Clarifier Blowdown Upgrades – Bid Documents Summary
This is a set of bid documents and construction drawings prepared by GHD for the Borough of Chambersburg Water Treatment Plant Clarifier Blowdown Upgrades project located at 7659 Lincoln Way East, Fayetteville, PA 17222. The project scope encompasses installation of approximately 500 linear feet of 8-inch diameter HDPE pipe within existing plant drain piping (24", 30", and 36" diameter), approximately 110 linear feet of buried 8-inch diameter PVC pipe, two new manholes with frames and covers, modifications to an existing drain manhole, and replacement of an existing buried gate valve. Additional work includes demolition and modifications to two clarifier valve pits to accommodate new piping and valves, magnetic flow meters, electric valve actuators, platforms, ladder access, and electrical demolition and upgrades. The project also requires demolition of an existing battery backup tower with associated conduit and conductor removal in the operations room, reconnection to an existing transformer, cleanout of the existing sedimentation lagoon via the plant's licensed hauler, and complete lawn restoration. Sealed bids are due February 10, 2026, at 10:00 AM via the PennBid online system. Bid security of ten percent of the maximum bid price is required, along with performance and payment bonds each in the amount of 100 percent of the contract price and an anti-collusion affidavit.
The contract is subject to the Prevailing Minimum Wage Determination established by the Commonwealth of Pennsylvania Department of Labor. The bid documents include comprehensive civil, structural, process, and electrical drawings with detailed specifications for site layout, piping installation, manhole construction, erosion and sediment control measures, and electrical system modifications. The project is located in Greene Township, Franklin County, Pennsylvania, within the Conococheague Creek watershed (Cold Water Fishes, Migratory Fishes classification). Utility notification is required through the Pennsylvania One Call System at 1-800-242-1776 or 811, with contacts provided for nine utility companies and municipal authorities in the area. The documents specify field verification requirements for existing infrastructure prior to construction and coordinate with approved equipment shop drawings for all piping and connections.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-CB Clarifier Blowdown Upgrade Bid Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Plot Date: Filename:6 January 2026 - 9:34 AM G:\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\General\11224278-G00001.dwgPlotted By: Mike Wiestling
IssueNo. Drawn Approved Date This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
COVER SHEET
G-00001
M. WIESTLING C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
AREA MAP LOCATION MAP
PROJECT
LOCATION
HARRISBURG
YORK
LANCASTER
PHILADELPHIA
PITTSBURGH
ERIE
STATE COLLEGE
WILLIAMSPORT
SCRANTON
CHAMBERSBURG
SITE ADDRESS:
WATER TREATMENT PLANT
7659 LINCOLN WAY EAST
FAYETTEVILLE, PA 17222
PROJECT
LOCATION
BOROUGH OF CHAMBERSBURG
WATER TREATMENT PLANT
CLARIFIER BLOWDOWN UPGRADES
GREENE TOWNSHIP, FRANKLIN COUNTY, PA
BID DOCUMENTS
JANUARY 2026
CALL BEFORE YOU DIG
PENNSYLVANIA LAW REQUIRES 3 WORKING DAYS NOTICE
FOR CONSTRUCTION PHASE AND 10 WORKING
DAYS IN DESIGN STAGE - STOP CALL
PENNSYLVANIA ONE CALL SYSTEM, INC.
1-800-242-1776 OR 811
POCS SERIAL NUMBER: 20252963793
UNDERGROUND UTILITIES ACT:
THE CONTRACTOR SHALL COMPLY WITH THE PROVISIONS OF THE PENNSYLVANIA GENERAL ASSEMBLY UNDERGROUND UTILITY LINE PROTECTION ACT, PA ACT 287 OF 1974, AS AMENDED BY ACT 50 OF 2017, 73 P.S. § 176 ET SEQ., FOR NOTIFICATION OF UTILITIES BEFORE EXCAVATION IN THE CONTRACT AREA. THE ONE UNDERGROUND UTILITIES CALL NUMBER IS 800-242-1776 OR 811.
INDIVIDUAL LOCAL UTILITIES ARE AS FOLLOWS:
COMPANY: CABLE PROTECTION SERVICES INC
ADDRESS: PO BOX 4816
MIDLOTHIAN, VA. 23112
CONTACT: DEBBIE KING
EMAIL: debbie_king@cableps.com
PHONE: 804-562-3409
COMPANY: STAKECENTER
ADDRESS: 7025 ALBERT PICK ROAD
SUITE 600
GREENSBORO, NC. 27409
CONTACT: STAKECENTER DISPATCH
EMAIL: mirasol.garza@brightspeed.com
PHONE: 801-364-1063
COMPANY: COLUMBIA GAS OF PA INC
ADDRESS: 1600 DUBLIN RD
COLUMBUS, OH. 43215
CONTACT: LISA COLLINS
EMAIL: ldugan@nisource.com
PHONE: 614-325-5961
COMPANY: GREENE TOWNSHIP MUNICIPAL AUTHORITY
ADDRESS: 4182 SUNSET PIKE
CHAMBERSBURG, PA. 17202
CONTACT: STEVE BRECHBILL
EMAIL: sbrechbill@greenetownshipma.com
PHONE: 717-263-5324
COMPANY: GREENE TOWNSHIP
ADDRESS: 1145 GARVER LN
CHAMBERSBURG, PA. 17202
CONTACT: TRAVIS BROOKENS
EMAIL: tbrookens@greenetwp.us
PHONE: 717-263-9160
COMPANY: GUILFORD WATER AUTHORITY
ADDRESS: 115 SPRING VALLEY RD
CHAMBERSBURG, PA. 17202
CONTACT: JEN COOLEY
EMAIL: jcooley@guilfordtwp.us
PHONE: 717-263-2813
COMPANY: PENNSYLVANIA ELECTRIC CO
ADDRESS: 341 WHITE POND DR
AKRON, OH. 44320
CONTACT: MELLYSSA ADAMS
EMAIL: madams@firstenergycorp.com
PHONE: 330-436-4013
COMPANY: CHAMBERSBURG BOROUGH
ADDRESS: 100 S 2ND ST
PO BOX 1009
CHAMBERSBURG, PA. 17201
CONTACT: DEVON COSEY
EMAIL: dcosey@chambersburgpa.gov
PHONE: 717-251-2435
COMPANY: ENERGY TRANSFER
ADDRESS: 1300 MAIN ST
HOUSTON, TX. 77002
CONTACT: SAUL SHAW
EMAIL: saul.shaw@energytransfer.com
PHONE: 713-989-7342
COMPANY: TEXAS EASTERN/ENBRIDGE
ADDRESS: SUITE 400
2601 MARKET PLACE
HARRISBURG, PA. 17110
CONTACT: RYAN LUMBATIS
EMAIL: ryan.lumbatis@enbridge.com
PHONE: 717-540-8330
N http://www.ghd.com/
Plot Date: Filename:9 January 2026 - 10:43 AM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\General\11224278-G00002.dwgPlotted By: Mike Wiestling
This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
GENERAL NOTES, LEGENDS AND SHEET INDEX
G-00002
M. WIESTLING C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
SINGLE LINE
90° BEND
45° BEND
TEE
LATERAL WYE
REDUCER
PLUG VALVE
GATE VALVE
WELDED JOINT (STEEL / STAINLESS
STEEL PIPE & FITTINGS)
UNION
ITEM DOUBLE LINE
ROTAMETER
UNION
PRESSURE REDUCING VALVE
SOLENOID VALVE
PRESSURE RELIEF VALVE
Y STRAINER
CALIBRATION COLUMN
PULSATION DAMPENER
FLEXIBLE TUBING
QUICK CONNECT (FEMALE)
PLUG VALVE
GATE VALVE
VALVE
ULTRASONIC LEVEL SENSOR
RUPTURE DISK
PRESSURE GAUGE
VACUUM REGULATOR
MOTOR OPERATOR
POLYMER FLOW METER
REDUCER
SOLENOID OPERATOR
PNEUMATIC OPERATOR
TEMPERATURE GAUGE
FLOW CONTROL VALVE
FLOW METER
COALESCING FILTER
PROCESS FLOW DIRECTION
ABBREVIATIONS: PIPING LEGENDSCHEMATIC SYMBOLS LEGEND
GENERAL NOTES (APPLY TO ALL DRAWINGS):
1. EXISTING FACILITIES AND PIPING SHOWN LIGHT. NEW FACILITIES AND PIPING SHOWN DARK.
2. CONTRACTOR SHALL FIELD VERIFY AND COORDINATE ALL EXISTING PIPING ELEVATIONS, LOCATIONS, SIZE AND TYPE OF MATERIAL WITH NEW PIPING PRIOR TO CONSTRUCTION. CONTRACTOR SHALL FIELD VERIFY AND COORDINATE ALL EXISTING EQUIPMENT DIMENSIONS AND ELEVATIONS, AS REQUIRED, PRIOR TO ORDERING NEW EQUIPMENT.
3. CONTRACTOR SHALL COORDINATE ALL PIPING AND OTHER CONNECTIONS WITH THE APPROVED
EQUIPMENT SHOP DRAWINGS.
4. ALL BURIED PIPING TO BE MIN. 5' BELOW GRADE, UNLESS OTHERWISE NOTED.
5. FOR DRAWINGS C-02101 AND C-02102, HORIZONTAL DATUM: NAD 83 (2011)(EPOCH:2010.0000) PA SOUTH
ZONE GRID. REFERENCED FROM "ZDC1", "P817" AND "YORK".
6. FOR DRAWINGS C-02101 AND C-02102, VERTICAL DATUM: NAVD 88. REFERENCED FROM NGS BENCH
MARK DISK "H 156" (JB3356).
7. FOR DRAWINGS C-02101 AND C-02102, SURVEY BASED ON DRAWING NO. 17028-001 To GHD 7 24 17, DATED JULY 7, 2017 AND PROVIDED BY KAYLOR, ALLWEIN & HARTMAN, INC., 1529 EAST CHOCOLATE AVENUE, HERSHEY, PA 17033, TEL: (717) 533-9077.
8. FOR DRAWINGS C-02101 AND C-02102, PRIOR DEED, DEED BOOK 632, PAGE 544, STATES THE PROPERTY IS SUBJECT TO A RIGHT OF INGRESS AND EGRESS TO AND FROM U.S. ROUTE 30 TO A TRACT RETAINED
BY GRANTOR ADJACENT TO THE NORTHWEST CORNER OF THE LANDS.
9. FOR DRAWINGS C-02101 AND C-02102, PRIOR DEED, DEED BOOK 632, PAGE 544, STATES SUBJECT TO RIGHT-OF-WAY FOR INGRESS AND REGRESS TO AND FROM U.S. ROUTE 30 TO AND FROM A TRACT OF
REAL ESTATE PREVIOUSLY CONVEYED TO GEORGE SNURR, ET AL. BY DEED 503, PAGE 736.
10. FOR DRAWINGS C-02101 AND C-02102, PROPERTY LINE INFORMATION SHOWN HEREON IS TAKEN FROM FRANKLIN COUNTY INSTRUMENT #201016563 AND FRANKLIN COUNTY DEED BOOK 674, PAGE 556.
PROPERTY LINES SHOWN ARE REPRESENTATIVE OF THE DEED CONFIGURATIONS BASED ON MINIMAL
FIELD EVIDENCE AND ARE NOT THE RESULT OF AN ACTUAL BOUNDARY RETRACEMENT SURVEY.
ADD'L ADDITIONAL
AFF ABOVE FINISHED FLOOR
ADJ ADJUSTABLE
AGGR AGGREGATE
ALLOW ALLOWANCE
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECT OR ARCHITECTURAL
ASSY ASSEMBLY
APPROX APPROXIMATE
BLDG BUILDING
BLK BLOCK
BOT or B BOTTOM
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CIP CAST IRON PIPE
CMP CORRUGATED METAL PIPE
CO CLEANOUT
CONN CONNECTION
CY CUBIC YARD
CL CLEAR
℄ CENTER LINE
CONC CONCRETE
CONT CONTINUOUS
CPVC CHLORINATED POLYVINYL CHLORIDE
CL JT CONTROL JOINT
DL DEAD LOAD
DIA, Ø DIAMETER
DIP DUCTILE IRON PIPE
DWL DOWEL
EF EACH FACE
EA EACH
EL or ELEV ELEVATION
ELEC ELECTRIC
EQ EQUAL
EX, EXIST EXISTING
EXT EXTERIOR
FF FAR FACE/ FINISHED FLOOR
FM FORCE MAIN
FLR FLOOR
FT FEET
FTG FOOTING
G NATURAL GAS
GPM GALLONS PER MINUTE
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
HDPE HIGH-DENSITY POLYURETHYLENE
HWL HIGH WATER LEVEL
HP HORSEPOWER
ID INSIDE DIAMETER
IF INSIDE FACE
INV INVERT
I/O INPUT / OUTPUT
LF LINEAR FEET
LL LIVE LOAD
LWL LOW WATER LEVEL
M MOTOR
MGD MILLION GALLONS PER DAY
MH MANHOLE
MJ MECHANICAL JOINT
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
POLY / PE POLYETHYLENE
⅊ PLATE, PROPERTY LINE
R RADIUS
REINF REINFORCING
REQD REQUIRED
SF SQUARE FOOT
SS STAINLESS STEEL
SCH SCHEDULE
SPEC SPECIFICATION
SQ SQUARE
STL STEEL
STD STANDARD
SYM SYMBOL
TEL TELEPHONE
TEMP TEMPERATURE
TYP TYPICAL
UV ULTRAVIOLET
W WATER
WL WATER LEVEL
W/O WITHOUT
WWF WELDED WIRE FABRIC
SHEET INDEX
SEQUENCE
NUMBER
SHEET
NUMBER SHEET TITLE
GENERAL
G-00001 COVERSHEET
G-00002 GENERAL NOTES, LEGENDS AND SHEET INDEX
CIVIL
C-02101 WATER TREATMENT PLANT EXISTING SITE PLAN
C-02102 WATER TREATMENT PLANT EXISTING YARD PIPING PLAN
C-02501 CIVIL DETAILS
C-02502 CIVIL DETAILS
C-02503 EXISTING DRAIN MANHOLES PLANS AND SECTIONS
CE-02001 EROSION AND SEDIMENT CONTROL PLAN NOTES
CE-02101 EROSION AND SEDIMENT CONTROL PLAN SITE PLAN
CE-02501 EROSION AND SEDIMENT CONTROL PLAN DETAILS
STRUCTURAL
S-02101 INLET FLUME PLAN AND SECTIONS
S-04101 EXISTING CLARIFIER No 1 PLAN AND SECTION
S-05101 EXISTING CLARIFIER No 2 PLAN AND SECTION
PROCESS
DD-04101 EXISTING CLARIFIER No 1 DEMOLITION PLANS AND SECTIONS
DD-05101 EXISTING CLARIFIER No 2 DEMOLITION PLANS AND SECTIONS
D-04101 EXISTING CLARIFIER No 1 PLAN AND SECTION
D-05101 EXISTING CLARIFIER No 2 PLAN AND SECTION
ELECTRICAL
E-00001 ABBREVIATIONS AND SYMBOLS
E-04101 EXISTING CLARIFIER No 1 PLAN AND SECTION
E-05101 EXISTING CLARIFIER No 2 PLAN AND SECTION
E-06101 TREATMENT PLANT BASEMENT AND PARTIAL FIRST FLOOR PLANS
E-07101 DETAILS
DETAIL NUMBER
(NUMERICAL ON EACH SHEET
BEGINNING WITH DETAIL 1)
DETAIL NUMBER
SHEET WHERE DETAIL IS SHOWN
(IF ON DIFFERENT SHEET) DEPICTION BOUNDARY
TYPICAL SECTION MARKS (FOR PLANS)
TYPICAL DETAIL TITLE
TYPICAL DETAIL CALLOUT
OR
D-101
DETAIL NAME
NO SCALE
A-501
A-501
SECTION INDICATORA
X-301
SECTION LETTER
SHEET WHERE SECTION IS SHOWN
(IF SHOWN ON DIFFERENT SHEET)
A D-101
SECTION
SCALE: 1/4" = 1'-0"
SECTION LETTER
(ALPHABETICAL FOR
EACH STRUCTURE)
0 8'4'2'
SHEET WHERE SECTION
IS REFERENCED
SHEET WHERE DETAIL
IS REFERENCED
NEW GRAPHICS; EQUIPMENT, STRUCTURES,
ETC., ARE SHOWN AS BOLD LINEWORK AND
IN THIS TEXT FORMAT.
TRUE NORTH
NORTH INDICATOR
N
XXX
EQUIPMENT TAG
TYPE
NUMBER
GENERAL LEGEND
KEYNOTE INDICATOR
KEYNOTE NUMBER
M
E
E E
E
SETBACK
SETBACK
30'
30'
SETBACK
CP 101
CP 100
Plot Date: Filename:8 January 2026 - 4:41 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-C02101.dwgPlotted By: Shawn Matthews
IssueNo. Drawn Approved Date This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
WATER TREATMENT PLANT
EXISTING SITE PLAN
C-02101
S. MATTHEWS C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
LEGENDS
PLAN
SCALE 1" - 40' 0 80'40'20'
N
EXISTING INDEX CONTOURS
EXISTING INTERMEDIATE CONTOURS
EXISTING STRUCTURE
EDGE OF ROAD
EDGE OF GRAVEL ROAD
100 YEAR FLOODPLAIN
TREES
UTILITY POLE
EXISTING FENCE
EXISTING PROPERTY LINE
EXISTING TREE LINE
EXISTING SETBACK LINE
EXISTING UNDERGROUND ELECTRIC
BENCHMARK
EXISTING UNDERGROUND TELEPHONE
CONTROL POINT LOCATIONS
ID NORTHING EASTING ELEVATION DESCRIPTION
CP 100 208906.810 2036509.250 888.58
CP 101 208591.750 2036498.220 909.450 MAG NAIL
M
E
E E
E
NEW 8" SDR35 PVC
NEW 8" Ø HDPE
C-02501
NEW 5'Ø
MANHOLE
(MH 1)
RECONNECT EXISTING PIPE TO
NEW DI STUB OUTS FROM NEW
5'Ø MANHOLE (TYP.) (HYMAX
COUPLINGS TO BE USED)NEW 8" Ø HDPE
C-02501
NEW 5'Ø INSIDE
DROP MANHOLE
(MH 2)
TEST PIT TO FIND 4"
SLUDGE PUMP LINE
S-02101
0+00 1+00
NEW
MH 1
NEW
MH 2
(INSIDE DROP MH)
98.62LF of 8" PVC SDR35 Pipe @ UNKNOWN SLOPE
TEST PIT TO LOCATE EXISTING
4" SLUDGE PUMP LINE
8'
INV OUT
STATION
RIM EL. ±
INV IN
INV OUT
STATION
RIM EL. ±
INV IN UNKNOWN
UNKNOWN
0+00.00 873.5
UNKNOWN
1+03.53
869.1
8" HDPE
Plot Date: Filename:8 January 2026 - 4:41 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-C02102.dwgPlotted By: Shawn Matthews
IssueNo. Drawn Approved Date This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
WATER TREATMENT PLANT
EXISTING YARD PIPING PLAN
C-02102
S. MATTHEWS C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
LEGENDS
SHEET GENERAL NOTES
SHEET KEYNOTES
1. CONTRACTOR TO LOCATE AND CONFIRM PIPE TYPE, DIAMETER AND DEPTH. SLOPE
FROM MH 1 TO MH 2 SHALL BE DETERMINED BASED ON DEPTH OF DRAIN LINE.
2. CONTRACTOR TO REPLACE VALVE WITH A NEW GATE VALVE AND NEW VALVE BOX AND
COVER. CONTRACTOR TO CONFIRM PIPE TYPE, DIAMETER AND DEPTH.
3. EXISTING STRUCTURE 'A' IS NOT EXTENDED TO GRADE. CONTRACTOR TO EXTEND
STRUCTURE TO GRADE PER DETAIL 1 ON SHEET C-02502.
4. PROVIDE HDPE BENDS, FLUSHING TEE AND FITTINGS TO COMPLETE BEND.
5. EXISTING STRUCTURE "B" IS TO BE TAKEN APART (CUT) TO FACILITATE THE
INSTALLATION OF THE NEW 8" HDPE BLOW-OFF LINE. ONCE COMPLETED STRUCTURE "B"
SHALL BE PUT BACK TOGETHER AND/OR REPLACED.
PLAN
SCALE 1" - 40' 0 80'40'20'
N
EXISTING INDEX CONTOURS
EXISTING INTERMEDIATE CONTOURS
EXISTING STRUCTURE
EDGE OF ROAD
EDGE OF GRAVEL ROAD
100 YEAR FLOODPLAIN
TREES
UTILITY POLE
EXISTING FENCE
EXISTING PROPERTY LINE
EXISTING TREE LINE
EXISTING SETBACK LINE
EXISTING UNDERGROUND ELECTRIC
BENCHMARK
EXISTING UNDERGROUND TELEPHONE
1. THIS DRAWING HAS BEEN PREPARED TO PROVIDE THE CONTRACTOR WITH A GENERAL
SCOPE OF DEMOLITION WORK TO BE REQUIRED. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO FIELD VERIFY ALL ITEMS THAT MAY EFFECT DEMOLITION COSTS
INCLUDING BUT NOT LIMITED TO EXACT EQUIPMENT AND PIPING LOCATIONS, ACTUAL
EQUIPMENT AND PIPING SIZES, AND ALL INCIDENTAL EQUIPMENT OR PIPING NOT SHOWN
BUT PART OF THE EQUIPMENT INDICATED TO BE REMOVED OR EFFECTING REMOVAL
PROCESS.
PROFILE
SCALE: H:1" = 40', V: 1" = 10' 0 80'40'20'
0 20'10'
O.
D.
EXCAVATED TRENCH
BACKFILL COMPACTED
TO 95% MIN.
COMPACTION PER
ASTM D-698 (STD.)
DETECTION TAPE
6" TOPSOILFINISH GRADE
TRENCH WALL
SHALL BE
MAINTAINED
AS VERTICAL
OR LAID BACK
UNDISTURBED SUBGRADE PIPE
AASHTO NO. 8
AGGREGATE BEDDING
LIM
IT
O F
PI
PE
B
ED
DI
NG
4'
MI
NI
MU
M
- D
EP
TH
V
AR
IE
S
" M
IN
6" MI
N.
" M
IN
6"
AG
GR
EG
AT
E
MIN.
6"
MIN.
O.D.
TO
DE
TE
CT
IO
N
TA
PE
Plot Date: Filename:8 January 2026 - 4:42 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-C02501.dwgPlotted By: Shawn Matthews
IssueNo. Drawn Approved Date This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
CIVIL
DETAILS
C-02501
S. MATTHEWS C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
TRENCH DETAIL - UNPAVED
NO SCALE
NOTE: ALL NON-SHRINK CEMENT GROUT SHALL BE TROWELED SMOOTH.
SECTION
MANHOLE FRAME AND LEVELING RINGS
MANHOLE GASKET SECTION
SECTION
GROOVE
TONGUE
PRECAST CONCRETE
PREFORMED
FLEXIBLE PLASTIC
JOINT SEALANT
WHOLE PRECAST CONCRETE
LEVELING RING (VARIED
THICKNESS) (RUBBER
ADJUSTMENT RISERS ARE
PERMITTED FOR PAVED
AREAS, ONLY)
3/4" DIA. STAINLESS STEEL
STUD W/NUT AND WASHER:
4" MIN. (4 BOLTS REQ'D)DOUBLE APPLICATION
OF PREFORMED
FLEXIBLE PLASTIC
JOINT SEALANT
THREADED INSERT CAST
INTO TOP SECTION
6" MAXIMUM
ALLOWABLE LEVELING
RING ADJUSTMENT
MANHOLE GASKETS, LEVELING
RINGS AND BOLTED FRAME DETAILS
NO SCALE
TYPICAL PLAN OF MANHOLE CHANNELS
NO SCALE
STANDARD MANHOLE FRAME AND COVER
NO SCALE
3/4 O.D.
NOTE: 1. BOLTING OF MANHOLE FRAME AND
COVER NOT REQUIRED FOR MANHOLES
INSTALLED IN PAVED SURFACES.
2. ALL STONE GRADATIONS ARE AASHTO
CLASSIFICATION.
3. PIPES SHALL PROTRUDE 2" INSIDE
MANHOLE WALL.
PLAN
VARIES
6" MIN.
5'-0"
6" MIN.
VARIES
(TYP.)
6"
5" MIN.
SECTION
R=1'-0"
1/2"/FT.
3'- 0" MIN. 2'-0"
18"MAX.
TO TOP
STEP
10"
6" MIN.
VARIES
6"
13-3/4"
VARIES
3'-0" MIN.
5" MIN. (TYP.)
1'-0"
MAX.
SECTION
3 5/8"
2'-0"
1-1/2"
3-3/4"
NOTE: 1. BOLTING OF MANHOLE FRAME AND
2. ALL STONE GRADATIONS ARE AASHTO
3. PIPES SHALL PROTRUDE 2" INSIDE
PLAN
COVER NOT REQUIRED FOR MANHOLES
INSTALLED IN PAVED SURFACES.
MANHOLE WALL.
CLASSIFICATION.
4" MIN. 3/4" DIA. STAINLESS STEEL STUD,
WASHER, AND NUT COATED WITH ONE
COAT OF STANDARD ASPHALT AFTER
INSTALLATION.
MATCH PAVEMENT/GRADE AND
SLOPE AS DIRECTED
FRAME AND LEVELING RINGS
SEALED WATERTIGHT (SEE
MANHOLE FRAME AND
LEVELING RINGS DETAIL)
MANHOLE STEPS
3-1/2" MIN. TO 4" MAX.
EMBEDMENT.
JOINTS SEALED WATERTIGHT
(SEE MANHOLE GASKET
DETAIL)
PRECAST REINFORCED
CONCRETE BASE WITH RISER
SECTION - CHANNEL FORMED
ON JOB WITH CONCRETE -
HOLES FOR PIPE CAST WITH
RUBBER GASKET TO SUIT
JOB CONDITIONS.
PIPE CONNECTION
MADE WITH RUBBER
GASKET. (SEE
MANHOLE PIPE
GASKETS DETAIL) SPACED ON
16" CENTERS
(TYP.)
THREADED INSERT
CAST INTO TOP
SECTION
ANTI-FLOTATION
COLLAR ON MANHOLES
NO.8 OR NO.57 COARSE
AGGREGATE, TAMPED.
6" MIN.
4" MIN. 3/4" DIA. STAINLESS STEEL
STUD, WASHER, AND NUT COATED
WITH ONE COAT OF STANDARD
ASPHALT AFTER INSTALLATION.
MATCH PAVEMENT/GRADE AND
SLOPE AS DIRECTED
FRAME AND LEVELING RINGS
SEALED WATERTIGHT (SEE
MANHOLE FRAME AND
LEVELING RINGS DETAIL)
MANHOLE STEPS
3-1/2" MIN. TO 4" MAX.
EMBEDMENT.
JOINTS SEALED WATERTIGHT
(SEE MANHOLE GASKET
DETAIL)
SPACED ON
16" CENTERS
(TYP.)
PRECAST REINFORCED
CONCRETE BASE WITH RISER
SECTION - CHANNEL FORMED
ON JOB WITH CONCRETE -
HOLES FOR PIPE CAST WITH
RUBBER GASKET TO SUIT
JOB CONDITIONS.
NO.8 OR NO.57 COARSE
AGGREGATE, TAMPED.
ANTI-FLOTATION
COLLAR ON MANHOLES
THREADED INSERT
CAST INTO TOP
SECTION
6 PRECAST CONCRETE MANHOLE WITH PRECAST CONCRETE BASE
NO SCALE
5'-0"
PRECAST CONCRETE INSIDE DROP MANHOLE DETAIL
NO SCALE
SECTION
PIPE CONNECTION MADE
(SEE MANHOLE PIPE
WITH RUBBER GASKET
GASKETS DETAIL)
02601 - MANHOLES)
(REFERENCE SECTION
CHANNEL
FLUSH TO MANHOLE
90° PVC BEND
INSIDE PVC
(S.S.) ANCHORS
STAINLESS STEEL
DROP BOWL W/
PIPE COUPLING
2'-0"
5'-0" (MIN.)
(SEE NOTE 1)
NOTES:
1. PVC DROP BOWL SHALL BE AS MANUFACTURED BY RELINER/DURAN,
INC. OR APPROVED EQUAL. DROP BOWL SHOULD HAVE A HOOD.
2. REFERENCE PRECAST CONCRETE MANHOLE AND MANHOLE COVER
AND CASTING DETAILS.
ADJUSTABLE S.S. PIPE
BRACKET (TYP.) W/
S.S. EXPANSION ANCHORS
BANDS TO BE SPACED AT
4' INTERVALS (MIN. 2)
(PER ENGINEER'S REC.)
8" SDR 35 PVC PIPE
ANTI-FLOTATION
COLLAR ON MANHOLES
(TYP.)
SEE APPROPRIATE TRENCH
DETAIL FOR BACKFILL REQUIREMENTS
PVC TO PVC CONNECTION USE PVC REPAIR SLEEVE
PVC TO CAST IRON CONNECTION USE MECHANICAL JOINT COUPLING
PVC TO ACP CONNECTION USE MECHANICAL JOINT COUPLING
PVC TO TCP/VCP CONNECTION USE S.S. ANTI-SHEAR COLLAR RUBBER ADAPTER
DIP/CIP TO DIP/CIP CONNECTION USE MECHANICAL JOINT COUPLING
FORCEMAIN USE MECHANICAL JOINT COUPLING
UNDISTURBED SUBGRADE
NEW PVC SANITARY SEWER PIPE/FORCEMAIN
50 LB. BAG OF CONCRETE CENTERED
BENEATH JOINT (NOT REQUIRED IN ROCK EXCAVATION)
NO. 8 OR PA NO. 2A. COARSE AGGREGATE
PIPE BEDDING MATERIAL, COMPACTED IN 4" LIFTS.
EXISTING SANITARY
SEWER PIPE/FORCEMAIN
6" MIN.
NOTES:
1. RECONNECTIONS TO BE AIR TESTED IN ACCORDANCE WITH SPECIFICATIONS.
2. MECHANICAL JOINT COUPLINGS TO BE SMITH-BLAIR OR APPROVED EQUAL
PIPE RECONNECTION DETAIL
NO SCALE
EXISTING RCP
4"
CASING SPACER
BLOW DOWN PIPE SPACER
NO SCALE
SECTIONAL ELEVATION
PLAN
34" DIA.
24" DIA.
9"
25-7/8" DIA.
2- 1/2
· 1-800-325-3549
· COVER CAT.# 2070770
· FRAME CAT.# 154510
EAST JORDON IRON WORKS, INC.
FRAME & COVER:
S
T O
R M S E W E
R CONCEALED COVER
PICK HOLE
(4) - 1" ANCHOR
BOLT HOLES
RAISED
LETTERS
TAPER RIBS
NON-SKID SURFACE
AS APPROVED BY ENGR.
27-7/8"
1/2
NOTES:
· CASTINGS TO BE GRAY IRON
· CAST IRON ASTM SPECS. A-48
· H-20 LOADING
· LETTERING AS SPECIFIED BY ENGINEER
· PAINT/COAT BLACK ASPHALTUM
MH ANCHOR BOLT DETAIL
3"
MIN.
MIN. PROJECTION OF 2-1/2" ABOVE
FINAL COURSE OF BRICK OR ADJUSTMENT RING
3/4" GALV. NUT
3/4"x1-1/2" GALV. WASHER
3/4" GALV. ALL THREAD ROD
CONCRETE INSERT
PRE-CAST CONCRETE
TOP SECTION
STANDARD MANHOLE STORM FRAME AND COVER
NO SCALE
SECTIONAL ELEVATION
PLAN
34" DIA.
24" DIA.
9"
25-7/8" DIA.
2- 1/2
· 1-800-325-3549
· COVER CAT.# 2070770
· FRAME CAT.# 154510
EAST JORDON IRON WORKS, INC.
FRAME & COVER:
C H
A M B E R S B
U R
G S
A
N
ITARY SEW
E
R
CONCEALED COVER
PICK HOLE
(4) - 1" ANCHOR
BOLT HOLES
RAISED
LETTERS
TAPER RIBS
NON-SKID SURFACE
AS APPROVED BY ENGR.
27-7/8"
1/2
NOTES:
· CASTINGS TO BE GRAY IRON
· CAST IRON ASTM SPECS. A-48
· H-20 LOADING
· LETTERING AS SPECIFIED BY ENGINEER
· PAINT/COAT BLACK ASPHALTUM
MH ANCHOR BOLT DETAIL
3"
MIN.
MIN. PROJECTION OF 2-1/2" ABOVE
FINAL COURSE OF BRICK OR ADJUSTMENT RING
3/4" GALV. NUT
3/4"x1-1/2" GALV. WASHER
3/4" GALV. ALL THREAD ROD
CONCRETE INSERT
PRE-CAST CONCRETE
TOP SECTION
Plot Date: Filename:8 January 2026 - 4:42 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-C02502.dwgPlotted By: Shawn Matthews
This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
CIVIL
DETAILS
C-02502
S. MATTHEWS C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
1 STRUCTURE 'A' - SECTION
SCALE 1/2' = 1'0" 0 4'2'1'
STRUCTURE 'A' - PLAN
SCALE 1/2' = 1'0" 0 4'2'1'
NEW 8" HDPE PIPE
SPACERS (2) - 10' O.C.
DOWNSTREAM SIDE
4" C
LE
AR
TOP SECTION OF
EXISTING MANHOLE
TO BE REMOVED
NEW STORM FRAME
AND COVER
RAISE EXISTING
MANHOLE TO GRADE
SAW CUT EXISTING STRUCTURE
AND ADD NEW PRECAST SECTION
OR POUR IN PLACE WALLS AND TOP
SECTION. REFER TO C-02503 FOR
EXISTING REINFORCING STEEL.
2 STRUCTURE 'B' - SECTION
SCALE 1/2' = 1'0" 0 4'2'1'
STRUCTURE 'B' - PLAN
SCALE 1/2' = 1'0" 0 4'2'1'
NEW 8" HDPE PIPE
4" C
LE
AR
SPACERS (2) - 10' O.C.
DOWNSTREAM SIDE
NEW 8"x4" HDPE TEE
WITH FLANGE TAPPED
FOR 3" QUICK CAM
FLUSHING CONNECTION
NEW 8" HDPE PIPE
NOTE:
1. CONTRACTOR TO CUT TOP OF
INLET, AS NECESSARY, TO
FACILITATE THE INSTALLATION
OF NEW 8" HDPE PIPE.
CIVIL
EXISTING DRAIN MANHOLES PLANS & SECTIONS
C-02503
S. MATTHEWS C. ANGLE
M. WIESTLING T. PARTHEMORE
NOT TO SCALE
SHEET GENERAL NOTES
1. ELEVATIONS OF THESE STRUCTURES ARE FROM THE NGVD 29 DATUM. DESIGN DRAWINGS
ARE BASED ON SURVEYED NAVD 88 DATUM. FOR THE CHAMBERSBURG WATER
TREATMENT PLANT SITE, THE NGVD 29 DATUM IS APPROXIMATELY 0.67 FEET HIGHER THAN
THE NAVD 88 DATUM.
2. EXISTING STRUCTURE 'A' IS NOT EXTENDED TO GRADE. CONTRACTOR SHALL TEST PIT TO
DETERMINE STRUCTURE 'A' DEPTH, AND PROVIDE RISER SECTION WITH NEW ACCESS PER
DETAIL 3 AND 4 ON SHEET C-02501.
3. THIS SHEET PROVIDED FOR REFERENCE ONLY AND IS NOT TO SCALE.
STRUCTURE 'A' STRUCTURE 'B'
Plot Date: Filename:8 January 2026 - 4:43 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-C02503.dwgPlotted By: Shawn Matthews
IssueNo. Drawn Approved Date This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
Plot Date: Filename:8 January 2026 - 4:43 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-CE02001.dwgPlotted By: Shawn Matthews
This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
EROSION AND SEDIMENT CONTROL PLAN
NOTES
CE-02001
S. MATTHEWS C. ANGLE
M. WIESLTING T. PARTHEMORE
AS SHOWN
Soil Description
Approximate boundaries of the soil-mapping units are shown on the attached drawings; this information is obtained from the USDA NRCS online Web Soil Survey (http://websoilsurvey.nrcs.usda.gov/app/). The soils found within the project area are summarized in Table 1.
Table 1 Soils Summary
Soil limitation resolutions:
— Depth to saturated zone, slow percolation, and wetness/depth to water limitations will be addressed by use of a pumped water filter bag if necessary. Pumped water filter bags must be placed at least 50 feet from any stream banks in well-vegetated, flat areas.
— Easily erodible limitations limitations will be addressed by limiting the amount of soil that is exposed. All areas disturbed during construction will be stabilized as described in this plan.
— All buried concrete and steel will be designed to resist the corrosive environment.
— All footers and buried utility pipes will be below the frost line to address frost action limitations.
— To address poor source of topsoil limitatins,topsoil will not be taken from the areas with source limitations.
— Road fill limitation is not applicable to this project.
— Areas to be filled are to be cleared, grubbed, and stripped of topsoil to remove trees, vegetation, roots, and other objectionable material need to have appropriate E&S controls.
— All fills shall be compacted as required to reduce erosion, slippage, settlement, subsidence or other related problems. Fill intended to support buildings, structures and conduits, etc. shall be compacted in accordance with local requirements or codes.
— All earthen fills shall be placed in compacted layers not to exceed nine inches in thickness.
— Fill materials shall be free of frozen particles, brush, roots, sod, or other foreign or objectionable materials that would interfere with or prevent construction of satisfactory fills.
— Frozen materials or soft, mucky, or highly compressible materials shall not be incorporated into fills.
— Fill shall not be placed on saturated or frozen surfaces.
— Seeps or springs encountered during construction shall be handled in accordance with the standard and specification for subsurface drain or other approved method.
Standard Erosion and Sediment Control Plan Notes
1. A copy of the approved erosion and sediment control plan must be available at the project site at all times. The Franklin County Conservation District shall be notified of any changes to the approved plan prior to implementation of those changes. The District may require a written submittal of those changes for review and approval at its discretion.
2. Contractor is responsible for installation and maintenance of all erosion and sediment Best Management Practices (BMPs).
3. At no time shall construction vehicles be allowed to enter areas outside the limit of disturbance boundaries shown on the plan maps. These areas must be clearly marked and fenced off before clearing and grubbing operations begin.
4. Immediately upon discovering unforeseen circumstances posing the potential for accelerated erosion and/or sediment pollution, the operator shall implement appropriate best management practices to minimize the potential for accelerated erosion and sediment pollution and notify the Franklin County Conservation District.
5. All off-site waste and borrow areas must have an E&S Plan approved by the Franklin County Conservation District and E&S measures must be fully implemented prior to being activated.
6. Contractor is responsible for ensuring that any material brought on site is Clean Fill. Form FP-001 must be retained by the property owner for any fill material affected by a spill or release of a regulated substance by qualifying as Clean Fill due to analytical testing (See Clean Fill Requirements).
7. All pumping of sediment laden water shall be through a sediment control BMP, such as a pumped water filter bag or equivalent sediment removal facility, over undisturbed vegetated areas.
8. Sediment tracked onto any public roadway or sidewalk shall be returned to the construction site by the end of each workday and disposed in the manner described in this plan. In no case shall the sediment be washed, shovelled, or swept into any roadside ditch, storm sewer, or surface water.
9. All sediment removed from BMPs shall be disposed of within the limits of disturbance upslope of steep slopes, outside of floodplains or drainage swales, and immediately stabilized or removed from the site.
10. Excess soil must be removed from this site and hauled away immediately to an off-site disposal area having an approved erosion and sediment control plan.
11. Concrete wash water shall be handled in the manner described on the plan drawings. In no case shall it be allowed to enter any surface waters or groundwater systems.
12. All graded areas shall be permanently stabilized immediately upon reaching finished grade. Cut slopes in competent bedrock and rock fills need not be vegetated.
13. Failure to correctly install sediment control facilities or failure to prevent sediment laden runoff from leaving the construction site or failure to take corrective actions to immediately resolve failures of sediment control facilities may result in administrative, civil and/or criminal penalties being instituted by the Pennsylvania Department of Environmental Protection as defined in Section 602 of the Clean Streams Law of Pennsylvania. The Clean Streams Law provides for up to $10,000 per day in civil penalties, up to $10,000 in summary criminal penalties, and up to $25,000 in misdemeanor criminal penalties for each violation.
14. All building materials and wastes shall be removed from the site and recycled or disposed of in accordance with the Department's Solid Waste Management Regulations at 25 Pa. Code 260.1 et seq., 271.1., and 287.1 et seq. No building materials or wastes or unused building materials shall be
15. The contractor will be responsible for the removal of any excess material and make sure the site(s) receiving the excess has an approved and fully implemented erosion and sediment control plan that meets the conditions of Chapter 102 and/or other State or Federal regulations.
16. Contractor is required to have a Preparedness, Prevention, and Contingency (PPC) Plan for the project site. PPC Plan is to be developed and implemented in accordance with PA DEP requirements and is to be in place before construction is started.
Staging of Construction Activities
Erosion and sediment BMPs must be constructed, stabilized, and functional before site disturbance begins within the tributary areas of those BMPs.
All earth disturbance activities shall proceed in accordance with the following sequence. Each stage shall be completed and immediately stabilized before any following stage is initiated. Clearing, grubbing and topsoil stripping shall be limited only to those areas described in each stage. Any deviation from the following sequence must be approved in writing from the Franklin County Conservation District.
The construction sequence will generally be as follows:
1. At least 7 days before starting any earth disturbance activities (including clearing and grubbing), the owner and/or operator shall invite all contractors involved in those activities, the land owner, appropriate municipal officials, the E&S plan preparer, the licensed professional or designee responsible for oversight during construction of the infiltration facility, and a representative of the Franklin County Conservation District for an onsite pre-construction meeting.
2. Excess soil must be removed from this site. At the preconstruction meeting, the Contractor shall provide the Franklin County Conservation District with copies of the Erosion and Sediment Pollution Control Plan for the disposal site(s).
3. At least 3 days before starting any earth disturbance activities, all contractors involved in those activities shall notify the Pennsylvania One Call System Incorporated at 1-800-242-1776 or 811 for buried utilities locations.
4. Clearly field mark the limits of disturbance shown on plan drawings prior to the start of any earth moving activities.
5. Install rock construction entrance and all compost filter socks prior to beginning any earth moving activities. Initial clearing and grubbing should be limited to that which is necessary to install the proposed perimeter BMPs. E&S BMP's shall be implemented and maintained until the permanent stabilization is completed.
6. Prior to any earth moving activities, delineate the proposed underground detention/infiltration facility area and mark off with stakes or orange construction fence to protect this area from compaction.
7. Clear and grub area as necessary.
8. Install concrete washout if required.
9. Install new sludge blowdown piping and connection manhole.
10. Remove concrete washout if required during construction.
11. Complete all other remaining work shown on the drawings and specified in the project manual.
12. Final placement of topsoil, seeding, and mulching of all disturbed areas that are not paved.
13. Upon final completion of an earth disturbance activity or any stage or phase of an activity, all areas disturbed during construction and not paved shall immediately have topsoil restored, replaced, or amended, seeded, fertilized, mulched or otherwise permanently stabilized and protected from accelerated erosion and sedimentation according to the seeding and fertilizing section.
14. No more than 15,000 square feet of disturbed area, which is to be stabilized by vegetation, may reach final grade without being seeded and mulched.
15. Upon completion of all earth disturbance activities and permanent stabilization of all disturbed areas, the owner and/or operators shall contact the Franklin County Conservation District for an inspection prior to removal of the E&S BMPs.
16. After final site stabilization has been achieved, remove all temporary E&S BMPs. Cut open compost filter socks (spread and seed the compost from the filter socks). Areas disturbed during the removal of the E&S BMPs must be permanently stabilized immediately upon completion of the temporary E&S BMP removal activity. In order to ensure rapid vegetation of disturbed areas, such removal should be done only during the germinating season.
17. Upon completion of all earth disturbance activities, removal of all temporary BMPs, installation of all permanent PCSM BMPs, and permanent stabilization of all disturbed areas, the owner and/or operators shall contact the Franklin County Conservation District for a final inspection.
Stabilization Specifications
1. E&S BMPs are to be located and installed as shown on the drawings. E&S BMPs must remain functional as such until all areas tributary to them are permanently stabilized or until they are replaced by another BMP approved by the Franklin County Conservation District.
2. Upon temporary cessation of an earth disturbance activity or any stage or phase of an activity where a cessation of earth disturbance activities will exceed 4 days, the site shall be immediately seeded, mulched, or otherwise protected from accelerated erosion and sedimentation pending future earth disturbance activities.
3. Permanent stabilization is defined as a minimum uniform 70% perennial vegetative cover or other permanent non-vegetative cover with a density sufficient to resist accelerated surface erosion and subsurface characteristics sufficient to resist sliding and other movements.
4. Areas which are to be topsoiled shall be scarified to a minimum depth of 3 to 5 inches - 6 to 12 inches on compacted soils - prior to placement of topsoil. Areas to be vegetated shall have a minimum 4 inches of topsoil in place prior to seeding and mulching. Fill outslopes shall have a minimum of 2 inches of topsoil.
5. Topsoil should not be placed while the topsoil or subsoil is in a frozen or muddy condition, when the subsoil is excessively wet, or in a condition that may otherwise be detrimental to proper grading and seedbed preparation. Compacted soils should be scarified 6 to 12 inches along contour whenever possible prior to seeding.
6. Immediately after earth disturbance activities cease, the operator shall stabilize the disturbed areas. During non-germinating periods, mulch must be applied as described in this plan. Disturbed areas which are not at finished grade and which will be re-disturbed within 1 year must be stabilized in accordance with the temporary vegetative stabilization specifications. Disturbed areas which are at final grade or which will not be re-disturbed within 1 year must be stabilized in accordance with the permanent vegetative stabilization specifications.
7. Erosion control blanketing shall be installed on all slopes 3H:1V or steeper, disturbed areas within 50 feet of a surface water regardless of slope, on all areas of concentrated flows, and on all other disturbed areas specified on the plan maps and/or detail sheets.
Maintenance of the Erosion and Sedimentation Controls
The contractor shall be responsible for the ongoing maintenance of all erosion and sediment control facilities throughout the period of construction and until such time that the site is deemed permanently stabilized.
1. Until the site is stabilized, all erosion and sediment BMP's must be maintained properly. Maintenance must include inspections of all erosion and sediment control BMPs after each runoff event and on a weekly basis. All preventative and remedial maintenance work, including clean out, repair, replacement, regarding, reseeding, remulching, and renetting, must be performed immediately, If erosion and sediment control BMPs fail to perform as expected, replacement BMPs, or modifications of those installed will be required.
2. Any sediment removed from BMPs during construction will be returned to upland areas on site and incorporated into the site grading.
3. A log showing dates that E&S BMPs were inspected as well as any deficiencies found and the date they were corrected shall be maintained on the site and be made available to regulatory agency officials at the time of inspection.
Staging, Laydown, and Equipment Storage
Staging, laydown and equipment storage areas will be located where shown on the drawings. The Contractor is required to provide adequate erosion and sedimentation control for these areas.
Storage and Disposal Areas for Excess Excavated Material
The Owner's Water Treatment Facility shall not be used for storage of excess excavated material. All excess excavated material must be hauled off-site. Areas used for storage and disposal of excess excavated material will be determined by the contractor. The Contractor will be responsible for the removal of any excess material and, prior to the start of the project, must ensure that the site receiving the excess material has an approved erosion and sedimentation control plan that meets the conditions of Chapter 102 and/or other state and federal regulations and, if required by the size of the area, an NPDES permit for Stormwater Discharges Associated with Construction Activities. Prior to the start of the project, the Franklin County Conservation District is to be notified of the location of all soils removed from the project site
Recycling
Wherever possible, recycling of waste materials is preferred rather than disposal. The contractor shall ensure that mechanisms are in place to control waste materials. Construction wastes include, but are not limited to, excess soil materials, building materials, concrete wash water, sanitary wastes, etc. that could adversely impact water quality. The contractor shall remove from site, recycle or dispose of all building materials and wastes in accordance with PA DEP's Solid Waste Management regulations at 25 PA Code 260.1 et seq., 271.1 et. seq., and 287.1 et. seq. The contractor shall not illegally bury, dump, or discharge any building material or waste at the site.
Receiving Stream Name/Chapter 93 Classification
The project's receiving watercourse is Conococheague Creek, and the Chapter 93 classification is Cold Water Fishes, Migratory Fishes (CWF, MF). There is no Existing Use classification.
Seeding and Fertilizing
1. Temporary Seeding
Temporary seed is to be annual ryegrass with 95% purity, 85% germination, and 0.15% max weed seed. Seeding rate is to be 40 lbs/acre. Seeding dates March 15 to October 15.
2. Permanent Seeding
Seed mixture is per the Penn State “Erosion Control and Conservation Plantings on Noncropland.” The seed mixture shall consist of:
· Minimum seed lots are truly minimum, and seed lots to be used for revegatation purposes should equal or exceed these standards.
· PLS is the product of the percentage of pure seed times the percentage germination divided by 100. To determine the actual planting rate, divide the pounds PLS by the PLS percentage shown on the seed tag or calculated as previously discussed.
Seeding dates: March 15 to June 1 and August 1 to October 15. Ryegrass portion: March 15 to October 15.
After seeding, fertilizer and mulch have been applied, all slopes 3H:1V or greater shall have erosion control mat installed as per PennDOT Publication 408, Section 806.2(a)1: Erosion Control Mat-Organic Yarns.
3. Fertilizing and Liming
Commercial fertilizer conforming to the requirements of the Pennsylvania Soil Conditioner and Plant Growth Substance Law. Pulverized agricultural limestone conforming to the requirements of the Agricultural Liming Materials Act.
Temporary seeding fertilizer to be 10-10-10 analysis commercial fertilizer; fertilizer rate to be 500 lb/acre; agricultural limestone rate to be 1 ton/acre.
Permanent seeding fertilizer to be 10-20-20 analysis commercial fertilizer; fertilizer rate to be 1000 lb/acre; agricultural limestone rate to be 6 tons/acre.
4. Mulching
Mulch material, mulch binders, construction and maintenance will be in accordance with PennDOT Publication 408 Section 805 and with the PA DEP Erosion and Sediment Pollution Control Program Manual, dated March 2012. Mulch rate for hay and straw to be 3 tons/acre.
Straw and hay mulch are to be anchored or tackified immediately after application to prevent being windblown; anchoring may be done by “crimping” the straw or hay into the soil, stapling mulch control netting over the mulch or using recycled cellulose fiber binder. If “crimping” is used, slopes must be less than 3H:1V, and the machinery is to be operated on the contour. Straw mulch shall be applied in long strands, not chopped or finely broken. Mulch on slope of 8% or steeper should be held in place with netting. If mulch control netting is used, it is to be stapled according to the manufacturer's recommendations. Binder rate to be 160 lbs/1,000 sq. yd. for recycled cellulose binder.
Mulching without seeding is to be used as an interim stabilization control during non-growing seasons of the year.
5. Topsoil
A minimum of four (4) inches of topsoil shall be placed on all disturbed areas prior to seeding.
Clean Fill Requirements
All fill material is to meet the following DEP Clean Fill requirements:
1. Clean Fill is defined as: Uncontaminated, non-water soluble, non-decomposable, inert, solid material. The term includes soil, rock, stone, dredged material, and used asphalt, as well as brick, block, or concrete from construction and demolition activities that is separate from other waste and is recognizable as such. The term does not include materials placed in or on the waters of the Commonwealth, unless otherwise authorized. (The term “used asphalt” does not include milled asphalt or asphalt that has been processed for re-use.).
2. Any placement of clean fill that has been affected by a spill or release of a regulated substance must use form FP-001 to certify the origin of the fill material and the results of the analytical testing to qualify the material as clean fill. Form FP-001 must be retained by the owner of the property receiving the fill.
3. Environmental due diligence must be performed to determine if the fill materials associated with the project qualify as clean fill. Environmental due diligence is defined as: Investigative techniques, including, but not limited to, visual property inspections, electronic data base searches, review of property ownership, review of property use history, Sanborn maps, environmental questionnaires, transaction screens, analytical testing, environmental assessments, or audits. Analytical testing is not a required part of due diligence unless visual inspection and/or review of the past land use of the property indicates that the fill may have been subjected to a spill or release of a regulated substance. If the fill may have been affected by a spill or release of a regulated substance, it must be tested to determine if it qualifies as clean fill. Testing should be performed in accordance with Appendix A of the Department's policy “Management of Clean Fill.”
SETBACK
SETBACK
M
E
E E
E
RCE
LO
D
LOD
ROCK CONSTRUCTION
ENTRANCE
STAGING, LAYDOWN AND
EQUIPMENT STORAGE AREA
CONCRETE
WASHOUT
SETBACK
SETBACK
SETBACK
CFS
CFS
CFS
CFS
INLET PROTECTION
SETBACK
30'
30'
SETBACK
CFS
CFS
CFS
Plot Date: Filename:8 January 2026 - 4:44 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-CE02101.dwgPlotted By: Shawn Matthews
IssueNo. Drawn Approved Date This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
EROSION AND SEDIMENT CONTROL PLAN
SITE PLAN
CE-02101
S. MATTHEWS C. ANGLE
M. WIESTLING T. PARTHEMORE
AS SHOWN
LEGEND:
EXISTING INDEX CONTOURS
EXISTING INTERMEDIATE
EXISTING STRUCTURE
EDGE OF ROAD
EDGE OF GRAVEL ROAD
100 YEAR FLOODPLAIN
TREES
UTILITY POLE
EXISTING FENCE
EXISTING PROPERTY LINE
EXISTING TREE LINE
EXISTING SETBACK LINE
EXISTING R-O-W
NEW STRUCTURE
LIMIT OF DISTURBANCE
(41085.107 sq ft - 0.94 acres)
LOD
(12") COMPOST FILTER SOCKCFS CFS
SOIL BOUNDARY
SOIL TYPE
NEW CONTOUR
SITE PLAN
SCALE 1" = 40'
PLAN
NORTH
0 80'40'20'
Plot Date: Filename:8 January 2026 - 4:44 PM \\ghdnet\ghd\US\Harrisburg\Projects\564\11224278\Digital_Design\_Clarifier Sludge\ACAD 2020\Sheets\Civil\11224278-CE02501.dwgPlotted By: Shawn Matthews
This document shall not be used for construction unless signed and sealed for construction. Sheet No.
Original Size
Title
Project
Client DesignerDrawn
Scale Arch D
Date Project No.
Reuse of Documents This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD and shall not be reused in whole or in part for any other project without GHD's written authorization.
© 2026 GHD
Drafting Check
0 1"
Bar is one inch on original size sheet
Design Check
Project Manager
BOROUGH OF CHAMBERSBURG
WTP CLARIFIER BLOWDOWN UPGRADES
11224278 C. ANGLE JANUARY 8, 2026GHD Inc.
225 Grandview Avenue, Suite 403 Camp Hill, Pennsylvania 17011 USA T 1 717 541 0622 W www.ghd.com
0 BID DOCUMENTS MRW CMA JAN-8-2026
EROSION AND SEDIMENT CONTROL PLAN
DETAILS
CE-02501
E. CAMACHO C. ANGLE
M. WIESLTING T. PARTHEMORE
AS SHOWN
50' MIN.
3 FEET
PROFILE
NOTES:
1. REMOVE TOPSOIL PRIOR TO INSTALLATION OF ROCK CONSTRUCTION ENTRANCE. EXTEND ROCK OVER FULL WIDTH OF ENTRANCE.
2. RUNOFF SHALL BE DIVERTED FROM ROADWAY TO A SUITABLE SEDIMENT REMOVAL BMP PRIOR TO ENTERING ROCK
CONSTRUCTION ENTRANCE.
3. MOUNTABLE BERM SHALL BE INSTALLED WHEREVER OPTIONAL…