RFQ-19KU2027Q0005- Diesel Generator Rental with ATS.docx
DOCX document 189 KB Posted
- Solicitation number
- 19KU2027Q0005
- Issued by
-
Department of State
About this file
This is a Request for Quotations (RFQ) for the rental, installation, and maintenance of two 500 kVA standby diesel generators with Automatic Transfer Switches (ATS) at the U.S. Embassy in Kuwait. The contract requires Caterpillar Model C15 generators or equivalent (Cummins or equal) meeting specified minimum salient characteristics including 500 kVA/400 kW at 0.8 power factor, 415/230V three-phase 50 Hz operation, weatherproof sound-attenuated enclosure with maximum 75 dBA at 7 meters, digital auto-start controller, and brushless alternator with automatic voltage regulator. The base contract period is one month commencing December 20, 2026, with four one-month option periods available subject to funds availability. Quotations must include one-time charges for commissioning/decommissioning and mobilization/demobilization, plus 10,000 liters of diesel fuel at contract start and up to 5,000 additional liters during the rental period, all priced in Kuwaiti Dinars (KWD). The contractor must supply a 5,000-liter fuel tank with 72-hour continuous operation capacity, install all power and control cables, perform load-bank testing for four hours including one hour at 100% rated load, and provide 24/7 emergency support with two-hour response time and 24-hour replacement unit capability.
Quotations are due December 8, 2026, at 10:00 AM Kuwait local time, with a mandatory site visit scheduled for November 24, 2026, at 11:00 AM. The Government will award to the lowest-priced, technically acceptable, and responsible contractor. Offerors must submit ten separate attachments including completed SF-1449, introduction with valid Kuwait commercial license, technical sections addressing business qualifications, past performance on at least two relevant projects within five years, qualified personnel qualifications, equipment availability confirmation, maintenance and emergency support capabilities, diesel fuel supply capability, and installation/performance plan, plus pricing. Quotations must remain valid for 30 days from submission deadline. All work must comply with local electrical codes, international standards (IEC 60364, ISO 8528, IEC 60947-6-1), and U.S. equivalents (NFPA 70, NFPA 110, UL 1008). The contractor is responsible for Defense Base Act insurance for covered employees, all permits and licenses, site preparation, preventive maintenance per manufacturer schedules, weekly no-load exercise runs, monthly inspections with written reports to the Contracting Officer's Representative, and compliance with Post security requirements and personnel security clearance procedures. This is an unrestricted acquisition issued by the Department of State for the American Embassy Kuwait General Services Office.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ-19KU2027Q0005- Diesel Generator Rental with ATS..pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Embassy
| GSO/Procurement |
| Kuwait City |
| November 18, 2026 |
Dear Prospective Quoters:
Subject: Request for Quotations number RFQ 19KU2027Q0005 - Rental, installation, and maintenance of Two (2) 500 kVA Standby Diesel Generators with Automatic Transfer Switches (ATS) – Caterpillar Model C15 or Equal
Enclosed is a Request for Quotations (RFQ) 19KU2027Q0005- Rental, installation, and maintenance of Two (2) a 500 kVA Standby Diesel Generator each equipped with Automatic Transfer Switch (ATS), Caterpillar Model C15 or Cummins or equal, meeting or exceeding the minimum salient characteristics specified in the Pricing Table and Section 4.1 of the Scope of Work (SOW), incorporated into the continuation of SF 1449. The requirement will be for one month with four one-month options to extend, subject to funds availability and Government’s best interest. If you would like to submit quotation, follow the instructions in Section 3 of the solicitation, complete the required portions of the attached document, and submit it to the address shown on Standard Form 1449 that follows this letter.
A site visit has been scheduled for Nov 24, 2026, at 11:00 AM Kuwait local time. For more information, please refer to page 46. Interested contractors are strongly encouraged to attend the scheduled site visit to inspect the premises prior to finalizing their proposals. It is the contractor’s sole responsibility to thoroughly assess the site during this visit. Any inaccuracies, omissions, or cost discrepancies in the submitted proposal resulting from failure to inspect the site shall be the contractor’s full responsibility.
1. Basis for Award The Government intends to award a fixed price one-month purchase order with four one-month options to the responsible, licensed contractor submitting an acceptable quotation at the lowest price. The Government intends to evaluate an award without discussion but reserves the right to conduct discussions in accordance with FAR 12.203 and 12.204 if determined to be in the Government’s best interest.
2. SAM Registration Note: Prospective offerors are strongly encouraged, though not required, to register in the System for Award Management (SAM) at https://www.sam.gov.
· Offerors with an active SAM registration need only provide their Unique Entity Identifier (UEI) number and are not required to complete the information 52.204-90 since relevant information is found in their SAM registration.
· Offerors without an active SAM registration must complete FAR 52.204-90, Offeror Identification, in Section 5, Representations and Certifications. This information must be updated annually if option years are included in the solicitation or award.
Offerors are strongly encouraged to maintain an active SAM account
For a quotation to be considered, you must also complete and submit the following:
1. SF-1449 (12, 17a, 24, 30a, 30b and 30c)
2. Section 1, Pricing (Completed pricing schedule, including unit prices and total price;
3. Section 5, Representations and Certifications
4. Additional information as required in Section 3 and/or in the solicitation
5. Proof of SAM Registration / Unique Entity ID, or if not, SAM registered, complete FAR 52.204-90, Offeror Identification, Failure to submit the required information may render the quotation non-compliant and ineligible for further consideration.
Direct any questions regarding this RFQ to Kuwait_Solicitation@state.gov no later than Nov 25, 2026. at 10:00 am Kuwait local time No questions will be accepted beyond this date. Please enter the title of your email as “Questions for RFQ: 19KU2027Q0005- Diesel Generator Rental with ATS.”
Submit your quote electronically by email to Kuwait_Solicitation@state.gov. Quotations are due by Dec 8, 2026, at 10:00 am Kuwait local time. No quotes will be accepted after this time. Please enter the title of your email as “Quote for RFQ: 19KU2027Q0005- Diesel Generator Rental with ATS.”
Sincerely,
| Jennifer S Bowmar |
| Contracting Officer |
TABLE OF CONTENTS
SECTION 1 - THE SCHEDULE
· SF 1449 cover sheet
· Continuation To SF-1449, RFQ Number 19KU2027Q0005 - Diesel Generator Rental with ATS Prices, Block 23
· Continuation To SF-1449, RFQ Number 19KU2027Q0005- Diesel Generator Rental with ATS, Schedule of Supplies/Services, Block 20 Description/Specifications/Work Statement
· Attachment 1: Crane
SECTION 2 - CONTRACT CLAUSES
· Contract Clauses
· Addendum to Contract Clauses - FAR and DOSAR Clauses not Prescribed in Part 12
SECTION 3 - SOLICITATION PROVISIONS
· Solicitation Provisions
· Addendum to Solicitation Provisions - FAR and DOSAR Provisions not Prescribed in Part 12
SECTION 4 - EVALUATION FACTORS
· Evaluation Factors
· Addendum to Evaluation Factors - FAR and DOSAR Provisions not Prescribed in Part 12
SECTION 5 - REPRESENTATIONS AND CERTIFICATIONS
· Offeror Representations and Certifications
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
| NOTE: OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30 |
| 1. REQUISITION NUMBER |
PR16381128
PAGE 1 OF
2. CONTRACT NO.
3. AWARD/EFFECTIVE
DATE
4. ORDER NUMBER
19KU
2027Q0005
5. SOLICITATION NUMBER
19KU2027Q0005
6. SOLICITATION ISSUE DATE
Nov 18, 2026
7. FOR SOLICITATION
INFORMATION CALL:
a. NAME Mohamad ELChami
b. TELEPHONE NUMBER (No collect calls) +965-2259-1216
8. OFFER DUE DATE/ LOCAL TIME Kuwait Dec 8, 2026 @ 10:00 am
| 9.ISSUED BY CODE: |
| 19KU20 |
| 10. THIS ACQUISITION IS |
| |X| UNRESTRICTED OR |
| |_| SET ASIDE: ____ % FOR: |
American Embassy Kuwait General Services Office Procurement Office.
| |_| SMALL BUSINESS |
| |_| WOMEN-OWNED SMALL BUSINESS |
|_| HUBZONE SMALL
BUSINESS
|_| (WOSB) ELLIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM NAICS:
|_|SERVICE-DISABLED
VETERAN-OWNED SMALL BUSINESS
|_| EDWOSB
| |_| 8 (A) |
| SIZE STANDARD: |
11. DELIVERY FOR FOB DESTINAT-
SECTION UNLESS BLOCK IS
MARKED
|X| SEE SCHEDULE
| 12. DISCOUNT TERMS |
| |_| 13a. THIS CONTRACT IS A RATED ORDER UNDER DEFENSE PRIORITIES AND ALLOCATIONS SYSTEM - DPAS (15 CFR 700) |
| 13b. RATING |
14. METHOD OF SOLICITATION
|X| RFQ Request for Quote |_| IFB Invitation for Bid |_| RFP Request for Proposal
| 15. DELIVER TO |
| CODE |
| 19KU20 |
| 16. ADMINISTERED BY |
| CODE |
| 19KU20 |
Kuwait_Solicitation@state.gov
AMERICAN EMBASSY, KUWAIT
GENERAL SERVICES OFFICE
MASJID AL AQSA STREET, BAYAN KUWAIT
17a. CONTRACTOR/
OFFERER
TELEPHONE NO.
CODE
FACILITY CODE
18a. PAYMENT WILL BE MADE BY Budget and Fiscal Office American Embassy Kuwait Email: KuwaitDBO@state.gov
| CODE |
| 19KU20 |
|_|17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN
OFFER
| 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK | |
| BELOW IS CHECKED | |_| SEE ADDENDUM |
| 19.ITEM NO. |
| 20.SCHEDULE OF SUPPLIES/SERVICES |
| 21.QUANTITY |
| 22.UNIT |
| 23.UNIT PRICE |
| 24.AMOUNT |
CLIN 0001
CLIN 0002
CLIN 0003
CLIN 0004
-Commissioning & decommissioning charges -Mobilization & demobilization charges -Diesel charges for 10,000 liters -Rental, installation, and maintenance of two (2) a 500 kVA Standby Diesel Generator with Automatic Transfer Switch for one month (Base period of performance)
Lot
Month
| 25. ACCOUNTING AND APPROPRIATION DATA |
| 26. TOTAL AWARD AMOUNT (For Govt. Use Only) |
| |X| 27a.SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. |
| |X| ARE |_| ARE NOT ATTACHED |
| |_| 27b.CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. |
| |_| ARE |_| ARE NOT ATTACHED |
| |X| 28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _1__ COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED HEREIN. |
| |_| 29. AWARD OF CONTRACT: REF. _________________ OFFER DATED ____________. YOUR OFFER ON SOLICITATION (BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE SET FORTH HEREIN, IS ACCEPTED AS TO ITEMS: |
| 30a. SIGNATURE OF OFFEROR/CONTRACTOR |
| 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) |
30b. NAME AND TITLE OF SIGNER (Type or print)
30c. DATE SIGNED
31b. NAME OF CONTRACTING OFFICER (Type or print)
31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
STANDARD FORM 1449 (REV. 11/2021)
Prescribed by GSA - FAR (48 CFR) 53.212
| 19.ITEM NO. |
| 20.SCHEDULE OF SUPPLIES/SERVICES |
| 21.QUANTITY |
| 22.UNIT |
| 23.UNIT PRICE |
| 24.AMOUNT |
| CLIN 0005 |
| -Option 1. Rental, Installation, and Maintenance of two (2) a |
500 kVA Standby Diesel Generator with Automatic Transfer Switch for one month
| 1 |
| 1 month |
| CLIN 0006 |
| -Option 2. Rental, Installation, and Maintenance of two (2) a |
500 kVA Standby Diesel Generator with Automatic Transfer Switch for one month
| 1 |
| 1 month |
| CLIN 0007 |
| -Option 3. Rental, Installation, and Maintenance of two (2) a 500 kVA Standby Diesel Generator with Automatic Transfer Switch for one month |
| 1 |
| 1 month |
| CLIN 0008 |
| -Option 4. Rental, Installation, and Maintenance of two (2) a |
500 kVA Standby Diesel Generator with Automatic Transfer Switch for one month
(Details as attached)
| 1 |
| 1 month |
32a. QUANTITY IN COLUMN 21 HAS BEEN
|_| RECEIVED |_| INSPECTED |_| ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED: _______________________________
32b. SIGNATURE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
| 32c. DATE |
| 32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT |
REPRESENTATIVE
| 32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE |
| 32f. TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE |
32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE
| 33. SHIP NUMBER |
| 34.VOUCHER NUMBER |
| 35. AMOUNT VERIFIED |
CORRECT FOR
| 36. PAYMENT |
| 37.CHECK NUMBER |
| |_| |
| PARTIAL |
| |_| |
| FINAL |
|_| COMPLETE |_| PARTIAL |_| FINAL
| STOCK RECORD (S/R) |
| 40. PAID BY |
38. S/R ACCOUNT NO.
39. S/R VOUCHER NO.
| 41.a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR PAYMENT |
| 42a. RECEIVED BY (Print) |
| 41b. SIGNATURE AND TITLE OF CERTIFYING OFFICER |
| 41C. DATE |
42b. RECEIVED AT (Location)
| 42c. DATE REC’D (YY/MM/DD) |
| 42d. TOTAL CONTAINERS |
STANDARD FORM 1449 (REV. Jan 2011) BACK
SECTION 1 - THE SCHEDULE
CONTINUATION TO SF-1449
RFQ NUMBER 19KU2027Q0005
Rental, Installation, and Maintenance of Two (2) a 500 kVA Standby Diesel Generator with Automatic Transfer Switch
PRICES, BLOCK 23
1. PERFORMANCE WORK STATEMENT
The purpose of this firm fixed price purchase order is for the rental, installation, and maintenance of two (2) a 500 kVA standby diesel generator each equipped with Automatic Transfer Switch (ATS) at U.S. Embassy Kuwait. The Contractor shall furnish, deliver, install, connect, test, commission, operate, maintain, and remove at the end of the contract the rented diesel generator sets. The set shall include a standby fuel tank that holds enough fuel for at least 72 hours (3 days) of continuous operation at maximum load, an ATS, and all power and control cabling needed to connect the generator to the residence's main isolator.
A. Contract Duration and Delivery Schedule:
1. Duration: The contract will be for one month with four one-month options.
2. Rental Start Date: The tentative start date for the base period shall commence December 20, 2026.
3. Delivery Requirement: The contractor must complete delivery of the required generators along with other related equipment to make sure they are operational from the start date of this rental.
B. The Government reserves the right to exercise any option period, if found to be in the best interest of the Government, subject to availability of funds.
C. In consideration of the Contractor's satisfactory performance of all services required under this contract, the Government shall pay the Contractor the fixed monthly rental rate per generator, as specified in the contract pricing schedule, together with applicable one-time charges. Additional diesel fuel supplied during the rental period shall be invoiced separately and paid based solely on the actual quantities ordered, delivered, and accepted by the Government, at the established contract unit price per liter, subject to the authorized contract quantities and funding limitations.
D. The Government will make payment in local currency. Invoices to be submitted at end of every month to process for payment.
2. Pricing
2.1 VALUE ADDED TAX. Value Added Tax (VAT) is not applicable to this contract and shall not be included in the CLIN rates or Invoices because the U.S. Embassy has a tax exemption certificate from the host government
2.2 The firm-fixed price shall include all direct and indirect costs necessary to perform the generator rental service, including labor, supervision, materials, equipment, overhead, profit, and all required insurance, including insurance requirement for employees assigned to this purchase order who are U.S. citizens, local National and direct hires and are subject to the Defense Base Act (DBA), the Contractor shall obtain and maintain Defense Base Act insurance in accordance with FAR 52.228-3, Workers' Compensation Insurance (Defense Base Act). To comply with DOSAR 652.228-71(b), the Contractor shall procure Defense Base Act (DBA) insurance directly from a Department of Labor (DOL) approved insurance provider. Information regarding approved DBA insurance carriers is available through the U.S. Department of Labor at: Web site at Longshore Authorized Carriers and Self-insured Employers | U.S. Department of Labor. All costs associated with DBA insurance shall be included in the firm-fixed prices for the base period and each option period.
2.3 The Contractor shall provide firm-fixed prices in Kuwaiti Dinars (KWD) for all Contract Line-Item Numbers (CLINs).
No additional compensation will be provided for increases in labor, material, transportation, shipping, insurance, registration, or any other associated costs, nor will the purchase order price be adjusted due to currency exchange rate fluctuations or the Contractor's failure to accurately estimate the costs of performance.
2.4 One-Time Charges
| Item No. |
| Description |
| QTY |
| Total Amount/KWD |
| CLIN 0001 |
| Commissioning & decommissioning charges |
| 1 Job |
| CLIN 0002 |
| Mobilization & demobilization charges |
| 1 Job |
| CLIN 0003 |
| Diesel charges for 10,000 liters |
| 1 Job |
2.5 Base Period (One Month) – Rental Monthly Charges – CLIN 0004
| Item No. |
| Description |
| QTY |
| Monthly Rental (KWD) |
CLIN 0004
The Government requires a Caterpillar Model C15 generator set, or Cummins or equal, meeting or exceeding the following minimum salient characteristics (Caterpillar model C15, 500kva/44kE, 415*230 v, 3 phase 50 Hz, 500rpm, in sound attenuated enclosure) The monthly lease charges shall include all items listed in this CLIN Required salient characteristics:
| Parameter | |
| Requirement |
| Rating |
| Minimum 500 kVA / 400 kW at 0.8 power factor, standby rating |
| Voltage / Phase |
| [415/230 V, 3-phase, 4-wire] |
| Frequency |
| [50 Hz] |
| Engine |
| Diesel, water-cooled, with electronic or mechanical governor (±0.5% frequency regulation or better) |
| Alternator |
| Brushless, self-excited, with automatic voltage regulator (AVR), ±1% voltage regulation or better |
| Enclosure |
| Weatherproof, sound-attenuated canopy, maximum [75 dBA at 7 meters] |
| Controller |
| Digital auto-start controller with display of voltage, current, frequency, kW, kVA, power factor, run hours, fuel level, oil pressure, and coolant temperature |
| Protection |
| Shutdown and alarm for low oil pressure, high coolant temperature, overspeed, over/under voltage, over/under frequency, overcurrent, short circuit, low fuel, and failure to start |
| Output breaker |
| Generator-mounted main circuit breaker sized to the generator rating |
| Starting |
| 12/24 V DC electric start, batteries with automatic battery charger |
| Condition |
| Equipment no more than [5] years old or under [10,000] run hours, in good working order |
Automatic Transfer Switch (ATS) Installation Rating: 3-pole or 4-pole (to match the site's neutral and earthing system), rated at least [800] A or the generator's full-load current plus 25%, whichever is greater.
| Fuel Tank 5,000L |
| 2 |
| 7 x 1C x 240 Sqmm Cable x 30 m |
| 1 set – 210m |
| 7 x 1C x 240 Sqmm Cable x 10 m |
| 2 sets – 140m |
Total Monthly Lease
The Contractor shall invoice diesel fuel supplied during the rental period separately from the monthly generator rental charges. The Government shall pay only for the actual quantities of diesel fuel ordered, delivered, and accepted, based on the contractually agreed unit price per liter and within the authorized contract limits.
| Item No |
| Description |
| Estimated Liters |
| Amount/KWD |
| 1 |
| Additional diesel fuel supply and refueling during the rental period |
| 5000 |
| ----------------- |
2.6 1st option period one (1) additional month rental charges - CLIN 5
| Item No. |
| Description |
| QTY |
| Monthly Rental (KWD) |
| CLIN 0005 |
| The Government requires a Caterpillar Model C15 generator set, or Cummins or equal, meeting or exceeding the following minimum salient characteristics (Caterpillar model C15, 500kva/44kE, 415*230 v, 3 phase 50 Hz, 500rpm, in sound attenuated enclosure) |
The monthly lease charges shall include all items listed in this CLIN Required salient characteristics:
| Parameter | |
| Requirement |
| Rating |
| Minimum 500 kVA / 400 kW at 0.8 power factor, standby rating |
| Voltage / Phase |
| [415/230 V, 3-phase, 4-wire] |
| Frequency |
| [50 Hz] |
| Engine |
| Diesel, water-cooled, with electronic or mechanical governor (±0.5% frequency regulation or better) |
| Alternator |
| Brushless, self-excited, with automatic voltage regulator (AVR), ±1% voltage regulation or better |
| Enclosure |
| Weatherproof, sound-attenuated canopy, maximum [75 dBA at 7 meters] |
| Controller |
| Digital auto-start controller with display of voltage, current, frequency, kW, kVA, power factor, run hours, fuel level, oil pressure, and coolant temperature |
| Protection |
| Shutdown and alarm for low oil pressure, high coolant temperature, overspeed, over/under voltage, over/under frequency, overcurrent, short circuit, low fuel, and failure to start |
| Output breaker |
| Generator-mounted main circuit breaker sized to the generator rating |
| Starting |
| 12/24 V DC electric start, batteries with automatic battery charger |
| Condition |
| Equipment no more than [5] years old or under [10,000] run hours, in good working order |
Automatic Transfer Switch (ATS) Installation Rating: 3-pole or 4-pole (to match the site's neutral and earthing system), rated at least [800] A or the generator's full-load current plus 25%, whichever is greater.
| Fuel Tank 5,000L |
| 2 |
| 7 x 1C x 240 Sqmm Cable x 30 m |
| 1 set – 210m |
| 7 x 1C x 240 Sqmm Cable x 10 m |
| 2 sets – 140m |
The Contractor shall invoice diesel fuel supplied during the rental period separately from the monthly generator rental charges. The Government shall pay only for the actual quantities of diesel fuel ordered, delivered, and accepted, based on the contractually agreed unit price per liter and within the authorized contract limits.
| Item No |
| Description |
| Estimated Liters |
| Amount/KWD |
| 1 |
| Additional diesel fuel supply and refueling during the rental period |
| 5000 |
| ----------------- |
2.7 2nd option period one (1) additional month rental charges – CLIN 6
| Item No. |
| Description |
| QTY |
| Monthly Rental (KWD) |
| CLIN 0006 |
| The Government requires a Caterpillar Model C15 generator set, or Cummins or equal, meeting or exceeding the following minimum salient characteristics (Caterpillar model C15, 500kva/44kE, 415*230 v, 3 phase 50 Hz, 500rpm, in sound attenuated enclosure) |
The monthly lease charges shall include all items listed in this CLIN Required salient characteristics:
| Parameter | |
| Requirement |
| Rating |
| Minimum 500 kVA / 400 kW at 0.8 power factor, standby rating |
| Voltage / Phase |
| [415/230 V, 3-phase, 4-wire] |
| Frequency |
| [50 Hz] |
| Engine |
| Diesel, water-cooled, with electronic or mechanical governor (±0.5% frequency regulation or better) |
| Alternator |
| Brushless, self-excited, with automatic voltage regulator (AVR), ±1% voltage regulation or better |
| Enclosure |
| Weatherproof, sound-attenuated canopy, maximum [75 dBA at 7 meters] |
| Controller |
| Digital auto-start controller with display of voltage, current, frequency, kW, kVA, power factor, run hours, fuel level, oil pressure, and coolant temperature |
| Protection |
| Shutdown and alarm for low oil pressure, high coolant temperature, overspeed, over/under voltage, over/under frequency, overcurrent, short circuit, low fuel, and failure to start |
| Output breaker |
| Generator-mounted main circuit breaker sized to the generator rating |
| Starting |
| 12/24 V DC electric start, batteries with automatic battery charger |
| Condition |
| Equipment no more than [5] years old or under [10,000] run hours, in good working order |
Automatic Transfer Switch (ATS) Installation Rating: 3-pole or 4-pole (to match the site's neutral and earthing system), rated at least [800] A or the generator's full-load current plus 25%, whichever is greater.
| Fuel Tank 5,000L |
| 2 |
| 7 x 1C x 240 Sqmm Cable x 30 m |
| 1 set – 210m |
| 7 x 1C x 240 Sqmm Cable x 10 m |
| 2 sets – 140m |
The Contractor shall invoice diesel fuel supplied during the rental period separately from the monthly generator rental charges. The Government shall pay only for the actual quantities of diesel fuel ordered, delivered, and accepted, based on the contractually agreed unit price per liter and within the authorized contract limits.
| Item No |
| Description |
| Estimated Liters |
| Amount/KWD |
| 1 |
| Additional diesel fuel supply and refueling during the rental period |
| 5000 |
| ----------------- |
2.8 3rd option period one (1) additional month rental charges – CLIN 7
| Item No. |
| Description |
| QTY |
| Monthly Rental (KWD) |
| CLIN 0007 |
| The Government requires a Caterpillar Model C15 generator set, or Cummins or equal, meeting or exceeding the following minimum salient characteristics (Caterpillar model C15, 500kva/44kE, 415*230 v, 3 phase 50 Hz, 500rpm, in sound attenuated enclosure) |
The monthly lease charges shall include all items listed in this CLIN Required salient characteristics:
| Parameter | |
| Requirement |
| Rating |
| Minimum 500 kVA / 400 kW at 0.8 power factor, standby rating |
| Voltage / Phase |
| [415/230 V, 3-phase, 4-wire] |
| Frequency |
| [50 Hz] |
| Engine |
| Diesel, water-cooled, with electronic or mechanical governor (±0.5% frequency regulation or better) |
| Alternator |
| Brushless, self-excited, with automatic voltage regulator (AVR), ±1% voltage regulation or better |
| Enclosure |
| Weatherproof, sound-attenuated canopy, maximum [75 dBA at 7 meters] |
| Controller |
| Digital auto-start controller with display of voltage, current, frequency, kW, kVA, power factor, run hours, fuel level, oil pressure, and coolant temperature |
| Protection |
| Shutdown and alarm for low oil pressure, high coolant temperature, overspeed, over/under voltage, over/under frequency, overcurrent, short circuit, low fuel, and failure to start |
| Output breaker |
| Generator-mounted main circuit breaker sized to the generator rating |
| Starting |
| 12/24 V DC electric start, batteries with automatic battery charger |
| Condition |
| Equipment no more than [5] years old or under [10,000] run hours, in good working order |
Automatic Transfer Switch (ATS) Installation Rating: 3-pole or 4-pole (to match the site's neutral and earthing system), rated at least [800] A or the generator's full-load current plus 25%, whichever is greater.
| Fuel Tank 5,000L |
| 2 |
| 7 x 1C x 240 Sqmm Cable x 30 m |
| 1 set – 210m |
| 7 x 1C x 240 Sqmm Cable x 10 m |
| 2 sets – 140m |
The Contractor shall invoice diesel fuel supplied during the rental period separately from the monthly generator rental charges. The Government shall pay only for the actual quantities of diesel fuel ordered, delivered, and accepted, based on the contractually agreed unit price per liter and within the authorized contract limits.
| Item No |
| Description |
| Estimated Liters |
| Amount/KWD |
| 1 |
| Additional diesel fuel supply and refueling during the rental period |
| 5000 |
| ----------------- |
2.9 4th option period one (1) additional month rental charges – CLIN 8
| Item No. |
| Description |
| QTY |
| Monthly Rental (KWD) |
| CLIN 0008 |
| The Government requires a Caterpillar Model C15 generator set, or Cummins or equal, meeting or exceeding the following minimum salient characteristics (Caterpillar model C15, 500kva/44kE, 415*230 v, 3 phase 50 Hz, 500rpm, in sound attenuated enclosure) |
The monthly lease charges shall include all items listed in this CLIN Required salient characteristics:
| Parameter | |
| Requirement |
| Rating |
| Minimum 500 kVA / 400 kW at 0.8 power factor, standby rating |
| Voltage / Phase |
| [415/230 V, 3-phase, 4-wire] |
| Frequency |
| [50 Hz] |
| Engine |
| Diesel, water-cooled, with electronic or mechanical governor (±0.5% frequency regulation or better) |
| Alternator |
| Brushless, self-excited, with automatic voltage regulator (AVR), ±1% voltage regulation or better |
| Enclosure |
| Weatherproof, sound-attenuated canopy, maximum [75 dBA at 7 meters] |
| Controller |
| Digital auto-start controller with display of voltage, current, frequency, kW, kVA, power factor, run hours, fuel level, oil pressure, and coolant temperature |
| Protection |
| Shutdown and alarm for low oil pressure, high coolant temperature, overspeed, over/under voltage, over/under frequency, overcurrent, short circuit, low fuel, and failure to start |
| Output breaker |
| Generator-mounted main circuit breaker sized to the generator rating |
| Starting |
| 12/24 V DC electric start, batteries with automatic battery charger |
| Condition |
| Equipment no more than [5] years old or under [10,000] run hours, in good working order |
Automatic Transfer Switch (ATS) Installation Rating: 3-pole or 4-pole (to match the site's neutral and earthing system), rated at least [800] A or the generator's full-load current plus 25%, whichever is greater.
| Fuel Tank 5,000L |
| 2 |
| 7 x 1C x 240 Sqmm Cable x 30 m |
| 1 set – 210m |
| 7 x 1C x 240 Sqmm Cable x 10 m |
| 2 sets – 140m |
The Contractor shall invoice diesel fuel supplied during the rental period separately from the monthly generator rental charges. The Government shall pay only for the actual quantities of diesel fuel ordered, delivered, and accepted, based on the contractually agreed unit price per liter and within the authorized contract limits.
| Item No |
| Description |
| Estimated Liters |
| Amount/KWD |
| 1 |
| Additional diesel fuel supply and refueling during the rental period |
| 5000 |
| ----------------- |
2.10 Grand Total Summary – Base Month and All Option Months
CLIN
Lease Period
Total Lease Price
Base Period of one month
1st option period of one additional month
2nd option period of one additional month
3rd option period of one additional month
4th option period of one additional month
Grand Total
CONTINUATION TO SF-1449
RFQ NUMBER 19KU2027Q0005
SCHEDULE OF SUPPLIES/SERVICES, BLOCK 20
DESCRIPTION/SPECIFICATIONS/PERFORMANCE WORK STATEMENT
Scope of Work: Rental, Installation, and Maintenance of two (2) a 500 kVA Standby Diesel Generator with Automatic Transfer Switch
1. Background The U.S. Government (USG) residence(s) at SDH draw power from the city grid. Grid outages disrupt operations and residents' safety and security. The USG needs a rented standby diesel generator. When the grid fails, the generator must start automatically and pick up the residence load through an Automatic Transfer Switch (ATS). When grid power returns, the ATS must transfer the load back to the grid.
2. Objective The Contractor shall furnish, deliver, install, connect, test, commission, operate, maintain, and remove at the end of the contract two (2) 500 kVA diesel generator sets equipped with ATS. The set shall include a standby fuel tank that holds enough fuel for at least 72 hours (3 days) of continuous operation at maximum load, an ATS, and all power and control cabling needed to connect the generator to the residence's main isolator.
3. Scope of Work The Contractor shall provide all labor, supervision, equipment, materials, transportation, tools, permits, and consumables needed to:
1. Survey the site and confirm the electrical configuration before mobilizing.
2. Deliver and place the generator set, fuel tank, and ATS at the location the COR approves.
3. Supply and install all power cables, control wiring, terminations, and cable protection between the generator, the ATS, and the main isolator.
4. Connect the generator output cables to the main isolator through the ATS.
5. Test and commission the complete system.
6. Operate, maintain, and repair the equipment for the full rental period.
7. Disconnect, remove, demobilize all equipment at contract end and restore the site to its original condition.
4. Technical Requirements
4.1 Generator Set. The Government requires a Caterpillar Model C15 generator set, or Cummins or equal, meeting or exceeding the following minimum salient characteristics: quotations offering products other than the specified Caterpillar model shall clearly identify the manufacturer, brand, model number, and country of manufacture and include technical specifications, manufacturer data sheets, and supporting documentation demonstrating compliance with all stated salient characteristics.
The Government will consider equivalent generator models that meet or exceed the specified minimum technical and performance requirements. Failure to demonstrate compliance with the salient characteristics may result in the quotation being determined technically unacceptable. The generator offered shall be manufactured by an established generator manufacturer and comply with applicable internationally recognized technical, electrical, safety, and performance standards, including relevant ISO and IEC standards. The offeror shall provide manufacturer documentation demonstrating compliance with the specified salient characteristics.
Evaluation: An equal product must satisfy the identified salient characteristics; it need not duplicate every feature of the Caterpillar C15 or Cummins
| Parameter |
| Requirement |
| Rating |
| Minimum 500 kVA / 400 kW at 0.8 power factor, standby rating |
| Voltage / Phase |
| [415/230 V, 3-phase, 4-wire] |
| Frequency |
| [50 Hz] |
| Engine |
| Diesel, water-cooled, with electronic or mechanical governor (±0.5% frequency regulation or better) |
| Alternator |
| Brushless, self-excited, with automatic voltage regulator (AVR), ±1% voltage regulation or better |
| Enclosure |
| Weatherproof, sound-attenuated canopy, maximum [75 dBA at 7 meters] |
| Controller |
| Digital auto-start controller with display of voltage, current, frequency, kW, kVA, power factor, run hours, fuel level, oil pressure, and coolant temperature |
| Protection |
| Shutdown and alarm for low oil pressure, high coolant temperature, overspeed, over/under voltage, over/under frequency, overcurrent, short circuit, low fuel, and failure to start |
| Output breaker |
| Generator-mounted main circuit breaker sized to the generator rating |
| Starting |
| 12/24 V DC electric start, batteries with automatic battery charger |
| Condition |
| Equipment no more than [5] years old or under [10,000] run hours, in good working order |
4.2 Standby Diesel Fuel Tank and Storage
1. The Contractor shall provide a fuel tank (base tank, external bulk tank, or both) with usable capacity for a minimum of 72 hours of continuous operation at 100% rated load.
2. The Contractor shall size the tank from the manufacturer's published full-load fuel consumption rate and submit the calculation with its proposal. (For planning only: a 500 kVA set typically consumes roughly 100–115 liters per hour at full load, which works out to about 7,200–8,300 liters over 72 hours. The Contractor's manufacturer data governs.)
3. The tank shall include a fuel level gauge, low-fuel alarm tied to the generator controller, vent, lockable fill cap, and drain valve.
4. Fuel lines between the bulk tank and the generator shall be rated for diesel, protected from physical damage, and leak-free.
5. Fuel Supply and Refueling: The Contractor shall be responsible for the supply and delivery of an initial 10,000 liters of diesel fuel at the commencement of the rental period, as a one-time charge, including filling the generator fuel tanks.
During the rental period, the Contractor shall also be responsible for supplying and delivering up to an additional 5,000 liters of diesel fuel, including refueling services, as required to maintain uninterrupted generator operations.
The initial 10,000 liters shall be invoiced separately as a one-time charge. Any additional diesel fuel supplied during the rental period shall be invoiced separately based on the actual quantities delivered and accepted by the Government, at the contractually agreed unit price per liter, not to exceed 5,000 additional liters without prior written authorization from the Contracting Officer.
The Contractor shall monitor fuel levels and coordinate timely refueling to maintain the generator fuel tanks at no less than 75% of their capacity throughout the rental period, subject to the contracted fuel quantities."
6. The contractor is responsible to top-up diesel as and when required.
4.3 Automatic Transfer Switch (ATS)
1. Rating: 3-pole or 4-pole (to match the site's neutral and earthing system), rated at least [800] A or the generator's full-load current plus 25%, whichever is greater.
2. Operation sequence:
· The ATS monitors city grid voltage and frequency on all phases continuously.
· On grid failure or phase loss, the ATS sends a start signal to the generator after an adjustable delay (0–10 seconds).
· Once generator voltage and frequency stabilize, the ATS transfers the load to the generator. Total time from outage to transfer shall not exceed [15] seconds.
· When grid power returns and stays stable for an adjustable period (default 5 minutes), the ATS transfers the load back to the grid.
· The generator then runs unloaded through an adjustable cool-down period (default 5 minutes) and shuts down automatically.
3. Interlocking: Mechanical and electrical interlocks that prevent the grid and generator from ever connecting to the load at the same time (no backfeed to the city grid).
4. Controls: Auto/Manual/Off selector, manual override, source-available and source-connected indicators, and an exercise timer for scheduled test runs.
5. Enclosure: Minimum IP54 if installed indoors, IP65 if outdoors, lockable.
4.4 Cables and Connections
1. The Contractor shall supply and install copper power cables, sized for the generator's full-load current plus at least 25% margin, with allowance for voltage drop (maximum 3%) over the actual route length.
2. Cables shall be armored or installed in conduit/cable tray and protected from vehicles, foot traffic, weather, and UV exposure. Cable crossings at walkways or driveways shall use rated cable protectors or buried ducts.
3. The Contractor shall terminate cables with properly sized lugs, glands, and phase identification.
4. The Contractor shall connect the generator output cables to the residence's main isolator through the ATS. The Contractor shall coordinate the shutdown of the main supply with the COR and Facility Manager at least [48] hours in advance and keep the outage to a minimum.
5. The Contractor shall install control wiring between the ATS and the generator controller for the remote start/stop signal.
4.5 Earthing and Bonding
The Contractor shall earth the generator frame, neutral (per the site's earthing system), fuel tank, and ATS enclosure. Earth resistance shall not exceed [5] ohms. The Contractor shall bond the system to the existing building earth where required.
4.6 Codes and Standards
All work shall comply with local electrical codes and with the applicable international standards (e.g., IEC 60364, ISO 8528, IEC 60947-6-1 for ATS) or the U.S. equivalents (NFPA 70, NFPA 110, UL 1008 for ATS), whichever are more stringent. All work shall also comply with Department of State and Bureau of Overseas Buildings Operations (OBO) facility requirements as directed by the COR.
5. Site Preparation and Installation
1. The Contractor shall place the generator on a level, stable base (concrete pad or steel skid) that the COR approves.
2. Generator location shall provide adequate ventilation and exhaust discharge away from windows, doors, air intakes, and occupied areas.
3. The Contractor shall maintain clearance around the unit for maintenance access and refueling vehicles.
4. The Contractor shall provide fire extinguishers (minimum one 9 kg dry chemical or CO₂) at the generator and fuel tank.
6. Testing and Commissioning
The Contractor shall perform the following tests:
1. Insulation resistance test on all new cables.
2. Phase rotation checks to confirm the generator and grid rotation match.
3. Load bank test: 4 hours total, including at least 1 hour at 100% rated load, recording voltage, frequency, current, and temperatures every 15 minutes.
4. ATS functional test: Simulate grid failure by opening the utility supply, and verify auto-start, transfer time, retransfer, cool-down, and shutdown.
5. Protection and alarm test: Verify that all shutdowns and alarms work.
6. Earth resistance test.
The Contractor shall submit a signed commissioning report. The USG will issue acceptance only after the system passes all tests.
7. Operation and Maintenance During the Rental Period
1. Preventive maintenance: The Contractor shall service the equipment according to the manufacturer's schedule (oil, filters, coolant, belts, batteries) at no extra cost.
2. Weekly no-load run: Automatic exercise of [15–30] minutes per week, logged.
3. Monthly inspection: Visual inspection, fluid levels, battery condition, fuel level, leak check, and ATS check, with a written report to the COR.
4. Emergency response: The Contractor shall provide a 24/7 hotline and arrive on site within [2] hours of a call. If the generator cannot be repaired within [8] hours, the Contractor shall supply a replacement unit of equal or greater capacity within [24] hours at no extra cost.
5. Run-hour and fuel logs: The Contractor shall keep these logs and submit them to the COR monthly.
8. Safety and Environmental Requirements
1. The Contractor shall follow lockout/tagout procedures for all electrical work.
2. Only qualified, licensed electricians shall perform connection work.
3. Personnel shall wear appropriate PPE.
4. The Contractor shall prevent fuel and oil spills. It shall keep a spill kit on site, clean up any spills immediately at its own cost, and dispose of waste oil, filters, and contaminated materials in line with local environmental regulations.
5. The Contractor shall report all accidents, injuries, and spills to the COR immediately.
9. Security and Access
1. Contractor personnel shall comply with Post's security and escort requirements and submit personnel information for clearance working days before site access.
2. Work at the residence shall take place only during hours the COR approves, with advance coordination with the residents.
10. ACCESS TO GOVERNMENT BUILDINGS AND STANDARDS OF CONDUCT
10.1 General. The Contractor shall designate a representative who shall supervise the Contractor's mechanics and be the Contractor's liaison with the U.S. Embassy/Consulate. The Contractor's employees shall be on-site only for contractual duties and not for any other business or purposes.
10.2 Personnel Security. The Government reserves the right to deny access to U.S owned and U.S.-operated facilities to any individual. The Contractor shall provide the names, biographic data and police clearance on all Contractor personnel who shall be used on this contract prior to their utilization. The Government shall issue identity cards to approved Contractor personnel, each of whom shall display his/her card(s) on the uniform at all times while on Government property or while on duty at private residences serviced under this contract. These identity cards are the property of the Government. The Contractor shall return all identity cards when the contract is completed, when a Contractor’s employee leaves this contract, or at the request of the Government.
10.3 Standards of Conduct
10.3.1 General. The Contractor shall maintain satisfactory standards of employee competency, conduct, cleanliness, appearance and integrity and shall be responsible for taking such disciplinary action with respect to employees as may be necessary. Each Contractor employee shall adhere to standards of conduct that reflect credit on themselves, their employer, and the United States Government. The Government reserves the right to direct the Contractor to remove an employee from the worksite for failure to comply with the standards of conduct. The Contractor shall immediately replace such an employee to maintain continuity of services at no additional cost to the Government.
10.3.2 Uniforms and Personal Equipment. The Contractor's employees shall wear clean, neat and complete uniforms when on duty. All employees shall wear uniforms approved by the Contracting Officer's Representative (COR). The Contractor shall provide, to each employee and supervisor, uniforms and personal equipment. The Contractor shall be responsible for the cost of purchasing, cleaning, pressing, and repair of the uniforms.
10.3.3 Neglect of duties shall not be condoned. This includes sleeping while on duty, unreasonable delays or failures to carry out assigned tasks, conducting personal affairs during duty hours and refusing to render assistance or cooperate in upholding the integrity of the worksite security.
10.3.4 The Contractor shall not condone disorderly conduct, use of abusive or offensive language, quarreling, and intimidation by words, actions, or fighting. Also included is participation in disruptive activities that interfere with normal and efficient Government operations.
10.3.5 Intoxicants and Narcotics. The Contractor shall not allow its employees while on duty to possess, sell, consume, or be under the influence of intoxicants, drugs or substances which produce similar effects.
10.3.6 Criminal Actions. Contractor employees may be subject to criminal actions as allowed by law in certain circumstances. These circumstances include but are not limited to the following actions: falsification or unlawful concealment, removal, mutilation, or destruction of any official documents or records or concealment of material facts by willful omission from official documents or records; unauthorized use of Government property, theft, vandalism, or immoral conduct; unethical or improper use of official authority or credentials; security violations; organizing or participating in gambling in any form; and misuse of weapons.
10.3.7 Key Control. The Contractor shall receive, secure, issue and account for any keys issued for access to buildings, offices, equipment, gates, or other areas, for the purposes of this contract. Keys shall not be duplicated without the COR's approval. Where the Government determines that the Contractor or its agents have duplicated a key without permission of the COR, the Contractor shall remove the individual(s) responsible from performing work under the contract. If the Contractor has lost any such keys, the Contractor shall immediately notify the COR. In either event, the Contractor shall reimburse the Government for the cost of rekeying that portion of the system so compromised.
11. Insurance Requirement
11.1 Personal Injury, Property Loss or Damage (Liability). The Contractor assumes absolute responsibility and liability for any and all personal injuries or death and property damage or losses suffered due to negligence of the Contractor's personnel in the performance of this contract
The Contractor's assumption of absolute liability is independent of any insurance policies.
Insurance. The Contractor, at its own expense, shall provide and maintain during the entire period of performance of this contract, whatever insurance is legally necessary. The Contractor shall carry the following minimum insurance:
(1) BODILY INJURY, ON OR OFF THE SITE, IN U.S. DOLLARS
| Per Occurrence |
| US$ 10,000 |
| Cumulative |
| US$ 10,000 |
(2) PROPERTY DAMAGE, ON OR OFF THE SITE, IN U.S. DOLLARS
| Per Occurrence |
| US$ 30,000 |
| Cumulative |
| US$ 30,000 |
11.2 Worker's Compensation Insurance. The Contractor agrees to provide all employees with worker's compensation benefits as required by the laws of either the country in which the employees are working or the employee's native country, whichever offers greater benefits, following FAR 52.228-3.
12.0 PERMITS
The Contractor shall maintain in full force and affect all permits, licenses, and appointments required for the prosecution of work under this contract at no additional cost to the Government. The Contractor shall obtain these permits, licenses, and appointments in compliance with host country laws.
13.0 LOCAL LAW REGISTRATION
If the local law or decree requires that one or both parties to the contract register the contract with the designated authorities to insure compliance with this law or decree, the entire burden of this registration shall rest upon the Contractor. Any local or other taxes which may be assessed against the contract shall be payable by the Contractor without Government reimbursement.
14. QUALITY ASSURANCE AND SURVEILLANCE PLAN (QASP)
14.1 This plan provides an effective method to promote satisfactory contractor performance. The QASP provides a method for the Contracting Officer's Representative (COR) to monitor Contractor performance, advise the Contractor of unsatisfactory performance, and notify the Contracting Officer of continued unsatisfactory performance. The Contractor, not the Government, is responsible for management and quality control to meet the terms of the contract. The role of the Government is to monitor quality to ensure that contract standards are achieved.
| Performance Objective |
| Scope of Work Para |
| Performance Threshold |
Services.
Performs all services set forth in the scope of work.
All.
All required services are performed and no more than one (1) customer complaint is received per month.
14.2 Surveillance. The COR will receive and document all complaints from Government personnel regarding the services provided. If appropriate, the COR will send the complaints to the Contractor for corrective action.
14.3 Standard. The performance standard is that the Government receives no more than one (1) customer complaint per month. The COR shall notify the Contracting Officer of the complaints so that the Contracting Officer may take appropriate action to enforce the inspection clause (FAR 52.212-4, Contract Terms and Conditions-Commercial Items), if any of the services exceed the standard.
14.4. Procedures.
14.4.1 If any Government personnel observe unacceptable services, either incomplete work or required services not being performed they should immediately contact the COR.
14.4.2 The COR will complete appropriate documentation to record the complaint.
14.4.3 If the COR determines the complaint is invalid, the COR will advise the complainant. The COR will retain the annotated copy of the written complaint for his/her files.
14.4.4 If the COR determines the complaint is valid, the COR will inform the Contractor and give the Contractor additional time to correct the defect, if additional time is available. The COR shall determine how much time is reasonable.
14.4.5 The COR shall, as a minimum, orally notify the Contractor of any valid complaints.
14.4.6 If the Contractor disagrees with the complaint after investigation of the site and challenges the validity of the complaint, the Contractor will notify the COR. The COR will review the matter to determine the validity of the complaint.
14.4.7 The COR will consider complaints as resolved unless notified otherwise by the complainant.
14.4.8 Repeat customer complaints are not permitted for any services. If a repeat customer complaint is received for the same deficiency during the service period, the COR will contact the Contracting Officer for appropriate action under the Inspection clause
Attachment 1 – Crane
U.S. Embassy-Kuwait-POSHO Office
CRANE OPERATION REQUIREMENTS AND SAFETY GUIDELINES
All contractors and vendors intending to provide crane services within the U.S. Embassy compound or on Embassy property in Kuwait must comply with the following minimum documentation, operational, and safety requirements.
1. Required Documentation Prior to the commencement of any crane operation, the contractor shall submit the following documents for review and recordkeeping:
· Valid crane inspection and load testing reports/certificates.
· Proof of qualification and competency of the crane operator.
· Proof of qualification of personnel assigned to rigging activities, as applicable.
· A lift plan and job-specific safety plan outlining the proposed crane operation.
2. Crane Access and Site Safety Requirements The contractor shall ensure that the following requirements are strictly observed during crane operations:
· Crane Access: The crane must enter the Embassy compound through the designated back gate. Entry through the front gate is not permitted.
· Ground Escort: At least one designated escort shall be available on the ground throughout the crane operation. The escort shall guide the crane along the approved travel route and alert pedestrians and other personnel to remain clear of the crane's swing radius and load-handling area.
· Barricades and Warning Devices: The contractor shall provide all necessary barricades, warning tape, traffic cones, and appropriate signage to restrict unauthorized access to the crane's swing area, load-handling area, and general work zone.
· Pedestrian and Vehicle Control: The contractor shall ensure that pedestrians and vehicles are safely diverted away from the crane's operating and lifting areas.
3. POSHO Coordination and Prior Approval In accordance with Department of State Office of Building Operations (OBO) and Safety, Health, and Environmental Management (SHEM) guidelines, all crane rentals and operations within the Embassy compound or on Embassy property must be coordinated with the Post Occupational Safety and Health Officer (POSHO) Office before the crane is rented or mobilized.
The requesting office shall notify the POSHO Office of the proposed crane operation and provide the following information:
• Purpose and Scope of Work (SOW): A brief description of the work to be performed, including the reason for requiring a crane.
• Lift Plan: A detailed description of the proposed lifting operation, including the lifting sequence and equipment to be used.
• Date and Location: The proposed date, time, and exact location of the crane operation.
• Crane Capacity: The required crane capacity and specifications.
• Load Information: The estimated weight, dimensions, and nature of the load to be lifted or relocated.
3.1 Lift Plan and Safety Requirements
The contractor shall submit a comprehensive lift plan addressing, at a minimum, the following:
• Engineering controls and relevant calculations to demonstrate that the crane and associated lifting equipment are suitable for the proposed operation.
• A site-specific safety plan identifying potential hazards and corresponding mitigation measures.
• Traffic management and access control arrangements, including proposed barriers for vehicles and pedestrians.
• Fall protection and other applicable personal protective equipment (PPE) requirements.
• Wind speed, weather conditions, and other environmental factors…
This is the start of the file's text. The full file is on GovTribe.