171.24438.JBB_EscanabaRTUReplacement_Plans_Bidding.pdf

PDF 3 MB Posted

Attached to
171/24438. JBB; Escanaba State Office Bldg. - RTU Replacement
Solicitation number
RFQ-171-250000000582-3
Issued by
Delta County, Edmore Village, Michigan

About this file

These documents are construction bid documents for the Rooftop Unit Replacement project for the Michigan State Office Building located at 305 Ludington St, Escanaba, MI, prepared by OHM Advisors for the Department of Technology, Management and Budget (DTMB) State Facilities Administration Design and Construction Division. The project involves replacing the existing rooftop unit (RTU-1) with a new Carrier 48K3HM30 rooftop unit, which will serve multiple floors and rooms totaling approximately 23,800 square feet. The bid documents are dated August 1, 2025, with a project number of 7136-24-0110 and DTMB File No. 171/24438.JBB.

The new rooftop unit is specified with detailed technical requirements, including a 13,500 CFM supply air capacity, 1,900 CFM outside air, 15 HP supply fan, DX cooling with 312 MBH total capacity, and an 800 MBH gas heating section. The unit will feature multi-stage high gas heat, digital scroll modulating cooling, variable frequency drives, 100% comparative enthalpy economizer, hot gas reheat coil, and BACnet control interface. Electrical and mechanical plans indicate the replacement will involve removing existing equipment, preparing new roof curbs, connecting gas and electrical services, and integrating with the building's existing Building Automation System. The project scope includes comprehensive demolition, installation, and system integration work to ensure minimal disruption to the state office building's operations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION MAP

PROJECT LOCATION

ROOFTOP UNIT REPLACEMENT

ISSUED: 2025/08/01

BIDS

OHM PROJECT NO. 7136-24-0110

DTMB File No. 171/24438.JBB

305 Ludington St, Escanaba, MI 49829

ESCANABA STATE OFFICE BUILDING

DRAWING INDEX

N U

M B

E R

SHEET NAME 0

/0 /0

B

ID

S

GENERAL

G-000 COVER & DRAWING INDEX •

ARCHITECTURAL

A-111 ROOF PLAN •

MECHANICAL

M-001 MECHANICAL NOTES AND SYMBOLS •

MD101 ROOF MECHANICAL DEMOLITION PLAN •

M-101 FIRST FLOOR MECHANICAL PLAN •

M-102 SECOND FLOOR MECHANICAL PLAN •

M-103 ROOF MECHANICAL PLAN •

M-601 MECHANICAL SCHEDULES •

M-602 MECHANICAL DIAGRAMS •

ELECTRICAL

E-001 ELECTRICAL NOTES AND SYMBOLS •

EDP101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN •

EDP102 ROOF ELECTRICAL DEMOLITION PLAN •

EP101 FIRST FLOOR POWER PLAN •

EP102 ROOF POWER AND LOW VOLTAGE PLAN •

E-501 ELECTRICAL DETAILS •

MICHIGAN STATE OFFICE BUILDING

BEN JOHNSON

305 LUDINGTON ST

ESCANABA, MI 49829

(906)-786-5394

JOHNSONB29@MICHIGAN.GOV

OWNER

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

G-000

C O

V E

R

D R

A W

IN

G

IN

D

E X

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

I Certify That The Architectural Plans Were Prepared Under My Direct Supervision

2. [PLACEHOLDER]

1. [PLACEHOLDER]

SCHEDULE NOTES:

REQUIRED BY CONTRACTOR R

PERMIT OBTAINED O

APPLICATION DATE: APPLICATION TYPE: PERMIT NO.: APPLICATION STATUS:

SCHEDULE KEY:

PLAN REVIEW / PERMIT SUBMISSIONS

APPLICATION

DATE APPLICATION TYPE PERMIT NO.

APPROVAL

DATE STATUS

[MM/DD/YYYY] BUILDING [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R

[MM/DD/YYYY] ELECTRICAL [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R

[MM/DD/YYYY] MECHANICAL [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R

[MM/DD/YYYY] PLUMBING [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R

I Certify That The Mechanical & Electrical Plans Were Prepared Under My Direct Supervision

WP

CLCL

X-XXX

SIM

ROOF SLOPE

EXISTING ROOF DRAIN

(UNSHADED) INDICATES AREA OF EXISTING FULLY ADHERED FLEECE BACKED

EPDM MEMBRANE ON RECOVERY BOARD ON TAPERED INSULATION

ERD

ROOF LEGEND

e1 eA e12 e11 e10 e9 e8 e7 e6 e5 e4 e3 e2 eB eC

ERD

ERD

ERD

ERDERDERDERDERD

A-111

HVAC EQUIPMENT - REFER TO MEP

EXISTING CURB TO REMAIN

LAYDOWN AREA

1. COORDINATE PENETRATIONS AND ROOF MOUNTED EQUIPMENT WITH MECHANICAL, PLUMBING,

ELECTRICAL AND STRUCTURAL DRAWINGS

2. ALL ROOF PENETRATIONS SHALL BE SEALED WITH APPROPRIATE MATERIAL

3. ALL EXPOSED METAL ELEMENTS TO BE PRE-FINISHED. COLOR AS SELECTED BY ARCHITECT

4. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION ON FINISHES & INSTALLATION

REQUIREMENTS

GENERAL NOTES - ROOF PLAN

NOTE:

COORDINATE W/ SPECIFICATIONS,

MECHANICAL EQUIPMENT

MANUFACTURER'S INSTALLATION

INSTRUCTIONS, & EXISTING

MEMBRANE SYSTEM

REQUIREMENTS

VIF

VARIES

EXISTING METAL DECK & OPENING FRAMING

EXISTING TAPERED INSULATION

EXISTING CURB TO REMAIN

LAP SPLICE SEALANT

EXISTING ROOF MEMBRANE OVER CURB TO REMAIN

EPDM ROOF MEMBRANE WRAPPED OVER PRE-

FABRICATED INSULATED CURB. SEAL TO EXISTING ROOF

MEMBRANE & MAINTAIN EXISTING ROOF WARRANTY

METAL COUNTER FLASHING

WOOD NAILER

SEALANT - CONTINUOUS AROUND TOP OF CURB

ROOF TOP UNIT - REFER TO MECHANICAL

PRE-FABRICATED INSULATED CURB - REFER TO MECHANICAL

1/2"

8" M

IN

IM

U M

F

LA

S H

IN

G

H E

IG

H

T

1. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN

CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO

CONTINUATION OF WORK

2. ALL WALL DIMENSIONS ARE TO FACE OF STUD OR MASONRY, UNO.

3. FIELD VERIFY ALL PROJECT CONDITIONS PRIOR TO THE START OF WORK, AND AS NEEDED

THROUGHOUT THE DURATION OF CONSTRUCTION. BRING ANY DISCREPANCIES WHICH MAY

SIGNIFICANTLY AFFECT NEW CONSTRUCTION WORK TO THE ATTENTION OF THE ARCHITECT FOR

REVIEW

4. ALL WOOD BLOCKING AND BACKING SHALL BE FIRE-RETARDANT TREATED, UNO

5. INFORMATION SHOWN IN ONE LOCATION ON THE DRAWINGS IS THE SAME AS IF SHOWN ON MULTIPLE

LOCATIONS

6. TYPICAL CONDITIONS ARE NOTED ONLY ONCE

7. COORDINATE OPENINGS AND PENETRATIONS BETWEEN TRADES

GENERAL NOTES - ARCHITECTURAL

ALUMINUM

CONCRETE

BATT INSULATION

WOOD

ROUGH WOOD

RIGID INSULATION

SHIM

ACOUSTICAL TILE

EARTH / COMPACT FILL

POROUS FILL

CONCRETE MASONRY

UNITS

FACE BRICK

PLYWOOD

STEEL

GYPSUM WALL BOARD

8x8 TILE

12x12 TILEWOOD BOARD

SIDING NARROW

WOOD BOARD

SIDING WIDE

4x4 TILE

MATERIAL SYMBOL LEGEND

NATURAL STONE

CAST STONE

MINERAL WOOL

INSULATION

DETAIL INDICATOR

SECTION DETAIL

INDICATOR

PLAN NORTH

TRUE NORTH

MATCHLINE

SEE 1 / A101

N

NEW CONSTRUCTION

NEW MASONRY CONSTRUCTION

EXISTING TO REMAIN

EXISTING TO BE REMOVED

DOORS

CENTER LINE

ELEVATION MARK

MATCHLINE

EXISTING GRID LINE

PROPOSED GRID LINE

BUILDING LINE

INDICATES EXISTING

SHEET KEYNOTE INDICATOR

REVISION INDICATOR

NORTH INDICATOR

e

CLEARANCE LINES

XX

ARCHITECTURAL SYMBOLS LEGEND

BL1

LEVEL

XXX' - XX"

e1

X-XXX

INDICATOR LINES BUILDING ELEMENTS

NOTES & ANNOTATIONSVIEW REFERENCES

8" TO 12" GRANULAR MATERIAL MDOT

CLASS II (COMPACTED TO 95%)

6" MDOT 22A OR 2AA AGGREGATE

(COMPACTED TO 98%)

1 1/2" MDOT 4EL BASE COURSE

1 1/2" MDOT 5EL TOP COURSE

PERMANENT HMA APPLICATION CHART

SYMBOL PAY ITEM

RATE

(LB/SYD)

DEPTH

(IN)

PERFORMANCE

GRADE

REMARKS

HMA, 5EL

HMA, 4EL

165 LB

220 LB

1.5

1.5

58-34

58-34

TOP COURSE, AWI - 260 MINIMUM

BASE COURSE

0.05 - 0.15

GAL/SYD

TYPE

SS-1h

BOND COAT - TO BE APPLIED

BETWEEN EACH LIFT OF NEW

PERMANENT HMA

5EL

4EL

SUITABLE MATERIAL EXCAVATED FROM

TRENCH (OTHER THAN WET UNSTABLE CLAY)

WARNING TAPE

GRANULAR MATERIAL MDOT

CLASS II OR CLASS IIIA

(COMPACTED TO 95%)

UTILITIESTRENCH WIDTH

4"

M

IN

B E

D D

IN

G

M

IN

EXISTING GROUND

HMA PAVEMENT

WARNING TAPE

GRANULAR MATERIAL MDOT

CLASS II OR CLASS IIIA

(COMPACTED TO 95%)

UTILITIESTRENCH WIDTH

4" M

IN

B

E D

D

IN

G

IN

EXISTING GROUND

EXISTING HMA

EXISTING HMA

EXISTING HMA

EXISTING HMA

6" MDOT 22A OR 21AA

AGGREGATE (COMPACTED TO

95%)

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:2

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

S A

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.r vt

A-111

R O

O F

P

LA

N

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

N

3/32" = 1'-0"1

ROOF PLAN

1 1/2" = 1'-0"2

MEMBRANE ROOF MECHANICAL CURB DETAIL

ABBREVIATIONS

A

& AND

@ AT

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

ANSI AMERICAN NATIONAL STANDARDS

INSTITUTE

ASTM AMERICAN SOCIETY FOR TESTING AND

MATERIALS

C

CL CENTER LINE

D

DN DOWN

DS DOWNSPOUT

E

EJ EXPANSION JOINT

EQ EQUAL

EXST EXISTING

H

HVAC HEATING-VENTILATING-AIR

CONDITIONING

M

MAX MAXIMUM

MFR MANUFACTURER

MIN MINIMUM

N

NA NOT APPLICABLE

ABBREVIATIONS

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

No. NUMBER

NTS NOT TO SCALE

O

OC ON CENTER

OPP OPPOSITE

OPP HND OPPOSITE HAND

R

RD ROOF DRAIN

S

SF SQUARE FOOT

SIM SIMILAR

T

TYP TYPICAL

U

UNO UNLESS NOTED OTHERWISE

V

VIF VERIFY IN FIELD

W

W/ WITH

W/O WITHOUT

N.T.S4

TYP HMA SECTION

3/4" = 1'-0"3

TRENCH DETAILS FOR UTILITIES

AD

AD

D

A

PLAN

ELEVATION

1/2", 1" & 2" WG

CFM PER 100 SQ FT @ 1" WG

SEAL CLASS C

RECTANGULAR DUCT 24

ROUND DUCT 12

SHEET METAL

SCREWS (TYP)

BAND OF SAME

SIZE AS HANGER

STRAP

HANGER

STRAP

ANGLE

SIZE BOLT(S)

FOR LOAD

ROD

DUCT DUCT DUCT

HANGER STRAP

RADIUS=1 1/2 xWIDTH OF DUCT

TURNING VANES AT

ALL MITERED ENDS

USE RADIUS ELBOW FOR ALL

DUCT 20" WIDTH AND LESS, IF

POSSIBLE

VOLUME DAMPERS AT

ALL TERMINAL TAKE-

OFFS, SUPPLY, RETURN

AND EXHAUST

VOLUME DAMPERS AT

ALL TERMINAL TAKE-

OFFS, SUPPLY, RETURN

AND EXHAUST

VOLUME DAMPERS

FOR BALANCING AT

ALL BRANCH TRUNKS

PREFERRED MAX

TRANSITION ANGLE

IN-DUCT COIL

PROVIDE ACCESS DOOR/PANEL

UPFLOW OF ALL IN-DUCT COILS

AND TURNING VANES

MIN DISTANCE OF STRAIGHT

DUCT FROM TRANSITIONS/

FITTINGS PRIOR TO TAKE-OFF

TYP ANGLE

UPFLOW, ALL

TAKE-OFFS

TYP ANGLE UPFLOW,

ALL TAKE-OFFS

FLOW

FLEX DUCT, 5 FT MAX

LENGTH, NO SHARP BENDS

SUPPLY DUCT ONLY

VOLUME DAMPERS

FOR BALANCING AT

ALL BRANCH TRUNKS

SEAL ALL DUCTS WATER

TIGHT WITHIN 15 LF OF ANY

FRESH AIR INTAKE OPENINGS

SUMP (PIPE TO DRAIN)

PITCH TO LOUVER

PARALLEL BLADE DAMPER

WHERE SHOWN ON PLANS

INTAKE LOUVER

EXTERIOR

WALL

SHEET METAL PLENUM

2.

5x

D U

C T

W

ID

T H

/D

IA

15'

1. ITEMS AS SHOWN ARE THE MINIMUM REQUIRED AND SHALL BE PROVIDED BY THE CONTRACTOR

WHETHER SHOWN ON THE FOLLOWING PLANS OR NOT.

2. LISTED DUCT SIZES INDICATE THE INSIDE CLEAR DIMENSIONS, NOT INCLUDING DUCT LINER.

3. ALL FLAT SURFACES ON DUCTS AND FITTINGS SHALL BE EITHER CROSS BROKE OR BEADED.

4. DUCT SEAMS SHALL BE EITHER PITTSBURG OR BUTTON LOCK.

5. STANDING RIB CLEATS ARE REQUIRED ON DUCTS HAVING WIDTHS OF 24" OR MORE.

6. ALL JOINTS IN SHEET METAL SHALL BE SEALED WITH AN APPROVED DUCT SEALANT.

7. ALL DAMPERS MUST HAVE A POSITION INDICATOR ON THE SHAFT.

8. DAMPERS GREATER THAN 8" IN WIDTH MUST BE OPPOSED BLADE.

FOLLOW SMACNA STANDARDS FOR HANGER TYPE, SIZING, GAUGE AND SPACING.

45°

15°

DUCTWORK REQUIREMENTS

DUCT SUPPORT DETAILS

NOTES

PRESSURE CLASS

ITEM THICKNESS TYPE REMARKS

1. ALL DUCTS WITHIN 25' OF MOTORS, INSTALL 1" MANVILLE LINO-COUSTIC DUCT LINER OR EQUAL, EXCLUDING OA DUCT.

2. EXPOSED DUCTWORK SHALL BE INSULATED WITH RIGID FIBERGLASS DUCT INSULATION AND JACKET.

INSULATION SCHEDULE

SUPPLY DUCT 1 1/2" FIBERGLASS TYPE ASJ

PROPOSED EXISTING DEMOLISH

EXHAUST AIR

OUTSIDE AIR

RETURN AIR

SUPPLY AIR

RECTANGLE ROUND

DROP RISE DROP RISE

RECTANGLE ROUND

DROP RISE DROP RISE DROP RISE DROP RISE

RECTANGLE ROUND

12x12

12x12

12x12

12ø

12ø

12ø

12ø

12x12

12x12

12x12

12x12

12ø

12ø

12ø

12ø

12x12

12x12

12x12

12x12

12ø

12ø

12ø

12øEA12x12

OA

RA

SA

EA

OA

RA

SA

EA

OA

RA

SA SA

RA

OA

EA

NEW EXISTING DEMOLISH

NATURAL GAS 6"ø G6"ø G 6"ø G

1. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM

AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.

2. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION, ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT MAY AFFECT THE WORK.

3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS

OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS BEING RE-USED

OR ENLARGED IN THE RENOVATION WORK.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW" CONDITION DURING

CONSTRUCTION.

5. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.

6. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE FLEXIBLE DUCT CONNECTORS.

7. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA AIR GAP.

8. COORDINATE ROOF MOUNTED EQUIPMENT SIZES WITH ARCHITECTURAL TRADES PRIOR TO CONSTRUCTION.

9. ROOF OPENINGS SHALL BE SEALED WEATHER-TIGHT AND WITH ROOFING MATERIALS COMPATIBLE WITH EXISTING ROOF MEMBRANE. CONTRACTOR SHALL

NOT VOID ROOF WARRANTY.

10. DUCT ACCESS PANELS SHALL BE PROVIDED AT ALL FIRE DAMPERS, FIRE/SMOKE DAMPERS, MOTORIZED DAMPERS, AND DUCT SMOKE DETECTORS. WHERE

NECESSARY, CEILING ACCESS PANELS SHALL BE PROVIDED AS WELL.

11. INSTALL ALL NEW EQUIPMENT IN COMPLIANCE WITH THE MANUFACTURER'S REQURIED CLEARANCES. ALL DISCONNECTS AND LOW VOLTAGE ELECTRICAL

PANELS SHALL HAVE THE CLEARANCE REQUIRED BY NEC ARTICLE 110 (36" FOR 120/208V, 42" FOR 227/460V, AND 48" WHEN FACING ONE ANOTHER).

12. ROUTE ALL CONTROL WIRING TO THE THERMOSTATS AND VAV BOXES WITHIN THE SOFFITS AND WALLS WHEREVER POSSIBLE. WIRING IN ANY WALLS OR

EXPOSED SHALL BE IN CONDUIT. WHERE CONNECTING TO VAV BOXES IN EXPOSED AREAS, CONTROL WIRING SHALL BE RUN IN EXPOSED PAINTED CONDUIT.

CONDUIT COLOR SHALL BE COORDINATED WITH ARCHITECT.

GENERAL NOTES - MECHANICAL

HVAC SYMBOLS LEGEND

H

T

DUCTS

PIPING

DIFFUSERS, GRILLES, TAGS AND SYMBOLS

CEILING DIFFUSER

LINEAR SLOT DIFFUSER

WALL DIFFUSER /

GRILLE

FLOOR REGISTER

CEILING GRILLE

TRANSFER GRILLE

TURNING VANES

12x12 DUCT WIDTH x HEIGHT

12Ø ROUND DUCT DIAMETER

101.1

DIFFUSER INDICATOR

MARK

FLOW

EQUIPMENT TAG

KEYNOTE TAG

BREAK LINE

XX-X

DIGITAL INPUT TO THE

CONTROLLER

DIGITAL OUTPUT TO THE

CONTROLLER

ANALOG INPUT TO THE

CONTROLLER

ANALOG OUTPUT TO THE

CONTROLLER

RELAY

CURRENT SWITCH

PNUEMATIC DAMPER

ACTUATOR

SOLENOID VALVE FINNED TUBE OR

RADIANT PANEL

REFRIGERANT

COOLING COIL

HOT WATER

HEATING COIL

V D

MANUAL VOLUME

DAMPER

MOTORIZED DAMPERM

FIRE DAMPER

SMOKE DAMPER

SMOKE AND FIRE DAMPER

THERMOSTAT

HUMIDISTAT

CONNECT TO EXISTING

PIPE BREAK

AVERAGING

TEMPERATURE SENSOR

AVERAGING

TEMPERATURE SENSOR

PUMP

ELECTRIC TO PNUEMATIC

TRANSDUCER

PNUEMATIC TO ELECTRIC

TRANSDUCER

DIFFERENTIAL PRESSURE

SENSOR / SWITCH

SMOKE DETECTOR

AIR FLOW MEASURING

STATION

CHILLED WATER

COOLING COIL

GAS HEAT SECTION

CHECK VALVE

GATE VALVE

BALL VALVE

BUTTERFLY VALVE

2-WAY ELECTRONIC

CONTROL VALVE

3-WAY ELECTRONIC

CONTROL VALVE

2-WAY PNEUMATIC

CONTROL VALVE

3-WAY PNEUMATIC

CONTROL VALVE

RELIEF VALVE

CIRCUIT SETTER

BALANCE VALVE

TRIPLE DUTY VALVE

AIR VENT

MOTORIZED VALVE

OCCUPANCY SENSOR

CO2 SENSOR

FAN

FILTER BANK

DX

C

C

C

M

M

M

H

C

H L

R

AI

AO

BI

BO

CS

M

S

CO2

OCC

EP

PE

T

SD

GAS LOAD SCHEDULE

MARK DESCRIPTION BTU / HOUR CU FT / HOUR NOTE

B-1 GAS BOILER 750,000 723 1

B-2 GAS BOILER 750,000 723 1

RTU-1 GAS ROOF TOP UNIT 525,000 506 1

TOTALS: 2,025,000 1,952

NOTE: 1. GAS LINE SIZES BASED ON 7" WC DELIVERY PRESSURE.

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

M-001

M E

C H

A N

IC

A

L N

O T

E S

A N

D S

Y M

B O

LS

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

MECHANICAL

ABBREVIATIONS

A

A AIR

AAV AUTOMATIC AIR VENT

AD ACCESS DOOR/PANEL

AFF ABOVE FINISH FLOOR

AHU AIR HANDLING UNIT

APD AIR PRESSURE DROP

AS AIR SEPARATOR

B

B BOILER

BDD BACK DRAFT DAMPER

BFP BACK FLOW PREVENTER

C

CFM CUBIC FEET PER MINUTE

CG CEILING GRID

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CND STEAM CONDENSATE

COND CONDENSING UNIT

CONV CONVECTOR

CR CONDENSATE RETURN

CUH CABINET UNIT HEATER

D

DB DRY BULB

DIA OR Ø DIAMETER

DN DOWN

E

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDB ENTERING DRY BULB

EF EXHAUST FAN

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EWB ENTERING WET BULB

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F

FCU FAN COIL UNIT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FOOT / FEET

FTR FIN TUBE RADIATION

°F FAHRENHEIT DEGREE

G

G NATURAL / LP GAS

GA GAUGE

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

H

HC HOT WATER COIL

HP HORSEPOWER

HPS HIGH PRESSURE STEAM

HRU HEAT RECOVERY UNIT

HTWR HEATING WATER RETURN

HTWS HEATING WATER SUPPLY

HVAC HEATING VENTILATING & AIR

CONDITIONING

HX HEAT EXCHANGER

I

IN INCH / INCHES

K

KH KITCHEN HOOD

L

L LOUVER

LAT LEAVING AIR TEMPERATURE

LDB LEAVING DRY BULB

LF LINEAL FEET

LPS LOW PRESSURE STEAM

LWB LEAVING WET BULB

LWT LEAVING WATER TEMPERATURE

M

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MCA MINIMUM CIRCUIT AMPS

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

MUA MAKE-UP AIR UNIT

MECHANICAL

ABBREVIATIONS

O

OA OUTSIDE AIR

P

P PUMP

PH OR Φ PHASE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

R

R SUPPLY REGISTER

RA RETURN AIR

RAD RADIANT HEATER

RD ROUND DIFFUSER

RF RETURN FAN

RH GRAVITY RELIEF HOOD

RPM REVOLUTIONS PER MINUTE

S

SA SUPPLY AIR

SC STEAM COIL

SD SMOKE DAMPER

SF SUPPLY FAN

SP STATIC PRESSURE

STD STANDARD

STM STEAM

SWG SIDE WALL GRILLE

SWR SIDE WALL REGISTER

T

TYP TYPICAL

U

UH UNIT HEATER

V

V VENT

VAV VARIABLE AIR VOLUME

VD VANED DIFFUSER

W

WH WATER HEATER

WPD WATER PRESSURE DROP

EX. CURB

EX. 1 1/2"ø G

E X

1/ 2" ø G

EX. VTR EX. VTREX. VTR

EX. VTR

EX. VTR

EX. VTR

REMOVE EXISTING GAS

SUPPORTS AND REPLACE

1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN

INTENT, COORDINATE WITH THE CM, AND PERFORM A CONSTRUCTABILITY ANALYSIS PRIOR TO

SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR

CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF COORDINATION.

2. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS

BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.

3. ANY DEVICE/EQUIPMENT NO LONGER NEEDED SHALL BE PROPERLY DISPOSED OF.

GENERAL NOTES - HVAC DEMOLITION

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

MD101

R O

O F

M E

C H

A N

IC

A

L D

E M

O

LI

T

IO

N P

LA

N

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

1/8" = 1'-0"1

ROOF MECHANICAL DEMOLITION PLAN

SHEET KEYNOTES - MECH. DEMOLITION

1 REMOVE ROOFTOP UNIT. DISCONNECT GAS AND CONTROL WIRING.

2 REMOVE UPPER ROOF CURB. PREP FOR NEW ROOF CURB.

3 REMOVE SECTION OF GAS LINE FOR PREPARATION OF NEW RTU.

LOBBY

VESTIBULE

BREAK ROOM

JANITOR

CORRIDOR

WOMEN

MEN

107WORKMAN'S COMP

SERVER

CONFERENCE

CORRIDOR

SOS DEALER

SOS VIDEO

SECRETARY OF STATE

SOS MANAGER

SOS STOR.

SOS BREAK

FIA

FIA CONF.

FIA BLIND

Room

PASSAGE

ENTRY

H.C. ACCESS RAMP

CORRIDOR

VAV-3

VAV-13

VAV-11

VAV-12

VAV-9

VAV-8

VAV-7

VAV-10 VAV-4

VAV-26 VAV-2

VAV-6

VAV-5

VAV-1

EX.44x14 SA

EX.36x12 SA

EX.78x14 RA

60x14

114.1

200 101.2

101.1

114.4

114.2

114.6

114.5

114.3

114.7

114.8

111.1

111.2

110.1

108.1

108.2

108.3

108.4

103.1

107.1

106.1

121.5

121.4

121.3

121.2

125119.1

120.1

125 121.1

118.3

118.6

118.2

118.5

118.1

118.4

117.1

116.1

115.1

112.1

113.1

1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN INTENT PRIOR TO SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF

COORDINATION.

2. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.

3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS

BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.

4. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.

5. SIZES INDICATED FOR EXISTING DUCTWORK AND PIPING ARE PER THE ORIGINAL DOCUMENTS. FIELD

VERIFY EXACT SIZES AND PROVIDE TRANSITIONS ACCORDINGLY.

6. COORDINATE LOCATIONS OF THE THERMOSTATS WITH OTHER TRADES.

GENERAL NOTES - MECHANICAL HVAC

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

M-101

F

IR

S T

F

LO

O R

M E

C H

A N

IC

A

L P

LA

N

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

1/8" = 1'-0"1

FIRST FLOOR MECHANICAL PLAN

NOTE:

THIS PLAN IS PROVIDED FOR

AIRFLOW BALANCING AND IS

FOR REFERENCE ONLY.

CONFERENCE

MEN'S

WOMEN'S

JAN.

STORAGE

CIS

OFFICES

BREAK ROOM

STAIR

REG. ACC.

CORRIDOR

VAV-25

VAV-24 VAV-22

VAV-18

VAV-17

VAV-14VAV-19VAV-27

VAV-20

VAV-16

VAV-21

VAV-23

EX.56x16 SAEX.50x20 SA

EX.114x16 RA

60x24

60x24

207.1

207.2

207.10

207.13

207.11

207.14

207.15

207.6

207.7

207.5

207.4

207.8

207.9

216.2

208.1

208.2

206.2

206.1

214.2

214.1

203.1

202.1

214.3

201.1

201.2

201.3

201.4

216.1

207.3

207.12

216.3

207.16

NOTE:

THIS PLAN IS PROVIDED FOR

AIRFLOW BALANCING AND IS

FOR REFERENCE ONLY.

EXISTING

BACNET

PANEL

1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN INTENT PRIOR TO SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF

COORDINATION.

2. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.

3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS

BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.

4. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.

5. SIZES INDICATED FOR EXISTING DUCTWORK AND PIPING ARE PER THE ORIGINAL DOCUMENTS. FIELD

VERIFY EXACT SIZES AND PROVIDE TRANSITIONS ACCORDINGLY.

6. COORDINATE LOCATIONS OF THE THERMOSTATS WITH OTHER TRADES.

GENERAL NOTES - MECHANICAL HVAC

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

M-102

S E

C O

N D

F

LO

O R

M E

C H

A N

IC

A

L P

LA

N

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

1/8" = 1'-0"1

SECOND FLOOR MECHANICAL PLAN

1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN INTENT PRIOR TO SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF

COORDINATION.

2. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.

3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS

BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.

4. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.

5. SIZES INDICATED FOR EXISTING DUCTWORK AND PIPING ARE PER THE ORIGINAL DOCUMENTS. FIELD

VERIFY EXACT SIZES AND PROVIDE TRANSITIONS ACCORDINGLY.

6. COORDINATE LOCATIONS OF THE THERMOSTATS WITH OTHER TRADES.

GENERAL NOTES - MECHANICAL HVAC

EX. 1 1/2"ø G

E X

1/ 2" ø G

NEW 1-1/2"ø GAS PIPING TO

UNIT CONNECTION. PROVIDE

ISOLATION BALL VALVE.

RTU-1

EX. VTR EX. VTREX. VTR

EX. VTR

EX. VTR

EXTEND 4"ø PLUMBING VENT

FROM ADJACENT TO INTAKE.

SEE DETAIL 2 / M-103

EX. VTR

3' - 6"

EXTEND 4"ø PLUMBING

VENT TO 3' 0" ABOVE

NEW RTU.

EX. CURB

SUPPORT GAS PIPING

PER SPECIFICATION WITH

FACTORY MANUFACTURED

SUPPORT SYSTEM.

EVERY 10 FT OR WITHIN

4 FT OF ANY FITTING.

SEE DETAIL 2 / M-103

RS-485 CABLE FROM

UNIT TO EX. BAC NET

PANEL FOR MS/TP

COMMUNICATIONS.

EX. VENT

NEW SECTION OF OFFSET

VENT (PVC)

EXTEND TO 3'

ABOVE NEW UNIT

1-5/8" VERTICAL UNISTRUT BOTH

SIDES OF PIPE. CLAMP PIPE TO

UNISTRUT.

8" LONG ROOF SUPPORT

MOUNTING BLOCK

ROOF LINE

3'-6"

ROOF LINE

8" C-PORT

RUBBER BLOCK

OR SIMILAR

MOULDED STRUT

MOUNT

GAS PIPE

PIPE CLAMP

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

M-103

R O

O F

M E

C H

A N

IC

A

L P

LA

N

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

1/8" = 1'-0"1

ROOF MECHANICAL PLAN

N.T.S2

VENT THRU ROOF OFFSET DETAIL

N.T.S3

GAS SUPPORT DETAIL

ROOM VENTILATION DATA - RTU-1

REQUIRED

EXHAUST FLOW

(CFM/SQFT)

REQUIRED EXHAUST

FLOW (CFM/PLUMBING

FIXTURE)

PLUMBING

FIXTURE

QUANTITY

REQUIRED

EXHAUST AIR

(CFM)

PROVIDED

EXHAUST AIR

(CFM)

OCCUPANTS/1

000 SQFT

NUMBER OF

OCCUPANTS

RA

CFM/SQFT

RP CFM/

OCCUPANT

REQUIRED

OUTDOOR

AIRFLOW

(RA+RP)

(CFM)

PROVIDED

OUTDOOR

AIRFLOW

(CFM)ROOM SQFT

BREAK ROOM 103 125 0 0 0 0 0 25 3 0 5 23

BREAK ROOM 208 310 0 0 0 0 0 25 8 0 5 57

CIS OFFICE 206 318 0 0 0 0 0 5 2 0 5 27

CONFERENCE ROOM 110 238 0 0 0 0 0 50 12 0 5 74

CONFERENCE ROOM 201 1000 0 0 0 0 0 50 50 0 5 310

CONFERENCE ROOM 201 CIRC

SPACE 460 0 0 0 0 0 0 0 0 0 28

CORRIDOR 207B 905 0 0 0 0 0 0 0 0 0 54

CORRIDOR 105 1330 0 0 0 0 0 0 0 0 0 80

CORRIDOR 207A 1246 0 0 0 0 0 0 0 0 0 75

CORRIDOR 214 906 0 0 0 0 0 0 0 0 0 54

CORRIDOR SOS 114A 87 0 0 0 0 0 0 0 0 0 5

DTMB FACILITIES 122 1100 0 0 0 0 0 5 6 0 5 94

ELEVATOR 181 0 0 0 0 0 0 0 0 0 0

ELEVATOR 72 0 0 0 0 0 0 0 0 0 0

ENTRY 465 0 0 0 0 0 0 0 0 5 0

FIA BLIND 120 120 0 0 0 0 0 5 1 0 5 10

FIA CONFERENCE 119 113 0 0 0 0 0 50 6 0 5 35

FIA OFFICE 118 1095 0 0 0 0 0 5 5 0 5 93

FIA OPEN OFFICE 215 3700 0 0 0 0 0 5 19 0 5 315

JANITOR 104 76 0 0 0 0 0 0 0 0 0 0

JANITOR 204 38 0 0 0 0 0 0 0 0 0 0

LOBBY 101 1205 0 0 0 0 0 10 12 0 5 133

LOBBY OFFICE 101A 94 0 0 0 0 0 5 0 0 5 8

MEN 107 244 0 50 3 150 150 0 0 0 0 0

MEN'S 202 231 0 50 3 150 150 0 0 0 0 0

OFFICE NEAR FIA 216A 282 0 0 0 0 0 5 1 0 5 24

PASSAGE 102 105 0 0 0 0 0 0 0 0 0 0

REG ACC 216 632 0 0 0 0 0 5 3 0 5 54

SERVER 109 79 0 0 0 0 0 0 0 0 5 0

SOS 114 1161 0 0 0 0 0 5 6 0 5 99

SOS BREAK ROOM 117 93 0 0 0 0 0 25 2 0 5 17

SOS DEALER 112 352 0 0 0 0 0 5 1 0 5 26

SOS MANAGER 115 157 0 0 0 0 0 5 1 0 5 13

SOS OFFICE CIRCULATION 1205 0 0 0 0 0 0 0 0 0 72

SOS STORAGE 116 90 0 0 0 0 0 0 0 0 5 5

SOS VIDEO OFFICE 113 180 0 0 0 0 0 5 1 0 5 15

STAIR 282 0 0 0 0 0 0 0 0 0 0

STAIR 2 213 0 0 0 0 0 0 0 0 0 13

STAIR 213 417 0 0 0 0 0 0 0 0 0 0

STORAGE 205 134 0 0 0 0 0 0 0 0 5 8

STORAGE 214 41 0 0 0 0 0 0 0 0 5 2

VESTIBULE 100 229 0 0 0 0 0 0 0 0 0 0

WOMEN 106 233 0 50 3 150 150 0 0 0 0 0

WOMENS 203 242 0 50 3 150 150 0 0 0 0 0

WORKMANS COMP OFFICE 108 850 0 0 0 0 0 5 4 0 5 72

TOTAL 1896

ROOF TOP UNIT SCHEDULE

SUPPLY FAN COOLING GAS HEATING ELECTRICAL FILTER

MARK SERVICE LOCATION SA CFM OA CFM ESP (IN-WG) TYPE QUANTITY MOTOR HP RPM ESP (IN-WG) TYPE

TOTAL CAPACITY

(MBH)

SENSIBLE CAPACITY

(MBH)

EAT DB/WB (°F) LAT DB/WB (°F) TYPE EDB (°F) LDB (°F) INPUT (MBH) OUTPUT (MBH)

MIN

EFFICENCY

V/PH/HZ MCA MOCP TYPE MANUFACTURER MODEL NOTES

RTU-1 VAV BOXES ROOF 13500 1900 1.5 FORWARD CURVE 1 15 1300 1.5 DX 312 227 71.6/60.2 55.2/51.7 INDIRECT GAS 55 86 800 648 81% 460/3/60 88 110 4" MERV 13 CARRIER 48K3HM30-2-6A1F6D0 1,2,3,4,5,6,7,8,9,10

NOTES: 1. PROVIDE WITH MULTI STAGE HIGH GAS HEAT WITH SS HEAT EXCHANGER.

2. PROVIDE WITH DIGITAL SCROLL MODULATING COOLING.

3. PROVIDE VFD WITH BYPASS ON SUPPLY FAN.

4. PROVIDE VFD WITH BYPASS CONTROLLED EXHAUST FAN.

5. PROVIDE WITH 100% COMPARATIVE ENTHALPY CONTROLLED ECONOMIZER.

6. PROVIDE WITH HOT GAS REHEAT COIL (MODULATING CONTROL).

7. PROVIDE WITH MSTP BACNET CONTROL INTERFACE.

8. PROVIDE WITH PHASE MONITORING.

9. PROVIDE WITH CURB TO ADAPT TO EXISTNG OPENINGS AND ROOF SUPPORTS.

10. UNIT TO PROVIDE FACTORY REFRIGERANT LEAK DETECTION AND ISOLATION.

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

M-601

M E

C H

A N

IC

A

L S

C H

E D

U

LE

S

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

AIR TERMINAL SCHEDULE

MARK SUPPLY RETURN EXHAUST

FLOW

(CFM)

DIMENSIONS

(IN)

DUCT

CONNECTOR (IN) MANUFACTURER MODEL NOTES

101.1 X 200 24x24 --- --- --- EXISTING

101.2 X 200 24x24 --- --- --- EXISTING

103.1 X 150 24x24 --- --- --- EXISTING

106.1 X 125 24x24 --- --- --- EXISTING

107.1 X 100 24x24 --- --- --- EXISTING

108.1 X 200 24x24 --- --- --- EXISTING

108.2 X 200 24x24 --- --- --- EXISTING

108.3 X 150 24x24 --- --- --- EXISTING

108.4 X 200 24x24 --- --- --- EXISTING

110.1 X 250 24x24 --- --- --- EXISTING

111.1 X 250 24x24 --- --- --- EXISTING

111.2 X 250 24x24 --- --- --- EXISTING

112.1 X 150 24x24 --- --- --- EXISTING

113.1 X 150 24x24 --- --- --- EXISTING

114.1 X 200 24x24 --- --- --- EXISTING

114.2 X 200 24x24 --- --- --- EXISTING

114.3 X 250 24x24 --- --- --- EXISTING

114.4 X 200 24x24 --- --- --- EXISTING

114.5 X 100 24x24 --- --- --- EXISTING

114.6 X 200 24x24 --- --- --- EXISTING

114.7 X 150 24x24 --- --- --- EXISTING

114.8 X 150 24x24 --- --- --- EXISTING

115.1 X 125 24x24 --- --- --- EXISTING

116.1 X 75 24x24 --- --- --- EXISTING

117.1 X 75 24x24 --- --- --- EXISTING

118.1 X 150 24x24 --- --- --- EXISTING

118.2 X 150 24x24 --- --- --- EXISTING

118.3 X 125 24x24 --- --- --- EXISTING

118.4 X 150 24x24 --- --- --- EXISTING

118.5 X 125 24x24 --- --- --- EXISTING

118.6 X 125 24x24 --- --- --- EXISTING

119.1 X 125 24x24 --- --- --- EXISTING

120.1 X 125 24x24 --- --- --- EXISTING

121.1 X 125 24x24 --- --- --- EXISTING

121.2 X 125 24x24 --- --- --- EXISTING

121.3 X 125 24x24 --- --- --- EXISTING

121.4 X 150 24x24 --- --- --- EXISTING

121.5 X 150 24x24 --- --- --- EXISTING

201.1 X 300 24x24 --- --- --- EXISTING

201.2 X 300 24x24 --- --- --- EXISTING

201.3 X 300 24x24 --- --- --- EXISTING

201.4 X 300 24x24 --- --- --- EXISTING

202.1 X 125 24x24 --- --- --- EXISTING

203.1 X 125 24x24 --- --- --- EXISTING

206.1 X 125 24x24 --- --- --- EXISTING

206.2 X 100 24x24 --- --- --- EXISTING

207.1 X 150 24x24 --- --- --- EXISTING

207.2 X 225 24x24 --- --- --- EXISTING

207.3 X 225 24x24 --- --- --- EXISTING

207.4 X 320 24x24 --- --- --- EXISTING

207.5 X 320 24x24 --- --- --- EXISTING

207.6 X 320 24x24 --- --- --- EXISTING

207.7 X 320 24x24 --- --- --- EXISTING

207.8 X 320 24x24 --- --- --- EXISTING

207.9 X 320 24x24 --- --- --- EXISTING

207.10 X 225 24x24 --- --- --- EXISTING

207.11 X 200 24x24 --- --- --- EXISTING

207.12 X 225 24x24 --- --- --- EXISTING

207.13 X 200 24x24 --- --- --- EXISTING

207.14 X 320 24x24 --- --- --- EXISTING

207.15 X 320 24x24 --- --- --- EXISTING

207.16 X 0 60x36 --- --- --- EXISTING

208.1 X 200 24x24 --- --- --- EXISTING

208.2 X 150 24x24 --- --- --- EXISTING

214.1 X 150 24x24 --- --- --- EXISTING

214.2 X 150 24x24 --- --- --- EXISTING

214.3 X 150 24x24 --- --- --- EXISTING

216.1 X 320 24x24 --- --- --- EXISTING

216.2 X 200 24x24 --- --- --- EXISTING

216.3 X 0 72x60 --- --- --- EXISTING

EA

SAOA

RA

ROOFTOP UNIT SEQUENCE OF OPERATION:

RUN CONDITIONS:

THE UNIT SHALL RUN ON AN OCCUPANCY SCHEDULE FROM THE EXISTING BAS SYSTEM AND SENT TO THE RTU AS A BINARY SIGNAL

FREEZE PROTECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.

ALARM ON ACTIVATION (ALARM SHALL BE SENT TO THE EXISTING BAS)

HIGH STATIC SHUTDOWN:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC SHUTDOWN SIGNAL.

ALARM ON ACTIVATION (ALARM SHALL BE SENT TO THE EXISTING BAS)

RETURN AIR SMOKE DETECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A RETURN AIR SMOKE DETECTOR STATUS.

ALARM ON ACTIVATION (ALARM SHALL BE SENT TO THE EXISTING BAS)

SUPPLY FAN:

THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.)

MINIMUM RUNTIME.

ALARMS SHALL BE PROVIDED AS FOLLOWS (ALARMS SHALL BE SENT TO THE EXISTING BAS):

SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

SUPPLY AIR DUCT STATIC PRESSURE CONTROL:

THE CONTROLLER SHALL MONITOR DUCT STATIC PRESSURE SIGNAL FROM EXISTING BAS SYSTEM AND MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT. THE SPEED SHALL NOT DROP BELOW 30% (ADJ.). THE STATIC PRESSURE SETPOINT SHALL BE RESET BASED UPON THE POSITION OF THE ZONE DAMPERS, WITH A GOAL OF REDUCING THE STATIC PRESSURE

UNTIL AT LEAST ONE VAV DAMPER IS NEARLY WIDE OPEN.

THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE 1.5 IN H2O (ADJ.).

IF NO VAV DAMPER IS NEARLY WIDE OPEN, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 1.3 IN H2O (ADJ.) .

AS ONE OR MORE DAMPERS NEARS THE WIDE OPEN POSITION, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 1.8 IN H2O (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.

LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.

SUPPLY FAN VFD FAULT.

EXHAUST FAN:

THE EXHAUST FAN SHALL RUN WHENEVER THE SUPPLY FAN RUNS.

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

EXHAUST FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

EXHAUST FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

EXHAUST FAN VFD FAULT.

BUILDING STATIC PRESSURE CONTROL:

THE CONTROLLER SHALL MONITOR BUILDING STATIC PRESSURE SIGNAL PROVIDED BY EXISTING BAS AND MODULATE THE RETURN FAN VFD SPEED TO MAINTAIN A BUILDING STATIC PRESSURE SETPOINT

OF 0.05IN H2O (ADJ.). THE RETURN FAN VFD SPEED SHALL NOT DROP BELOW 20% (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH BUILDING STATIC PRESSURE: IF THE BUILDING AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.

LOW BUILDING STATIC PRESSURE: IF THE BUILDING AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.

SUPPLY AIR TEMPERATURE SETPOINT - OUTSIDE AIR RESET:

THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL RESET SUPPLY AIR TEMPERATURE SETPOINT RESET BASED ON OUTSIDE AIR TEMPERATURE.

THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET FOR COOLING AS FOLLOWS:

AS OUTSIDE AIR TEMPERATURE RISES FROM 50°F (ADJ.) TO 85°F (ADJ.)

THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET DOWNWARDS FROM 65°F (ADJ.) TO 55°F (ADJ.).

IF THE RETURN AIR TEMPERATURE DROPS BELOW 68°F (ADJ.), THEN THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR HEATING AS FOLLOWS:

AS OUTSIDE AIR TEMPERATURE DROPS FROM 50°F (ADJ.) TO 20°F (ADJ.).THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET UPWARDS FROM 75°F (ADJ.) TO 95°F (ADJ.)

COOLING:

THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COOLING TO MAINTAIN ITS COOLING SETPOINT.

THE COOLING SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).

AND THE ECONOMIZER IS DISABLED OR FULLY OPEN.

AND THE SUPPLY FAN STATUS IS ON.

AND THE HEATING IS NOT ACTIVE.

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN SETPOINT.

HEATING:

THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND STEP THE GAS VALVE TO MAINTAIN ITS HEATING SETPOINT.

THE HEATING SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).

AND THE SUPPLY FAN STATUS IS ON.

AND THE COOLING IS NOT ACTIVE.

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) LESS THAN SETPOINT.

ECONOMIZER:

THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE MIXED AIR DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.

THE ECONOMIZER SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).

AND THE OUTSIDE AIR ENTHALPY IS LESS THAN 22BTU/LB (ADJ.)

AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE.

AND THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY.

AND THE SUPPLY FAN STATUS IS ON.

THE ECONOMIZER SHALL CLOSE WHENEVER:

THE FREEZESTAT IS ON.

OR ON LOSS OF SUPPLY FAN STATUS.

THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE MIXED AIR DAMPER SHALL OPEN WHEN THE UNIT IS OFF.

MINIMUM OUTSIDE AIR VENTILATION - CARBON DIOXIDE (CO2) CONTROL:

WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL MEASURE THE RETURN AIR CO2 CONCENTRATION AND MODULATE THE OUTSIDE AIR DAMPERS OPEN ON RISING CO2 CONCENTRATIONS, OVERRIDING NORMAL DAMPER OPERATION TO MAINTAIN A CO2 SETPOINT OF 750 PPM (ADJ.).

OPTIMAL START (HEATING AND COOLING):

THE UNIT SHALL START PRIOR TO SCHEDULED OCCUPANCY ON A SIGNAL FROM THE EXISTING BAS AS NECESSARY FOR THE ZONES TO REACH THEIR OCCUPIED SETPOINTS. DURING HEATING THE SUPPLY AIR DISCHARGE SETPOINT SHALL BE 100 DEG F (ADJ.) AND DURING COOLING 55 DEG F (ADJ.) THE UNIT SHALL REMAIN IN THIS MODE UNTIL THE SIGNAL IS NO LONGER RECEIVED FROM THE

EXISTING BAS,

DEHUMIDIFICATION:

THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND OVERRIDE THE COOLING SEQUENCE TO RUN THE COOLING COMPRESSOR AND MODULATE THE HOT GAS REHEAT TO MAINTAIN RETURN AIR HUMIDITY AT OR BELOW 60% RH (ADJ.). WITHOUT COMPROMISING THE SUPPLY AIR SETPOINT. DEHUMIDIFICATION SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON.

FILTER DIFFERENTIAL PRESSURE MONITOR:

THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER.

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

MIXED AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE MIXED AIR TEMPERATURE AND USE AS REQUIRED FOR ECONOMIZER CONTROL OR PREHEATING CONTROL

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).

LOW MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).

RETURN AIR HUMIDITY:

THE CONTROLLER SHALL MONITOR THE RETURN AIR HUMIDITY AND USE AS REQUIRED FOR ECONOMIZER CONTROL OR HUMIDITY CONTROL

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH RETURN AIR HUMIDITY: IF THE RETURN AIR HUMIDITY IS GREATER THAN 70% (ADJ.).

RETURN AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE RETURN AIR TEMPERATURE AND USE AS REQUIRED FOR SETPOINT CONTROL OR ECONOMIZER CONTROL (IF PRESENT).

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).

LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).

SUPPLY AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.

ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)

HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).

LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).

AI

SA TEMP

AI

FILTER STATUS

H L

EF

BI

SUPPLY FAN

STATUS

L H

AI

OA PRESS

L H

SPACE PRESS

BO SUPPLY FAN VFD START/STOPS/S

AO SUPPLY FAN VFD SPEEDSPD

BI

EXHAUST FAN

STATUS

HL

BOEXHAUST FAN VFD START/STOP S/S

AOEXHAUST FAN VFD SPEED SPD

BO S/S

BO

MODULATION

VALVE

GAS

AO

CONDENSER

C

DX

AI

MIXED AIR TEMP

AI

RA TEMP

AI

RA HUMIDITY

AO

MIXED AIR

DAMPERS

EF VFD

SF VFD

AI

OA HUMIDITY

AI

OA TEMP INTLK

LOW LIMIT

BI

FROM EX.

BAS

BO

BO

BO

AI

RA CO2

AI

H L

DUCT PRESSURE

(FROM EX. BAS)

BI

S

OCCUPANCY

(FROM EX. BAS)

AO

HGR

BI

SMOKE

DETECTOR

S

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:0

9:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.rv t

M-602

M E

C H

A N

IC

A

L D

IA

G

R A

M S

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

EX. DUCT DETECTOR

IS IN DUCT AND NOT

PROVIDED WITH UNIT.

CABLE TV, TELEPHONE,

DATA OR DUPLEX RECEPT

OUTLET (UNLESS NOTED)

TOP OF

COUNTER

BASEBOARD RADIATOR

FIRE ALARM

HORN/SPEAKER/STROBE

SWITCHES,

THERMOSTAT, WALL

OCCUPANCY SENSOR,

FIRE ALARM PULL

STATION

FLOOR

ELECTRIC WATER COOLER

CEILING

CL

7'

4'

6" M

IN

ELECTRICAL OUTLET

6"

6"

CL

/4

RECOMMENDATIONS

PER MANUFACTURERS

PANEL BOARD

POWER CIRCUIT WIRING

UNDERGROUND WIRING

SWITCH LOOP WIRING

UN-SWITCHED HOT WIRING

LOW VOLTAGE WIRING

DATA WIRING

PROPOSED EXISTING DEMOLISH

TYPICAL 3⌀ 4-WIRE

DRY-TYPE UTILITY

TRANSFORMER

T-X

TYPICAL 3⌀ 4-WIRE

DRY-TYPE TRANSFORMER

SERVICE FROM SERVICE PANEL

T-X

BRANCH PANEL

CONNECTIONS BY

UTILITY

SUPPLY-SIDE

BONDING JUMPER

SERVICE

PANEL

G

NEU. NEU.

G

BRANCH PANEL

GROUNDED CONDUCTOR

GROUNDING ELECTRODE

CONDUCTOR

GROUNDING ELECTRODE

REFER TO NOTE 2

EQUIPMENT GROUNDING

CONDUCTOR

MAIN BUILDING JUMPER

GRADE

GROUNDED CONDUCTOR SYSTEM BONDING

JUMPER

SUPPLY-SIDE

BONDING

JUMPER

SEPARATELY DERIVED SYSTEM

G

NEU.

1. SIZE GROUNDING/BONDING CONDUCTORS PER NEC ARTICLE 250

2. GROUNDING ELECTRODE SYSTEM AS PER NEC ARTICLE 250 SECTION III.

NOTES

1. ALL ELECTRICAL INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE, CURRENT STATE OF MICHIGAN ELECTRICAL

CODE (PART 8), AND ANY LOCAL AMENDMENTS.

2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACQUISITION OF AN ELECTRICAL PERMIT AND SCHEDULING OF THE NECESSARY INSPECTIONS. UPON COMPLETION OF THE WORK THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE OWNER EVIDENCE OF INSPECTION APPROVAL.

3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION REQUIRED WITH THE ELECTRIC UTILITY SERVING THE FACILITY. UTILITY

COSTS SHALL BE PAID SEPARATELY BY THE OWNER.

GENERAL NOTES - ELECTRICAL

SURFACE / CEILING MOUNT

EMERGENCY SURFACE / CEILING

MOUNT

PENDANT / CHAIN MOUNT

EMERGENCY PENDANT / CHAIN

MOUNT

RECESSED MOUNT

EMERGENCY RECESSED MOUNT

COMBINATION FAN / LIGHT

TRACK STRIP

WALL MOUNT

EMERGENCY WALL MOUNT

EXTERIOR POLE MOUNT

EXTERIOR POST MOUNT

EMERGENCY WALL PACK

EXIT SIGN

CEILING FAN

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

COMBINATION MOTOR STARTER

WITH DISCONNECT SWITCH

MOTOR STARTER

ELECTRICAL METER

DISTRIBUTION PANEL

ELECTRICAL POWER PANEL

SURFACE MOUNT

ELECTRICAL POWER PANEL

FLUSH MOUNT

LIGHITNG CONTROL PANEL

RELAY

ELECTRICAL TRANSFORMER

ELECTRICAL PULL BOX

JUNCTION BOX

SINGLE PHASE MOTOR

THREE PHASE MOTOR

VARIABLE FREQUENCY DRIVE

X = NUMBER AND TYPE OF PORTS

C COAXIAL PORT

D DATA PORT

H HDMI PORT

P PHONE PORT

W WIRELESS ACCESS POINT

X

X H Z

SENSORS

J J

PC

IC

PS

K

CR

DL

M

R

A

CO

HD

F F

F F

F

T

PB

1. MINIMUM SIZE OF RIGID CONDUIT SHALL BE 3/4".

2. MINIMUM SIZE OF FLEX CONDUIT SHALL BE 1/2".

3. MINIMUM SIZE WALL BOX IN CMU SHALL BE

4"X4".

4. MINIMUM SIZE OF UNDERGROUND CONDUIT

SHALL BE 1 1/4".

5. CONDUIT AND CONDUCTORS NOT CALLED OUT

ON PLANS SHALL BE 3/4" CONDUIT

w/(2) #12AWG + #12 GND, UNO.

J

(WALL) (CEILING)

NURSE

N

N

FACP

FAA

FS

TS

PS

DH

C

P

(LIGHT)(NO LIGHT)

CARD READER

MAGNETIC SWITCH (DOOR CONTACT)

ELECTRONIC DOOR LOCK

MOTORIZED DOOR OPERATOR

ELECTRIC STRIKE

KEYPAD ENTRY DEVICE

ENTRANCE CALL SYSTEM

SECURITY CAMERA

PANIC ALARM SPEAKER/STROBE

ES

DP##

PP##

PP##

(WALL)

(CLG)

(FLR)

B

M

WG

F F

HSS

OUTDOOR BELL / CHIME

SMOKE DETECTOR

SMOKE DETECTOR WITH AUDIBLE BASE

SMOKE/CARBON MONOXIDE DETECTOR

DUCT SMOKE DETECTOR

HEAT DETECTOR

FIRE ALARM HORN/STROBE

FIRE ALARM STROBE

FIRE ALARM SPEAKER

FIRE ALARM SPEAKER/STROBE

FIRE ALARM PULL STATION

ELECTROMAGNETIC DOOR HOLD OPEN

END OF LINE RESISTOR

FIRE ALARM FLOW SWITCH

FIRE ALARM PRESSURE SWITCH

FIRE ALARM TAMPER SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

HOOD SUPPRESSION SYSTEM FIRE ALARM

CONTACT

ELR

I/C

DC

DO

SWITCHES: X = DESIGNATION BELOW

H = HUB CONTROLLER

Z = LIGHTING ZONE

PUSH BUTTON

EMERGENCY STOP BUTTON

PHOTOCELL

CEILING MOUNTED PULL SWITCH

WIRELESS NETWORK LIGHTING CONTROLLER

(HUB) H# = CONTROLLER INDICATOR

LIGHTING CONTROL SCHEME NUMBER

SINGLE POLE

2 TWO POLE

3 THREE WAY

4 FOUR WAY

DM DIMMER

F FAN

K KEY OPERATED

LV LOW VOLTAGE

M MOTION DETECTION

O OCCUPANCY SENSOR

P PILOT LIGHT

T TIMER

F F

S S

X

X X

(FURN)

SPEAKER

INTERCOM CALL BOX

BELL

MICROPHONE JACK

POWER SUPPLY

REQUIRES WIRE GUARD

NURSE CALL MAIN PANEL

NURSE CALL PULL STATION

NURSE CALL LIGHT

CLOCK

SIMPLEX RECEPTACLE

DUPLEX GROUNDED RECEPTACLE

208/240/480V, 1ϕ STRAIGHT BLADE RECEPTACLE

QUADRUPLEX RECEPTACLE

DUPLEX RECEPTACLE ON EMERGENCY POWER

FLOOR BOX

CEILING BOX

SPECIALTY RECEPTACLE

CTR MOUNTED ABOVE COUNTER

G GROUND FAULT CIRCUIT INTERRUPTER

GC GFCI - MOUNTED ABOVE COUNTER

T TAMPER-PROOF

U DUAL USB PORTS

UC DUAL USB PORTS ABOVE COUNTER

WP WEATHERPROOF RECEPT & COVER, GFI

H##

D DAYLIGHT

M MOTION DETECTION

O OCCUPANCY

V VACANCY

H = HUB CONTROLLER

Z = LIGHTING ZONE

XS X

H Z

S X H Z

LP##

(CEILING) (WALL)

(CEILING) (WALL)

(CEILING)

(WALL)

(WALL)(CLG)

(CLG) (WALL) (FLR)

ELECTRICAL SYMBOLS LEGEND

VFD

XX-X EQUIPMENT INDICATOR

INDICATES EXISTING

e LF-1

H Z

LIGHT FIXTURE INDICATOR

HUB CONTROLLER

LIGHTING ZONE

e

RACEWAY / CONDUCTOR NOTES

WIRES

OTHER SYMBOLS

TELEPHONE/COMMUNICATIONS

FIRE ALARM SYSTEMRECEPTACLE OUTLETS

SECURITY

POWER DISTRIBUTION

LIGHT FIXTURES

SWITCHES

(360 VIEW)

P P

SX

(W/ LIGHTS)

(INT.) (EXT.)

(INT.) (EXT.)

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

8/ 1/

:1

0:

P M

A ut od es k D oc s:

//7

6-

-0

E sc an ab a

S O

B R

T U

R ep l/7

0_

F P

M E

_E sc an ab aS O

B _R

T U

_2

3_ C

E N

.r vt

E-001

E

LE

C T

R

IC

A L

N O

T E

S A

N D

S Y

M B

O

LS

Lu di ng to n S t, E sc an ab a, M I 4

E S

C A

N A

B A

S T

A T

E O

F F

IC

E

B U

IL

D

IN

G

R O

O F

T O

P U

N

IT

R E

P

LA

C E

M E

N T

B

ID

S

-2 4-

LM

/0 8/

1/

8.

JB

B

D T

M B

F ile

N o.

N.T.S

TYPICAL MOUNTING HEIGHTS

ELECTRICAL

ABBREVIATIONS

_SPECIAL

Φ PHASE

A

A AMPERE

AFF ABOVE FINISHED FLOOR

C

C CONDUIT

CAT CATALOGUE

CB CIRCUIT BREAKER

CKT CIRCUIT

CMU CONCRETE MASONRY UNIT

CO. COMPANY

CUH CABINET UNIT HEATER

E

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EWC ELECTRIC WATER COOLER

F

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

G

G GROUND FAULT CIRCUIT

INTERRUPTER

GND EQUIPMENT GROUND

H

HVAC HEATING VENTILATING & AIR

CONDITIONING

K

K KEY OPERATED DEVICE

KVA KILOVOLT-AMPERES

KW KILOWATTS

L

LED LIGHT EMITTING DIODE

M

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MTD MOUNTED

N

NEU NEUTRAL

No. NUMBER

P

PL PILOT

R

RECEPT RECEPTACLE

T

TEL TELEPHONE

TV TELEVISION

TYP TYPICAL

U

UGE UNDERGROUND ELECTRIC

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V

V VOLT

VA VOLT-AMPERES

W

W WIRE

WAP WIRELESS ACCESS POINT

WP WEATHERPROOF

X

XFMR TRANSFORMER

N.T.S

GROUNDING BONDING DIAGRAM

EP1

MDP1

MDP2

SECRETARY OF STATE

SOS STOR.

SOS BREAK

SOS MANAGER

SOS VIDEO

SOS DEALER

H.C. ACCESS RAMP

ENTRY

MECHANICAL

FIA

CORRIDOR

WORKMAN'S COMP

108CONFERENCE

SERVER

MEN

WOMEN

BREAK ROOM

JANITOR

PASSAGE

CORRIDOR

Room

FIA CONF.

FIA BLIND

LOBBY

VESTIBULE

EXISTING PANELS TO REMAIN.

RE-FEED FROM NEW PANEL MDP

PDP

EXISTING PANELS TO REMAIN,

RE-FEED FROM NEW PANEL PDP

200A FUSED DISCONNECT

1. DRAWINGS SHOW MAJOR DEMOLITION ONLY; THE CONTRACTOR SHALL PROVIDE ALL DEMOLITION

FOR THE COMPLETION OF THE WORK WHETHER EXPLICITLY SHOWN OR NOT.

2. THE OWNER RESERVES THE RIGHT TO KEEP ANY REMOVED EQUIPMENT OR MATERIALS. ALL

DEMOLITION DEBRIS TO BE REMOVED FROM THE SITE AND DISPOSED OF IN AN APPROVED LANDFILL.

3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TEMPORARY EXTERIOR OPENINGS MADE FROM

DEMOLITION WORK TO ENSURE THEY ARE WEATHER TIGHT AT THE END OF EACH DAY.

4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING WHERE CONDUITS AND

JUNCTION BOXES ARE REMOVED UNLESS OTHERWISE NOTED.

5. ANY JUNCTION BOXES REMAINING IN PLACE THAT HAVE HAD DEVICES…

This is the start of the file's text. The full file is on GovTribe.