2020.08.27_19169_OTSEGO WASHINGTON ES_HS_REROOF DRAWINGS.pdf
PDF 3 MB Posted
- Solicitation number
- RFP OTS 200000002324 2
- Issued by
- Allegan County, Oden CDP, Michigan
About this file
This document consists of construction drawings for a roof replacement project at Otsego Public Schools facilities in Otsego, Michigan, prepared by Tower Pinkster Architects/Engineers dated August 27, 2020. The project encompasses re-roofing work at two school buildings: Otsego Washington Elementary School (89,856 square feet) located at 538 Washington Street and Otsego High School (139,111 square feet) located at 550 Washington Street. The construction documents include cover sheets, demolition roof plans, roof plans, and detailed roof specifications with multiple design alternatives. For Washington Elementary, the drawings present two re-roofing options: a membrane re-roof system (project 19169.20) and a liquid-applied re-roof system (project 19169.21). Similarly, for the High School, two alternatives are provided: a membrane re-roof system (project 19169.11) and a liquid-applied re-roof system (project 19169.12). The drawings specify roof demolition requirements, new membrane installation details, flashing systems, roof drains, equipment curbs, and edge treatments for various building configurations.
The construction documents reference compliance with the 2015 Michigan Building Code, 2012 NFPA 101 Life Safety Code, 2015 Michigan Energy Code, and applicable plumbing, mechanical, electrical, and barrier-free standards. The project includes typical roof slopes of 1/4 inch per 12 inches, fully adhered membrane systems with perimeter fastening enhancements, rigid insulation installation, roof drain specifications per plumbing drawings, and pre-finished metal flashing and coping systems. Roof areas vary across the buildings, with individual roof sections ranging from 152 square feet to 31,655 square feet. The drawings indicate existing roof conditions including EPDM and TPO membranes, various insulation types, and metal or concrete deck substrates. General notes require contractor inspection of existing conditions, verification of dimensions, protection of existing finishes, and accommodation of new construction per structural, mechanical, plumbing, and electrical plans.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2020.09.09_19169_OTSEGO WASHINGTOIN ES_HS_REROOF ADDENDUM 1.pdf | ||
| 2020.08.27_19169_OTSEGO WASHINGTON ES_HS_REROOF SPECIFICATION.pdf | ||
| Upload.url | URL file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN TEAM
ARCHITECT/ENGINEER
SITE ADDRESS
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O N
E
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
SITE ADDRESS
SITE ADDRESS
OTSEGO WASHINGTON ES & HIGH SCHOOL
RE-ROOF
OTSEGO PUBLIC SCHOOLS
Otsego, Michigan
CONSTRUCTION DOCUMENTS
C O
V E
R S
H E
E T
-1
.2
G
A U
G U
S T
O T
S E
G O
W A
S H
IN
G
T O
N E
S
H
IG
H S
C H
O O
L R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
DRAWING INDEX
OTSEGO HIGH SCHOOL
550 WASHINGTON STREET
OTSEGO, MI 49078
GENERAL
G 001 COVER SHEET
ARCHITECTURAL DEMOLITION (A1) - WASHINGTON ES
AD 111 ROOF DEMOLITION PLAN
ARCHITECTURAL DEMOLITION (A2) - HIGH SCHOOL
AD 111 DEMOLITION ROOF PLAN
ARCHITECTURAL DEMOLITION (B1) - WASHINGTON ES
AD 111 ROOF DEMOLITION PLAN
ARCHITECTURAL DEMOLITION (B2) - HIGH SCHOOL
AD 111 DEMOLITION ROOF PLAN
ARCHITECTURAL (A1) - WASHINGTON ES
A 111 ROOF PLAN
A 112 ROOF DETAILS
ARCHITECTURAL (A2) - HIGH SCHOOL
A 111 ROOF PLAN
A 112 ROOF DETAILS
ARCHITECTURAL (B1) - WASHINGTON ES
A 111 ROOF PLAN
A 112 ROOF DETAILS
ARCHITECTURAL (B2) - HIGH SCHOOL
A 111 ROOF PLAN
A 112 ROOF DETAILS
242 E. KALAMAZOO AVE, SUITE 100
KALAMAZOO, MICHIGAN 49007
PHONE: 269.343.6133
FAX: 269.343.6633
BUILDING: 2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE
ENERGY: 2015 MICHIGAN ENERGY CODE
PLUMBING: 2015 MICHIGAN PLUMBING CODE
MECHANICAL: 2015 MICHIGAN MECHANICAL CODE
FUEL GAS: (IFGC) 2015 INTERNATIONAL FUEL GAS CODE
ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS
BARRIER-FREE: 2015 MICHIGAN BUILDING CODE AND 2009 ICC & C A117.1
USE GROUP: E
CONSTRUCTION TYPE: IIB
AUTOMATIC SPRINKLERS: YES
PROJECT AREA
WASHINGTON ES TOTAL FINISHED PROJECT: 89,856 SQ. FT.
REFERENCED CODES
4 EAST FULTON STREET, SUITE 200
GRAND RAPIDS, MICHIGAN 49503
PHONE: 616.456.9944
FAX: 616.456.5936
ISSUED FOR DATE
OTSEGO WASHINGTON ELEMENTRY SCHOOL
538 WASHINGTON STREET
OTSEGO, MI 49078
PROJECT AREA
HIGH SCHOOL TOTAL FINISHED PROJECT: 139,111 SQ. FT.
A
B
C
D
E
F
G
H
J
K
L
A.1
C.1
E.1
M
N
P
Q
R
S
T
U
V
W
X
Y
Z
AA
BB
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
9,672 SF
18,652 SF
9,806 SF
2,755 SF 31,655 SF 2,525 SF
1,104 SF 2,790 SF
10,927 SF
152 SF
2 4
EX. BRICK CHIMNEY
EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT
30' - 10" 55' - 10" 30' - 10"
16' - 11"
8' - 8"
22' - 7"
22' - 8"
8' - 2" 9' - 7"
6 6
6 6
57' - 11"
22' - 8"
DEMOLITION ROOF PLAN KEY
COMPLETE DEMOLITION OF EXISTING ROOF SYSTEM
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
EX.R.D. EXISTING ROOF DRAIN - SEE PLUMBING DRAWINGS
OUTLINE OF EXISTING ROOF SYSTEM
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS
WHICH ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS
AND BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY
AND ALL DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
D E
M O
L
IT
IO
N
P L A
N
.2
A D
A U
G U
S T
O T
S E
G O
W
A S
H
IN
G T
O N
E L E
M E
N T
A R
Y M
E M
B R
A N
E R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
ISSUED FOR DATE
1/16" = 1'-0"
DEMOLITION ROOF PLAN
KEYED NOTES - DEMOLITION
1 REMOVE DEBRIS AND CLEAN EXISTING TPO MEMBRANE AND FLASHING. PREP FOR NEW
MEMBRANE TO BE APPLIED ON TOP OF EXISTING CLEANED MEMBRANE.
2 REMOVE DEBRIS AND CLEAN EXISTING EPDM MEMBRANE AND FLASHING. PREP FOR
NEW MEMBRANE TO BE APPLIED ON TOP OF EXISTING CLEANED MEMBRANE.
3 REMOVE AND DISCARD EXISTING EPDM MEMBRANE, LAYERS OF RIGID INSULATION,
BUILT-UP ROOF SYSTEM, AND FIBER GLASS BOARD DOWN TO THE ROOF DECK. PREP
FOR NEW ROOF MEMBRANE, RIGID, AND TAPERED INSULATION SYSTEM.
4 REMOVE AND DISCARD EXISTING TPO MEMBRANE, LAYERS OF RIGID INSULATION ,
BUILT-UP ROOF SYSTEM, AND FIBER BOARD DOWN TO THE CONCRETE ROOF DECK.
PREP FOR NEW ROOF MEMBRANE, RIGID, AND TAPERED INSULATION SYSTEM.
5 LEAVE EXISTING ROOF SYSTEM, NO WORK
6 REMOVE AND DISCARD EXISTING FLASHING. PREP FOR NEW FLASHING, MATCH EXISTING
COLOR, SIZE, AND STYLE.
1. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED OTHERWISE.
2. PROVIDE ROOFING MANUFACTURERS STANDARD ROOFING TERMINATION DETAILS AT ALL
PARAPETS, PRE-MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE PENETRATIONS, ETC.
3. PROVIDE CRICKETS AS REQUIRED AT ALL MECHANICAL UNITS, VENTS, ETC. TO MAINTAIN
POSITIVE SLOPE OF 1/4" /1'-0" MINIMUM.
4. EXISTING TAPERED INSULATION NOT SHOWN. CONTRACTOR TO V.I.F. EXISTING TAPERED
INSULATION QUANTITY, LOCATION, AND LAYOUT AND INSTALL NEW AS REQUIRED.
NOTES
ROOF PLAN KEY
TAPERED INSULATION
R.D.
O.D.
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
AHU OR RTU
ACCU
E.F.
ROOF DRAIN - SEE PLUMBING DRAWINGS
OVERFLOW DRAIN - SEE PLUMBING DRAWINGS
ROOF TOP UNIT - SEE MECHANICAL DRAWINGS
CONDENSING UNIT - SEE MECHANICAL DRAWINGS
EXHAUST FAN / HOOD - SEE MECHANICAL DRAWINGS
1. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED OTHERWISE.
2. PROVIDE ROOFING MANUFACTURERS STANDARD ROOFING TERMINATION DETAILS AT ALL
PARAPETS, PRE-MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE PENETRATIONS, ETC.
3. PROVIDE CRICKETS AS REQUIRED AT ALL MECHANICAL UNITS, VENTS, ETC. TO MAINTAIN
POSITIVE SLOPE OF 1/4" /1'-0" MINIMUM.
4. EXISTING TAPERED INSULATION NOT SHOWN. CONTRACTOR TO V.I.F. EXISTING TAPERED
INSULATION QUANTITY, LOCATION, AND LAYOUT AND INSTALL NEW AS REQUIRED.
NOTES
EX.R.D. EXISTING ROOF DRAIN - SEE PLUMBING DRAWINGS
A
B
C
D
E
F
G
H
J
K
L
A.1
C.1
E.1
M
N
P
Q
R
S
T
U
V
W
X
Y
Z
AA
BB
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
9,672 SF
18,605 SF
9,806 SF
2,620 SF 31,655 SF 2,525 SF
1,104 SF
2,790 SF
10,927 SF
152 SF
7 8
43' - 11"
54' - 3"
20' - 1"
EX. BRICK CHIMNEY
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
EX. ROOF
EXPANSION JOINT
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
EX. ROOF
EXPANSION JOINT
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM 10
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
A 112
SIM
A 112
SIM
EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM 7
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
30' - 10" 55' - 10" 30' - 10"
16' - 11"
8' - 8" 13' - 11"
17' - 9"
12' - 8" 9' - 6"
57' - 6"
13' - 1" 9' - 7"
27' - 0" 63' - 0" 27' - 6"
27' - 0" 63' - 6" 27' - 0"
9' - 7"
8' - 2"
117' - 8"
135' - 3"
"6' - 0"
44' - 4"
22' - 3" 67' - 6"
26' - 7"
8' - 2" 9' - 7"
49' - 9"
44' - 3"
27' - 11" 64' - 2" 7' - 3"
64' - 2"
110' - 4"
6 6
GENERAL NOTES
1. NEW FLASHING, FASCIA, PRE-MANUFACTURED ROOF EDGE SYSTEM REQUIRED IF
EXISITNG IS DAMAGED OR NOT ABLE TO REUSE EXISTING FLASHING, FASCIA, OR PRE-
MANUFACTURED ROOF EDGE SYSTEM.
2. ROOF DETAILS REFER TO SHEET A112
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
P L A
N
.2
A
A U
G U
S T
O T
S E
G O
W
A S
H
IN
G T
O N
E L E
M E
N T
A R
Y M
E M
B R
A N
E R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
ISSUED FOR DATE
1/16" = 1'-0"
ROOF PLAN
KEYED NOTES - NEW CONSTRUCTION - RE-ROOF
1 FLEECEBACK TPO MEMBRANE INSTALLED DIRECTLY ON EXISTING TPO ROOF SYSTEM
WITH FASTENING ENHANCEMENTS AT PERIMETER.
2 FULLY ADHERED EPDM, ON FULLY ADHERED 4" RIGID INSULATION, FULLY ADHERED
1/2" COVERBOARD, AND TAPPERED INSULATION AS NEEDED, ADHERED TO METAL
ROOF DECK.
3 FULLY ADHERED FLEECEBACK EPDM INSTALLED DIRECTLY OVER EXISTING EPDM ROOF
SYSTEM WITH FASTENING ENHANCEMENTS AT THE PERIMETER.
4 FULLY ADHERED EPDM, ON FULLY ADHERED 4" RIGID INSULATION, FULLY ADHERED
1/2" COVERBOARD, AND TAPPERED INSULATION AS NEEDED, ADHERED TO CONCRETE
ROOF DECK.
5 LEAVE EXISTING ROOF, IN VERY GOOD CONDITION.
6 NEW PARAPET FLASHING AT PERIMETER.
7 NEW WALL FLASHING AT FULL PERIMETER.
8 INSTALL NEW EPDM OVER ROOF EXPANSION JOINT, OVERLAP AND JOIN WITH
ADJACENT ROOF(S).
9 NEW 2" RIGID INSULATION UP PARAPET WALL.
ROOF STRUCTURE (SEE
STRUCTURAL)
TREATED NAILER(s) AS REQUIRED
ROOF DECK
EX. CANT STRIP
11/2" RIGID INSULATION
EX. PREFAB ROOF CURB
COUNTER FLASHING WITH
APPROVED SEALING WASHER
AND FASTENER @ 6" O.C.
EX. ROOF MOUNTED EQUIPMENT
EX. TREATED 2x4 NAILER
M
IN
EX. LAP SEALANT
EX. MEMBRANE ROOF
NOTE:
FOR TYPICAL INSTANCES BELOW AHU's & RTU's
WHERE ROOF DECK RUNS CONTINUOUS,
PROVIDE NOISE ISOLATION REQUIREMENTS
USING (2) LAYERS OF 5/8" GYPSUM BOARD
(TOP & BOTTOM (4 TOTAL)) WITH (2) LAYERS OF
1 1/2" MINERAL FIBER INSULATION BETWEEN,
SEE MECH. DRAWINGS FOR ADDITIONAL INFO.
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS AT
THE PERIMETER AND CORNERS
CONTINUE
MEMBRANE INTO
ROOF DRAIN
ROOF DRAIN - REFER TO
PLUMBING DRAWINGS AND
SPEC SECTION 22 1423.
14 GAGE COATED STEEL
BEARING PAN FURNISHED
WITH ROOF DRAIN
CLAMPING RING FURNISHED
WITH ROOF DRAIN
1 1/2" METAL DECK REINFORCED
AT OPENING WITH 3" x 3" x 1/4"
STEEL ANGLES
EX. MEMBRANE ROOFING ON RIGID
INSULATION, TAPER TO DRAIN
/2
CENTER LINE OF VALLEY OF
FINISHED ROOF
1" THICK INSULATION
PER 22 0700.
PIPE INSULATION ON DRAIN
LEADERS PER 22 0700.
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE PERIMETER
AND CORNERS
ROOF DECK
INSULATION
FLASHING
VENT PIPE
SEALANT
ROOFING
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS AT
THE PERIMETER AND CORNERS
INSERT BOX THROUGH WALL FROM BACKSIDE (ROOF
SIDE) OF WALL. TURN OVER METAL AT FACE OF WALL
WITH HEMMED EDGES & SECURE BOX TO WALL. (TYPICAL
ALL FOUR SIDES. - METAL CORNERS ARE OPEN,
SMOOTH-CUT ALL SHARP EDGES, REMOVE ANY BURRS.)
MEMBRANE FROM ABOVE TO BE FOLDED INTO BOX
APPROX. 2", ADHERED TO TOP & SEALED AT EDGE.
FOLD ROOFING MEMBRANE INTO SCUPPER
APPROXIMATELY 6" AT BOTTOM & SIDES. ADHERE
MEMBRANE TO BOX METAL AND CLOSE ENTIRE
PERIMETER WITH ROOFERS "WATER-CUT-OFF" MASTIC.
ROOFING
MEMBRANE.
FABRICATE PREFINISHED METAL DRIP AT
BOTTOM OF SCUPPER. IF NECESSARY
POP-RIVET TO BOTTOM OF FRAME PIECE
AND SET IN BED OF SEALANT.
HEM OVER FRONT EDGES
OF SCUPPER BOX AND SEAL
AROUND PERIMETER
FABRICATE PREFINISHED METAL
"PICTURE FRAME" FOR EXTERIOR
OPENING FACE OF SCUPPER. INSTALL IN
SEALANT BED FACE AND BOTTOM / TOP
SIDES OF BRICK ALL AROUND
PREFINISHED METAL SCUPPER BOX CONSTRUCTION.
FABRICATE FROM SINGLE SHEET OF MATERIAL, WITH
ONE JOINT IN TOP UPPER CORNER. SMEAR SEALANT
OVER ENTIRE JOINT FOR WATER TIGHT CLOSURE
A P P R O
X.
APPROX.
6" x
LO
N G
O P E N
IN
G
/2
VARIES - SEE PLAN
3'-0" x 2'-6"
6" 2' - 6"
EX. INSULATED
METAL ROOF HATCH
EX. CAP FLASHING
EX. CANT STRIP
EX. LAP SEALANT
EX. MEMBRANE
ROOFING
TAPERED
INSULATION
PRECAST PLANK,
REFER TO
STRUCTURAL
SEE STRUCTURAL
FOR SUPPORTS
SNAP LATCH AND HANDLE
SAFETY POST BY ROOF
HATCH MANUFACTURER
LIFT MECHANISM
LADDER - SEE LADDER
DETAIL FOR ADDITIONAL
INFORMATION
EPDM FULLY ADHERED ROOF
SYSTEM WITH
ENHANCEMENTS AT THE
PERIMETER AND CORNERS
SECOND FLOOR
112' - 0 1/2"
1 3/8"
ALUM. EDGE TRIM
(MATCH EX. STYLE
AND COLOR)
PRE-FINISHED ALUM.
GRAVEL STOP (MATCH
EX. STYLE AND COLOR)
FLEECEBACK EPDM FULLY ADHERED
ROOF SYSTEM WITH ENHANCEMENTS
AT THE PERIMETER AND CORNERS
EX. 1-1/2" METAL ROOF DECK
EX. 2-1/2" EPS INSLUATION
EX. 2" POLYISO INSULATION
V .I .F
/8
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. CMU WALL CONSTRUCTION
EX. P.T. 2X8, 1X8, 3/4" PLYWOOD,
2X8 (REPLACE AS NEEDED)
ALUM. EDGE TRIM
(MATCH EX. STYLE
AND COLOR)
FLEECEBACK TPO FULLY ADHERED
ROOF SYSTEM WITH ENHANCEMENTS
AT THE PERIMETER AND CORNERS
EX. 1-1/2" METAL ROOF DECK
EX. 1-1/2" POLYISO INSULATION
EX. TPO ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. METAL STUD WALL CONSTRUCTION
EX. P.T. (2) 2X8, 1X8, 3/4"
PLYWOOD, 2X8, V.I.F.
(REPLACE AS NEEDED)
PRE-FABRICATED,
PREFINISHED METAL
COPING ASSEMBLY , V.I.F.
(MATCH EX. STYLE AND
COLOR)
1 3/8"
EX. 1-3/4" POLYISO INSULATION
EX. 1-1/2" POLYISO INSULATION
V .I .F
/8
V .I .F
ALUM. EDGE TRIM
(MATCH EX. STYLE
AND COLOR)
FLEECEBACK EPDM FULLY ADHERED
ROOF SYSTEM WITH ENHANCEMENTS
AT THE PERIMETER AND CORNERS
EX. 1-1/2" METAL ROOF DECK
EX. 2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. METAL STUD WALL CONSTRUCTION
EX. P.T. (2) 2X8, 1X8, 3/4"
PLYWOOD, 2X8, V.I.F.
(REPLACE AS NEEDED)
PRE-FABRICATED,
PREFINISHED METAL COPING
ASSEMBLY , V.I.F. (MATCH
EX. STYLE AND COLOR)
EX. 1" BUILT-UP ROOF SYSTEM
EX. 3/4" FIBER GLASS BOARD
V .I .F
/8
1 3/8"
R
122' - 5 1/2"
1/8"
ALUM. EDGE TRIM
(MATCH EX. STYLE
AND COLOR)
PRE-FABRICATED,
PREFINISHED METAL
COPING ASSEMBLY, V.I.F.
(MATCH EX. STYLE AND
COLOR)
FLEECEBACK EPDM FULLY
ADHERED ROOF SYSTEM WITH
ENHANCEMENTS AT THE
PERIMETER AND CORNERS.
RUN UP AND OVER PARAPET
EX. 1-1/2" METAL ROOF DECK
EX. 2" EPS INSLUATION
EX. 2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. CMU WALL CONSTRUCTION
EX. P.T. 2X10, 1X10
(REPLACE AS NEEDED)
EX. DOUBLE WYTHE CMU
WALL CONSTRUCTION
V .I .F
/8
V .I .F
120' - 3"
BB
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS AT
THE PERIMETER AND CORNERS.
RUN UP AND OVER PARAPET
EX. 1'-5" CONCRETE ROOF DECK
(2) LAYERS OF 2" RIGID INSULATION
EX. PRECAST
PARAPET
1/2" COVER BOARD
VAPOR BARRIER, TURN UP
AT PARAPET EDGES
PRE-FINISHED ALUM.
GRAVEL STOP, V.I.F.
(MATCH EX. STYLE AND
COLOR)
V .I .F
SEALANT (MATCH
PRE-FINISHED COLOR)
2" RIGID INSULATION ALONG PARAPET
CANT STRIP
/2
1 3/8"
ALUM. EDGE TRIM
(MATCH EX. STYLE
AND COLOR)
PRE-FINISHED ALUM.
GRAVEL STOP (MATCH
EX. STYLE AND COLOR)
FLEECEBACK EPDM FULLY ADHERED
ROOF SYSTEM WITH ENHANCEMENTS
AT THE PERIMETER AND CORNERS
EX. 2" POLYISO INSULATION
V .I .F
/8
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. 1-1/2" POLYISO INSULATION ON 3/4"
PLYWOOD SYSTEM (REPLACE AS NEEDED)
EX. P.T. 2X6, 1X6
(REPLACE AS NEEDED)
EX. METAL STUD
SYSTEM
EX. EPDM ROOF MEMBRANE SYSTEM
EX. 1-1/2" METAL ROOF DECK
EX. PLASTER FASCIA
EX. BLOCKING
125' - 0"
122' - 5"
EX. P.T. 3/4" PLYWOOD ON 2X4
WALL SYSTEM (REPLACE AS NEEDED)
EX. P.T. 3/4" PLYWOOD ON 2X4
WALL SYSTEM (REPLACE AS NEEDED)
1"
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS AT
THE PERIMETER AND CORNERS.
RUN UP AND OVER PARAPET
EX. 1'-5" CONCRETE ROOF DECK
(2) LAYERS OF 2" RIGID INSULATION
1/2" COVER BOARD
VAPOR BARRIER, TURN UP
AT PARAPET EDGES
2" RIGID INSULATION ALONG PARAPET
CANT STRIP
EX. CONCRETE STRUCTURE
8"
METAL EXPANSION JOINT COVER SYSTEM
MOISTURE BARRIER
DETAIL 10 / A112 SIDE DETAIL 11/ A112 SIDE
11 1/2"
FLEECEBACK EPDM FULLY ADHERED
ROOF SYSTEM WITH ENHANCEMENTS
AT THE PERIMETER AND CORNERS,
RUN UP AND OVER PARAPET
EX. 2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. 1-1/2" METAL ROOF DECK
125' - 9 1/2"
123' - 10"
K
1"
EX. COMPRESSIBLE TUBE
(REPLACE AS NEEDED)
EX. RUBBERGARD EPDM
MEMBRANE (REPLACE AS NEEDED)
FLEECEBACK EPDM FULLY
ADHERED ROOF SYSTEM WITH
ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN
UP AND OVER EXPANSION JOINT
EX. 1-1/2" METAL ROOF DECK
EX. 2" EPS INSLUATION
EX. 1-1/2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEMV
A R
IE
S
111' - 6 1/2"
EX. CMU WALL CONSTRUCTIONEX. BRICK CONSTRUCTION
FLEECEBACK EPDM FULLY
ADHERED ROOF SYSTEM WITH
ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN
UP AND OVER EXPANSION JOINT
EX. 1-1/2" METAL ROOF DECK
EX. 2" EPS INSLUATION
EX. 1-1/2" POLYISO
INSULATION
EX. EPDM ROOF
MEMBRANE SYSTEM
EX. BUILT-UP ROOF MATERIAL
BETWEEN ROOF SYSTEMS
STAINLESS STEEL FLASHING AND COUNTER
FLASHING. TURN UP AND SECURE TO MASONRY
WALL @ 12" O.C.; PROVIDE CONTINUOUS SEALANT
@ TOP EDGE. (MATCH EX. STYLE AND COLOR)
EX. CANT STRIP (REPLACE AS REQUIRED)
FLEECEBACK EPDM FULLY ADHERED
ROOF SYSTEM WITH ENHANCEMENTS
AT THE PERIMETER AND CORNERS,
RUN UP WALL TO FLASHING
EX. INSULATION (VARIES)
EX. EPDM ROOF MEMBRANE SYSTEM
EX. 1-1/2" METAL ROOF DECK
EX. INSULATION (VARIES)
EX. BRICK AND CMU WALL CONSTRUCTION
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
D E
T A
IL
S
.2
A
A U
G U
S T
O T
S E
G O
W
A S
H
IN
G T
O N
E L E
M E
N T
A R
Y M
E M
B R
A N
E R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
ISSUED FOR DATE
1 1/2" = 1'-0"A 112
1 TYPICAL ROOF CURB
1 1/2" = 1'-0"A 112
4 ROOF DRAIN DETAIL
1 1/2" = 1'-0"A 112
3 TYPICAL ROOF PENETRATION
3" = 1'-0"A 112
5 TYPICAL SCUPPER SECTION
1 1/2" = 1'-0"A 112
2 TYPICAL ROOF HATCH
1 1/2" = 1'-0"A 112
7 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
6 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
8 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
9 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
10 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
11 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
12 EX. ROOF EXPANSION JOINT DETAIL
1 1/2" = 1'-0"A 112
13 EX. ROOF EXPANSION JOINT DETAIL
1 1/2" = 1'-0"A 112
14 EX. ROOF TIE-IN DETAIL
1 1/2" = 1'-0"A 112
15 EX. TYPICAL ROOF-WALL DETAIL
A
B
C
D
E
F
G
H
J
K
L
A.1
C.1
E.1
M
N
P
Q
R
S
T
U
V
W
X
Y
Z
AA
BB
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
9,672 SF
18,652 SF
9,806 SF
2,755 SF 31,655 SF 2,525 SF
1,104 SF 2,790 SF
10,927 SF
152 SF
2 2
EX. BRICK CHIMNEY
EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT
DEMOLITION ROOF PLAN KEY
COMPLETE DEMOLITION OF EXISTING ROOF SYSTEM
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
EX.R.D. EXISTING ROOF DRAIN - SEE PLUMBING DRAWINGS
OUTLINE OF EXISTING ROOF SYSTEM
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS
WHICH ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS
AND BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY
AND ALL DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
D E
M O
L
IT
IO
N
P L A
N
.2
A D
A U
G U
S T
O T
S E
G O
W
A S
H
IN
G T
O N
E L E
M E
N T
A R
Y L
IQ
U
ID
A P
P L
IE
D R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
ISSUED FOR DATE
1/16" = 1'-0"
DEMOLITION ROOF PLAN
KEYED NOTES - DEMOLITION
1 REMOVE DEBRIS AND CLEAN EXISTING TPO MEMBRANE AND FLASHING. PREP FOR
NEW MEMBRANE TO BE APPLIED ON TOP OF EXISTING CLEANED MEMBRANE.
2 REMOVE DEBRIS AND CLEAN EXISTING EPDM MEMBRANE AND FLASHING. PREP FOR
NEW MEMBRANE TO BE APPLIED ON TOP OF EXISTING CLEANED MEMBRANE.
3 LEAVE EXISTING ROOF SYSTEM, NO WORK
ROOF PLAN KEY
TAPERED INSULATION
R.D.
O.D.
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
AHU OR RTU
ACCU
E.F.
ROOF DRAIN - SEE PLUMBING DRAWINGS
OVERFLOW DRAIN - SEE PLUMBING DRAWINGS
ROOF TOP UNIT - SEE MECHANICAL DRAWINGS
CONDENSING UNIT - SEE MECHANICAL DRAWINGS
EXHAUST FAN / HOOD - SEE MECHANICAL DRAWINGS
1. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED OTHERWISE.
2. PROVIDE ROOFING MANUFACTURERS STANDARD ROOFING TERMINATION DETAILS AT ALL
PARAPETS, PRE-MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE PENETRATIONS, ETC.
3. PROVIDE CRICKETS AS REQUIRED AT ALL MECHANICAL UNITS, VENTS, ETC. TO MAINTAIN
POSITIVE SLOPE OF 1/4" /1'-0" MINIMUM.
NOTES
EX.R.D. EXISTING ROOF DRAIN - SEE PLUMBING DRAWINGS
A
B
C
D
E
F
G
H
J
K
L
A.1
C.1
E.1
M
N
P
Q
R
S
T
U
V
W
X
Y
Z
AA
BB
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
9,672 SF
18,605 SF
9,806 SF
2,620 SF 31,655 SF 2,525 SF
1,104 SF
2,790 SF
10,927 SF
152 SF
EX. BRICK CHIMNEY
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
EX. ROOF
EXPANSION JOINT
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
EX. ROOF
EXPANSION JOINT
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM 10
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
A 112
SIM
A 112
SIM
EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT
EX. ROOF
EXPANSION JOINT
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM 7
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
1 1
GENERAL NOTES
1. NEW FLASHING, FASCIA, PRE-MANUFACTURED ROOF EDGE SYSTEM REQUIRED IF
EXISITNG IS DAMAGED OR NOT ABLE TO REUSE EXISTING FLASHING, FASCIA, OR PRE-
MANUFACTURED ROOF EDGE SYSTEM.
2. FLASHING, FASCIA, PRE-FINISHED ALUMINUM PARAPET GRAVE STOP TO BE REMOVED,
SALVAGED, AND REINSTALLED.
3. ROOF DETAILS REFER TO SHEET A112
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
P L A
N
.2
A
A U
G U
S T
O T
S E
G O
W
A S
H
IN
G T
O N
E L E
M E
N T
A R
Y L
IQ
U
ID
A P
P L
IE
D R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
ISSUED FOR DATE
1/16" = 1'-0"
ROOF PLAN
KEYED NOTES - NEW CONSTRUCTION - RE-ROOF
1 FULLY ADHERED 3 COURSE OVER ALL MEMBRANE AND FLASHING LAPS. APPLY
LIQUID BASE COAT AND LIQUID TOP COAT.
TREATED NAILER(s) AS REQUIRED
ROOF DECK
CANT STRIP
1-1/2" RIGID INSULATION
EX. PREFAB ROOF CURB
COUNTER FLASHING WITH
APPROVED SEALING WASHER
AND FASTENER @ 6" O.C.
EX. ROOF MOUNTED EQUIPMENT
EX. TREATED 2x4 NAILER
M
IN
/4
EX. LAP SEALANT
EX. MEMBRANE ROOF
NOTE:
FOR TYPICAL INSTANCES BELOW AHU's & RTU's
WHERE ROOF DECK RUNS CONTINUOUS,
PROVIDE NOISE ISOLATION REQUIREMENTS
USING (2) LAYERS OF 5/8" GYPSUM BOARD
(TOP & BOTTOM (4 TOTAL)) WITH (2) LAYERS OF
1 1/2" MINERAL FIBER INSULATION BETWEEN,
SEE MECH. DRAWINGS FOR ADDITIONAL INFO.
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
EX. RIGID INSULATION
THREE-COURSE OVER ALL EX.
MEMBRANE AND FLASHING LAPS CONTINUE MEMBRANE
INTO ROOF DRAIN
ROOF DRAIN - REFER TO
PLUMBING DRAWINGS AND
SPEC SECTION 22 1423.
14 GAGE COATED STEEL
BEARING PAN FURNISHED
WITH ROOF DRAIN
CLAMPING RING FURNISHED
WITH ROOF DRAIN
1 1/2" METAL DECK REINFORCED
AT OPENING WITH 3" x 3" x 1/4"
STEEL ANGLES
EX. MEMBRANE ROOFING ON RIGID
INSULATION, TAPER TO DRAIN
/2
CENTER LINE OF VALLEY OF
FINISHED ROOF
1" THICK INSULATION
PER 22 0700.
PIPE INSULATION ON DRAIN
LEADERS PER 22 0700.
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
LIQUID APPLIED
REINFORCED BASE COAT
EX. ROOF DECK
EX. INSULATION
EX. FLASHING
EX. VENT PIPE
EX. SEALANT
EX. ROOFING
LIQUID APPLIED TOP COAT
LIQUID APPLIED BASE COAT
LIQUID APPLIED REINFORCED FLASHING
INSERT BOX THROUGH WALL FROM BACKSIDE (ROOF
SIDE) OF WALL. TURN OVER METAL AT FACE OF WALL
WITH HEMMED EDGES & SECURE BOX TO WALL. (TYPICAL
ALL FOUR SIDES. - METAL CORNERS ARE OPEN,
SMOOTH-CUT ALL SHARP EDGES, REMOVE ANY BURRS.)
MEMBRANE FROM ABOVE TO BE FOLDED INTO BOX
APPROX. 2", ADHERED TO TOP & SEALED AT EDGE.
FOLD ROOFING MEMBRANE INTO SCUPPER
APPROXIMATELY 6" AT BOTTOM & SIDES. ADHERE
MEMBRANE TO BOX METAL AND CLOSE ENTIRE
PERIMETER WITH ROOFERS "WATER-CUT-OFF" MASTIC.
EX. ROOFING MEMBRANE.
FABRICATE PREFINISHED METAL DRIP AT
BOTTOM OF SCUPPER. IF NECESSARY
POP-RIVET TO BOTTOM OF FRAME PIECE
AND SET IN BED OF SEALANT.
HEM OVER FRONT EDGES
OF SCUPPER BOX AND SEAL
AROUND PERIMETER
FABRICATE PREFINISHED METAL
"PICTURE FRAME" FOR EXTERIOR
OPENING FACE OF SCUPPER. INSTALL IN
SEALANT BED FACE AND BOTTOM / TOP
SIDES OF BRICK ALL AROUND
PREFINISHED METAL SCUPPER BOX CONSTRUCTION.
FABRICATE FROM SINGLE SHEET OF MATERIAL, WITH
ONE JOINT IN TOP UPPER CORNER. SMEAR SEALANT
OVER ENTIRE JOINT FOR WATER TIGHT CLOSURE
A P P R O
X.
APPROX.
6" x
LO
N G
O P E N
IN
G
/2
VARIES - SEE PLAN
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
THREE-COURSE OVER ALL
MEMBRANE AND FLASHING LAPS
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
THREE-COURSE OVER ALL MEMBRANE AND FLASHING LAPS
3'-0" x 2'-6"
6" 2' - 6"
INSULATED
METAL ROOF
HATCH
CAP FLASHING
CANT STRIP
LAP SEALANT
MEMBRANE
ROOFING
TAPERED
INSULATION
PRECAST PLANK,
REFER TO
STRUCTURAL
SEE STRUCTURAL
FOR SUPPORTS
SNAP LATCH AND HANDLE
SAFETY POST BY ROOF
HATCH MANUFACTURER
LIFT MECHANISM
LADDER - SEE LADDER
DETAIL FOR ADDITIONAL
INFORMATION
SECOND FLOOR
112' - 0 1/2"
1 3/8"
EX. ALUM. EDGE
TRIM (REPLACE
AS NEEDED)
EX. PRE-FINISHED
ALUM. GRAVEL STOP
(REPLACE AS NEEDED)
EX. 1-1/2" METAL ROOF DECK
EX. 2-1/2" EPS INSLUATION
EX. 2" POLYISO INSULATION
V .I .F
/8
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. CMU WALL CONSTRUCTION
EX. P.T. 2X8, 1X8, 3/4"
PLYWOOD, 2X8
(REPLACE AS NEEDED)
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS
LIQUID APPLIED BASE COAT,
TO GRAVEL STOP EDGE
LIQUID APPLIED TOP COAT, TO
GRAVEL STOP EDGE1
EX. ALUM. EDGE
TRIM (REPLACE
AS NEEDED)
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS
EX. 1-1/2" METAL ROOF DECK
EX. 1-1/2" POLYISO INSULATION
EX. TPO ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. METAL STUD WALL CONSTRUCTION
EX. P.T. (2) 2X8, 1X8, 3/4" PLYWOOD,
2X8, V.I.F. (REPLACE AS NEEDED)EX. PRE-FABRICATED,
PREFINISHED METAL
COPING ASSEMBLY , V.I.F.
(REPLACE AS NEEDED)
1 3/8"
EX. 1-3/4" POLYISO INSULATION
EX. 1-1/2" POLYISO INSULATION
V .I .F
/8
V .I .F
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
REMOVE, SALVAGE, AND
REINSTALL COPING ASSEMBLY
EX. ALUM. EDGE
TRIM (REPLACE
AS NEEDED) EX. 1-1/2" METAL ROOF DECK
EX. 2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. METAL STUD WALL CONSTRUCTION
EX. P.T. (2) 2X8, 1X8, 3/4" PLYWOOD,
2X8, V.I.F. (REPLACE AS NEEDED)EX. PRE-FABRICATED,
PREFINISHED METAL
COPING ASSEMBLY , V.I.F.
(REPLACE AS NEEDED)
EX. 1" BUILT-UP ROOF SYSTEM
EX. 3/4" FIBER GLASS BOARD
V .I .F
/8
1 3/8"
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
REMOVE, SALVAGE, AND
REINSTALL COPING ASSEMBLY
R
122' - 5 1/2"
1/8"
EX. ALUM. EDGE
TRIM (REPLACE
AS NEEDED)
EX. PRE-FABRICATED,
PREFINISHED METAL
COPING ASSEMBLY, V.I.F.
(REPLACE AS NEEDED)
EX. 1-1/2" METAL ROOF DECK
EX. 2" EPS INSLUATION
EX. 2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. CMU WALL CONSTRUCTION
EX. P.T. 2X10, 1X10
(REPLACE AS NEEDED)
EX. DOUBLE WYTHE CMU
WALL CONSTRUCTION
V .I .F
/8
V .I .F
120' - 3"
REMOVE, SALVAGE, AND REINSTALL
COPING ASSEMBLY
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP AND
OVER PARAPET
LIQUID APPLIED TOP COAT, UP AND
OVER PARAPET
BB
EX. 1'-5" CONCRETE ROOF DECK
(2) LAYERS OF 2" RIGID INSULATION
EX. PRECAST
PARAPET
1/2" COVER BOARD
VAPOR BARRIER, TURN UP
AT PARAPET EDGES
EX. PRE-FINISHED
ALUM. GRAVEL STOP
(REPLACE AS NEEDED)
V .I .F
EX. SEALANT
(REPLACE AS NEEDED,
MATCH COLOR)
CANT STRIP
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP
AND OVER PARAPET TO EDGE
LIQUID APPLIED TOP COAT, UP
AND OVER PARAPET TO EDGE
EX. EPDM MEMBRANE SYSTEM
1 3/8"
EX. ALUM. EDGE
TRIM (REPLACE
AS NEEDED)
EX. PRE-FINISHED
ALUM. GRAVEL STOP
(REPLACE AS NEEDED)
EX. 2" POLYISO INSULATION
V .I .F
/8
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CEMENT
PLASTER FASCIA
EX. 1-1/2" POLYISO INSULATION ON 3/4"
PLYWOOD SYSTEM (REPLACE AS NEEDED)
EX. P.T. 2X6, 1X6
(REPLACE AS NEEDED)
EX. METAL STUD
SYSTEM
EX. EPDM ROOF MEMBRANE SYSTEM
EX. 1-1/2" METAL ROOF DECK
EX. PLASTER FASCIA
EX. BLOCKING
125' - 0"
122' - 5"
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP
AND OVER PARAPET TO EDGE
LIQUID APPLIED TOP COAT, UP
AND OVER PARAPET TO EDGE
EX. P.T. 3/4" PLYWOOD ON 2X4
WALL SYSTEM (REPLACE AS NEEDED)
EX. P.T. 3/4" PLYWOOD ON 2X4
WALL SYSTEM (REPLACE AS NEEDED)
1"
EX. 1'-5" CONCRETE ROOF DECK
(2) LAYERS OF 2" RIGID INSULATION
1/2" COVER BOARD
VAPOR BARRIER, TURN UP
AT PARAPET EDGES
CANT STRIP
EX. CONCRETE STRUCTURE
8"
REMOVE, SALVAGE, AND REINSTALL METAL
EXPANSION JOINT COVER SYSTEM
MOISTURE BARRIER
DETAIL 10 / A112 SIDE DETAIL 11/ A112 SIDE
EX. 2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. 1-1/2" METAL ROOF DECK
123' - 10"
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP AND
OVER PARAPET
LIQUID APPLIED TOP COAT, UP AND
OVER PARAPET
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP AND
OVER PARAPET
LIQUID APPLIED TOP COAT, UP AND
OVER PARAPET
EX. PEDM ROOF MEMBRANE SYSTEM
K
1"
EX. COMPRESSIBLE TUBE
(REPLACE AS NEEDED)
EX. RUBBERGARD EPDM MEMBRANE
(REPLACE AS NEEDED)
EX. 1-1/2" METAL ROOF DECK
EX. 2" EPS INSLUATION
EX. 1-1/2" POLYISO INSULATION
EX. EPDM ROOF MEMBRANE SYSTEMV
A R
IE
S
111' - 6 1/2"
EX. CMU WALL CONSTRUCTIONEX. BRICK CONSTRUCTION
EX. 1-1/2" METAL ROOF DECK
EX. 2" EPS INSLUATION
EX. 1-1/2" POLYISO
INSULATION
EX. EPDM ROOF
MEMBRANE SYSTEM
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP AND
OVER PARAPET
LIQUID APPLIED TOP COAT, UP AND
OVER PARAPET
THREE-COURSE OVER ALL
MEMBRANE AND FLASHING LAPS,
UP AND OVER PARAPET
LIQUID APPLIED BASE COAT,
UP AND OVER PARAPET
LIQUID APPLIED TOP COAT,
UP AND OVER PARAPET
EX. BUILT-UP ROOF MATERIAL
BETWEEN ROOF SYSTEMS
THREE-COURSE OVER ALL
MEMBRANE AND FLASHING
LAPS, UP AND OVER PARAPET
LIQUID APPLIED BASE COAT
LIQUID APPLIED TOP COAT
EX. STAINLESS STEEL FLASHING AND COUNTER
FLASHING. TURN UP AND SECURE TO MASONRY
WALL @ 12" O.C.; PROVIDE CONTINUOUS
SEALANT @ TOP EDGE. (REPLACE AS NEEDED)
EX. CANT STRIP (REPLACE AS REQUIRED)
EX. INSULATION (VARIES)
EX. EPDM ROOF MEMBRANE SYSTEM
EX. 1-1/2" METAL ROOF DECK
EX. INSULATION (VARIES)
EX. BRICK AND CMU WALL CONSTRUCTION
THREE-COURSE OVER ALL MEMBRANE
AND FLASHING LAPS, UP AND OVER
PARAPET
LIQUID APPLIED BASE COAT, UP AND
OVER PARAPET
LIQUID APPLIED TOP COAT, UP AND
OVER PARAPET
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
D E
T A
IL
S
.2
A
A U
G U
S T
O T
S E
G O
W
A S
H
IN
G T
O N
E L E
M E
N T
A R
Y L
IQ
U
ID
A P
P L
IE
D R
E -R
O O
F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
ISSUED FOR DATE
1 1/2" = 1'-0"A 112
1 TYPICAL ROOF CURB
1 1/2" = 1'-0"A 112
4 ROOF DRAIN DETAIL
1 1/2" = 1'-0"A 112
3 TYPICAL ROOF PENETRATION
3" = 1'-0"A 112
5 TYPICAL SCUPPER SECTION
1 1/2" = 1'-0"A 112
2 TYPICAL ROOF HATCH
1 1/2" = 1'-0"A 112
7 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
6 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
8 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
9 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
10 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
11 EX. ROOF EDGE DETAIL
1 1/2" = 1'-0"A 112
12 EX. ROOF EXPANSION JOINT DETAIL
1 1/2" = 1'-0"A 112
13 EX. ROOF EXPANSION JOINT DETAIL
1 1/2" = 1'-0"A 112
14 EX. ROOF TIE-IN DETAIL
1 1/2" = 1'-0"A 112
15 EX. TYPICAL ROOF-WALL DETAIL
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS WHICH
ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS AND
BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
ROOF PLAN KEY
OUTLINE OF EXISTING ROOF SYSTEM
R.D
O.D
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
AHU OR RTU
ACCU
E.F
ROOF DRAIN - SEE PLUMBING DRAWINGS
OVERFLOW DRAIN - SEE PLUMBING DRAWINGS
ROOF TOP UNIT - SEE MECHANICAL DRAWINGS
CONDENSING UNIT - SEE MECHANICAL DRAWINGS
EXHAUST FAN / HOOD - SEE MECHANICAL DRAWINGS
1. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED OTHERWISE.
2. PROVIDE ROOFING MANUFACTURERS STANDARD ROOFING TERMINATION DETAILS AT ALL
PARAPETS, PRE-MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE PENETRATIONS, ETC.
3. PROVIDE CRICKETS AS REQUIRED AT ALL MECHANICAL UNITS, VENTS, ETC. TO MAINTAIN
POSITIVE SLOPE OF 1/4" /1'-0" MINIMUM.
NOTES
31,166 SF
22,448 SF
4,636 SF
16,477 SF
15,101 SF
3,073 SF
4,820 SF4,321 SF
7,994 SF
3,468 SF
4,485 SF
5,605 SF
5,605 SF
666 SF
6,831 SF
510 SF
1,033 SF
436 SF
436 SF
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
2 2 2
2 2
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
D E
M O
L
IT
IO
N
R O
O F
P L A
N
.1
A D
A U
G U
S T
O T
S E
G O
H
IG
H S
C H
O O
L
M E
M B
R A
N E
R E
-R O
O F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
KEYED NOTES - DEMOLITION
1 REMOVE DEBRIS AND CLEAN EXISTING EPDM MEMBRANE AND FLASHING. PREP FOR
NEW MEMBRANE TO BE APPLIED ON TOP OF EXISTING PREPARED MEMBRANE.
2 REMOVE DEBRIS AND CLEAN AREA SOURROUNDING LOCALIZED DEFICIENCIES. PREP
FOR MEMBRANE PATCH AT AREAS INDICATED.
3 REMOVE AND DISCARD EXISTING PRE-FINISHED METAL PARAPET SYSTEM. REPAIR
ANY ROTTED SUB STRUCTURE AND PREP FOR NEW PRE-FINISHED METAL PARAPET
SYSTEM.
1" = 20'-0"
ROOF DEMOLITION PLAN
ISSUED FOR DATE
31,166 SF
22,448 SF
4,636 SF
16,477 SF
15,101 SF
3,073 SF
4,820 SF4,321 SF
7,994 SF
3,468 SF
4,485 SF
5,605 SF
5,605 SF
666 SF
6,831 SF
510 SF
1,033 SF
436 SF
436 SF
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM7
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
1 1
116' - 8"
47' - 4" 67' - 0" 12' - 0" 37' - 8"
16' - 0"
' - 2
' - 8
' - 9
' - 7
223' - 10" 64' - 4" 94' - 8" 12' - 9"
36' - 11"
7' - 4"
36' - 0"
14' - 6"
43' - 2" 25' - 6"
5' - 4"
73' - 2"
106' - 10" 154' - 8" 58' - 0" 49' - 8"
94' - 8" 10' - 0"
41' - 0"
ROOF PLAN KEY
EX. TAPERED INSULATION
R.D
O.D
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
AHU OR RTU
ACCU
E.F
ROOF DRAIN - SEE PLUMBING DRAWINGS
OVERFLOW DRAIN - SEE PLUMBING DRAWINGS
ROOF TOP UNIT - SEE MECHANICAL DRAWINGS
CONDENSING UNIT - SEE MECHANICAL DRAWINGS
EXHAUST FAN / HOOD - SEE MECHANICAL DRAWINGS
1. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED OTHERWISE.
2. PROVIDE ROOFING MANUFACTURERS STANDARD ROOFING TERMINATION DETAILS AT ALL
PARAPETS, PRE-MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE PENETRATIONS, ETC.
3. PROVIDE CRICKETS AS REQUIRED AT ALL MECHANICAL UNITS, VENTS, ETC. TO MAINTAIN
POSITIVE SLOPE OF 1/4" /1'-0" MINIMUM.
NOTES
EX.R.D. EXISTING ROOF DRAIN - SEE PLUMBING DRAWINGS
GENERAL NOTES
1. NEW FLASHING, FASCIA, PRE-FINISHEDA ALUMINUM PARAPET COPING & GRAVEL STOP
REQUIRED IF EXISTING IS DAMAGED OR NOT ABLE TO REUSE EXISTING FLASHING,
FASCIA, OR PRE-FINSISHED ALUMINUM RARAPET COPING & GRAVEL STOP.
2. ROOF DETAILS REFER TO SHEET A112
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
P L A
N
.1
A
A U
G U
S T
O T
S E
G O
H
IG
H S
C H
O O
L
M E
M B
R A
N E
R E
-R O
O F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
1" = 20'-0"
ROOF PLAN
KEYED NOTES - NEW CONSTRUCTION - RE-ROOF
1 FULLY ADHERED FLEECEBACK EPDM INSTALLED DIRECTLY OVER EXISTING EPDM ROOF
SYSTEM WITH FASTENING ENHANCEMENTS AT THE PERIMETER.
TREATED NAILER(s) AS REQUIRED
ROOF DECK
EX. CANT STRIP
EX. 11/2" RIGID INSULATIONEX. PREFAB ROOF CURB
EX. COUNTER FLASHING WITH
APPROVED SEALING WASHER
AND FASTENER @ 6" O.C.
EX. ROOF MOUNTED EQUIPMENT
EX. TREATED 2x4 NAILER
M
IN
EX. LAP SEALANT
EX. MEMBRANE ROOF
NOTE:
FOR TYPICAL INSTANCES BELOW AHU's & RTU's
WHERE ROOF DECK RUNS CONTINUOUS,
PROVIDE NOISE ISOLATION REQUIREMENTS
USING (2) LAYERS OF 5/8" GYPSUM BOARD
(TOP & BOTTOM (4 TOTAL)) WITH (2) LAYERS OF
1 1/2" MINERAL FIBER INSULATION BETWEEN,
SEE MECH. DRAWINGS FOR ADDITIONAL INFO.
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE PERIMTER
AND CORNERS. RUN UP TO AND
UNDER FLASHING
3'-0" x 2'-6"
6" 2' - 6"
INSULATED METAL
ROOF HATCH
CAP FLASHING
EX. CANT STRIP
EX. LAP SEALANT
EX. MEMBRANE
ROOFING
EX. TAPERED
INSULATION
EX. PRECAST
PLANK, REFER TO
STRUCTURAL
SEE STRUCTURAL
FOR SUPPORTS
SNAP LATCH AND HANDLE
SAFETY POST BY ROOF
HATCH MANUFACTURER
LIFT MECHANISM
LADDER - SEE LADDER
DETAIL FOR ADDITIONAL
INFORMATION
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS AT
THE PERIMTER AND CORNERS. RUN
UP TO AND UNDER FLASHING
ROOF DECK
INSULATION
FLASHING
VENT PIPE
SEALANT
EX. ROOFING
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS
AT THE PERIMTER AND
CORNERS. RUN UP TO AND
UNDER FLASHING
CONTINUE
MEMBRANE INTO
ROOF DRAIN
ROOF DRAIN - REFER TO
PLUMBING DRAWINGS AND
SPEC SECTION 22 1423.
14 GAGE COATED STEEL
BEARING PAN FURNISHED
WITH ROOF DRAIN
CLAMPING RING FURNISHED
WITH ROOF DRAIN
1 1/2" METAL DECK REINFORCED
AT OPENING WITH 3" x 3" x 1/4"
STEEL ANGLES
EX. MEMBRANE ROOFING ON RIGID
INSULATION, TAPER TO DRAIN
/2
CENTER LINE OF VALLEY OF
FINISHED ROOF
1" THICK INSULATION
PER 22 0700.
PIPE INSULATION ON DRAIN
LEADERS PER 22 0700.
EPDM FULLY ADHERED ROOF
SYSTEM WITH ENHANCEMENTS AT
THE PERIMTER AND CORNERS.
RUN UP TO AND UNDER FLASHING EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE
SYSTEM RUN UP AND OVER
BUILT UP SYSTEM
EX. METAL PANEL WALL
CONSTRUCTION
/2
EX. 3" METAL ROOF DECK
EX. RIGID INSULATION
131' - 4 1/2"
EX. TAPERED INSULATION
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. CAST STONE CAP
EX. CAST STONE
EX. 1-1/2" METAL DECK
EX. RIGD INSULATION
EX. EPDM ROOF MEMBRANE SYSTEM
EX. CMU WALL CONSTRUCTION
EX. BRICK WALL CONSTRUCTION
TWO PIECE COUNTER FLASHING
(MATCH EX. STYLE AND COLOR)
RIGID FLASHING (MATCH
EX. STYLE AND COLOR)
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP TO
AND UNDER COUNTER FLASHING
RIGID FLASHING
EX. TAPERED RIGD INSULATION
/2
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
EX. EPDM ROOF MEMBRANE
SYSTEM
EX. TAPERED RIGID
INSULATION
EX. RIGID INSULATION
EX. 1-1/2" METAL DECK
EX. CMU WALL CONSTRUCTION
EX. BRICK WALL CONSTRUCTION
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF
MEMBRANE SYSTEM RUN
UP AND OVER PARAPET
TWO PIECE COUNTER FLASHING
(MATCH EX. STYLE AND COLOR)
RIGID FLASHING
EX. EPDM ROOF MEMBRANE SYSTEM
EX. TAPERED RIGID INSULATION
EX. RIGID INSULATION
EX. 1-1/2" METAL DECK
EX. CMU WALL CONSTRUCTION
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP TO
AND UNDER COUNTER FLASHING
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
/4
136' - 8"
132' - 0"
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE
SYSTEM RUN UP AND OVER
BUILT UP SYSTEM
EX. CMU WALL CONSTRUCTION
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. BRICK WALL CONSTRUCTION
/2
EX. 1-1/2" METAL ROOF DECK
EX. RIGID INSULATION
/2
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE
SYSTEM RUN UP AND OVER
BUILT UP SYSTEM
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. ALUM. CURTAINWALL
CONSTRUCTION
EX. 3" METAL ROOF DECK
EX. RIGID INSULATION
EX. TAPERED INSULATION6
/2
132' - 0"
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
EX. BRICK WALL CONSTRUCTION
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE
SYSTEM RUN UP AND OVER
PARAPET
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
/2
EX. CMU WALL CONSTRUCTION
EX. 3" ROOF DECK
EX. RIGID INSULATION
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE
SYSTEM RUN UP AND OVER
BUILT UP SYSTEM
EX. CMU WALL CONSTRUCTION
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. METAL PANEL WALL
CONSTRUCTION
/2
EX. 3" METAL ROOF DECK
EX. RIGID INSULATION
130' - 0"
EX. 2X4 P.T. NAILERS
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. EPDM ROOF MEMBRANE
SYSTEM
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET
EX. RIGID INSULATION
EX. 3" METAL DECK
EX. CMU WALL CONSTRUCTION
EX. 1-1/2" METAL DECK
EX. RIGID INSULATION
EX. EPDM ROOF
MEMBRANE SYSTEM
EX. BRICK WALL CONSTRUCTION
EX. 2X6 P.T. NAILERS
PRE-FINISHED ALUMINUM
FASCIA WITH GRAVEL STOP
AND DRIP EDGE (MATCH EX.
STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE
SYSTEM RUN UP AND OVER
PARAPET
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. INSULATED
TRANSLUCENT PANEL
CONSTRUCTION
EX. 3" METAL ROOF DECK
EX. RIGID INSULATION
/2
EX. 2X4 P.T. NAILERS
EX. 1/2" P.T. PLYWOOD
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. 2X4 P.T. NAILERS
WITH CHAMFER
PRE-FINISHED ALUMINUM FASCIA
WITH GRAVEL STOP AND DRIP EDGE
(MATCH EX. STYLE AND COLOR)
EX. EPDM ROOF MEMBRANE SYSTEM
RUN UP AND OVER PARAPET
EX. CMU WALL CONSTRUCTION
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. BRICK WALL
CONSTRUCTION
/2
EX. 1-1/2" METAL ROOF DECK
EX. RIGID INSULATION
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET AND OVER EX.
PRE-FINISHED FASCIA
EX. EPDM ROOF MEMBRANE SYSTEM
RUN UP AND OVER PARAPET
124' - 0"
EX. 2X4 P.T. NAILERS
EX. 3/4" P.T. PLYWOOD TOP
AND BOTTOM OF ASSEMBLY
WITH CHAMFER
EX. EPDM ROOF MEMBRANE
SYSTEM
EPDM FULLY ADHERED ROOF SYSTEM
WITH ENHANCEMENTS AT THE
PERIMETER AND CORNERS. RUN UP
AND OVER PARAPET
EX. RIGID INSULATION
EX. 1-1/2" METAL DECK
EX. CMU WALL CONSTRUCTION
EX. 3" METAL DECK
EX. RIGID INSULATION
EX. EPDM ROOF MEMBRANE
SYSTEM
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
R O
O F
D E
T A
IL
S
.1
A
A U
G U
S T
O T
S E
G O
H
IG
H S
C H
O O
L
M E
M B
R A
N E
R E
-R O
O F
O ts e g o M ic h ig a n
O T
S E
G O
P U
B L
IC
S C
H O
O L S
1 1/2" = 1'-0"A 112
1 TYPICAL ROOF CURB
1 1/2" = 1'-0"A 112
2 TYPICAL ROOF HATCH
1 1/2" = 1'-0"A 112
3 TYPICAL ROOF PENETRATION
1 1/2" = 1'-0"A 112
4 TYPICAL ROOF DRAIN DETAIL
1 1/2" = 1'-0"A 112
5 ROOF DETAIL
1 1/2" = 1'-0"A 112
6 ROOF DETAIL
1 1/2" = 1'-0"A 112
10 ROOF DETAIL
1 1/2" = 1'-0"A 112
7 ROOF DETAIL
1 1/2" = 1'-0"A 112
8 ROOF DETAIL
1 1/2" = 1'-0"A 112
9 ROOF DETAIL
1 1/2" = 1'-0"A 112
11 ROOF DETAIL
1 1/2" = 1'-0"A 112
12 ROOF DETAIL
1 1/2" = 1'-0"A 112
13 ROOF DETAIL
1 1/2" = 1'-0"A 112
14 ROOF DETAIL
1 1/2" = 1'-0"A 112
15 ROOF DETAIL
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS WHICH
ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS AND
BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY AND ALL
DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
ROOF PLAN KEY
OUTLINE OF EXISTING ROOF SYSTEM
R.D
O.D
ROOF SLOPE DUE TO TAPERED INSULATION OR
SLOPED STRUCTURE - REFER TO STRUCTURAL DRAWINGS
AHU OR RTU
ACCU
E.F
ROOF DRAIN - SEE PLUMBING DRAWINGS
OVERFLOW DRAIN - SEE PLUMBING DRAWINGS
ROOF TOP UNIT - SEE MECHANICAL DRAWINGS
CONDENSING UNIT - SEE MECHANICAL DRAWINGS
EXHAUST FAN / HOOD - SEE MECHANICAL DRAWINGS
1. TYPICAL ROOF SLOPE 1/4" / 1'-0" UNLESS NOTED OTHERWISE.
2. PROVIDE ROOFING MANUFACTURERS STANDARD ROOFING TERMINATION DETAILS AT ALL
PARAPETS, PRE-MANUFACTURED ROOF EDGE SYSTEMS, CURBS, PIPE PENETRATIONS, ETC.
3. PROVIDE CRICKETS AS REQUIRED AT ALL MECHANICAL UNITS, VENTS, ETC. TO MAINTAIN
POSITIVE SLOPE OF 1/4" /1'-0" MINIMUM.
NOTES
31,166 SF
22,448 SF
4,636 SF
16,477 SF
15,101 SF
3,073 SF
4,820 SF4,321 SF
7,994 SF
3,468 SF
4,485 SF
5,605 SF
5,605 SF
666 SF
6,831 SF
510 SF
1,033 SF
436 SF
436 SF
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
2 2 2
2 2
E a s t K a la m a z o o A v e n u e S u it e
K a la m a z o o M ic h ig a n
-5
.3
.6
P H
O
.3
.6
F A
X
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
E a s t
F u lt o n S tr e e t, S u it e
G ra n d R a p id s M ic h ig a n
.4
.9
P H
O N
E
.4
.5
F A
X
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
D E
M O
L
IT
IO
N
R O
O F
P L A
N
.1
A D
A U
G U
S T
O T
S E
G O
H
IG
H S
C H
O O
L
L
IQ
U
ID
A P
P L
IE
D R
E -R
O O
F
O s te g o M ic h ig a n
O S
T E
G O
P U
B L
IC
S C
H O
O L S
KEYED NOTES - DEMOLITION
1 REMOVE DEBRIS AND CLEAN EXISTING EPDM MEMBRANE AND FLASHING. PREP FOR
NEW MEMBRANE TO BE APPLIED ON TOP OF EXISTING PREPARED MEMBRANE.
2 REMOVE DEBRIS AND CLEAN AREA SOURROUNDING LOCALIZED DEFICIENCIES. PREP
FOR MEMBRANE PATCH AT AREAS INDICATED.
1" = 20'-0"
ROOF DEMOLITION PLAN
31,166 SF
22,448 SF
4,636 SF
16,477 SF
15,101 SF
3,073 SF
4,820 SF4,321 SF
7,994 SF
3,468 SF
4,485 SF
5,605 SF
5,605 SF
666 SF
6,831 SF
510 SF
1,033 SF
436 SF
436 SF
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D. EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.
EX.R.D.EX.R.D.
EX.R.D.
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
A 112
SIM
A 112
SIM
A 112
A 112
SIM
A 112
1 1
ROOF PLAN KEY
EX.…