Rain Bird file.pdf
PDF 2 MB Posted
- Solicitation number
- 19MX5725Q0016
- Issued by
-
Department of State
About this file
This document is a collection of Rain Bird troubleshooting guides for various irrigation and pump system components, including the ESP-LXD Controller, PEB & PESB Valves, FS Series Flow Sensors, and Watertronics pumping systems. The guides provide comprehensive diagnostic procedures for addressing common operational issues such as valve malfunctions, electrical problems, pressure and flow irregularities, and system alarms.
The troubleshooting guides offer systematic approaches to identifying and resolving problems, with each section detailing probable causes and corresponding corrective actions. For instance, the ESP-LXD Controller guide includes flowcharts for addressing issues like short finding modes, duplicate decoder addresses, and flow alarms. The valve and pump system guides cover a wide range of symptoms, from valves not shutting off or turning on electrically to pressure and temperature-related alarms, providing step-by-step instructions for technicians to diagnose and repair equipment. The documents include technical details such as voltage ranges, sensor testing procedures, and recommendations for component replacement or adjustment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Site visit minute.pdf | ||
| Q and A 19MX5725Q0016.pdf | ||
| SF 1449 Grounds irrigation and landscape services.docx | DOCX document | |
| RFQ Grounds irrigation and landscape services COB.docx | DOCX document | |
| letter to offerors 19MX5725Q0016.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JYAlvarez Snapshot
10 Rain Bird ESP-LXD Controller Troubleshooting Guide Rain Bird ESP-LXD Controller Troubleshooting GuideTable of Contents
Table of Contents 11
Troubleshooting Getting Started
Turn the dial to AUTO and press the Alarm button
Call the ESP-LX Series
HOTLINE at +1-866-544-1406
No Water Days No Run Times No Start Times No PGM will...
More Exit
Short Finding Mode
Duplicate Decoder Address
Valve Shorts/ Open Circuit (Decoder Test)
Flow Alarms
END - Job Well Done!
What does the screen display?
Is the LXD front panel Alarm
Light on?
Is the LXD front panel Alarm Light still on?
Go to page
Go to page
Go to page
Go to page
Go to page
Go to page
YES NO
Alarm: No Water Days, No Run Times, …
YES NO
Turn the dial to Set Current Date and Time
Is the LXD and installation working?
Check the display for Alarms, see
Troubleshooting
END - Job Well Done!
NO YES
Test LXD system using Manual Run or Auto Run
Turn the dial to Set Watering Start Time, etc. and follow programming directions in the User Manual
12 Rain Bird ESP-LXD Controller Troubleshooting Guide Rain Bird ESP-LXD Controller Troubleshooting GuideTable of
Table of Contents 13
Short Finding Mode Short Finding Mode cont.
The controller has automatically entered Short Finding Mode to protect itself against a short on the 2-wire path
Press the Down Arrow button to select 2-wire Diagnostic, then press Next
Turn the dial to Test All Stations / Check Systems
Press the Down Arrow button to select Line Survey, then press Next
The Line Survey screen is displayed
The display reads Temp OK, Current Not OK and Overload Not OK. This indicates a dead short in the 2-wire path. Temp could also show Not OK.
Next Page
Open the front panel and check the two inidicator lights on the ESP-LXD-M50 module.
The top indicator light should be green and the bottom indicator light should be dark. This indicates that the controller put the module in
Short Finding Mode
If there are more than one 2-wire paths connected, disconnect the first 2-wire path
Did the controller exit Short
Finding Mode and are both Indicator Lights illuminated?
NO YES
Reconnect the Maxi-Cable to verify the controller goes back into Short Finding Mode
Disconnect the second/ third/fourth 2-wire path
Next Page
NOTE: The Voltage1 reading for a normal healthy system is typically in the +14.0 to +16.0 range for both A and B. The Voltage 2 reading is typically in the -20.0 to -21.0 range for both A and B. The Voltage1 and Voltage2 readings should be approx. equal for A and B.
Milliamperage (mA) varies with the number of decoders installed and should be approx. equal to the amperage calculations detailed on page 16.
b
NOTE: In “looped” systems, cut the loop in the middle to create two independent paths.
b
Rain Bird ESP-LXD Controller Troubleshooting GuideTable of Contents 17
Duplicate Decoder Address
The controller will Alarm if duplicate decoder addresses are entered for one or more weather sensors, flow sensors or station decoders.
Go to page 11 and follow the Basic Programming Wizards: Station Setup to enter the correct decoder address
NOTE: Only the first two duplicates will be shown, so you may need to repeat this process until all of the duplicate have addressed.
b Test LXD system using
Manual Run or Auto Run
Check the dis-play for Alarms, see page 10 Trouble-shooting
END - Job Well Done!
NO YES
Is the LXD and installation working?
Enter a different decoder address for one of the decoders
18 Rain Bird ESP-LXD Controller Troubleshooting Guide Table of Contents
Manual Short Finding Mode
If you think a station is shorted:
Press the Down Arrow button to select 2-wire Diagnostic, then press Next
Turn the dial to Test All Stations / Check Systems
Press the Down Arrow button to select Line Survey, then press Next
The Line Survey screen is displayed
The display reads Temp OK, Current Not OK and Overload OK. This indicates a possible short in the 2-wire path or one or more misconfigured decoders. A Not OK Overload flag can be caused by a dead short.
Next Page
NOTE: The Voltage1 reading for a normal healthy system is typically in the +14.0 to +16.0 range for both A and B. The Voltage 2 reading is typically in the -20.0 to -21.0 range for both A and B. The Voltage1 and Voltage2 readings should be approx. equal for A and B.
Milliamperage (mA) varies with the number of decoders installed and should be approx. equal to the amperage calculations detailed on page 16.
b https://youtu.be/6qDx-0K0aC0
20 Rain Bird ESP-LXD Controller Troubleshooting Guide Rain Bird ESP-LXD Controller Troubleshooting GuideTable of
Table of Contents 21
Flow Alarms cont.Flow Alarms
Next Page
Select Flow Smart Module and press Next
Select View Flow Alarms
Select Station Flow Alarms
Check for Flow Alarms and fix the zone which causes the Flow Alarm
Go Back and select Mainline Flow Alarm
Check for Flow Alarm and fix mainline
After fixing all leaks and flow issues, go Back and select Clear Flow Alarms
Read screen and select Yes to clear Alarms
END - Job Well Done!
Run all zones manually to check for Flow Alarms
Alarm is cleared on the display
NO YES
The display shows the following:
Press the Alarm button
Press the Exit button
Turn the dial to Module Status
22 Rain Bird ESP-LXD Controller Troubleshooting Guide Rain Bird ESP-LXD Controller Troubleshooting GuideTable of
Table of Contents 23
Decoder Test cont.Decoder Test
Press the Down Arrow button to select 2-wire Diagnostic then press Next
Press the Down Arrow button to select Decoder Test then press Next
Select Start to start the decoder test. This can take a few minutes.
The display shows Decoder Test - Test in Progress - Cancel
Some valves don’t turn on, even when trying to run those zones/valves in Manual Run
Turn the dial to Test All Stations / Check Systems
Are there any issues?
Next Page
A list with problems will be displayed
Press the + and - buttons to scroll through the list of stations/decoders
Go to each identified decoder and check the wiring and fix any issues
Next Page
NO
YES
Go to Ping Decoders on page 25 for fast track and testing of a single decoder
Turn the dial to Test all Stations/
Check System
Go to page 24
In this example, Station 2 is shorted out
In this example, Station 4 has an open circuit
24 Rain Bird ESP-LXD Controller Troubleshooting Guide Table of
Decoder Test cont.
Select Test all Stations and push Run
Observe that all valves / zones turn on and no Alarm message is displayed on the controller LCD screen
END - Job Well Done!
No issues observed?
Turn the dial to Test all Stations/Check System
For video instructions on Using Decoder Test & Ping Decoders to Troubleshoot Valves, please visit:
https://youtu.be/wkZBaBo08W0 https://youtu.be/wkZBaBo08W0
Overview:
This procedure allows the Flow Sensor and associated wiring to be tested independently of an Irrigation Controller. A Battery and Resistor combination is used if no powered controller is available for the voltage and frequency measurement tests.
When broken up into its component parts, an irrigation system consists of the following elements: Controller, Wiring/Splices, and Sensor, for two-wire systems, also decoders.
The purpose of this procedure is to isolate the elements to rule out each as the cause until the actual failure cause is isolated.
The procedure consists or four parts. If the complete circuit fails any of the test steps, isolate the flow senor by breaking the last splice closest to the flow sensor, and repeat test on the wiring and sensor separately in order to determine if the problem is with the wiring or the sensor itself.
1 Check controller settings for correct Flow Sensor installation
2. Testing wiring to the flow sensor for ground faults resulting from moisture penetration into the wiring, splices, or sensor itself.
3. Testing for broken or shorted wires, splices, or problems internal to the sensor itself
4. Confirming frequency output and confirmation of actual flow rate sensor is reporting.
Test Equipment:
(Battery and Resistor are not required if Controller is operational)
Troubleshooting Guide FS Series Flow Sensors
1. Multi-meter with Ohms, Volts, and Hz (Radio Shack Model 2200075 (shown) or Equivalent)
2. 1K Resistor ( Radio Shack 271-1118 or Equivalent)
3. 9 Volt Battery
4. Connector clip for 9V Battery (Radio Shack 270- 325 or Equivalent)
If an operational flow meter or controller is not available, it can be simulated with a Battery and Resistor. Connect one end of the 1.0k resistor to the Red Battery Clip wire, and the other end of the resistor to the Flow Sensor + Wire (Usually Red or White). Connect the Black Battery Clip Wire to the Flow Sensor (-) Black Wire. Follow the directions, the same as if the controller was powering the sensor.
Registered Trademark of Rain Bird Corporation © 2016 Rain Bird Corporation 1/16 D40827EO
Rain Bird Corporation 6991 E. Southpoint Road Tucson, AZ 85756 Phone: (520) 741-6100 Fax: (520) 741-6522
Rain Bird International, Inc.
1000 West Sierra Madre Ave.
Azusa, CA 91702 Phone: (626) 963-9311 Fax: (626) 852-7343
Rain Bird Professional Support +1-866-544-1406 (U.S. and Canada)
Rain Bird Corporation 970 West Sierra Madre Avenue Azusa, CA 91702 Phone: (626) 812-3400 Fax: (626) 812-3411
Specification Hotline 800-458-3005 (U.S. and Canada)
The Intelligent Use of Water™ www.rainbird.com www.rainbird.com
STEP ➋STEP ➊ STEP ➍
Test for Voltage on the Sensor Wires
1. At the controller end, completely disconnect any and all wires running to the flow Sensor.
2. Set multi-meter on its Auto-Ranging Voltage setting.
3. Connect the multi-meter Black wire to Earth Ground (This can be a pipe, fence, grounding rod, or building steel beam). Electrical panel ground can also be used if available.
4. Touch the Red Multi-Meter test lead to each of the Flow Sensor Wires one at a time, and take note of the reading.
Check Controller Settings for Correct Flow Sensor Configuration
1. At the controller, turn the dial to “Module Programming”. The LCD screen should display “Flow Smart Module”.
2. Press “Next”. The LCD screen should display:
“Flow Sensor Setup” and “SEEF/SELF Settings”, etc. Select “Flow Sensor Setup” and press “Next”.
3. The LCD screen should display:
Flow Sensor Setup
Type:
Back Next+ -
* “Disabled” or “Custom” or “FS050P” or “FS150P” or “FS350B” or etc…
4. Make sure that the settings are representative of the installed flow sensor.
For “Custom” settings of k-factor and offset factor, please contact flow sensor manufacturer. For Rain Bird’s flow sensors, please chose the appropriate flow sensor from the provided list.
Test for Broken or Shorted Wires, Bad Splices, or Internal Sensor Problem
1. If controller is operational, measure the Open Circuit voltage on the terminals to which the flow sensor will be connected. If not, use the Battery Resistor combination shown above, and measure the voltage, between the open end of the resistor and the black battery clip.
Connect the flow sensor and with no flow, re-measure the voltage on the same terminals.
The sensor draws about 0.6mA, so the voltage should be slightly less than measured open circuit. For example, the Battery Voltage would have been about 9.1VDC, so with 0.6mA flowing through the 1k resistor the expected voltage across the flow sensor would be 8.5VDC. Since controllers vary on design, voltages will vary.
However, the following list may be helpful and a general guide.
Test for Ground Faults
1. Confirm that the controller is still completely disconnected from any and all wires running to the Flow Sensor.
2. Set multi-meter on its highest OHM’s scale, and short its Red and Black test leads together to confirm proper operation.
3. Connect the multi-meter Black wire to Earth Ground (This can be a pipe, fence, grounding rod, or building steel beam). Electrical panel ground can also be used if available.
4. Touch the Red Multi-Meter test lead to each of the Flow Sensor Wires one at a time, and take note of the reading.
Measure Flow Rate in HZ and convert to GPM
1. Establish a flow of at least 1 Ft/Sec to insure the impeller rotates.
2. Without moving the Multi-meter leads from the connections of Step#3, switch the Multi-meter to read Frequency ( Hz).
3. Note the Hz reading, and estimate the actual expected flow rate at the time the measurement was taken.
4. Locate the K and Offset values found in the Flow Sensor owner’s manual. For example, if the flow sensor was a 228 Series 2” PVC ➞ K = 2.8429 Offset = 0.1435
5. Use equation to convert Hz to GPM:
GPM = (Measured Hz + Offset)*K
If for example 23.5 Hz was measured in this 228PV-2 sensor:
GPM = ( 23.5 + 0.1435) * 2.8429 = 67.2 GPM
6. Compare the computed flow rate with the expected flow rate, and as shown on the controller or monitor if operational. If all are in agreement, everything is working properly.
STEP ➌
STEP ➎
Is the voltage greater than a few milli-volts? YES
NO
Did the voltage drop about ½ to 1VDC?
YES
NO
Was there no change in voltage?
YES
NO
Was there a drop to less than 1VDC?
YES
NO
Is the voltage unstable?
YES
Is the resistance lower than 1 Meg Ohm? NO
YES
This suggests a problem with the wiring. Confirm that these wires really do run to the flow sensor and not to something else.
Indicates a broken wire, splice, or internal problem with the sensor.
This is normal.
Continue to Step 4.
Indicates a Short in the wiring or sensor.
This may indicate flow in the pipe, something is interfering with normal operation, an intermittent connection, or internal problem in the sensor itself.
Anything less than 1 Meg Ohm suggests a problem with either the wiring, splices, or flow sensor itself.
Model for K Offset Suggested Operating Range (gpm)
228PV15xx-xxxx 1.697 -0.316 5…100
228PV20xx-xxxx 2.8429 0.1435 10…200
228PV30xx-xxxx 8.309 0.227 20…300
228PV40xx-xxxx 13.74283 0.23707 40…500
Update settings and check flow sensor operation.
Are the settings correct?
NO
YES
XF Series Dripline Design, Installation and Maintenance Guide www.rainbird.com44
FLUSHING
• Flush the system every two weeks for the first 6 weeks and check the water that is flushed out for cleanliness
• Establish a regular flush schedule for the future after these initial checks
• Flush the system well after any repairs are made
• Check the pressure at the supply and flush headers on a regular basis and compare with the pressure readings taken right after installation
• Winterizing an irrigation system involves removing enough water to ensure that components are not damaged due to freezing weather
• Check the manufacturer’s instructions for winterizing the valves, filters and backflow prevention devices
If compressed air is used to blowout the lines:
• Compressed air may be used only be used with the flush valve open and with the air pressure at 40 psi (2.76 bar) or less
• XF Series Dripline fittings are rated to 50 psi (3.45 bar), so the air pressure must be adjusted below this pressure
• It is air volume, not pressure, which is effective when blowing out the lines
• The pressure-regulating valve that is part of the control zone regulates water, not air pressure
| • | With all drain ports open, compressed air should be |
| applied until no water is seen exiting the ports |
• After turning off the air, close all drain ports
If compressed air is not used to blowout the lines:
• A drain port should be installed at all low points in the zone. These ports may be a tee or elbow with a threaded plug or a manual flush valve
• If the zone is in a grid or closed loop system, the headers may contain a significant amount of water because they are either blank XF Series tubing, PVC, or poly pipe. It is important to provide drain ports for these components
| • | If the zone has laterals that dead-end and are not |
| connected to an exhaust header, the lateral ends should |
be opened to drain at the lowest point(s)
WINTERIZING
MAINTENANCE
PREVENTATIVE
Se ct io n
Se ct io n
Watertronics® Owners Guide
This guide is intended solely for the purpose of giving a better understanding of the Watertronics® Pumping Systems. Watertronics® assumes no responsibility or liability due to the use or misuse of this manual.
Reproduction of the contents of this publication, in whole or part, without written permission of Watertronics, Inc is strictly prohibited.
Identifies information about practices or circumstances that can lead to personnel injury, death, property loss or economic loss.
Publish Date 02/06/2012 Copyright Watertronics LLC 2009
TROUBLESHOOTING GUIDE
--- WARNING !! ---
This equipment contains LIFE THREATENING VOLTAGES.
Exercise EXTREME CAUTION when working on or near this part of the station. Never open the electrical enclosure until you have
TURNED OFF all power to the station.
NOTE: When checking fuses for continuity, make sure that ALL power is OFF. If the fuses are good, check the electrical power for CORRECT Voltage Levels before replacing suspected bad components. Since this must be done with power ON, exercise EXTREME
CAUTION.
(1) ------------------------------------------------------------------------------------ SYMPTOM: Pressure Display Remains at One Reading (and/or above 200 PSI) on the Display
PROBABLE CAUSE: CORRECTIVE ACTION:
The Pressure sensor is not Check for loose or unplugged wires and repair.
Connected at the Terminal Strip or is unplugged.
The Pressure sensor has Replace PRESSURE SENSOR.
FROZEN and Failed.
(2) ------------------------------------------------------------------------------------ SYMPTOM: Pumps will NOT come on in AUTO mode -- even though The Pressure in the system is LOW.
PROBABLE CAUSE: CORRECTIVE ACTION:
Low Pressure Alarm Check for Cause(s) of LOW PRESSURE Condition exists. Alarm and correct.
The Pressure Reading on Calibrate the Pressure Display to match the the Display is not Accurate. Liquid-Filled Gauge.
Troubleshooting Guide (Continued...Page 2 of 5)
(3) ------------------------------------------------------------------------------------ SYMPTOM: Pumps will NOT run in either MANUAL or AUTO.
PROBABLE CAUSE: CORRECTIVE ACTION:
No Power at Pump Motor(s). Turn ON Main Power. Turn ON Panel Power.
Phase Monitor NOT on. Ensure Correct Phase & Voltage Level.
Duplex Outlet/GFCI Tripped. Press RESET on GFCI Unit.
An Overload Relay has tripped. Check OVERLOAD Relays. RESET if Tripped.
Blown Motor Fuse(s) Replace FUSE(s).
Blown Transformer Primary, or Check for loose wires or shorted wires and Secondary Fuse(s). Replace FUSE(s).
(4) ------------------------------------------------------------------------------------ SYMPTOM: Pumps run in AUTO mode, but do not SHUT-OFF, And/Or, Continuously Cycle ON & OFF.
PROBABLE CAUSE: CORRECTIVE ACTION:
Irrigation System is Check for open sprinkler heads, stuck valves, Demanding Water. or broken pipes in the system.
The Flow Reading on the Re-calibrate the FLOW Display.
Display is not Accurate.
The Flow Sensor is Defective. Replace SENSOR if unable to Calibrate Flow or, if Green LED (on term. Strip) does NOT Flash when water is flowing in the System.
The Pressure Relief Valve (PRV) Check the PRV. Clean and Adjust as Required.
is Leaking or needs Adjustment.
(Continued...Page 3 of 5)
(5) ------------------------------------------------------------------------------------ SYMPTOM: Pump runs in AUTO mode, but ALARMS.
PROBABLE CAUSE: CORRECTIVE ACTION:
Alarm Condition -- Low/High Correct & Clear Alarm Condition.
Pressure, etc...
The Electronic Butterfly Valve Check for proper operation of EBV’s.
(EBV) did not open.
Tripped Motor Overload Relay. Check & RESET Overload(s).
(6) ------------------------------------------------------------------------------------ SYMPTOM: The Electronic Butterfly Valve(s) -- EBV’s -- will NOT Open or Close.
PROBABLE CAUSE: CORRECTIVE ACTION:
There is a Blown Fuse on a Check Output FUSE(s) and Replace.
PLC output driving an EBV.
The Pressure sensor is Test & Replace PRESSURE SENSOR.
Defective.
Defective Butterfly Valve(s) Check to see if EBV will OPEN Manually.
Defective Electric Actuator(s). Remove the Actuator Cover and inspect for:
Loose Wires, Loose/broken RC Snubbers, Stripped/Broken gears, Loose/Broken Brake Wheel assembly.
(Continued...Page 4 of 5)
(7) ----------------------------------------------------------------------------------- SYMPTOM: Excessively HIGH Pressure Develops Before the Station Shuts-Down (High Pressure Alarm).
PROBABLE CAUSE: CORRECTIVE ACTION:
There is a defective, dirty, or Clean, adjust or repair as required.
Misadjusted Pressure Relief Valve
The Pressure sensor is Test & Replace PRESSURE SENSOR.
Disconnected or Defective.
EBV(s) not functioning properly. Test each EBV for correct operation. Repair or
Replace EBV(s) as required.
(see SYMPTOM #6)
The Pressure Display Needs Re-calibrate Pressure Display to match Calibration. The Reading on the Liquid-filled gauge.
(8) ------------------------------------------------------------------------------------ -SYMPTOM: The Station Alarms on LOW PRESSURE ALARM.
PROBABLE CAUSE: CORRECTIVE ACTION:
Irrigation system is demanding If number of sprinkler heads ON exceeds water Beyond Station’s Capacity. Capacity, Change Program accordingly.
A Pump(s) is NOT coming ON when Check for a TRIPPED Overload or a BLOWN called for by PLC. Fuse(s). RESET or REPLACE as Required.
One, or more, EBV is NOT Opening Check & Correct OPERATION of EBV(s) or when directed to by the PLC. Electric Actuators (see SYMPTOM #6).
The Pressure sensor is Test & Replace PRESSURE SENSOR.
Defective.
(Continued...Page 5 of 5)
(9) ------------------------------------------------------------------------------------ SYMPTOM: The Pumps lose PRIME (HC Model Systems Only).
PROBABLE CAUSE: CORRECTIVE ACTION:
The Positive Prime is plugged Clear obstruction, or open the Positive Prime or shut-off. Valve if it is shut-off.
A significant leak exists in Repair the leak in the line.
the Suction Line.
The suction line Foot Valve Repair, or replace Foot Valve.
is leaking.
A Petcock on the Volute Case Close the Petcock.
may be open.
There may be a defective Pump Repair/Replace the defective SEAL.
Mechanical Seal.
(10) ---------------------------------------------------------------------------------- SYMPTOM: The Station Alarms on HIGH TEMPERATURE.
PROBABLE CAUSE: CORRECTIVE ACTION:
The Water Temperature of the Check for Loss of PRIME; or for a LEAK in Pump Inlet is above 120 degrees. The Suction Line.
Defective Temperature Sensor. Replace TEMPERATURE SENSOR.