This document contains a mechanical equipment schedule for a federal medical facility renovation project. The schedule lists over one hundred supply terminal units, fan coil units, and exhaust terminal units to be installed on the first and second floors. It provides specifications for each unit such as location, supply air volume, control type, and sequence. It also includes notes specifying that some units require emergency power and referencing additional terminal unit schedules on other drawings. The project involves replacing the HVAC system at the New Orleans, Louisiana VA Medical Center.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. REFER TO DRAWING MH603 AND 604 FOR

TERMINAL UNIT SCHEDULES.

2. REFER TO DRAWINGS MH608 AND

MH609 FOR FCU AND CAC UNIT SCHEDULE.

3. REQUIRES EMERGENCY POWER.

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

1MH611

BLDG 1 HVAC TERMINAL UNIT AND FAN COIL

UNIT SCHEDULE

KJS DCDFebruary 29, 2012

01629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC./ IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR AREA B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 1B134 01 1B1 D3 725 CFM 375 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 2 1B132 01 1B1 E3 1100 CFM 550 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 3 1B132 01 1B1 B3 400 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 1B C04 01 1B1 B3 325 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 1B111 01 1B1 A3 175 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 1B C04 01 1B1 C1 500 CFM 500 1.0 CV DETAIL 1/MH821 NOTE (1)

S 7 01 1B1 H3 2400 CFM 1200 2.25 VCV DETAIL 3/MH821 NOTE (1)

S 8 01 1B1 C2 600 CFM 600 1.25 CV DETAIL 1/MH821 NOTE (1)

S 9 01 1B1 D2 900 CFM 900 1.75 CV DETAIL 1/MH821 NOTE (1)

S 10 1B116 01 1B1 B3 300 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 1B105 01 1B1 D3 700 CFM 350 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 1B105 01 1B1 D3 875 CFM 425 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 13 1B134 01 1B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 14 1B134 01 1B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 15 1B203 01 1B1 B3 250 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 16 1B C05 01 1B1 E2 950 CFM 475 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 17 1B C10 01 1B1 E2 1125 CFM 550 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 18 1B194 01 1B1 E2 1200 CFM 600 1.25 VCV DETAIL 3/MH821 NOTE (1)

S 19 1B194 01 1B1 E3 975 CFM 475 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 20 1B192H 01 1B1 D2 900 CFM 450 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 21 1B192A 01 1B1 E3 975 CFM 475 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 22 1B192C 01 1B1 E2 1125 CFM 550 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 23 1B208 01 1B1 C2 600 CFM 600 1.25 CV DETAIL 1/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FIRST FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 1B130 01 1B1 E NOTE (2),(3)

FCU 1 01 1B1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 2 01 1B1 4C1 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR AREA B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 1B190 01 1B2 C1 600 CFM 300 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 2 1B C13 01 1B2 F3 1700 CFM 850 1.5 VCV DETAIL 3/MH821 NOTE (1)

S 3 1B190 01 1B2 B2 400 CFM 400 0.75 CV DETAIL 1/MH821 NOTE (1)

S 4 1B174A 01 1B2 E2 1000 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 5 1B C07 01 1B2 E2 1000 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 6 01 1B2 C2 600 CFM 300 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 1B172A 01 1B2 D2 900 CFM 450 1.75 VCV DETAIL 3/MH821 NOTE (1)

S 8 1B172E 01 1B2 E2 1000 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 9 01 1B2 E2 1000 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 10 1B C06 01 1B2 D2 675 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FIRST FLOOR B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 STB 2 1 01 1B2 4B2 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR AREA C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 01 1C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 2 01 1C1 F3 1600 CFM 800 1.5 VCV DETAIL 3/MH821 NOTE (1)

S 3 1C141 01 1C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 4 1C135 01 1C1 C3 450 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 1C136 01 1C1 B3 275 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 01 1C1 E2 1000 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 7 1C123 01 1C1 B3 300 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 8 1C C01C 01 1C1 B1 300 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 1C125 01 1C1 B3 300 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 10 1C126 01 1C1 B3 600 CFM 300 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 1C C01 01 1C1 D2 750 CFM 750 1.5 CV DETAIL 1/MH821 NOTE (1)

S 12 1C C04 01 1C1 B3 400 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 13 1C C04 01 1C1 B3 400 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 14 1C163 01 1C1 A2 175 CFM 175 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 15 1C163 01 1C1 A3 150 CFM 75 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 16 1C163 01 1C1 A2 200 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 17 1C C04 01 1C1 B3 350 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 18 1C C04 01 1C1 B3 350 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 19 1C168 01 1C1 D2 1600 CFM 1600 3.0 CV DETAIL 1/MH821 NOTE (1)

S 20 1C C03 01 1C1 C2 500 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 21 1C C03 01 1C1 B3 450 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 22 1C C03 01 1C1 B3 325 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 23 1C168 01 1C1 B1 375 CFM 375 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 24 1C163 01 1C1 D2 700 CFM 350 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 25 1C167 01 1C1 A2 250 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 26 1C145 01 1C1 C1 500 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FIRST FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 1C134 01 1C1 E NOTE (2),(3)

FCU 1 01 1C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 2 01 1C1 4B3 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FIRST FLOOR AREA C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 01 1C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 2 01 1C2 B3 325 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 3 1C225 01 1C2 C2 450 CFM 450 0.75 CV DETAIL 1/MH821 NOTE (1)

S 4 1C227 01 1C2 A3 250 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 01 1C2 B2 450 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 1C228 01 1C2 A1 225 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 01 1C2 B3 575 CFM 275 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 8 01 1C2 E2 1250 CFM 625 1.25 VCV DETAIL 3/MH821 NOTE (1)

S 9 1C C06 01 1C2 D3 900 CFM 450 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 10 01 1C2 C3 875 CFM 425 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 11 1C205 01 1C2 B2 400 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 12 1C C06 01 1C2 D3 900 CFM 450 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 13 01 1C2 C3 825 CFM 400 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 14 01 1C2 F2 1650 CFM 825 1.5 VCV DETAIL 3/MH821 NOTE (1)

S 15 1C C06 01 1C2 C3 450 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 16 01 1C2 A2 250 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FIRST FLOOR C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 01 1C2 4B3 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � SECOND FLOOR AREA B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 2B120 1 01 2B1 B2 425 CFM 425 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 2 2B C02 01 2B1 D2 800 CFM 800 1.5 CV DETAIL 1/MH821 NOTE (1)

S 3 2B114 01 2B1 A3 250 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 01 2B1 B2 350 CFM 350 0.75 CV DETAIL 1/MH821 NOTE (1)

S 5 2B C05 01 2B1 A3 150 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 2B C05 01 2B1 A3 150 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 2B105 01 2B1 D2 800 CFM 800 1.5 CV DETAIL 1/MH821 NOTE (1)

S 8 2B106 01 2B1 D3 875 CFM 425 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 9 2B104 01 2B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 10 2B102 01 2B1 D2 900 CFM 450 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 11 2B103 01 2B1 C2 600 CFM 300 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 2B118 01 2B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 13 2B118 01 2B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 14 2B108 01 2B1 C3 550 CFM 550 1.0 CV DETAIL 2/MH821 NOTE (1)

S 15 2B108 01 2B1 E2 1050 CFM 1050 2.0 CV DETAIL 1/MH821 NOTE (1)

S 16 2B108 01 2B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 17 2B108 01 2B1 C3 550 CFM 550 1.0 CV DETAIL 2/MH821 NOTE (1)

S 18 2B108 01 2B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 19 2B108 01 2B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 20 2B108 01 2B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 21 2B108 01 2B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 22 2B108 01 2B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 23 2B108 01 2B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 24 2B108 01 2B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 25 2B108 01 2B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 26 2B108 01 2B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � SECOND FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 2B114 01 2B1 E NOTE (2),(3)

FCU 1 01 2B1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 2 01 2B1 4C1 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � SECOND FLOOR AREA B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 2B109 01 2B2 E2 1200 CFM 1200 2.25 CV DETAIL 1/MH821 NOTE (1)

S 2 2B109 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 3 2B109 01 2B2 A3 200 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 2B109 01 2B2 B2 350 CFM 350 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 2B109 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 6 2B109 01 2B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 2B109 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 8 2B109 01 2B2 C3 550 CFM 275 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 2B109 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 10 2B109 01 2B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 2B109 01 2B2 C3 650 CFM 325 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 12 2B109 01 2B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 13 2B109 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 14 2B109 01 2B2 B2 300 CFM 300 0.5 CV DETAIL 1/MH821 NOTE (1)

S 15 2B109 01 2B2 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 16 2B109 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 17 2B166 01 2B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � SECOND FLOOR B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 STB 2 2 01 2B2 4C2 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � SECOND FLOOR AREA C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 2C C04 01 2C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 2 2C119 01 2C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 3 2C C04 01 2C1 B2 400 CFM 400 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 4 2C109 01 2C1 B3 375 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 2C C04 01 2C1 C1 500 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 6 2C123 01 2C1 A3 200 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 2C103 01 2C1 B2 350 CFM 350 0.75 CV DETAIL 1/MH821 NOTE (1)

S 8 2C103 01 2C1 D1 900 CFM 450 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 9 2C103 01 2C1 B3 400 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 10 2C C04 01 2C1 C3 550 CFM 550 1.0 CV DETAIL 1/MH821 NOTE (1)

S 11 2C104 01 2C1 D2 750 CFM 750 1.5 CV DETAIL 1/MH821 NOTE (1)

S 12 2C111 01 2C1 B3 375 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 13 2C C02 01 2C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 14 2C C02 01 2C1 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 15 2C C02 01 2C1 E2 1400 CFM 1400 2.5 CV DETAIL 1/MH821 NOTE (1)

S 16 2C C02 01 2C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 17 2C C02 01 2C1 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 18 2C C02 01 2C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 19 2C C02 01 2C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 20 2C C02 01 2C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 21 2C C02 01 2C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 22 2C C02 01 2C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 23 2C C02 01 2C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 24 2C C02 01 2C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 25 2C C02 01 2C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � SECOND FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 2C122 01 2C1 E NOTE (2),(3)

FCU 1 01 2C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 2 STC 4 1 01 2C1 4C3 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � SECOND FLOOR AREA C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 2C C02 01 2C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 2 2C C02 01 2C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 3 2C C02 01 2C2 D2 825 CFM 825 1.5 CV DETAIL 1/MH821 NOTE (1)

S 4 2C C02 01 2C2 C3 550 CFM 275 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 2C C02 01 2C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 6 2C C02 01 2C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 2C C02 01 2C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 8 2C C02 01 2C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 2C C02 01 2C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 10 2C C02 01 2C2 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 11 2C C02 01 2C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 2C C02 01 2C2 B2 275 CFM 275 0.5 CV DETAIL 1/MH821 NOTE (1)

S 13 2C C02 01 2C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 14 2C C02 01 2C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 15 2C C02 01 2C2 B2 350 CFM 350 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 16 2C C02 01 2C2 A3 200 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 17 2C C02 01 2C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � SECOND FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 2B C02 01 2B1 D3 750 CFM 750 CV DETAIL 2/MH821 NOTE (1)

E 2 2B C02 01 2B1 D3 750 CFM 750 CV DETAIL 2/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � SECOND FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 2C C05 01 2C1 D3 100 CFM 850 CV DETAIL 2/MH821 NOTE (1)

E 2 2C C05 01 2C1 D3 850 CFM 850 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � SECOND FLOOR C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 STC 3 1 01 2C2 4C3 DETAIL 2/MH820 NOTE (2)

EXHAUST TERMINAL UNIT SCHEDULE � SECOND FLOOR C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 2C C02 01 2C2 A3 250 CFM 250 CV DETAIL 2/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � SECOND FLOOR B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 2B109 01 2B2 A3 250 CFM 250 CV DETAIL 2/MH821 NOTE (1)