This is a submittal data form and technical documentation for Baltimore Aircoil Company closed circuit cooling towers. The customer is SAEG Engineering Group, representing the U.S. Embassy in Lima, Peru, for an embassy retrofit alteration project (Purchase Order 46976). Two units of the VFL-036-31K model are specified.

Each cooling tower unit is rated for 160 USGPM of water flow, cooling from 93°F inlet to 85°F outlet at 76°F entering air wet bulb with 1.52 PSIG fluid pressure drop. Equipment includes one 10 HP premium efficiency inverter-duty fan motor (TEFC, 460V, 3-phase, 60 Hz) and one 1 HP standard efficiency pump motor with matching electrical specifications. The units feature factory-fabricated forced draft counterflow design with Type 304 stainless steel construction, including heavy gauge panel construction, stainless steel coil with 300 psig maximum allowable working pressure, PVC drift eliminators, and galvanized steel fan wheels protected with BALTIBOND corrosion protection. Supporting systems include integral pump assembly with strainer, PVC spray distribution branches with 360° nozzle pattern, and mechanical float valve basin water level control suitable for 15-50 psig supply pressure. Unit anchorage is designed to resist wind loads up to 30 psf and seismic forces of 161% of operating weight horizontally and 24% vertically. The units comply with ASHRAE Standard 90.1-2010 for energy efficiency, are CTI certified for thermal performance, and manufactured under ISO 9001 quality standards with a five-year warranty on fan and motor components. Sound data indicates A-weighted levels of 79 dB at 5 feet and 67 dB at 50 feet from the top. Complete rigging, installation, and maintenance documentation is available at baltimoreaircoil.com.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

© 2014 Baltimore Aircoil Company Corporate Headquarters: 7600 Dorsey Run Road, Jessup, MD 20794 – Tele: (410) 799-6200 / Fax: (410) 799-6416

Submittal Data Form 9-1-2016

Sold To :

SAEG ENGINEERING GROUP

8012 NW 68 ST

Miami, FL 33166 United States

Project: EMBASSY USA RETROFIT ALTERNAT Purchase Order No: 46976 Engineer: EDUARDO RAMIREZ BAC Order # U164282907

Representative: SAEG ENGINEERING GROUP

All Information is per Unit

Quantity: 2 Model VFL-036-31K CLOSED CIRCUIT COOLING TOWER

Certified Capacity: 160.00 USGPM of Water from 93.00°F to 85.00°F at 76.00°F entering air wet bulb and 1.52 PSIG fluid pressure drop.

Fan Motor(s): One (1) 10 HP fan motor(s): Totally Enclosed, Fan Cooled (TEFC), 1 Speed/1 Winding - Premium Efficiency (Inverter Duty), suitable for 460 volt, 3 phase, 60 hertz electrical service. Drives are based on 0 inches ESP.

NOTE: Inverter Duty fan motors, furnished in accordance with NEMA Standard Mg.1 -- Part 31, are required for applications using variable frequency drives for fan motor control.

Pump(s): One (1) 1 HP pump motor: 1 Speed/1 Winding - Standard Efficiency, suitable for 460 volt, 3 phase, 60 hertz.

Submittal Information Equipment Summary BAC Terms and Conditions of Sale Mechanical Specifications Performance Curves and Sound Data Submittal Drawings/Diagrams

BAC-15807AX Unit Print BAC-13237B Unit Support

Forced Draft, Counterflow Closed Circuit Cooling Tower Quality Assurance - ISO 9001 Certified Unit Energy Efficiency per ASHRAE Standard 90.1-2010 CTI Certified Thermal Performance Stainless Steel Unit Construction Galvanized Steel Fan Wheel(s) Protected with the BALTIBOND® Corrosion Protection System Type 304 Stainless Steel, Full Circuit Coil Polyvinyl Chloride (PVC) Drift Eliminators Upgraded Unit Anchorage Integral Pump(s) with Standard Make-Up, Drain and Overflow Connections PVC Spray Branches Mechanical Float Valve Assembly

THANK YOU FOR YOUR BUSINESS!

Rigging and Installation Instructions, as well as Operating and Maintenance Instructions are available at www.baltimoreaircoil.com http://www.baltimoreaircoil.com/ rcastillo Text Box

U.S. EMBASSY

LIMA - PERU

rcastillo Text Box

Corporate Headquarters: 7600 Dorsey Run Road, Jessup, MD 20794 – Tele: (410) 799-6200 / Fax: (410) 799-6416

Mechanical Specifications 9-1-2016

Customer: SAEG ENGINEERING GROUP Project: EMBASSY USA RETROFIT ALTERNAT Purchase Order No: 46976 Engineer: EDUARDO RAMIREZ BAC Order # U164282907

All Information is per Unit

Quantity: 2 Model VFL-036-31K CLOSED CIRCUIT COOLING TOWER

Unit Type:

Factory fabricated, forced draft, counterflow closed circuit cooling tower with vertical discharge.

Quality Assurance:

Each unit is manufactured under closely-controlled conditions using standardized parts to ensure each unit is built precisely to the same high-quality design and construction standards. The design, manufacture, and business processes of Baltimore Aircoil Company are ISO 9001:2000 certified.

Unit Efficiency:

The unit(s) complies with the energy efficiency requirements established by ASHRAE Standard 90.1-2010.

CTI Certification:

The thermal performance is certified by the Cooling Technology Institute in accordance with CTI Certification Standard STD-201.

Materials of Construction:

Heavy gauge panel construction of Type 304 stainless steel utilizing double break flanges for maximum strength, rigidity, and reliable sealing at watertight joints. Circular access doors provided for interior inspection, cleaning, and adjustments are constructed of Type 304 stainless steel and are held in place with phenolic knob screws. The heat transfer casing section is contructed of Type 304 stainless steel.

The fan(s) is located in the dry air stream to provide greater reliability and ease of maintenance. Fan wheels are forwardly curved, centrifugal, squirrel-cage type which are statically and dynamically balanced, and are mounted on a steel shaft supported by heavy-duty, self-aligning, relubricatable bearings with cast iron housings. Fan housings have curved inlet rings for efficient air entry and are constructed of Type 304 stainless steel. The fan housings are of split design to facilitate fan wheel and shaft removal.

V-belt sheaves, selected for 150% motor nameplate horsepower, are mounted and aligned at the factory. Drive and all moving parts are protected by removable screens and panels made of Type 304 stainless steel. The fan(s), fan shaft(s), bearings, mechanical equipment support and fan motors are warranted against defects in materials and workmanship for five (5) years from date of shipment.

Fan Wheels:

Forwardly curved, centrifugal, squirrel cage type fan wheels are constructed from G-235 (Z700 metric) hot-dip galvanized steel protected with the BALTIBOND® Corrosion Protection System. Fan wheels are statically and dynamically balanced. Fan housings have curved inlet rings for efficient air entry.

Coil Type:

Continuous 1.05" (27 mm) O.D. all prime surface Type 304 stainless steel encased in steel framework. Coil will be designed for free liquid drainage. Coil has a maximum allowable working pressure of 300 psig (2170 kPa) and is tested at 375 psig (2685 kPa) air pressure under water.

Drift Eliminators:

Drift eliminators are constructed of polyvinyl chloride (PVC), and are removable in easily handled sections. They impart three distinct changes in air direction to effectively strip entrained moisture from the leaving airstream with minimum air resistance. PVC eliminators are not a working surface. A working platform by others may be required to service the water distribution system.

Corporate Headquarters: 7600 Dorsey Run Road, Jessup, MD 20794 – Tele: (410) 799-6200 / Fax: (410) 799-6416

Unit Anchorage:

When supported as recommended, the unit will have anchorage to resist wind loads up to 30 psf (146.6 kg/m^2) acting on the full vertical projected area with 16 psf (78.1kg/m^2) acting simultaneously on the full horizontal projected area or seismic forces of 161% of the operating weight acting in the horizontal direction, and 24% of the operating weight acting in the vertical direction applied at the center of gravity.

Spray Water Pump Assembly:

Basin has integral pump(s) with large area, lift out, steel strainer screen(s) including perforated openings sized smaller than the water distribution nozzle orifices. Strainers include anti-vortexing baffles to prevent air entrainment. Close-coupled, bronze-fitted pump(s) with mechanical seal is mounted on the basin. The pump motor(s) are totally enclosed, fan cooled (TEFC). A water bleed line with a metering valve to control the bleed rate is installed between the pump discharge and the overflow connection. Electrical requirements match fan motor.

Spray Distribution System:

Spray header with schedule 40 PVC branches. Removable branches and 360° spray pattern plastic spray nozzles are held in place with snap-in rubber grommets.

Basin Water Level Control:

A make-up valve with unsinkable polystyrene filled plastic float arranged for easy adjustment. The corrosion resistant make-up valve is suitable for water supply pressures between 15 psig (103 kPa) and 50 psig (345 kPa).

Baltimore Aircoil Company, Inc.

Closed Circuit Cooling Tower Selection Program Version: 7.3.0 NA Product data correct as of: August 10, 2016

Project Name:

Selection Name:

Project State/Province:

Project Country: United States Date: September 01, 2016

Model Information Design Conditions Product Line: Low Profile Series VFL Fluid: Water Model: VFL-036-31K Number of Units: 1 Flow Rate: 160.00 USGPM Coil Type: Stainless Steel Entering Fluid Temp.: 93.00 °F Coil Finning: None Leaving Fluid Temp.: 85.00 °F Fan Type: Standard Fan Wet Bulb Temp.: 76.00 °F Fan Motor: (1) 10.00 = 10.00 HP/Unit Total Standard Fan Power: Full Speed, 10.00 BHP/Unit Total Pump Motor Power: (1) 1.00 = 1.00 HP/Unit Fluid Pressure Drop: 1.46 psi Intake Option: None Internal Option: None Discharge Option: None External Static Pressure: 0.00 in. of H2O

Design Conditions @ Standard Total Fan Motor Power per Unit (10.00 HP) Predicted Performance

Fan Motor Alternative = Full Speed, 10.00 BHP Flow Rate = 160.00 USGPM (100.00% of Design)

These performance curves are based on constant fan power.

Applies to Applies to Warning(s) Design Off Design

Conditions Conditions

1. One or more selected model options are outside of CTI Certification limits. Yes Yes

Page 1/2

Baltimore Aircoil Company, Inc.

Closed Circuit Cooling Tower Selection Program Version: 7.3.0 NA Product data correct as of: August 10, 2016

Project Name:

Selection Name:

Project State/Province:

Project Country: United States Date: September 01, 2016

Model Information Product Line: Low Profile Series VFLFan Type: Standard Fan Model: VFL-036-31K Fan Motor: (1) 10.00 = 10.00 HP/Unit Number of Units: 1 Total Standard Fan Power: Full Speed, 10.00 BHP/Unit Coil Type: Stainless Steel Total Pump Motor Power: (1) 1.00 = 1.00 HP/Unit Coil Finning: None Intake Option: None Internal Option: None Discharge Option: None External Static Pressure: 0.00 in. of H2O

Octave band and A-weighted sound pressure levels (Lp) are expressed in decibels (dB) reference 0.0002 microbar. Sound power levels (Lw) are expressed in decibels (dB) reference one picowatt. Octave band 1 has a center frequency of 63 Hertz.

Top Lp Sound Pressure (dB)

Octave Distance Band 5 ft. 50 ft.

1 75 68 2 75 66 3 75 63 4 74 63 5 73 61 6 73 60 7 70 59 8 70 51

A-wgtd 79 67

Back Lp Sound Pressure (dB)

Octave Distance Band 5 ft. 50 ft.

1 70 64 2 68 61 3 69 60 4 67 64 5 65 60 6 58 51 7 51 44 8 45 37

A-wgtd 69 64

End Lp Sound Pressure (dB)

Octave Distance Band 5 ft. 50 ft.

1 72 63 2 67 61 3 69 58 4 71 58 5 71 56 6 70 55 7 67 54 8 61 46

A-wgtd 76 62

End Lp Sound Pressure (dB)

Octave Distance Band 5 ft. 50 ft.

1 72 63 2 67 61 3 69 58 4 71 58 5 71 56 6 70 55 7 67 54 8 61 46

A-wgtd 76 62

Fan Side Lp Sound Pressure (dB)

Octave Distance Band 5 ft. 50 ft.

1 74 63 2 67 60 3 68 58 4 69 55 5 66 55 6 64 53 7 61 48 8 54 41

A-wgtd 71 60

Sound Power (dB) Octave Center Frequency Band (Hertz) Lw

1 63 97 2 125 94 3 250 92 4 500 93 5 1000 90 6 2000 88 7 4000 86 8 8000 79

Note: The use of frequency inverters (variable frequency drives) can increase sound levels.