This document is a visual survey report prepared by the State of Michigan Department of Technology, Management & Budget (DTMB) for the Muskegon Correctional Facility roof assessment. The report, dated January 5, 2023 (ATI Report No. P2225-001), contains photographic documentation and visual survey findings for roof conditions across multiple buildings at the facility, including the Administration Building, Housing Units 1-5, the Maintenance Building, and the Powerhouse Building. The survey documents the physical condition of roof systems, insulation, flashing, ventilation components, and structural elements through 42 detailed photographs organized by building section. The assessment captures existing roof configurations, material types, deterioration patterns, and repair history across steep-sloped metal panel roofs and low-sloped membrane roofs throughout the correctional facility.
The photographic survey reveals significant maintenance and repair needs across the facility's roof systems. Key findings include deteriorated paint coatings on aluminum metal panels exposing bare metal, displaced and inadequate insulation in attic spaces, failed soil pipe flashings allowing water entry, missing foam insulation panels, inconsistent roof modifications and repairs, asbestos-containing caulk at parapet joints, and various ventilation system deficiencies. Multiple roof sections show evidence of previous repairs with varying degrees of quality, including ridge vent modifications, valley flashing installations, and panel replacements using different materials and dimensions than original construction. The survey documents conditions that suggest the need for comprehensive roof restoration or replacement work to address performance, water intrusion risks, energy efficiency, and facility integrity concerns.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
State of Michigan – DTMB – Muskegon Correctional Roof Survey Photographs
Appendix D1 – Visual Survey Photos (Administration Building)
ATI Report No. P2225-001 Date 1-05-23 Page 1 of 3
1. Administration Building. Main low sloped roof. General View. Frost on roof. Insulation fasteners shown.
2. Administration Building. Another general view of the main low sloped roof. No apparent heat loss due to wet insulation as frost is not melted.
3. Administration Building. Core #1 on main low sloped roof. Steel deck, 1.5” ISO and modified membrane roof.
Insulation found to be dry at core.
4. Administration Building. Core #2 on main low sloped roof at parapet wall. Wood blocking found. Insulation found to be dry at core.
5. Administration Building. View of narrow rib steel roof deck below main low sloped roof.
6. Administration Building. View of the metal roof panels on the north side. These metal panels are “newer” and have ribs at 16 inches on center.
Photographs 1-6
ATI Report No. P2225-001 Date 1-05-23 Page 2 of 3
7. Administration Building. View of “older” metal panels on south side and at east/west steep mansards. Ribs are at 12” on center. The older panels are losing their paint.
8. Administration Building. View of west mansard and the flaking paint. There is a securing camera over the entrance door.
9. Administration Building. The “older” metal panels were at one time “painted” and the added paint is flaking off and is especially visible at the west entrance door side.
10. Administration Building. The “east” steep sloped mansards have multiple rows of razor ribbon in place, as well as other security wires.
11. Administration Building. View in the attic showing the steel roof deck supporting the metal panels. Spray foam looks to be “added” at this valley location and is shown on the original construction drawings for “valley”.
12. Administration Building. Fiberglass insulation exists on the floor of the attic below the metal panels. Much of the insulation appears to be moved or displaced.
Photographs 7-12
ATI Report No. P2225-001 Date 1-05-23 Page 3 of 3
13. Administration Building. There are rectangular intake soffit vents below the metal panel roofs.
14. Administration Building. In the attics, the openings for the soffit events are visible in the building overhang. The overhang was not insulated.
15. Administration Building. Raised low slope roof near SW corner of building.
16. Administration Building. Raised low slope roof. Also, a modified roof. Slopes from west to east. No melted frost.
17. Administration Building. Raised low slope roof near SW corner of building. Roof Core #3. Core found an orange colored foam insulation that may be phenolic foam.
18. Administration Building. Raised low slope roof near SW corner of building. The parapet does not have a metal cap. The caulk joint from stone to brick is poor. Asbestos sampling of this caulk showed it as containing asbestos.
Photographs 12-18
Appendix D2 – Visual Survey Photos (Housing Units 1-5)
ATI Report No. P2225-001 Date 1-5-23 Page 1 of 7
1. Housing Unit 1. Underside of attic in housing unit portion. View of steel roof deck.
2. Housing Unit 1. Insulation on floor of attic in housing unit portion.
3. Housing Unit 1. Deck and insulation in the one story Health Services Wing.
4. Housing Unit 1. At the Health Service Wing, one side of the 12” wide aluminum metal panel roof has been replaced with a different sized 16” wide steel metal panel.
5. Housing Unit 1. Reverse view looking back over Health Service wing onto the housing unit. Note failing paint and poor appearance of the original aluminum metal panels.
6. Housing Unit 1. Past mastic repair at a lead soil pipe.
ATI Report No. P2225-001 Date 1-5-23 Page 2 of 7
7. Housing Unit 1. Some leaves on metal panels. The ridge vent appears to have been modified or repaired at least once in the past. Typical mechanical room construction.
8. Housing Unit 1. Typical metal panel to wall flashing construction. (Two such locations each Housing Unit).
9. Housing Unit 1. More evidence of past repairs at the ridge. At the “repair”, the ridge looks to be un-vented.
10. Housing Unit 2. Much of the main roof has a 3 foot soffit overhang. Most overhangs have a soffit intake vent strip, or spaced rectangular vents.
11. Housing Unit 2. Much of the main roof has a 3 foot soffit overhang. Most overhangs have a soffit intake vent strip, or spaced rectangular vents. This building has spaced vents about 8 feet on center.
12. Housing Unit 2. Most areas of the housing units have a 12 inch on center aluminum metal panel. Each has a vertical mansard portion.
ATI Report No. P2225-001 Date 1-5-23 Page 3 of 7
13. Housing Unit 2. Spray foam applied to this interior building valley (as describe on the original construction drawings for “valleys”).
14. Housing Unit 2. A layer of foam insulation found above the steel roof deck and below the metal roof panel.
15. Housing Unit 2. Typical insulation layer at the bottom of the attic (on the gypsum ceiling of the housing unit).
16. Housing Unit 2. Attic insulation measured at only 2 or 3 inches thick.
17. Housing Unit 2. Typical roof eave flashing. Panels lapped onto a L shaped drip.
18. Housing Unit 2. The vertical mansard portion is 24 inches in size (elevation).
ATI Report No. P2225-001 Date 1-5-23 Page 4 of 7
19. Housing Unit 2. Typical rib height of 2.75”.
20. Housing Unit 2. Typical panels as viewed from the top, looking down.
21. Housing Unit 2. Typical raised mechanical room roof.
Apron flashing.
22. Housing Unit 2. Typical raised mechanical room roof.
Apron metal counterflashing. No weeps observed above through wall flashing receiver.
23. Housing Unit 2. Typical valley flashing extending 6 inches on either side of centerline.
24. Housing Unit 2. This particular hip flashing was installed with a ridge vent. That is not common on the other housing unit buildings at the hip condition.
Photographs 19-24
ATI Report No. P2225-001 Date 1-5-23 Page 5 of 7
25. Housing Unit 3. Typical view of the eave and mansard.
26. Housing Unit 3. Typical view of the eave with the panels secured. Note how much of the original panel paint coating is gone and exposes the aluminum below.
27. Housing Unit 3. This building had a 2” wide strip soffit vent, as compared to spaced rectangular vents.
28. Housing Unit 3. View from attic looking down at the soffits and seeing “light” visible at the eave. Intake air from soffits appears open and unblocked/. Insulation not always smooth and even and continuous.
29. Housing Unit 4. This building also has a 2” wide strip soffit vent, as compared to spaced rectangular vents.
30. Housing Unit 4. View of the interior attic. Insulation is not always smooth and continuous and appears to have been disturbed over time during repairs.
Photograph 25 – 30
ATI Report No. P2225-001 Date 1-5-23 Page 6 of 7
31. Housing Unit 4. View of ceiling under insulation next to access hatch. Insulation has been pushed back.
32. Housing Unit 4. View of gable end and mechanical vent room at each end.
33. Housing Unit 4. General view. Many panels have lost their paint and expose the metal below.
34. Housing Unit 4. View of the roof ridge with a small house ridge vent added to what was a previously unvented cap metal.
35. Housing Unit 4. Typical view from the back side.
36. Housing Unit 5. General view and leaves on the roof from nearby mature trees.
Photographs 31-36
ATI Report No. P2225-001 Date 1-5-23 Page 7 of 7
37. Housing Unit 5. Typical rake metal and vertical face mansard.
38. Housing Unit 5. This soil pipe metal flashing was found torn and open to water entry.
39. Housing Unit 5. View of the two piece soil pipe flashing system.
40. Housing Unit 5. View in attic of typical fiberglass roof insulation.
41. Housing Unit 5. View of light entering attic from torn soil pipe condition.
42. Housing Unit 5. View of the 2” strip soffit at Housing Unit 5.
Photograph 37 – 42
Appendix D5 – Visual Survey Photos (Maintenance & Powerhouse Bldg)
ATI Report No. P2225-001 Date 1-5-23 Page 1 of 5
1. Maintenance Building. View of west side, near north end.
4 inch per foot main panel with 2 foot vertical mansard.
2. Maintenance Building. Area of damaged and lost stucco on rear of building.
3. Maintenance Building. Rear mansard at the joint between the original building and south building addition.
Older panels on left, newer on right. [Note: Even the newer panels are old!]
4. Maintenance Building. Cracking in the block wall at a portion of the rear side of building. Determining the cause of cracking was beyond the scope of our services.
5. Maintenance Building. Overview of typical roof panels.
Many panels have lost their factory paint coat.
6. Maintenance Building. What appears to be some remnant of snow guard on the rear (west) section near the north end over garage doors.
ATI Report No. P2225-001 Date 1-5-23 Page 2 of 5
7. Maintenance Building. View of the front steep mansard side. At doorway locations the front mansard has a slightly different overhand and dimension.
8. Maintenance Building. View of the underside of the roof.
Insulation boards approximately 12 inches wide appear to match the 12” metal panels. Purlins about 6 feet on center.
9. Maintenance Building. The panels appear to be secured to the purlins by some type of crimped panel anchor.
10. Maintenance Building. The foam insulation board was missing at this location and the underside of the roof panel was able to be viewed directly.
11. Maintenance Building. A different roof panel assembly exists on the south gable end. Different coating and different panel shape.
12. Maintenance Building. View of the different kind of roof panel on the south gable end. Visible rust forming on the panel. These appear to be nailed barn siding type panels.
ATI Report No. P2225-001 Date 1-5-23 Page 3 of 5
13. Maintenance Building. Yet a 3rd type of roof panel assembly exists on the north gable end.
14. Maintenance Building. The north gable end has a 16” wide standing seam panel, similar in size as Housing Unit 6.
15. Powerhouse Building. View of the front, east portion. 16. Powerhouse Building. View of the front, west portion.
17. Powerhouse Building. The front overhang is very heavy steel and appears in fair condition.
18. Powerhouse Building. There is a vestibule heater immediately in front of the main entrance.
ATI Report No. P2225-001 Date 1-5-23 Page 4 of 5
19. Powerhouse Building. The front overhang canopy abuts the eave drip of the main roof.
20. Powerhouse Building. The metal panels are the same shape as those on Housing Units 1-5 and Maintenance.
Ribs are approximately 2.75” high.
21. Powerhouse Building. General View. Slope 4 inches per foot. One hot stack is shorter than the others.
22. Powerhouse Building. The larger curbed units on the front side each have good sized saddles to divert water.
23. Powerhouse Building. View from the inside, showing support for the roof and penetrations. Purlin spacing is shorter and the purlins have a different design when compared to some of the Maintenance Building.
24. Powerhouse Building. Closer view of a location where the foam insulation panel is cracked and open and exposed the underside of the metal roof panel.
Photographs 19-24
ATI Report No. P2225-001 Date 1-5-23 Page 5 of 5
25. Powerhouse Building. Closer view of a typical curb saddle.
26. Powerhouse Building. View of the ridge metal closure.
The back side of the building is sloped 90 degrees from the front side (approximately 36 inches per foot). This ridge is not vented.
27. Powerhouse Building. Closer view of the ridge metal closure, approximately 10 inches long on the front side.
28. Powerhouse Building. Closer view of the ridge metal closure, approximately 6 inches long on the back side.
29. Powerhouse Building. View of the ridge cap lap onto the front panels.
30. Powerhouse Building. View of rake metal, approximately 6 inches in size.
Photograph 25 – 30