides revised drawings showing an updated location for a concrete pad and bollards for a new 15kV switch, transformer and panelboard, as well as other electrical revisions. It also addresses pre-bid questions received and provides bid opening instructions and a site visit roster. The construction project, number 538-20-207, will improve an existing fleet parking area and add dual-port Level 2 electric vehicle charging stations with related electrical infrastructure upgrades at the Chillicothe, Ohio VA medical center.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Site Visit Rosters 21JUN2021.pdf | ||
| 538-20-207 Bid Opening Instructions.docx | DOCX document | |
| S02. 36C25021B0021 0001.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL ELECTRICAL PLUMBING FIRE PROTECTION
COLUMBUS | INDIANAPOLIS | VIRGINIA BEACH
1405 DUBLIN ROAD, COLUMBUS, OH 43215 ∙ PHONE: (614) 486-4778 ∙ FAX: (614) 486-4082 ∙ WWW.AECMEP.COM
ADDENDUM NO.1
7/6/2021
Subject: VA 538-20-207 Improve Fleet Parking Area and Add Vehicle Charging Stations Chillicothe, OH
This Addendum No. 1 supplements and amends the original Contract Documents issued pursuant to Solicitation No.
36C25021B0021 and shall become part thereof.
SPECIFICATIONS
1. No changes.
DRAWINGS
1. C-102 – Revised location of concrete pad and bollards for new 15kV switch, transformer and panelboard.
Added coded note 4 for concrete expansion joint.
2. ES101 - Revised location of new 15kV switch, transformer and Panel EVP1. Revised coded note 12 and 17.
Added coded note 25. Added plan note about existing underground storm pipe crossing.
3. ES501 – Added concrete pad detail 10.
4. ES601 – Revise breaker of circuit EVP1-38 to 20/1 in lieu of 30/1 shown.
ATTACHMENTS
C-102, ES101, ES501, ES601
1"=20'-0"
10' 20' 40'
F1
SITE PLAN - ELECTRICAL
GENERAL SHEET NOTES:
A. ALL INSTALLATIONS SHALL COMPLY WITH ANY APPLICABLE LOCAL AND NATIONAL BUILDING CODES, AND THE NATIONAL ELECTRICAL CODE (NEC) 2017 EDITION.
B. COORDINATE ANY UTILITY OUTAGES WITH THE OWNER NO LESS THAN 7 CALENDAR DAYS PRIOR.
C. WHERE EXACT DIMENSIONS ARE NOT CALLED OUT, THE LOCATION OF EQUIPMENT, JUNCTION BOXES, OUTLETS, WIRE WAYS, PANELS ETC. ARE TO BE IDENTIFIED ON COORDINATION DRAWINGS FOR
REVIEW ACCORDING TO PROJECT GENERAL CONDITIONS.
D. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
INSTRUCTIONS.
E. ALL INSTALLATIONS SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. CONDUIT SHALL
BE DEBURRED, CAPPED, AND TAGGED.
F. CONTRACTOR IS RESPONSIBLE FOR ALL REMOVAL AND DISPOSAL OF DEBRIS FROM THE SITE
RESULTING FROM ELECTRICAL CONSTRUCTION ACTIVITIES.
G. UNLESS NOTED OTHERWISE, CIRCUIT WITH TYPE THWN COPPER CONDUCTORS IN CONDUIT.
LIQUID-TIGHT NON-METALLIC CONDUITS SHALL BE USED FOR FINAL CONNECTIONS TO ALL
EQUIPMENT. QUANTITIES AND SIZE AS NOTED.
H. UNLESS NOTED OTHERWISE, ALL CONDUCTORS SHALL BE COPPER TYPE.
I. UNLESS NOTED OTHERWISE, ALL EXTERIOR AND UNDERGROUND CONDUITS SHALL BE A MINIMUM OF
1" TRADE SIZE.
J. UPON COMPLETION OF WORK, ALL MATERIALS AND EQUIPMENT FURNISHED IN THIS CONTRACT
SHALL BE THOROUGHLY CLEANED OF DIRT, GREASE, RUST AND OILS. PREPARE FOR FINISH
PAINTING OR TOUCH-UP AS REQUIRED.
K. ALL OUTDOOR INSTALLATION SHALL BE WITH WEATHERPROOF RATED ENCLOSURES AND DEVICES
(E.G. NEMA 3R, IP65 RATED).
L. PROVIDE WEATHER-RESISTANT SELF-ADHESIVE PRINTED LABELS DESCRIBING BOXES. LABEL SHALL
BE PRINTING IN A TRUE-TYPE FONT AND SIZED FOR LEGIBILITY.
M. DRAWING REPRESENTS AN APPROXIMATION OF INITIAL CONDITIONS. ELECTRICAL CONTRACTOR
SHALL FIELD VERIFY EXTENT OF THE DEMOLITION WORK PRIOR TO BID.
N. UNLESS NOTED OTHERWISE, EXISTING DEVICES ARE TO REMAIN.
O. PROVIDE UPDATED AND TYPEWRITTEN DIRECTORY IN PANELBOARDS WHERE WORK HAS BEEN
PERFORMED.
P. UNLESS NOTED OTHERWISE, ALL EXTERIOR AND UNDERGROUND CONDUITS TO BE RIGID
GALVANIZED STEEL (EXCEPT FOR CONCRETE ENCASED CONDUITS).
SHEET KEYNOTES:
1. EXISTING 15KV SWITCH PMSC51 SHALL REMAIN. REFER TO ONE-LINE DIAGRAM.
2. PROVIDE PANELBOARD AT TRANSFORMER PAD. PANELBOARD SHALL BE INSTALLED IN A NEMA 3R
ENCLOSURE. REFER TO DETAIL 3/ES501, ONE-LINE DIAGRAM, PANELBOARD SCHEDULE AND
SPECIFICATIONS.
3. PROVIDE TRANSFORMER TO SERVE NEW PANELBOARD. REFER TO ONE-LINE DIAGRAM AND
SPECIFICATIONS.
4. PROVIDE CIRCUITING AND DUPLEX RECEPTACLE (WEATHER RESISTANT, GFCI) ON A LUMBER POST.
ROUTE CIRCUIT THROUGH PULLBOX IDENTIFIED BY CODED NOTE 10. REFER TO DETAIL 9/ES501.
5. EXISTING CAMERA TO REMAIN.
6. PROVIDE 15KV PAD MOUNTED PRIMARY INTERRUPTER SWITCH. REFER TO ONE-LINE DIAGRAM AND
DETAIL 8/ES501.
7. PROVIDE AREA LUMINAIRE (SINGLE OR DOUBLE HEAD AS SHOWN) ON 17' POLE. REFER TO
LUMINAIRE SCHEDULE AND DETAIL 4/ES501.
8. PROVIDE 11" x 18" x 18" UNDERGROUND PULLBOX (MINIMUM TIER 15) TO SERVE EV CHARGING
STATION.
9. APPROXIMATE LOCATION OF DUAL PORT LEVEL 2 EV CHARGING STATION AND CONCRETE PAD.
REFER TO DETAILS ON ES501. VERIFY EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.
10. PROVIDE 11" x 18" x 18" UNDERGROUND PULLBOX (MINIMUM TIER 15) TO SERVE DOWNSTREAM
CIRCUITS.
11. PROVIDE 17" X 30" X 18" UNDERGROUND PULLBOX (MINIMUM TIER 15) TO SERVE DOWNSTREAM
CIRCUITS.
12. PROVIDE A 15 KV FEEDER IN ONE 5" RIDGID GALVANIZED STEEL CONDUIT STUB FROM EXISTING
SWITCH TO 15KV INTERRUPTER SWITCH AND TRANSFORMER.
13. PROVIDE (1) 2" CONDUITS TO SERVE RECEPTACLES IDENTIFIED BY CODED NOTE 4.
14. PROVIDE 1" CONDUIT TO SERVE NEW LIGHT POLES. INTERCEPT EXISTING LIGHTING CIRCUIT FROM
BASE OF EXISTING POLE AND EXTEND TO NEW LIGHT POLES AND LUMINAIRES.
15. PROVIDE DISCONNECT SWITCH AND POWER CONNECTION TO MOTORIZED GATE OPERATOR.
PROVIDE A WEATHERPROOF KEY SWITCH ON UNSECURE SIDE OF FENCE FOR OPERATION OF GATE.
KEY SWITCH SHALL HAVE A LOCK CYLINDER AND KEYING THE SAME AS PANELBOARD ENCLOSURE
LOCK DESCRIBED IN DETAIL 3/ES501.
16. PROVIDE TWO 1" CONDUITS (ONE FOR POWER, ONE FOR SIGNAL) WITH PULL STRINGS, STUBBED UP
AND CAPPED IN PULLBOX FOR MOTORIZED GATE.
17. PROVIDE 1" UNDERGROUND CONDUIT TO SERVE SPACE HEATER CIRCUIT (EVP1-38) IN THE 15kV
SWITCH.
18. PROVIDE 17" x 30"x 18" UNDERGROUND PULLBOX (MINIMUM TIER 15) ADJACENT TO PANELBOARD
FOR PULLING CONDUCTORS.
19. PROVIDE (3) 2" CONDUITS TO SERVE EV CHARGING STATIONS, AND (1) 2" CONDUIT WITH
PULLSTRING FOR SPARE.
20. PROVIDE (2) 2" CONDUITS TO SERVE EV CHARGING STATIONS AND (1) 2" CONDUIT WITH PULLSTRING
FOR SPARE.
21. PROVIDE (1) 2" CONDUIT TO SERVE EV CHARGING STATION AND (1) 2" CONDUIT WITH PULLSTRING
FOR SPARE.
22. PROVIDE (4) 2" CONDUITS FOR RECEPTACLES CIRCUITS THROUGH PULLBOX IDENTIFIED BY CODED
NOTE 10. IF ALTERNATE 3 IS ACCEPTED, PROVIDE PULLSTRINGS IN CONDUIT IN LIEU OF
CONDUCTORS.
23. IF ALTERNATE 2 IS ACCEPTED, DELETE THIS WORK.
24. IF ALTERNATE 3 IS ACCEPTED, DELETE THIS WORK.
25. PROVIDE UNDERGROUND CONDUITS FOR FEEDER AND BRANCH CONDUITS TO SERVE
DOWNSTREAM EQUIPMENT/CIRCUITS AS SHOWN.
NORTH
PTZ
DD PTZ
PTZ
PTZ
F
5 5
PNL EVP1
P2
BUILDING 23BUILDING 21
BUILDING 259
BUILDING 52
GREENHOUSE
GREENHOUSE
GREENHOUSE
PMSC51
EVP1-1,3
EVP1-5,7
EVP1-17,19
EVP1-21,23
EVP1-9,11
EVP1-13,15
P2
P2
P2
P2
P2
P2
EVP1-33
4 24
M
30/30/3,3R
EVP1-40,42
EVP1-35
EVP1-29
EVP1-31
EVP1-37
4 24
EVP1-39
141424
APPROXIMATE LOCATION OF
UNDERGROUND STORM LINE.
CONTRACTOR SHALL HAND
TRENCH THIS AREA FOR
UNDERGROUND CONDUIT
INSTALLATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
IMPROVE FLEET PARKING AREA
AND ADD VEHICLE CHARGING
STATIONS
CHILLICOTHE, OHIO
538-20-207
P20 Chief Engineer
10/19/2020Revisions: Date:
genesis design llc
"EXPERIENCE SAVES"
Cincinnati, Ohio 45208-2564 (513) 616-9694 email genesisdesignllc@gmail.com Civil Engineering
A DVANCED
E NGINEERING
C ONSULTANTS
Mechanical | Electrical | Plumbing | Fire Protection
1405 Dublin Road Tel: (614) 486-4778
Columbus, Ohio 43215 Fax: (614) 486-4082
D a t e
A
M
F i l e
L o c a t i o n Z p r o j
I m p r o v e
F l e e t
P a r k i n g a n d
A d d
V e h i c l e
C h a r g i n g
S t a t i o n s C
A D
E
E l e c t r i c a l
L a s t
E d i t G a v i n L i m
ES101S. SMITHG. LIM
SITE PLAN - ELECTRICAL
RYAN JETER, PE, PS, CHFM
ADDENDUM 1
07/06/2021
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
IMPROVE FLEET PARKING AREA
AND ADD VEHICLE CHARGING
STATIONS
CHILLICOTHE, OHIO
538-20-207
P20 Chief Engineer
10/19/2020Revisions: Date:
genesis design llc
"EXPERIENCE SAVES"
Cincinnati, Ohio 45208-2564 (513) 616-9694 email genesisdesignllc@gmail.com Civil Engineering
A DVANCED
E NGINEERING
C ONSULTANTS
Mechanical | Electrical | Plumbing | Fire Protection
1405 Dublin Road Tel: (614) 486-4778
Columbus, Ohio 43215 Fax: (614) 486-4082
D a t e
A
M
F i l e
L o c a t i o n Z p r o j
I m p r o v e
F l e e t
P a r k i n g a n d
A d d
V e h i c l e
C h a r g i n g
S t a t i o n s C
A D
E
E l e c t r i c a s t
E d i t G a v i n L i m
ES501S. SMITHG. LIM
DETAILS - ELECTRICAL SITE
IN LAWN AREAS, SAVE TOP SOIL. PAVING,
STREETS, DRIVES, PARKING, CURBS,
FOOTINGS, GUTTERS, STEPS, SIDEWALKS
AND SIMILAR SURFACES TO MATCH
ORIGINAL CONDITION
M
I N
I M
U M
COMPACTED GRANULAR FILL TO PAVEMENT
OR SIDEWALK. OTHERWISE, SELECTED
BACKFILL TO GRADE
CONCRETE ENCASEMENT 4000PSI.
TROWEL RED COLORENDUM INTO
TOP OF CONCRETE
FINISHED GRADE
RED METAL BACKED
POLYETHYLENE TAPE
MARKED "ELECTRIC", ONE
TAPE PER THREE
HORIZONTAL CONDUITS
GRANULAR BACKFILL
SCHEDULE 40 PVC CONDUIT SIZE AND
QUANTITY OF CONDUITS VARIES WITH
LOCATION. TRANSITION FROM PVC TO
RIGID STEEL CONDUIT LAST 6 FEET TO
MANHOLES, HANDHOLES, BUILDINGS,
AND/ OR EQUIPMENT.
CONDUIT SUPPORT
BACKFILL NOTES:
UNDER LAWN AREAS, SIDEWALK, STEPS ETC:
CLEAN CLAY OR SAND WATER COMPACTED IN TWO OR MORE LAYERS.
UNDER ROADS, DRIVES, STREETS, PARKING, CURBS, GUTTERS ETC.:
CLEAN SAND WATER COMPACTED IN 6" LAYERS.
DETAIL - CONCRETE-ENCASED DUCT BANK
DETAIL - DIRECT BURIED CONDUIT
FINISHED GRADE
RED METAL BACKED POLYETHYLENE TAPE
MARKED "ELECTRIC", OR ONE TAPE PER
THREE HORIZONTAL CONDUITS
GRANULAR BACKFILL, USE LSM-50 UNDER
PAVEMENT AND WITH-IN 5'-0" OF PAVEMENT EDGE
RGS CONDUIT, SIZE AND QUANTITY OF CONDUITS VARIES WITH
LOCATION. REFER TO ELECTRICAL SITE PLAN.
CONDUIT SPACER
TRENCH WIDTH AS
REQUIRED
COMPACTED GRANULAR FILL TO
PAVEMENT OR SIDEWALK.
OTHERWISE, SELECTED BACKFILL
TO GRADE
NTS
NTS
3"
3"
3"
3"
2"
3"
SAND COVER
M
I N
I M
U M
3"
2"
3"
DETAIL - PANELBOARD EVP1 ENCLOSURE
NTS
2"
PROTECT NUTS AND
THREADS DURING
CONCRETE POUR
1 INCH ROUNDED CHAMFER. SLOPE
TOP FROM CENTER TO EDGE
ANCHOR BOLTS FURNISHED
BY POLE MANUFACTURER.
COORDINATE BOLT SPACING
PER THE MANUFACTURER'S
WRITTEN INSTRUCTIONS
RUBBED CONCRETE ABOVE
GRADE
FINISHED GRADE OR
PAVEMENT
3/4" RGS CONDUIT
24" MIN RADIUS (TYP)
RED, METAL BACKED
POLYETHYLENE TAPE
MARKED "ELECTRIC"
#4 BARE STRANDED COPPER
GROUND CABLE
EXOTHERMIC WELD
1" RGS
CONDUIT TO
NEXT POLE
3/4"X10" COPPER CLAD
GROUND ROD
CONCRETE FOUNDATION -
USE SONOTUBE TO FORM
24"
GRADE
12"
DETAIL - POLE BASE
NTS
REINFORCING STEEL REQUIRED,
BUT NOT COMPLETELY SHOWN.
(6)#6 VERTICAL REINFORCING BARS
EQUALLY SPACED & #3 HORIZONTAL
TIES @ 12" ON CENTER WIRE-TIED
TOGETHER AT 3" FROM OUTSIDE
CONCRETE SURFACE
46"
90° BEND
REINFORCE WITH 6x6-W2-9/2-9
EPOXY COATED MESH
CLASS "QC1"
CONCRETE
4" MIN. COMPACTED
GRANULAR FILL
TO PULLBOX
PULL SERVICING WIRING UP THROUGH THE
CONDUIT, LEAVING APROXIMATELY 6' EXTENDING
OUT OF THE CONDUIT. MAKE FINAL CONNECTIONS
PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
CHARGING STATION
BOLLARD
2" RGS CONDUIT.
STUB UP 6" ABOVE GRADE AND
PROVIDE INSULATED BUSHING
8"
23"
BOLLARD
(REFER TO
CIVIL DETAILS)
EV CHARGING STATION
FIELD COORDINATE EXACT
LOCATION OF CONCRETE
PAD WITH CIVIL PLANS.
FRONT
PLAN VIEW
DETAIL - BASE-PLATE/BOLLARD MOUNTING
FOR EV CHARGING STATION
NTS
SECTION
EV CHARGING STATION.
REFER TO PLANS FOR
LOCATION.
PARKING BLOCK - REFER TO CIVIL PLANS
(TYPICAL)
SIGNAGE (TYPICAL). SEE DETAIL 7/ES501.
DETAIL - TYPICAL LEVEL 2 EV CHARGING STATION PARKING SPACE
NTS
DETAIL - EV CHARGING STATION SIGNAGE
NTS
M
I N
R
BACKFILL NOTES:
UNDER LAWN AREAS, SIDEWALK, STEPS ETC:
CLEAN CLAY OR SAND WATER COMPACTED IN
TWO OR MORE LAYERS.
UNDER ROADS, DRIVES, STREETS, PARKING, CURBS, GUTTERS ETC.:
CLEAN SAND WATER COMPACTED IN 6" LAYERS.
FINISHED GRADE
ELECTRIC PULLBOX. REFER TO
ELECTRICAL SITE PLAN FOR TYPE
AND LOCATION
M I N
I M
U M
POST SHALL BE BURIED A
MINIMUM OF 30" BELOW GRADE
PROVIDE 4' x 4" TREATED LUMBER
POST, EXTENDED 48" ABOVE GRADE
PROVIDE DUPLEX WEATHER
RESISTANT, GFCI RECEPTACLE
WITH A DIE-CAST "IN-USE"
WEATHERPROOF COVER AND "FS"
WEATHERPROOF JUNCTION BOX
(TYPICAL OF 2 PER POST)
DETAIL - POST MOUNTED RECEPTACLES FOR
LEVEL 1 EV CHARGING
DETAIL - 15KV INTERRUPTER SWITCH
FRONT VIEW
REAR VIEW
FRONT VIEW
INSIDE
REAR VIEW
INSIDE
15KV, 95KVBIL
PORCELAIN INSULATOR
15KV, 600A, 50KAIC,
95KVBIL LOAD
INTERRUPTER SWITCH
GPD-3 INSULATING
BARRIER
VENTILATION OPENINGS
SWITCH OPERATOR
WITH INTERLOCK
SWITCH BLADE POSITION
VIEWING WINDOW
EQUIPMENT RATING LABEL
PADLOCKABLE
DOOR HARDWARE
GRADE
GPD-3 INSULATING
BARRIER
15KV, 22.4KAIC, 95KVBIL
POWER FUSE ASSEMBLY
15KV, 95KVBIL
PORCELAIN INSULATOR
SILVER PLATED
COPPER MAIN BUS
VENTILATION OPENINGS
PADLOCKABLE
DOOR HARDWARE
CURRENT TRANSFORMER
MOUNTING PANEL
NTS
NTS
PROVIDE NEMA 1 PANELBOARD FOR EV
CHARGING STATIONS MOUNTED INSIDE A
3R ENCLOSURE. REFER TO ONE-LINE
DIAGRAM AND PANEL SCHEDULE FOR
ADDITIONAL INFORMATION.
PROVIDE CONCRETE PAD TO
MOUNT PANEL ENCLOSURE.
PROVIDE A LOCKABLE NEMA 3R
ENCLOSURE, WITH MINIMUM
DIMENSIONS OF 72"x36"x18" TO
HOUSE PANELBOARD . PROVIDE
WATERTIGHT SEALS FOR ALL
PENETRATIONS THROUGH THIS
ENCLOSURE.
90° BEND
REINFORCE WITH 6x6-W2-9/2-9
EPOXY COATED MESH
4" MIN. COMPACTED
GRANULAR FILL
TO PULLBOX
M
I N
R
COORDINATE ALL CONDUIT TYPES AND
QUANTITIES THROUGH PAD INTO
BOTTOM OF PANEL PRIOR TO
ROUGHING IN THE PAD. REFER TO
ELECTRICAL SITE PLAN.
500W HEATER500W HEATER
PROVIDE CYLINDRICAL LOCK TO ACCEPT
7 PIN BEST INTERCHANGEABLE LOCK
SYSTEM CORE COMPATIBLE WITH
GREAT GRAND MASTER KEY SYSTEM
FOR THE CHILLICOTHE VA MEDICAL
CENTER. CORE TO BE PROVIDED BY VA.
COORDINATE WITH THE COR AND THE
VA LOCK SHOP FOR FURTHER DETAILS
CONCERNING THE GREAT GRAND
MASTER KEY SYSTEM FOR THE MEDICAL
CENTER.
PROVIDE PEDESTAL LEGS ON
BASE OF ENCLOSURE FOR
MOUNTING TO CONCRETE PAD.
PROVIDE BACKBOARD
OPTION IN ENCLOSURE FOR
MOUNTING OF PANELBOARD.
DETAIL 8 NOTE:
PROVIDE 600A, 15KV, 3 POLE, 40KAIC, 95KV BIL LOAD BREAK INTERRUPTER SWITCH.
SWITCH SHALL BE PROVIDED WITH NEMA 3R OUTDOOR PAD MOUNT ENCLOSURE AND 500W (120V, 1 PHASE) SPACE HEATER, MINIMUM 11 GAUGE STEEL ENCLOSURE WITH 10 GAUGE GALVANIZED STEEL CHANNEL FRAME BASE. ENCLOSURE SHALL
HAVE A SPARE FUSE STORAGE POCKET. PROVIDE WITH 1/4" X 2" COPPER GROUND BUS FRONT REAR AND BOTH SIDES
BOLTED TO ENCLOSURE FRAME. EXTERIOR SWITCH OPERATOR SHALL BE PAD-LOCKABLE AND INTERLOCKED WITH DOOR
TO PREVENT OPENING UNLESS SWITCH IS IN THE "OPEN" POSITION. ENCLOSURE SHALL BE PAINTED WITH EXTERIOR RATED
PAINT (CUSTOM COLOR TO BE SELECTED BY THE OWNER). ASSEMBLY SHALL BE UL LISTED.
REFER TO ONE-LINE DIAGRAM FOR FUSE TYPE. PROVIDE 3 ADDITIONAL SPARE FUSE CARTRIDGES.
PROVIDE
BRANCH
CIRCUIT IN
1" RGS
CONDUIT
BOLLARD
(REFER TO
CIVIL DETAILS)
RYAN JETER, PE, PS, CHFM
DETAIL - EXTERIOR CONCRETE EQUIPMENT PAD
NTS
6" THICK
#5 REBAR @ 12" O.C.
MAINTAIN MIN 2"
CLEARANCE
SECTION
COMPACTED ODOT
#304 GRAVEL BASE,
8 THICK
GRADE GRADE
DETAIL 10 NOTES:
1. ADD #3 DOWEL PINS AT MID-POINT OF EXISTING EDGE OF PAD, AND SPACED AT 6" O.C. TO TIE INTO NEW PAD.
2. PROVIDE CONCRETE EQUIPMENT PAD WITH MINIMUM OF 6" SPACING BEYOND FOOTPRINT OF EQUIPMENT.
3. CONCRETE PAD SHALL BE ALLOWED TO CURE FOR NO LESS THAN 7 DAYS PRIOR TO PLACING OF EQUIPMENT.
1 07/06/2021
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
IMPROVE FLEET PARKING AREA
AND ADD VEHICLE CHARGING
STATIONS
CHILLICOTHE, OHIO
538-20-207
P20 Chief Engineer
10/19/2020Revisions: Date:
genesis design llc
"EXPERIENCE SAVES"
Cincinnati, Ohio 45208-2564 (513) 616-9694 email genesisdesignllc@gmail.com Civil Engineering
A DVANCED
E NGINEERING
C ONSULTANTS
Mechanical | Electrical | Plumbing | Fire Protection
1405 Dublin Road Tel: (614) 486-4778
Columbus, Ohio 43215 Fax: (614) 486-4082
D a t e
A
M
F i l e
L o c a t i o n Z p r o j
I m p r o v e
F l e e t
P a r k i n g a n d
A d d
V e h i c l e
C h a r g i n g
S t a t i o n s C
A D
E
E l e c t r i c a s t
E d i t G a v i n L i m
ES601S. SMITHG. LIM
ELECTRICAL SCHEDULES AND
ONE-LINE DIAGRAM
NTS
PARTIAL ONE-LINE DIAGRAM
F1 F1
(E) MH 40
(E) TO BLDG T53, BLDG T57, BLDG 208 VIA
TRANSFORMER PMTT53
(E) PMSG53
(E) PMSC51
TO PMSG259
(E) 3 #500 KCM EPR
15KV CABLE IN 5" CDT
(E) 3 #2/0 KCM EPR 15KV
CABLE & #2-600V GND IN
5" CDT
(E) TO PMSC36
EVP1
(SERVICE
ENTRANCE
RATED)
#1/0 AWG GROUNDING
ELECTRODE CONDUCTOR
3 - #1 AWG ALUMINUM FEEDER, TYPE MV-90,
XLP, 133% INSULATION. REFER TO DRAWING
ES101 FOR PATHWAY REQUIREMENTS. EXTEND
CIRCUIT VIA SWITCH TO TRANSFORMER.
PROVIDE 400A, 208Y/120V, 3Ø, NEMA 1,
PANELBOARD FOR EV CHARGING
STATIONS. MOUNT PANELBOARD WITHIN
A LOCKABLE NEMA 3R ENCLOSURE
(REFER TO DETAIL 3/ES501). ATTACH
WEATHER-RESISTANT VINYL LABEL WITH
PANELBOARD NAME ON ENCLOSURE
DOOR. REFER TO PANEL SCHEDULE ON
THIS SHEET.
PROVIDE TYPE 1 INTERNAL
SURGE PROTECTIVE DEVICE TO
SERVE PANELBOARD. CONNECT
WITH #6 AWG CONDUCTORS
SPD
4 - 600 KCMIL FEEDER,
#3 AWG GROUND,
4" RGS CONDUIT
GENERAL SHEET NOTES:
A. UNLESS NOTED OTHERWISE, ALL CONDUCTORS SHALL BE COPPER
TYPE.
B. PROVIDE TYPEWRITTEN DIRECTORY IN PANELBOARDS WHERE WORK
HAS BEEN PERFORMED
112.5 KVA TRANSFORMER
4160V-208/120V, 3Ø
#1/0 AWG GROUNDING
ELECTRODE CONDUCTOR
PROVIDE 15KV
INTERRUPTER SWITCH
WITH 15KV, 22KAIC, 95KV
BIL FUSES. REFER TO
DETAIL 8/ES501.
NTS
PANELBOARD SCHEDULE
SHEET KEYNOTES:
1. IF ALTERNATE 2 IS ACCEPTED: CIRCUIT BREAKER SHALL REMAIN AS
SPARE.
2. IF ALTERNATE 3 IS ACCEPTED: CIRCUIT BREAKERS SHALL REMAIN AS
SPARES.
EXISTING 4160Y/2400V, 3PH, 4W DISTRIBUTION SYSTEM
RYAN JETER, PE, PS, CHFM
1 07/06/2021