2. Existing Hydronic System.pdf

PDF 170 KB Posted

Attached to
490/25061. JBB; Bay Pines - Generator, HVAC, Fire Supp
Solicitation number
RFP-171-250000002458-3
Issued by
Delta County, Edmore Village, Michigan

About this file

This schematic diagram is a Revised Hydronic System and DOAS (Dedicated Outdoor Air System) Schematic for the State of Michigan, specifically the Department of Health and Human Services (MDHHS) Design and Construction Division. The technical drawing details a complex mechanical system involving heat pumps, air handling units (AHUs), temperature sensors, control valves, and various piping configurations for water treatment, heating, cooling, and ventilation systems. The diagram includes specific equipment like DOAS-1, AHU-1, AHU-2, AHU-3, and multiple pumps and heat exchangers, with a focus on integrating new equipment with existing building automation systems.

The schematic emphasizes several key operational sequences, including maintaining specific temperature controls, managing heating and cooling modes, and ensuring compatibility with the existing building automation system (BAS/DDC). Notable requirements include interfacing new equipment with the central BAS, retaining existing peer-to-peer network controllers, using only current manufacturer products, and ensuring spare parts availability for at least 10 years after contract completion. A specific note highlights the need to separate the fire protection system from the hydronic system, indicating a comprehensive approach to system design and safety integration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P L U R I B U E

S U N U M

C I R C U M S P I C E

S I QU EREI S P E N I N SU L AM AMOENA M

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

STATE OF MICHIGAN

ROBERT C. HALL, RA, NCARB, DIRECTOR

FACILITIES AND BUSINESS SERVICES ADMINISTRATION

DESIGN AND CONSTRUCTION DIVISION

F

IL

E N

O . 4

/1

.R A

A

IN

D

E X

N O

. 6

WATER

TREATMENT

BF

P

BFP

T-3

T-1 T-2

M

P-1

P-2

P-3

P-4

ET-2

PRV STATION

3/4" MAKE-UP

WATER

4"

3" R-4B

2-1/2"

1-1/2"

2-1/2"

AHU-1

GARAGE AND RECEIVING

GYMNASIUM AHU-2,3

BALANCE VALVE (TYP.)

4" HWR

3"

3"

2-1/2"

HX-1

ET-1

FC-1

4" BYPASS

N.O.

4"

4"

4"

4"

FIRE

PROTECTION

SYSTEM RISER

1" COLD

WATER

R-4

4"

3"

P-5

P-6

P

2"

2" DRAIN

FIRE PROTECTION

BYPASS

CHEMICAL POT FEEDER

FOR PROPYLENE

GLYCOL AND CHEMICAL

TREATMENT OF WATER

N.O.

HIGH LIMIT TO SHUT-

DOWN AT 120°F

4"

PS-1

UH-2

UH-3

T

T

T

DUCTED OA FROM SOFFIT

DUCTED OA FROM SOFFIT

R A

R A

TS-2 PS-2

SA

SA

FACE AND

BYPASS

DAMPERS

FACE AND

BYPASS

DAMPERS

AHU-3

HC-2

AHU-2

HC-3

PRIMARY AIR MEDIUM PRESSURE

DUCT SYSTEM

P

PP

PRESSURE

GAUGE (TYP.) HEAT PUMP

LOOP

CONTROL

M

M M

TS-1

1.2" WC

MANUAL

BALANCING

DAMPER

8"

FILTER PLENUM WITH 8" ROUND

FA INLET AND 14x12 RA OPENING

HEAT

PUMP

FILTER PLENUM WITH 8" ROUND

FA INLET AND 14x12 RA OPENING

HEAT

PUMP

MANUAL

BALANCING

DAMPER

HOSE KIT WITH

AUTOFLOW CV

B-1 B-2

3"

4" 4"

P-7 P-8

HEAT PUMP SUPPLY

OUT TO BUILDING

HEAT PUMP RETURN

OUT TO BUILDING

3" 4"

T-4

T-5

T-6

T-7

UH-1

MIXED AIR

DAMPERS

MIXED AIR

DAMPERS

NEW DISCHARGE

AIR TEMPERATURE

SENSOR

4 4

SPACE

SENSORS

NOTE: EXISTING AIR FLOW

SYSTEM SCHEMATICS SHOWN

ARE FOR REFERENCE ONLY;

EXISTING CONTROLS TO REMAIN.

P-9

SEE ENLARGED DHWG-1

PLAN FOR CONTINUATION

CONTROLLED BY BMS

ENERGIZED ON CALL FOR

DOMESTIC HOT WATER.

PREHEATED

AIR TO COIL

T-8

DOAS-1

54" X 30"54" X 30"

40" X 20"

RHC-1

BarschJ Callout Separate Fire Protection System from Hydronic System