2. Drawings.pdf
PDF 1 MB Posted
- Solicitation number
- 697DCK-23-R-00489
About this file
This document package includes construction drawings and specifications for replacing doors and repairing roofs at the Power Service Building of the Denver Air Route Traffic Control Center in Longmont, Colorado. The project involves replacing up to 15 doors throughout the facility with fire-rated doors and new hardware, as well as repairing the roofing on the west and east sides. Relevant details include specifications for door sizes, materials, fire ratings, and notes on reusing or replacing frames and hardware. The related federal contract opportunity is issued by the Federal Aviation Administration Southwestern Region for the siding and roof replacement work depicted in the drawings, with a solicitation number of 697DCK-23-R-00489.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0001.pdf | ||
| 1. Specifications.pdf | ||
| 3. Wage Determination.pdf | ||
| 4. Past Performance Survey Form.doc | DOC document | |
| 697DCK-23-R-00489.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NUMBER DESCRIPTION
ZDV 21003287 G001 COVER SHEET, VICINITY MAP AND DRAWING INDEX
ZDV 21003287 A201 PSB FIRST FLOOR DOOR REPLACEMENT
ZDV 21003287 A202 PSB SECOND FLOOR DOOR REPLACEMENT
ZDV 21003287 A211 PSB ROOF WEST REPAIR
ZDV 21003287 A212 PSB ROOF EAST REPAIR
ZDV 21003287 A301 PSB ELEVATIONS
ZDV 21003287 A401 PSB ROOF DETAILS
ZDV 21003287 A801 DOOR SCHEDULES
DRAWING INDEX
NOMINAL SIZE
NUMBER
OF
LEAVES WIDTH HEIGHT DEPTH JA
M
B
HE
AD
TH
RE
SH
O
LD
PSB-1 4 F HM PS 2 6'-0" 7'-0" 1-3/4" RHRB T HM 1 * * * 1, 2, 4, 6 102
PSB-2 104 F HM PS 1 3'-0" 7'-0" 1-3/4" RHRB 3 HM 2 * * 1, 4, 6 109
PSB-3 106 F HM PS 1 3'-5" 7'-0" 1-3/4" RHRB 3 HM 2 * * * 1, 2, 4, 6 110
PSB-4 107 F HM PS 2 6'-0" 7'-0" 1-3/4" RHRB 3 HM 1 * * * 1, 2, 4, 6 110
PSB-5 110 F HM PS 2 6'-0" 7'-0" 1-3/4" RHRB 3 HM 1 * * 1, 4, 6 106
PSB-6 112 F HM PS 2 7'-0" 8'-0" 1-3/4" RHRB 3 HM 1 * CONT 1, 4, 6 101
PSB-7 3 F HM PS 2 6'-0" 7'-0" 1-3/4" RHRB T HM 1 * * * CONT 1, 2 102
PSB-13 NA F HM PS 1 3'-8" 7'-0" 1-3/4" RHRB 3 HM 2 * * * CONT 1, 2, 3, 7, 8 104
PSB-15 9 F HM PS 1 3'-8" 7'-0" 1-3/4" RHRB 3 HM 2 * * 1, 4, 6 104
PSB-300 202 F HM PS 1 3'-0" 7'-0" 1-3/4" LHRB 3 HM * 1, 4, 5, 14 201
104 V HM 2 5'-0" 7'-0" 1-3/4" RH 3 HM 60 min 5, 13 104 110 F HM 2 6'-0" 7'-0" 1-3/4" RH 3 HM 90 min 3 * * 9, 10 106
113 F WD --- --- 7'-0" 1-3/4" RH 3 WD 11 104
200 F HM 2 6'-0" 7'-0" 1-3/4" RH 3 HM 3 * * 9, 10 202
T
* MIDDLE 37-1/8" BOTTOM
PS
SND
DOOR SCHEDULE
Fire Rated Smoke gasket Remove leafs do not replace. Patch holes and paint door frame to match wall Good Condition
Replace hinges and lock guard only Reuse hardware
Coordinate hardware with existing frame When replacing frame elimnate continous hinges
Reuse PIV card access
Replace threshold Replace door and frame with a 1.5 HR fire rated
DO
O
R
NO
TY
PE
M
AT
ER
IA
L
FI
RE
R
AT
IN
G
L
AB
EL
(M
IN
UT
ES
RE
PL
AC
E
FR
AM
E
HINGE LOCATION (site verify)
INSULATION
Polystyrene Sound
Possible door brands Currie, Mesker or Pioneer
TOP 4-7/8" 96-3/8"
HANDING
TYP
E M
AT
ER
IA
L
DETAILS
FRAMEDOOR
IN
SU
LA
TI
O N
ROOM NUMBER
STAIR (FLOOR 1)
WEST GENERATOR ROOM
UPS ROOM
BATTERY ROOM
UPS ROOM
SWITCHGEAR ROOM
EAST GENERATOR ROOM
EAST GENERATOR ROOM
MECHANICAL ROOM
WEST GENERATOR ROOM
DOOR SCHEDULE NOTES:
Coordinate with FAA's Security Systems Design & Integration (SSDI) Contractor for door access control system
Remove Cipher Lock per security requiement Reuse HM frame - patch holes, dents, remove rust, paint, rust prevention frames according to ANSI/SDI A 250.8 Guidelines, replace if frame is no longer plumb Reuse HM Door Leaf - patch holes, dents, remove rust, paint, rust prevention frames according to ANSI/SDI A 250.8 Guidelines
RE
PL
AC
E
DO
O
R
HA
RD
W
AR
E
SE
T
NO
STAIR (FLOOR 2)
STAIR (FLOOR 1)
WEST GENERATOR ROOM
NOTE NUMBER ENTER TO ROOM
WEST GENERATOR ROOM
PR
EV
IO
US
D O
O R
NO
HI
NG
E
LO
CA
TI
O N
FRAME TYPE
3-sided Frame Transom Frame/Removable Panel and/or Bar and/or Louver
NMD-D-501-40479-A909/A910
DEN-E-5896-A23R
NOT AVAILABLE
DEN-E-5896-A23R
NMD-D-501-40479-A909/A910
DEN-E-5896-A23R
NMD-D-501-40479-A909/A910
NMD-D-501-40479-A909/A910
NMD-D-501-40479-A909/A910
NMD-D-501-40479-A909/A910
PI
V
CA
RD
A
CC
ES
S