19BK8025Q0002_ATTACHMENT 2 - Bill of Quantity.xlsx

XLSX spreadsheet 26 KB Posted

Attached to
Construction Services - Purchase and Installation of HVAC Equipment
Solicitation number
19BK8025Q0002
Issued by

About this file

This document is a Bill of Quantity (BOQ) for a Request for Quotations (RFQ) for HVAC equipment purchase and installation at the U.S. Embassy in Sarajevo, Bosnia and Herzegovina. The detailed spreadsheet outlines three separate Inverter VRF (Variable Refrigerant Flow) system installations for different embassy locations: SCAC-Loading dock, UTL-Switchgear room, and UTL-Pump room. Each system requires outdoor and indoor units with specific technical specifications, including heating and cooling capacities (minimum 22kW/25kW), temperature ranges (-15°C to 40°C), and specific electrical and noise level requirements.

The solicitation is issued by the Department of State, with quotations due by September 12, 2025, at 2:00 p.m. local time. The government reserves the right to award the contract for all three HVAC components or selectively for one or two components. Submission options include electronic submission to specified email addresses or sealed envelope delivery. The procurement follows a lowest-price, technically acceptable approach, with potential award without further discussions. The BOQ includes additional line items for mobilization, documentation handover, and demobilization, with a 17% VAT applied to the total cost.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BOM-HVAC

ATTACHMENT 2 - BILL OF QUANTITY

U.S. EMBASSY SARAJEVO - REQUEST FOR QUOTATIONS No.: 19BK8025Q0002
PURCHASE AND INSTALLATION OF HVAC EQUIPMENT
No.ITEM DESCRIPTIONUNITQTYUNIT PRICETOTAL

Delivery and installation of the specified equipment, materials, and accessories:

HVAC SYSTEMS

1SCAC-Loading dock
Inverter VRF system , consisting of following items:
1.1- Outdoor unit (ODU), casing with corrosion resistant color, friendly enviroment refrigerant ( R410, R407, R22 ) for following capacytiespcs1[$BAM] 0.00
Heating capacity min.- 22kw
Cooling capacity min - 25kw
Compressor type - scroll
Temperature range between -15C / 40C or broader
Noise level mode up to 76dB
Air flow min 9000m3/h
The size of the unit so that it can be installed without major structural changes and displacement of the existing equipment
1.2Indoor unit,The duct type, compatible with the existing duct installation,pcs1[$BAM] 0.00
Power - 380-415V, 3Phase, 50hz
Heating capacity min.- 22kw
Cooling capacity min - 25kw
Air flow- min 2900m3/h
Temperature range between -15C / 40C or broader
Sound pressure level up to 45dB
The size of the unit so that it can be installed without major structural changes and displacement of the existing equipment
1.3Standard wired remote controller, genuine manufacturer type, manual and auto mode with programing 7 dayspcs1[$BAM] 0.00
1.4Communication cable for interconnection between outdoor and indoor unitsm'20[$BAM] 0.00
1.5Outdoor unit mounting kit consisting of H-beam supports, M10 anchor bolts , anti vibration cushion padsset1[$BAM] 0.00
1.6Indoor unit mounting kit an connection consisting all adapters and materials for reliable and long-lasting connection with existing air ductsset1[$BAM] 0.00
1.7Miscelanious- Small material for repairing any damage to existing thermal insulation, waterproofing, paint, etc.set1[$BAM] 0.00
1.8Flexible drain hose, with pipe connecting accessories, recommended by manufacturerSet3[$BAM] 0.00
1.9Filling of copper pipe lines with nitrogen gas and checking for tightness.Lump Sum3[$BAM] 0.00
1.10Evacuation of the pipe lines and filling with required refrigerant according to the manufacturers recommendations.Lump Sum3[$BAM] 0.00
1.11Electrical work
1.11.1Connect new outdoor units to the power supply network. Use existing installationsLump Sum1[$BAM] 0.00
1.11.2Electrical cable for connecting the outdoor and indoor units according to the equipment manufacturer's specifications. use existing conduitsm30[$BAM] 0.00
1.11.3Electrical cable for connecting the indoor units and thermostat according to the equipment manufacturer's specifications. use existing conduitsm30[$BAM] 0.00
Subtotal:[$BAM] 0.00
2UTL - Switchgear room
Inverter VRF system , consisting of following items:
2.1- Outdoor unit (ODU), casing with corrosion resistant color, friendly enviroment refrigerant ( R410, R407, R22 ) for following capacytiespcs1[$BAM] 0.00
Heating capacity min.- 22kw
Cooling capacity min - 25kw
Compressor type - scroll
Temperature range between -15C / 40C or broader
Sound pressure night mode up to 45dB
Noise level mode up to 76dB
Air flow min 9000m3/h
The size of the unit so that it can be installed without major structural changes and displacement of the existing equipment
2.2Indoor unit,The duct type, compatible with the existing duct installation,pcs1[$BAM] 0.00
Power - 380-415V, 3Phase, 50hz
Heating capacity min.- 22kw
Cooling capacity min - 25kw
Air flow- min 2900m3/h
Temperature range between -15C / 40C or broader
Sound pressure level up to 45dB
The size of the unit so that it can be installed without major structural changes and displacement of the existing equipment
2.3Standard wired remote controller, genuine manufacturer type, manual and auto mode with programing 7 dayspcs1[$BAM] 0.00
2.4- communication cable for interconnection between outdoor and indoor unitsm'20[$BAM] 0.00
2.5Otdoor unit mounting kit consisting of H-beam supports, M10 anchor bolts , anti vibration cushion padsset1[$BAM] 0.00
2.6Indoor unit mounting kit an connection consisting all adapters and materials for reliable and long-lasting connection with existing air ductsset1[$BAM] 0.00
2.7Miscelanious- Small material for repairing any damage to existing thermal insulation, waterproofing, paint, etc.set1[$BAM] 0.00
2.8Flexible drain hose, with pipe connecting accessories, recommended by manufacturerSet3[$BAM] 0.00
2.9Filling of copper pipe lines with nitrogen gas and checking for tightness.Lump Sum3[$BAM] 0.00
2.10Evacuation of the pipe lines and filling with required refrigerant according to the manufacturers recommendations.Lump Sum3[$BAM] 0.00
2.11Electrical work
2.11.1Connect new outdoor units to the power supply network. Use existing installationsLump Sum1[$BAM] 0.00
2.11.2Electrical cable for connecting the outdoor and indoor units according to the equipment manufacturer's specifications. use existing conduitsm30[$BAM] 0.00
2.11.3Electrical cable for connecting the indoor units and thermostat according to the equipment manufacturer's specifications. use existing conduitsm30[$BAM] 0.00
Subtotal:[$BAM] 0.00
3UTL - Pump room
Inverter VRF system , consisting of following items:
3.1- Outdoor unit (ODU), casing with corrosion resistant color, friendly enviroment refrigerant ( R410, R407, R22 ) for following capacytiespcs1[$BAM] 0.00
Heating capacity min.- 22kw
Cooling capacity min - 25kw
Compressor type - scroll
Temperature range between -15C / 40C or broader
Sound pressure night mode up to 45dB
Noise level mode up to 76dB
Air flow min 9000m3/h
The size of the unit so that it can be installed without major structural changes and displacement of the existing equipment
3.2Indoor unit,The duct type, compatible with the existing duct installation,pcs1[$BAM] 0.00
Power - 380-415V, 3Phase, 50hz
Heating capacity min.- 22kw
Cooling capacity min - 25kw
Air flow- min 2900m3/h
Temperature range between -15C / 40C or broader
Sound pressure level up to 45dB
The size of the unit so that it can be installed without major structural changes and displacement of the existing equipment
3.3Standard wired remote controller, genuine manufacturer type, manual and auto mode with programing 7 dayspcs1[$BAM] 0.00
3.4Communication cable for interconnection between outdoor and indoor unitsm'20[$BAM] 0.00
3.5Otdoor unit mounting kit consisting of H-beam supports, M10 anchor bolts , anti vibration cushion padsset1[$BAM] 0.00
3.6Indoor unit mounting kit an connection consisting all adapters and materials for reliable and long-lasting connection with existing air ductsset1[$BAM] 0.00
3.7Miscelanious- Small material for repairing any damage to existing thermal insulation, waterproofing, paint, etc.set1[$BAM] 0.00
3.8Flexible drain hose, with pipe connecting accessories, recommended by manufacturerSet3[$BAM] 0.00
3.9Filling of copper pipe lines with nitrogen gas and checking for tightness.Lump Sum3[$BAM] 0.00
3.10Evacuation of the pipe lines and filling with required refrigerant according to the manufacturers recommendations.Lump Sum3[$BAM] 0.00
3.11Electrical work
3.11.1Connect new outdoor units to the power supply network. Use existing installationsLump Sum1[$BAM] 0.00
3.11.2Electrical cable for connecting the outdoor and indoor units according to the equipment manufacturer's specifications. use existing conduitsm30[$BAM] 0.00
3.11.3Electrical cable for connecting the indoor units and thermostat according to the equipment manufacturer's specifications. use existing conduitsm30[$BAM] 0.00
Subtotal:[$BAM] 0.00
4Other works
4.1Mobilization of the construction list with delivery of materialsLump Sum1[$BAM] 0.00
4.2Documentation handover - operating instructions, user manuals, maintenance plan, equipment certificates and guarantee lists.Lump Sum1[$BAM] 0.00
4.3Demobilization of the construction site, final cleaning and site handoverLump Sum1[$BAM] 0.00
Subtotal:[$BAM] 0.00
SUMMARY

HVAC SYSTEMS

1 SCAC-Loading dock [$BAM] 0.00

2 UTL - Switchgear room [$BAM] 0.00

3 UTL - Pump room [$BAM] 0.00

4 OTHER WORKS [$BAM] 0.00

SUBTOTAL (1 + 2 + 3 + 4)[$BAM] 0.00
VAT 17%:[$BAM] 0.00
GRAND TOTAL INCL. 17% VAT:[$BAM] 0.00