2018-03-405 Drawings.pdf
PDF 16 MB Posted
- Attached to
- Veguita Healthcare Center
- Solicitation number
- 2018-03-405
- Issued by
- Valencia County, New Mexico
About this file
The documents are architectural, mechanical, electrical, and plumbing design drawings and specifications for the Veguita Healthcare Center, a new outpatient diagnostic and treatment facility located at 1 Salomon Griego Drive in Veguita, New Mexico 87062. The project is being developed by Socorro County and involves constructing a 1,499 square foot healthcare facility that will include various medical spaces such as exam rooms, treatment rooms, a nurse station, reception area, waiting room, bathrooms, clean and soiled supply rooms, a janitor room, mechanical room, and vestibule. The design drawings, dated March 14, 2014, were prepared by Lee Gamelsky Architects and include comprehensive plans for architectural, structural, mechanical, electrical, and plumbing systems.
The project specifications indicate the facility will be fully equipped and furnished to create a turnkey healthcare office capable of providing basic medical services. The design emphasizes compliance with New Mexico Construction Code specifications and ADA requirements. The mechanical and electrical systems are designed with energy efficiency in mind, including a rooftop HVAC unit (RTU-1), split system cooling unit, electric unit heater, and carefully planned electrical distribution. The project appears to be funded through local government resources, with mechanical and electrical systems sized appropriately for a small healthcare clinic. The drawings provide detailed specifications for everything from building structure and mechanical systems to electrical panel layouts and plumbing infrastructure, ensuring a comprehensive and integrated design approach.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2018-03-405 Project Manual.pdf | ||
| 2018-03-405 Addendum 2.pdf | ||
| 2018-03-405 Addendum 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLG CEILING (OR COOLING)
ENTERING AIR TEMPERATUREEAT
EA EXHAUST AIR
CONN
CO
DHR
CONNECT
CLEANOUT
DOMESTIC HOT WATER RECIRC
BELOW FINISHED GRADE
CUBIC FEET PER MINUTE (AIR FLOW RATE)
BOTTOM OF PIPE FROM FINISHED FLOOR
CFM
BOP
BFG
ABOVE FINISHED GRADEAFG
AFF ABOVE FINISHED FLOOR
ENTERING WATER TEMPERATUREEWT
OSA OUTSIDE AIR
UNLESS NOTED OTHERWISE
TYP
UNO
TYPICAL
OPPOSED BLADE VOLUME DAMPER
OC
OBD
NIC
ON CENTER
NOT IN CONTRACT
LEAVING AIR TEMPERATURE
LEAVING WATER TEMPERATURE
LAT
LWT
FBO FURNISHED BY OWNER
EXH EXHAUST
PLAN ABBREVIATIONS
(N) NEW
COTG CLEANOUT TO GRADE
GPM GALLONS PER MINUTE (WATER FLOW RATE)
RA RETURN AIR
SA SUPPLY AIR
WITHW/
WALL CLEANOUTWCO
FCO FLOOR CLEANOUT
BACK DRAFT DAMPERBDD
90° ELBOW DOWN (ROUND DUCT ONLY)
ROUND 90° ELBOW UP (ROUND DUCT ONLY)
OFFSET TO CHANGE ELEVATION
(AT 30° WHEN POSSIBLE)
D = DROP R = RISE
ROUND RADIUS ELBOW
90° STRAIGHT TEE
90° CONICAL TEE
45° BRANCH
45° CONICAL TEE
SIZE OR SHAPE TRANSITION
ROUND FLEXIBLE DUCT
90° ELBOW UP (NEGATIVE PRESSURE)
90° ELBOW UP (POSITIVE PRESSURE)
AHU
AS
B
CH
CC
CT
CV
DEF
EBH
ECU
EF
F
HC
HX
AIR HANDLING UNIT
AIR SEPARATOR
BOILER (HOT WATER)
CHILLER
COILING COIL
COOLING TOWER
CONSTANT VOLUME BOX
DISHWASHER EXHAUST FAN
ELECTRIC BASEBOARD HEATER
EVAPORATIVE COOLING UNIT
EXHAUST FAN
FURNACE
FAN COIL
FAN POWERED BOX
HEATING COIL
HEAT EXCHANGER
FC
FP
HUMIDIFIER
KITCHEN EXHAUST FAN
RETURN (OR RELIEF) AIR FAN
SUPPLY FAN
VARIABLE VOLUME BOX
VARIABLE VOLUME BOX W/ REHEAT
H
KEF
RF
SF
VV
VR
UNIT HEATERUH
EWH ELECTRIC WATER HEATER
CUH CABINET UNIT HEATER
GLYCOL FEEDERGF
WATER HEATERWH
PUMP (SEE PIPING LEGEND FOR DETAILS)P
MIXING VALVEMV
THERMOSTATIC MIXING VALVETMV
ET EXPANSION TANK
AUTOMATICAUTO
ABOVEABV
CONC CONCRETE
COND CONDENSATE
(E) EXISTING
FIRE DAMPERFD
COMBINATION FIRE/SMOKE DAMPERFSD
KW KILOWATTS
MOTOR OPERATED DAMPERMOD
TRANSFERXFR
T.A. THROW-AWAY
EQUIPMENT ABBREVIATIONS
DC DUCT COIL
D D
DW(OR CW) DOMESTIC WATER
DHW DOMESTIC HOT WATER
DN DOWN
90° RADIUS ELBOW
90° RADIUS ELBOW W/TURNING VANES
SQUARE DUCT SPLIT
ROUND DUCT SPLIT
SPLIT BRANCH TAKE-OFF
WITH SQUARE ELBOW &
SPLITTER DAMPER
SPLIT BRANCH TAKE-OFF
WITH RADIUS ELBOW &
SPLITTER DAMPER
POSITIVE PRESSURE RISER,
TYPICALLY SUPPLY.
NEGATIVE PRESSURE RISER,
TYPICALLY RETURN, EXHAUST OR
OUTSIDE AIR.
90° ELBOW DN (NEGATIVE PRESSURE)
90° ELBOW DN (POSITIVE PRESSURE)
F/S COMBINATION FIRE AND SMOKE DAMPER F/S
FIRE DAMPER
MOTOR OPERATED DAMPER (MOD)
MANUAL VOLUME DAMPER, SINGLE BLADE
DAMPER (SBD) FOR ROUND OR <10" TALL,
OPPOSED BLADE DAMPER (OBD) >10" TALL.
BACKDRAFT DAMPERBDD BDD
SMOKE DAMPER
SMOKE DETECTOR
DUCT SIZE: FIRST NUMBER IS PLAN WIDTH,
SECOND NUMBER IS DEPTH.
24x36 24x36
SNOWMELT SUPPLY
SNOWMELT RETURN
HEATING WATER SUPPLY (HIGH TEMP)
HEATING WATER RETURN (HIGH TEMP)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER SUPPLY
CONDENSER RETURN
NATURAL GAS
MEDIUM PRESSURE GAS
HIGH PRESSURE STEAM SUPPLY
HP CONDENSATE RETURN
LOW PRESSURE STEAM SUPPLY
LP CONDENSATE RETURN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DOMESTIC WATER (DW)
DOMESTIC HOT WATER (DHW)
DHW RECIRCULATION (DHR)
FIRE LINE
PRESSURIZED WASTE
PLUMBING VENT PIPE
WASTE PIPE
ACID WASTE PIPE
STORM DRAIN PIPE
STORM DRAIN OVERFLOW
COMPRESSED AIR PIPE
GREASE WASTE PIPE
ACID VENT PIPE
LIQUID PROPANE GAS
SECONDARY DRAIN
SAND AND OIL WASTE
FLOOR COOLING SUPPLY
FLOOR COOLING RETURN
PIPING DESIGNATIONS
FIRE RISER
DIAGRAM CONTINUATION REFERENCE
PLUMBING RISER
HEATING WATER RISER
THERMOSTAT
HVAC RISER
POINT OF DISCONNECTION
POINT OF NEW CONNECTION
SECTION CUT LETTER./
SHEET SHOWN ON.
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CONTROL PANEL/RADIANT MANIFOLD
DUCT STATIC PRESSURE SENSOR
ROOM PRESSURE SENSOR
HUMIDISTAT
REMOTE TEMPERATURE SENSOR
EMERGENCY POWER OFF SWITCH
PLAN SYMBOLS
MANUFACTURERMFG
BUILDINGBLDG
MAKE-UP AIR UNITMAU DWR DOMESTIC HOT WATER RECIRC
OA OUTSIDE AIR
DUCTWORK LEGEND
DIAMETERØ
SP STATIC PRESSURE
HP HORSEPOWER
1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS
ON LEGEND SHEET ARE NOT NECESSARILY USED ON
THIS PROJECT.
2. THIS DRAWING SET CONSISTS OF DATA GENERATED, IN
PART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES
AND NOTATION CONVENTIONS OCCURRING IN THIS
DRAWING SET ARE NECESSARILY DEFINED ON THESE
LEGENDS. CONSULT THE ENGINEER IN THE EVENT
SYMBOLOGY OR NOTATION INTERPRETATION IS
REQUIRED.
NOTES
COMBUSTION AIRCA
HW HOT WATER
SS STAINLESS STEEL
ACCESS PANEL
SNOWMELT MANIFOLD
FCT FOR CONTINUATION
PRESSURE REDUCING VALVE
FLOW SWITCH
SHOCK ABSORBER
HOSE BIBB
STRAINER W/ BLOW-OFF VALVE
ROOF DRAIN
SAFETY RELIEF VALVE
FLOOR DRAIN
FLOOR SINK
HORIZONTAL CLEANOUT
VACUUM BREAKER
VERTICAL CLEANOUT
PRESSURE GAUGE W/ PIG TAIL & COCK
THERMOMETER
PRESSURE - TEMP. TAP
AIR VENT
PIPE ANCHOR
FLEXIBLE CONNECTOR
PIPE EXPANSION JOINT
PIPE UNION
STEAM TRAP:
DOUBLE CHECK BACKFLOW PREVENTER
PUMP & EQUIPMENT CONNECTOR
WALL HYDRANT
TEMPERATURE CONTROL VALVE (2-WAY)
DRAIN VALVE W/ HOSE END
PLUG VALVE IN RISER
FLOW BALANCING VALVE
GATE OR GLOBE VALVE IN RISER
FLOW CONTROL VALVE
BALL VALVE
PLUG OR BALANCING VALVE
CHECK VALVE
GLOBE VALVE
BUTTERFLY VALVE
VENTURI/FLOW INDICATOR
PIPING SYMBOLS
TEMPERATURE CONTROL VALVE (3-WAY)
SOLENOID VALVE
S
TEMPERATURE CONTROLLER OR SENSOR
KITCHEN SINK W/ OR W/O DISPOSER
FIXTURE CONNECTION SCHEDULE
DISHWASHER ROUGH-IN
DISH MACHINE ROUGH-IN
BATHTUB / SHOWER
DRINKING FOUNTAIN / E.W.C.
BAR SINK
- 2"
2"
2"
2"
FIXTURE
WATER CLOSET (FLUSH TANK)
WATER CLOSET (FLUSH VALVE)
MOP SERVICE BASIN
URINAL (WASHDOWN)
URINAL (BLOWOUT)
SERVICE SINK
LAVATORY
HW CW WASTE VENT
1"
1"
3"
3"
2"
2"
4"
4"
2"
2"
2"
2"
NOTES:
1. SIZES SHOWN ARE MINIMUM PIPE SIZES TO A SINGLE FIXTURE. LARGER SIZES
MAY BE INDICATED ON PLANS WHERE REQUIRED.
2. MINIMUM DOMESTIC PIPE SIZE TO 2 OR MORE FIXTURES IS 3/4".
3. RE: MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR INDIRECT WASTE
SIZES.
4. WASTE & VENT SIZES SHOWN ABOVE APPLY TO INDIVIDUAL VENTING ONLY.
WHERE ALLOWED, INDIVIDUAL VENT CONNECTIONS MAY BE OMITTED OR SIZES
MAY VARY WHEN CIRCUIT VENTS, COMMON VENTS, WASTE STACK VENTS, WET
VENTS, OR COMBINATION DRAIN & VENT SYSTEMS ARE USED. PRIOR
APPROVAL FROM THE ENGINEER IS REQUIRED TO USE THESE ALTERNATIVE
VENTING METHODS.
5. PROVIDE TRAP PRIMER FOR ALL FLOOR DRAINS AND FLOOR SINKS NOT
LOCATED IN FOOD SERVICE AREAS.
6. MINIMUM SIZE FOR W&V PIPING BENEATH SLAB IS 2".
7. ALL FIXTURES LISTED ARE NOT NECESSARILY USED ON THIS PROJECT.
8. REFER TO APPLIANCE SCHEDULES (BY OTHERS) FOR ADDITIONAL PLUMBING
FIXTURE CONNECTIONS SUCH AS INST-HOTS, COFFEE MAKERS, AND GARBAGE
DISPOSALS.
9. PROVIDE ICE MAKER BOX ROUGH IN W/ 1
2"CW CONNECTION FOR ALL
REFRIGERATOR LOCATIONS.
ABBREV.
WCT
WC
UR
UR
LAV
SS
MSB
DF
KS
SH
DM
DW
BS
FLOOR SINK
FLOOR DRAIN
TROUGH DRAIN
FS
FD
TD
3" 2"
2"
3" 2"
HAND SINK HS
CLOTHES WASHER ROUGH-IN 2"CW
WORK SINK WS 2"
90° ELBOW UP
90° ELBOW DN
TEE UP
TEE DOWN
URINAL (WATERLESS) - 2"UR
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
PROPANE GAS
HEATING WATER SUPPLY (LOW TEMP)
HEATING WATER RETURN (LOW TEMP)
SOLAR HEATING WATER SUPPLY
SOLAR HEATING WATER RETURN
GROUND LOOP SUPPLY
GROUND LOOP RETURN
GROUND WATER SUPPLY
GROUND WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
HYDRONIC PIPING
PLUMBING PIPING
PERFORATED DRAIN PIPE
SOLID DRAIN PIPE
FUEL OIL SUPPLY
FUEL OIL RETURN
GLYCOL FEED
GREASE VENT
DECK/ROOF DRAIN ABOVE
COMMONC
NC NORMALLY CLOSED
N0 NORMALLY OPEN
GC GENERAL CONTRACTOR
MECHANICAL CONTRACTORMC
EC ELECTRICAL CONTRACTOR
CONTROLS CONTRACTORCC
AAV AIR ADMITTANCE VALVE
BUILDING CONTROL SYSTEMBCS
CONTINUATION DESIGN BUILD CDBBC BY CONTRACTOR
CIP CAST IN PLACE
CONTR'R CONTRACTOR
LINEAR FOOTLF
NEC NATIONAL ELECTRIC CODE
REQ'D REQUIRED
REQ'MTS REQUIREMENTS
SF SQUARE FOOT (FEET)
STORAGE TANKST
BT BUFFER TANK
BB BASE BOARD
SNOWMELT AREASA
RADIANT ZONERZ
NON-SOFTENED DOMESTIC WATER
MEDIUM PRESSURE STEAM SUPPLY
MP CONDENSATE RETURN
FUEL OIL VENT
FUEL OIL FILL
HOSE BIB HB -- -
SHUT OFF (BALL, GATE, BUTTERFLY)
PUMPED CONDENSATE
STEAM TRAP TEST CHAMBER
ILO IN LIEU OF
VENT THRU ROOFVTR
FT-FLOAT & THERMOSTATIC
TD-THERMODYNAMIC
IB-INVERTED BUCKET
TS-THERMOSTATIC
BP-BALANCED PRESSURE
BETWEENB/N
CP CIRC PUMP
HP HEAT PUMP
MOTOR CONTROL CENTERMCC
GHX GROUND HEAT EXCHANGER
STEAM & CONDENSATE PIPING
GEOTHERMAL (OR GROUND) LOOP SUPPLY
GEOTHERMAL (OR GROUND) LOOP RETURN
HEATING WATER RETURN (HEAT PUMP)
HEATING WATER RETURN (HEAT PUMP)
CLOSED CONDENSER SUPPLY
CLOSED CONDENSER RETURN
SUMP BASINSB
WITH REGARD TOWRT
WATER COOLEDW/C
RE: REFER TO:
PROPANE DRAIN
ERU ENERGY RECOVERY UNIT
FIRE ALARM CONTROL PANELFACP
PD
CCR
CCS
HWR(HP)
HWS(HP)
GLR
GLS
PC
FOF
FOV
MPR
MPS
FCR
FCS
GV
DS
D
FOR
FOS
GF
HWR
HWS
GWR
GWS
GLR
GLS
SHWR
SHWS
HWR(LT)
HWS(LT)
HWR(HT)
HWS(HT)
PG
140°
SMS
NS
SO
SD
LPG
LPS
LPR
HPR
HPS
CA
ST(OF)
ST
GW
AW
AV
V
W
PW
F
RS
RL
MG
G
CR
CS
CHR
CHS
SMR
SDSD
TC
FS
W H
H B
SP
CO2
EPO
P
CO
H
S
P
T
3/4"3/4"
3/4"3/4"
3/4" 3/4"
3/4"3/4"
3/4"
FFI FOR FURTHER INFORMATION
MANUAL VOLUME DAMPER MVD
C-OR-
'*' ISSUED FOR INFORMATION ONLY
' ' NOT PART OF SET
' ' ISSUED AS PART OF A SET
ISSUE LOG KEY:
D A
TE
ISSUE LOG
MECHANICAL SHEET INDEX
TITLE
MECHANICAL / PLUMBING COVER SHEET
FO
R
PE
RM
IT
/1
4/
AIR DEVICE DESIGNATION KEY
SIZE (INCHES) OR MINIMUM FREE
AREA REQUIRED IN SQUARE FEET
TYPE OF AIR DEVICE,
RE: GRD SCHEDULE.
# = AIR QUANTITY (CFM)
CA = COMB. AIR
OSA = OUTSIDE AIR
RET = RETURN
EXH = EXHAUST
XFR = TRANSFER
A
12x6
B
XFR
12x6
INDICATES AIR INLET DEVICE
CH - CHILLED WATER
DW - DOMESTIC WATER
HW - HEATING WATER
G - GAS PIPING
WV - WASTE AND/OR VENT
PR - PIPING RISER (MISC TYPES)
ST - STORM DRAIN
S2 - SECONDARY STORM DRAIN
RISER NUMBER
PIPING:
OA - OUTSIDE AIR
EX - EXHAUST AIR
RA - RETURN AIR
AIR SIDE:
DUCT/ PIPE RISER
DESIGNATION KEY
PR
NOTE: FOR STANDARD MODULE
SIZE REGISTERS, SIZE GIVEN
IS NECK SIZE. REFER TO
GRD SCHEDULE FOR MODULE
SIZE.
REFERENCE SAMPLE
SHEET NUMBER
DRAWING NUMBER OR DIAGRAM
LETTER
REFER TO:
FFI = FOR FURTHER INFORMATION
FCT = FOR CONTINUATION
MP-001
M-101 MECHANICAL HVAC FLOOR PLAN
MECHANICAL / PLUMBING SPECIFICATIONSMP-002
PLUMBING WATER/WASTE AND VENT FLOOR PLANSP-101
MP-501 MECHANICAL/PLUMBING DIAGRAMS
MP-601 MECHANICAL/PLUMBING SCHEDULES
PLUMBING SITE PLANPS-100
' ABOVE SEA LEVEL
PROJECT ALTITUDE
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
MP-001
MECHANICAL/PLUMBING
COVER SHEET
944900MP001.DWG
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO
COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR
ALL DIMENSIONS.
2. ALL SUBCONTRACTORS SHALL BE LICENSED, EXPERIENCED, AND
THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE
CONSTRUCTION INDUSTRY AND SHALL PERFORM IN A RESPONSIBLE
MANNER WITH ESTABLISHED CONSTRUCTION SEQUENCE, SHALL
RECOGNIZE THE PRIORITY OF THE CONSTRUCTION DOCUMENTS, AND
SHALL INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN
THE CONSTRUCTION DOCUMENTS ARE UNCLEAR OR INCONSISTENT.
3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME
CONTRACTOR OF DISCREPANCIES OR CONFLICTS IN THE CONSTRUCTION
DOCUMENTS FOUND DURING BIDDING AND/OR PRIOR TO PERFORMING THE
WORK.
4. EXAMINATION OF BIDDING DOCUMENTS.
A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY,
AND NOT LATER THAN SEVEN (7) DAYS PRIOR TO THE DATE OF RECEIPT
OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR
INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES,
AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY
DISCOVER. THE ARCHITECT WILL ISSUE ANY INTERPRETATION OR
CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION
OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL
RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY
OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES,
OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN
DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR
MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER
COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA
COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE
TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED
ABOVE.
B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY
INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE
CONTRACTOR OF HIS RESPONSIBILITIES. THE SIGNING OF THE
CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE
CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL
INTENT AND SCOPE OF THE CONSTRUCTION CONTRACT DRAWINGS
AND SPECIFICATIONS.
5. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED EQUIPMENT
OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS FOR THE
LISTED EQUIPMENT SHALL BE ALLOWED IN THE BASE BID.
A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON
THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS
LISTED ARE CONSIDERED GENERAL EQUIVALENTS ONLY.
B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS:
WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL
GENERAL EQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED,
COORDINATE CLEARANCE AND OTHER INTERFACE REQUIREMENTS
WITH MECHANICAL AND OTHER WORK.
1) PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR
SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF
DESIGN AND PROPERLY FITS IN THE AVAILABLE SPACE ALLOCATED
FOR THE BASIS OF DESIGN.
2) PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF
DESIGN PLUS ANY SPECIFIED OPTIONS.
3) BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT,
FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL
EQUIVALENTS OR SUBSTITUTIONS DO NOT CAUSE ACCESS,
SERVICE, OR OPERATIONAL DIFFICULTIES ANY GREATER THAT
WOULD BE ENCOUNTERED WITH THE BASE DESIGN.
6. INASMUCH AS DESIGN FOR REMODEL AND/OR REHABILITATION REQUIRES
THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS,
AND BECAUSE SOME OF THESE ASSUMPTIONS CANNOT BE VERIFIED
WITHOUT DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE
PORTIONS OF THE BUILDING, THE ENGINEER CANNOT ASSURE THE OWNER
OR THE CONTRACTOR THAT THE PROFESSIONAL CONSULTING SERVICES
HEREIN ENCOMPASS ALL CONTINGENCIES. FIELD COORDINATION DURING
CONSTRUCTION IS IMPERATIVE. MAKE REASONABLE ALLOWANCES FOR
UNSEEN CONDITIONS.
7. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS,
MATERIALS AND/OR EQUIPMENT SHALL BE IDENTIFIED BY THE
SUBCONTRACTOR WITH SUFFICIENT TIME TO ALLOW SELECTION,
PURCHASE, AND DELIVERY TO MAINTAIN CONSTRUCTION SCHEDULE.
8. VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND PIPING
PRIOR TO TRENCHING.
9. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE
STRUCTURE, BEAMS, AND COLUMNS, AND EXISTING EQUIPMENT.
10. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE
SATISFACTION OF THE ARCHITECT, OWNER, AND ENGINEER.
11. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS/HER WORK IN
CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND LIFE
SAFETY FEATURES AS REQUIRED BY LOCAL, STATE, OR NATIONAL
AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF
MODIFICATION OF HIS/HER WORK IS REQUIRED FOR COMPLIANCE.
12. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR EXCEED
THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE CURRENT
BUILDING CODE, UNIFORM MECHANICAL, UNIFORM PLUMBING, AND
NATIONAL ELECTRICAL CODES, MOST CURRENT NFPA, ALL LOCAL
ORDINANCES AND AMENDMENTS AND MANUFACTURER'S INSTALLATION
RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE PUBLICATIONS
EXISTS, THE MOST STRINGENT REQUIREMENT SHALL APPLY.
13. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS. PRIOR
TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES OF
COMPLETION.
14. WARRANTY THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND
WORKMANSHIP. THE WARRANTY SHALL BE FOR A PERIOD OF ONE YEAR
AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED
WITHOUT COST TO THE OWNER.
15. SUBMIT RECORD DOCUMENTS TO ARCHITECT. DOCUMENTS SHALL
INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS,
REROUTING, ETC.
16. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS
OPERATION PRIOR TO ACCEPTANCE BY THE OWNER.
17. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A
MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK
ARE DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT
NO ADDITIONAL COST TO OWNER.
18. ALL MATERIALS AND/OR EQUIPMENT SHALL BE HANDLED AND INSTALLED
AS PER MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.
19. SUBMIT ALL MECHANICAL DIVISION SHOP DRAWING AND PRODUCT DATA AT
ONE TIME. SUBMITTAL SHALL BE BOUND AND INDEXED IN A NEAT AND
ORDERLY MANNER. PARTIAL SUBMITTALS WILL BE REJECTED. SUBMITTALS
SHALL INCLUDE, BUT NOT BE LIMITED TO: EQUIPMENT, FIXTURES,
INSULATION, DIFFUSERS, PUMPS, FANS, PIPING, VALVES, CONTROLS, AND
FIRE PROTECTION.
20. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND/OR
EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE
ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
21. PROVIDE NECESSARY TRENCHING, BACKFILL, EXCAVATION, SUPPORTS,
SAWCUTTING AND PATCHING, CONCRETE, ETC., AS REQUIRED. BACKFILL
TRENCHES IN 6” LAYERS AND TO 90% COMPACTION AND PATCH TO MATCH
EXISTING GRADE.
22. TEMPORARY HEAT SHALL BE FURNISHED BY THE GENERAL CONTRACTOR.
USE OF THE PERMANENT HEATING SYSTEM WILL NOT BE ALLOWED.
23. FIRE STOPPING REQUIREMENT. PENETRATIONS THROUGH RATED WALLS
AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF
PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN
SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC
FOR FIRE STOPS ASTM-E-814. ACCEPTABLE MATERIALS INCLUDE: DOW
CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND
ELECTRICAL CABLE; 3M FIRE DAM 150 CAULK FOR BARE PIPE, METAL
CONDUIT, AND BUILDING CONSTRUCTION GAPS; 3M CP-25 CAULK AND
FS-195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR
CONDUIT, AND ELECTRICAL CABLE. SUBMIT UL LISTED APPLICATION DATA
FOR EACH TYPE OF PENETRATION ENCOUNTERED.
24. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL HAVE
ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE
ARCHITECTURAL DRAWINGS. IN THE ABSENCE OF ANY OTHER
REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING
VENTS IN BUILT-UP ROOFS, TALL CONE WITH EPDM BOOT FOR PIPE AND
CONDUIT IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF
PENETRATIONS IN ALL TYPES OF ROOF. INSTALLATION SHALL BE
WATERTIGHT.
25. ALL FLOOR DRAINS CONNECTED TO THE SEWER SYSTEM SHALL BE
EQUIPPED WITH ELASTOMERIC TRAP GUARDS. INSTALL IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS.
26. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL CEILING
PENETRATIONS AND AIR DEVICE LOCATIONS.
27. COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL,
AND INTERIOR DESIGN DRAWINGS PRIOR TO INSTALLATION.
28. VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE AVAILABLE.
29. MOUNT ALL STATS AT 48” A.F.F. IN “ACCESSIBLE” AREAS. COORDINATE
LOCATION WITH WALL FINISH, AND TO AVOID CASEWORK, FURNITURE,
DOOR SWINGS, HEAT SOURCES, AND EXTERIOR WALLS. NOTIFY ENGINEER
OF ANY CONFLICTS PRIOR TO BEGINNING THERMOSTAT INSTALLATION.
30. SUBMIT A WRITTEN BALANCE REPORT BY A NEBB OR AABC CERTIFIED
BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE IN
ACCORDANCE WITH NEBB OR AABC GUIDELINES FOR PROPORTIONAL
BALANCE. SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS
FOR REVIEW PRIOR TO BALANCING. MEASUREMENTS SHALL INCLUDE ALL
MOTOR AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS;
STATIC PRESSURE AT INLET AND OUTLET OF ALL PACKAGED EQUIPMENT,
FANS, COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY,
EXHAUST, RETURN, AND OUTSIDE AIR MAIN DUCTS, AT MINIMUM OUTSIDE
AIR, AND 100% (ECONOMIZER) OUTSIDE AIR; VELOCITY DISTRIBUTION
ACROSS THE FACE OF FILTERS; AIR INLET AND OUTLETS.
A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO
ADJUST FAN SPEED.
B. ADJUST FLOWS TO WITHIN 10% OF REQUIRED QUANTITY. WHERE
ROOM AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE
MAINTAINED AS SHOWN BY A DIFFERENTIAL OF SUPPLY AND
EXHAUST/RETURN OR BY NOTE, ADJUST SUPPLY TO WITHIN 10% AND
THEN ADJUST EXHAUST/RETURN TO PROVIDE THE INDICATED ROOM
PRESSURE. IF ACTUAL QUANTITY IS LESS THAN 90%, INVESTIGATE
CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER. SUBMITTAL OF
BALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT
EXPLANATION IS CAUSE FOR REJECTION OF REPORT.
C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY
REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES
SHALL BE RETAINED BY THE OWNER, ARCHITECT, AND ENGINEER.
32. DUCTWORK: (LOW VELOCITY)
A. FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE
RETARDANT POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM
LAYER OF FIBERGLASS INSULATION, HIGH-STRENGTH GALVANIZED
STEEL HELIX ENCAPSULATED IN REINFORCED “RIP STOP” ALUMINUM
LAMINATE INTERIOR CORE, UL LISTED AND LABELED, CLASS 1 AIR
DUCT. WORKING PRESSURE RATING: POS. 6”, NEC. 4”. FLEXMASTER
TYPE 5 OR EQUIVALENT. SUBMIT SAMPLES TO DETERMINE
EQUIVALENCE.
B. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS
CLOTH, 10” W.C. RATED.
C. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR 5
GORE ELBOWS. “SNAP-LOCK”, LONGITUDINAL SEAM DUCT, OR
ADJUSTABLE FITTINGS ARE ACCEPTABLE ON INDIVIDUAL
GRILLE/DIFFUSER RUNOUTS ONLY.
D. INSULATION:
1) EXTERNALLY WRAP ALL SUPPLY AIR DUCTS WITH FLEXIBLE GLASS
FIBER, ANSI/ASTM C612; 0.002 INCH FOIL SCRIM FACING.
2) INSULATION THICKNESS: 1 1/2" THICK, 0.75 LB/CUFT NOMINAL
DENSITY
E. DUCTWORK: G60 GALVANIZED SHEET STEEL; LOCK FORMING QUALITY;
CONSTRUCTED TO THE LATEST EDITION OF SMACNA “HVAC DUCT
CONSTRUCTION STANDARDS”; +/- 1” W.C. PRESSURE CLASSIFICATION,
SEAL CLASS “C”; WITH GALVANIZED STEEL FASTENERS, ANCHORS,
ANGLES, STRAPS, ETC.
F. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH
UNITED MCGILL “UNI-GRIP” UL LISTED, WATER BASED, NON-HARDENING,
ELASTIC SEALANT OR EQUIVALENT. TAPE NOT ALLOWED.
G. EXTERIOR DUCTWORK: PROVIDE EXTERIOR DUCTWORK TO THESE
SPECIFICATIONS WHERE EXPOSED TO WEATHER:
1) DUCTWORK SUPPORT MATERIALS: EXCEPT AS OTHERWISE
INDICATED, PROVIDE GALVANIZED STEEL FASTENERS, ANCHORS,
RODS, STRAPS, TRIM AND ANGLES FOR SUPPORT OF DUCTWORK.
PROVIDE EQUIPMENT SUPPORT RAIL TYPE OR EQUIVALENT ROOF
SYSTEM COMPATIBLE WEATHERPROOF INTERFACE AT ALL ROOF
SUPPORTS.
2) DUCT SEALING SYSTEM: ARMACELL ARMATUFF PLUS II SYSTEM.
WHITE WITH 10 YEAR MEMBRANE WARRANTY, 16 MIL LAMINATED
COVERING THAT IS UV RESISTANT.
3) CONSTRUCT AND SEAL DUCTS TO 3” STATIC PRESSURE
STANDARDS.
4) DO NOT LINE EXTERIOR DUCT. INSULATE SUPPLY AND RETURN
DUCT WITH TWO LAYERS OF 2” THICK CLOSED CELL ELASTOMERIC
INSULATION. STAGGER SEAMS AND JOINTS. PROVIDE FULL
ADHESIVE COAT ON DUCT SURFACE AND BETWEEN INSULATION
LAYERS. INSTALL PER MANUFACTURERS REQUIREMENTS.
5) INSTALL ALUMINUM, STUCCO EMBOSSED JACKET, 0.016 INCH THICK
OVER INSULATION MATERIAL.
33. PROVIDE ¼” GALVANIZED MESH SCREEN ON ALL COMBUSTION AIR DUCTS
OR OPENINGS, AND ALL OPEN END RETURN AND EXHAUST DUCTS.
34. ALL DUCTWORK DIMENSIONS ARE INSIDE FREE AREA DIMENSIONS.
35. DUCTWORK NOTES:
A. DIFFUSER NECK SIZE IS SAME AS FLEXIBLE DUCT SIZE.
B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE
MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO
1.5 DUCT WIDTH.
1) WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE
THROAT ELBOWS WITH SINGLE WIDTH (NON-AIRFOIL) TURNING
VANES.
2) FOR DUCT DEPTHS OF 36” OR LESS, PROVIDE MANUFACTURED
SINGLE WIDTH (NON-AIRFOIL) TURNING VANES, WITH SPACING IN
ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS
FOR “STANDARD SPACING”. USE NO TRAILING EDGES.
C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED SIX FEET IN LENGTH.
36. SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR
CLAMPS. NO PIPE TAPE OR STRAPPING ALLOWED. ALL HANGERS SHALL BE
SIZED FOR OD OF INSULATION, IF ANY. PROTECT INSULATED LINES WITH 20
GA SHEET METAL SHIELDS FOR PIPING 1-1/2” AND LESS. PROVIDE CALCIUM
SILICATE INSULATION INSERTS FOR ALL INSULATED PIPING 2” AND LARGER.
MAINTAIN VAPOR BARRIER ON ALL COLD LINES. ISOLATE BARE COPPER
LINES FROM HANGERS WITH VIBRASORB OR EQUIVALENT, COPPER COATED
HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT
ACCEPTABLE.
37. REFER TO PLUMBING FIXTURE CONNECTIONS SCHEDULE FOR PIPE SIZES
TO INDIVIDUAL PLUMBING FIXTURES.
38. PROVIDE SHOCK ARRESTERS AT ALL DOMESTIC HOT AND COLD WATER
BRANCHES SERVING FIXTURES AND EQUIPMENT WITH QUICK CLOSING
VALVES. SUCH FIXTURES AND EQUIPMENT INCLUDES FLUSH VALVE WATER
CLOSETS, DISHWASHERS, ICE MACHINES, AND CLOTHES WASHERS. SHOCK
ARRESTERS SHALL BE CONSTRUCTED WITH A PISTON IN A SEALED COPPER
TUBE CHAMBER, AND APPROVED FOR INSTALLATION WITHIN WALLS
WITHOUT ACCESS PANELS. SIOUX CHIEF OR EQUIVALENT. BELLOWS TYPE
NOT ACCEPTABLE. PROVIDE ACCESS PANELS FOR SERVICE &
MAINTENANCE.
39. DOMESTIC HOT AND COLD PIPING INSIDE BUILDING--BURIED LINES, TYPE “K”
SOFT ANNEALED COPPER WATER TUBE, SINGLE LENGTH TO AVOID
FITTINGS, (WROUGHT COPPER FITTINGS WHERE UNAVOIDABLE) AND 1100°F
SOLDER. NON-BURIED LINES, TYPE “L” HARD COPPER WATER TUBE,
WROUGHT COPPER FITTINGS AND NO LEAD 95-5 SOLDER.
40. COPPER PIPE VALVES AND SPECIALTIES
A. BALL VALVES - BRONZE, CLASS 125, 600 LB. W.O.G.
B. CHECK VALVES - BRONZE, CLASS 125, 200 LB. W.O.G.
C. BALANCING VALVES - 125 PSI W.P. FOR 250° FAHRENHEIT SERVICE
TIGHT SHUTOFF, TOUR AND ANDERSON STA, ARMSTRONG CBV,
GERAND, OR FLOWSET, BELL AND GOSSETT CIRCUIT SETTER.
D. DIRECT UNIONS: FURNISH AND INSTALL A DIELECTRIC UNION AT EACH
CONNECTION BETWEEN DISSIMILAR METALS.
41. MATERIALS; SOIL, WASTE, AND VENT PIPING (INSIDE BUILDING)
A. LINES BURIED BELOW GROUND--STANDARD WEIGHT, C.I. SOIL PIPE,
AND FITTINGS HUB AND SPIGOT WITH NEOPRENE GASKETS, OR NO
HUB WITH HEAVY DUTY 4-BAND 304 STAINLESS STEEL CLAMPS, HUSKEY
OR EQUIVALENT. SOLID-WALL PVC PIPE, SOCKET FITTINGS, SOLVENT
CEMENTED JOINTS ALSO ACCEPTABLE
B. LINES ABOVE GROUND--STANDARD WEIGHT, C.I. SOIL PIPE, AND
FITTINGS. HUB AND SPIGOT WITH NEOPRENE GASKETS, OR NO HUB
WITH 4-BAND CLAMPS. UP THROUGH 2-1/2” MAY BE DWV COPPER TUBE
WITH DWV FITTINGS AND 95-5 NO LEAD SOLDER. PVC PIPE AND
FITTINGS ARE NOT ACCEPTABLE FOR USE ABOVE GRADE.
42. INSULATE ALL NEW DOMESTIC COLD, HOT , AND HOT WATER
RECIRCULATION PIPING, HEATING AND CHILLED WATER PIPING WITH U.L.
APPROVED, WHITE, ALL SERVICE, GLASS FIBER, SNAP-ON, PIPE INSULATION.
INSULATE FITTINGS WITH GLASS FIBER BLANKET INSULATION AND
PREMOLDED P.V.C. COVERS. ALL MATERIALS SHALL HAVE A SMOKE
DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25
OR LESS. INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS.
VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH
“NON-BREATHING” MASTIC ON COLD PIPING. ALL RAW EDGES OF
INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC.
A. INSULATION THICKNESS:
1) DOMESTIC HOT WATER: ALL SIZES - 1”; RUNOUTS WITHIN INTERIOR
WALL TO FIXTURE - 1/2”.
2) DOMESTIC COLD WATER AND STORM: ALL SIZES - 1/2”.
43. EQUIPMENT LABELS: LABEL ALL PIPING AND EQUIPMENT. PROVIDE FULL
BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING. PROVIDE
ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND ATTACH WITH
STANDARD CHAIN OR S-HOOKS. PROVIDE ENGRAVED PLASTIC SIGN ON OR
NEAR SPECIFIED EQUIPMENT.
GENERAL NOTES:
A. BOOKS OF OPERATING AND MAINTENANCE INSTRUCTIONS SHALL BE PERSONALLY DELIVERED TO THE OWNER'S AUTHORIZED REPRESENTATIVE AND THE OWNER INSTRUCTED AS TO THEIR USE AND THE EQUIPMENT INVOLVED. (PROVIDE TWO BOOKS). ALSO, INSTRUCT THE OWNER'S PERSONNEL ON EACH VALVE.
B. THE BOOK SHALL CONTAIN, BUT NOT BE LIMITED TO, THE FOLLOWING GENERAL ITEMS:
1. SPARE PARTS LISTS FOR EACH PIECE OF EQUIPMENT.
2. OPERATING MANUALS FOR EACH PIECE OF EQUIPMENT AND CONTROL.
3. LUBRICATION CHARTS SHOWING TYPE OF LUBRICANT AND APPLICATION METHODS AND FREQUENCIES.
4. FILTER CLEANING OR REPLACEMENT SCHEDULE. (ON CONTRACTOR'S LETTERHEAD STATIONARY).
5. PREVENTIVE MAINTENANCE SCHEDULE FOR CHECKING ALL ITEMS SUCH AS BELT DRIVE, SAFETY
CONTROLS AND OIL AND REFRIGERANT CHARGES. CLEANING SCHEDULE OF ALL TRAPS, COILS, ETC.
(ON CONTRACTOR'S LETTERHEAD STATIONARY).
6. NORMAL OPERATING INSTRUCTIONS INCLUDING A SEQUENCE OF OPERATION FOR EACH SYSTEM. (ON
CONTRACTOR'S LETTERHEAD STATIONARY).
7. INSTRUCTIONS AS TO PROCEDURE TO BE FOLLOWED FOR ANY EMERGENCY SITUATION, SUCH AS
ALARMS OR SAFETY ITEMS BEING TRIPPED. (ON CONTRACTOR'S LETTERHEAD STATIONARY).
8. INSTRUCTIONS ON WHO TO CALL FOR SERVICE DURING GUARANTEE PERIOD. (ON CONTRACTOR'S
LETTERHEAD STATIONARY).
9. RECORD OF EQUIPMENT INSTALLED (COPY OF EACH SHOP DRAWING AS SET FORTH UNDER "SHOP
DRAWING" PARAGRAPH).
10. ALL WARRANTIES PROVIDED BY MANUFACTURERS ON THEIR EQUIPMENT THAT RUN LONGER THAN THE
ONE YEAR GUARANTEE BY THE CONTRACTOR.
C. BOOKS SHALL BE ARRANGED IN SEQUENCE TO MATCH THE EQUIPMENT SCHEDULES INCLUDED IN THE
SPECIFICATIONS.
D. PROVIDE RECORD DRAWINGS
E. APPROVAL WILL NOT BE GIVEN FOR FINAL PAYMENT UNTIL THE TESTS, BALANCING AND OPERATING
INSTRUCTION PORTIONS HAVE BEEN COMPLETED.
OPERATION AND MAINTENANCE INSTRUCTIONS
1. ALL REFRIGERATION, AND PACKAGED EQUIPMENT SHALL BE STARTED BY THE MANUFACTURER OR UNDER THE MANUFACTURER'S SUPERVISION. START-UP DATA SHALL BE RECORDED IN LOGS. COPIES OF START-UP LOGS SHALL BE FORWARDED TO MECHANICAL ENGINEER AND INCLUDED IN OPERATION AND MAINTENANCE
EQUIPMENT START-UP
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
MP-002
MECHANICAL/PLUMBING
SPECIFICATIONS
944900MP002.DWG
x x x x x x x x x x x x x x x x x x x
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E
E E x x
N 89° 48' 16" E
S
' 0 0"
W
S 89° 48' 16" W
0.
439.60'
0.
439.60'
S
' 0 0"
W
NEW SEPTIC FIELD
FUTURE
ADDITION
EXISTING SEPTIC FIELD
RELOCATE EXISTING
DRIVEWAY INTO SITE.
CLOSE THIS ROAD.
NEW DRIVEWAY
INTO SITE
LA PROMESA
ELEMENTARY SCHOOL
FIRE DEPARTMENT SUB
STATION
EXISTING SENIOR CENTER
EXISTING EXISTING
FUTURE PARKING
FU
TU
R E
PA
R
KI
N
G
SCALE:
PLUMBING SITE PLAN
1" = 20'-0"
NOTES:
X FLAG NOTES:
1. INSTALL FIRST STAGE (HIGH PRESSURE) REGULATOR ON PROPANE TANK. ROUTE
OUTLET TO LPG LINE AS SHOWN. BURY PIPE IN TRENCH PER CODE. LINE TO BE A
MINIMUM OF 18" BELOW GRADE.
2. ROUTE 4" WASTE FROM BUILDING SEWER TO NEW SEPTIC TANK/FIELD (22 DFU'S),
REFER TO SEPTIC SYSTEM NOTES.
3. CONNECT NEW DOMESTIC WATER PIPE INTO EXISTING WELL SYSTEM.
COORDINATE WITH OWNER FOR CONNECTION AND METERING REQUIREMENTS.
4. DOMESTIC WATER, WASTE AND PROPANE TO BUILDING. REFER TO PLUMBING
FLOOR PLAN FOR CONTINUATION.
5. REMOVE TREES AS NEEDED REFER TO ARCHITECTURAL.
6. 1,000 GALLON PROPANE TANK ON CONCRETE PAD. PROPANE TANK TO BE
PROVIDED BY OWNER OR LEASED BY OWNER. PROVIDER TO VERIFY
SITE/CAPACITY. INSTALL PER PROVIDER REQUIREMENTS.
7. 11/2" IRRIGATION LINE WITH VALVE IN BOX AND CAP.
FENCE ENCLOSURE
AND GATE
WELL HOUSE
FUTURE BUILDING
FUTURE PLAZA
EXISTING SEPTIC SYSTEM
RTU-1
CU-1
1. REFER TO MP-001 FOR SYMBOLS AND LEGENDS.
2. REFER TO MP-002 FOR GENERAL NOTES.
3. REFER TO MP-501 FOR DIAGRAMS.
4. REFER TO MP-601 FOR SCHEDULES.
4" W 1/2" LPG
1 1/2" CW
SEPTIC SYSTEM NOTES:
1. THE ON-SITE LIQUID WASTE SYSTEM SELECTION, SIZING, MATERIALS, AND
INSTALLATION SHALL CONFORM TO ALL REQUIREMENTS OF THE NEW MEXICO
ADMINISTRATIVE CODE (NMAC) 20.7.3 LIQUID WASTE DISPOSAL AND TREATMENT
AND ALL LOCAL COUNTY AND MUNICIPALITY CODES.
2. THE CONTRACTOR SHALL PAY FOR AND OBTAIN A NEW LIQUID WASTE PERMIT
ISSUED BY THE NEW MEXICO ENVIRONMENT DEPARTMENT BEFORE BUILDING OR
TRANSPORTING ANY PART OF THE SEPTIC SYSTEM.
3. THE CONTRACTOR IS RESPONSIBLE FOR ALL FEES AND PAPERWORK INVOLVED
WITH OBTAINING THE PERMIT INCLUDING BUT NOT LIMITED TO PROVIDING THE
FOLLOWING ITEMS: FLOOR PLANS AND DIMENSIONED PLOT PLANS, RECORDED
WARRANTY DEED, UNIFORM PROPERTY CODE, AND A SOIL ANALYSIS. A TEST
HOLE MAY ALSO BE REQUIRED IF THE BUILDING IS IN AN AREA WHERE IT IS
SUSPECTED THAT A HIGH WATER TABLE OR BEDROCK PROBLEMS EXIST. ALL
TESTING AND INSPECTION REQUIREMENTS OF THE PERMITTING PROCESS ARE
THE RESPONSIBILITY OF THE CONTRACTOR. SUBMIT ALL RECORDS OF
PERMITTING DESIGN AND PAPERWORK TO ENGINEER FOR REVIEW AND
APPROVAL.
4. THE ABSORPTION AREA OF A DISPOSAL FIELD OR SEEPAGE PIT IS TO BE
DETERMINED BY THE CONTRACTOR UPON COMPLETION AND EVALUATION OF
SOILS REPORT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EXACT
LOCATION OF SEPTIC SYSTEM AND COMPONENTS IN ACCORDANCE WITH
SETBACK AND CLEARANCE REQUIREMENTS IN TABLE 302.1 OF THE ABOVE
LISTED CODE.
5. ALL INSTALLATIONS MUST BE PERFORMED BY A LICENSED CONTRACTOR I.E.
MM1, MM-98, MS1, MS3. THE INSTALLATION MUST BE IN ACCORDANCE WITH
MANUFACTURER'S REQUIREMENTS AND RECEIVE A FINAL INSPECTION BEFORE IT
IS ACTIVATED.
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
PS-100
PLUMBING SITE PLAN
944900PS100.DWG
shanti Rectangle shanti Rectangle shanti Rectangle shanti Rectangle shanti Typewritten Text shanti Typewritten Text
PROVIDE AND INSTALL BY GENERAL CONTRACTOR.
1 FLAG NOTES:
NOTES:
1. REFER TO SITE FOR CONTINUATION.
2. INSTALL BALANCING VALVE.
3. ROUTE CONDENSATE DOWN IN WALL TO TAIL PIECE.
4. CONDENSATE PIPE ABOVE CEILING FROM AC. REFER TO MECHANICAL PLAN FOR
CONTINUATION.
5. WATER HEATER AND CIRCULATOR PUMP. REFER TO DIAGRAM FOR INSTALLATION
AND ACCESSORIES REQUIRED. REFER TO MECHANICAL PLAN FOR FLUE ROUTING.
ROUTE OUTLET OF T/P RELIEF VALVE TO EXTERIOR. PROVIDE DOWN TURNED
OUTLET.
6. ROUTE CW DOWN IN WALL. PROVIDE TAPS FOR BOTH WATER CLOSETS.
7. ROUTE CW/HW BACK TO BACK TO LAVATORIES.
8. DOMESTIC WATER ENTRANCE. REFER TO DIAGRAM.
9. ROUTE GAS PIPE THROUGH WALL TO WATER HEATER IN ROOM. SEAL
PENETRATION. PROVIDE SHUT OFF VALVE. REFER TO WATER HEATER DIAGRAM
FOR GAS PIPE CONTINUATION.
10. ROUTE 3/4" CW DOWN IN WALL TO HOSE BIB. MOUNT HOSE BIB 24" A.F.G.
11. PROVIDE PLASTER TRAP, JR SMITH #8710, OR EQUAL, ON OUTLET OF SINK. INSTALL
BELOW COUNTER.
12. RISE GAS PIPE UP FROM BELOW GRADE ROUTE GAS UP TO RTU. PROVIDE GAS
COCK, DIRT LEG FLEX CONNECTION AND UNION AT UNIT CONNECTION.
13. PROVIDE SHUT OFF VALVE IN PIPE UP FROM BELOW GRADE. INSTALL PRESSURE
REGULATOR ON PIPE AFTER SHUT OFF VALVE. BRANCH AS SHOWN ON PLANS,
DOWNSTREAM OF REGULATOR. SIZE REGULATOR FOR 200 MBH (APPX 80 CFH) GAS
DEMAND, 10 PSI TO 11 IN. W.C.
14. DROP GAS PIPE DOWN TO BELOW GRADE. ROUTE TO RTU AS SHOWN.
SCALE:1 PLUMBING WATER FLOOR PLAN
1/4" = 1'-0"
SCALE:2 PLUMBING WASTE AND VENT FLOOR PLAN
1/4" = 1'-0"
WH-1
1" HW
H B
1 1/4" CW
3/4" HW/CW
P4
P5
P1
P2
P3
P3
P3
P2
P1 P6
3/4" HW
P4
P5 P1
P2
P3
P3 P2
P1
DCOTG
COTG
COTG
WCO
2" VTR
P3
P3
1 1/2" V
2" VTR
4"
4"
2" 4"
1. REFER TO MP-001 AND MP-002 FOR LEGEND, AND SPECIFICATIONS.
2. REFER TO MP-501 FOR DIAGRAMS.
3. REFER TO MP-601 FOR SCHEDULES.
4. PROVIDE LINE SIZE ISOLATION VALVES ON ALL BRANCH PIPING.
WCO
3/4" D
2"
1 1/2" VTR
1 1/2" VTR
2" 4"
1 1/2"
4"2"
3"
P8
3/4" CW
3/4" HWC
3/4" HWC
3/4" HWC
3/4" CW
P3
3/4" HW
P7 10
3/4" CW
1 1/4" CW
CP-1 5
VESTIBULE
WAITING
RECEPTION
HALL
EXAM
TREATMENT
OFFICE
CLEAN
SUPPLY
DRUG ROOM
CL.SOILED
NURSE STATION UNISEX 1 UNISEX 2
JANITOR
VESTIBULE
WAITING
RECEPTION
HALL
EXAM
TREATMENT
OFFICE
CLEAN
SUPPLY DRUG ROOM
CL.SOILED
NURSE STATION
UNISEX 1
UNISEX 2
JANITOR
1 1/2"
2"
1/2" LPG
3/4" LPG
14 13
1/2" LPG
3"
RTU-1
CU-1
WCO
WCO
3/4" CW
H B
P7 10
3/4" CW
2"
1" CW
3/4" HW/CW
1" CW
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
P-101
PLUMBING WATER/WASTE AND VENT
FLOOR PLANS
944900P101.DWG
1 FLAG NOTES:
NOTES:
SCALE:1 MECHANICAL FLOOR PLAN
1/4" = 1'-0"
1. REFER TO MP-001 AND MP-002 FOR LEGEND, AND SPECIFICATIONS.
2. REFER TO MP-501 FOR DIAGRAMS.
3. REFER TO MP-601 FOR SCHEDULES.
4. PROVIDE TRANSFER DUCTS FROM EACH ROOM TO THE CENTRAL HALLWAY FOR
RETURN AIR TO RTU AS SHOWN. REFER TO DIAGRAM, MP-601 FOR CONSTRUCTION.
SIZE PER PLAN.
5. PROVIDE LOCKING BALANCING DAMPERS ON ALL BRANCH TAPS FROM MAINS.
x1
6" Ø
1. EXHAUST UP TO CAP ON ROOF.
2. CEILING MOUNTED EXHAUST FAN.
3. ROUTE SUPPLY AND RETURN DUCTWORK FROM GROUND MOUNTED A/C UNITS TO
WALL PENETRATION OUTSIDE WALL. INSULATE AND JACKET EXTERIOR DUCTWORK.
4. GROUND MOUNTED RTU-1 UNIT. REFER TO SCHEDULES FOR SIZING INFORMATION.
PROVISE 4" HOUSING KEEPING PAD UNDER MOUNTING CURB.
5. DUCT THROUGH WALL IN ONE WALL PENETRATION WITH EXTERIOR INSULATION AND
JACKET ENCLOSING BOTH DUCTS. REFER TO ARCHITECTURAL. FIELD COORDINATE
WALL OPENING.
6. REFRIGERANT PIPING UP ON WALL IN CONCEALMENT CHANNEL TO ABOVE CEILING
SPACE. ROUTE TO OUTDOOR CONDENSING UNIT IN MECHANICAL YARD.
7. ROUTE PUMPED CONDENSATE UP TO ABOVE CEILING. GRAVITY DRAIN TO NEAREST
TAIL PIECE. REFER TO PLUMBING FOR CONTINUATION.
8. ELECTRIC UNIT HEATER MOUNTED FROM WALL. SET THERMOSTAT FOR FREEZE
PROTECTION.
9. CONDENSING UNIT ON EQUIPMENT SUPPORTS. PROVIDE 4" HOUSEKEEPING PAD
BELOW MOUNTING FRAME.
10. RISE DUCTS UP IN WALL. TRANSITION ABOVE CEILING TO DIMENSIONS SHOWN.
11. AIR CONDITIONER ON WALL ABOVE DOOR. PROVIDE T-STAT ON WALL BY DOOR. FIELD
COORDINATE FINAL LOCATION.
12. FLUE AND COMBUSTION AIR TO WATER HEATER. ROUTE TO ROOF. TERMINATE WITH
CONCENTRIC VENT KIT. COORDINATE WITH ROOFING CONTRACTOR FOR FLASHING
REQUIREMENTS. PROVIDE LATEX PAINT ON CONCENTRIC VENT IF USING PVC
MATERIAL.
13. REFRIGERANT LINE SET FOR CONDENSING UNIT TO INDOOR UNIT. PROVIDE UV
RESISTANT JACKET OVER LINE-SET ON ALL EXPOSED ROUTING.
6" Ø
12x12
C
6" Ø
B
C
6"
Ø
C50
6" Ø
A
8" Ø
10x10
10x10
6" Ø
10x10
10x10
10" Ø 16" Ø 14" Ø
12" Ø
8" Ø
6" Ø
A
8" Ø
A
8" Ø
A
8" Ø
A
8" Ø TO RTU-1
TY
P
10x10
A
8" Ø
T
C
6" Ø
EUH-1
C
6" Ø
14x1210x12 x1
12" Ø 16" Ø x1 x1
A
8" Ø
A
8" Ø
A
8" Ø
VESTIBULE
WAITING
RECEPTION
HALL
EXAMTREATMENT
OFFICE
CLEAN
SUPPLY
DRUG ROOM
CL.
SOILED
NURSE STATION
UNISEX 1 UNISEX 2
JANITOR
RTU-1
CU-1
D
B
TYP
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
M-101
MECHANICAL HVAC FLOOR PLAN
944900M101.DWG
TO PIPE &
PIPE THRU ROOF DIAGRAM
NO SCALE
REFER TO ARCHITECT AND ROOFING CONTRACTOR
CAULKING BY M.C.
PIPE.
BETWEEN JACK &
PROVIDE SEALANT
ROOFING
PIPE SLEEVE BY M.C.
PENETRATION WITH
SEAL JACK TO MEM-
CLAMP ROOF JACK
PIPE BY M.C.
BRANE WATERTIGHT.
CONTRACTOR.
BY ROOFING
PREFAB OR FIELD
BUILT ROOF JACK COOR'D ROOF
CONTRACTOR.
ROOFING
NOTE:
AIR HANDLING UNIT DRAIN TRAP DIAGRAM
NO SCALE
SAME SIZE AS THE NIPPLE ON THE
DRAIN LINE SHALL BE AT LEAST THE
PITCH DOWN TOWARD DRAIN
CLEAN OUT, TYP.
DRAIN PAN
UNIT TYPE
BLOW THRU
DRAW THRU
B
A x 1"
1" MIN.
PAN
DRAIN
A
2.0 x
1.5 x
B
DRAIN TO CODE
APPROVED
RECEPTACLE
DOMESTIC WATER ENTRANCE DIAGRAM
NO SCALE
GLOBE VALVE
CERTIFIED TESTER TO TEST.
BACKFLOW PREVENTER.
DOUBLE CHECK TYPE
CW TO BUILDING.
PRESSURE REDUCING
VALVE, WATTS 223, 1 1/4"
SET @ 60 PSI
TO EXTERIOR
DOMESTIC WATER SERVICE SHUT-OFF VALVE.
PRESSURE GAUGE
STRAINER WITH BLOW DOWN
UNION
TO CW SERVICE.
EXTERIOR WALL
FLOOR
WATER HEATER PIPING DIAGRAM
NO SCALE
LP
G
D
S
( GAS )
COLD WATER SUPPLY.
HWC FROM FIXTURES.
DIAPHRAGM TYPE EXPANSION
TANK.
WATER HEATER, TYP.
RELIEF VALVE, PIPE INDIRECT
TO FLOOR DRAIN, UNO.
PROPANE SUPPLY.
DOMESTIC HW RECIRC. PUMP.
SUPPORT FROM FLOOR.
HOT WATER TO SYSTEM
NOTE:
THE WATER HEATER SHALL BE ANCHORED OR
STRAPPED TO RESIST HORIZONTAL
DISPLACEMENT DUE TO EARTHQUAKE MOTION.
STRAPPING SHALL BE AT POINTS WITHIN THE
UPPER 1/3 AT AND LOWER 1/3 OF ITS VERTICAL
DIMENSION. AT THE POWER POINT, A
DISTANCE OF NOT LESS THAN 4" SHALL BE
MAINTAINED ABOVE THE CONTROLS WITH THE
STRAPPING.
3" HOUSE
KEEPING
PAD.
1 1/4" WILKINS OR EQUAL
WALL CLEANOUT
DIAGRAM
NO SCALE
CLEANOUT DIAGRAMS
FLOOR CLEANOUT (FCO)
NO SCALE
SLOPE DN @ 1/4"/L.F.
CLEANOUT TO GRADE (COTG)
WASTE LINE
FINISHED GRADE
6"
ADJUSTABLE GRADE CLEANOUT AND ACCESS ENCLOSURE WITH ANCHOR FLANGE,
HEAVY DUTY TOP, AND VANDAL PROOF FASTENERS, ZURN, Z-1400-HD-KBRASS
CLEANOUT PLUG W/COUNTER SUNK HEAD.
ADJUSTABLE CLEANOUT
AND ACCESS COVER ZURN
ZB-1400. TOP OF COVER TO
BE FLUSH W/ TOP OF FLOOR.
16" CONC. PAD TROWEL
SMOOTH & EDGE.
1/8 C.I. BEND
BALANCE OF PIPING SAME
AS CLEANOUT TO GRADE.
FLOOR LINE
1/8 C.I. BEND
C.I. WASTE LINE.
LGTH TO SUIT.
1/8 BEND IF CLEANOUT
OCCURS AT END OF LINE.
PROVIDE FOLLOWING OPTIONS AS APPROPRIATE
CARPET MARKER - FOR CARPETED AREAS.
SQUARE TOP - FOR CERAMIC TILE OR
SIMILAR SQUARE PATTERN FLOOR.
FLASHING CLAMP - FOR ABOVE GRADE
WATER PROOFED AREAS.
EXHAUST FAN DIAGRAM
NO SCALE ( VERTICAL DISCHARGE )
BREIDERT TYPE "L" ROOF
CAP W/ FR-4 BASE; SIZE 6".
FLASHING AND COUNTER
FLASHING
ROOF
COOR'D ROOF PENETRATION
W/ ROOF MANUFACTURER
SAME SIZE AS UNIT
OPENING.
CEILING
GRILLE
18"
MIN.
EXH.
FAN
CONNECTION DIAGRAM
CEILING TRANSFER DUCT
NO SCALE
(NO INSULATION).
SHEET METAL BOX
12" HIGH
CEILING RETURN
CEILING DIFFUSER.
INSULATED FLEX DUCT.
EXTERIOR DUCT INSULATION.
AS REQUIRED.
SQUARE TO ROUND ADAPTER
S.S. WORM DRIVE CLAMP.
SHEET METAL STRAP
SUPPLY DUCT WITH WRAP
SPIN-IN FITTING WITH
SHEET METAL SHIELD
NO SCALE
TYPICAL DIFFUSER CONNECTION DIAGRAM
S.B.D.
INSULATION. MINIMUM
SIZE SHOWN IN PLAN.
DUCT W/ 1" DUCT
SHEET METAL
SEAL DUCT AND PLENUM
CONNECTIONS WITH MASTIC OR
APPROVED EQUAL.
CEILING RETURN
EXTEND PER PLAN
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
MP-501
MECHANICAL/PLUMBING
DIAGRAMS
944900MP501.DWG
shanti
PLUMBING FIXTURE SCHEDULE
SYMBOL TYPE A.D.A. FINISH MANUFACTURER* &
MODEL #
FAUCET TRIM MFR.* &
MODEL # ACCESSORIES REMARKS
WATER CLOSET ADA WHITE VITREOUS
CHINA AMERICAN STANDARD 215AA AMERICAN STANDARD
5321.110 SEAT
1.6 GPF LOW FLOW FLUSH TANK
MODEL
LAVATORY ADA VITREOUS CHINA ZURNZ5340 ZURN MODEL Z81104, 4" CNTR,
WRIST BLADE HANDLES
GRID DRAIN, 0.5 GPM
AERATOR, PTRAP, ANGLE
STOPS AND RISERS,
CONCEALED WALL CARRIER
ADA WRAP WATER AND SUPPLIES
EXAM SINK ADA STAINLESS STEEL ELKAY ELUHAD1316 ZURN Z812A4
1.5 GPM OUTLET AERATOR,
P-TRAP, TRUBRO UNDER-SINK
PROTECTION, LOW-LEAD
5" DEPTH, UNDER MOUNT. PLASTER
TRAP REQUIRED IN PROCEDURE
ROOM, REFER TO FLOOR PLAN FOR
LOCATION.
DRINKING FOUNTAIN - STAINLESS STEEL HAWS MODEL 1011 WALL SUPPORT CARRIER WALL MOUNT SEE ARCHITECTURAL
FOR MOUNTING HEIGHTS
MOP SINK - PRECAST TERRAZZO FIAT TSB100 FIAT 830-AA
WATERPROOF BACKSPLASH,
HOSE RIM GUARDS, MOP
HANGERS
ICEMAKER
WALL BOX - GALVANIZED
STEEL
GUY GRAY
BIM-875 - - SHOCK ARRESTER
HOSE BIB - CHROME WOODFORD MODEL 65 - FREEZE PROOF HOSE BIB,
LOOSE KEY SIZE TO MATCH WALL THICKNESS
FLOOR SINK - CAST IRON ZURN Z1902 - ELASTOMERIC TRAP GUARD 12x12 INLET/3" OUTLET
MANUFACTURERS:
FIXTURE: AMERICAN STANDARD, FIAT, JUST
FAUCET: DELTA, AMERICAN STANDARD, T&S
DRAIN: JOSAM, WADE SMITH
GENERAL NOTES:
A: REFER TO FLOOR PLANS FOR FIXTURE LOCATIONS.
B:
P1
P2
P3
P4
P5
P6
P7
P8
DX UNITARY PACKAGED HVAC EQUIPMENT SCHEDULE
MARK AREA SERVED TYPE
MIN. OUTSIDE
AIR (CFM)
AIR DELIVERY CAPACITY COOLING COIL HEATING COIL ELECTRICAL FILTER
TYPE
WEIGHT (LBS) MANUFACTURER* &
MODEL # ACCESSORIES REMARKS
SUPPLY FAN AIR CONDITIONS AIR CONDITIONS GAS-FIRED SECTION
MCA MOCP VOLT/
PHASE TYPE
CFM E.S.P. @ ALT E.A.T. DB/WB
(°F)
L.A.T. DB/WB
(°F) EER TOTAL
MBH
SENSIBLE
MBH
E.A.T. DB
(°F)
L.A.T. (DB
(°F)
INPUT @ ALT
(MBH)
OUTPUT @
ALT. (MBH)
RTU-1 CONSTANT
VOLUME 420 2000 0.5 80/63 52 13 52 50 56 97 115 74.4 28 40 208/3 MERV 8 750 CARRIER 48TCEA06 A,B
AMBIENT OA CLG 105 DEG F, GROUND
MOUNTED UNIT, SIDE DISCHARGE,
REFER TO PLANS
MANUFACTURERS:
* TRANE, MCQUAY
ACCESSORY PACKAGES:
A: PREMIUM EFFICIENCY MOTOR; HAIL GUARDS; HIGH ALTITUDE PROPANE BURNER; DUCT SMOKE DETECTOR PROVIDED BY ELECTRICAL, INSTALLED BY MECHANICAL, WIRED BY ELECTRICAL; 24" TALL MOUNTING CURB
B: FULLY MODULATING ECONOMIZER, BAROMETRIC RELIEF DAMPER. IF FACTORY RELIEF UNAVAILABLE, PROVIDE FIELD INSTALLED BAROMETRIC RELIEF DAMPER. FIELD COORDINATE ANY REQUIRED POWER FOR RELIEF.
GENERAL NOTES:
A: UNIT SELECTED AT 4800 FEET ABOVE SEA LEVEL
B:
DX SPLIT SYSTEM COOLING UNIT SCHEDULE
MARK TYPE CFM
COOLING ELECTRICAL
MANUFACTURER*
& MODEL # ACCESSORIES REMARKS
SOUND dBA WEIGHT MCA MOCP VOLT/
PHCAPACITYE
MBH REFER SEER
CU-1/AC-1 WALL
MOUNTED 700 24 R-410A 13 42,48 50 LBS
175 LBS 18A 30 208/1 MITSUBISH: PKA-24KA
PUY-D24NHA
SEE NOTES A,B,C POWER FOR AC-1 FED
THROUGH CU-1
MANUFACTURERS:
GENERAL NOTES:
A: PROVIDE FACTORY LINE SET BETWEEN UNITS SIZED PER MANUFACTURER'S RECOMMENDED INSTALLATION INSTRUCTIONS.
B:
PROVIDE UNIT WITH CONDENSATE PUMP; POWER PUMP THROUGH UNIT, AND SHUT DOWN ON OVERFLOW. PROVIDE INDOOR THERMOSTAT AND WALL CONCEALMENT CHANNEL FOR REFRIGERANT AND
CONDENSATE PIPING; PROVIDE LOW AMBIENT COOLING MODULE.
C: PROVIDE AIRTEC (OR EQUIVALENT) CONDENSER BRACKET FOR GROUND MOUNTING OF OUTDOOR CONDENSER UNIT.
WATER HEATER SCHEDULE (GAS-FIRED)
MARK TYPE
STORAGE
CAPACITY
(GAL.)
RECOVERY
(GPH)
WATER
TEMP. RISE
(°F)
INPUT
@ S.L.
(MBH)
MANUFACTURER* &
MODEL # ACCESSORIES REMARKS
WH-1 STORAGE 50 43 100 47 RHEEM
GPDV50-65LP SEE NOTE A
PROPANE FIRED, POWER DIRECT
VENT, 80% THERMAL EFFICIENCY
MIN., 120v POWER REQUIRED
MANUFACTURERS:
* A.O. SMITH, STATE, OR LOCHINVAR EQUIVALENT
GENERAL NOTES:
A: PROVIDE UNIT WITH IECC 504.3 COMPLIANT TEMPERATURE CONTROLS, HIGH ALTITUDE KIT, AND CONCENTRIC VENT KIT
B:
PUMP SCHEDULE
MARK SERVIC
E TYPE GPM
TDH
(FT) FLUID
MOTOR MANUFACTURER* &
MODEL # ACCESSORIES REMARKSWATTS RPM VOLT/
PH
CP-1 RECIRC-
ULATION INLINE 2 15 WATER 270 2650 120 BELL AND GOSSETT
MODEL NBF-25 SEE NOTE A DHW RECIRCULATION
PUMP
*MANUFACTURER:
* B&G, GRUNDFOS, TACO OR AURORA EQUIVALENT
GENERAL NOTES:
A: PROVIDE PUMP WITH TIME CLOCK AND AQUASTAT
B:
CEILING EXHAUST FAN SCHEDULE
MARK TYPE
FAN MOTOR
MANUFACTURER* &
MODEL # ACCESSORIES REMARKS
CFM SONES
ESP
HP/
(WATT)
VOLT/
PHASE@ ALT (IN
WC)
CEF-1 CEILING 60 - 0.25 45W 120/1 GREENHECK
SP-B80
ROOF CAP, ELECTRIC
SPEED CONTROL SEE NOTE B
CEF-2 CEILING 60 - 0.25 45W 120/1 GREENHECK
SP-B80
ROOF CAP, ELECTRIC
SPEED CONTROL SEE NOTE A
CEF-3 CEILING 60 - 0.25 45W 120/1 GREENHECK
SP-B80
ROOF CAP, ELECTRIC
SPEED CONTROL SEE NOTE A
CEF-4 CEILING 60 - 0.25 45W 120/1 GREENHECK
SP-B80
ROOF CAP, ELECTRIC
SPEED CONTROL SEE NOTE B
MANUFACTURERS:
* COOK, PANASONIC
GENERAL NOTES:
A: WIRE FAN TO OCCUPANCY SWITCH
B: FAN TO RUN CONTINUOUS
UNIT HEATER SCHEDULE
MARK TYPE CAPACITY
ELECTRICAL
MANUFACTURER*
& MODEL # ACCESSORIES REMARKS
WATT VOLT/
PH
EUH-1 ELECTRIC
HEATER 1500 WATTS 1500 120/1 QMARK
CWH1151
WALL MOUNTING KIT,
BUILT-IN THERMOSTAT
ELECTRIC HEATER FOR
JANITOR ROOM; SET UNIT TO 1500W
MODE; INSTALL FROM WALL.
MANUFACTURERS:
* QMARK, REZNOR
GENERAL NOTES:
A:
B:
AIR DISTRIBUTION DEVICE SCHEDULE
MARK DESCRIPTION MOUNTING MANUFACTURER*
& MODEL # MATERIAL FINISH REMARKS
CEILING SUPPLY DIFFUSER LAY-IN CEILING PRICE SCD STEEL WHITE BAKED ENAMEL
24x24 FULLY LOUVERED FACE 4-WAY
THROW OR AS SHOWN. NECK SIZE AS
INDICATED
CEILING RETURN GRILLE LAY-IN CEILING PRICE 80TB ALUMINUM WHITE BAKED ENAMEL 24x12 PANEL, 1/2"x1/2"x1/2" EGG CRATE
CORE
CEILING SUPPLY GRILLE PER PLAN PRICE SCD ALUMINUM WHITE BAKED ENAMEL
12x12 PANEL, FULLY LOUVERED FACE
4-WAY THROW OR AS SHOWN. NECK SIZE
AS INDICATED
CEILING RETURN GRILLE LAY-IN CEILING PRICE 80TB ALUMINUM WHITE BAKED ENAMEL 24x48 PANEL, 1/2"x1/2"x1/2" EGG CRATE
CORE
MANUFACTURERS:
* PRICE, KRUGER
GENERAL NOTES:
A: PROVIDE INTEGRAL BALANCING DAMPERS ON EXHAUST/RETURN APPLICATIONS ONLY. DAMPERS SHALL BE ADJUSTABLE THROUGH FACE OF AIR DEVICE AND SHALL BE
OPPOSED BLADE TYPE WHERE AVAILABLE.
B: PROVIDE TAPERED TRANSITIONS FOR ALL SUPPLY DIFFUSERS WITH NECK SIZES DIFFERENT THAN SUPPLY DUCT RUN-OUT SIZES.
Project #:
LEE GAMELSKY, AIA
PROJECT ARCHITECT:
Date:
Sheet:
File:
By:
ALBUQUERQUE, NM 87106
2412 MILES ROAD SE
505.842.8865 FAX 842.1693
lee@lganm.com
Of:
00-00-0
COPYRIGHT 2013
B
ANZEG
EAUDIN
(970) 949-6108
(303) 278-3820
(970) 221-5691
(505) 323-9070
(307) 739-3944
Vail:
Denver:
Fort Collins:
Albuquerque:
Jackson:
www.bgce.com
03/14/2014
14 MARCH 2014
Veguita Healthcare Center 1 Salomon Griego Drive Veguita, New Mexico 87062
MP-601
MECHANICAL/PLUMBING
SCHEDULES
944900MP601.DWG
ELECTRICALCOVER SHEET
E-001
ELECTRICAL SITE PLANES-100
ELECTRICAL SCHEDULES & DIAGRAMS
E-601
GENERAL NOTES
1. THESE DRAWINGS ACCOMPANY THE PUBLISHED CONSTRUCTION DOCUMENT SPECIFICATION SHEET E-002.
2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK.
3. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTS REQUIRED TO
MAKE HIS WORK MEET EXISTING CONDITIONS.
4. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER - IN WRITING. WORK WHICH COULD RESULT IN AN ACCIDENTAL
OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK.
5. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLE GENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAIN CONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLE EQUIPMENT SHALL BE
SUBJECT TO OWNER APPROVAL.
6. REVIEW ARCHITECTURAL, MECHANICAL AND OTHER DRAWINGS PRIOR TO BID.
7. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.
8. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE OF NEW MEXICO, AND NATIONAL CODES
AND ORDINANCES.
9. PROVIDE PERMITS AND INSPECTIONS REQUIRED.
10. PROVIDE WITH SHOP DRAWING SUBMITTAL, 1/4” SCALE LAYOUT DRAWINGS OF ROOMS WITH ELECTRICAL SWITCHBOARDS AND
TRANSFORMERS. LAYOUTS SHALL SHOW LOCATIONS OF, AND SHALL BE COORDINATED WITH MECHANICAL EQUIPMENT. ALL EQUIPMENT
SHALL BE DRAWN TO SCALE.
11. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO
SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
12. VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND UTILITIES, PIPING AND RACEWAY SYSTEMS PRIOR TO TRENCHING. PROVIDE
NECESSARY TRENCHING, BACKFILL, EXCAVATION, SUPPORTS, SERVICE FEEDERS (CONDUIT AND/OR WIRE), PULLBOXES, TRANSFORMER PADS, SAWCUTTING AND PATCHING, CONCRETE/PAVING, ETC. REQUIRED. BACKFILL TRENCHES TO 90 PERCENT COMPACTION AND PATCH TO MATCH
EXISTING. CONTRACTOR SHALL OBTAIN AND VERIFY EXACT UTILITY COMPANY DRAWINGS AND REQUIREMENTS. ELECTRICAL CONTRACTOR IS
TO SUBMIT A COMPLETE CONSTRUCTION DRAWING SET TO THE ELECTRICAL UTILITY COMPANY WITH-IN 10 DAYS OF AWARD OF CONTRACT.
COORDINATE TIMELINE OF THEIR REVIEW, APPROVAL, CONSTRUCTION SCHEDULING AND INSTALLATION OF THE UTILITY TRANSFORMER WITH
THE UTILITY COMPANY. NOTIFY OWNER OF ANY SCHEDULING CONFLICTS.
13. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
14. REVIEW ARCHITECTURAL AND MECHANICAL DRAWINGS AND PROVIDE LIGHTS, SWITCHES, RECEPTACLES, TELECOM OUTLETS, EQUIPMENT
CONNECTIONS, ETC. AND ASSOCIATED CIRCUITING IN NEW AND REMODELED AREAS.
15. INSTALL ALL MATERIALS IN ACCORDANCE…
This is the start of the file's text. The full file is on GovTribe.