About this file
This document comprises construction drawings for the City of Orem, Utah's 2026 Sewer Replacement Project (Project Number 25-041), prepared by design engineer Samuel Cuessy in March 2026. The project encompasses the installation of sixteen 60-inch sanitary sewer manholes, 3,180 linear feet of 8-inch SDR35 PVC sanitary sewer pipe, 1,555 linear feet of 8-inch ductile iron water pipe, and 5,640 square yards of roadway reconstruction with 4-inch asphalt (PG 58-28), along with associated improvements including curb, gutter, sidewalk restoration, fire hydrant installations, and water valve replacements. The work extends across multiple street segments within Orem including 450 East, 550 East, 630 North, 800 West, Atlantis Drive, Main Street, and Crest Drive, with a construction completion date of September 12, 2026. The nine construction drawing sheets provide detailed plans, elevations, and specifications for sewer lateral reconnections, utility coordination, and surface restoration requirements across the project areas.
The contractor is responsible for survey staking, potholing and locating all existing utilities, developing and implementing a Storm Water Pollution Prevention Plan (SWPPP) for city approval, and maintaining driveway access to all properties during construction. Key coordination requirements include notifications to the Utah Transit Authority regarding bus routes, Enbridge Gas for any line conflicts requiring relocation, and the Orem City Sign Shop for street sign removal and relocation. The contractor must repair all damage to asphalt, curb, gutter, sidewalk, sprinklers, and landscaping, raise all manhole covers and water valves with concrete collars to match new asphalt surface elevation, and maintain asphalt joints at striping locations rather than wheel paths. Bypass pumping may be required depending on groundwater conditions encountered in the field, with no price adjustment permitted. Contact information for project managers overseeing sewer, water, storm drain, streets, street lights, signs, traffic control, and SWPPP implementation is provided throughout the drawings.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-2026 Sewer Replacement Project Contract Docs and Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT VICINITY MAP SYMBOLS DRAWING INDEX
LOCATION MAP
ABBREVIATIONS
CITY OF OREM
ENGINEERING DIVISION
COMMUNITY DEVELOPMENT
OREM, UT 84057
56 NORTH STATE ST
(801) 229-7107
APPROVAL CITY ENGINEER
APPROVAL COMMUNITY DEVELOPMENT DIRECTOR
DESIGN: SAMUEL CUESSY
DATE: MARCH 2026
2000 NORTH
1600 NORTH
1200 NORTH
800 NORTH
400 NORTH
CENTER ST
400 SOUTH
800 SOUTH
1200 SOUTH
1600 SOUTH
2000 SOUTH
W
ES
T
W
ES
T
W
ES
T
W
ES
T
M
AI
N S
T
EA
ST
EA
ST
E
AS
T
GENERAL INFORMATION
PROJECT NUMBER: 25-041
SHEET
IRR IRRIGATION
OC ON CENTER
OUTSIDE DIAMETEROD
LIP OF GUTTER
NOT IN CONTRACT
NOT TO SCALE
NIC
NTS
LG
MH MANHOLE
SIDEWALK
TOP OF WALK
TOP OF CONCRETE
TELEPHONE
EOA EDGE OF ASPHALT
END VERTICAL CURVE
FIRE HYDRANT
INSIDE DIAMETER
G
ID
GAS
EVC
FL
FH
FLOW LINE
CONTROL POINT
DUCTILE IRON
END CURB RETURN
EL
ECR
EC END CURVE
ELEVATION
CP
CTV
DI
CABLE TV
TW
W
TYP
WATER
TYPICAL
SW
TC
T
ENGINEERING STATION
POINT OF TANGENCY
POINT ON CURVE
POINT OF INTERSECTION
POLYVINYL CHLORIDE
RIGHT OF WAY
STORM DRAIN
SANITARY SEWER
POINT OF CURVATURE
POLE, POWER
CURB & GUTTER
BEGIN VERTICAL CURVE
CORRUGATED METAL PIPE
CG
CONC
CI
CO
CMP
CAST IRON
CLEANOUT
CONCRETE
BVC
CB
BM BENCH MARK
CATCH BASIN
R/W
SS
SD
STA
PT
PVC
PRV
ASPHALT CONCRETE
BEGIN CURVE
BEGIN CURB RETURN
AC
.BCR
BC
P
POC
PI
PC
S S
EXISTING CATCH BASIN
EXISTING CLEANOUT
EXISTING MANHOLE
EXISTING PRESSURE REDUCER
EXISTING SUMP
EXISTING WATER METER
EXISTING FIRE HYDRANT
EXISTING WATER VALVE
NEW CATCH BASIN
NEW CLEANOUT
NEW MANHOLE
NEW PRESSURE REDUCER
NEW SUMP
NEW WATER METER
NEW FIRE HYDRANT
NEW WATER VALVE
NEW WATER CROSS
NEW WATER TEE
NEW WATER ELBOW
NEW WATER SLEEVE
NEW WATER REDUCER
NEW WATER PLUG
NEW STREETLIGHTEXISTING STREETLIGHT
EXISTING POLE
EXISTING POLE WITH ANCHOR
SECTION CORNER
CONTROL POINT
SIGN
CONIFEROUS TREE DECIDUOUS TREE
CURB, GUTTER & SIDEWALKCG&SW
ROAD CENTERLINERCL
PRESSURE REDUCING VALVE
EXISTING UTILITIES NEW UTILITIES
INVERT ELEVATIONINV
HDPE
REINFORCED CONCRETE PIPERCP
CL CENTERLINE
FO FIBER OPTIC
HIGH-DENSITY POLYETHYLENE
400 SOUTH
CONTACTS
GENERAL NOTES
TOP OF ASPHALTTA
W
ES
T
ANGLE POINTAP
2026 SEWER REPLACEMENT
PROJECT
1) THE CONTRACTOR IS TO READ AND UNDERSTAND THE M&P SPECIAL
CONDITIONS LOCATED IN THE SPECIFICATIONS. EACH LINE ITEM IS COVERED IN
DETAIL WITH EXTRA INFORMATION THAT MAY NOT BE FOUND ON THE PLANS.
CONSTRUCTION COMPLETION DATE IS SEPTEMBER 12, 2026.
2) UNDERGROUND UTILITIES ARE APPROXIMATE. THE CONTRACTOR IS
RESPONSIBLE TO POTHOLE, LOCATE AND PROTECT ALL EXISTING UTILITIES. THE
CONTRACTOR IS RESPONSIBLE TO POTHOLE EXISTING UTILITIES TO VERIFY
ELEVATION AND LOCATION.
3) THE CONSTRUCTION SURVEY STAKING IS TO BE PROVIDED BY THE
CONTRACTOR.
4) THE CONTRACTOR IS REQ'D TO DEVELOP AND IMPLEMENT A STORM WATER
POLLUTION PREVENTION PLAN (SWPPP) ACCORDING TO SPECIFICATION 01 57
00 BEFORE CONSTRUCTION BEGINS. THE SWPPP IS TO BE SUBMITTED TO THE
CITY OF OREM DEVELOPMENT SERVICES FOR APPROVAL.
5) CONTACT TRENT MALLINSON (229-7519 OREM CITY SIGN SHOP) TO
COORDINATE OREM CITY STREET SIGN REMOVAL AND RELOCATION. THE CITY
WILL BE RESPONSIBLE TO MOVE ANY AND ALL OREM CITY SIGNS. THE SIGN
SHOP HOURS ARE 7:00 AM TO 3:30 PM. NOTIFICATION FOR RELOCATION OR
REMOVAL WILL NEED TO BE BY 9:00 AM TO INSURE REMOVAL OR RELOCATION
BY 3:30 PM.
6) THROUGHOUT CONSTRUCTION THE CONTRACTOR IS REQUIRED TO NOTIFY
AND COORDINATE WITH THE UTAH TRANSIT AUTHORITY (UTA) CONCERNING
BUS ROUTES, BUS STOPS, AND UTA ROUTE SIGNS.
7) HIGH GROUNDWATER CONDITIONS MAY EXIST. THE CONTRACTOR SHOULD
PLAN ON MINIMAL TRENCH DEWATERING. IF MAJOR GROUNDWATER IS
ENCOUNTERED AND WELL POINTS ARE REQUIRED, THEN WELL POINTS WILL BE
ADDRESSED WITH A CHANGE ORDER.
8) THE CONTRACTOR IS REQ'D TO MAINTAIN DRIVEWAY PARKING ACCESS TO
ALL APARTMENT BUILDINGS, BUSINESSES, HOMES, ETC. DURING
CONSTRUCTION. STEEL PLATES ARE REQ'D WHILE THE NEW CONCRETE CURES
FOR THE CURB, GUTTER, AND SIDEWALK FOR ANY DRIVEWAY ENTRANCES
AFFECTED.
9) THE CONTRACTOR IS RESPONSIBLE TO SURVEY AND LOCATE ALL MANHOLE
COVERS AND WATER VALVES IF NEEDED DURING PAVING. ALL MANHOLES AND
WATER VALVES ARE TO BE RAISED BY THE CONTRACTOR WITH CONCRETE
COLLARS TO BE FLUSH WITH THE NEW ASPHALT SURFACE.
10) WHENEVER FEASIBLY POSSIBLE THE CONTRACTOR IS REQUIRED TO HAVE
ALL ASPHALT JOINTS PLACED AT THE STRIPING LOCATIONS AND NOT IN THE
WHEEL PATH LOCATIONS.
11) ALL SECTIONS CORNERS MUST BE PROTECTED DURING THE CONSTRUCTION
PROCESS. ANY DAMAGED OR DISTURBED SECTION CORNERS MUST BE
RE-SURVEYED AT THE CONTRACTORS EXPENSE AND VERIFIED WITH THE CITY
SURVEYOR.
12) ROAD CLOSURES WILL ONLY BE ALLOWED WITH APPROVAL FROM THE CITY
ENGINEER. FOR ANY ROAD CLOSURES CONTRACTOR MUST NOTIFY PUBLIC
SAFETY, WASTE MANAGEMENT, POST OFFICE, ANY SCHOOL DISTRICTS
AFFECTED, AND UTA.
EXISTING STRUCTURE
OR FACILITY
800 WEST ATLANTIS DRIVE
EA
ST
ATLANTIS DRIVE
700 NORTH
PROJECT
AREAS
450 EAST 550 EAST
EA
ST
EA
ST
400 NORTH
400 NORTH
CREST DRIVE
CREST DRIVE
W
ES
T
1200 NORTH
TITLENUMBER
TITLE SHEET1
INDEX2
SS1
450 EAST STA. 00+00 TO 05+06
630 NORTH STA. 50+00 TO 53+20
800 WEST STA. 10+00 TO 15+74
ATLANTIS DR STA. 53+20 TO 58+14
450 EAST STA. 05+60 TO 7+46
550 EAST STA. 60+00 TO 64+45
MAIN STREET STA. 80+00 TO 84+00
CREST DRIVE STA. 00+00 TO 02+00
CREST DRIVE STA. 02+00 TO 7+46
SS2
SS3
SS4
SS5
SS6
SS7
SS8
SS9
DESIGN ENGINEER SAMUEL CUESSY 229-7542
PROJECT MANAGER TOM NISSON 229-7331
SEWER RYAN JOHNSON 229-7481
WATER QUINN FENTON 229-7546
STORM DRAIN RICK SABEY 229-7545
STREETS BILL PETERSON 229-7537
STREET LIGHTS SHAUN BRIDGES 229-7584
SIGNS TRENT MALLINSON 229-7519
TRAFFIC CONTROL JOHN DORNY 229-7320
SWPPP RYAN CASPER 229-7573
1200 SOUTH
M
AI
N S
TR
EE
T
MAIN STREET
60" Ø SS MANHOLE #02
STATION: 53+67.66
OFFSET: 0.000
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
8"
5° B
EN
D
(2
8" 22.5° BEND
8" MJ X 6" FL TEE
ABANDON EXISTING
WATER VALVE
INSTALL NEW FIRE
HYDRANT ASSEMBLY
-2 .9
-3
.1
-3 .2
-2
.8
-2 .7
-3
.0
-2 .9
-3
.6
ABANDON EXISTING
FIRE HYDRANT
8" GATE VALVE
-0 .8
-1
.3
P
P
P
P
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
FO
FO
FO
FO
FO
FO
FO
W in
W in
W 4in W 4in W 4in W 4in W 4in
W
2i n
W
2i n
W
2i n
W
/4 in
W 3/4in
W 3/4in
P P
SS
in
SS
in
SS
in
SS
in
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G in
G in
G in
G in G in
G in G in
G in
G G G
G
G
G
G
G G
G
G
G
GG
W 8in
W 8in W 8in W 8in W 8in W 8in W 8in
W in
W in
W in
630 NORTH
EA
ST
351.13' OF 8" SDR35 PVC @ 0.40%
60" Ø SS MANHOLE #01
STATION: 50+16.53
OFFSET: 0.000
CONNECT EXISTING PIPE
TO NEW STRUCTURE (2)
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
NOTES
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED EQUIVALENT TO CONNECT
NEW PIPE TO EXISTING PIPE.
3. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4. BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. 630 NORTH SEWER HAS VERY LITTLE FLOW. EXACT FLOW
DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5.ASPHLAT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS.
6.CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY BE IN CONFLICT
WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
8" 45° BEND
INSTALL NEW 8"
DI WATERLINE
N
EW
W
AT
ER
S
ER
VI
C E
(T
YP
CONNECT NEW WATERLINE
TO EXISTING WATERLINE
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
CONNECT NEW 8" WATERLINE TO EXISTING
8" WATERLINE WITH 8" 45° BEND AND SLEEVE.
ABANDON EXISTING 4" WATER MAIN. PLUG
END WITH MJ CAP AND MEGALUGS.
Overhead Power and Fiber
+0
+0
+0
+0
54+00
15'
49+35 49+50 50+00 50+50 51+00 51+50 52+00 52+50 53+00 53+50 54+00 54+50 55+00
351.13' OF 8" SDR35 PVC @ 0.40%
Existing 3/4" Water Service Station ≈ 51+97.10
Existing 3/4" Water Service Station ≈ 50+77.53
Existing 3/4" Water Service Station ≈ 52+32.67
Existing 3/4" Water Service Station ≈ 53+28.04
Existing 3/4" Water Service Station ≈ 53+48.82
Existing 3/4" Water Service Station ≈ 53+75.04
Existing 3/4" Water Service Station ≈ 53+84.05
Existing 3/4" Water Service Station ≈ 54+72.54
Existing 3/4" Water Service Station ≈ 54+34.53
Existing 3/4" Gas Service Station ≈ 54+61.34
Existing 3/4" Gas Service Station ≈ 54+43.90
Existing 2" Gas Main Station ≈ 53+60.64
Existing 3/4" Gas Service Station ≈ 52+16.45
Existing Ground
REMOVE AND DISPOSE
EXISTING CONCRETE SEWER PIPE
REMOVE AND DISPOSE EXISTING
6" CONCRETE SEWER PIPE
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL
RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL
RECONNECT
SS LATERAL RECONNECT
Ex
Ex
INSTALL NEW 8" DI WATERLINE
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 5
3+
.6
O
FF
SE
T:
.0
T
R
IM
: 4
3.
8"
IN
V O
U T:
.8
(W
8"
IN
V O
U T:
.8
(N
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 5
0+
.5
O
FF
SE
T:
.0
T
R
IM
: 4
1.
8"
IN
V
IN
:4
6.
(E
8"
IN
V
IN
:4
6.
(S
8"
IN
V O
U T:
.3
(N
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
400 TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS1
MATCHLINE STATION 54+25
MATCHLINE SHEET SS2
N O
RT
H
ST
A.
0+
T
O
3+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
LEGEND
4" THICK ASPHALT (3
8" PG 58-28)
-2.7% P
P
P
P
P
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
SS SS
SS
SS
SS
SS
SSSS
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
SS SS
SS
SS
SS
SS
SSSS
IR
R
4i n
IR
R in
IR
R in
IR
R in
IR
R in
FO
FO
FO
FO
W 4in
W 4in
W 4in
W 4in W 4inW 4in W 4in W 4in
W 4in
W 3/4in
W 3/4in W
3/4in
SS
in
SS
in
SS 8in
SS 8in
SS
in
SS
in
G 2in
G 2in
G 2in G 2in
G 2in G 2in
G 2in G 2in
G 2in G 2in
G 2in
G 2in
G 2in
G 2in
G 2in
G
G
G
G
G
G
G G
G G
G G
G G
G
G
G
G
G
G
G
G
W 4in
W 8in
W 8in
W 8in W 8in W 8in W 8in
W 8in W 8in W 8in W 8in
W 8in
N O
R
TH
ATLANTIS DR
379.61' OF 8" SDR35 PVC @ 0.45%
59.50' OF 8" SDR35 PVC @ 2.72%-0.7%
-1.7%
-0.8%
-1 .8
-1.0% -1 .9
-1 .9
60" Ø SS MANHOLE #03
STATION: 57+47.27
OFFSET: 0.000
60" Ø SS MANHOLE #04
STATION: 58+06.77
OFFSET: 0.000
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
NN
EC
T
CONNECT EXISTING PIPE
TO NEW STRUCTURE (2)
CONNECT EXISTING PIPE
TO NEW STRUCTURE
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
NOTES
1.CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2.SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED EQUIVALENT TO
CONNECT NEW PIPE TO EXISTING PIPE.
3.CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4.BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. ATLANTIS DR SEWER HAS VERY LITTLE FLOW. EXACT FLOW
DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
6.CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY BE IN
CONFLICT WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
8" GATE VALVE
CONNECT NEW WATERLINE
TO EXISTING WATERLINE
INSTALL DROP MANHOLE SECTION
INSTALL NEW 8"
DI WATERLINE
ABANDON EXISTING 4" WATER MAIN.
PLUG WITH MJ CAPSS
L
AT
ER
AL
R
EC
O N
N
EC
T
8" X 4" REDUCER
4" SLEEVE
53+00
+0
+0
0 56 +0
+0
+0
+0
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
NN
EC
T
8" 45° BEND
8" 45° BEND
8" 22.5° BEND
8" 45° BEND (2)
N
EW
W
AT
ER
S
ER
VI
C E
(T
YP
53+10 53+50 54+00 54+50 55+00 55+50 56+00 56+50 57+00 57+50 58+00 58+50
379.61' OF 8" SDR35 PVC @ 0.45%
Existing 3/4" Water Service Station ≈ 53+28.04
Existing 3/4" Water Service Station ≈ 53+48.82
Existing 3/4" Water Service Station ≈ 53+75.04
Existing 3/4" Water Service Station ≈ 53+84.05
Existing 3/4" Water Service Station ≈ 55+78.24
Existing 3/4" Water Service Station ≈ 54+72.54
Existing 3/4" Water Service Station ≈ 54+34.53
Existing 3/4" Water Service Station ≈ 56+21.53
Existing 3/4" Water Service Station ≈ 56+69.81
Existing 3/4" Water Service Station ≈ 57+24.65
Existing 3/4" Water Service Station ≈ 56+62.20
59.50' OF 8" SDR35 PVC @ 2.72%
Existing 3/4" Gas Service Station ≈ 57+04.26
Existing 3/4" Gas Service Station ≈ 56+00.88
Existing 3/4" Gas Service Station ≈ 55+91.59
Existing 3/4" Gas Service Station ≈ 54+61.34
Existing 3/4" Gas Service Station ≈ 54+43.90
Existing 2" Gas Main Station ≈ 53+60.64
Existing Ground
REMOVE AND DISPOSE EXISTING
6" CONCRETE SEWER PIPE
REMOVE AND DISPOSE EXISTING
6" CONCRETE SEWER PIPE
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
Ex
Ex
Ex
INSTALL NEW 8" DI WATERLINE
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 5
3+
.6
O
FF
SE
T:
.0
T
R
IM
: 4
3.
8"
IN
V O
U T:
.8
(W
8"
IN
V O
U T:
.8
(N
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 5
7+
.2
O
FF
SE
T:
.0
T
R
IM
: 4
3.
8"
IN
V
IN
:4
6.
(S
8"
IN
V
IN
:4
6.
(E
8"
IN
V O
U T:
.0
(N
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 5
8+
.7
O
FF
SE
T:
.0
T
R
IM
: 4
3.
8"
IN
V
IN
:4
4.
(S
8"
IN
V O
U T:
.1
(W
8"
IN
V O
U T:
.3
(N
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
M
AT
C H
LI
N
E
SH
EE
T
SS
M
AT
C H
LI
N
E S
TA
TI
O N
4+
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS2
AT
LA
N
TI
S
DR
S
TA
. 5 3+
T
O
8+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
LEGEND
4" THICK ASPHALT ( 38" PG 58-28)
SE
C
O R
52 47
.5
PP PP
P
P P
P
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSS
SS
IRR 24in
IRR 24in
IR
R
4i n
IR
R
4i n
IR
R
4i n
S
S
S
IR
R
4i n
IR
R
4i n
S
S
S
W 12in W 12in W 12in W 12in W 12in W 12in W 12in
W 12in
W
6i n
W
6i n
W
6i n
W
6i n
W W W
W in W in
FO
FO
FO
FO
FO
FO
FO
FO
FO
SS
5i n
SS
5i n
SS
2i n
SS
2i n
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G in G in
G in G in
G in
G
G G
G G
G
G G
G
G G
G G
G
G in
SO
U
TH
800 WEST
SO
U
TH
264.53' OF 10" SDR35 PVC @ 0.33%
278.22' OF 10" SDR35 PVC @ 0.33%
60" Ø SS MANHOLE #05
STATION: 10+16.04
OFFSET: 0.000
60" Ø SS MANHOLE #06
STATION: 12+96.76
OFFSET: 0.000
60" Ø SS MANHOLE #07
STATION: 15+61.29
OFFSET: 0.000
CONNECT NEW STRUCTURE
TO EXISTING PIPE (3)
EXISTING SURVEY MONUMENT. CONTRACTOR
SHALL NOTIFY UTAH COUNTY SURVEYOR AND
APPLY FOR A "SURVEY MONUMENT EXCAVATION
PERMIT" AT LEAST 72 HOURS PRIOR TO
DISTURBING OR REMOVAL OF ANY MONUMENT.
CONTRACTOR SHALL BE RESPONSIBLE FOR
ANY PERMIT FEES AND FOR ANY DAMAGE
CAUSED TO THE SURVEY MONUMENT.
CONNECT NEW STRUCTURE
TO EXISTING PIPE
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
ABANDON EXISTING IRRIGATION PIPE
FILL ENDS WITH 1.5X DIAMETER
WITH CONCRETE
NOTES
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED
3. EQUIVALENT TO CONNECT NEW PIPE TO EXISTING PIPE.
4. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
5. BYPASS PUMPING REQUIRED FOR 400 SOUTH. 400 SOUTH SEWER AVG FLOW: 0.25 MGD. 800 WEST SEWER HAS VERY LITTLE FLOW AND BYPASS PUMPING MAY OR MAY NOT BE REUIRED. ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE CONTRACTOR. NO PRICE
ADJUSTMENT SHALL BE MADE.
6. ASPHALT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS
7. CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY
BE IN CONFLICT WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
ABANDON EXISTING IRRIGATION PIPE
FILL ENDS WITH 1.5X DIAMETER
WITH CONCRETE
PROTECT 16" WATERLINE IN PLACE.
BRACE IF NEEDED
Existing Aerial Fiber Line
+0
+0
+0
+0
+0
+0
10+00 10+50 11+00 11+50 12+00 12+50 13+00 13+50 14+00 14+50 15+00 15+50
278.22' OF 10" SDR35 PVC @ 0.33%
Existing 16" Water Main Station ≈ 10+36.19
Existing Fiber Line Station ≈ 10+48.96
Existing Power Line Station ≈ 10+51.30
Existing 3/4" Water Service Station ≈ 13+20.08
Existing 3/4" Water Service Station ≈ 12+25.11
Existing 3/4" Water Service Station ≈ 13+70.98
Existing 3/4" Gas Service Station ≈ 11+79.04
Existing 3/4" Gas Service Station ≈ 12+90.71
Existing 3/4" Gas Service Station ≈ 13+42.80
Existing 3/4" Gas Service Station ≈ 14+45.79
Existing 3/4" Gas Service Station ≈ 15+45.85
Existing 8" Water Main Station ≈ 14+65.58
264.53' OF 10" SDR35 PVC @ 0.33%
Existing 2" Fiber Line Station ≈ 11+84.99
Existing Ground
REMOVE AND DISPOSE EXISTING
10" CONCRETE SEWER PIPEREMOVE AND DISPOSE EXISTING
10" CONCRETE SEWER PIPE
Ex
Ex
Ex
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
ABANDON EXISTING IRRIGATION PIPE
FILL ENDS WITH 1.5X DIAMETER
WITH CONCRETE
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 1
5+
.2
O
FF
SE
T:
.0
T
R
IM
: 4
1.
" I
N V
IN
:4
8.
(N
" I N
V O
U T:
.2
(S
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 1
2+
.7
O
FF
SE
T:
.0
T
R
IM
: 4
0.
" I
N V
IN
:4
7.
(N
" I N
V O
U T:
.2
(S
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 1
0+
.0
O
FF
SE
T:
.0
T
R
IM
: 4
9.
" I
N V
IN
:4
6.
(N
" I N
V
IN
:4
6.
(E
" I
N V
O U
T:
.2
(W
8"
IN
V
O U
T:
.7
(S
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS3
W
ES
T
ST
A.
0+
T O
5+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
LEGEND
5" THICK ASPHALT (1
2" PG 58-28)
P P
SS
in
SS
in
SS
in
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
FO
FO
FO
FO
FO
W in W in
W in
W 4in W 4in W 4in W 4in W 4in W 4in W 4in W 4in W 4in W 4in
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G 2in G 2in G 2in G in
G in G in
G in
G
G
G G
G G
G
G
GG
G
G
450 EAST
N O
R
TH
325.60' OF 8" SDR35 PVC @ 0.50% 313.47' OF 8" SDR35 PVC @ 0.50%
60" Ø SS MANHOLE #09
STATION: 3+87.24
OFFSET: 0.000
60" Ø SS MANHOLE #08
STATION: 0+61.63
OFFSET: 0.000
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
CONNECT EXISTING PIPE
TO NEW STRUCTURE (2)
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
NOTES
1.CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2.SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED EQUIVALENT TO CONNECT
NEW PIPE TO EXISTING PIPE.
3.CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4.BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. 450 EAST SEWER HAS VERY LITTLE FLOW. EXACT FLOW
DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5.ASPHALT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS.
6.CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY BE IN CONFLICT
WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
Existing Aerial Fiber Line
0+
1+
2+
3+
4+
5+
' 15
0+00 0+50 1+00 1+50 2+00 2+50 3+00 3+50 4+00 4+50 5+00 5+50
325.60' OF 8" SDR35 PVC @ 0.50%
313.47' OF 8" SDR35 PVC @ 0.50%
Existing 3/4" Water Service Station ≈ 2+35.11 Existing 3/4" Water Service
Station ≈ 3+22.50
Existing 3/4" Water Service Station ≈ 3+76.88
Existing 3/4" Water Service Station ≈ 4+76.24
Existing 12" Storm Pipe Station ≈ 0+73.67
Existing 3/4" Water Service Station ≈ 5+24.97
Existing 3/4" Gas Service Station ≈ 5+11.88
Existing 3/4" Gas Service Station ≈ 3+30.88
Existing 3/4" Gas Service Station ≈ 2+59.65
Existing 4" Gas Main Station ≈ 0+66.46
Existing 3/4" Gas Service Station ≈ 4+28.98
Existing Ground
REMOVE AND DISPOSE EXISTING
6" CONCRETE SEWER PIPE
REMOVE AND DISPOSE EXISTING
6" CONCRETE SEWER PIPE
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
Ex
Ex
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 3
+8 7.
O
FF
SE
T:
.0
T R
IM
: 4
7.
8"
IN
V
IN
:4
8.
(N
8"
IN
V
O U
T:
.8
(S
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 0
+6 1.
O
FF
SE
T:
.0
T R
IM
: 4
7.
8"
IN
V
IN
:4
7.
(N
8"
IN
V
IN
:4
7.
(E
8"
IN
V
O U
T:
.1
(W
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS4
EA
ST
S
TA
. 0 0+
T
O
5+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
LEGEND
M
AT
C H
LI
N
E
SH
EE
T
SS
M
AT
C H
LI
N
E
ST
AT
IO
N
5+
5" THICK ASPHALT (12" PG 58-28)
PP
SS
SS
SS
SS
SS
SS
SS
FO
W 6in W 6in W 6inW 4in W 4in W 4in
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G G
G
G
G
G G
450 EAST
313.47' OF 8" SDR35 PVC @ 0.50%
60" Ø SS MANHOLE #10
STATION: 7+00.71
OFFSET: 0.000
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
NOTES
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED
EQUIVALENT TO CONNECT NEW PIPE TO EXISTING PIPE.
3. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4. BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. 450 EAST SEWER HAS VERY LITTLE FLOW. EXACT FLOW DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5. ASPHALT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS
6. CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY
BE IN CONFLICT WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
5+
6+
7+
7+
' 15
4+60 5+00 5+50 6+00 6+50 7+00 7+50 8+00 8+50
313.47' OF 8" SDR35 PVC @ 0.50%
Existing 3/4" Water Service Station ≈ 4+76.24
Existing 3/4" Water Service Station ≈ 5+24.97
Existing 3/4" Water Service Station ≈ 5+85.61
Existing 3/4" Water Service Station ≈ 6+64.26
Existing 3/4" Gas Service Station ≈ 5+11.88
Existing Ground
REMOVE AND DISPOSE EXISTING
6" CONCRETE SEWER PIPE
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 7
+0 0.
O
FF
SE
T:
.0
T R
IM
: 4
8.
8"
IN
V
O U
T:
.5
(S
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS5
EA
ST
S
TA
. 0 5+
T
O
+4
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
M
AT
C H
LI
N
E
SH
EE
T
SS
M
AT
C H
LI
N
E
ST
AT
IO
N
5+
P P
P
P
SS 6in SS 6in SS 6in SS 6in
SS
in
SS
in
SS
in
SS
inSS SS
SS
SS
SS
IR
R
IR
R
IR
R
IR
R
IR
R
W 6in
W in
W 6in W 6in W 6in W 6in
W in W in
W 4in W 4in W 4in W 4in W 4in
FO FO FO
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G
G G
G G
FO
FO
G in G in
G in G in
G
G
G
G
G
G in in in in in
550 EAST
N O
R
TH
335.84' OF 8" SDR35 PVC @ 0.35%
60" Ø SS MANHOLE #11
STATION: 60+55.46
OFFSET: 0.000
60" Ø SS MANHOLE #12
STATION: 63+91.30
OFFSET: 0.000
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
CONNECT EXISTING PIPE
TO NEW STRUCTURE (3)
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
REMOVE AND REPLACE
EXISTING IRRIGATION PIPE
NOTES
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED
EQUIVALENT TO CONNECT NEW PIPE TO EXISTING PIPE.
3. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4. BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. 550 EAST SEWER HAS VERY LITTLE FLOW. EXACT FLOW DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5. ASPHALT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS.
6. CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY
BE IN CONFLICT WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
+0
+0
+0
+0
+0
+4
' 15
60+00 60+50 61+00 61+50 62+00 62+50 63+00 63+50 64+00 64+50 65+00 65+50
335.84' OF 8" SDR35 PVC @ 0.35%
Existing 3/4" Water Service Station ≈ 60+89.72
Existing 3/4" Water Service Station ≈ 61+82.52
Exisitng 18" Irrigation Pipe Station ≈ 61+97.65
Existing 6" Water Main Station ≈ 63+65.95
Existing 3/4" Gas Service Station ≈ 60+87.48
Existing 3/4" Gas Service Station ≈ 61+02.82
Existing 3/4" Gas Service Station ≈ 62+94.86
Existing 12" Storm Pipe Station ≈ 63+60.65
Existing Ground
REMOVE AND DISPOSE EXISTING
8" CONCRETE SEWER PIPE
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
Ex
Ex
Ex
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 6
0+
.4
O
FF
SE
T:
.0
T
R
IM
: 4
1.
8"
IN
V O
U T:
.0
(N
" Ø
S S
M
AN
H O
LE
ST
AT
IO
N : 6
3+
.3
O
FF
SE
T:
.0
T
R
IM
: 4
3.
8"
IN
V
IN
:4
3.
(S
8"
IN
V
IN
:4
3.
(E
6"
IN
V
IN
:4
3.
(N
8"
IN
V O
U T:
.7
(W
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS6
EA
ST
S
TA
. 6 0+
T
O
4+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
LEGEND
N E
C O
R
7 47
.9
P
SS 8in SS 8in SS 8in SS 8in SS 8in
SS
5i n
SS
5i n
SS
5i n
SS
5i n
SS
SS
SS
SS
SSSS
SS
SS
SS
SS
SD 15in SD 15in SD 15in SD 15in SD 15in SD 15in SD 15in SD 15in
SD
4i n
SD
4i n
SD
4i n
SD 24in SD 24in
SD
SD
SSSD
SD
SD
W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in
W 12in
W
6i n
W
6i n
W
6i n
FO
FO
FO
FO FO FO FO FO FO FO FO FO FO FO FO FO
G in G in
G in
G 2in
G in
G 12in G 12in G 12in G 12in G 12in G 12in G 12in G 12in G 12in G 12in G 12in G 12in G 12in
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G G
G G
G G
G
G
G
G
S O
U
TH
MAIN STREET
334.62' OF 8" SDR35 PVC @ 0.37%
60" Ø Ex. SS Manhole #1
STATION: 80+40.48
OFFSET: 0.000
60" Ø SS Manhole #13
STATION: 83+75.10
OFFSET: 0.000
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
CONNECT NEW PIPE TO
EXISTING STRUCTURE
REMOVE AND DISPOSE OF
EXISTING SS MANHOLE
CONNECT NEW STRUCTURE
TO EXISTING PIPE
REMOVE AND DISPOSE OF
EXISTING SS MANHOLEABANDON EXISTING IRRIGATION PIPE
FILL ENDS WITH 1.5X DIAMETER
WITH CONCRETE
NOTES
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR
APPROVED EQUIVALENT TO CONNECT NEW PIPE TO EXISTING PIPE.
3. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4. BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. MAIN STREET SEWER HAS VERY LITTLE FLOW. EXACT FLOW DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5. ASPHALT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS
6. CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY
BE IN CONFLICT WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
PRESERVE AND PROTECT
EXISTING SURVEY MONUMENT
+0
+0
+0
+0
+0
+0
16'
80+00 80+50 81+00 81+50 82+00 82+50 83+00 83+50 84+00 84+50 85+00 85+50
334.62' OF 8" SDR35 PVC @ 0.37%334.62' OF 8" SDR35 PVC @ 0.37%
Existing 16" Water Main Station ≈ 80+56.22
Existing 3/4" Water Service Station ≈ 82+42.88
Existing 3/4" Water Service Station ≈ 82+97.10
Existing 3/4" Water Service Station ≈ 83+25.50
Existing 3" Power Line Station ≈ 81+51.38
Existing 3/4" Gas Service Station ≈ 83+03.15
Existing 3/4" Gas Service Station ≈ 82+33.24
Existing 3/4" Gas Service Station ≈ 81+45.63
Existing Ground
REMOVE AND DISPOSE EXISTING
8" CONCRETE SEWER PIPE
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
Ex
Ex
Ex . Ex
ABANDON EXISTING IRRIGATION PIPE
FILL ENDS WITH 1.5X DIAMETER
WITH CONCRETE
" Ø
E x.
S S
M an ho le
ST
AT
IO
N
: 8 0+
.4
O
FF
SE
T:
.0
T R
IM
: 4
0.
8"
IN
V
IN
:4
6.
(N
" I N
V
IN
:4
6.
(E
8"
IN
V
IN
:4
6.
(S
" I
N V
O U
T:
.0
(W
" Ø
S S
M an ho le
ST
AT
IO
N
: 8 3+
.1
O
FF
SE
T:
.0
T R
IM
: 4
0.
8"
IN
V
IN
:4
7.
(N
8"
IN
V
O U
T:
.3
(S
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS7
M
AI
N S
TR
EE
T
ST
A.
0+
T O
4+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
W in
W 6in
W 6in W 6in
W 6in
SS 8in SS 8in SS 8in SS 8in
SS
in
SS
in
SS
in
SS
in
SS
in
SS
SS
SS
W in W in
SS
G
G 2in G 2in G 2in G 2in
G 2in
G 2in
G
G
G
G
G
G
G G
G G
G
T
T
T
T
P P
P P
P
P
P
P
P
P
P
P
P
FO
FO
FO
FO
FO
S
CREST DRIVE
W
ES
T
60" Ø SS Manhole #14
STATION: 2+25.11
OFFSET: 0.000
W 8in W 8in W 8in W 8in
W 8in
W 8in
CONTRACTOR TO KEEP EXISTING
WATERLINE IN SERVICE UNTIL NEW
WATERLINE PASSES ALL TESTING AND
OREM CONSTRUCTION ENGINEER
APPROVES ABANDONING OLD WATERLINE
8" SLEEVE
8" X 8" TAPPING TEE WITH THRUST BLOCK
ABANDON EXISTING WATER VALVE
8" GATE VALVE
8" SLEEVE
8" 45° BEND
INSTALL NEW 8" DI WATERLINE
SS LA
TERAL R
ECONNECT
PLUG EXISTING WATERLINE
WITH MJ CAP AND MEGA LUGS
REMOVE AND DISPOSE
OF EXISTING SSMH
REPLACE EXISTING CROSS GUTTER
NOTES:
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR
APPROVED EQUIVALENT TO CONNECT NEW PIPE TO EXISTING PIPE.
3. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER,
SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4. BYPASS PUMPING IS REQUIRED. CREST DRIVE HAS VERY LITTLE FLOW . EXACT FLOW
DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE
FIELD BY THE CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5. INSTALL WATER TIGHT SEAL BELL JOINT CLAMP UNDER EVERY SEWER MAIN OR LATERAL
WITHIN 10' OF ANY NEW WATERLINE JOINTS. SEE DETAIL W SHEET D6
6. ASPHALT PAVING JOINTS NOT ALLOWED IN VEHICLE WHEEL PATHS
N
EW
W
AT
ER
S
ER
VI
C E
(T
YP
PLUG EXISTING TEE
-3.9% -2.6%
-3.
0%
TOP
4733.42
-1 .2
-0
.2
-4 .8
-3
.2
-4 .5
-3
.0
-4 .3
-3
.0
+0
+0
+0
+00
NEW W
ATER SERVICE (T
YP.)
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS8
CR
ES
T
DR
IV
E
ST
A.
0+
T
O
2+
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
C
RE
ST
S
EW
ER
.D W
G
MATC
HLIN
E S
HEET S
S9
MATC
HLIN
E S
TA
TIO
N 2+
LEGEND
W 6i n
W 6i n
W 6in W 6in W 6in W 6in W 6i n
W 6in W 6in
SS 8in
SS 8in
SS 8inSS
SS
SS
SS SS SS
SS
SS
SS
SS
G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in G 2in
G 2in
G 2in
G 2in
G 2in
GG
G
G
G G
G
G
G
GG
G
T T
T
T
T
P
P P
P
P P
P P
P P
FO
FO
FO FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
SS 8in
60" Ø SS Manhole #14
STATION: 2+25.11
OFFSET: 0.000
60" Ø SS Manhole #15
STATION: 3+62.03
OFFSET: 0.000
60" Ø SS Manhole #16
STATION: 7+30.42
OFFSET: 41.723 R
CREST DRIVE
710 WEST
W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in W 8in
W 8i n
INSTALL NEW FIRE
HYDRANT ASSEMBLY
8"
° B
END
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
SS
L
AT
ER
AL
R
EC
O
N N
EC
T
8" TEE
6" SLEEVE
8" GATE VALVE
8" 22.5° BEND
8" 22.5° BEND
ABANDON EXISTING
FIRE HYDRANT
REMOVE AND DISPOSE OF EXISTING SSMH
ABANDON EXISTING
WATER VALVE
PLUG EXISTING LINE WITH MJ CAP AND MEGA LUGS
8" X 6"
REDUCER
8" X 6"
REDUCER
CONNECT EXISTING SEWER PIPE TO NEW STRUCTURE
6" SLEEVE
CONNECT EXISTING
SEWER PIPE TO NEW
STRUCTURE (2)
REMOVE AND DISPOSE
OF EXISTING SSMH
NOTES
1. CONTRACTOR TO FIELD VERIFY SEWER LATERAL SIZE AND MATERIAL.
2. SEWER LATERAL RECONNECTS REQUIRE STAINLESS STEEL FERNCO SHEAR RINGS OR APPROVED EQUIVALENT
CONNECT NEW PIPE TO EXISTING PIPE.
3. CONTRACTOR REQUIRED TO REPAIR ALL DAMAGE TO ASPHALT, CURB, GUTTER, SIDEWALK, SPRINKLERS, AND LANDSCAPING.
4. BYPASS PUMPING MAY OR MAY NOT BE REQUIRED. CREST DR SEWER HAS VERY LITTLE FLOW. EXACT FLOW DATA AND ALL EQUIPMENT NEEDED FOR BYPASS PUMPING WILL BE DETERMINED IN THE FIELD BY THE
CONTRACTOR. NO PRICE ADJUSTMENT SHALL BE MADE.
5. CONTACT MANNY TORRES WITH ENBRIDGE GAS AT 801-376-8798 TWO WEEKS PRIOR TO ANY WORK THAT MAY
BE IN CONFLICT WITH ENBRIDGE GAS'S LINES AND REQUIRE RELOCATION.
INSTALL NEW 8" DI WATERLINE
MODIFIED ADA RAMP
MODIFIED ADA RAMP
-3 .9
-2
.6
-3 .9
-3
.0
-3 .9
-2
.7
-3 .9
-3
.6
-5 .1
-4
.3
-4 .6
-4
.8
-4 .7
-4
.9
-4 .9
-4
.7
-4.8%
-4.3%
+0
+0
+0
+0
+0
17+00
17+90
N
EW
W
AT
ER
S
ER
VI
C E
(T
YP
1+85 2+00 2+50 3+00 3+50 4+00 4+50 5+00 5+50 6+00 6+50 7+00 7+46
" Ø
S S
M an ho le
ST
AT
IO
N
: 2 +2
5.
O
FF
SE
T:
.0
T
R
IM
: 4
4.
8"
IN
V O
U T:
.2
(S E)
" Ø
S S
M an ho le
ST
AT
IO
N
: 3 +6
2.
O
FF
SE
T:
.0
T
R
IM
: 4
5.
8"
IN
V
IN
:4
8.
(N W
8"
IN
V
O U
T:
.6
(S
E)
136.92' OF 8" SDR35 PVC @ 0.35%
383.94' OF 8" SDR35 PVC @ 0.35%
Existing 3/4" Water Service Station ≈ 4+23.84
Existing 4" Sewer Lateral Station ≈ 4+17.56
Existing 3/4" Gas Service Station ≈ 3+78.04 Existing 2" Fiber Line Station ≈ 3+77.03
Existing 3/4" Water Service Station ≈ 3+51.47
Existing 3/4" Water Service Station ≈ 2+75.26
Existing 2" Power Line Station ≈ 2+31.09
Existing 3/4" Gas Service Station ≈ 2+38.75
Existing 3/4" Water Service Station ≈ 6+74.02
Existing 3/4" Gas Service Station ≈ 4+71.88
INSTALL NEW 8" DI WATERLINE
Existing Ground
REMOVE AND DISPOSE EXISTING
8" CONCRETE SEWER PIPE
REMOVE AND DISPOSE EXISTING
8" CONCRETE SEWER PIPE
Existing 3/4" Water Service Station ≈ 6+04.03
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT
SS LATERAL RECONNECT SS LATERAL RECONNECT
SS LATERAL RECONNECT
Existing 3/4" Water Service Station ≈ 5+08.63
Ex
Ex .60
" Ø S
S M an ho le
ST
AT
IO
N : 7
+3 0.
O
FF
SE
T:
1.
R T
R
IM
: 4
7.
8"
IN
V
IN
:4
7.
(N W
8"
IN
V
IN
:4
7.
(N
8"
IN
V
O U
T:
.2
(S
DA
TE
CO
M
M U
N
IT
Y
DE
VE
LO
PM
EN
T
DI
RE
CT
O R
CI
TY
E N
GI
N
EE
R
DA
TE
AP
PR
O
VE
D
AP
PR
O
VA
L
RE
CO
M
M
EN
DE
D
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
SCALE: 1" = 40' (11"x 17" SHEET SIZE)
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
SS9
CR
ES
T
DR
IV
E
ST
A.
2+
T
O
+4
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
C
RE
ST
S
EW
ER
.D W
G
M
AT
C H
LI
N
E
SH
EE
T
SS
M
AT
C H
LI
N
E
ST
AT
IO
N
+0
LEGEND
NOTE:
1. CUT ASPHALT T-PATCH TO WIDTH OF TRENCH, CONSTRUCT PIPELINE & RESTORE SUB-SURFACE. THEN CUT ASPHALT 12" WIDER THAN THE TRENCH ON EACH SIDE. REMOVE ASPHALT & FINISH RESTORATION. IF
TRENCH WALLS COLLAPSE OR WIDEN CUT 12" FROM THAT NEW FINAL WIDTH
BACKFILL IN ROADWAYS OR PARKING AREAS BACKFILL FOR OUTSIDE OF ROADWAYS OR PARKING AREAS
GRADATION
NON-LOAD
NON-LOAD
LOAD
ROADWAY
D
C
B
A
TOP SOIL
REUSE
SPOILS
BACKFILL
UTBC/
SUBBASE
ZONE
TYPE
90%
90%
95%
95%
-6"
-6"
-6"
-3/4"(UTBC)
-3" (SUBBASE)
NOT
SPECIFIED
NOT
SPECIFIED
MAX 12"
MAX 12"
COMPACTION
BACK FILL MATERIAL
LIFT THICKNESS
AASHTO T-180
AASHTO T-180
TEST
ZONE A
ZONE B
ZONE D
ZONE C12"12"
SEE M-4 PIPE ZONES SEE M-4 PIPE ZONES
2. LONGITUDINAL EDGE OF A ROADWAY PATCH SHALL BE CUT TO THE NEAREST SEAM OR ROAD
STRIPING (AND/OR OUT OF THE WHEEL-PATH OF VEHICLES
3. NEW TRENCHES WITHIN 10 FT OF ONE ANOTHER SHALL BE COMBINED INTO A SINGLE PATCH
4. PATCHES EXTENDING MORE THAN 3 4 OF A ROADWAYS WIDTH SHALL BE EXTENDED TO THE FULL
WIDTH OF THE ROAD (GUTTER TO GUTTER). WHEN TRENCHING IS WITHIN 24" OF A CURB AND GUTTER THE REMOVAL OF THE SURFACE LAYERS MUST BE EXTENDED ALL THE WAY TO THE LIP OF GUTTER
SLOPE AS REQUIRED
UTBC AND SUBBASE
WHERE APPLICABLE
AT SPECIFIED THICKNESS
ASPHALT
(MIN. 4" THICK)
SEE NOTE 7
SLOPE AS
REQUIRED
5. PLACE ASPHALT CONCRETE IN LIFTS NO GREATER THAN 3", OR LESS THAN 2"
6. T-PATCH REQUIRED FOR ALL FINAL ASPHALT PAVEMENT RESTORATION
7. ASPHALT THICKNESS WILL MATCH THE EXISTING ASPHALT THICKNESS PLUS 1", WITH A MINIMUM OF
4". IF EXISTING ASPHALT THICKNESS IS 6" OR GREATER, THEN THE ASPHALT PATCH WILL MATCH THE
EXISTING THICKNESS.
8. LIMIT LENGTH OF OPEN TRENCHES TO 200 LINEAL FEET DAY OR NIGHT
TRENCH DETAILS
N.T.S.
DETAIL #3
DELICATE PIPE PVC, PLASTIC
OR HDPE
(STORM DRAIN AND SEWER)
DETAIL #1
DUCTILE IRON WRAPPED STEEL, PVC OR HDPE
(WATERLINE)
DETAIL #2
CONCRETE PIPE (STORM
DRAIN)
DETAIL #4
STEEL PIPE OR PVC LINES LESS
THAN 3" DIA.
12" MIN.
4"
MIN
W
12" MIN
O. D.
4" MIN
SAND
NOTES:
1. ALL WATERLINE PIPE BEDDING SHALL BE SAND, MIN. 12" ABOVE TOP OF PIPE.
2. SAND IS ACCEPTABLE BEDDING FOR ALL FIBER OPTIC OR COMMUNICATIONS
CONDUITS.
3. FOR CONCRETE PIPE "W" SHALL NOT EXCEED 24" GREATER THAN THE DIAMETER OF
THE PIPE, "W" MUST ALLOW ENOUGH SPACE FOR COMPACTION EQUIPMENT
4. DETAIL #2 CONSISTS OF TYPE III BEDDING FOR CONCRETE PIPE.
5. SEE TRENCH DETAILS FOR INFORMATION ABOUT BACKFILL.
6. PIPE BEDDING TO BE COMPACTED BY VIBRATING OR CONSOLIDATING TO A MIN.
DENSITY OF 90% OF STANDARD PROCTOR MAX DENSITY (AASHTO-99.) PIPE BEDDING
TO MEET PIPE MANUFACTURE'S INSTALLATION SPECIFICATIONS. THE MORE
RESTRICTIVE STANDARD TO BE APPLIED.
7. LIFTS SHALL NOT EXCEED 12" IN THICKNESS.
8. PLASTIC POLYETHYLENE, CORRUGATED STEEL. LARGE DIAMETER WRAPPED STEEL
PIPE, VITRIFIED CLAY OR OTHER TYPES NOT LISTED.
O.D.
O.D.
4"
MIN
O.D.
12" MIN.
-3 4" GRANULAR
-3 4" GRANULAR
(SEE NOTE #6)
SAND
SAND
(SEE NOTE #6)
-2" MATERIAL (SEE NOTE #6)
-2" MATERIAL
4"
MIN
W
W
W
12" MIN.
PIPE ZONES
N.T.S.
2.9
5.3
5.3
5.4
5.4
10.0
2.0
3.7
4.8
5.5
7.5
9.0
2.75
4.9
6.4
7.4
10.0
14.0
4.0
7.1
9.3
11.8
14.6
18.0
7.5
13.2
17.3
20.0
27.0
33.0
5.3
9.4
12.3
14.2
19.3
24.0
8"
10"
12"
14"
16"
1502.02.02.02.03.42.4
6"
--AABC, G, H D, E, F
4"
WATER
DESIGN PSI
REDUCER ONE
SIZE
REDUCTION
22.5° & 11.25°
ELBOW BEND
30° ELBOW
BENDS
45° ELBOW
BENDS
90° ELBOW &
CROSSES
IN LINE VAVLE,
TEE OR END
PLUG
PIPE SIZE
(INCHES)
WATERLINE THRUST BLOCK BEARING AREA (SQ. FEET)
DIRECT BEARING THRUST BLOCKS
THE AREA OF BEARING
PER THRUST BLOCK TO
EQUAL THE FULL AREA
SPECIFIED FOR THE
LARGEST PIPE
THE AREA OF
BEARING PER
THRUST BLOCK TO
EQUAL 12 THE AREA
SPECIFIED FOR THE
LARGEST PIPE
SEE NOTE 4
THRUST BLOCK SIZES
N.T.S.
3" MIN - 6" MAX
6" MAX.
IN CUL DE SAC
25' 0"
THRUST BLOCK (BEARING
AREA = 6 SQ. FEET)
TAPE
BACK OF WALK
LID
NEW 6" GATE VALVETRACER WIRE
THRUST BLOCK (BEARING
AREA = 6 SQ. FEET)
TEE CONNECTION TO MAIN
LINE & WRAP WITH MIN. 8 MIL
POLY WRAP (SEE AWWA C105)
FLANGE X FLANGE
CONNECTION
4" - 2" SCREENED DRAINROCK
9 CU. FEET STOP AND WASTE RESERVE
SLAG NOT PERMITTED
VALVE BOX
DO NOT POUR CONCRETE
AROUND WEEP HOLE
OF FIRE HYDRANT.
VALVE BOX CENTERING AND
ALIGNMENT DEVICE (SEE NOTE 6)
18" MIN. - 24" MAX.
TO FLANGE
FIRE HYDRANT ASSEMBLY
N.T.S.
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
A -N.T.S.
B
C
D
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
DT1
DE
TA
IL
S
A- D
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D
G
TAPPING SADDLE
PVC, DUCTILE, OR CAST
DIRECT TAP
DUCTILE IRON AND CAST IRON PIPE
MAIN LINE
6" MIN.
6" MAX
6" MAX / 0" MIN
6" MINIMUM
NOTES:
1. 3/4" AND 1" TAPS FOR DUCTILE IRON PIPE 4" AND LARGER.
2. USE SAND ONLY FOR PIPE BEDDING.
3. ON EXISTING WATER MAINLINES OREM CITY WILL INSTALL
ALL TAPS 2" AND SMALLER.
4. IF USING POLY, INSERTS ARE REQUIRED AT THE
COMPRESSION FITTING.
5. TAPS MUST BE STAGGERED A MINIMUM OF 8" APART ON DI
AND 18" APART ON PVC.
6. SADDLES MUST BE DESIGNED FOR THE TYPE OF PIPE THEY
ARE BEING USED WITH, I.E. ROMAC 305, 306 OR EQUIVALENT
FOR PVC AND ROMAC 202NS (NYLON COATED) OR
EQUIVALENT FOR DI.
MAIN LINE
6" MAX / 0" MIN
PVC, DUCTILE,
OR CAST
STAINLESS STEEL
STAINLESS STEEL NUT
RUBBER GASKET
SADDLE BODY TO BE FUSION
BONDED AND EPOXY COATED
CORPORATION STOP IRON PIPE THREAD
ONLY. NO CC TAPER THREAD FORD FB1100
Q-NL OR APPROVED EQUAL
COMPRESSION JOINT W/ INSERT
14 GAUGE INSULATED SOLID
COPPER TRACER WIRE
WHEN USING POLYETHYLENE TUBING,
WIRE IS TO BE SPLICED WITH ALL
SERVICE CONNECTIONS AND COVERED
WITH CORROSION PROTECTION SUCH
AS GEL CAPS OR MASTIC PADS. TRACER
WIRE IS STILL REQUIRED WHEN USING
TYPE "K" COPPER.
14 GAUGE INSULATED SOLID
COPPER TRACER WIRE
TYPE "K" 3 4" OR 1" COPPER TUBING
OR BLUE HDPE CTS 200 PSI, SDR-9
AS APPROVED BY CITY OF OREM
CORPORATION STOP IRON PIPE THREAD ONLY.
NO CC TAPER THREAD FORD FB1100 Q-NL OR APPROVED EQUAL
DUCTILE IRON
COMPRESSION JOINT W/ INSERT
WHEN USING POLYETHYLENE TUBING,
WIRE IS TO BE SPLICED WITH ALL
SERVICE CONNECTIONS AND COVERED
WITH CORROSION PROTECTION
SUCH AS GEL CAPS OR MASTIC PADS.
TRACER WIRE IS STILL REQUIRED WHEN
USING TYPE "K" COPPER
WATERMAIN TAPS
N.T.S.
NOTE:
1. WIRE IS TO BE SPLICED IN AT ALL CONNECTIONS AND COVERED OR COATED WITH
CORROSION PROTECTION USING EITHER GEL CAPS OR MASTIC PAD. INSTALLER TO WRAP
W/ PIPE WRAP TAPE UPON COMPLETION OF WIRE CONNECTION
SPLIT BOLT
CONNECTION
EXPOSED
GROUND WIRE
WIRE TAPED TO
TOP OF WATERLINE
TRACER
WIRE
14 GAUGE
TRACER WIRE
(MAIN LINE)
14 GAUGE
SPLIT BOLT
14 GAUGE
TRACER WIRE
(FH SERVICE,
TEE IN LINE,
OR METER)
FOR USE WITH
TEE, FIRE HYDRANT,
OR SERVICE
VALVE BOX
BOTTOM
VALVE BOX
TOP
TRACER
WIRE
18" PVC STABILIZER
REQ'D
SPLIT BOLT
CONNECTION
BARE 6" OF TRACER WIRE AND
WRAP TIGHTLY AROUND
SETTER. SECURE WITH PIPE
WRAP TAPE TO PROTECT ALL
BARE WIRE
TRACER WIRE DETAILS
N.T.S.
RING & COVER
D&L SUPPLY TYPE B-5076-R1 AND B-5076-01
4"
29" 4"
35" 30"
2"
8"
WATER METER RING AND COVER
N.T.S.
NOTES:
1. MIN. COVER ON SERVICE LINE IS 42".
2. FOR INSTALLATIONS WITH CONTINUOUS TRAFFIC FLOW ON METER LID, A STANDARD MANHOLE SECTION
CONE WITH 36" MIN. HEIGHT REINFORCED CONCRETE WITH STANDARD 30" MANHOLE RING AND COVER
SHALL BE USED AS APPROVED BY WATER SECTION PERSONNEL.
3. TRACER WIRE SHALL BE 14 GAUGE SOLID INSULATED COPPER WIRE INSTALLED WITHIN 6" ABOVE TOP OF
PIPE.
4. WIRE IS TO BE SPLICED IN AT ALL SERVICE CONNECTIONS TO THE MAIN AND COVERED OR COATED WITH
CORROSION PROTECTION SUCH AS GEL CAPS OR MASTIC PAD.
5. MULTIPLE SETTERS IN A BOX SHALL BE TAGGED FOR ADDRESS IDENTIFICATION.
6. IF A SERVICE IS NOT INSTALLED IN A STRAIGHT ALIGNMENT IT MUST BE COPPER.
7. IF USING POLY, INSERTS ARE REQUIRED AT THE COMPRESSION FITTING.
8. ALL BRASS FITTINGS MUST BE LEAD-FREE.
9. ALL TREES, SHRUBS, AND DEEP ROOTED VEGETATION MUST BE A MINIMUM OF 36" HORIZONTAL AND 10'
VERTICAL FROM EDGE OF METER CAN
10. ALL COMMERCIAL IRRIGATION SYSTEMS MUST BE PROTECTED BY A REDUCED PRESSURE ZONE (RPZ)
BACKFLOW ASSEMBLY. (SEE W-23).
11. RESIDENTIAL IRRIGATION SYSTEMS SHALL BE PROTECTED AGAINST BACKFLOW BY AN ATMOSPHERIC
VACUUM BREAKER OR A PRESSURE VACUUM BREAKER INSTALLED TO THE MANUFACTURERS GUIDELINES
OR A REDUCED PRESSURE PRINCIPAL BACKFLOW PREVENTION ASSEMBLY. (SEE W-23).
24" MIN.
DISTANCE
BETWEEN
CAN AND
STOP &
WASTE
WHITE METER BOX: 21" DIA. 36" MIN. HEIGHT
CORRUGATED PVC OR ADS INSTALLED
WITH STANDARD 21" CAST IRON RING
AND LID ASSEMBLY WITH LOCKING NUT
LID TO BE D&L SUPPLY MODEL
L2244-F1, L2240-01, OR
APPROVED EQUIVALENT
LID TO BE FLUSH WITH
FINISHED LANDSCAPING
a. DUAL CHECK VALVE SHALL
CONFORM TO AMERICAN SOCIETY
OF SANITARY ENGINEERS Std.
1024.
b. FORD HCCA "SERVICEABLE IN
LINE" OR APPROVED EQUIVALENT.
c. INSTALLATION FOR NEWLY
CONSTRUCTED BUILDINGS ONLY.
18" PVC
STABILIZER
REQ'D
3' OF EXCESS WIRE SHALL BE
LEFT IN THE TOP OF ALL
METER CANS TO PROVIDE
FOR LOCATOR CONNECTION
TRACER WIRE TO BE USED WITH POLYETHYLENE TUBING
TAP @ 30° (MAXIMUM) SEE W-10
COMPRESSION JOINT W/ INSERT
TYPE "K" 3 4" OR 1" COPPER TUBING
OR BLUE HDPE CTS 200PSI, SDR-9
WITH INSERTS
6" NOTCH
COMPRESSION
JOINT W/
INSERT
SIZE AS DETERMINED BY
BUILDING DEPARTMENT
4" MINUS GRAVEL
ENVELOPE 4 CU. FT BELOW
BARE 6" OF TRACER WIRE AND WRAP
TIGHTLY AROUND SETTER. SECURE
WITH PIPE WRAP TAPE TO PROTECT
ALL BARE WIRE
3/4" & 1" SERVICE LINE INSTALLATION
N.T.S.
CORPORATION STOP IRON PIPE THREAD ONLY.
NO CC TAPER THREAD. FORD 1" FB100-4-Q-NL
OR APPROVED EQUAL
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
D -N.T.S.
E
F
G
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
DT2
DE
TA
IL
S
E- G
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D
D
C
B
A
WATER SERVICES OVER
OPTION #1
WATER SERVICES UNDER
OPTION #2
WATER MAINS UNDER
OPTION #3
NOTES:
1. CROSS REFERENCE WATER LATERAL
CROSSING SEWER.
2. ALL POLY LINE W/ COMPRESSION FITTINGS FOR
WATER SERVICES REQUIRE INSERTS
3. ANY PIECE OF PIPE SPLICED TO THE SERVICE
LINE MUST BE OF SAME MATERIAL AS EXISTING
PIPE.
CENTERED
TABLE OF DIMENSIONS
NO. SEWER MAIN OTHER
18" 2"
6"10' - 0"
18" 12" MIN.
O.D. + 12"O.D. + 20'
A
A
VARIES
C
VAR
IES
D
REFER TO THE SPECIFICATIONS
FOR CASING PLACEMENT
EXISTING
SERVICE LINE
OBSTRUCTION
COMPRESSION
COUPLING W/ INSERT
MATCH SIZE OF EXISTING
SERVICE LINE
EXISTING GROUND
OBSTRUCTION
REFER TO THE SPECIFICATIONS
FOR CASING PLACEMENT
EXISTING
SERVICE LINE
COMPRESSION
COUPLING W/ INSERT
INSULATION MUST BE INSTALLED
IF THERE IS NOT ADEQUATE
SEPARATION AND DEPTH
ATTACH TO EXISTING
MAIN WITH SLEEVE
OR COUPLING WITH
LOCKING FOLLOWERS
THRUST BLOCKS
AND TIE-DOWN
RESTRAINTS (2) #4 REBAR
INSTALL LOCKING
FOLLOWERS ON ALL BENDS
THRUST BLOCKS
AND TIE-DOWN
RESTRAINTS (2) #4 REBAR
INSTALL LOCKING
FOLLOWERS ON ALL BENDS
OBSTRUCTION CASING REQUIRED IF VERTICAL
SEPARATION CANNOT BE MET
B
WATERLINE LOOP
N.T.S.
DEEP DROP
SHALLOW DROP
SEE MANHOLE DETAIL SS-1 FOR MORE
DETAILS ON MANHOLE CONSTRUCTION.
NOTES:
1. CONCRETE PLACED AGAINST UNDISTURBED MATERIAL OR
SHEETING
2. EXTEND CASEMENT TO FIRST JOINT BEYOND EXCAVATION FOR
DROP CONNECTION
3. DROP PIPE TO BE SAME DIAMETER AS SEWER DISCHARGING INTO
MANHOLE FOR SEWERS UP TO AND INCLUDING 12" SIZE
4. IF THE ELEVATION DIFFERENCE FROM FLOWLINE IN TO FLOWLINE
OUT IS 12" TO 24" USE SHALLOW DROP DETAIL. IF IT IS GREATER
THAN 24" USE DEEP DROP DETAIL.
CONCRETE ENCASEMENT
(SEE NOTE #2)
JOINT
CUT OPENING IN PRECAST
MANHOLE BARREL AND SEAL
WITH NON-SHRINK MORTAR (TYP.)
JOINT
CONCRETE ENCASEMENT
8" MIN. COVER
DROP MANHOLE SECTION
N.T.S.
NOTES:
1. CLEANOUT REQ'D EVERY 75.
2. INSTALL ADDITIONAL CLEANOUT REQ'D 5'-0" MAX. FROM WALL OF BUILDING STRUCTURE.
3. CLEANOUT REQ'D 2' MIN. TO 4' MAX. FROM PROPERTY LINE.
4. IF FERNCO'S ARE USED THEY ARE REQUIRED TO BE SHEAR BANDS OR APPROVED EQUAL.
5. ALL SEWER LATERALS ARE REQUIRED TO HAVE A MINIMUM OF 2.0% SLOPE. A 1.0% MINIMUM
SLOPE MAY BE ALLOWED FOR THE FOLLOWING TYPES OF PIPE:
- SDR-35 PVC PIPE FOR 6" DIAMETER AND LARGER.
- ABS OR SCHEDULE 40 PVC PIPE FOR 4" DIAMETER.
6. IF THE DIAMETER OF THE SEWER LATERAL PIPE IS GREATER THAN HALF THE SIZE OF THE
SEWER MAIN LINE PIPE A MANHOLE SHALL BE PLACED AT THE MAIN LINE CONNECTION.
2'-0"
SEE M-4 PIPE ZONE
1'-0"
42" MIN COVER
AT PROPERTY LINE
5'-0" MAX
FROM WALL,
MIN 2'-0"
FROM ANY
STRUCTURE
2'-0"
SEE M-4 PIPE ZONES
SAFE TRENCH SLOPE
3/4" MINUS
MATERIAL
GROUT AROUND
CONNECTION TO
SEWER MAIN
SEWER LATERAL
CONNECTION SHALL
BE 45° TO THE CENTER
OF SEWER MAIN
B-101 WITH BOWL WAX OR EQUIVALENT.
INSERT-A-TEE CAN ONLY BE USED ON 8" OR LARGER PIPE
COUPLING
45 DEGREE BEND
4" SEWER PIPE MIN
SLOPE (SEE NOTE 5)
COUPLING
COUPLING
PVC
WYE-COMBO
4" SDR35 PVC
OR ABS PIPE
SEWER MAIN
COUPLING
BRASS CLEAN-
OUT PLUG
SEWER LATERAL CONNECTION
N.T.S.
SEE M-3 TRENCH DETAILS SEE M-3 TRENCH DETAILS
TRAFFIC RATED AREAS REQUIRE RING
AND COVER D&L SUPPLY M-9009 WITH
"SEWER" ON LID OR APPROVED EQUAL
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
I
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
DT3
DE
TA
IL
S
H- J
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D W
G
H
J
KE
N
T
SE
AL
KE
N
T
SE
AL
A
A
FLOW FLOW
D O
M
ES
TI
C
D
IS
C H
AR
G
E
4% M
IN
SECTION A-A
NOTE:
1. MANHOLE BASE AND PRECAST TO CONFORM TO ASTM C 478
2. NO 4" LATERAL CONNECTIONS ARE ALLOWED INTO
MANHOLES
3. NO STEPS ALLOWED
4. NO REVERSIBLE HARDWARE IS ALLOWED
5. MIN. 0.1' DROP THROUGH MANHOLE UNLESS NOTED
OTHERWISE
4% MIN.
FOUNDATION
6" MIN
6" MIN
PIPE
EMBEDMENT
SUITABLE
BACKFILL
6" MIN
4" MIN
5"21 2"
2"
2"
1'-3"
4"
3'-0" CONE
SECTION
6"
8" MIN
25" HARDWARE
INFRA-RISER, WHIRLYGIG, OR
APPROVED EQUIVALENT REQ'D
TO MAKE LID FLUSH W/ FINAL
SURFACE. (NO SHIMS ALLOWED.)
24 3/4" VENTED SEWER LID REQ'D
PRE-CAST BASE WITH
RUBBER BOOT
-1' GRANULAR AREA
UNDER BASE TO BE
COMPACTED TO 95%
PIPES VARY
IN SIZE
RESILIENT CONNECTION
BETWEEN PIPES AND
MANHOLE REQ'D
SET LEG IN
CONCRETE
BASE
PRECAST SEWER MANHOLE
N.T.S.
BELL JOINT CLAMP
1'-0" MIN
BELL JOINT CLAMP REQUIRED WHEN JOINT IS
WITHIN 10' OF SS LATERAL OR MAIN CROSSING
EXISTING SS LATERAL
1'-0"
INSTALL WARNING TAPE 1' ABOVE
AND PARALLEL TO SS LATERAL
8"-12" CLASS 350
DI WATERLINE
NOTES:
1. MINIMUM 12" TO 18" CLEARANCE BETWEEN WATERLINE AND SS LATERAL WATERLINE / SS LATERAL CROSSING DETAIL
N.T.S.
2%
NOTES:
1. THIS IS ONLY A GENERAL DETAIL OF A MODIFIED ADA RAMP. EVERY MODIFIED
RAMP MUST BE ADJUSTED ACCORDINGLY TO FIT TO THE CORNER ON WHICH IT
IS INSTALLED.
2. ANY MODIFICATIONS TO THIS STANDARD MUST BE APPROVED BY THE PROJECT
ENGINEER.
3. THE FLARES SHALL NOT EXCEED 8.33% GRADE.
4. THE MINIMUM DISTANCE FROM THE BACK OF CURBWALL TO THE FLOW LINE OF
THE GUTTER SHALL BE 6'-6" THROUGH THE RAMP.
5. THE RAMP SHALL NOT EXCEED A 2% GRADE.
6. WITH THE EXCEPTION OF THE DETECTABLE WARNING AREA, ALL CONCRETE
SURFACES ON THE RAMP AND FLARES SHALL BE BROOMED ROUGH.
7. THE RAMP & FLARES SHALL BE VISUALLY CONTRASTING.
8. A 7" CONCRETE THICKNESS SHALL BE REQUIRED ON THE RADIUS.
9. A 4" CONCRETE THICKNESS SHALL BE REQUIRED IN THE WALKWAY OUTSIDE
OF THE RADIUS.
10. CURB WALL CAN BE POURED MONOLITHIC WITH THE RAMP.
11. COLOR OF ADA DETECTABLE WARNING STRIPS / TRUNCATED DOMES SHALL BE
YELLOW
4'-0" RAMP FROM THE BACK OF
SIDEWALK INCLUDING
DETECTABLE WARNING AND
TRACE AREA.
2% GRADE
6" SMOOTH AREA
AT 8.33%
GRADE
1'-6"
GUTTER AT 5% MAX
GRADE
DOME SPACING SHALL NOT
EXCEED 2.4" O.C AND SHALL
NOT BE LESS THAN 1.6" O.C
0.5" OR 50%
OF BOTTOM
0.9" MIN; 1.4" MAX
6"
CURB
WALL
5' FLARE MIN.
5' FLARE
0.2"
HEIGHT VARIES
6'-6"
7"
1-1/2"
DETECTABLE WARNINGS
RAISED TRUNCATED DOMES
A
A
MIN.
SUBBASE TO BE A MINIMUM OF 6" OF A-1
GRADATED MATERIAL. REMOVAL OF EXISTING
MATERIAL AS DETERMINED BY CITY ENGINEER.
4" MIN. COMPACTED UTBC REQ'D
RADIUS WILL
VARY
FOR EACH RAMP
CURB
WALL 6"
MODIFIED ADA RAMP
N.T.S.
6"
1-1/8"
TYPICAL SECTION
DRIVE APPROACH
7"
4"
6'
5"
1"
1'-6"4'
7"
1"
6"
6'
1'-5"2'-1"2'-6"
1-12" 6-12"
2"
SUBBASE TO BE A MINIMUM OF 6" OF A-1
GRADATED MATERIAL. REMOVAL OF EXISTING
MATERIAL AS DETERMINED BY CITY ENGINEER.
(TYP)
4" MIN. COMPACTED UTBC REQ'D (TYP.)
6' MONOLITHIC CURB, GUTTER, AND SIDEWALK CROSS SECTIONS
N.T.S.
CI
TY
O F
O
RE
M
O
RE
M , U
T
N
O
RT
H
ST
AT
E
ST
EN
GI
N
EE
RI
N G
DI
VI
SI
O
N
CO
M M
U N
IT
Y
DE
VE
LO
PM
EN
T
DE
SC
RI
PT
IO
N
BY
RE
V
DA
TE
CH
EC
KE
D
DR
AW
N
DE
SI
GN
K -N.T.S.
L
M
N
TL
N
SCSC
M
AR
CH
M
AR
CH
M
AR
CH
DT4
DE
TA
IL
S
K- N
S
EW
ER
R
EP
LA
CE
M
EN
T
PR
O
JE
CT
PR
O
JE
CT
N U
M
BE
R:
5-
Z:
\D
S_
EN
G\
EN
G_
PR
O
JE
CT
S\
\2 5-
1-
SW
R
SE
W
ER
R
EH
AB
IL
IT
AT
IO
N
P
RO
JE
CT
\D
ES
IG
N
\D W
G\
-0
B
AS
EM
AP
.D
6"
1-1/8"
TYPICAL SECTION
DRIVE APPROACH
7"
4"
6'
5"
1"
1'-6"4'
7"
1"
6"
6'
1'-5"2'-1"2'-6"
1-12" 6-12"
2"
SUBBASE TO BE A MINIMUM OF 6" OF A-1
GRADATED MATERIAL. REMOVAL OF EXISTING
MATERIAL AS DETERMINED BY CITY ENGINEER.
(TYP)
4" MIN. COMPACTED UTBC REQ'D (TYP.)
6' MONOLITHIC CURB, GUTTER, AND SIDEWALK CROSS SECTIONS
N.T.S.
5'-0"
9" 7"
3"
6" 12" TYP.
4" MIN. COMPACTED
UTBC REQ'D
5 - #4 BARS @ 12" O.C. (TYP)
SUBBASE TO BE A MINIMUM OF 6" OF A-1 GRADED MATERIAL.
REMOVAL OF EXISTING MATERIAL AS DETERMINED BY CITY
ENGINEER. (TYP)
5' CONCRETE CROSS GUTTER
N.T.S.
VARIES VARIES
VARIES
2% MIN. TO 7% MAX. 2% MIN. TO 7% MAX.
℄ CROWN 4" THICK HMA (38" PG 58-28)
EXISTING CONCRETE CURB, GUTTER & SIDEWALK
EXISTING CONCRETE CURB, GUTTER & SIDEWALK
ROADBASE (8" THICK MINIMUM)
8"
VARIES
Existing Subgrade
8"
Existing Subgrade
ROADBASE
HMA (4" 38" PG 58-28)
VARIES
8" MINIMUM
MOISTURE CONDITION
AND COMPACT DISTURBED
SUBGRADE
ROADWAY SECTION
SHEETS SS1, SS8, SS9
PAVEMENT RECONSTRUCT SECTION
8"
FINE GRADE AND
COMPACT ROADBASE
Q
PAVEMENT RECONSTRUCTION SECTION