This document is a specification for the annual fire protection equipment inspection and servicing at the Halawa Correctional Facility (HCF) in Hawaii. It covers the period from March 1, 2019 to February 29, 2020. The scope of work includes visual and physical inspection, weight (heft), tagging, and sealing of 295 dry chemical fire extinguishers, 7 carbon dioxide fire extinguishers, inspection and testing of 21 automatic sprinkler risers, 8 fire hydrants, 4 dry standpipes, and 35 fire hoses. The work also includes certifying the equipment and providing written reports. The bid closes on Wednesday, February 20, 2019 at 2:00 P.M., and all bids must be posted on HIePRO by the deadline. No faxes, telephone, email or hand delivered bids will be accepted.
The contract value is not specified in the document. The contract is for the Hawaii Department of Public Safety, Corrections Division, Halawa Correctional Facility, located in Aiea, Hawaii. The jurisdiction is Honolulu County. No further details are provided regarding pricing terms, set asides, incumbents, funding requirements or sources, or any other salient information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 103D-1 General Conditions.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HALAWA CORRECTIONAL FACILITY (HCF)
ANNUAL FIRE PROTECTION EQUIPMENT INSPECTION AND SERVICING
PERIOD: MARCH 1, 2019 to FEBRUARY 29, 2020
AMOUNT DESCRIPTION
295 Each Fire Extinguishers, Dry Chemical, ABC, 10 lbs.
ANNUAL MAINTENANCE - Visual and physical inspection of cylinders; weight (heft), tag and seal cylinders; certify with tags and provide written reports.
7 Each Fire Extinguishers, Carbon Dioxide, CO2, 10 lbs.
ANNUAL MAINTENANCE - Visual and physical inspection of cylinders; weight (heft), tag and seal cylinders; certify with tags and provide written reports. HYDROSTATIC TESTING – Inspection, servicing and testing of cylinders; weight (heft), tag and seal cylinders; certify with tags and provide written reports.
21 Each Automatic Sprinkler Risers (Wet) and Fire Department Connections ANNUAL MAINTENANCE - Inspection, servicing and testing of valves and associated parts to ensure proper operation and assurance of good condition; activate tamper switches to send and receive signal at panel; flow from inspector’s test valve to examine alarm bell response; visual check of sprinkler piping; walk through entire location to visually inspect heads and ensure proper coverage; air pressure test Fire Department connections; open main drain and record residual pressure; certify with tags and provide written reports.
8 Each Fire Hydrants ANNUAL MAINTENANCE - Inspection, servicing and testing of hydrants, two at a time to ensure proper operation and assurance of good condition; open each hydrant unit to ensure all foreign material has been cleared, record consumption rate, pivot reading, static and residual GPM readings; certify with tags and provide written reports.
4 Each Dry Stand Pipes and Fire Department Connections ANNUAL MAINTENANCE – Visual and physical inspection of dry stand pipes; test for sway bracing, hangers and corrosion to ensure that the system is in proper working condition; perform pressure test, air tests, hydrostatic tests, flow tests, gauge tests, onsite water supply test, air pressure test; validate Fire Department connections; certify with tags and provide written reports.
35 Each Fire Hoses and Fire Department Connections ANNUAL MAINTENANCE – Inspection, servicing and testing of valves and associated parts to ensure proper operation and assurance of good condition; validate Fire Department connections; certify with tags and provide written reports.
Note: Installed, certified and tagged February 2016 by National Fire Protection
BID CLOSES: WEDNESDAY, FEBRUARY 20, 2019 @ 2:00 P.M.