19KZ1026Q0002_Solicitation for Elevator Preventive Maintenance Services.pdf
PDF 868 KB Posted
- Attached to
- Elevator Preventive Maintenance Services
- Solicitation number
- 19KZ1026Q0002
- Issued by
-
Department of State
About this file
This is a Request for Quotations (RFQ) for elevator preventive maintenance services at the U.S. Embassy in Astana, Kazakhstan. The solicitation number is 19KZ1026Q0002, issued February 20, 2026, with quotations due by March 6, 2026 at 3:00 PM local time. The Government intends to award a firm fixed-price contract to the lowest-priced, technically acceptable, responsible quoter based on initial quotations without discussions, though discussions may occur with competitive-range quoters if necessary. A pre-quotation conference will be held on February 25, 2026 at 2:00 PM local time at the U.S. Embassy Astana.
The contract requires maintenance of two KONE passenger elevators (models H404470 and H404471, both installed October 2006) to maintain safe, reliable, and efficient operating condition. Services include monthly preventive maintenance by a trained elevator mechanic, 24-hour/7-day emergency response service with one-hour maximum response time for emergencies and 24-hour maximum for non-emergencies, callback service within three hours for repeat malfunctions, annual no-load and five-year full-load safety tests per ASME 17.1 standards, maintenance control plans, hazardous materials disposal, and firefighter emergency operations testing. The contract is for a base year plus four option years. Contractors must be KONE-certified, maintain comprehensive general liability insurance ($5,000 USD bodily injury, $100,000 USD property damage), workers' compensation coverage (500,000 tenge), obtain all required local licenses and permits, and register in SAM prior to quotation submission. Quotations must include SF-1449 forms, pricing for base and option years in Kazakhstani tenge with VAT shown separately, Section 5 representations and certifications, and proof of SAM registration. All proposals must be submitted electronically to AstanaGSOProcurement@state.gov in MS-Word or PDF format not exceeding 30MB, with proposals in English only.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
1. REQUISITION NUMBER
PR15799972
2. CONTRACT NO. 3. AWARD/EFFECTIVE
4. ORDER NUMBER
PR15799972
5. SOLICITATION NUMBER
19KZ1026Q0002
6. SOLICITATION ISSUE DATE
February 20, 2026
7. FOR SOLICITATION
INFORMATION CALL:
a. NAME
Jeffrey Meyer
b. TELEPHONE NUMBER(No collect calls)
+7 7172 702100
8. OFFER DUE DATE/
LOCAL TIME: March 6, 2026 local Astana time, 3pm
9. ISSUED BY
CODE
10. THIS ACQUISITION
IS
UNRESTRICTED OR SET ASIDE:____ %
FOR:
American Embassy Astana SMALL BUSINESS WOMEN-OWNED SMALL BUSINESS
R. Koshkarbayev Avenue, Blvd#3 Astana, Kazakhstan
HUBZONE SMALL
BUSINESS
(WOSB) ELLIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM NAICS:
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
EDWOSB
8 (A) SIZE STANDARD:
11. DELIVERY FOR FOB
DESTINATION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS 13a. THIS CONTRACT IS A
RATED ORDER
UNDER
DPAS (15 CFR
700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ IFB RFP
15. DELIVER TO CODE 16. ADMINISTERED BY CODE
American Embassy Astana, Kazakhstan, R. Koshkarbayev Avenue, Blvd#3
Mr. Jeffrey Meyer, Contracting Officer
17a. CONTRACTOR/
OFFERER
CODE FACILITY
CODE
18a. PAYMENT WILL BE MADE BY
American Embassy Astana Financial Management Section, R. Koshkarbayev Avenue, Blvd#3, AstanaInvoices@state.gov
CODE
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS
IN
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK
BELOW IS CHECKED SEE ADDENDUM
19.
ITEM NO.
20.
SCHEDULE OF SUPPLIES/SERVICES
21.
QUANTITY
22.
UNIT
23.
UNIT PRICE
24.
AMOUNT
Elevator Preventive
Maintenance Services (see attached)
25. ACCOUNTING AND APPROPRIATION DATA 26. TOTAL AWARD AMOUNT (For Govt. Use Only)
27a.SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE
ATTACHED ADDENDA
ARE ARE NOT ATTACHED
27b.CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN 2 COPIES
TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DELIVER ALL
ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY ADDITIONAL
SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED HEREIN.
29. AWARD OF CONTRACT: REF. _________________ OFFER DATED
____________. YOUR OFFER ON SOLICITATION (BLOCK 5), INCLUDING
ANY ADDITIONS OR CHANGES WHICH ARE SET FORTH HEREIN, IS
ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)
30b. NAME AND TITLE OF SIGNER (Type or print) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (Type or print) Jefferey Meyer 31c. DATE SIGNED
02/20/2026
19.
ITEM NO.
20.
SCHEDULE OF SUPPLIES/SERVICES
21.
QUANTITY
22.
UNIT
23.
UNIT PRICE
24.
AMOUNT
32a. QUANTITY IN COLUMN 21 HAS BEEN
RECEIVED INSPECTED ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED:
32b. SIGNATURE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32c. DATE 32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE 32f. TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE
32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE
33. SHIP NUMBER 34. VOUCHER NUMBER 35. AMOUNT VERIFIED
CORRECT FOR
36. PAYMENT 37. CHECK NUMBER
PARTIAL FINAL COMPLETE PARTIAL
38. S/R ACCOUNT NO. 39. S/R VOUCHER
NO.
40. PAID BY
41.a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR
PAYMENT
42a. RECEIVED BY (Print)
41b. SIGNATURE AND TITLE OF CERTIFYING 41C. DATE
42b. RECEIVED AT (Location)
42c. DATE REC’D (YY/MM/DD) 42d. TOTAL CONTAINERS
TABLE OF CONTENTS
SECTION 1 - THE SCHEDULE
SF 1449 cover sheet Continuation To SF-1449, RFQ Number 19KZ1026Q0002, Prices, Block 23 Continuation To SF-1449, RFQ Number 19KZ1026Q0002 , Schedule Of
Supplies/Services, Block 20 Description/Specifications/Work Statement Attachment 1 -List of Elevators to be Maintained Attachment 2 - List of Tasks to be Performed
SECTION 2 - CONTRACT CLAUSES
Contract Clauses Addendum to Contract Clauses - FAR and DOSAR Clauses not Prescribed in Part 12
SECTION 3 - SOLICITATION PROVISIONS
Solicitation Provisions Addendum to Solicitation Provisions - FAR and DOSAR Provisions not Prescribed in
Part 12
SECTION 4 - EVALUATION FACTORS
Evaluation Factors Addendum to Evaluation Factors - FAR and DOSAR Provisions not Prescribed in Part 12
SECTION 5 - REPRESENTATIONS AND CERTIFICATIONS
Offeror Representations and Certifications Addendum to Offeror Representations and Certifications - FAR and DOSAR Provisions not Prescribed in Part 12
SECTION 1 - THE SCHEDULE
Continuation/Addendum to SF-1449
RFQ Number 19KZ1026Q0002
PRICES, BLOCK 23
1.0 DESCRIPTION
The U.S. Embassy/Consulate in Astana requires services to maintain building elevators in safe, reliable and efficient operating condition. The contract type is a firm fixed price contract for routine maintenance services paid at the monthly rate below. These rates include all costs associated with providing elevator maintenance services in accordance with manufacturer’s warranty including materials, labor, insurance (see FAR 52.228-4 and 52.228-5), overhead, profit and VAT (if applicable). The contract will be for a base-year period, with four option year period of performance.
2.0 PRICING
2.1 VALUE ADDED TAX
VALUE ADDED TAX. Value Added Tax (VAT) is not included in the CLIN rates. Instead, it will be priced as a separate Line Item in the contract and on Invoices. Local law dictates the portion of the contract price that is subject to VAT; this percentage is multiplied only against that portion. It is reflected for each performance period, and can be adjusted if the government changes the VAT.
2.2 Base Year - The Contractor shall provide the services shown below for the base period of the contract, starting on the date stated in the Notice to Proceed and continuing for a period of 12 months.
The fixed unit prices, estimated quantities, and ceiling for each category are:
Line Item Description
Monthly Price x 12 Months Annual Total, tenge
Routine monthly maintenance for all elevators described in Attachment 1
2.3 Option Year 1 - The Contractor shall provide the services shown below for Option Year 1, starting one year after the date stated in the Notice to Proceed and continuing for a period of 12 months.
Line Item Description
Monthly Price x 12 Months Annual Total, tenge
2.4 Option Year 2 - The Contractor shall provide the services shown below for Option Year 2, starting two years after the date stated in the Notice to Proceed and continuing for a period of 12 months.
Line Item Description
Monthly Price x 12 Months Annual Total, tenge
2.5 Option Year 3 - The Contractor shall provide the services shown below for Option Year 3, starting three years after the date stated in the Notice to Proceed and continuing for a period of 12 months.
Line Item Description
Monthly Price x 12 Months Annual Total, tenge
2.6 Option Year 4 - The Contractor shall provide the services shown below for Option Year 4, starting four years after the date stated in the Notice to Proceed and continuing for a period of 12 months.
Line Item Description
Monthly Price x 12 Months Annual Total, tenge
Routine monthly maintenance for all elevators described in
Base Year Total
Option Year 1 Total
Option Year 2 Total
Option Year 3 Total
Option Year 4 Total
GRAND TOTAL OF BASE YEAR PLUS ALL OPTION
YEARS
3.0 NOTICE TO PROCEED
After contract award and submission of acceptable insurance certificates and copies of all applicable licenses and permits, the Contracting Officer will issue a Notice to Proceed. The Notice to Proceed will establish a date (a minimum of ten (10) days from date of contract award unless the Contractor agrees to an earlier date) on which performance shall start.
CONTINUATION/ADDENDUM TO SF-1449
RFQ Number 19KZ1026Q0002
SCHEDULE OF SUPPLIES/SERVICES, BLOCK 20
DESCRIPTION/SPECIFICATION/WORK STATEMENT
1.0 SCOPE OF WORK
The U.S. Embassy in Astana, Kazakhstan requires the Contractor to maintain the elevators identified in Attachment 1 in safe, reliable and efficient operating condition. The Contractor shall provide all necessary managerial, administrative and direct labor personnel, and as well as all necessary transportation, equipment, tools, repair parts, supplies and materials required to perform inspection, maintenance, repair, and component replacement as required to maintain the elevators in accordance with the manufacturer's specifications. Under this contract the Contractor shall provide:
The services of a trained elevator mechanic on a monthly basis to check and repair equipment operation and perform scheduled and preventive maintenance;
24 hours/day, 7 days/week emergency response service;
appropriate, same day, service in response to an elevator malfunction trouble call; and after-hours emergency minor adjustment callback service
2.0 HOURS OF PERFORMANCE
The Contractor shall schedule all routine maintenance and repair work during normal building hours which are defined as 8:00 to 18:00 Monday to Friday, excluding local, bank, and American holidays, unless approved in advance by the Contracting Officer's Representative (COR).
3.0 ACCESS TO GOVERNMENT BUILDINGS AND STANDARDS OF CONDUCT
3.1 General. The Contractor shall designate a representative who shall supervise the Contractor's elevator mechanics and be the Contractor's liaison with the U.S. Embassy/Consulate. The Contractor's employees shall be on-site only for contractual duties and not for any other business or purposes.
Contractor employees shall have access to the elevators' hoistways, lobbies and machine rooms, either with or without security escorts, only with specific permission by either the Contracting Officer or the
COR.
3.2 Personnel Security. The Government reserves the right to deny access to U.S owned and U.S.-operated facilities to any individual. The Contractor shall provide the names, biographic data and police clearance on all Contractor personnel who shall be used on this contract prior to their utilization.
The Government shall issue identity cards to approved Contractor personnel, each of whom shall display his/her card(s) on the uniform at all times while on Government property or while on duty at private residences serviced under this contract. These identity cards are the property of the Government. The Contractor shall return all identity cards when the contract is completed, when a Contractor’s employee leaves this contract, or at the request of the Government.
3.3 Standards of Conduct
3.3.1 General. The Contractor shall maintain satisfactory standards of employee competency, conduct, cleanliness, appearance and integrity and shall be responsible for taking such disciplinary action with respect to employees as may be necessary. Each Contractor employee shall adhere to standards of conduct that reflect credit on themselves, their employer, and the United States Government. The Government reserves the right to direct the Contractor to remove an employee from the worksite for failure to comply with the standards of conduct. The Contractor shall immediately replace such an employee to maintain continuity of services at no additional cost to the Government.
3.3.2 Uniforms and Personal Equipment. The Contractor's employees shall wear clean, neat and complete uniforms when on duty. All employees shall wear uniforms approved by the Contracting Officer's Representative (COR). The Contractor shall provide, to each employee and supervisor, uniforms and personal equipment. The Contractor shall be responsible for the cost of purchasing, cleaning, pressing, and repair of the uniforms.
3.3.3 Neglect of duties shall not be condoned. This includes sleeping while on duty, unreasonable delays or failures to carry out assigned tasks, conducting personal affairs during duty hours and refusing to render assistance or cooperate in upholding the integrity of the worksite security.
3.3.4 The Contractor shall not condone disorderly conduct, use of abusive or offensive language, quarreling, and intimidation by words, actions, or fighting. Also included is participation in disruptive activities that interfere with normal and efficient Government operations.
3.3.5 Intoxicants and Narcotics. The Contractor shall not allow its employees while on duty to possess, sell, consume, or be under the influence of intoxicants, drugs or substances which produce similar effects.
3.3.6 Criminal Actions. Contractor employees may be subject to criminal actions as allowed by law in certain circumstances. These circumstances include but are not limited to the following actions:
falsification or unlawful concealment, removal, mutilation, or destruction of any official documents or records or concealment of material facts by willful omission from official documents or records;
unauthorized use of Government property, theft, vandalism, or immoral conduct; unethical or improper use of official authority or credentials; security violations; organizing or participating in gambling in any form; and misuse of weapons.
3.3.7 Key Control. The Contractor shall receive, secure, issue and account for any keys issued for access to buildings, offices, equipment, gates, or other areas, for the purposes of this contract. Keys shall not be duplicated without the COR's approval. Where the Government determines that the Contractor or its agents have duplicated a key without permission of the COR, the Contractor shall remove the individual(s) responsible from performing work under the contract. If the Contractor has lost any such keys, the Contractor shall immediately notify the COR. In either event, the Contractor shall reimburse the Government for the cost of rekeying that portion of the system so compromised.
4.0 WORK REQUIREMENTS
4.1 General. The Contractor shall provide full service to meet routine maintenance requirements.
The Contractor shall maintain elevators so that the elevators are in a safe and efficient operating condition at all times. In the event of a breakdown, the Contractor shall make every effort to immediately return the elevator to an operating condition.
4.2 Summary of Services - Electric traction and Hydraulic
4.2.1 Scope
The Contractor agrees to provide skilled competent employees trained by the elevator manufacturer or an accredited elevator apprentice program for the purpose of maintenance and repair of elevators, dumbwaiters, accessibility lifts, and material lifts as defined in ASME 17.1 Safety Standard for Elevators and Escalators. Maintenance shall include monthly preventive maintenance, repair and replacement of worn or defective components, lubrication, cleaning, and adjusting as required for operation as designed. Only parts and supplies recommended by the original equipment manufacturer shall be installed.
Other services to be provided by the contractor include:
- 24 hour call back service. Entrapments or accidents involving vertical transportation equipment are an emergency call back, as is a condition where all units are out of service.
These calls should have a 1 hour maximum response time. Other call backs should carry a maximum response time of 24 hours.
- Periodic inspection and tests. Annual “No-Load” Safety Tests and Five Year “Full Load” Safety Tests in accordance with ASME 17.1. The contractor shall provide all necessary procedures, labor, testing equipment and test weights.
- Maintenance Control Plan. The contractor shall provide a maintenance control plan to include all units.
- Disposal of hazardous materials in accordance with contract and local regulations.
- Firefighters emergency operations monthly operation, including documentation.
- Examination and testing of underground hydraulic systems.
Regulation:
ASME A17.1 Safety Standard for Elevators and Escalators ASME A17.2 Guide for Inspections of Elevators, Escalators, and Moving Walks ASME A17.2 Safety Code for Existing Elevators and Escalators 15 FAM 660 Elevator Management Program
4.2.2 Owners Responsibilities
- Main line disconnects shall be of the enclosed type: circuit breaker or properly fused and provided with a lockout feature.
- Machine rooms, pits and other equipment rooms must be kept locked.
- Control of keys as required by ASME A17.1, Section 8.6.10.3.
- Machine rooms and pits shall have proper illumination. Pit lights shall be guarded.
Convenience outlets equipped with GFCI shall be furnished.
- Class ABC fire extinguishers are required in machine room. See ASME A17.1, Section
8.6.1.6.5.
- Car top exits must be able to open from outside only.
- Side exits, where provided, must be arranged so the door can be opened from inside the car only by a special removable key and from outside the car by a non-removable handle. Side exits shall be equipped with contacts. Keys shall be stored as specified in Paragraph 4.3.
- Repair and replacement of door panels, frames, fixtures and their appurtenances, car interiors and lighting, as well as damages including misuse and vandalism and shall be promptly corrected through coordination with the maintenance contractor.
- Equipment room environment shall be maintained as specified by the equipment manufacturer.
- Smoke detectors etc. for firefighters' service and main line disconnecting means where sprinklers are provided in elevator spaces.
Identification:
- Test tags and seals must be in place.
- Rope tags (and resocketing tags) shall be furnished as required.
- Ensure machine room code data sign, crosshead data plate, buffer data plates, etc. are provided in accordance with the applicable codes. Data plates shall be updated to list any alterations.
- Ensure all landings are properly illuminated.
- Communication systems.
- Hoistway door unlocking device key(s) shall be stored as specified in Paragraph 4.3.
4.2.3 Elevator Cleanliness
- Car top shall be free of debris, lint and lubricants. Pans, securely fastened in place, shall be provided under the door operator and rope hitches, if necessary. Assessment of cleanliness shall be based on minimum fire hazard and freedom from lubricant and dirt that could be tracked through the building or could constitute an unsafe surface for a person on the car top.
A vacuumed surface free from lubricants shall be satisfactory. Material must not be stored on the car top. All equipment on the car top, including flexible cords, must be securely fastened to prevent snagging or falling from the car.
- Pit area shall be dry and free from rubbish or lubricants. Rusted pit equipment shall be cleaned and painted or replaced if severely damaged. See ASME A17.1, Section 8.6.4.7.
- Hoistway, Rails and Counterweight: Dirt, lint and excess oil in hoistway, particularly on the rails, shall be removed. The counterweight, the rear of sills and headers shall be clear of dirt accumulation. The bottom and sides of the car shall be free of oil and lint.
- Machine Room and Equipment: The floor shall be "broom" clean. Selectors and controllers shall be cleaned to remove any accumulation of dirt or lubricants. Electronic components and printed circuit boards may be damaged by cleaning with a blower or compressed air. Follow the manufacturers' procedures.
- Machines, motors and generators shall be clear of oil leakage, dirt and carbon dust. Some lubricant leakage is normal; however, it shall not be allowed to accumulate.
- Foreign matter collected on the windings may damage insulation, reduce air flow and eventually result in a burn out, shorts or grounds. Oil and carbon dust that is allowed to accumulate in commutator slots will inhibit proper commutation and may result in bar to bar shorts.
- Storage Cabinets and areas shall be neat and organized. Storage of soiled wipers (rags) shall be discouraged. The tops of lubricant cans shall be clean and all containers shall be closed by properly fitting covers.
4.2.4 Elevator Lubrication
- Lubricants and schedules recommended by the equipment manufacturer shall be used, unless an engineering evaluation of alternate products has been conducted. Ensure that proper lubrication schedules are being used. Lubricants shall be clean, not gummy or thickened.
Grease shall be soft.
- Guide shoe pivots and stems shall be free to move.
- Rails used with roller guides shall be dry.
- Rails used with slide guides must use a lubricant compatible with the safeties.
- Rails must be free of oxidized lubricant in the area where the safety jaws apply.
- Rail blades shall not be painted when “B” Type safeties are used.
- Hoist ropes shall be clean and lubricated in accordance with manufacturer’s specifications.
- Manufacturers recommended lubricant shall be used on non-metallic sheave liners.
- Brake cores and pivots shall be lubricated per manufacturer's specifications.
- Governor ropes shall not be lubricated in the field.
- Car safety linkage, governor tension frame and sheaves shall be friction free.
- Sleeve bearing 2:1 sheaves shall be carefully examined for proper lubrication.
- External gears shall be examined for proper lubrication.
- Oil rings and chains must turn and carry oil.
- Worm gears must carry oil.
- Machine roller and ball bearings shall be lubricated per manufacturer’s specifications.
4.2.5 Elevator Door Operation
Adjustment:
- Door system masses must be considered when adjusting the door closing speed to ensure compliance with ASME A17.1 Code requirements. Closing force must be 135 N (30 lb.) or less. The doors shall open and close smoothly, quietly and without slamming. All installed door reopening device(s) shall be fully functional. Reversal shall occur with minimum stroke of safety edge. Light ray shall be operative. Electronic devices shall provide sufficient range to reverse door with out physical contact.
Noise Levels:
- Rattles and squeaks in the door operator linkage and hangers shall be investigated and corrected. Fastenings of drive arms, clutch or vanes shall be tight. Pivots and joints shall be free from excessive wear and be properly lubricated.
Mechanical System:
- Door gibs, on both car and hall doors shall be securely fastened, have minimum wear, ¼ in.
(6.4 mm) sill engagement and equipped with safety tabs. Check for worn sill grooves and doors that rub together.
- Door rollers and tracks shall be clean, rust free and lubricated as specified. Rollers with loose tires, flat spots, or bad bearings shall be replaced.
- Up thrusts shall prevent the doors from jumping the track but shall not ride the track. Up thrust roller to track clearance shall not exceed 0.015 in. (0.4 mm). Fastenings shall be locked and rollers must turn freely.
- Hoistway door closers shall ensure full door closure of the stopped door from any position.
Spirator or weight troughs must be tightly fastened and cords (cables) shall have no abrasion or broken wires.
- Rough tracks shall be made smooth or be replaced.
- Relating cables, chains, arms or racks and their fastenings must be tight. Cables with excessive broken wires or abrasion shall be replaced. Sheaves shall turn freely. Inspect for worn sheave grooves and stamped sheaves that are separating.
- Hydraulic door checks shall be adjusted to avoid slamming. Some checks function in both the open and close direction. Checks shall be filled to the proper level with the fluid recommended by the manufacturer. Excessive oil leakage shall be corrected and leakage shall be cleaned up.
Door Operator and Motor:
- The door operator shall be reasonably clean. Lubricants shall be in accordance with the manufacturer’s instructions, including oil levels. Oil leaks must be at a minimum since damage to the inside canopy finish may result.
- Motor brushes shall be free in the holders and of sufficient length to avoid commutator damage.
- Excessive gear backlash and loose or worn belts shall be adjusted or shall have worn parts replaced. All bearings shall be quiet and "fits" shall be tight. Loose set screws, pins or keys shall be corrected.
Car Door Contact:
- The car door contact must make reliably. For automatic elevators, the contact shall be adjusted to limit the clear open space to 2 in. (51 mm) or less. The contact location and design must comply with the ASME A17.1 Code.
Hoistway Door Interlocks:
- Interlocks must be properly maintained to ensure safe and reliable elevator operation.
- Contacts shall be free from pitting or burning, wiring connections must be tight and in good condition. The mechanical pivots, engaging rollers and linkage shall operate freely and be lubricated as required. Worn or damaged rollers and linkage shall be repaired or replaced.
4.2.6 Elevator Fixtures, Indicators, and Buttons
- Buttons and Key switches:
- Shall have the correct legible markings.
- Must not stick or be plugged.
- Damaged buttons shall be replaced.
- Indicators and Signals:
- Indicator lamps shall illuminate as required. The use of neon lamps, LED or other long life light sources shall be encouraged.
- Broken lenses shall be replaced.
- Audible indicators shall function.
General:
- Face plates shall be in place and mounted square or plumb.
- Fastening screws shall be of the proper type.
- Missing screws shall be replaced.
4.2.7 Elevator Control System
General:
- Acceleration and stopping shall be smooth and within the design limitations.
- Controller components shall be clearly identified as shown on wiring diagrams.
Safety Devices:
- Safety circuits must be fully operational. It is absolutely necessary to test each and every part of this circuit. Particular attention shall be given to the interlocks and car door contacts.
Hoistway limits and terminal slowdowns shall have rollers in good condition and turn freely.
Mechanically driven speed and position sensors shall be provided with means to detect mechanical failures.
- Static motion control systems have additional protection requirements. Ensure that they comply with code requirements.
- Fuses shall be of the proper type and rating as listed on the controller or as listed on the wiring diagram. Time delay fuses shall be used only in the circuits, where specified. Renewable link fuses are not recommended. Wire jumpers must not be installed.
Switch Gear:
- Contacts shall not be excessively worn and have adequate contact pressure to ensure reliable operation. Pitted contacts shall be dressed or replaced.
- Shunts must be flexible. Insulation on conductors and end attachments must be in good condition, no broken wires or cracked or hardened sections.
- Switches or contacts shall not be blocked. Residual guards and shading coils shall not be damaged. Pivot points or pins shall be clean and lubricated as directed by manufacturers standards. Kickoff springs in place, not stretched. Discolored encapsulated relays or switches, shall be examined for mechanical or electrical damage.
- Overload relays shall be tagged indicating test dates and operation parameters. Oil dashpots shall be filled to the specified levels with the recommended fluid. Ensure that the pistons are free to move.
- Switch gear shall operate quietly and smoothly and shall pull in and drop out properly.
Selectors and Positioning Devices:
- Selector traveling cables and all movable wiring must be flexible. All terminations shall be secure with insulation and connections in good condition.
- Selector brushes and contacts shall be examined for wear or pitting and be replaced as necessary.
- Examine mechanical condition of selectors for bearing wear or failure. Keys and set screws must be tight. Examine for looseness and fretting.
- Gears, guides and chains must be lubricated, free from rust and evidence of cutting (scoring).
Drip pans shall be provided where necessary.
Mechanical Condition:
- All connections shall be examined for tightness and indications of heating.
- Controller and selector shall be clean as listed in Paragraph 6.4.
- Resistors and grids must not be patched. Bands must be properly placed and free from burning.
Examine wiring for insulation charring.
- Resistors and capacitors must be securely and properly mounted to ensure proper heat dissipation. Resistors and capacitors that are mechanically or electrically damaged shall be replaced. Wiring, both field and internal shall be neat and bundled. Temporary wiring shall not be used. Terminal blocks shall be labeled.
- Traveling cables shall be in good condition. Minor abrasion may be taped or repaired. Guide wires, beam pads or screens shall be provided if conditions warrant. Traveling cable attachments must be secure.
Wiring Diagrams:
- Wiring diagrams shall be available, be reasonably clean and in good condition and must match the controller. Changes shall be clearly marked.
4.2.8 Electric Elevator Mechanical Condition And Adjustment
Worms and Gears:
- Shall not show abnormal wear, no ridging or scored teeth.
- Bearings shall run quietly.
- Some leakage of worm shaft seals is acceptable.
- Gland packing shall have controlled leakage.
- Bearings or gears that run at a high temperature shall be investigated.
Drive, Deflector and Secondary Sheaves:
- Excessive groove wear or damage shall be corrected.
- Keys and or shrink fits shall not show fretting (rust or corrosion)
Brake Pulley and Coupling:
- Fits to shafts shall be secure, no fretting at the interface.
- Flexible couplings shall be tight, all pins and bushings securely in place. Pulley surface shall be smooth, with no excessive scoring.
Brake:
- Brake switch, if furnished, shall be adjusted to properly open and close the contacts.
- The linings shall not be worn to the extent that the rivets touch the drum.
- Brake shoes shall have minimum lift without dragging.
- Ensure full lift is consistent.
- Brakes to be adjusted to comply with code requirements.
Motors and Generators:
- Bearings shall run quietly.
- DC motor field coils shall not have excessive movement.
- Electrical connections shall be tight. Look for discoloration.
- Armature or rotor clearances shall be approximately equal throughout their circumference.
Commutators shall run true. Undercutting shall provide clean slots without feather edge mica.
Scoring or grooving, if any, shall be at a minimum.
- Brushes must be free in holders. Inspect for damage, copper embedment and short brushes.
- Pin point sparking is normal during acceleration and stopping. Severe arcing shall be investigated.
- Insulation resistance must be monitored to ensure proper life of electrical equipment. The minimum resistance permissible depends upon the operating voltage and temperature. Wet conditions will reduce insulation resistance as will high humidity. Any leakage to ground less than 1 megaohm needs to be investigated. The use of high voltage meggers or high voltage pulse tests is not recommended. Such testing may result in insulation damage that cannot be readily detected. In most cases, the windings can be field cleaned to restore proper insulation resistance. In extreme cases, the equipment may have to be removed to a qualified shop for steam cleaning, dipping and baking. Care must be taken when painting windings in the field to avoid sealing in lubricants or carbon dust.
Sound Isolation, kick angles, etc.:
- Sound isolation pads shall be pliable. Check for disintegration, splitting or cracking.
- Kick angles and tie downs shall be properly in place.
- Ropes and Compensating Means:
- Hoist and compensating ropes shall be equalized.
- Fastenings must be of an approved type and ends made up as directed by applicable codes.
- Rope data tags, including resocketing tags for drum machines, are required.
- Governor ropes must not be lubricated.
- Wear and wire breaks within limits. Inspect ropes as specified by ASME A17.1.
- Hoist ropes shall be clean to permit inspection, lightly lubricated to reduce abrasion and corrosion, yet must provide adequate traction, without slippage.
- Hoist ropes may be restricted from turning as outlined in the ASME A17.1.
- Compensating means shall be examined for damage and for proper attachment.
- Check run-by’s and clearances for code compliance.
Compensating Sheave Assembly:
- Tie down compensation must be properly operating, if furnished.
- Examine compensating sheave for freedom of movement and uneven grooves. The switch must operate within the limits of compensating sheave travel.
- Oil buffers shall be filled with the manufacturer’s specified fluid to the indicated level. Ports shall be covered. Buffer pistons shall be rust free and be provided with corrosion protection.
Examine all buffers for full extension. Traveling buffers shall not be pre-compressed.
- Buffers shall be properly located and securely fastened in place.
- All moving parts of safety mechanisms shall be kept lubricated and free of rust and dirt. The clearance between the safety jaws and the rail shall comply with the applicable code requirement.
Governors system:
- Governor shall be kept clean. Jaws shall operate freely and must be clear of obstructions.
Rope lead shall be aligned to the jaws. Linkages shall be lubricated and operate freely. Gears, set screws, keys, pins and bearings must have correct fits and minimum wear or backlash.
Sheave groove shall be free of foreign matter. Check depth of groove wear that may cause rope to interfere with jaw engagement.
- Governor adjustments shall be sealed to prevent tampering. Test tags shall be in place indicating the date of the last test and the person or firm who made the test.
- A governor marking plate as required by the applicable code, securely attached to the governor shall list: The tripping speed in feet per minute. The size, material and construction of the governor rope.
- Ensure the paint does not interfere with governor operation.
- Governor switches shall operate as intended, both mechanically and electrically.
- Fly ball governors must clear obstructions that may prevent full extension of the flyballs.
- Car rope hitches must be socketed correctly. Rope data shall be furnished.
- Governor ropes must not be lubricated.
- Governor rope tension frame shall be free to move vertically with rope tensioned as designed.
Hold downs shall be adjusted to suit job conditions. Sheave bearings shall be quiet, wear limited to sheave clearance and tolerance. Sheave groove must be free of foreign matter.
Rails and Brackets:
- Rail bracket fastenings shall be tight. Masonry walls supporting rail brackets must be structurally sound.
- Rail clip bolts must be tight. Sliding clips must be free to move. Sliding clips of the type backed with spring steel clips must be examined for missing or broken spring clips. Fishplate bolts must be tight. Rail backing must be securely fastened.
- Check rails for alignment. Building settlement may transfer building load to guide rails.
- Check counterweight rails for bracket spacing and spreader brackets, particularly in the pit area.
- Rail blades shall be rust free. Blades shall not be painted when Type B safeties are used.
Refer to Paragraphs 7.4 and 7.5 and crosshead data plate for lubrication and blade condition.
5.0 SCHEDULED ROUTINE MAINTENANCE
5.1 General
5.1.1 The objective of scheduled routine maintenance is to eliminate or minimize elevator malfunction, breakdown and deterioration. Contract maintenance of the elevator must assure continuous, safe, and satisfactory operation of all elevators, their parts and components. The Contractor shall schedule routine maintenance to include all tasks herein described, in addition to routine lubrication and adjustments.
5.1.2. Elevator equipment shall include, but is not limited to: controllers, selectors, worm gears, thrust bearings, brake magnet coils, brake shoes, brushes, windings, commutators, rotating elements, contacts, coils, resistors for operating and motor circuits, magnet frames, cams, car door and hoistway door hangers, tracks and guides, door operating devices, interlocks and contacts, pushbuttons, pumps, pump motors, operating valves, electronic tubes, electronic programmable controllers, hall lanterns and indicators, hatch lighting, pit bulbs, bulb replacement and all other elevator signal accessories.
5.1.3 The Contractor shall inventory, supply, repair and replace all parts that have become unsafe due to wear and tear. The Contractor shall use genuine manufacturer’s parts or approved or equal (to be approved by COR) for all replacements. The Contractor shall maintain an easily accessible supply of spare parts sufficient for normal maintenance and expedient emergency repairs.
5.2 Checklist Approval - The Contractor shall submit to the COR a schedule and description of the scheduled routine maintenance tasks which the Contractor plans to provide. The Contractor shall prepare this schedule and task description in a checklist format similar to the one provided in Attachment 2. The Contracting Officer or COR must approve the proposed "Scheduled Routine Maintenance Task Checklist" prior to contract work commencement.
5.3 Minimum Requirements - The Contractor shall provide a trained mechanic certified by KONE to inspect and service every elevator a minimum of once a month, every month of the year. The elevator mechanic shall sign off on every item of the checklist. The elevator mechanic shall provide a soft copy of the checklist with the COR or the COR's designate following that week's routine maintenance visit. This weekly inspection and servicing shall include, but not be limited to, the following tasks:
Ride all cars to detect and repair any improper operation of the car doors, hoistway doors, acceleration, leveling accuracy on the floor stops, and the action of the machine brake;
Check and make necessary repairs to assure proper operation of retractable doors;
Review elevator’s performance with the COR, or the designated representative, to determine if any malfunctions have occurred in connection with the operation of the cars since the most recent previous scheduled routine maintenance visit;
Investigate any malfunctions which have occurred, devoting special attention to any problem involving unsafe operations, and make repairs as necessary;
Examine car stations and call buttons and replace any damaged switches, burned out lamps, bulbs and broken buttons, defective fixtures, switches, covers, and related hardware;
Trouble shoot any failure to equipment, lighting and receptacle electrical circuits;
Report findings to the COR or the COR's designee including identification of failed equipment and reason for failure;
Leave signed and dated copy of the Maintenance Checklist and also leave signed and dated copies of any other monthly, quarterly or annual checklists if those were completed during the subject visit;
Maintain emergency light units in operable condition.
6.0 TROUBLE CALL RESPONSE SERVICE
6.1 General. The Contractor shall provide "around-the-clock" service coverage for elevator trouble calls as described below and which are not excluded by paragraph 8.0 below.
6.2 Emergency Response Service - The Contractor shall provide, at no extra cost, a 24 hours/day, 7 days/week, 52 weeks/year coverage for emergency trouble calls. A trained mechanic shall be "on call" and shall be on site within a one-hour time period of the placement of an emergency trouble call by the Contracting Officer or COR. Emergency situations include people trapped in an elevator car, the suspicion/confirmation of a fire in or around elevator equipment, or an inoperative elevator with no suitable backup.
6.3 Non-Emergency Response Service - The Contractor shall provide, at no extra cost, a non-emergency response service. A trained elevator mechanic will be on site, within one working day, to trouble shoot and repair an elevator malfunction.
6.4 Callback Service - When an elevator which was previously worked on by the Contractor's mechanic, has a repeat malfunction within a 24-hour period, the Contractor shall be obligated to provide, at no extra cost, a return visit by a trained elevator mechanic to correct the problem, even if the problem is minor in nature. The elevator mechanic shall respond to this callback within a three-hour time period regardless of what time the Contracting Officer or COR made the callback complaint, including the "after hours" time periods.
7.0 PERSONNEL, TOOLS, REPAIR PARTS, MATERIALS AND SUPPLIES
The Contractor shall provide trained elevator mechanics with the appropriate tools and testing equipment for scheduled maintenance, unscheduled repairs, emergency repairs/assistance, safety inspection, and safety testing as required by this contract. The Contractor shall provide all of the necessary repair parts, materials and supplies to maintain, service, inspect and test the elevators as required by this contract.
8.0 EXCLUSIONS
The Contractor shall not assume responsibility for the following items of elevator equipment, which are not included in this contract:
Car enclosures and related items including, but not limited to, fixed or removable panels, door panels, car gates, plenum chambers, hung ceilings, light diffusers, fluorescent tubes, dry cell batteries, handrails, mirrors, floor coverings, carpets and other architectural features and accessories;
Buried caissons, cylinders and piping, and power supply feeder circuits to the machine room circuit breakers;
Computer and microprocessor devices not exclusively dedicated to the elevator equipment such as terminal keyboards and display units;
Communications equipment, such as telephones, intercoms, heat detectors, and smoke sensors, which were not installed by the Contractor or the original elevator installer;
Major Repairs: Any individual unit or incident of repair with a total estimated cost (labor and direct material costs) exceeding $3,000.00 which is not covered under routine maintenance, is not covered by this contract. The Government reserves the right to determine how these repairs are to be handled.
Such repairs will normally be accomplished by separate purchase order or contract. This exclusion does not apply if the repair is to correct damage caused by Contractor negligence.
INSURANCE REQUIREMENTS
9.1 Personal Injury, Property Loss or Damage (Liability). The Contractor assumes absolute responsibility and liability for any and all personal injuries or death and property damage or losses suffered due to negligence of the Contractor's personnel in the performance of this contract
The Contractor's assumption of absolute liability is independent of any insurance policies.
Insurance. The Contractor, at its own expense, shall provide and maintain during the entire period of performance of this contract, whatever insurance is legally necessary. The Contractor shall carry the following minimum insurance:
Comprehensive General Liability
Bodily Injury 5.000 USD per occurrence Property Damage 100.000 USD per occurrence
Workers’ Compensation and Employer’s Liability
Workers’ Compensation and Occupational Disease 500,000.00 tenge per occurrence Statutory, as required by host country law
Employer’s Liability N/A per occurrence
9.3 Worker's Compensation Insurance.
RESERVED.
10.0 PERMITS
The Contractor shall maintain in full force and affect all permits, licenses, and appointments required for the prosecution of work under this contract at no additional cost to the Government. The Contractor shall obtain these permits, licenses, and appointments in compliance with host country laws.
11.0 LOCAL LAW REGISTRATION
If the local law or decree requires that one or both parties to the contract register the contract with the designated authorities to insure compliance with this law or decree, the entire burden of this registration shall rest upon the Contractor. Any local or other taxes which may be assessed against the contract shall be payable by the Contractor without Government reimbursement.
12.0 GOVERNMENT FURNISHED PROPERTY/EQUIPMENT
RESERVED
13.0 QUALITY ASSURANCE AND SURVEILLANCE PLAN (QASP)
13.1 This plan provides an effective method to promote satisfactory contractor performance. The QASP provides a method for the Contracting Officer's Representative (COR) to monitor Contractor performance, advise the Contractor of unsatisfactory performance, and notify the Contracting Officer of continued unsatisfactory performance. The Contractor, not the Government, is responsible for management and quality control to meet the terms of the contract. The role of the Government is to monitor quality to ensure that contract standards are achieved.
Performance Objective Scope of Work Para Performance Threshold Services.
Performs all elevator preventive maintenance services set forth in the scope of work.
1. thru 19. All required services are performed and no more than one
(1) customer complaint is received per month.
13.2 Surveillance. The COR will receive and document all complaints from Government personnel regarding the services provided. If appropriate, the COR will send the complaints to the Contractor for corrective action.
13.3 Standard. The performance standard is that the Government receives no more than one (1) customer complaint per month. The COR shall notify the Contracting Officer of the complaints so that the Contracting Officer may take appropriate action to enforce the inspection clause (FAR 52.212-4, Contract Terms and Conditions-Commercial Items), if any of the services exceed the standard.
13.4. Procedures.
13.4.1 If any Government personnel observe unacceptable services, either incomplete work or required services not being performed they should immediately contact the COR.
13.4.2 The COR will complete appropriate documentation to record the complaint.
13.4.3 If the COR determines the complaint is invalid, the COR will advise the complainant. The COR will retain the annotated copy of the written complaint for his/her files.
13.4.4 If the COR determines the complaint is valid, the COR will inform the Contractor and give the Contractor additional time to correct the defect, if additional time is available. The COR shall determine how much time is reasonable.
13.4.5 The COR shall, as a minimum, orally notify the Contractor of any valid complaints.
13.4.6 If the Contractor disagrees with the complaint after investigation of the site and challenges the validity of the complaint, the Contractor will notify the COR. The COR will review the matter to determine the validity of the complaint.
13.4.7 The COR will consider complaints as resolved unless notified otherwise by the complainant.
13.4.8 Repeat customer complaints are not permitted for any services. If a repeat customer complaint is received for the same deficiency during the service period, the COR will contact the Contracting Officer for appropriate action under the Inspection clause.
ATTACHMENT 1
LIST OF ELEVATORS TO BE SERVICED
“Passenger Elevator 1” Name: “Elevator H404470”
Date of Install: “10/2006” Manufacturer: “KONE” Capacity: “1800 kg” Speed: “1 m/s” Drive Type: “Overhead traction” Date of Last Inspection: “4/20/2015” Known Issues: “None”
“Passenger Elevator 2” Name: “Elevator H404471”
Date of Install: “10/2006” Manufacturer: “KONE” Capacity: “1600 kg” Speed: “1 m/s” Drive Type: “Overhead traction” Date of Last Inspection: “4/20/2015” Known Issues: “None”
ATTACHMENT 2 - LIST OF TASKS TO BE PERFORMED
YEAR_________________ OBSERVE, CLEAN, ADJUST & TEST
MAINTENANCE CHECKLIST FOR MONOSPACE ELEVATORS
MONTH OF
MAINTENANCE/SERVICE :
COMMISSIONED ON:
(dd/mm/yyyy) REMARKS
Elevator/Local Unit ID : EE- 1103/1104 Location: Office Building
INSPECTION ACTIONS TO BE MADE IF NECESSARY
(condition / LUBRICATION ADJUSTING CLEANING WEEK operation check)
MX MACHINE
Rope guards Operation of machine stop button
Wear of traction sheave grooves and suspension ropes Machine: Tightness of the fastenings
Machine: Function of brake and manual release device Machine: Bearings and seals Machine: Fan
Control system: condition and operation of devices Control system: cables and mountings
SHAFT AND SHAFT EQUIPMENT
Guide rails and fixings
Counterweight: guide shoes and guide lubricators (if used) Counterweight: rope suspension, diverting pulley, diverting pulley bearing Overspeed governor and rope
Electrical installations and travelling cables Floor positioning devices Limit switches Lighting, ventilation and drainage Buffers Tension weights: fixings, operation
CAR AND CAR EQUIPMENT
Car sling: bolts/joints/bearings
Fixing of car sling, insulators Guide shoe fixings and condition Guide lubricators Mounting of suspension ropes
Service drive operations Car top Electrical installations
Surface of car walls
Car load weighing devices Car lighting and ventilation and fans Safety circuit: mechanical devices Safety circuit: electrical devices
Push buttons and displays
Emergency situation test (alarm devices and roof emergency hatch if used) Handrails, mirrors and other car equipment Car doors and gates (locking and operator) Door way safety devices curtain of light
FLOOR LEVEL EQUIPMENT
Push buttons, displays and alarm bell Door locks, guide shoes, sills, panels and fixings Door operation and equipment
TEST DRIVE
Operation
Noise Ride comfort Stopping accuracy
SECTION 2 - CONTRACT CLAUSES
52.212-4 CONTRACT TERMS AND CONDITIONS – COMMERCIAL ITEMS
(NOV 2023) IS INCORPORATED BY REFERENCE. (SEE SF-1449,
BLOCK 27A)
FAR 52.212-5 Contract Terms and Conditions Required to Implement Statutes or Executive Orders—
(a) The Contractor shall comply with the following Federal Acquisition Regulation (FAR) clauses, which are incorporated in this contract by reference, to implement provisions of law or Executive orders applicable to acquisitions of commercial products and commercial services:
(1) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (Jan 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L. 113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).
(2) 52.204-23, Prohibition on Contracting for Hardware, Software, and Services Developed or Provided by Kaspersky Lab Covered Entities (Dec 2023) (Section 1634 of Pub. L. 115-91).
(3) 52.204-25, Prohibition on Contracting for Certain Telecommunications and Video Surveillance Services or Equipment. (Nov 2021) (Section 889(a)(1)(A) of Pub. L. 115-232).
(4) 52.209-10, Prohibition on Contracting with Inverted Domestic Corporations (Nov 2015).
(5) 52.232-40, Providing Accelerated Payments to Small Business Subcontractors (Mar 2023) ( 31 U.S.C. 3903 and 10 U.S.C. 3801).
(6) 52.233-3, Protest After Award (Aug 1996) (31 U.S.C.
This is the start of the file's text. The full file is on GovTribe.