200330 - FULL SET.pdf
PDF 5 MB Posted
- Solicitation number
- W50S84-20-B-0002
About this file
This solicitation seeks bids for an alteration project at the Battle Creek Air National Guard Base in Michigan. The project scope includes interior renovations to the base's Defense Operations Center and is valued between $250,000 and $500,000. The solicitation is set aside for small businesses with a NAICS code of 236220. Bids are due by August 12, 2020 and award will be made based on price and price-related factors to the responsible bidder submitting a conforming bid most advantageous to the government. A pre-bid conference will be held on August 12 at 10:00 AM local time. The Michigan Army National Guard is the contracting agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Battle Creek BASE ACCESS REQUEST.pdf | ||
| W50S8420B0002.pdf | ||
| Battle Creek Base Access and Work Battle Creek ANGB.docx | DOCX document | |
| 200331 BTL Alter BDOC-VOLUME 1.pdf | ||
| Battle Creek Access Form directions.pdf | ||
| SANGB Base Access List.xlsx | XLSX spreadsheet | |
| 200331 BTL Alter BDOC-VOLUME 2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEMO 10 JUNE 2011
DEMO 16 AUGUST 2014
D E
M O
A U
G
MAIN GATE CONTRACTOR GATE
W E S T G
A
TE
SIGNSIGN
SIGN
WEST PROPERTY
WATER SERVICE
BACKFLOW
PREVENTION
LO
T
I
TAXILANE - F
D
C
SOUTH RAMP
EAST APRON
TRANSIENT PAD
POWER
CHECK PAD
E
E
HC
F
E
E
E
E
SOUND WALL
WEST RAMP
CLOSED
"P
C C
"P
C C
"A
C C
"P
C C
"A
C C
"P
C C
RE
C
RU
IT
ING
VI SIT
OR
S
ON
L
Y
RE
C
RU
IT
ING
VI SIT
OR
S
ON
L
Y
RE
C
RU
IT
ING
VI SIT
OR
S
ON
L
Y
RESERVED
VISITOR
RESERVED
VISITOR
RESERVED
VISITOR
R E
S
ER
V E
D
R E
S
ER
V E
D
R E
S
ER
V E
D
H A
N D
IC
A
P
H A
N D
IC
A
P
R E
S
ER
V E
D
R E
S
ER
V E
D
R E
S
ER
V E
D
HANDICAP
CUSTO M ER
HANDICAP
CUSTO M ER
CUSTO M ER
RESERVED
RESERVED
RESERVED
H A
N D
IC A
P
H A
N D
IC
A
P
H A
N D
IC
A
P
V
ISI T
O R
RESERVED
UTA 91
RESERVED
RESERVED
UTA 89
RESERVED
UTA 88
RESERVED
RESERVED
U T
A
U
U
U
RESERVED
RESERVED
RESERVED
8 7
8 5
8 4
8 3
RESERVED
RESERVED
UTA 18
RESERVED
UTA 17
RESERVED
UTA 16
RESERVED
UTA 15
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
R E
S
ER
V E
D
0 R E
S
ER
V E
D
R E
S
ER
V E
D
9 R E
S
ER
V E
D
R E
S
ER
V E
D
RESERVED
8 0
RESERVED
8 1
RESERVED
8 2
RE
S
ERV
E
D
5 0
RE
S
ERV
E
D
5 1
RE
S
ERV
E
D
5 2
RE
S
ERV
E
D
UT
A 53
RE
S
ERV
E
D
5 4
RE
S
ERV
E
D
UT
A 55
RE
S
ERV
E
D
UT
A 56
RE
S
ERV
E
D
UT
A 57
RE
S
ERV
E
D
5 9
RE
S
ERV
E
D
6 0
RE
S
ERV
E
D
7 4
RE
S
ERV
E
D
7 4
RESERVED
UTA 45
RESERVED
UTA 44
RESERVED
RESERVED
RESERVED
RESERVED
RESERVED
GO
RESERVED
RESERVED
RESERVED
UTA 71
RESERVED
RESERVED
UTA 73
R E
S
ER
V E
D
U
R E
S
ER
V E
D
U
E
S
ER
V E
D
U
E
S
ER
V E
D
R E
S
ER
V E
D
U
E
S
ER
V
R E
S
ER
V
20 spaces
17 spaces
18 spaces
14 spaces
16 sp a ces
14 sp a ces
9 s p a c e s
1 0 s pa c es
1 4 s p a ce s
13 s p a ce s
13 s p a ce s
LOT A
LOT P
LOT C
L O
T D
LOT E
LOT E LOT E
LOT G
LO
T
H
L O
T K
LOT M
LOT N
LOT F
LOT J
LOT O
L O
T R
L O
T Q
LOT S
LOT B
THUNDERBOLT AVE.
THUNDERBOLT AVE.
S A
B R
E S
T R
E E
T
S P
IT
F
IR
E
A V
E
MUSTANG AVE.
MUSTANG AVE.
FALCON STREET
D R
A G
O N
F L Y
TALON DRIVE
C A
N B
E R
R A
S E
N T R
Y D
R
IV
E
SENTRY DRIVE
MUSTANG AVE.
DICKMAN AVE.
S E
N T R
Y D
R
IV
E
P H
A N
T O
M A
V E
S C
O R
P
IO
N S
T R
E E
T
TH
UN
DER
BO
LT AVE.
TH
UN
DER
BO
LT
A
VE
CANBERRA
S K
Y
LI
N E D
R
DICKMAN AVE.
DICKMAN AVE.
OUTSIDE
STORAGE
H A
Z M
A T
S T
O R
A G
E
BATTLE CREEK
SPRINGFIELD
BATTLE
CREEK ANGB
WK KELLOGG
AIRPORT
NORTH
LOCAL VICINITY MAP
BUILDING LOCATION
PROJECT LOCATION
NORTH
VICINITY MAP
MICHIGAN
LANSING
CALHOUN
COUNTY
NORTH
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
ALTER BDOC
BATTLE CREEK ANGB
BATTLE CREEK, MICHIGAN
MICHIGAN AIR NATIONAL GUARD
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
G-001
COVER SHEET
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
ANG NO.: MBMV172815
GENERAL
G-001 COVER SHEET
ARCHITECTURAL
A-001 NOTES & SYMBOLS
A-002 INTERIOR PARTITION TYPES
AD101 FIRST FLOOR DEMOLITION PLAN
A-101 FIRST FLOOR PLAN
A-301 BUILDING SECTIONS
A-401 ENLARGED FLOOR PLAN
A-402 ENLARGED CEILING PLAN
A-421 CASEWORK DETAILS
A-501 DETAILS
A-601 SCHEDULES
FIRE PROTECTION
F-001 SYMBOLS, ABBREVIATIONS, NOTES AND DETAILS
PLUMBING
P-001 NOTES, SYMBOLS, ABBREVIATIONS, SCHEDULES, AND DETAILS
P-101 DRAIN AND VENT PLAN
P-131 SUPPLY PLAN AND ISOMETRIC PLANS
MECHANICAL
M-001 NOTES, SYMBOLS AND ABBREVIATIONS
MD101 FIRST FLOOR HVAC DEMOLITION PLAN
MD131 FIRST FLOOR PIPING DEMOLITION PLAN
M-101 FIRST FLOOR HVAC PLAN
M-131 FIRST FLOOR PIPING PLAN
M-501 HVAC DETAILS
M-511 PIPING DETAILS
M-601 HVAC SCHEDULES
M-602 HVAC SCHEDULES
M-611 PIPING SCHEDULES
M-801 CONTROL SCHEMATICS
ELECTRICAL
E-001 NOTES, SYMBOLS & ABBREVIATIONS
ED101 FIRST FLOOR POWER DEMOLITION PLAN
E-101 FIRST FLOOR POWER PLAN
E-121 FIRST FLOOR LIGHTING PLAN
E-401 ENLARGED PLANS, ELEVATIONS & SECTIONS
TECHNOLOGY SYSTEMS
T-001 NOTES, SYMBOLS & ABBREVIATIONS
TD101 FIRST FLOOR TECHNOLOGY SYSTEMS DEMOLITION PLAN
T-101 FIRST FLOOR TECHNOLOGY SYSTEMS PLAN
T-401 ENLARGED PLANS, ELEVATIONS & SECTIONS
T-501 DETAILS
SHEET INDEX
03/30/20 B2 PREFINAL
HATCH SYMBOLS
EARTHWORK
GRAVEL
PLASTER,
SAND, GROUT
CONCRETE
CONCRETE
MASONRY
CLAY
MASONRY
PRECAST
CONCRETE
METAL
PLYWOOD
FINISH LUMBER
WOOD STUDS,
BLOCKING
STEEL STUDS
GYPSUM
WALLBOARD
ACOUSTICAL
TILE
BATT
INSULATION
RIGID
INSULATION
ANGLE
@ AT
AB ANCHOR BOLT
AC ACOUSTIC
ACC ACCESS
ACT ACOUSTIC CEILING TILE
ACP ACOUSTIC CEILING PANEL
AD AREA DRAIN
ADD ADDITIONAL
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASPH ASPHALT
BB BOND BEAM
BD BOARD
BF BOTH FACES
BFC BELOW FINISH CEILING
BG BUMPER GUARD
BIT BITUMINOUS
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BM BEAM/BENCH MARK
BLK BLOCK
BOT BOTTOM
BRG BEARING
BRKR BREAKER
BRK BRICK
BRKT BRACKET
BS BACK SPLASH
BSMT BASEMENT
BTWN BETWEEN
CHANNEL
CAB CABINET
CER CERAMIC
CFCI CONTRACTOR FURNISHED,
CONTRATOR INSTALLED
CG CORNER GUARD
CH COAT HOOK
CIP CAST IN PLACE
CJ CONTROL JOINT/CONSTRUCTION
JOINT
CLG CEILING
CLO CLOSET/CLOSURE
CLR CLEAR
COL COLUMN
COMB COMBINATION
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION/CONNECT
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPT CARPET
CR COAT RACK/CURTAIN ROD
CSG CASING
CT CERAMIC TILE
CTR CENTER/COUNTER
CTSK COUNTERSUNK
CUH CABINET UNIT HEATER
CW COLD WATER
D DEPTH
DBL DOUBLE
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIR DIRECTION
DIV DIVISION
DM DEMOUNTABLE PARTITION
DN DOWN
DO DITTO
DR DOOR
DRWR DRAWER
DS DOWNSPOUT
DWG DRAWING
DWL DOWEL
DWS DEFORMED WELDED STUD
EA EACH
EC ELECTRICAL CONTRACTOR
EF EACH FACE
EH ELECTRICAL HEATER/EXHAUST
HOOD
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR/ELEVATION
EMBED EMBEDDED
EMER EMERGENCY
ENT ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ES EMERGENCY SHOWER
ESR ELASTOMERIC SHEET ROOFING
ETR EXISTING TO REMAIN
EVC ELASTIC VINYL COATING
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVATE
EXP EXPANSION
EXPD EXPOSED
EXPF EXPLOSION PROOF
EXT EXTERIOR
FA FIELD ADJUSTABLE
FV FIELD VERIFY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FLEX FLEXIBLE
FLR FLOOR
FLRG FLOORING
FP FIREPROOF/FIRE PROTECTION
FR FIRE RETARDANT
FS FULL SIZE/FULL SCALE
FT FEET
FTG FOOTING
FURG FURRING
GA GAUGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERAL
GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GFRC GLASS FIBER REINFORCED CONCRETE
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GMU GLAZED MASONRY UNIT
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HEIGHT
HDBD HARDBOARD
HDCP HANDICAPPED
HDWD HARDWOOD
HDWE HARDWARE
HK HOOK
HM HOLLOW METAL
HP HIGH POINT
HR HANDRAIL
HT HEIGHT
HVAC HEATING VENTILATION AND AIR CONDITIONING
HWS HEAD WELDED STUDS
ID INSIDE DIAMETER
IMP INSULATED METAL PANEL
IN INCHES
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
IPW INSULATED PLENUM WALL
IRF INSULATED ROOF FILL
JAN JANITOR
JS JANITOR SINK
JST JOIST
JT JOINT
KD KNOCKED DOWN
KO KNOCK-OUT / KNEE OPENING
L LENGTH
LAB LABORATORY
LAM LAMINATED
LB POUND
LBS POUNDS
LD LINEAR DIFFUSER
LDG LANDING
LF LINEAR FOOT
LG LONG
LGT LIGHT
LKR LOCKER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LP LOW POINT
LSH LONG SLOTTED HOLE
LTG LIGHTING
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
MACH MACHINE
MAN MANUAL
MAR MARBLE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBW MASONRY BEARING WALL
MC MECHANICAL CONTRACTOR
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MK MARK
ML METAL LATH
MLDG MOLDING
MO MASONRY OPENING
MP METAL PARTITION
MS MACHINE SCREW
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NONSHRINK
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER/OVERFLOW DRAIN
OFF OFFICE
OPNG OPENING
OPP OPPOSITE
OZ OUNCE
PART PARTITION
PC PIECE
PCC PRECAST CONCRETE
PCPL PORTLAND CEMENT PLASTER
PDWR PAPER TOWEL DISPENSER & WASTE RECEPTACLE
PH PHILLIPS HEAD/PHASE
PL PLASTIC LAMINATE/PLATE/PROPERTY LINE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PM PROTECTED METAL
PNL PANEL
PNLG PANELING
POL POLISHED
PR PAIR
PRE FAB PREFABRICATED
PRE FIN PRE-FINISHED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT/PAINT
PTM PAINT TO MATCH
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
QTY QUANTITY
RAD RADIUS
RAH ROOFTOP AIR HANDLING UNIT
RB RUBBER BASE
RC REINFORCED CONCRETE
RCP RADIANT CEILING PANEL
/ REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REINF REINFORCING
REL RELOCATE
REM REMAINDER
REQD REQUIRED
RES RESILIENT
RET RETURN
RI ROUGH IN
RM ROOM
RO ROUGH OPENING
RT RUBBER TILE
RUB RUBBER
SAT STANDARD AGGREGATE TOPPING
SB SOIL BEARING
SC SEAMLESS COATING
SCF SPECIAL CONCRETE FINISH
SCHD SCHEDULE
SD SOAP DISPENSER
SE SHELF EDGE
SECT SECTION
SF SAND FLOAT
SG SUPPLY AIR GRILLE
SGL SINGLE
SH SHELF
SHD SHOWER DOOR
SHT SHEET
SIM SIMILAR
SJ STEEL JOIST
SLV SHORT LEG VERTICAL
SM SMOOTH
SND SANITARY NAPKIN DISPENSER
SNV SANITARY NAPKIN VENDER
SOG SLAB ON GRADE
SPEC SPECIFICATION
SPR SPRINKLER
SQ SQUARE
SR SHOWER ROD
SS STAINLESS STEEL
ST STREET
STD STANDARD
STL STEEL
STO STORAGE
STRU STRUCTURAL/STRUCTURE
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
TB TACKBOARD/TOWEL BAR
TBR TO BE REMOVED
TCP THIN COAT PLASTER
TD TOWEL DISPENSER
TDW TOWEL DISPENSER AND WASTE
TEMP TEMPERATURE/TEMPERED
TER TERRAZZO
TEX TEXTURE
TFC TROWELED FLOOR COVERING
T & G TONGUE AND GROOVE
THK THICK
TOB TOP OF BEAM
TOC TOP OF CURB/TOP OF CONCRETE
TOD TOP OF DECK/TOP OF DUCT ELEVATION
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOP TOP OF PIPE ELEVATION
TOS TOP OF SLAB/TOP OF STEEL
TOW TOP OF WALL
TPG TOPPING
TPH TOILET PAPER HOLDER
TRAN TRANSOM
TRANS TRANSVERSE
TS TUBE STEEL
TWS THREADED WELDED STUD
TYP TYPICAL
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VINYL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VOL VOLUME
VWC VINYL WALL COVERING
W WIDE FLANGE STEEL BEAM
W/ WITH
WAF WELDED ANGLE FRAME
WC WATER CLOSET
WD WOOD
WDW WINDOW
WF WIDE FLANGE
WG WIRE GLASS
W/O WITHOUT
WP WEATHERPROOF
WPFG WATERPROOFING
WR WASTE RECEPTACLE
WSCT WAINSCOT
WSTP WEATHERSTRIP
WTR WATER
WWF WELDED WIRE FABRIC
X EXISTING
ABBREVIATIONS ABOVE ARE FOR ARCHITECTURAL SHEETS ONLY.
ABBREVIATIONS
LEGEND - PLAN SYMBOLS
ACP-X
10'-10" CEILING HEIGHT & FINISH
W18
ROOM NAME AND NUMBER
WALL TYPE IDENTIFICATION
KEYED NOTE IDENTIFICATION
WINDOW IDENTIFICATION
DOOR IDENTIFICATION
CALLOUTS
SECTION DETAIL SYMBOL, 1/A-101
INDICATES DETAIL 1 CAN BE FOUND ON
SHEET A-101
PLAN DETAIL OR ENLARGED PLAN
SYMBOL, 1/A-101 INDICATES DETAIL 1
CAN BE FOUND ON SHEET A-101
EXTERIOR ELEVATION SYMBOL, 1/A-201
INDICATES DETAIL 1 CAN BE FOUND ON
SHEET A-201
WALL SECTION SYMBOL, 1/A-101
INDICATES DETAIL 1 CAN BE FOUND ON
SHEET A-101
A-101
SIM
A-101
SIM
A-101
SIM
1A-211
INTERIOR ELEVATION SYMBOL, 1/A-211
INDICATES DETAIL 1 CAN BE FOUND ON
SHEET A-211
NAME
ELEVATION
VERTICAL OR SPOT ELEVATION
IDENTIFICATION
1 REVISION IDENTIFICATION
NEW CONSTRUCTION GRID LINE IDENTIFICATION
EXISTING CONSTRUCTION GRID LINE IDENTIFICATION
1A-201
BUILDING SECTION SYMBOL, 1/A-101
INDICATES DETAIL 1 CAN BE FOUND ON
SHEET A-101
A-101
SIM
ROOM NAME
FLOOR DRAINFD
F.E. FIRE EXTINGUISHER - SURFACE MOUNTED
CONSTRUCTION
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION WORK
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE
DEMOLISHED
NEW DOOR
A
F.E.C. FIRE EXTINGUISHER CABINET - SEMI-RECESSED
XXX
X
4.XXX
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:3
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-001
NOTES & SYMBOLS
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
PARTITION GENERAL NOTES:
1. PARTITIONS SHALL BE TYPE "A3" UNLESS OTHERWISE NOTED.
2. ALL ELEMENTS OF ACOUSTIC PARTITIONS SHALL EXTEND TO ROOF OR
FLOOR DECK ABOVE AND ALL JOINTS AND PENETRATIONS OF ACOUSTIC
RATED PARTITIONS SHALL BE FILLED AND SEALED.
3. REFER TO SHEET A-002 FOR PARTITION DETAILS.
4. REFER TO "INTERIOR PARTITION TYPE MODIFIERS" FOR SYMBOLS USED TO
IDENTIFY ADDITIONAL REQUIREMENTS OR MODIFICATIONS TO BASIC
PARTITION TYPES.
5. PARTITION TYPES DESCRIBE GENERAL REQUIREMENTS FOR PARTITIONS.
REFER TO PRODUCT MANUFACTURERS' SPECIFICATIONS AND
REQUIREMENTS FOR APPLICABLE TESTING AGENCIES FOR SPECIFICS OF
PARTITION CONSTRUCTION.
6. PARTITION REQUIREMENTS SHOWN ARE CONSIDERED MINIMUM
STANDARDS. WHERE CONDITIONS OF THE WORK CAUSE PARTITION(S) TO
EXCEED LIMITS RECOMMENDED BY MANUFACTURER, REINFORCE
PARTITION(S).
7. PENETRATIONS IN RATED PARTITIONS AND CONNECTIONS OF THE
PARTITIONS TO OTHER PORTIONS OF THE WORK SHALL BE IN
ACCORDANCE WITH MANUFACTURERS' RECOMMENDED DETAILS AND IN
COMPLIANCE WITH APPLICABLE TESTING AGENCY REQUIREMENTS.
8. WHERE A CLEAR DIMENSION OR OPENING IS REQUIRED OR NOTED,
MEASURE DIMENSION TO FACE OF PARTITION FINISH.
9. REFER TO STRUCTURAL DRAWINGS FOR EXTENT AND DESCRIPTION OF
INTERIOR STRUCTURAL WALLS NOT IDENTIFIED BY PARTITION TYPES.
10. INSTALL BLOCKING OR BACKER MATERIAL FOR ATTACHMENT/MOUNTING OF
WALL HUNG ITEMS OR EQUIPMENT DESCRIBED IN THE DOCUMENTS.
11. FIRE RATED PARTITIONS: GA AND UL TEST NUMBERS MAY VARY DEPENDING
ON THE MANUFACTURER OF COMPONENTS ACTUALLY USED.
12. PROVIDE 5/8" TYPE "X" GYPSUM BOARD (UNLESS NOTED OTHERWISE)
13. PROVIDE TYPE "X" GYPSUM BOARD AT FIRE RATED PARTITIONS.
14. PROVIDE WATER RESISTANT TYPE GYPSUM BOARD AT AREAS THAT ARE
SCHEDULED TO RECEIVE CERAMIC TILE FINISH AND AT AREAS SO REQUIRED
BY CODE TO RECEIVE IT.
15. PROVIDE TILE BACKER BOARD AT SHOWER AREAS AND AT OTHER WET
AREAS THAT ARE SCHEDULED IN ROOM FINISH SCHEDULE TO RECEIVE
CERAMIC TILE FINISH.
16. PROVIDE VENEER PLASTER BASE BOARD WHERE PARTITION IS SCHEDULED
IN ROOM FINISH SCHEDULE TO RECEIVE VENEER PLASTER.
17. INSTALLATION OF GYPSUM BOARD, BACKER BOARD AND BASE BOARD SHALL
CONFORM TO REQUIREMENTS FOR FIRE RATINGS AND ACOUSTICAL
RATINGS.
18. TYPICAL FLOOR PLAN DIMENSIONS OF PARTITIONS ARE TO THE NOMINAL
FINISH FACE OF GYPSUM BOARD UNLESS NOTED TO THE CENTERLINE OF
THE PARTITION.
19. WHERE PARTITIONS AND/OR FURRING MEET, MAINTAIN A FLUSH SURFACE
ON THE SIDE WHERE THE FINISH IS STRAIGHT OR CONTINUOUS
UNLESS OTHERWISE NOTED.
F O
R H
E
IG
H T
R E
F E
R T
O S
U B
S C
R
IP
T
UNDERSIDE
OF FLOOR
OR ROOF
DECKING
CEILING
HEIGHT
FLOOR
LINE
STUDS TO
STRUCTURE,
GYP BD TO
6" ABOVE HIGHEST
ADJC. CEILING
SUBSCRIPT (S)
EXTEND TOTAL
PARTITION TO
STRUCTURE
NO SUBSCRIPT
EXTEND TOTAL
PARTITION TO
6" ABOVE ADJC.
CEILING (BRACE AS
NECESSARY)
SUBSCRIPT (T)
EXTEND TOTAL
PARTITION TO
CEILING (BRACE
AS NECESSARY)
SUBSCRIPT (C)
PARTITION HEIGHT IN
INCHES AS NOTED,
SEE ABOVE DETAIL
FOR OTHER
REQUIREMENTS
SUBSCRIPT (XX")
NO ACOUSTIC
INSULATION
SUBSCRIPT (N)
PARTITION TYPE SYMBOL AND SUBSCRIPT DEFINITIONS:
SA3 SA3
N
SA3
S
SA3
T
SA3
C
SA3
42"
A-002
A-002
A-002
A-002
ACOUSTIC INSULATION
FULL HEIGHT OF
CAVITY UNLESS NOTED
BY SUBSCRIPT "N"
RATED PARTITION
SUBSCRIPT (#H)
SA3
1H
SEE PLAN FOR
PARTITION TYPE
REFER TO
DRAWINGS FOR
BASE TYPE AND
LOCATION
SEALANT, ACOUSTIC
SEALANT WHERE
WALL TYPE
INDICATES
/2
/2
SEE PLAN FOR PARTITION TYPES
BOTTOM OF STRUCTURE
SEALANT
STRUCTURE
DEEP LEG RUNNER
HOLD STUDS 1 1/2" SHORT
TO ACCOMMODATE DECK
DEFLECTION, TYPICAL
EXTEND STUDS TO STRUCTURE
CEILING AS SCHEDULED,
REFER TO DRAWINGS
ONE LAYER 5/8"
TYPE X GYPSUM
BOARD (U.N.O.)
INSULATION
METAL STUD AT
16" O.C.
WALL WIDTH
"SA" SERIES
PTN
TYPE
STUD
WIDTH
WALL
WIDTH NOTES
SA3 3 5/8" 4 7/8"
SA6 6" 7 1/4"
ONE LAYER 5/8"
TYPE X GYPSUM
BOARD (U.N.O.)
INSULATION
METAL STUD AT
16" O.C.
"FC" SERIES
PTN
TYPE
STUD
WIDTH
WALL
WIDTH NOTES
FC3 3 5/8" 4 1/4"
FC1 1 5/8" 2 1/4"
TWO LAYERS 5/8"
TYPE X GYPSUM
BOARD
SOUND ATTENUATING
BATT. INSULATION
METAL STUD AT
16" O.C. (U.N.O.)
WALL WIDTH
"SC" SERIES
PTN
TYPE
STUD
WIDTH
WALL
WIDTH NOTES
SC3 3 5/8" 6 1/8"
SC6 6" 8 1/2"
STC 50 MINIMUM
STC 50 MINIMUM
2"
ADJACENT WALL
SWING DOOR -
REFERENCE SCHEDULE
REFERENCE PLAN FOR
PARTITION TYPE
/2
/2
T.O. METAL DECK
ACOUSTIC
SEALANT,
TYP. BOTH
SIDES
CLIP
B.O. METAL
DECK
5/8" GYPSUM
BOARD FIRE CODE
'X' CORE, TYP.
BOTH SIDES
TYPE
SEE WALL
TYPE
SEE WALL
MINERAL
FIBER
A PERPENDICULAR TO METAL DECKBPARALLEL TO METAL DECK
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:3
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-002
INTERIOR PARTITION
TYPES
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
3" = 1'-0"1
GYP WALL BASE
3" = 1'-0"3
PARTITION HEAD
3" = 1'-0"2
PARTITION HEAD
NO SCALE
PARTITION TYPES
1/2" = 1'-0"4
TYPICAL DOOR/FRAME LOCATION (U.N.O.)
3" = 1'-0"5
PARTITION HEAD
UP
GUARDMOUNT
STAIR 1
275A
PARTITION
ALCOVE
CATS
CATM CLASS
CATM STORAGE
JANITOR
CORRIDOR
UNISEX
UNISEX
CATM NCOIC
CONFERENCE
INSTRUCTORS ADMIN
CATM STORAGE
CORRIDOR
CORRIDOR
COMMANDER
262A
CLOSET
261A
CLOSET
CHIEF S.F.
1ST SERGEANT
SUPERINTENDENT
TRAINING NCOIC
265A
CLOSET
ARMS CLEANING/ISSUE
ARMS VAULT
CORRIDOR
OFFICE
UNIT LEARNING CENTER
MEN'S
SHOWERS
MENS LOCKER RM
MEN'S TOILET RM.
WOMEN'S
TOILET RM.
WOMENS
LOCKER RM.
WOMEN'S
SHOWERS
MECH/ELECTRICAL 202
VESTIBULE
NORTH CLASSROOM
SOUTH CLASSROOM
VENDING
STORAGE
CORRIDOR
212A
AUDIO/VISUAL
CLOSET
LOBBY
VESTIBULE
MOBILITY STORAGE
COVERED MOBILITY
STAGING
ALCOVE
264A
CLOSET
263A
CLOSET
CORRIDOR115
ROOM
COMM
COMAND
CONTROL
OFFICE
OFFICE
CORRIDOR
OFFICE
A B C
4.005
4.001
4.002
4.004
4.0014.0014.001
4.002
4.004
4.0014.001
4.002
4.003
4.003
4.001
4.006
4.004
4.007
DEMOLITION PLAN GENERAL NOTES:
1. THE GENERAL CONTRACTOR SHALL VERIFY ALL BUILDING AND SITE
CONDITIONS AND REPORT ANY DISCREPENCIES TO THE ARCHITECT
BEFORE PROCEEDING WITH ANY SCHEDULED DEMOLITION WORK.
2. THE GENERAL CONTRACTOR SHALL COORDINATE ARCHITECTURAL,
STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL, TECHNOLOGY, AND
PLUMBING WORK AND ALL SUBCONTRACTORS FOR DEMOLITION AND REPAIR
WORK.
3. IT IS THE INTENT OF THESE DRAWINGS TO INDICATE THE REMOVAL OF ALL
ITEMS WHICH INTERFERE WITH THE FINAL CONSTRUCTION AS SHOWN ON
THE FLOOR PLANS, ELEVATIONS, DETAILS, AND SCHEDULES. ALL FLOOR
FINISHES, BASE, ABANDONED FURNITURE, WINDOW TREATMENTS, SHELVING,
SIGNAGE, AND ROOFING MATERIALS SHALL BE DEMOLISHED IN THEIR
ENTIRETY.
4. REMOVE ALL ITEMS OF DEMOLITION WORK FROM THE PROJECT DAILY AND
DISPOSE OF PROPERLY.
5. EXISTING CONCRETE AND STEEL STRUCTURE TO REMAIN, TYP. PROTECT
COLUMNS, PILASTERS, BEAMS, AND SLABS.
6. THE EXISTING MECHANICAL, ELECTRICAL,TECHNOLOGY, AND PLUMBING
ITEMS AND/OR SYSTEMS, AND GAS, WATER AND ELECTRICAL METERS ARE
GENERALLY INTENDED TO REMAIN. WHERE WORK CONFLICTS WITH NEW
WORK, DEMOLITION OR REROUTING OF EXISTING INFRASTURCTURE SHALL
BE REQUIRED. REF: MEP FOR ALL ITEMS TO BE REUSED TYP. ALL ITEMS TO BE
DEMOLISHED SHALL BE REMOVED IN THEIR ENTIRETY, BACK TO THE ORIGINAL
SOURCE. SURROUNDING MATERIALS WHICH ARE DISTURBED OR
DEMOLISHED THAT ARE SCHEDULED TO REMAIN SHALL BE PATCHED WITH
LIKE SURROUNDING MATERIALS, TYPICAL.
7. DEMOLISH CONCRETE FLOOR SLABS AS REQUIRED TO INSTALL NEW
EQUIPMENT, UNDERGROUND CONDUIT, PLUMBING SYSTEMS, AND FLOOR
DRAINS, REF: STRUCTURAL, EQUIPMENT, ELECTRICAL, PLUMBING
DEMOLITION, AND PLUMBING DRAWINGS.
8. PROTECT EXISTING SURFACES TO REMAIN DURING DEMOLITION AND
CONSTRUCTION.
9. REPAIR OR REPLACE ANY EXISTING CONSTRUCTION (WINDOWS, WALLS,
DOORS, CEILINGS, FLOORS, ETC.) TO REMAIN WHICH ARE DAMAGED DURING
CONSTRUCTION. REPLACEMENT MATERIAL SHALL MATCH IN KIND.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
AD101
FIRST FLOOR
DEMOLITION PLAN
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
1/8" = 1'-0"1
FIRST FLOOR DEMOLITION PLAN
KEYED NOTES
4.001 REMOVE EXISTING FLOOR FINISHES INCLUDING MASTIC. PREP FLOOR FOR
INSTALLATION OF NEW FINISHES PER MANUFACTURERS RECOMMENDATIONS.
4.002 REMOVE SUSPENDED ACOUSTICAL CEILING SYSTEM.
4.003 REMOVE DOOR, FRAME AND HARDWARE.
4.004 SAW CUT AND REMOVE EXISTING CONCRETE SLAB AS REQUIRED FOR THE
INSTALLATION OF PLUMBING. SEE PLUMBING DRAWINGS FOR EXTENT OF WORK.
4.005 REMOVE PORTION OF WALL FOR NEW WINDOW, SEE SHEET A-101 AND A-401 FOR
REQUIREMENTS, LOCATION AND SIZE.
4.006 REMOVE PORTION OF WALL AS REQUIRED FOR INSTALLATION OF PLUMBING.
SEE PLUMBING DRAWINGS FOR EXTENT OF WORK.
4.007 REMOVE PORTION OF SUSPENDED CEILING SYSTEM AS REQUIRED FOR
INSTALLATION OF PLUMBING. SEE PLUMBING DRAWINGS FOR EXTENT OF WORK.
GUARDMOUNT
STAIR 1
275A
PARTITION
ALCOVE
CATS
CATM CLASS
CATM STORAGE
JANITOR
CORRIDOR
UNISEX
UNISEX
CATM NCOIC
CONFERENCE
INSTRUCTORS ADMIN
CATM STORAGE
CORRIDOR
CORRIDOR
COMMANDER
262A
CLOSET
261A
CLOSET
CHIEF S.F.
1ST SERGEANT
SUPERINTENDENT
TRAINING NCOIC
265A
CLOSET
ARMS CLEANING/ISSUE
ARMS VAULT
CORRIDOR
OFFICE
UNIT LEARNING CENTER
MEN'S
SHOWERS
MENS LOCKER RM
MEN'S TOILET RM.
WOMEN'S
TOILET RM.
WOMENS
LOCKER RM.
WOMEN'S
SHOWERS
MECH/ELECTRICAL 202
VESTIBULE
NORTH CLASSROOM
SOUTH CLASSROOM
VENDING
STORAGE
CORRIDOR
212A
AUDIO/VISUAL
CLOSET
LOBBY
VESTIBULE
MOBILITY STORAGE
COVERED MOBILITY
STAGING
ALCOVE
264A
CLOSET
263A
CLOSET
CORRIDOR
A-301
A-301
INVESTIGATION
COMMAND CONTROL
EX. SIPR
COMM
BREAK
OPEN OFFICE
TOILET
A-401
A B C FLOOR PLAN GENERAL NOTES:
1. SITE DATUM OF FINISHED FIRST FLOOR INDICATED ON SITE PLAN = 100'-0" ON
ARCHITECTURAL DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE
ATTENTION OF THE ARCHITECT/ENGINEER FOR FINAL DECISION.
3. ALL INTERIOR DIMENSIONS ARE FROM FINISH FACE OF WALLS (I.E. GYPSUM
WALLBOARD OR CMU), UNLESS NOTED OTHERWISE.
4. FINISH FLOOR ELEVATIONS ARE TO THE TOP OF CONCRETE, UNLESS NOTED
OTHERWISE.
5. REFERENCE SHEET G-011 AND G-021 FOR ALL CODE, FIRE RATING, AND
SEPARATION REQUIREMENTS.
6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR EXISTING CONSTRUCTION
(WALLS, DOORS, CEILINGS, FLOORS, ETC.) AS REQUIRED FROM DEMOLITION
OR CONSTRUCTION TO ALLOW FOR THE PREP WORK AND NEW OR
COMPLETION OF EXISTING FINISHES. REPAIRS OR REPLACEMENTS MUST BE
DURABLE, SEAMLESS, AND MATCH THE EXISTING MATERIAL.
7. GENERAL CONTRACTOR SHALL PATCH ALL FLOOR AND WALL PENETRATIONS
CAUSED BY DEMOLITION OF MECHANICAL, ELECTRICAL, TECHNOLOGY, AND
PLUMBING, INCLUDING BUT NOT LIMITED TO PIPING AND CONDUIT RUNS, IN A
MANNER THAT IS CONSISTENT WITH THE EXISTING FLOOR AND WALL
CONSTRUCTION AND FINISH. ALL PENETRATIONS SHALL MEET REQUIRED FIRE
RATINGS.
8. COORDINATE THE INSTALLATION OF ALL OWNER-SUPPLIED EQUIPMENT.
REFERENCE PLANS, SPECS, AND INTERIOR ELEVATIONS FOR SPECIFIC
EQUIPMENT AND ITS INSTALLATION REQUIREMENTS.
9. GENERAL CONTRACTOR SHALL PROVIDE BLOCKING, STIFFENERS, BRACINGS,
BACKING PLATES, SUPPORTING BRACKETS, AND NECESSARY SELECTIVE
DEMOLITION REQUIRED FOR THE PROPER INSTALLATION OF ALL CASEWORK,
TOILET ROOM ACCESSORIES, TOILET PARTITIONS AND MISCELLANEOUS
EQUIPMENT.
10. EXISTING AND INFILL CONCRETE SUB-FLOOR SHALL BE MADE LEVEL, PLUMB
AND IN SOUND CONDITION AS REQUIRED FOR THE INSTALLATION OF FINAL
FLOOR FINISHES, TYPICAL. PROVIDE ARDEX OR EQUAL LEVELING CONCRETE
TO PROVIDE A SMOOTH WALKABLE AREA.
11. ALL RECESSED CABINETS, PANELS, BOXES, ETC. LOCATED IN FIRE-RATED
PARTITIONS SHALL BE INSTALLED IN A MANNER WHICH MAINTAINS THE FIRE
RATED CONSTRUCTION.
12. SEE ENLARGED PLANS FOR NOTES, DIMENSIONS, AND WALL TYPES WITHIN
THE DETAIL CALLOUT BOUNDARIES.
13. REFERERNCE SHEET A-002 FOR INTERIOR PARTITION TYPES. INTERIOR
PARTITION TAGS NOTED ENCOMPASS THE ENTIRE LENGTH OF WALL SHOWN
TO CORNERS OF ROOM, OVER AND AROUND DOORWAYS SHOWN.
14. REFERENCE SHEET A601 FOR FINISHES SCHEDULE.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-101
FIRST FLOOR PLAN
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
1/8" = 1'-0"1
FIRST FLOOR PLAN
First Floor 100'-0"
A-301
UNIT LEARNING CENTER
CORRIDOR
COMM
ROOM
COMMAND CONTROL
3 4 5 6
4.1024.102
4.104
4.105
4.107
4.105
4.108
First Floor 100'-0"
TO MASONRY
114'-0"
ROOF EAVE
115'-0"
A-301
TOILET
CORRIDOR
A B
OPEN OFFICE
BREAK
4.108
4.102
4.103
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-301
BUILDING SECTIONS
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
1/4" = 1'-0"1
BUILDING SECTION
1/4" = 1'-0"2
BUILDING SECTION
KEYED NOTES
4.102 EXTEND EXISTING PARTITION WALL TO DECK. MATCH EXISTING
WALL CONSTRUCTION AND FINISH.
4.103 INFILL OPENING IN EXISTING WALL, MATCH EXISTING WALL
CONSTRUCTION AND FINISH.
4.104 SOLID SURFACE COUNTERTOP WITH TRANSACTION DRAWER ,
SEE DETAIL 1/A-501.
4.105 MONITORS, OWNER FURNISHED. PROVIDE BLOCKING IN WALL
FOR MONITOR WALL BRACKET INSTALLATION.
4.107 RELOCATION OF EXISTING COMM. RACK. BY OWNER.
4.108 WORK STATION, OWNER FURNISHED.
A-301
A-301
A-401 2
CORRIDOR
CORRIDOR
OFFICE
UNIT
LEARNING
CENTER
SOUTH
CLASSROOM
VENDING
MOBILITY
STORAGE
CORRIDOR
EX. SIPR
COMMAND CONTROL
TOILET
INVESTIGATION
COMM
OPEN OFFICE
/2
/2
7'-5 1/2" 7'-5" 12'-8 1/2"
/2
BREAK
A
A
1002A
A B
A-401
4 5
/2
7'-3" 13'-2" 7'-1 1/2"
W1
SA3
T
SA3
T
SC3
6'-3 1/2"
FC1
T
SC3 SA3
SC3
FC6
T
TPD
GB-1
GB-3
GB-2
LSD MIR
PTD
W2
FC3
T
SA3
T
/2
LAV
FD
4.101
4.102
4.102
4.103
4.103
4.104
4.1054.105
4.106
4.107
4.1074.107
4.108
4.109
4.1104.110
5' -6
3'-0" 1'
-6
SA3
T
SA3
S
3'-10 1/2"
1003A
SA3
T
FC64.111
4.111 4.111
4.112
4.113
4.101
4.1014.101
4.115
FLOOR PLAN GENERAL NOTES:
1. SITE DATUM OF FINISHED FIRST FLOOR INDICATED ON SITE PLAN = 100'-0" ON
ARCHITECTURAL DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE
ATTENTION OF THE ARCHITECT/ENGINEER FOR FINAL DECISION.
3. ALL INTERIOR DIMENSIONS ARE FROM FINISH FACE OF WALLS (I.E. GYPSUM
WALLBOARD OR CMU), UNLESS NOTED OTHERWISE.
4. FINISH FLOOR ELEVATIONS ARE TO THE TOP OF CONCRETE, UNLESS NOTED
OTHERWISE.
5. REFERENCE SHEET G-011 AND G-021 FOR ALL CODE, FIRE RATING, AND
SEPARATION REQUIREMENTS.
6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR EXISTING CONSTRUCTION
(WALLS, DOORS, CEILINGS, FLOORS, ETC.) AS REQUIRED FROM DEMOLITION
OR CONSTRUCTION TO ALLOW FOR THE PREP WORK AND NEW OR
COMPLETION OF EXISTING FINISHES. REPAIRS OR REPLACEMENTS MUST BE
DURABLE, SEAMLESS, AND MATCH THE EXISTING MATERIAL.
7. GENERAL CONTRACTOR SHALL PATCH ALL FLOOR AND WALL PENETRATIONS
CAUSED BY DEMOLITION OF MECHANICAL, ELECTRICAL, TECHNOLOGY, AND
PLUMBING, INCLUDING BUT NOT LIMITED TO PIPING AND CONDUIT RUNS, IN A
MANNER THAT IS CONSISTENT WITH THE EXISTING FLOOR AND WALL
CONSTRUCTION AND FINISH. ALL PENETRATIONS SHALL MEET REQUIRED FIRE
RATINGS.
8. COORDINATE THE INSTALLATION OF ALL OWNER-SUPPLIED EQUIPMENT.
REFERENCE PLANS, SPECS, AND INTERIOR ELEVATIONS FOR SPECIFIC
EQUIPMENT AND ITS INSTALLATION REQUIREMENTS.
9. GENERAL CONTRACTOR SHALL PROVIDE BLOCKING, STIFFENERS, BRACINGS,
BACKING PLATES, SUPPORTING BRACKETS, AND NECESSARY SELECTIVE
DEMOLITION REQUIRED FOR THE PROPER INSTALLATION OF ALL CASEWORK,
TOILET ROOM ACCESSORIES, TOILET PARTITIONS AND MISCELLANEOUS
EQUIPMENT.
10. EXISTING AND INFILL CONCRETE SUB-FLOOR SHALL BE MADE LEVEL, PLUMB
AND IN SOUND CONDITION AS REQUIRED FOR THE INSTALLATION OF FINAL
FLOOR FINISHES, TYPICAL. PROVIDE ARDEX OR EQUAL LEVELING CONCRETE
TO PROVIDE A SMOOTH WALKABLE AREA.
11. ALL RECESSED CABINETS, PANELS, BOXES, ETC. LOCATED IN FIRE-RATED
PARTITIONS SHALL BE INSTALLED IN A MANNER WHICH MAINTAINS THE FIRE
RATED CONSTRUCTION.
12. SEE ENLARGED PLANS FOR NOTES, DIMENSIONS, AND WALL TYPES WITHIN
THE DETAIL CALLOUT BOUNDARIES.
13. REFERERNCE SHEET A-002 FOR INTERIOR PARTITION TYPES. INTERIOR
PARTITION TAGS NOTED ENCOMPASS THE ENTIRE LENGTH OF WALL SHOWN
TO CORNERS OF ROOM, OVER AND AROUND DOORWAYS SHOWN.
14. REFERENCE SHEET A601 FOR FINISHES SCHEDULE.
GB-2
GB-3
GB-1
TPD
LSD
MIR
LAV
PTDPTD
LAV
LSD
MIR
TPD
GB1
GB3
GB2
3'-0" 2'-6"
A-421
4.202
4.202
4.201
4.203
4.204
A-421
FD = FLOOR DRAIN (PITCH FLOOR TO DRAIN)
GB1 = GRAB BAR (42" L. x 33" A.F.F.)
GB2 = GRAB BAR (36" L. x 33" A.F.F.)
GB3 = GRAB BAR (18" L. x 39" A.F.F.)
LSD = LIQUID SOAP DISPENSER
MIR = MIRROR (2'-0"w. x 3'-10"h.)
PTD = PAPER TOWEL DISPENSER
TPD = (2) TOILET PAPER DISPENSERS - (2 ROLL)
TOILET ROOM ACCESSORY GENERAL NOTES:
1. PROVIDE BLOCKING IN WALLS FOR ALL WALL MOUNTED ACCESSORIES.
2. PROVIDE WATER RESISTANT GYPSUM WALLBOARD AT ALL WET AREAS AND/OR
AREAS TO RECEIVE WALL TILE.
3. PROVIDE MOISTURE AND MOLD RESISTANT GYPSUM BOARD, AND TILE BACKING
GYPSUM BOARD AS SPECIFIED AND AS REQUIRED BY THE BUILDING CODE.
4. SEE "ARCHITECTURAL FINISH LIST" IN SPECIFICATIONS FOR MATERIAL INFORMATION.
5. SEE SHEET A-601 FOR "WALL FINISH" AND "FLOOR FINISH" ABBREVIATIONS.
6. SEE SHEET A-402 FOR "CEILING FINISH" ABBREVIATIONS.
7. SEE DETAIL 6/A-401 FOR ALL TOILET ACCESSORY MOUNTING HEIGHTS.
TOILET ACCESSORY KEY
SEE SPECIFICATIONS
FOR MODEL NUMBERS
FLOOR LINE
MAX
6"
MAX
1'-0"
T
O
GRAB BAR,
REQD (GB3)
GRAB BAR,
REQD (GB1)
GRAB
BAR,
REQD
(GB2)
(2) TOILET PAPER
HOLDER DBL
ROLL (TPH)
41"
39" TO
MIN
3'-6"
1'-6" 8"
MIN
3'-0"
A D
A R
E Q
M A
X
SOAP
DISPENSER
(SD)
MIRROR
(MIR)
LAVATORY
(LAV) (WALL
MOUNTED)
2'-0"
M A
X
M A
X
PAPER
TOWEL
DISP.
(PTD)
FLOOR
MOUNT
TOILET
M
A X
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-401
ENLARGED FLOOR
PLAN
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
1/4" = 1'-0"1
ENLARGED FLOOR PLAN
KEYED NOTES
4.101 NEW SLAB IN FILL AS REQUIRED FOR THE INSTALLATION OF NEW PIPING.
MATCH EXISTING 4" THICK CONCRETE FLOOR AND FLOOR FINISH. DRILL AND
EPOXY 12" LONG #4 REBAR AT 24" O.C. MINIMUM 5" EMBEDMENT. RESTORE
FLOOR FINISH TO MATCH EXISTING.
4.102 EXTEND EXISTING PARTITION WALL TO DECK. MATCH EXISTING WALL
CONSTRUCTION AND FINISH.
4.103 INFILL OPENING IN EXISTING WALL, MATCH EXISTING WALL CONSTRUCTION
AND FINISH.
4.104 SOLID SURFACE COUNTERTOP WITH TRANSACTION DRAWER , SEE DETAIL
1/A-501.
4.105 MONITORS, OWNER FURNISHED. PROVIDE BLOCKING IN WALL FOR MONITOR
WALL BRACKET INSTALLATION.
4.106 LOCKERS SEE SPECIFICATIONS. SEE BASE DETAIL 2/A-421 .
4.107 RELOCATION OF EXISTING COMM. RACK. BY OWNER.
4.108 WORK STATION, OWNER FURNISHED.
4.109 COMMAND CONTROL DESK, OWNER FURNISHED.
4.110 INVESTIGATION ROOM FURNITURE, OWNER FURNISHED.
4.111 PARTITION HEAD MUST BE SEALED TO METAL DECK, SEE DETAIL 5/A-002.
4.112 (4) 12" DEEP X VERIFIED WIDTH SHELVES COORDINATE SPACING WITH OWNER.
4.113 PATCH AND REPAIR EXISTING WALL AS REQUIRED FOR INSTALLATION OF NEW
PLUMBING. MATCH EXISTING WALL CONSTRUCTION AND PREP FOR NEW
FINISH.
4.115 RECESSED FIRE EXTINGUISHER CABINET.
4.201 CERAMIC WALL TILE.
4.202 FINISHED END PANEL ON CABINET.
4.203 MICROWAVE, BY OWNER.
4.204 COFFEE MAKER, BY OWNER,
1/4" = 1'-0"3
INTERIOR ELEVATION
1/4" = 1'-0"5
INTERIOR ELEVATION
1/4" = 1'-0"4
INTERIOR ELEVATION
1/4" = 1'-0"2
INTERIOR ELEVATION
1/4" = 1'-0"6
TOILET ACCESSORY MOUNTING HEIGHTS
A-301
A-301
A B
ACP-1
9'-0"
ACP-1
9'-0"
ACP-2
9'-0"
ACP-1
9'-0"
ACP-1
9'-0"
ACP-1
9'-0"
4.114
2' x 2' SUSPENDED CEILING GRID
LIGHT FIXTURE (RECESSED MOUNTED)
GYPSUM BOARD CEILING/
PORTLAND CEMENT PLASTER (PAINTED)
LIGHT FIXTURE (SURFACE MOUNTED)
SUPPLY AIR DIFFUSER
RETURN AIR DIFFUSER / EXHAUST GRILL
LIGHT FIXTURE (RECESSED CAN)
LIGHT FIXTURE (SURFACE MOUNTED)
EXHAUST FAN
LIGHT FIXTURE (SUSPENDED)
LIGHT FIXTURE (SUSPENDED)OR
CEILING PLAN LEGEND: SEE ELECTRICAL FOR
EXACT FIXTURE MODEL
LIGHT FIXTURE (RECESSED MOUNTED 4" WIDE OR LESS)
8"6"
CEILING RECEPTACLES
CEILING OCCUPANCY SENSOR
CEILING FIRE ALARM DEVICES
CEILING MASS NOTIFICATION DEVICE
CEILING SPEAKER
SPRINKLER HEADS
CEILING SECURITY STRODE
CEILING CAMERA
LIGHT FIXTURE (RECESSED MOUNTED)OR
XX-X
X'-X" ELEVATION ABOVE FINISHED FLOOR
CEILING TYPE
CEILING TYPE TAG
CEILING PLAN GENERAL NOTES:
1. SEE ROOM FINISH SCHEDULE FOR FLOOR, WALL AND CEILING FINISHES AND
ROOM HEIGHTS.
2. FIELD VERIFY ALL DIMESIONS, BRING ANY DISCREPANCIES TO THE
ATTENTION OF THE ARCHITECT FOR FINAL DECISION.
3. ALL RECESSED LIGHTS, SPRINKLERS, FIRE DETECTION EQUIPMENT,
OCCUPANCY SENSORS, ETC. SHALL BE CENTERED IN THE TILES UNLESS
NOTED OTHERWISE.
4. CENTER ALL CEILING GRIDS IN SPACE UNLESS NOTED OTHERWISE.
5. ALL METAL LINEAR DIFFUSERS SHALL BE PAINTED TO MATCH SURROUNDING
WALL OR CEILING CURFACE.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-402
ENLARGED CEILING
PLAN
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
1/4" = 1'-0"1
ENLARGED CEILING PLAN
03/30/20 B2 PREFINAL
KEYED NOTES
4.114 PATCH AND REPAIR EXISTING SUSPENDED CEILING SYSTEM AS REQUIRED
FOR INSTALLATION OF NEW PLUMBING. MATCH EXISTING FINISH.
S
E E
L E
V A
T
IO
N S
S E
E E
L E
V A
T
IO
N S
S E
E E
L E
V A
T
IO
N S
/2
/2
/2
2'-0"
1'-3"
BLOCK/NAILER
AS REQUIRED
BLOCK/NAILER
AS REQUIRED
PLASTIC LAMINATE ON
ALL EXPOSED SURFACES
OF 3/4" PARTICLE BOARD
PLASTIC LAMINATE CLAD
INTERIOR TO MATCH
CABINET FACE
MELAMINE CLAD INTERIOR
WITH ADJUSTABLE SHELF
DOORS - OVERLAY MOUNT
PLASTIC LAMINATE
2x CONT. WOOD BLOCKING
RUBBER BASE, RB-1
SEALANT
2'-1"
DOOR HARDWARE
SEE RCP
SIDESPLASH WHERE COUNTER
ABUTS WALL (TYP.)
1'-0"
COORDINATE SIZE
REQUIREMENTS
WITH OWNER FOR
APPLIED
BACKSPLASH
SOLID SURFACE COUNTERTOP
WITH ROUNDED EDGE
S E
E E
L E
V A
T
IO
N S
S E
E E
L E
V A
T
IO
N S
S E
E E
L E
V A
T
IO
N S
/2
/2
/2
2'-0"
1'-0"
BLOCK/NAILER
AS REQUIRED
BLOCK/NAILER
AS REQUIRED
PLASTIC LAMINATE ON
ALL EXPOSED SURFACES
OF 3/4" PARTICLE BOARD
MELAMINE CLAD
INTERIOR WITH
ADJUSTABLE SHELVES,
SUPPLY (2) SHELVES MIN
MELAMINE CLAD INTERIOR
DOORS - OVERLAY MOUNT
PLASTIC LAMINATE
2x CONT. WOOD
BLOCKING
RUBBER BASE, RB-1
SEALANT
2'-1"
DOOR HARDWARE
APPLIED
BACKSPLASH
SOLID SURFACE COUNTERTOP
WITH ROUNDED EDGE
SEE RCP
LOCKER, SEE SPECIFICATION
MANUFACTURERS LOCKER BASE,
SEE SPECIFICATIONS
ANCHOR EVERY THIRD LOCKER
WITH WOOD SCREWS
CONTINUE FLOOR AND
BASE FINISH
CONT. SLOPED TOP (TYP.)
ANCHOR MIN. EVERY THIRD
LOCKER WITH WOOD SCREWS
CONT. 1x2 FURRING BY G.C.
SEE FLOOR PLANS FOR
PARTITION TYPE
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-421
CASEWORK DETAILS
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
Author
PJC
03/30/2020
Designer
1 1/2" = 1'-0"1
CABINETRY SECTION
1 1/2" = 1'-0"3
CABINETRY SECTION
1" = 1'-0"2
LOCKER BASE
3/4" SOLID SURFACE MATERIAL
OVER 3/4" PLYWOOD.
SEE FLOOR PLAN FOR PARTITION TYPE
B.O. WINDOW
102'-8"
B.O. WINDOW
107'-4"
BULLETPROOF WINDOW UNIT
6" 6" 2'-1"
EXISTING CMU PARTTION
(2)L4x3-1/2x1/4 WITH 4" MINIMUM BEARING
3'-4"
2" 3'-0" 2"
3/4" SOLID SURFACE MATERIAL
OVER 3/4" PLYWOOD.
BULLETPROOF WINDOW UNIT
SEE FLOOR PLAN FOR
PARTITION TYPE
EXISTING CMU PARTTION
SEALANT
SEALANT
SEALANT
SECTION A-A
PLAN VIEW
T.O. COUNTER
102'-9 1/2"
DRAWER MANUFACTURER
DIM. PER TRANSACTION
D R
A W
E R
M A
N U
F A
C T
U R
E R
D
IM
P
E R
T R
A N
S A
C T
IO
N
D
IS
T A
N C
E
M A
X T
R A
V E
L
B
B
A
A
PREFABRICATED COUNTER SUPPORT
AS SPECIFIED. PROVIDE QUANTITY
PER SUPPORT MANUFACTURER'S
REQUIREMENTS.
ANCHOR PRE MANUFACTURES
REQUIREMENTS - PROVIDE
BLOCKING IN WALLS
3/4" SOLID SURFACE MATERIAL
OVER 3/4" PLYWOOD.
SEE FLOOR PLAN FOR PARTITION TYPE
EXISTING CMU PARTTION
(2)L4x3-1/2x1/4 WITH 4" MINIMUM BEARING
SEALANT
SECTION B-B
T.O. COUNTER
102'-9 1/2"
SECURITY TRANSITION DRAWER UNIT
DRAWER MANUFACTURER
DIM. PER TRANSACTION
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-501
DETAILS
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
1 1/2" = 1'-0"1
SECURITY WINDOW
F
FLUSH DOOR
SCHED.
SEE
S E
E S
C H
E D
HG
HALF GLASS DOOR
S E
E S
C H
E D
SCHED.
SEE
8" 1'-8" 8"
GL-1
F1
S E
E S
C H
E D
2"
SCHED.
SEE 2"
SEE PLAN FOR
PARTITION TYPE
CONTINUOUS SEALANT
(BOTH SIDES)
DOOR FRAME (SEE SCHEDULE)
STEEL STUD DOUBLE
BOX HEADER
DOOR (SEE SCHEDULE)
1/2" WALL 1/2"
JAMB
D O
O R
O P
E N
IN
G
O P
E N
IN
G
S
M
IN
/2
A T
F
IR
E R
A T
E D
/2
W
A L
L
/2
J A
M B
DOOR (SEE SCHEDULE)
DOOR FRAME (SEE SCHEDULE)
JAMB ANCHORS (3 PER JAMB)
DOUBLE STUDS
SEE PLAN FOR PARTITION TYPE
2" DOOR OPENING
CONTINUOUS SEALANT
OPENINGS
MIN. 1/2" AT
FIRE RATED
WALL
WINDOW UNIT
(SEE SCHEDULE)
GLAZING, SEE SCHEDULE
1/2"1/2"
GLAZING STOPS
CONTINUOUS SEALANT
(BOTH SIDES)
SEE PLAN FOR PARTITION TYPE
STEEL STUD DOUBLE
BOX HEADER
W A
L L
WINDOW UNIT (SEE SCHEDULE)
GLAZING, SEE SCHEDULE
JAMB ANCHORS
DOUBLE STUD JAMBS
/2
/2
GLAZING STOPS
CONTINUOUS SEALANT (BOTH SIDES)
SEE PLAN FOR PARTITION TYPE
NOTE : SILL SIMILAR
First Floor 100'-0"
10'-1 1/2"
/2
/2
2 1/2" 3'-1"
2 1/2"
3'-1"
2 1/2"
3'-1" 2 1/2"
GL-1 GL-1GL-1
A-601
A-601
First Floor 100'-0"
" 2
3'-4"
2" 3'-0" 2"
GL-2
A-501
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:0
:4
A
M C
R e v it L o c a l\
-1
.0
-A
-C E
N T
R A
L -2 m a rk
.b ra it h w a it e .r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
A-601
SCHEDULES
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
MAB
PJC
03/30/2020
TMH
DOOR AND HARDWARE SCHEDULE
DOOR
NUMBER
DOOR FRAME MISCELLANEOUS
REMARKS
LEAF SIZE
TYPE MAT'L
GLAZING
TYPE FINISH TYPE MAT'L
DETAILS
FINISH LABEL
HDWR
SETQTY. WIDTH HEIGHT HEAD JAMB OTHER
1000A (1) 3'-0" 7'-0" F HM - PT F1 HM 3A-601 4/A-601 - PT 4 2
1001A (1) 3'-0" 7'-0" F HM - PT F1 HM 3A-601 4/A-601 - PT 1
1002A (1) 3'-0" 7'-0" F HM - PT F1 HM 3A-601 4/A-601 - PT 3 1
1003A (1) 3'-0" 7'-0" HG HM GL1 PT F1 HM 3A-601 4/A-601 - PT 2
DOOR AND HARDWARE SCHEDULE ABBREVIATIONS
DOOR/FRAME MATERIALS
HM = HOLLOW METAL
FINISH
PT = PAINT
GLAZING
GL-1 GLAZING, SEE SPECIFICATIONS
DOOR AND HARDWARE SCHEDULE GENERAL NOTES
1. UNDERCUT DOOR
2. STC 50 DOOR AND FRAME ASSEMBLY.
NO SCALE
DOOR TYPES
NO SCALE
FRAME TYPES
ROOM FINISH SCHEDULE
ROOM
NO. ROOM NAME FLOOR BASE
WALLS CEILING
REMARKSNORTH EAST SOUTH WEST MTL HEIGHT
1000 INVESTIGATION CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACP-1 9'-0"
1001 BREAK RFT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACP-1 9'-0"
1002 TOILET RFT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACP-2 9'-0"
1003 OPEN OFFICE RFT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACP-1 9'-0"
1005 COMMAND CONTROL RFT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACP-1 9'-0"
3" = 1'-0"3
INTERIOR DOOR HEAD
3" = 1'-0"4
INTERIOR DOOR JAMB
3" = 1'-0"5
INTERIOR WINDOW HEAD
3" = 1'-0"6
INTERIOR WINDOW JAMB
1/4" = 1'-0"1
WINDOW TYPE W1
1/4" = 1'-0"2
WINDOW TYPE W2
ARCHITECTURAL FINISHES SCHEDULE
FINISH
NUMBER FINISH DESCRIPTION
PRODUCT DESCRIPTION
REMARKSMANUFACTURER
MODEL
NUMBER STYLE COLOR SIZE
ACP-1 ACCOUSTIC CEILING PANEL - TYPE 1 ARMSTRONG 556 CIRRUS BEVELED TEGULAR WHITE 24" x 24"
ACP-2 ACCOUSTIC CEILING PANEL - TYPE 2 ARMSTRONG
CT-1 CERAMIC TILE - TYPE 1
GR-1 GROUT COLOR - TYPE 1
PL-1 PLASTIC LAMINATE - TYPE 1 WILSONART D92-60 DOVE GREY
PT-1 PAINT COLOR - TYPE 1 SHERWIN WILLIAMS 2134-70 GENESSE WHITE
PT-2 PAINT COLOR - TYPE 2 SHERWIN WILLIAMS AIR GUARD ARCHITECTURAL BROWN
RB-1 RUBBER WALL BASE - TYPE 1 ARCHITECTURAL BROWN 6"
RFT-1 RUBBER FLOOR TILE - TYPE 1 NORA GRANO 5310 HELICHRYSUM 24" x 24"
SS-1 SOLID SURFACE - TYPE 1 CORIAN
FIRE PROTECTION SYMBOLS:
FIRE DEPARTMENT CONNECTION
ORIFICE
FLOW SWITCH
ALARM BELL
ISOLATION VALVE
GATE VALVE
PRESSURE GAUGE
CHECK VALVE
VALVE SUPERVISION/TAMPER
SWITCH
STRAINER
T
PIPE DROP
PIPE RISE
STRAINER
FIRE PROTECTION
GROUP PATTERN LEGEND:
LIGHT HAZARD
ORDINARY HAZARD GROUP 1
ORDINARY HAZARD GROUP 2
FIRE PROTECTION GENERAL NOTES
1. ABBREVIATIONS INDICATED HERE AND NOT USED IN THE CONTRACT
DOCUMENTS DO NOT APPLY TO THIS PROJECT. ADDITIONAL ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
2. THESE DRAWINGS ARE DESIGN DRAWINGS AND ARE DIAGRAMMATIC, THEY MAY
NOT SHOW ALL PHYSICAL ARRANGEMENTS, OFFSETS, BENDS, OR ELBOWS
WHICH MAY BE REQUIRED FOR PROPER INSTALLATION OF VARIOUS
MATERIALS, EQUIPMENT, AND PIPING SYSTEMS IN ALLOTTED SPACES. EXAMINE
THESE AND OTHER AVAILABLE DRAWINGS TO DETERMINE SPACE LIMITATIONS
AND INTERFERENCES. MAKE ANY MINOR CHANGES IN LOCATIONS OF
EQUIPMENT, AND PIPING FROM THAT SHOWN ON DRAWINGS AND FOR ALL
PHYSICAL DETAILS REQUIRED FOR INSTALLATION. COST FOR ADAPTING WORK
TO JOB SITE CONDITIONS SHALL NOT BE CONSIDERED AS BASIS OF AN EXTRA
COST TO CONTRACT.
3. ELEVATION OF PIPING INDICATED ON THESE DRAWINGS ARE TO BE USED AS
GUIDELINES TO ASSIST WITH INSTALLATIONS. MINOR CHANGES TO THESE
ELEVATIONS MAY BE NECESSARY TO ELIMINATE UNFORESEEN
INTERFERENCES. ANY CHANGE IN ELEVATION SHALL BE APPROVED PRIOR TO
CHANGE.
4. ANY AND ALL INFORMATION SHOWN ON THESE DRAWINGS WITH RESPECT TO
EXISTING STRUCTURES, UTILITIES, AND MECHANICAL SYSTEMS, IS AS EXACT AS
COULD BE SECURED. THE INFORMATION IS NOT WARRANTED NOR
GUARANTEED ACCURATE, FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
PROCEEDING WITH WORK.
5. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS. CONTRCTOR SHALL
VERIFY ALL CONDITIONS AND DIMENSIONS AT THE PROJECT SITE PRIOR TO THE
START OF CONSTRUCTION. WHERE SPECIFIC DEMENSIONS, DETAILS OR
DESIGN INTENT CANNOT BE DETERMIND, CONSULT COR BEFORE PROCEEDING
WITH THE WORK.
6. SEQUENCE OF WORK AND/OR PLACE OF COMMENCEMENT OF WORK SHALL BE
APPROVED PRIOR TO WORK BEING STARTED. SCHEDULED SHUTDOWNS SHALL
BE CLOSELY COORDINATED WITH OWNER & EXISTING OPERATIONS.
7. ACCURATE AND LEGIBLE RECORD (AS-BUILT) DRAWINGS SHALL BE MAINTAINED
AT THE JOB SITE, AND BE SUBMITTED PRIOR TO FINAL PAYMENT.
8. ALL EXISTING ROOFING SYSTEMS SHALL BE PROTECTED FROM DAMAGE
DURING CONSTRUCTION ACTIVITIES.
9. TEMPORARILY PATCH ALL ROOF OPENINGS WATERTIGHT UNTIL FINAL CLOSURE
CAN BE MADE.
10. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH OWNER PRIOR TO
INSTALLATION.
11. ALL SPRINKLER IN ACOUSTICAL CELINGS SHALL BE LOCATED IN THE CENTER
OF CEILING TILE.
12. PROVIDE CONCEALED SPRINKLER HEADS IN ALL FINISHED AREAS.
13. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILINGS TYPES AND
HEIGHTS.
14. VISIT THE BUILDING SITE & BECOME THOROUGHLY FAMILIAR WITH ALL EXISTING
CONDITIONS AFFECTING WORK.
15. NOMINAL FINISHED FLOOR ELEVATION = 100.0 FT. UNLESS OTHERWISE NOTED.
FIRE PROTECTION NOTES
1. PROVIDE A HYDRAULICALLY DESIGNED WET PIPE SPRINKLER SYSTEM FOR
HAZARD CLASSIFICATION SHOWN. SYSTEM SHALL BE IN CONFORMANCE WITH
THE FOLLOWING CODES AND STANDARDS:
A. A. ANG ETL 15-01-04.
B. UFC 3-600-01 (8 AUGUST 2016)
C. NFPA 13 (LATEST PREVAILING EDITION)
D. BATTLECREEK BASE STANDARDS
E. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) STANDARDS
2. ANG AND UFC SPECIFIC DESIGN REQUIREMENTS INCLUDE BUT NOT LIMITED TO
THE FOLLOWING:
A. USE AREA / DENSITY METHOD TO DETERMINE WATER DEMAND
REQUIREMENTS
B. USE VALUES SHOWN IN TABLE 9-4 UFC 3-600-01 (DOD) IN-LIEU OF
EQUIVELENT TABLE IN NFPA 13.
C. PROVIDE VALVED OUTLETS TO DRAIN ALL PIPING. ESTEND DRAIN PIPING
TO EXTERIOR.
D. PROVIDE SUPERVISORY SWITCHES ON ALL ISOLATION VALVES INSTALLED
IN CIRCUITS TO ANY SPRINKLERS.
E. VERIFY ALL EQUIPMENT LOCATIONS AND PIPE ROUTING WITH COR PRIOR
TO INSTALLATION.
F. PROVIDE IDENTIFICATION TAGS ON SPECIFIC COMPONENTS. SEE
SPECIFICATIONS.
G. PAINT EXPOSED PIPE. SHOW FLOW DIREDTION AND PIPE IDENTIFICATION.
H. PROVIDE SPLASH BLOCKS FOR DRAINS.
I. INSTALL EXTENDED SLEEVES AT ALL WALL PENETRATIONS.
J. FPE STAMP REQUIRED ON ALL FIRE PROTECTION SUBMITTALS.
WATER SUPPLY FLOW BASIS OF BID:
NOTE: BASIS FOR BID SHOWN. NOT FOR DESIGN.
FIRE SPRINKLER DESIGN/INSTALLATION CONTRACT SHALL CONDUCT WATER
FLOW TEST AND USE RESULTS IN HYDRAULIC CALCULATIONS
A B
UNIT
LEARNING
CENTER
VENDING
CORRIDOR
CORRIDOR
OFFICE
MOBILITY
STORAGE
228COMMAND
CONTROL
EX. SIPR
TOILET
INVESTIGATION
BREAK
OPEN
OFFICE
COMM
CORRIDOR
5.101
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
/3
/2
:3
:2
A
M c o rp .m e a d h u n t.
c o m
\s h a re d fo ld e rs
\e n tp
\3
\1
.0
\T E
C H
\C A
D \3
-1
.0
-P
-C E
N T
R A
L -2
.r v t
M
IC
H
IG
A N
A
IR
N A
T
IO
N A
L G
U A
R D
B A
T T
L E
C R
E E
K A
N G
B B
A T
T L E
C R
E E
K M
IC
H
IG
A
N
A L T
E R
B D
O C
F-001
SYMBOLS,
ABBREVIATIONS,
NOTES AND DETAILS
NOT FOR CONSTRUCTION
MBMV172815ANG NO.:
3141900-191875.01
JET
RMM
03/30/2020
JET
ANG AIR NATIONAL GUARD
AFF ABOVE FINISHED FLOOR
BPD BACKFLOW PREVENTION DEVICE
CW COLD WATER
DCVA DOUBLE CHECK VALVE ASSEMBLY
DI DUCTILE IRON
DOD DEPARTMENT OF DEFENSE
FDC FIRE DEPARTMENT CONNECTION
FH FIRE HYDRANT
FPE PROFESSIONAL FIRE PROTECTION
ENGINEER
PIV POST INDICATOR VALVE
SP SPRINKLER MAIN ENGINEER
TFB TO FLOOR BELOW
UFC UNIFIED FACILITIES CRITERIA
FIRE PROTECTION ABBREVIATIONS
1/4" = 1'-0"1
FIRE PROTECTION PLAN
EXTRA (H-3) 500 (1900) 500 (1900) 90
ORDINARY (H-2) 250 (950) 500 (1900) 60
LIGHT (H-1) 250 (950) 500 (1900) 60
CEILING HEIGHT 60 FT.
OR LESS (18.3m)
CEILING HEIGHT
GREATER THAN 60 FT.
(18.3m)
HAZARD
CLASIFICATION
HOSE DEMAND, gpm (lpm)
DURATION, MIN
Table 9-4 Hose Stream Demand and Duration
K-factor 11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
25.2 (360)
N/A
EXTRA
(H-3)
DESIGN
.3/2500 (12/230)
.3/3500 (12/330)
.3/3600 (12/340)
.3/4600 (12/430)
.5/3000 (20/280)
.5/4000 (20/370)
12.0 @ 7 psi
N/A
K-factor 8.0
(115) 8.0
(115) 11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
25.2 (360)
N/A
ORDINARY
(H-2)
DESIGN
.2/2500 (8/230)
.2/3500 (8/330)
.2/2500 (8/230)
.2/3500 (8/330)
.2/2500 (8/230)
.2/3500 (8/330)
12.0 @ 7 psi
N/A
K-factor 5.6 (80)
5.6 (80)
11.2 (160)
11.2 (160)
11.2 (160)
11.2 (160)
25.2 (360)
N/A
LIGHT
(H-1)
DESIGN
.1/1500 (4/140)
.1/1500 (4/140)
.2/2500 (8/230)
.2/3500 (8/330)
.2/2500 (8/230)
.2/3500 (8/330)
12.0 @ 7 psi
N/A
WET DRY WET DRY WET DRY WET DRY
HAZARD
CLASIFICATION
CEILING HEIGHT
UP TO 30 FT.
(9.1m)
CEILING HEIGHT
UP TO >30-45FT.
(9.1-13.7m)
CEILING HEIGHT
UP TO 45-60 FT.
(13.7-18.3m)
CEILING
HEIGHT UP TO
60-100 FT.
(18.3m-30.5)
(gpm/ft²)/ft² (mm/min)/m² [minimum K factor]
Table 9-3 Sprinkler Design Demand and Minimum K-Factor
KEYED NOTES
5.101 REVISE EXISTING SPRINKLER SYSTEM TO ACCOMMODATE NEW PARTITION
WALL LAYOUT.
PIPING SYMBOLS
PIPE TURNED TOWARD
PIPE TURNED AWAY
PIPE TURNED AWAY
UNION
FLANGES
PIPE CAP
FLUID FLOW DIRECTION
NEW CONNECTION TO EXISTING
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW TO BE INSTALLED
PRESSURE GAUGE
WATER HAMMER ARRESTOR
ISOLATION/SHUT-OFF/
MANUAL VALVE
PIPE TURNED TOWARD
BALL VALVE
SANITARY DRAIN
VENT FOR SANITARY DRAIN
DOMESTIC MIXED WATER
PLUMBING PIPING:
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER
DOMESTIC COLD WATERCW
HW
HWR
MW
SAN
V
0' -0 31/128"
1" MIN.
'-0
/2
28"-60"
FINISHED WALL SURFACE
VENT STACK-PIPE
MATERIAL AS SPECIFIED
MECHANICAL CONNECTOR
IF REQUIRED
CLEANOUT TEE SAME MATERIAL
AS CONNECTED PIPE
STAINLESS STEEL COVER PLATE
WITH SECURING SCREW
FINISHED FLOOR
UNDERGROUND DRAIN OR VENT
LINE PIPE MATERIAL AS SPECIFIED
WITHOUT CONCRETE TOPPINGWITH CONCRETE TOPPING
FINISHED FLOORCONCRETE TOPPING
CONCRETE
FLOOR
WATERPROOFING
MEMBRANE. EXTEND
MIN. 12" FROM DRAIN
IN ALL DIRECTIONS
EXTEND WATERPROOFING
MEMBRANE INTO SEEPAGE
PAN & SECURE WITH
CLAMPING COLLAR.
ABOVEGROUND:
PROVIDE UNDER DECK
CLAMP ON THIN SLAB
INSTALLATIONS OF 5"
OR LESS
TO TRAP
CONCRETE FLOOR
AUTOMATIC PRESSURE DROP
ACTIVATED TRAP PRIMER
FUNNEL
1/2" COPPER OR PEX TUBE TO
FLOOR DRAIN TRAP
SANITARY TRAP
INSTALL PER MANUFACTURERS REQUIREMENTS
AND STATE AND LOCAL CODES.
TMV
COLD
WATER