17204fdc-6e80-45f6-bf57-b24f01044199.pdf
PDF 1 MB Posted
- Attached to
- 408 DAMON ST. - DEMOLITION
- Solicitation number
- 2025-DEPARTMENT-024
- Issued by
- Kalamazoo County, Huntington Woods City, Michigan
About this file
This document is an asbestos and hazardous materials inspection report prepared by Red Cedar Consulting for the City of Jackson, Michigan, regarding the property located at 408 Damon St. The inspection was conducted on November 6, 2024, to comply with United States Environmental Protection Agency (USEPA) and Occupational Safety and Health Administration (OSHA) regulations for demolition and renovation. The report details a comprehensive survey of the 979 square foot residential building constructed in 1923, which includes a concrete basement and two aboveground floors with fire damage.
The inspection identified several asbestos-containing materials (ACM) requiring abatement prior to demolition, including roof tar (4 in. x 8 lin. ft.), Transite siding (1,820 sq. ft.), floor tiles in Bedroom 1 (100 sq. ft.), and friable HVAC duct wrap in the basement (12 sq. ft. on register boots and 25 lin. ft. of ductwork). The report provides detailed laboratory analysis results from APEX Research Inc., confirming the presence of chrysotile asbestos in some materials. Red Cedar Consulting recommends that all identified asbestos-containing materials be properly removed by a certified asbestos abatement contractor following OSHA and USEPA regulations, with specific attention to friable materials that must be abated before any renovation or demolition activities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 408_Damon-_Water_Sewer_Card.pdf | ||
| 408_Damon_St.-_Demolition_Special_Conditions.docx | DOCX document | |
| 408_Damon_St_-_DEMOLITION_-_CDBG.docx | DOCX document | |
| 408_Damon_St_-_DEMOLITION_-_CDBG.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P.O. Box 13216 Lansing, MI 48901 Phone: 888.449.4566 Fax: 888.448.8739 www.redcedarconsulting.net
December 11, 2024
Mr. Brian Taylor City of Jackson Community Development Department Jackson, MI 49202
RE: Asbestos Containing Material and Hazardous Materials Inspection 408 Damon St. Jackson, MI 49203 Parcel ID: 5213500000
Dear Mr. Taylor:
Red Cedar Consulting has completed an asbestos-containing material (ACM) and hazardous materials inspection at 408 Damon St. Jackson, Michigan (Subject Property). This inspection was completed at the request of the City of Jackson to comply with the United States Environmental Protection Agency (USEPA) requirements for demolition and renovation set forth under the National Emissions Standards for Hazardous Air Pollutants (NESHAP, 40 CFR Part 61). This inspection was also completed to comply with the Occupational Safety and Health Administration (OSHA) Asbestos Standards for Construction (29 CFR 1926.1101) which limits employee exposure to asbestos.
SUBJECT PROPERTY
The Subject Property is comprised of a .15-acre residential parcel which contains an approximate 979 square foot residential building (the Building) constructed in 1923. The Building was constructed on a concrete basement with two aboveground floors. The exterior walls of the Building were finished with Transite siding over wood while the roof was sealed with asphalt shingles. The Building can be further divided into a front porch, living room, dining room, kitchen, bath, and two bedrooms on the first floor while the second floor contains two bedrooms. Please note, the Building has extensive fire damage throughout but appears to be structurally sound to facilitate abatement activities.
VISUAL INSPECTION AND SAMPLING
Asbestos Containing Materials Inspection
Jeff Cain of Red Cedar Consulting (Red Cedar), accredited State Of Michigan/EPA Asbestos Building Inspector (Accreditation Number A14057) who completed training per the Michigan Asbestos Workers Accreditation Act 440, completed an inspection of the Subject Property on November 6, 2024 for suspected asbestos containing building materials.
Project No.: 12-1027
This inspection, and subsequent sample collection was completed in accordance with the USEPA Asbestos Hazard Emergency Response Act (AHERA) (40 CFR Part 763) assessment and sampling protocol.
During the completion of the inspection, each area of the Subject Property was visually inspected for asbestos containing building materials (ACBM). Following the completion of the visual inspection, Red Cedar staff identified each suspect area of friable and non-friable ACBM and sorted them into one of three homogenous categories for sampling purposes. AHERA defines friable as a material that when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. A homogenous area is defined by OSHA as an area of surfacing, thermal system insulation (TSI) or miscellaneous material that is uniform in color and texture. Surfacing materials are most commonly found in sprayed-on, troweled-on or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members. TSI refers to materials applied to pipes, fittings, boilers, ductwork, or other components to prevent heat loss or gain, or condensation. Any material that does not fall under the surfacing or TSI category, such as floor tile, drywall, and acoustical ceiling tile are placed into the miscellaneous materials category.
Following the completion of the visual inspection, Red Cedar staff identified the following materials as suspect ACBM:
• Asphalt Shingle
• Roof Tar
• Window Trim Caulk
• Transite Siding with Paper
• Chimney Brick and Mortar
• Roof Trim Caulk
• HVAC Paper
• Multilayer Flooring Materials
• Plaster
Red Cedar staff collected forty-one samples of suspect ACBM separated into eighteen distinct homogenous groups for laboratory analysis. Samples were collected and submitted to APEX Research Inc. Laboratories (APEX) (Accreditation Number 102118-0) for laboratory analysis. Analysis was completed utilizing polarized light microscopy (PLM) which is the Environmental Protection Agency (EPA) approved method for analysis of bulk materials for asbestos. PLM analysis completed pursuant to method (EPA 600/M4-82-020) identifies asbestos fiber bundles by the visual properties displayed when the sample is treated with various dispersion staining liquids. The laboratory report completed following the sample analysis indicates if asbestos is present, and at what percentage along with a description and percentage of other fibrous and non-fibrous materials and sample color. Chain-of-custody documentation was followed from sample collection through shipping and receiving of the samples at the designated laboratory. The documentation assures that samples will meet the quality assurance/quality control measures defined by AHERA. The laboratory analytical report prepared by APEX for the forty-one samples is included as Attachment A.
Hazardous Materials Inspection
On November 6, 2024 the Subject Property was also inspected for the presence of hazardous materials which include but are not limited to polychlorinated biphenyls (PCBs) and potential mercury containing equipment and any items or containers that may contain or be classified as a hazardous or regulated material. Each material, if identified, was documented along with the approximate location. Any materials identified as hazardous are included in Table 1.
INSPECTION RESULTS AND RECOMMENDATIONS
During the completion of the asbestos inspection, forty-one samples of suspect ACM were collected and are documented in Table 2 along with the Red Cedar sample number, description, friability, material type, ACM classification, sample location, material quantity and laboratory analytical results. A Site Diagram was prepared which provides the general building layout and sample locations and is included as Attachment B.
ACM, as defined by the USEPA NESHAP is “any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 Section 1, Polarized Light Microscopy”.
Friable ACM is defined by NESHAP as any material containing more than 1 percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. Friable ACM is a concern due to the ease of unintentionally disturbing the ACM which may result in “visible emissions” which is known as a Fiber Release Episode.
Non-friable asbestos-containing material is defined as “material containing more than 1 percent asbestos that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. Non-friable ACMs are separated into Category I and Category II ACM. Category I ACM is any asbestos containing packing’s, gaskets, resilient floor coverings (vinyl floor tile and linoleum are examples of these) and asphalt roofing products. Category II ACM is stated by NESHAP as any material excluding Category I non-friable ACM such as drywall, plaster or fiberboard insulation.
Presumed Asbestos Containing Material
Presumed Asbestos Containing Materials (PACM) are suspect surfacing, TSI and miscellaneous materials found in buildings constructed prior to 1980 which are classified as and due to the age of the structure, are assumed to be ACM and do not require sample collection and analysis. OSHA dictates that PACM may be “rebutted” following a complete inspection pursuant to AHERA protocol.
No PACM was identified during the completion of this inspection. All suspect materials identified were sampled and analyzed for ACM.
Table 3 lists the location, material description, friability, condition, material type (surfacing, thermal or miscellaneous) and approximate quantity of all PACM documented at the Subject Property.
Table 4 provides a summary of all ACM documented at the Subject Property which includes the material location, description, and approximate quantity.
Friable ACM’s
Duct Wrap identified in the building in conjunction with the forced air heating system is classified as friable ACM. The visual assessment to quantify the extent of this material identified HVAC Duct Wrap at the following locations within the basement, first and second floors:
• Basement (misc. HVAC wrap on 6 register boots 2 sq. ft. each, 12 sq. ft.)
• Basement (12 in. dia. HVAC Wrapped Ductwork, 25 lin. ft.)
Category I ACM
One type of resilient floor covering (Flooring Tile) located within Bedroom 1 was found to contain up to 2% Chrysotile asbestos. The assessment to quantify the extent of this material identified approximately 100 sq. ft. of this material within the Building.
Roof Tar samples collected during the completion of the inspection were found to contain up to 10% Chrysotile asbestos. The assessment to quantify the extent of this material identified 8 lin. ft. of 4 inch wide roofing tar materials on the Building.
Category II ACM
The cementatious “Transite” siding located on the exterior of the Building was classified as PACM and no samples were collected. The visual assessment to quantify the extent of this material identified 700 sq.
ft. of cementatious (Transite) siding on the Building.
RECOMMENDATIONS
Asbestos Containing Materials
HVAC material identified in the Building system and listed below is classified as friable ACM and should be removed prior to any renovation/demolition activities.
• Basement (misc. HVAC wrap on 6 register boots 2 sq. ft. each, 12 sq. ft.)
• Basement (12 in. dia. HVAC Wrapped Ductwork, 25 lin. ft.)
Transite siding was identified on the exterior of the Building and must be abated prior to completion of any demolition activities at the Subject Property. In demolition, all cementatious ACM must be removed prior to demolition due to the likelihood of becoming regulated due to the demolition process.
The Category I roofing materials and resilient floor coverings (Flooring Tile) are non-friable ACM’s that should be abated to mitigate any future exposure.
Please note: The location of samples obtained during this inspection were in a random fashion and areas that were not identified during this inspection may be damaged or have become damaged since the inspection was completed. If Category I or Category II friable materials are discovered prior to or during the demolition/renovation process, these materials must be abated prior to commencement of any demolition/renovation activities at the Subject Property.
Hazardous Materials
Hazardous Materials identified at the Subject Property and documented in Table 1 which require proper removal and disposal consist of the following items:
• No Hazardous Materials Identified
REGULATORY REQUIREMENTS
A Notification of intent to Renovate/Demolish form must be filed with the Michigan Department of Environmental Quality- Air Quality Division at least 10 working days prior to any renovation or demolition activities at a site.
The Notification of Intent to Renovate/Demolish form must also be completed and submitted to the MIOSHA-Asbestos Program whenever demolition, encapsulation and/or renovation activities at a site involving greater than ten lineal feet and/or fifteen square feet of ACM will be completed.
Regulated asbestos containing materials per NESHAP (40 CFR Part 61) which falls into any of the following categories are ACM’s that must be removed prior to any renovation/demolition activities at the Subject Property.
• Friable asbestos material.
• Category I non-friable ACM that has become friable.
• Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading.
• Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of renovation or demolition operations.
Asbestos abatement should only be performed by a certified asbestos abatement contractor licensed to complete abatement work. The contractor must also follow the standards and requirements set forth per the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61).
Additional information regarding the OSHA Asbestos Standards for Construction (29 CFR 1926.1101) and the USEPA NESHAP (40 CFR Part 61) can be obtained by contacting the associated agency below.
NESHAP Asbestos Program MIOSHA-CSHD-Asbestos Program Department of Environmental Quality State of Michigan Phone: 517-284-6777 Phone: 517-284-7680 Email: asbestos@michigan.gov
DISCLAIMER
Red Cedar Consulting performed destructive testing methods in an attempt to access and inspect all areas of the Building. Unfortunately, due to the age of construction along with multiple additions/renovations that may have been completed on the Building, additional inspections may be required if suspect ACM material not documented within this report is encountered during renovation/demolition activities.
This report was prepared at the request and for exclusive use by the City of Jackson and may not be reproduced or sold without written permission from Red Cedar Consulting.
We appreciate the opportunity to provide the requested services. Please contact us at (888) 449-4566 with any questions or concerns.
Sincerely, Red Cedar Consulting
Aaron Paquet
Michigan/EPA Certified Asbestos Building Inspector (A30955)
©2024 Red Cedar Consulting, LLC.
Attachment A
APEX Research Laboratory Analytical Results
Certificate of Laboratory Analysis Test Method, Polarized Light Microscopy (PLM)
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 01 Asbestos Present: NO Fiberglass - 30%
Cust. #: DS-HM-01A No Asbestos Observed Other - 70% Material: Roofing M/L Location:
Appearance: black,fibrous,nonhomogenous Layer: 1 of 4
Lab ID #: 114063 - 01a Asbestos Present: NO Fiberglass - 30% Cust. #: DS-HM-01A No Asbestos Observed Other - 70% Material: Shingle Location:
Appearance: black,fibrous,nonhomogenous Layer: 2 of 4
Lab ID #: 114063 - 01b Asbestos Present: NO Fiberglass - 20% Cust. #: DS-HM-01A No Asbestos Observed Other - 80% Material: Felt Location:
Appearance: black,fibrous,homogenous Layer: 3 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Project #: Jackson, MI
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Liability limited to cost of analysis.
Project: 408 Damon St.
NVLAP Lab Code 102118-0
APEX Research Inc., 7717 Kensington Ct., Brighton, MI 48116
(734) 449-9990, Fax (734) 449-9991 Page 1 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 01c Asbestos Present: NO Cellulose - 60%
Cust. #: DS-HM-01A No Asbestos Observed Other - 40% Material: Felt Location:
Appearance: black,fibrous,homogenous Layer: 4 of 4
Lab ID #: 114063 - 02 Asbestos Present: NO Fiberglass - 30% Cust. #: DS-HM-01B No Asbestos Observed Other - 70% Material: Roofing M/L Location:
Appearance: black,fibrous,nonhomogenous Layer: 1 of 4
Lab ID #: 114063 - 02a Asbestos Present: NO Fiberglass - 30% Cust. #: DS-HM-01B No Asbestos Observed Other - 70% Material: Shingle Location:
Appearance: black,fibrous,nonhomogenous Layer: 2 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 2 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 02b Asbestos Present: NO Fiberglass - 20%
Cust. #: DS-HM-01B No Asbestos Observed Other - 80% Material: Tar Location:
Appearance: black,fibrous,homogenous Layer: 3 of 4
Lab ID #: 114063 - 02c Asbestos Present: NO Cellulose - 60% Cust. #: DS-HM-01B No Asbestos Observed Other - 40% Material: Felt Location:
Appearance: black,fibrous,homogenous Layer: 4 of 4
Lab ID #: 114063 - 03 Asbestos Present: YES Other - 90% Cust. #: DS-HM-02A Chrysotile - 10% Material: Roof Tar Location:
Appearance: black,fibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 3 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 04 Asbestos Present:
Cust. #: DS-HM-02B Material: Roof Tar Location: NOT ANALYZED Appearance:
Layer: 1 of 1
Lab ID #: 114063 - 05 Asbestos Present: NO Other - 100% Cust. #: DS-HM-03A No Asbestos Observed Material: Window Trim Caulk Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 114063 - 06 Asbestos Present: NO Other - 100% Cust. #: DS-HM-03B No Asbestos Observed Material: Window Trim Caulk Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 4 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 07 Asbestos Present: YES Other - 90%
Cust. #: DS-HM-04A Chrysotile - 10% Material: Transite Siding Location:
Appearance: grey,fibrous,homogenous Layer: 1 of 2
Lab ID #: 114063 - 07a Asbestos Present: NO Cellulose - 80% Cust. #: DS-HM-04A No Asbestos Observed Other - 20% Material: Paper Location:
Appearance: black,fibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 08 Asbestos Present:
Cust. #: DS-HM-04B Material: Transite Siding Location: NOT ANALYZED Appearance:
Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 5 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 08a Asbestos Present: NO Cellulose - 80%
Cust. #: DS-HM-04B No Asbestos Observed Other - 20% Material: Paper Location:
Appearance: black,fibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 09 Asbestos Present: NO Other - 100% Cust. #: DS-HM-05A No Asbestos Observed Material: Basement Window Trim Caulk Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 114063 - 10 Asbestos Present: NO Other - 100% Cust. #: DS-HM-05B No Asbestos Observed Material: Basement Window Trim Caulk Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 6 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 11 Asbestos Present: NO Other - 100%
Cust. #: DS-HM-06A No Asbestos Observed Material: Chimney Brick Location:
Appearance: red,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 114063 - 11a Asbestos Present: NO Other - 100% Cust. #: DS-HM-06A No Asbestos Observed Material: Mortar Location:
Appearance: grey,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 12 Asbestos Present: NO Other - 100% Cust. #: DS-HM-06B No Asbestos Observed Material: Chimney Brick Location:
Appearance: red,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 7 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 12a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-06B No Asbestos Observed Material: Mortar Location:
Appearance: grey,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 13 Asbestos Present: NO Other - 100% Cust. #: DS-HM-07A No Asbestos Observed Material: Roof Trim Caulk Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 114063 - 14 Asbestos Present: NO Other - 100% Cust. #: DS-HM-07B No Asbestos Observed Material: Roof Trim Caulk Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 8 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 15 Asbestos Present: YES Cellulose - 25%
Cust. #: DS-HM-08A Chrysotile - 50% Other - 25% Material: Paper - Tape on Duct Location:
Appearance: white,fibrous,homogenous Layer: 1 of 1
Lab ID #: 114063 - 16 Asbestos Present:
Cust. #: DS-HM-08B Material: Paper - Tape on Duct Location: NOT ANALYZED Appearance:
Layer: 1 of 1
Lab ID #: 114063 - 17 Asbestos Present: NO Other - 100% Cust. #: DS-HM-09A No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 9 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 17a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-09A No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 2 of 4
Lab ID #: 114063 - 17b Asbestos Present: NO Cellulose - 1% Cust. #: DS-HM-09A No Asbestos Observed Other - 99% Material: Floor Tile Location:
Appearance: brown,nonfibrous,homogenous Layer: 3 of 4
Lab ID #: 114063 - 17c Asbestos Present: NO Other - 100% Cust. #: DS-HM-09A No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 4 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 10 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 18 Asbestos Present: NO Other - 100%
Cust. #: DS-HM-09B No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
Lab ID #: 114063 - 18a Asbestos Present: NO Other - 100% Cust. #: DS-HM-09B No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 2 of 4
Lab ID #: 114063 - 18b Asbestos Present: NO Cellulose - 1% Cust. #: DS-HM-09B No Asbestos Observed Other - 99% Material: Floor Tile Location:
Appearance: brown,nonfibrous,homogenous Layer: 3 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 11 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 18c Asbestos Present: NO Other - 100%
Cust. #: DS-HM-09B No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 4 of 4
Lab ID #: 114063 - 19 Asbestos Present: NO Other - 100% Cust. #: DS-HM-10A No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
Lab ID #: 114063 - 19a Asbestos Present: NO Other - 100% Cust. #: DS-HM-10A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 12 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 19b Asbestos Present: NO Cellulose - 2%
Cust. #: DS-HM-10A No Asbestos Observed Other - 98% Material: Floor Tile Location:
Appearance: brown,fibrous,homogenous Layer: 3 of 4
Lab ID #: 114063 - 19c Asbestos Present: NO Other - 100% Cust. #: DS-HM-10A No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 4 of 4
Lab ID #: 114063 - 20 Asbestos Present: NO Other - 100% Cust. #: DS-HM-10B No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 13 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 20a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-10B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 4
Lab ID #: 114063 - 20b Asbestos Present: NO Cellulose - 2% Cust. #: DS-HM-10B No Asbestos Observed Other - 98% Material: Floor Tile Location:
Appearance: brown,fibrous,homogenous Layer: 3 of 4
Lab ID #: 114063 - 20c Asbestos Present: NO Other - 100% Cust. #: DS-HM-10B No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 4 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 14 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 21 Asbestos Present: NO Other - 100%
Cust. #: DS-HM-11A No Asbestos Observed Material: Flooring Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 114063 - 21a Asbestos Present: NO Other - 100% Cust. #: DS-HM-11A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 22 Asbestos Present: NO Other - 100% Cust. #: DS-HM-11B No Asbestos Observed Material: Flooring Location:
Appearance: white,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 15 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 22a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-11B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 23 Asbestos Present: NO Other - 100% Cust. #: DS-HM-12A No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
Lab ID #: 114063 - 23a Asbestos Present: NO Other - 100% Cust. #: DS-HM-12A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 16 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 23b Asbestos Present: NO Other - 100%
Cust. #: DS-HM-12A No Asbestos Observed Material: Floor Tile Location:
Appearance: white,nonfibrous,homogenous Layer: 3 of 4
Lab ID #: 114063 - 23c Asbestos Present: NO Other - 100% Cust. #: DS-HM-12A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 4 of 4
Lab ID #: 114063 - 24 Asbestos Present: NO Other - 100% Cust. #: DS-HM-12B No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 17 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 24a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-12B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 4
Lab ID #: 114063 - 24b Asbestos Present: NO Other - 100% Cust. #: DS-HM-12B No Asbestos Observed Material: Floor Tile Location:
Appearance: white,nonfibrous,homogenous Layer: 3 of 4
Lab ID #: 114063 - 24c Asbestos Present: NO Other - 100% Cust. #: DS-HM-12B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 4 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 18 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 25 Asbestos Present: YES Other - 98%
Cust. #: DS-HM-13A Chrysotile - 2% Material: Floor Tile Location:
Appearance: grey,fibrous,homogenous Layer: 1 of 2
Lab ID #: 114063 - 25a Asbestos Present: NO Other - 100% Cust. #: DS-HM-13A No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 26 Asbestos Present:
Cust. #: DS-HM-13B Material: Floor Tile Location: NOT ANALYZED Appearance:
Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 19 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 26a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-13B No Asbestos Observed Material: Glue Location:
Appearance: yellow,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 27 Asbestos Present: NO Fiberglass - 5% Cust. #: DS-HM-14A No Asbestos Observed Other - 95% Material: Flooring Location:
Appearance: brown,fibrous,nonhomogenous Layer: 1 of 1
Lab ID #: 114063 - 28 Asbestos Present: NO Fiberglass - 5% Cust. #: DS-HM-14B No Asbestos Observed Other - 95% Material: Flooring Location:
Appearance: brown,fibrous,nonhomogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 20 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 29 Asbestos Present: NO Other - 100%
Cust. #: DS-HM-15A No Asbestos Observed Material: Flooring Location:
Appearance: black,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 114063 - 29a Asbestos Present: NO Other - 100% Cust. #: DS-HM-15A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 30 Asbestos Present: NO Other - 100% Cust. #: DS-HM-15B No Asbestos Observed Material: Flooring Location:
Appearance: black,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 21 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 30a Asbestos Present: NO Other - 100%
Cust. #: DS-HM-15B No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 114063 - 31 Asbestos Present: NO Fiberglass - 2% Cust. #: DS-HM-16A No Asbestos Observed Other - 98% Material: Flooring Location:
Appearance: beige,fibrous,nonhomogenous Layer: 1 of 1
Lab ID #: 114063 - 32 Asbestos Present: NO Fiberglass - 2% Cust. #: DS-HM-16B No Asbestos Observed Other - 98% Material: Flooring Location:
Appearance: beige,fibrous,nonhomogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 22 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O. Box 13216 Date Analyzed: 11/13/24 Lansing, MI 48901 Date Reported: 11/15/24
Project #: Jackson, MI Project: 408 Damon St.
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 114063 - 33 Asbestos Present: NO Other - 100%
Cust. #: DS-HM-17A No Asbestos Observed Material: Flooring M/L Location:
Appearance: grey,nonfibrous,homogenous Layer: 1 of 4
Lab ID #: 114063 - 33a Asbestos Present: NO Other - 100% Cust. #: DS-HM-17A No Asbestos Observed Material: Glue Location:
Appearance: clear,nonfibrous,homogenous Layer: 2 of 4
Lab ID #: 114063 - 33b Asbestos Present: NO Other - 100% Cust. #: DS-HM-17A No Asbestos Observed Material: Floor Tile Location:
Appearance: white,nonfibrous,homogenous Layer: 3 of 4
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 40 CFR - Part 763 and/or EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples as submitted and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal
(734) 449-9990, Fax (734) 449-9991 Page 23 of 27
Report To: ARI Report # 24-114063 Mr. Aaron Paquet Date Collected: 11/06/24 Red Cedar Consulting Date Received: 11/08/24 P.O.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .