Product Catalog - 21-115532-001-06.pdf

PDF 3 MB Posted

Attached to
RFQ 19PK4025Q5028 - KHI-FAC Medium Voltage Equipment's Spares
Solicitation number
19PK4025Q5028
Issued by

About this file

This document is a detailed Installation, Operation, and Maintenance manual for a Siemens JFR Distribution Step-Voltage Regulator (Product #21-115532-001, PR4018-06). The manual provides comprehensive technical specifications, installation guidelines, maintenance procedures, and parts lists for the voltage regulation equipment. Key features include a Vari-AmpTM position indicator, polarized disconnect switch, hinged control panel, and options for remote mounting of control equipment. The manual covers various electrical configurations, including single-phase, open delta, closed delta, and wye connected systems, with voltage ratings ranging from 2,500 to 19,920 volts and kVA capacities from 50 to 1,665.

The document details critical operational considerations such as lightning protection, thru-fault ratings, cooling mechanisms, and maintenance requirements. It includes explicit safety warnings about high-voltage risks and provides detailed instructions for placing the regulator in service, removing it from service, and performing periodic inspections. The parts list is extensive, covering components like bypass arresters, bushings, dial switches, and quick-break mechanisms, with specific part numbers and compatibility information for different voltage and kVA ratings. The manual is designed to support comprehensive understanding and maintenance of the JFR voltage regulator across various electrical system configurations.

View the file

Other files

File Type Posted
RFQ 19PK4025Q5028 Medium Voltage Equipments Spares.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

s Installation / Operation / Maintenance

Instructions

21-115532-001

PR4018-06

SUPERCEDES

21-115532-001

PR4018-05

www .

El ec tric alP ar tM an ua ls

. c om

INTRODUCTION

Inspection for Damage in Shipment……….…. 1 Special Features Polarized Disconnect Switch And Hinged Control Panel………….........…... 13 Remote Mounting of Control Equipment…….. 13 Vari-AMPTM Position Indicator………………... 13 Operation at Less Than Rated Voltage….…… 14 Forced Air Cooling……………………………... 15 Subbase Assembly…………………………….. 15 Parts List Major Components…………………………….. 16 Position Indicator………………………………. 17 Type TLG Dial Switch…………………….……. 18 Type TLG Quick Break Mechanism………….. 19 Type TLF Dial Switch………………………….. 20 Type TLF Quick Break Mechanism………….. 21 Bypass Arresters………………………………. 22 Bushings………………………………………… 23

Special Features Polarized Disconnect Switch And Hinged Control Panel……....………..…... 13 Remote Mounting of Control Equipment…….. 13 Vari-AMPTM Position Indicator………………... 13 Operation at Less Than Rated Voltage….…… 14 Forced Air Cooling……………………………... 15 Subbase Assembly…………………………….. 15 Parts List Major Components…………………………….. 16 Position Indicator………………………………. 17 Type TLG Dial Switch……….…………………. 18 Type TLG Quick Break Mechanism………….. 19 Type TLF Dial Switch………………………….. 20 Type TLF Quick Break Mechanism………….. 21 Bypass Arresters………………………………. 22 Bushings………………………………………… 23

TABLE OF CONTENTS

Page Page

For Emergency Service Call: 1-800-241-4453

Siemens Power Transmission & Distribution, Inc.

THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT, NOR TO PR VIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAl TENANCE. SHOULD FURTHER INFOR- MATION BE DESIRED OR PROBLEMS ARISE WHICH ARE NOT COVERED SUFI CIENTLY FOR THE PURCHASER’S PURPOSES, THE MATTER SHOULD BE REFERRED TO YOUR SIEMENS POWE TRANSMISSION & DISTRIBUTION LLC REPRESENTATIVE.

THE CONTENTS OF THIS INSTRUCTION MANUAL SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR EXI~ ING AGREEMENT, COMMITMENT OR RELATIONSHIP. THE SALES CONTRACT CONTAINS THE ENTIRE OBLIGATION ( SIEMENS POWER TRANSMISSION & DISTRIBUTION LLC. THE WARRANTY CONTAINED IN THE CONTRACT BETWEE THE PARTIES IS THE SOLE WARRANTY OF SIEMENS POWER TRANSMISSION & DISTRIBUTION LLC. ANY STAT MENTS CONTAINED HERON DO NOT CREATE NEW WARRANTIES OR MODIFY

THE EXISTING WARRANTY.

www .

El ec tric alP ar tM an ua ls

INTRODUCTION

Type JFR single-phase step-voltage regulators are designed to give dependable service and to make installation, opera-tion and maintenance as simple as possible.

Technology advances, especially in the realm of the control apparatus, make it efficient to provide a separate instruction manual for the Accu/StatTM control provided with this JFR Regu-lator. For specific control information, refer to the Accu/StatTM control manual included with the regulator.

QUALIFIED PERSON

Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices.

(b)

Is trained in rendering first aid.(c)

(a)

This equipment contains hazardous voltages. Se-vere personal injury or property damage can result if safety instructions are not followed.

To prevent:

Do not service or touch until you have de-energized high voltage, grounded all terminals and turned off control voltage. Grounding terminals with line to ground capacitors may produce a small arc.

Only qualitifed personnel should work on or around this equipment after becoming thoroughly familiar with all maintenance procedures contained herein.

WARNING

Indicates an imminently hazardous situa-tion which, if not avoided, will result in death or serious injury

DANGER

Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.

WARNING

Indicates a potentially hazardous situa-tion which, if not avoided, may result in minor or moderate injury.

CAUTION

FOR THE PURPOSE OF THIS MANUAL AND PRODUCT

LABELS, A QUALIFIED PERSON IS ONE WHO IS FAMILIAR

WITH THE INSTALLATION, CONSTRUCTION AND OPERA-

TION OF THE EQUIPMENT, AND THE HAZARDS INVOLVED.

IN ADDITION, HE HAS THE FOLLOWING QUALIFICATIONS:

Is trained and authorized to de-energize, clear, ground and tag circuits and equipment in accordance with es-tablished safety practices.

Distinctive signal words (DANGER, WARNING, CAUTION) are used in this instruction book to indicate degrees of hazard that may be encountered by the user. For the purpose of this manual and product labels these signal words are defined below.

www .

El ec tric alP ar tM an ua ls

INSPECTION FOR

DAMAGE IN SHIPMENT

Check each item with the shipping manifest immediately upon receipt of the regulator. Make a thorough visual in-spection of the regulator. Check for evidence of damage attributable to mishandling in shipment. Should any short-age or damage be found, notify the local agent of the carrier making the delivery and make appropriate notation on the freight bill. A claim should be made immediately with the carrier. Siemens should be notified

STORAGE PRIOR TO

INSTALLATION

The regulator may be stored without any particular pre-cautions or protection. Assure, however, that the control compartment enclosure is tightly closed.

www .

El ec tric alP ar tM an ua ls

DANGER

Hazardous high voltage is present at the line terminals of the bushings on the cover of the regulator.

Will cause severe injury or death.

To prevent:

Isolate the regulator before servicing.

Type JFR voltage regulators are routinely equipped with line bushing terminals per the following criteria.

Clamp type terminals for use through 668 ampere are capable of accepting an aluminum or copper conductor.

Tank grounding provision consists of a 0.5-13NC tapped hole in a steel pad for regulators rated to 300 amperes. Above 300 ampere ratings, a copper-faced pad with two 0.5-13NC tapped holes is provided.

Type JFR regulators are commonly installed using any of four electrical configurations.

One regulator in single-phase application. (Figure 4D)

Two regulators in open delta on a three-phase ungrounded system. (Figure 4B)

Three regulators in closed delta on a three-phase ungrounded system. (Figure 4C)

Handling. Type JFR regulators are designed to be lifted either by a forklift at the base or by use of hangar brackets on the side of the tank. Each JFR regulator is provided with either 2 or 4 lifting hooks on the side of the tank. The number of hooks has been established to provide a mar-gin of safety on lifting when all hooks provided are used.

PHYSICAL CONSIDERATIONS

Location. Type JFR regulators are designed for outdoor installation. Any regulator may be platform or pedestal mounted. Regulators provided with hangar brackets are suitable for pole mounting. When the regulator is to be installed in a substation on a pedestal it is recom-mended that a minimum elevation to the live connection be established, as required by applicable codes.

Elevation. When the regulator will be used at an elevation above 1000 meters (3300 feet) the kVA rating must be reduced to assure operating temperature limits are not exceeded.

Falling unit can cause severe injury or damage.

To prevent:

Do not use cover lifting eyes tolift complete unit.

Cover lifting eyes are for untanking of regulator only.

Lift complete regulator by using all side tank hooks.

WARNING

For air cooled (OA) rating, derate kVA rating 0.4% for every 100 meters (330 feet) elevation above 1000 meters.

For forced air cooled (FA) rating, derate kVA rating 0.5% for every 100 meters (330) feet elevation above 1000 meters.

LINE TERMINALS

AND CONNECTIONS

Nameplate Line Current Rating

50A to 300A 301A to 668A 669A to 1200A 1201 A to 2000A

Conductor Size Range or Threaded Stud Size

#2 to 477 MCM #2 to 800 MCM

1.125 - 12 UNF-2A

1.500 - 12 UNF-2A

Three regulators in wye on a grounded-neutral three-phase system. (Figure 4D)

ELECTRICAL CONSIDERATIONS

Each of the four alternatives, when complete with switching provisions, will take the electrical configuration as shown on the next page.

The descriptions 'S', 'L', and 'SL' are embossed into the cover for user convenience at time of installation.www .

El ec tric alP ar tM an ua ls

INSTALLATION DIAGRAMS

INTRODUCTION

(Figure 4A)

(Figure 4B)

(Figure 4B)

(Figure 4D) www .

El ec tric alP ar tM an ua ls

PROTECTIVE MEASURES

Bypass Arrester. All JFR regulators are equipped with a properly sized arrester, connected externally between the 'S' and 'L' line terminals. The arrester is provided to protect the series winding of the regulator from line surges. Of itself, the bypass arrester does not provide lightning protection for the regulator.

Lightning Protection. The number of lightning arresters used will be a judgmental decision on the part of the user, consid-ering such factors as isokeraunic level and degree of risk of damage to be accepted. The minimum recommended light-ning protection consists of a properly sized arrester between the 'S' or 'L' bushing and ground on a single phase or a wye connected system. A delta connection system requires the use of two arresters to accomplish minimum protection lev-els. Additional protection can be obtained with the use of arresters at both the 'S' and 'L' terminals in single phase or wye systems and on all three terminals on a delta system.

For best results, install lightning arresters on the mounting lugs adjacent to the bushings near the top of the tank. The lugs are 0.5 - 13NC located on 2.5 inch centers. Ground the arrester(s) and the regulator tank solidly to the same ground connection. Be careful to keep the ground lead connections as short as possible.

Thru Fault. Type JFR regulators are rated under condition of thru-faults for twenty five times the OA rated current for 2 seconds or 40 times the OA rated current for 0.8 second to a maximum of 20,000 amperes rms symmetrical. The fault current may be asymmetrical to the extent that the peak of the first current loop is equal to 2.26 times the rms value of the current wave.

The user is advised to provide for additional source imped-ance, bus sectionalizing or other means of limiting the avail-able thru-fault current if these criteria are exceeded at the installation

CONTROL CONNECTIONS

Many regulators can be used at several different nominal system voltages. It is therefore necessary to assure that the regulator is properly connected at the 19 pin upper terminal block for the system voltage on which the particular regulator will be used.

For this purpose, it is necessary to use the nameplate drawing and control diagram found in the control enclosure.

Refer to the Nameplate Diagram. A column is indicated to connect lead P2 to P( ), based on the applicable system voltage. The control diagram will aid in identifi-cation of the appropriate pin on the 19-pin terminal block.

1.

Depending on the regulator, there may be a second column indicating that lead U2 is to be connected to U ( ). The same procedure is followed.

2.

For regulator equipped with fans for forced-air cooling, another set of connections will be shown.

3.

Matters specifically relating to the Accu/ StatTM control used in conjuntions with the regulator are not included in this manual.

Refer to the appropriate control instruction manual.

NOTE

INTRODUCTION

Figure 5A www .

El ec tric alP ar tM an ua ls

CONNECTION DIAGRAMS

www .

El ec tric alP ar tM an ua ls www .

El ec tric alP ar tM an ua ls www .

El ec tric alP ar tM an ua ls

PLACING THE REGULATOR IN SERVICE

The following checks will be useful in assuring the regulator is ready for use. The list cannot be all inclusive; careful at-tention on the part of a qualified operator remains impera-tive.

BEFORE CONNECTING

Check oil level at oil sight window. If low, add sufficient oil (ASTM D-3487 Type II) to bring level to that desired.

Check dielectric strength of the oil per ASTM D-877. If found to be below 24 kV, filtering should be accomplished and additional testing of oil integrity is justified. Note:

This is not necessary if regulator is being installed im-mediately upon receipt from the factory.

Take power factor reading of all bushings (common) against ground (tank). Reading should be less that 2.0%.

Verify from the nameplate that the unit is connected for the proper output voltage, motor voltage and control panel voltage.

Assure that the regulator is on the neutral tap position.

This should be accomplished by observing the position indication pointer and by powering the control from a 120V external source and observing the NeutraliteTM to be illuminated.

Identify 'S', 'L' and 'SL' bushings on the cover. Make elec-trical connections per the appropriate installation dia-grams, page 4, first connecting 'SL' bushing.

Set Vari-AmpTM limits on position indicator, if necessary.

See Page 11.

Set Accu/StatTM Control as desired. See Accu/StatTM instruction manual

SWITCHING THE REGULATOR

"ON THE LINE"

It is absolutely imperative that the regulator be on the neutral tap position before switching the regulator on the line.

CONNECTING

High pressure or mechanical failure due to improper by-pass operation can cause death, severe injury or damage.

To prevent:

Energize regulator only with regulator on neutral tap posi-tion.

Follow instructions:

1. Make certain regulator is in neutral (N) position.

2. Turn voltage source switch to "OFF".

3. Remove power fuse.

4. Close, sequentially, the source and load switches.

5. Open the bypass switch.

6. Visually observe that bypass circuit has opened.

7. Replace power fuse.

8. Place voltage source switch to normal.

WARNING

CHECKING REGULATOR

OPERATION

Turn the transfer switch to MANUAL.

Run the tapchanger in the lower direction, at least until the control is observed to go out of band "LOW".

Turn the transfer switch to AUTO. After a time delay, the regulator will return to an "IN" band condition.

Turn the transfer switch to MANUAL.

Run the tapchanger in the raise direction, at least until the control is observed to go out of band "HIGH".

Turn the transfer switch to AUTO. After a time delay, the regulator will return to an "IN" band condition.

(Refer to applicable Accu/StatTM Control instruction manual.)

1.

2.

3.

4.

5.

6.

www .

El ec tric alP ar tM an ua ls

REMOVING THE REGULATOR FROM SERVICE

WARNING

High pressure or mechanical failure due to improper by-pass operation can cause death, severe injury or damage.

To prevent:

Bypass regulator only with regulator on neutral tap posi-tion.

Follow instructions:

REMOVING THE REGULATOR

FROM THE LINE

In order to remove a regulator from service without dropping load, it is imperative that the regulator be on the neutral posi-tion. The system must first be de-energized (load dropped) before removal. If the regulator being removed is in a closed delta bank, it is necessary to bypass and isolate all regula-tors in the bank. The routine removal procedure is essen-tially the reverse of the procedure used to place the regulator on the line.

Run the regulator under normal voltage source to the neutral position, as revealed by the tap position indica-tor.

1.

Confirm via the NeutraliteTM indicator that the regula-tor is on neutral. If the independent checks of the po-sition indicator and NeutraliteTM indicator do not con-firm the neutral position, bypassing must not be at-tempted. In such event, de-energize the system to re-move the regulator from service.

2.

After assuring that the regulator is on neutral, close the bypass switch.

Open, sequentially, the load and source switches.

3.

4.

5.

6. Exercise appropriate care in the removal of the regulator. High voltage will still be present at the bypass witch and the source and load switch terminals. Remove the ground connection last.

(b.) For a closed delta connection, be sure all regula-tors in the bank are bypasses and isolated.

(a.) For a single phase or grounded wye connection, make sure that the high voltage disconnect switches are opened.

www .

El ec tric alP ar tM an ua ls

MAINTENANCE

GENERAL INSTRUCTIONS

Failure to properly maintain the regulator can result in se-vere personal injury and product failure. The instructions contained herein should be carefully reviewed, understood and followed. The following maintenance procedures should be performed regularly:

1. Operational checks

• Control performance

• Tapchanger performance

• Vari-AmpTM limit performance.

2. Periodic inspection

• Oil sample

• Oil oxidation inhibitor addition

• Contact wear

• Fans

This checklist does not represent an exhaustive survey of maintenance steps necessary to ensure safe operation of the regulator. Particular applications may require further pro-cedures. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the local Siemens sales representative.

When powered, dangerous voltages are present in the equip-ment that can cause severe personal injury, death, and prod-uct failure. Always de-energize and ground the equipment before maintenance requiring access to high voltage parts.

The use of unauthorized parts in the repair of the equipment, tampering by unqualified personnel, or faulty repair and ad-justments will result in dangerous conditions which can cause severe personal injury or equipment damage. Follow all safety instructions contained herein.

OPERATIONAL CHECKS

Basic regulator operation can be checked while the regula-tor remains in service. Simply provide means to observe the output voltage (such as a voltmeter connected at the test terminals).

• Observe that the voltmeter reads the voltage level setting required by the control, to within one-half of the band-width tolerance. Note 1: The control must be “in” band.

Note 2: Line drop compensation must be set to zero if the regulator is carrying load.

• Run the tapchanger several steps in one direction in the manual mode until the output voltage is outside of the bandwidth. Return the control to automatic mode. After the predetermined time delay, the tapchanger motor will be observed to return the output voltage in-band. Repeat this operation, running the tapchanger in the opposite direction.

• Check the Vari-AmpTM limit switches by attempting to run the tapchanger beyond the position to which the switches are set. The limit switches should function to open the circuit. Note: If the limit switch is set at the maximum 10% range and fails to function, the tapchanger will stall against a mechanical stop. The motor is designed to stall con-tinuously without damage

CAUTION

WARNING

Operation of the regulator at extreme tap positions could produce a line voltage above or below desired operating limits at the load.

To prevent:

Operate the regulator only to judiciously determined voltage extremes.

Regulator may have High Internal Pressure. Can cause serious personal injury or death, or damage to the regulator.

To prevent:

Use pressure relief valve to vent regulator before untanking.

www .

El ec tric alP ar tM an ua ls

A sample of oil from the regulator should be subjected to dielectric breakdown test, per ASTM D-877. It is recom-mended that oil testing less than 24 kV be filtered. Other tests, especially Neutralization Number, Interfacial Tension and Power Factor are also useful and may be preferred by particular users.

The oxidation inhibitor in the oil will be depleted over a pe-riod of a few years and should be replaced. The inhibitor is 2, 6-ditertiary-butyl-para-cresol (DBPC) at a concentration level of 0.2 to 0.3%.

The time interval between internal inspections will depend upon frequency of tapchanger operation and the load on the regulator. Regulators subjected to numerous overloads and a high load factor may require more frequent inspections than those carrying normal loads. While internal inspection is not a necessity, preventive maintenance inspections will help assure the continuity of service.

PERIODIC INSPECTION

If cover top cap is removed, make certain the cap is properly sealed when replaced on cover. Siemens recommends ap-plying pipe sealant (Loctite PST or equivalent) around the threads of the adapter. Furthermore, it is recommended that the seal be tested by applying 5 psig pressure through the pressure relief valve fitting for 5 minutes, with no loss in pressure. Failure to assure seal may allow moisture to be pulled into the unit during a cool-down cycle.

Remove the regulator from service as described on Page 7.

Place the regulator in a position where energized overhead lines will not interfere.

1.

2.

Operate pressure relief valve to vent regulator before untanking

3.

Remove the three mounting bolts holding the control box onto the main tank.

4.

Loosen all cover bolts and turn outward 180 degrees.5.

The regulator can now be pulled from the main tank by the cover lifting eyes.

6.

When inspecting, check to be certain all hardware and con-nections are tight. The principal point of the internal inspec-tion will be the condition of the arcing contacts on the tapchanger. Since numerous factors influence the rate of contact tip wear, no one criteria can be stated to recom-mend when a contact should be changed.

The following figure shows the possible condition of con-tact wear after a period of operation. If a contact surface has burned down so that only a 1/8 inch wide line contact area remains, the contact will probably be giving adequate ser-vice at low contact temperatures, but much further deterio-ration will probably result in decreased spring pressure and possibly faulty operation. Therefore, the contact should defi-nitely be replaced. (See Figure in next column.)

Contacts, both movable and stationary, show normal burning and wear after 1,500,000 operations. If for any reason A1 dimensions exceeds 4/5 of A, the stationary contact should be replaced.

SEALED REGULATORS WITH

PRESSURE RELIEF VALVE

To untank a JFR regulator, proceed as folllows:

The fans used for cooling (on some regulators) require a minimum of attention. Fans with plain sleeve bearings or Oil-Lite sleeve bearings should be oiled at least once a year with a good grade of SAE 10-W mineral engine oil which does not thicken in cold weather. Oil must be added to sleeve bearings before starting motor for the first time after installation.

Fans equipped with ball bearing motors are packed with grease before shipment and should be greased at least once a year with a soda-soap, ball-bearing grease of me-dium consistency furnished by a reliable supplier.

For fans that are seldom used, the frequency for greasing or oiling may be less than outlined above, but it is recom-mended that this lubrication be placed on a yearly schedule.

It is often possible to determine by inspection whether lubri-cation is required.

• FANS

MAINTENANCE

www .

El ec tric alP ar tM an ua ls

SPECIAL FEATURES

The Accu/StatTM control panel is hinged and may be re-moved completely from the regulator control box by remov-ing the wing nuts on the polarized jack plug and pulling the jack from its fixed portion. This will automatically de-energize the control. It is not necessary to bypass or de-energize the regulator to remove the control.

A spring-loaded shorting bar in the plug automatically short circuits the current transformer secondary when the jack is removed.

The Accu/StatTM control may be remotely mounted. Remote cable is available in standard lengths of 18, 25 and 30 feet incorporating oil and moisture resistant, color-coded conduc-tors.

REMOTE MOUNTING

OF CONTROL

EQUIPMENT

VARI-AMPTM POSITION INDICATOR

The Vari-AmpTM feature provides a method of operating the regulator at increased load by decreasing the range of op-eration. It provides operator flexibility by allowing the range of regulation to be adjusted in 1 1/4 percent increments. The various regulation ranges together with the corresponding current capacities for standard regulators are listed on page

11. All that is necessary to adjust the range of regulation anywhere from ±5 percent to ±10 percent is to turn the ad-justing knobs until the proper range of regulation is shown on the side of the position indicator. The upper and lower limits need not be the same.

It is not necessary to remove the regulator from service to make this adjustment. The switches are, however, in the motor power circuit so the motor should not be running while the switches are being set.

POLARIZED DISCONNECT SWITCH

(JACK PLUG) AND HINGED

CONTROL PANEL

www .

El ec tric alP ar tM an ua ls

Catalog Number VARI-AMPTM RANGE AND CURRENT RATINGS AVAILABLE Includes

Voltage & kVA ±10% ±83/4% ±71/2% ±61/4% ±5%

10-02.5-050.0 200 220 240 270 320 10-02.5-075.0 300 330 360 405 480 10-02.5-100.0 400 440 480 540 640 10-02.5-167.0 668 668 668 668 668 10-02.5-250.0 1000 1000 1000 1000 1000 10-02.5-333.0 1332 1332 1332 1332 1332 11-02.5-416.3 1665 1665 1665 1665 1665

10-05.0-050.0 100 110 120 135 160 10-05.0-100.0 200 220 240 270 320 10-05.0-167.0 334 367 401 451 534 10-05.0-250.0 500 550 600 668 668 10-05.0-333.0 668 668 668 668 668 11-05.0-416.3 835 835 835 835 835

10-07.6-038.1 50 55 60 68 80 10-07.6-057.2 75 83 90 102 120 10-07.6-076.2 100 110 120 135 160 10-07.6-114.3 150 165 180 203 240 10-07.6-167.0 219/232 241/255 263/278 296/313 351 /371 10-07.6-250.0 328/347 361/381 394/416 443/468 525/555 10-07.6-333.0 437/463 481/509 524/556 590/625 668/668 10-07.6-416.3 546/578 601 /636 656/668 668/668 668/668 10-07.6-500.0 656 668 668 668 668 10-07.6-667.0 875 875 875 875 875 11-07.6-889.0 1167 1167 1167 1167 1167

10-13.8-069.0 50 55 60 68 80 10-13.8-138.0 100 110 120 135 160 10-13.8-207.0 150 165 180 203 240 10-13.8-276.0 200 220 240 270 320

10-14.4-072.0 50 55 60 68 80 10-14.4-144.0 100 110 120 135 160 10-14.4-288.0 200 220 240 270 320 10-14.4-333.0 231 254 277 312 370 10-14.4-432.0 300 330 360 405 480 10-14.4-576.0 400 440 480 540 640 10-14.4-720.0 500 550 600 668 668 10-14.4-833.0 578 636 668 668 668

10-19.9-100.0 50 55 60 68 80 10-19.9-200.0 100 110 120 135 160 10-19.9-333.0 167 184 201 226 268 10-19.9-400.0 200 220 240 270 320 10-19.9-667.0 335 368 402 452 536 10-19.9-833.0 418 459 502 565 668

OPERATION AT LESS

THAN

RATED VOLTAGE

JFR regulators may be operated at less than the voltage for which they were de-signed. All system voltages for which control system taps have been provided are shown on the nameplate. When this is to be accomplished it may be neces-sary to reconnect particular leads at the upper 19-pin terminal block as illustrated on page 5. When operating the regula-tor at reduced voltage it must be noted that the regulator carries a maximum current rating which rules regardless of the voltage (see table at right). It may therefore be necessary to operate the regulator at less than its nameplate kVA rating.

Units with catalog number starting with 10 are self cooled 11 are forced-air cooled

Regulators can be modified at factory for 50 Hz operation with appropriate derating of voltage.

*Capab le o f car ry ing cur ren t corresponding to rated kVA when operated at 7200/12470 volts grounds wye.

www .

El ec tric alP ar tM an ua ls

Certain regulators may be equipped for forced-air cooling and include fans mounted on the radiators. The fans are usually automatically controlled by means of the change in oil temperature (see Connection Diagram). The thermom-eter located in the top transformer oil contains two identical switches which control fan operation when fan control switch is in “Auto” position.

The switches are normally set to start the fans at 65°C and to stop them at 55°C top oil temperature, but may be ad-justed plus or minus 5°C.

A thermal overload relay is mounted on each fan motor. Any fan that develops trouble will be automatically disconnected from the line without affecting the other fans of the system.

One fan can be removed from the radiators without affecting the operation of the others. When fans are out of service, care must be exercised to prevent overloading the regulator.

Fan should be removed and replaced carefully to prevent damage to the radiators.

FORCED AIR COOLING SUBBASE ASSEMBLY

Subbase assemblies are available in 4-inch high increments from 21 through 49 inches for most JFR regulators. The proper height is selected by picking the elevation that will provide required clearance from foundation to the live part of the regulator bushing.

Figure 15A

Figure 15B www .

El ec tric alP ar tM an ua ls

PARTS LIST

MAJOR COMPONENTS PARTS LIST

INSTRUCTIONS FOR ORDERING PARTS

When ordering parts give the quantity of parts required, the regulator serial number, parts list item number, complete description, and method of shipping. State whether for emergency repair, maintenance, spare part, etc.

All shipments will be made F.O.B Factory

Item 01-11 Description

5050A 5094B 81A 90A

Control Compartment Gasket Main Cover Gasket Pressure Relief Valve Terminal Box Gasket Nameplate Sampling Device Grounding Lug Terminal (not shown) Terminal Block Clamp Terminal Block Studs Terminal Block Gasket Motor Capacitor TLG Motor Capacitor TLF Drain Valve Oil Sight Glass Oil Sight Gauge Gasket J-Bolt Assy - Stainless Steel

Figure 16A www .

El ec tric alP ar tM an ua ls

POSITION INDICATOR PARTS LIST

Item 01-11

Description Position Indicator - Complete Solenoid Housing Gasket Drag Hand Solenoid Coil Adjusting Knob Faceplate Window Clamping Ring Vari-AmpTM Adjusting Switch Limit Switch (each) Flang Gasket Spacer Ring (not shown)

Item 01-11 Description

5063C 5062C 5065C 5067C 5068C 5069C 5071C 5072C 5073C 5079C

Position Indicator - Complete Drag Hand Solenoid Coil Adjusting Knob Faceplate Window Clamping Ring Vari-AmpTMAdjusting Switch (each) Limit Switch (each) Flange Gasket Window Gasket www .

El ec tric alP ar tM an ua ls

TYPE TLG DIAL SWITCH

Item 01-11 Description Item

01-11 Description

*5320 *5320B 5317A

Phenolic Panel Glass Polyester Panel Reversing Main Shaft Main Stationary Contacts Reversing Stationary Contact R Reversing Stationary Contact L Neutral Stationary Contact Collector Ring Collector Hub Reversing Switch Arm

5328A 5328B *5329 *5329A *5329B

Reversing Switch Finger Assembly Reversing Switch Hub Finger Assembly Drive Arm - Phenolic Drive Arm - Phenolic Drive Arm - Glass Phenolic Hub Finger Support Ring Finger Support Main Moving Finger Assembly Hub Finger Assembly Ring Finger Assembly Phenolic Drive Pin www .

El ec tric alP ar tM an ua ls

TYPE TLG QUICK BREAK MECHANISM

Item 01-11 Description

Item 01-11 Description

*5320 *5320B 5317A

Phenolic Panel Glass Polyester Panel Reversing Main Shaft Main Stationary Contacts Reversing Stationary Contact R Reversing Stationary Contact L Neutral Stationary Contact Collector Ring Collector Hub Reversing Switch Arm

5328A 5328B 5329A 5329B

Reversing Switch Finger Assembly Reversing Switch Hub Finger Assembly Drive Arm - Phenolic Drive Arm - Phenolic Drive Arm - Glass Phenolic Hub Finger Support Ring Finger Support Main Moving Finger Assembly Hub Finger Assembly Ring Finger Assembly Phenolic Drive Pin www .

El ec tric alP ar tM an ua ls

Item 01-11 Description

Item 01-11 Description

5358A 5360A

Panel Stationary Contact Neutral Stationary Contact Stationary Contact - LH Stationary Contact - RH Collector Ring Shaft Assembly Main Finger Assembly (each) Contact Finger Assembly Collector Ring Contact Finger Assembly Collector Hub

*5363 *5366 5366A

Drive Plate Contact Finger Assembly - Rev. Switch Contact Support Assembly Reversing Drive Pin Reversing Drive Pin Reversing Shaft Spacer Contact Finger Support Contact Finger Support Reversing Switch Stop

TYPE TLF DIAL SWITCH

FIGURE 20A

www .

El ec tric alP ar tM an ua ls

TYPE TLF QUICK BREAK MECHANISM

5323A 5243B

Counter Switch Assembly Neutral Switch* Mounting Frame Motor Drive Spring Tube Drive Spring Spacer Notched Index Plate Latch Latch Spring Latch Pin Reversing Switch Drive Arm

*5266 **5287

Interlock Disc and Drive Sprocket Assembly Quick Break Mechanism Shaft Actuating Arm Assembly Spacer A-Frame Drive Chain for Position Indicator Motor Sprocket Motor Capacitor (may be located in control box) Actuating Disc and Sprocket Main Drive Chain Position Indicator Drive Mechanism Reversing Switch Spring Assembly Flexible Shaft

Item 01-11

Item 01-11 Description Description

*This neutral switch switch became effective with type TLF-30D quick break mechanism.

*Include regulator serial number when ordering, and specify whether brown phenolic or gray polyester material.

**Motor capacitor located in control box - effective with S/N 05582.

Figure 21A www .

El ec tric alP ar tM an ua ls

Bypass Arrester Assembly 3 kV MOV Bypass Arrester Crystal, 3 kV MOV Mounting Bracket Assembly Bypass Arrester Assembly, 3 kV MOV Bypass Arrester Crystal, 3 kV MOV Mounting Bracket Assembly Bypass Arrester Assembly, 6 kV MOV Bypass Arrester Crystal, 6 kV MOV Mounting Bracket Assembly

2,500, 5,000, 7,620

12,000-13,800-14,400

19,920

I t e m 01-11 Description Volts

Include regulator serial number when ordering

Polymer arresters now used on voltage regulators.

Supersedes previous porcelain arresters.

NOTE: 1.5 kV porcelain arresters superseded by

3.0 kV MOV polymer arresters.

BYPASS ARRESTERS

5428A

Figure 22A

Figure 22B www .

El ec tric alP ar tM an ua ls

BUSHINGS

5400P

5400R

5400S

5401P

5401R

5401S

Bushing Assembly for 15 kV

Bushing Assembly for 15 kV

Bushing Assembly for 15 kV

Bushing Porcelain for 15 kV

Bushing Porcelain for 15 kV

Bushing Porcelain for 15 kV Clamping Ring for 5400 and R Ratings Clamping Ring for 5400S Rating Cushion Spring Cap Screw Bushing Cap Line Terminal for 5400P Rating Bushing Cap Line Terminal for 5400R and S Ratings Gasket Gasket

5 0

38.1 thru 76.2

69 thru 138 5 0

114.3 thru 167

7 5 5 0

38.1 thru 76.2 69 thru 138

5 0

114.3 thru 167 7 5

13,800

13,800

13,800

13800

Item 01-11 Description kVA Volts

Figure 23A www .

El ec tric alP ar tM an ua ls

5400T

5400U 5400V

5400W

5400X 5400Y

5400YY

5400Z

5400AB

5400AC

5401T

5401U 5401V

5401W

5401X 5401Y

5401YY

5401Z

5401AB

5401AC

Bushing Assembly 15 kV

Bushing Assembly, 15 kV Bushing Assembly, 23 kV

Bushing Assembly 15 kV

Bushing Assembly, 23 kV Bushing Assembly, 23 kV

Bushing Assembly, 15 kV Bushing Assembly, 23 kV Bushing Assembly, 23 kV Bushing Assembly, 15 kV Bushing Porcelain, 15 kV

Bushing Porcelain, 15 kV Bushing Porcelain, 23 kV

Bushing Porcelain, 15 kV

Bushing Porcelain, 23 kV Bushing Porcelain, 23 kV

Bushing Porcelain, 15 kV Bushing Porcelain, 23 kV Bushing Porcelain, 23 kV Bushing Porcelain, 15 kV Clamping Ring for 5400T X, Z and AB Ratings Clamping Ring for 5400U V, W (SL Bushing only), Y and YY Ratings Clamping Ring for 5400W Rating S and L Bushings only Cushion Spring Gasket Gasket Gasket *Bushing Cap Line Terminal for 5400T X, YY and AB Ratings *Bushing Cap Line Terminal for 5400U, Y and Z ratings *Bushing Cap Line Terminal for 5400V Rating Cap Screw

100 thru 167

250 thru 509 207-276

72 thru 144 100 thru 200

333 thru 416.3 250 thru 416.3 576 thru 833

333 thru 400

333 thru 432 667 thru 833

667-889 100 thru 167

250 thru 509

207-276 72 thru 144

100 thru 200 250 thru 416.3 250 thru 416.3 576 thru 833

333 thru 400

333 thru 432 667 thru 833

13,800 14,400 19,920

14,400 14,400 19,920 12,000 14,400 19,920

13,800 14,400 19,920

14,400 14,400 19,920 12,000 14,400 19,920

BUSHINGS

I t e m 01-11 Description k V A Volts

*Units rated 250 kVA and above, 2500 and 5000 volts are not supplied with line terminals

Indicate Regulator Serial Number

Figure 24A www .

El ec tric alP ar tM an ua ls

Siemens Power Transmission & Distribution, Inc.

P.O. Box 6289 Jackson, MS 39288-6289 Phone: 601-939-0550 Fax: 601-939-3606

ACCU/STAT, DATA/PAK, NEUTRALITE

and VARI-AMP are trademarks of Siemens Power Transmission & Distribution, Inc.

s

PR4018-06

PR4018-05

PR4018-04

June/01

PRINTED IN U.S.A.