171.24438.JBB_EscanabaRTUReplacement_Plans_Bidding.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ-171-250000000582-3
- Issued by
- Delta County, Edmore Village, Michigan
About this file
These documents are construction bid documents for the Rooftop Unit Replacement project for the Michigan State Office Building located at 305 Ludington St, Escanaba, MI, prepared by OHM Advisors for the Department of Technology, Management and Budget (DTMB) State Facilities Administration Design and Construction Division. The project involves replacing the existing rooftop unit (RTU-1) with a new Carrier 48K3HM30 rooftop unit, which will serve multiple floors and rooms totaling approximately 23,800 square feet. The bid documents are dated August 1, 2025, with a project number of 7136-24-0110 and DTMB File No. 171/24438.JBB.
The new rooftop unit is specified with detailed technical requirements, including a 13,500 CFM supply air capacity, 1,900 CFM outside air, 15 HP supply fan, DX cooling with 312 MBH total capacity, and an 800 MBH gas heating section. The unit will feature multi-stage high gas heat, digital scroll modulating cooling, variable frequency drives, 100% comparative enthalpy economizer, hot gas reheat coil, and BACnet control interface. Electrical and mechanical plans indicate the replacement will involve removing existing equipment, preparing new roof curbs, connecting gas and electrical services, and integrating with the building's existing Building Automation System. The project scope includes comprehensive demolition, installation, and system integration work to ensure minimal disruption to the state office building's operations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION MAP
PROJECT LOCATION
ROOFTOP UNIT REPLACEMENT
ISSUED: 2025/08/01
BIDS
OHM PROJECT NO. 7136-24-0110
DTMB File No. 171/24438.JBB
305 Ludington St, Escanaba, MI 49829
ESCANABA STATE OFFICE BUILDING
DRAWING INDEX
N U
M B
E R
SHEET NAME 0
/0 /0
B
ID
S
GENERAL
G-000 COVER & DRAWING INDEX •
ARCHITECTURAL
A-111 ROOF PLAN •
MECHANICAL
M-001 MECHANICAL NOTES AND SYMBOLS •
MD101 ROOF MECHANICAL DEMOLITION PLAN •
M-101 FIRST FLOOR MECHANICAL PLAN •
M-102 SECOND FLOOR MECHANICAL PLAN •
M-103 ROOF MECHANICAL PLAN •
M-601 MECHANICAL SCHEDULES •
M-602 MECHANICAL DIAGRAMS •
ELECTRICAL
E-001 ELECTRICAL NOTES AND SYMBOLS •
EDP101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN •
EDP102 ROOF ELECTRICAL DEMOLITION PLAN •
EP101 FIRST FLOOR POWER PLAN •
EP102 ROOF POWER AND LOW VOLTAGE PLAN •
E-501 ELECTRICAL DETAILS •
MICHIGAN STATE OFFICE BUILDING
BEN JOHNSON
305 LUDINGTON ST
ESCANABA, MI 49829
(906)-786-5394
JOHNSONB29@MICHIGAN.GOV
OWNER
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
G-000
C O
V E
R
D R
A W
IN
G
IN
D
E X
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
I Certify That The Architectural Plans Were Prepared Under My Direct Supervision
2. [PLACEHOLDER]
1. [PLACEHOLDER]
SCHEDULE NOTES:
REQUIRED BY CONTRACTOR R
PERMIT OBTAINED O
APPLICATION DATE: APPLICATION TYPE: PERMIT NO.: APPLICATION STATUS:
SCHEDULE KEY:
PLAN REVIEW / PERMIT SUBMISSIONS
APPLICATION
DATE APPLICATION TYPE PERMIT NO.
APPROVAL
DATE STATUS
[MM/DD/YYYY] BUILDING [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R
[MM/DD/YYYY] ELECTRICAL [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R
[MM/DD/YYYY] MECHANICAL [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R
[MM/DD/YYYY] PLUMBING [LARA] [PERMIT NUMBER] [YYYY/MM/DD] R
I Certify That The Mechanical & Electrical Plans Were Prepared Under My Direct Supervision
WP
CLCL
X-XXX
SIM
ROOF SLOPE
EXISTING ROOF DRAIN
(UNSHADED) INDICATES AREA OF EXISTING FULLY ADHERED FLEECE BACKED
EPDM MEMBRANE ON RECOVERY BOARD ON TAPERED INSULATION
ERD
ROOF LEGEND
e1 eA e12 e11 e10 e9 e8 e7 e6 e5 e4 e3 e2 eB eC
ERD
ERD
ERD
ERDERDERDERDERD
A-111
HVAC EQUIPMENT - REFER TO MEP
EXISTING CURB TO REMAIN
LAYDOWN AREA
1. COORDINATE PENETRATIONS AND ROOF MOUNTED EQUIPMENT WITH MECHANICAL, PLUMBING,
ELECTRICAL AND STRUCTURAL DRAWINGS
2. ALL ROOF PENETRATIONS SHALL BE SEALED WITH APPROPRIATE MATERIAL
3. ALL EXPOSED METAL ELEMENTS TO BE PRE-FINISHED. COLOR AS SELECTED BY ARCHITECT
4. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION ON FINISHES & INSTALLATION
REQUIREMENTS
GENERAL NOTES - ROOF PLAN
NOTE:
COORDINATE W/ SPECIFICATIONS,
MECHANICAL EQUIPMENT
MANUFACTURER'S INSTALLATION
INSTRUCTIONS, & EXISTING
MEMBRANE SYSTEM
REQUIREMENTS
VIF
VARIES
EXISTING METAL DECK & OPENING FRAMING
EXISTING TAPERED INSULATION
EXISTING CURB TO REMAIN
LAP SPLICE SEALANT
EXISTING ROOF MEMBRANE OVER CURB TO REMAIN
EPDM ROOF MEMBRANE WRAPPED OVER PRE-
FABRICATED INSULATED CURB. SEAL TO EXISTING ROOF
MEMBRANE & MAINTAIN EXISTING ROOF WARRANTY
METAL COUNTER FLASHING
WOOD NAILER
SEALANT - CONTINUOUS AROUND TOP OF CURB
ROOF TOP UNIT - REFER TO MECHANICAL
PRE-FABRICATED INSULATED CURB - REFER TO MECHANICAL
1/2"
8" M
IN
IM
U M
F
LA
S H
IN
G
H E
IG
H
T
1. DO NOT SCALE DRAWINGS. IF DIMENSIONS CANNOT BE DETERMINED OR DOCUMENTS ARE IN
CONFLICT, THE CONTRACTOR SHALL OBTAIN CLARIFICATION FROM THE ARCHITECT PRIOR TO
CONTINUATION OF WORK
2. ALL WALL DIMENSIONS ARE TO FACE OF STUD OR MASONRY, UNO.
3. FIELD VERIFY ALL PROJECT CONDITIONS PRIOR TO THE START OF WORK, AND AS NEEDED
THROUGHOUT THE DURATION OF CONSTRUCTION. BRING ANY DISCREPANCIES WHICH MAY
SIGNIFICANTLY AFFECT NEW CONSTRUCTION WORK TO THE ATTENTION OF THE ARCHITECT FOR
REVIEW
4. ALL WOOD BLOCKING AND BACKING SHALL BE FIRE-RETARDANT TREATED, UNO
5. INFORMATION SHOWN IN ONE LOCATION ON THE DRAWINGS IS THE SAME AS IF SHOWN ON MULTIPLE
LOCATIONS
6. TYPICAL CONDITIONS ARE NOTED ONLY ONCE
7. COORDINATE OPENINGS AND PENETRATIONS BETWEEN TRADES
GENERAL NOTES - ARCHITECTURAL
ALUMINUM
CONCRETE
BATT INSULATION
WOOD
ROUGH WOOD
RIGID INSULATION
SHIM
ACOUSTICAL TILE
EARTH / COMPACT FILL
POROUS FILL
CONCRETE MASONRY
UNITS
FACE BRICK
PLYWOOD
STEEL
GYPSUM WALL BOARD
8x8 TILE
12x12 TILEWOOD BOARD
SIDING NARROW
WOOD BOARD
SIDING WIDE
4x4 TILE
MATERIAL SYMBOL LEGEND
NATURAL STONE
CAST STONE
MINERAL WOOL
INSULATION
DETAIL INDICATOR
SECTION DETAIL
INDICATOR
PLAN NORTH
TRUE NORTH
MATCHLINE
SEE 1 / A101
N
NEW CONSTRUCTION
NEW MASONRY CONSTRUCTION
EXISTING TO REMAIN
EXISTING TO BE REMOVED
DOORS
CENTER LINE
ELEVATION MARK
MATCHLINE
EXISTING GRID LINE
PROPOSED GRID LINE
BUILDING LINE
INDICATES EXISTING
SHEET KEYNOTE INDICATOR
REVISION INDICATOR
NORTH INDICATOR
e
CLEARANCE LINES
XX
ARCHITECTURAL SYMBOLS LEGEND
BL1
LEVEL
XXX' - XX"
e1
X-XXX
INDICATOR LINES BUILDING ELEMENTS
NOTES & ANNOTATIONSVIEW REFERENCES
8" TO 12" GRANULAR MATERIAL MDOT
CLASS II (COMPACTED TO 95%)
6" MDOT 22A OR 2AA AGGREGATE
(COMPACTED TO 98%)
1 1/2" MDOT 4EL BASE COURSE
1 1/2" MDOT 5EL TOP COURSE
PERMANENT HMA APPLICATION CHART
SYMBOL PAY ITEM
RATE
(LB/SYD)
DEPTH
(IN)
PERFORMANCE
GRADE
REMARKS
HMA, 5EL
HMA, 4EL
165 LB
220 LB
1.5
1.5
58-34
58-34
TOP COURSE, AWI - 260 MINIMUM
BASE COURSE
0.05 - 0.15
GAL/SYD
TYPE
SS-1h
BOND COAT - TO BE APPLIED
BETWEEN EACH LIFT OF NEW
PERMANENT HMA
5EL
4EL
SUITABLE MATERIAL EXCAVATED FROM
TRENCH (OTHER THAN WET UNSTABLE CLAY)
WARNING TAPE
GRANULAR MATERIAL MDOT
CLASS II OR CLASS IIIA
(COMPACTED TO 95%)
UTILITIESTRENCH WIDTH
4"
M
IN
B E
D D
IN
G
M
IN
EXISTING GROUND
HMA PAVEMENT
WARNING TAPE
GRANULAR MATERIAL MDOT
CLASS II OR CLASS IIIA
(COMPACTED TO 95%)
UTILITIESTRENCH WIDTH
4" M
IN
B
E D
D
IN
G
IN
EXISTING GROUND
EXISTING HMA
EXISTING HMA
EXISTING HMA
EXISTING HMA
6" MDOT 22A OR 21AA
AGGREGATE (COMPACTED TO
95%)
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:2
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
S A
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.r vt
A-111
R O
O F
P
LA
N
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
N
3/32" = 1'-0"1
ROOF PLAN
1 1/2" = 1'-0"2
MEMBRANE ROOF MECHANICAL CURB DETAIL
ABBREVIATIONS
A
& AND
@ AT
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
C
CL CENTER LINE
D
DN DOWN
DS DOWNSPOUT
E
EJ EXPANSION JOINT
EQ EQUAL
EXST EXISTING
H
HVAC HEATING-VENTILATING-AIR
CONDITIONING
M
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
N
NA NOT APPLICABLE
ABBREVIATIONS
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
No. NUMBER
NTS NOT TO SCALE
O
OC ON CENTER
OPP OPPOSITE
OPP HND OPPOSITE HAND
R
RD ROOF DRAIN
S
SF SQUARE FOOT
SIM SIMILAR
T
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
VIF VERIFY IN FIELD
W
W/ WITH
W/O WITHOUT
N.T.S4
TYP HMA SECTION
3/4" = 1'-0"3
TRENCH DETAILS FOR UTILITIES
AD
AD
D
A
PLAN
ELEVATION
1/2", 1" & 2" WG
CFM PER 100 SQ FT @ 1" WG
SEAL CLASS C
RECTANGULAR DUCT 24
ROUND DUCT 12
SHEET METAL
SCREWS (TYP)
BAND OF SAME
SIZE AS HANGER
STRAP
HANGER
STRAP
ANGLE
SIZE BOLT(S)
FOR LOAD
ROD
DUCT DUCT DUCT
HANGER STRAP
RADIUS=1 1/2 xWIDTH OF DUCT
TURNING VANES AT
ALL MITERED ENDS
USE RADIUS ELBOW FOR ALL
DUCT 20" WIDTH AND LESS, IF
POSSIBLE
VOLUME DAMPERS AT
ALL TERMINAL TAKE-
OFFS, SUPPLY, RETURN
AND EXHAUST
VOLUME DAMPERS AT
ALL TERMINAL TAKE-
OFFS, SUPPLY, RETURN
AND EXHAUST
VOLUME DAMPERS
FOR BALANCING AT
ALL BRANCH TRUNKS
PREFERRED MAX
TRANSITION ANGLE
IN-DUCT COIL
PROVIDE ACCESS DOOR/PANEL
UPFLOW OF ALL IN-DUCT COILS
AND TURNING VANES
MIN DISTANCE OF STRAIGHT
DUCT FROM TRANSITIONS/
FITTINGS PRIOR TO TAKE-OFF
TYP ANGLE
UPFLOW, ALL
TAKE-OFFS
TYP ANGLE UPFLOW,
ALL TAKE-OFFS
FLOW
FLEX DUCT, 5 FT MAX
LENGTH, NO SHARP BENDS
SUPPLY DUCT ONLY
VOLUME DAMPERS
FOR BALANCING AT
ALL BRANCH TRUNKS
SEAL ALL DUCTS WATER
TIGHT WITHIN 15 LF OF ANY
FRESH AIR INTAKE OPENINGS
SUMP (PIPE TO DRAIN)
PITCH TO LOUVER
PARALLEL BLADE DAMPER
WHERE SHOWN ON PLANS
INTAKE LOUVER
EXTERIOR
WALL
SHEET METAL PLENUM
2.
5x
D U
C T
W
ID
T H
/D
IA
15'
1. ITEMS AS SHOWN ARE THE MINIMUM REQUIRED AND SHALL BE PROVIDED BY THE CONTRACTOR
WHETHER SHOWN ON THE FOLLOWING PLANS OR NOT.
2. LISTED DUCT SIZES INDICATE THE INSIDE CLEAR DIMENSIONS, NOT INCLUDING DUCT LINER.
3. ALL FLAT SURFACES ON DUCTS AND FITTINGS SHALL BE EITHER CROSS BROKE OR BEADED.
4. DUCT SEAMS SHALL BE EITHER PITTSBURG OR BUTTON LOCK.
5. STANDING RIB CLEATS ARE REQUIRED ON DUCTS HAVING WIDTHS OF 24" OR MORE.
6. ALL JOINTS IN SHEET METAL SHALL BE SEALED WITH AN APPROVED DUCT SEALANT.
7. ALL DAMPERS MUST HAVE A POSITION INDICATOR ON THE SHAFT.
8. DAMPERS GREATER THAN 8" IN WIDTH MUST BE OPPOSED BLADE.
FOLLOW SMACNA STANDARDS FOR HANGER TYPE, SIZING, GAUGE AND SPACING.
45°
15°
DUCTWORK REQUIREMENTS
DUCT SUPPORT DETAILS
NOTES
PRESSURE CLASS
ITEM THICKNESS TYPE REMARKS
1. ALL DUCTS WITHIN 25' OF MOTORS, INSTALL 1" MANVILLE LINO-COUSTIC DUCT LINER OR EQUAL, EXCLUDING OA DUCT.
2. EXPOSED DUCTWORK SHALL BE INSULATED WITH RIGID FIBERGLASS DUCT INSULATION AND JACKET.
INSULATION SCHEDULE
SUPPLY DUCT 1 1/2" FIBERGLASS TYPE ASJ
PROPOSED EXISTING DEMOLISH
EXHAUST AIR
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
RECTANGLE ROUND
DROP RISE DROP RISE
RECTANGLE ROUND
DROP RISE DROP RISE DROP RISE DROP RISE
RECTANGLE ROUND
12x12
12x12
12x12
12ø
12ø
12ø
12ø
12x12
12x12
12x12
12x12
12ø
12ø
12ø
12ø
12x12
12x12
12x12
12x12
12ø
12ø
12ø
12øEA12x12
OA
RA
SA
EA
OA
RA
SA
EA
OA
RA
SA SA
RA
OA
EA
NEW EXISTING DEMOLISH
NATURAL GAS 6"ø G6"ø G 6"ø G
1. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM
AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.
2. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION, ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT MAY AFFECT THE WORK.
3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS
OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS BEING RE-USED
OR ENLARGED IN THE RENOVATION WORK.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW" CONDITION DURING
CONSTRUCTION.
5. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.
6. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE FLEXIBLE DUCT CONNECTORS.
7. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA AIR GAP.
8. COORDINATE ROOF MOUNTED EQUIPMENT SIZES WITH ARCHITECTURAL TRADES PRIOR TO CONSTRUCTION.
9. ROOF OPENINGS SHALL BE SEALED WEATHER-TIGHT AND WITH ROOFING MATERIALS COMPATIBLE WITH EXISTING ROOF MEMBRANE. CONTRACTOR SHALL
NOT VOID ROOF WARRANTY.
10. DUCT ACCESS PANELS SHALL BE PROVIDED AT ALL FIRE DAMPERS, FIRE/SMOKE DAMPERS, MOTORIZED DAMPERS, AND DUCT SMOKE DETECTORS. WHERE
NECESSARY, CEILING ACCESS PANELS SHALL BE PROVIDED AS WELL.
11. INSTALL ALL NEW EQUIPMENT IN COMPLIANCE WITH THE MANUFACTURER'S REQURIED CLEARANCES. ALL DISCONNECTS AND LOW VOLTAGE ELECTRICAL
PANELS SHALL HAVE THE CLEARANCE REQUIRED BY NEC ARTICLE 110 (36" FOR 120/208V, 42" FOR 227/460V, AND 48" WHEN FACING ONE ANOTHER).
12. ROUTE ALL CONTROL WIRING TO THE THERMOSTATS AND VAV BOXES WITHIN THE SOFFITS AND WALLS WHEREVER POSSIBLE. WIRING IN ANY WALLS OR
EXPOSED SHALL BE IN CONDUIT. WHERE CONNECTING TO VAV BOXES IN EXPOSED AREAS, CONTROL WIRING SHALL BE RUN IN EXPOSED PAINTED CONDUIT.
CONDUIT COLOR SHALL BE COORDINATED WITH ARCHITECT.
GENERAL NOTES - MECHANICAL
HVAC SYMBOLS LEGEND
H
T
DUCTS
PIPING
DIFFUSERS, GRILLES, TAGS AND SYMBOLS
CEILING DIFFUSER
LINEAR SLOT DIFFUSER
WALL DIFFUSER /
GRILLE
FLOOR REGISTER
CEILING GRILLE
TRANSFER GRILLE
TURNING VANES
12x12 DUCT WIDTH x HEIGHT
12Ø ROUND DUCT DIAMETER
101.1
DIFFUSER INDICATOR
MARK
FLOW
EQUIPMENT TAG
KEYNOTE TAG
BREAK LINE
XX-X
DIGITAL INPUT TO THE
CONTROLLER
DIGITAL OUTPUT TO THE
CONTROLLER
ANALOG INPUT TO THE
CONTROLLER
ANALOG OUTPUT TO THE
CONTROLLER
RELAY
CURRENT SWITCH
PNUEMATIC DAMPER
ACTUATOR
SOLENOID VALVE FINNED TUBE OR
RADIANT PANEL
REFRIGERANT
COOLING COIL
HOT WATER
HEATING COIL
V D
MANUAL VOLUME
DAMPER
MOTORIZED DAMPERM
FIRE DAMPER
SMOKE DAMPER
SMOKE AND FIRE DAMPER
THERMOSTAT
HUMIDISTAT
CONNECT TO EXISTING
PIPE BREAK
AVERAGING
TEMPERATURE SENSOR
AVERAGING
TEMPERATURE SENSOR
PUMP
ELECTRIC TO PNUEMATIC
TRANSDUCER
PNUEMATIC TO ELECTRIC
TRANSDUCER
DIFFERENTIAL PRESSURE
SENSOR / SWITCH
SMOKE DETECTOR
AIR FLOW MEASURING
STATION
CHILLED WATER
COOLING COIL
GAS HEAT SECTION
CHECK VALVE
GATE VALVE
BALL VALVE
BUTTERFLY VALVE
2-WAY ELECTRONIC
CONTROL VALVE
3-WAY ELECTRONIC
CONTROL VALVE
2-WAY PNEUMATIC
CONTROL VALVE
3-WAY PNEUMATIC
CONTROL VALVE
RELIEF VALVE
CIRCUIT SETTER
BALANCE VALVE
TRIPLE DUTY VALVE
AIR VENT
MOTORIZED VALVE
OCCUPANCY SENSOR
CO2 SENSOR
FAN
FILTER BANK
DX
C
C
C
M
M
M
H
C
H L
R
AI
AO
BI
BO
CS
M
S
CO2
OCC
EP
PE
T
SD
GAS LOAD SCHEDULE
MARK DESCRIPTION BTU / HOUR CU FT / HOUR NOTE
B-1 GAS BOILER 750,000 723 1
B-2 GAS BOILER 750,000 723 1
RTU-1 GAS ROOF TOP UNIT 525,000 506 1
TOTALS: 2,025,000 1,952
NOTE: 1. GAS LINE SIZES BASED ON 7" WC DELIVERY PRESSURE.
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
M-001
M E
C H
A N
IC
A
L N
O T
E S
A N
D S
Y M
B O
LS
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
MECHANICAL
ABBREVIATIONS
A
A AIR
AAV AUTOMATIC AIR VENT
AD ACCESS DOOR/PANEL
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
AS AIR SEPARATOR
B
B BOILER
BDD BACK DRAFT DAMPER
BFP BACK FLOW PREVENTER
C
CFM CUBIC FEET PER MINUTE
CG CEILING GRID
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CND STEAM CONDENSATE
COND CONDENSING UNIT
CONV CONVECTOR
CR CONDENSATE RETURN
CUH CABINET UNIT HEATER
D
DB DRY BULB
DIA OR Ø DIAMETER
DN DOWN
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EF EXHAUST FAN
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F
FCU FAN COIL UNIT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FOOT / FEET
FTR FIN TUBE RADIATION
°F FAHRENHEIT DEGREE
G
G NATURAL / LP GAS
GA GAUGE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H
HC HOT WATER COIL
HP HORSEPOWER
HPS HIGH PRESSURE STEAM
HRU HEAT RECOVERY UNIT
HTWR HEATING WATER RETURN
HTWS HEATING WATER SUPPLY
HVAC HEATING VENTILATING & AIR
CONDITIONING
HX HEAT EXCHANGER
I
IN INCH / INCHES
K
KH KITCHEN HOOD
L
L LOUVER
LAT LEAVING AIR TEMPERATURE
LDB LEAVING DRY BULB
LF LINEAL FEET
LPS LOW PRESSURE STEAM
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
M
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPS
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MUA MAKE-UP AIR UNIT
MECHANICAL
ABBREVIATIONS
O
OA OUTSIDE AIR
P
P PUMP
PH OR Φ PHASE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
R
R SUPPLY REGISTER
RA RETURN AIR
RAD RADIANT HEATER
RD ROUND DIFFUSER
RF RETURN FAN
RH GRAVITY RELIEF HOOD
RPM REVOLUTIONS PER MINUTE
S
SA SUPPLY AIR
SC STEAM COIL
SD SMOKE DAMPER
SF SUPPLY FAN
SP STATIC PRESSURE
STD STANDARD
STM STEAM
SWG SIDE WALL GRILLE
SWR SIDE WALL REGISTER
T
TYP TYPICAL
U
UH UNIT HEATER
V
V VENT
VAV VARIABLE AIR VOLUME
VD VANED DIFFUSER
W
WH WATER HEATER
WPD WATER PRESSURE DROP
EX. CURB
EX. 1 1/2"ø G
E X
1/ 2" ø G
EX. VTR EX. VTREX. VTR
EX. VTR
EX. VTR
EX. VTR
REMOVE EXISTING GAS
SUPPORTS AND REPLACE
1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN
INTENT, COORDINATE WITH THE CM, AND PERFORM A CONSTRUCTABILITY ANALYSIS PRIOR TO
SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR
CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF COORDINATION.
2. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS
BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.
3. ANY DEVICE/EQUIPMENT NO LONGER NEEDED SHALL BE PROPERLY DISPOSED OF.
GENERAL NOTES - HVAC DEMOLITION
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
MD101
R O
O F
M E
C H
A N
IC
A
L D
E M
O
LI
T
IO
N P
LA
N
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
1/8" = 1'-0"1
ROOF MECHANICAL DEMOLITION PLAN
SHEET KEYNOTES - MECH. DEMOLITION
1 REMOVE ROOFTOP UNIT. DISCONNECT GAS AND CONTROL WIRING.
2 REMOVE UPPER ROOF CURB. PREP FOR NEW ROOF CURB.
3 REMOVE SECTION OF GAS LINE FOR PREPARATION OF NEW RTU.
LOBBY
VESTIBULE
BREAK ROOM
JANITOR
CORRIDOR
WOMEN
MEN
107WORKMAN'S COMP
SERVER
CONFERENCE
CORRIDOR
SOS DEALER
SOS VIDEO
SECRETARY OF STATE
SOS MANAGER
SOS STOR.
SOS BREAK
FIA
FIA CONF.
FIA BLIND
Room
PASSAGE
ENTRY
H.C. ACCESS RAMP
CORRIDOR
VAV-3
VAV-13
VAV-11
VAV-12
VAV-9
VAV-8
VAV-7
VAV-10 VAV-4
VAV-26 VAV-2
VAV-6
VAV-5
VAV-1
EX.44x14 SA
EX.36x12 SA
EX.78x14 RA
60x14
114.1
200 101.2
101.1
114.4
114.2
114.6
114.5
114.3
114.7
114.8
111.1
111.2
110.1
108.1
108.2
108.3
108.4
103.1
107.1
106.1
121.5
121.4
121.3
121.2
125119.1
120.1
125 121.1
118.3
118.6
118.2
118.5
118.1
118.4
117.1
116.1
115.1
112.1
113.1
1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN INTENT PRIOR TO SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF
COORDINATION.
2. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.
3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS
BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.
4. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.
5. SIZES INDICATED FOR EXISTING DUCTWORK AND PIPING ARE PER THE ORIGINAL DOCUMENTS. FIELD
VERIFY EXACT SIZES AND PROVIDE TRANSITIONS ACCORDINGLY.
6. COORDINATE LOCATIONS OF THE THERMOSTATS WITH OTHER TRADES.
GENERAL NOTES - MECHANICAL HVAC
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
M-101
F
IR
S T
F
LO
O R
M E
C H
A N
IC
A
L P
LA
N
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
1/8" = 1'-0"1
FIRST FLOOR MECHANICAL PLAN
NOTE:
THIS PLAN IS PROVIDED FOR
AIRFLOW BALANCING AND IS
FOR REFERENCE ONLY.
CONFERENCE
MEN'S
WOMEN'S
JAN.
STORAGE
CIS
OFFICES
BREAK ROOM
STAIR
REG. ACC.
CORRIDOR
VAV-25
VAV-24 VAV-22
VAV-18
VAV-17
VAV-14VAV-19VAV-27
VAV-20
VAV-16
VAV-21
VAV-23
EX.56x16 SAEX.50x20 SA
EX.114x16 RA
60x24
60x24
207.1
207.2
207.10
207.13
207.11
207.14
207.15
207.6
207.7
207.5
207.4
207.8
207.9
216.2
208.1
208.2
206.2
206.1
214.2
214.1
203.1
202.1
214.3
201.1
201.2
201.3
201.4
216.1
207.3
207.12
216.3
207.16
NOTE:
THIS PLAN IS PROVIDED FOR
AIRFLOW BALANCING AND IS
FOR REFERENCE ONLY.
EXISTING
BACNET
PANEL
1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN INTENT PRIOR TO SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF
COORDINATION.
2. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.
3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS
BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.
4. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.
5. SIZES INDICATED FOR EXISTING DUCTWORK AND PIPING ARE PER THE ORIGINAL DOCUMENTS. FIELD
VERIFY EXACT SIZES AND PROVIDE TRANSITIONS ACCORDINGLY.
6. COORDINATE LOCATIONS OF THE THERMOSTATS WITH OTHER TRADES.
GENERAL NOTES - MECHANICAL HVAC
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
M-102
S E
C O
N D
F
LO
O R
M E
C H
A N
IC
A
L P
LA
N
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
1/8" = 1'-0"1
SECOND FLOOR MECHANICAL PLAN
1. ALL BIDDING CONTRACTORS ARE REQUIRED TO FIELD VERIFY EXISTING CONDITIONS AND DESIGN INTENT PRIOR TO SUBMITTING A BID. QUESTIONS OR COMMENTS SHALL BE SUBMITTED IN WRITING DURING THE BIDDING PHASE. NO ADDITIONAL COSTS TO THE PROJECT WILL BE ACCEPTED AFTER PROJECT AWARD FOR CHANGES DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS OR LACK OF
COORDINATION.
2. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT THE INTENTION THE OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT SCALE FROM DRAWINGS.
3. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE PATCHING, CAPPING, OR REPAIRING OF WALLS, FLOOR, AND ROOF WHERE OPENINGS OCCUR AS A RESULT OF REMOVAL OF MECHANICAL AND ELECTRICAL COMPONENTS AS PART OF THIS CONTRACT, UNLESS THE OPENING IS
BEING RE-USED OR ENLARGED IN THE RENOVATION WORK.
4. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE AND BRANCH DUCT.
5. SIZES INDICATED FOR EXISTING DUCTWORK AND PIPING ARE PER THE ORIGINAL DOCUMENTS. FIELD
VERIFY EXACT SIZES AND PROVIDE TRANSITIONS ACCORDINGLY.
6. COORDINATE LOCATIONS OF THE THERMOSTATS WITH OTHER TRADES.
GENERAL NOTES - MECHANICAL HVAC
EX. 1 1/2"ø G
E X
1/ 2" ø G
NEW 1-1/2"ø GAS PIPING TO
UNIT CONNECTION. PROVIDE
ISOLATION BALL VALVE.
RTU-1
EX. VTR EX. VTREX. VTR
EX. VTR
EX. VTR
EXTEND 4"ø PLUMBING VENT
FROM ADJACENT TO INTAKE.
SEE DETAIL 2 / M-103
EX. VTR
3' - 6"
EXTEND 4"ø PLUMBING
VENT TO 3' 0" ABOVE
NEW RTU.
EX. CURB
SUPPORT GAS PIPING
PER SPECIFICATION WITH
FACTORY MANUFACTURED
SUPPORT SYSTEM.
EVERY 10 FT OR WITHIN
4 FT OF ANY FITTING.
SEE DETAIL 2 / M-103
RS-485 CABLE FROM
UNIT TO EX. BAC NET
PANEL FOR MS/TP
COMMUNICATIONS.
EX. VENT
NEW SECTION OF OFFSET
VENT (PVC)
EXTEND TO 3'
ABOVE NEW UNIT
1-5/8" VERTICAL UNISTRUT BOTH
SIDES OF PIPE. CLAMP PIPE TO
UNISTRUT.
8" LONG ROOF SUPPORT
MOUNTING BLOCK
ROOF LINE
3'-6"
ROOF LINE
8" C-PORT
RUBBER BLOCK
OR SIMILAR
MOULDED STRUT
MOUNT
GAS PIPE
PIPE CLAMP
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
M-103
R O
O F
M E
C H
A N
IC
A
L P
LA
N
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
1/8" = 1'-0"1
ROOF MECHANICAL PLAN
N.T.S2
VENT THRU ROOF OFFSET DETAIL
N.T.S3
GAS SUPPORT DETAIL
ROOM VENTILATION DATA - RTU-1
REQUIRED
EXHAUST FLOW
(CFM/SQFT)
REQUIRED EXHAUST
FLOW (CFM/PLUMBING
FIXTURE)
PLUMBING
FIXTURE
QUANTITY
REQUIRED
EXHAUST AIR
(CFM)
PROVIDED
EXHAUST AIR
(CFM)
OCCUPANTS/1
000 SQFT
NUMBER OF
OCCUPANTS
RA
CFM/SQFT
RP CFM/
OCCUPANT
REQUIRED
OUTDOOR
AIRFLOW
(RA+RP)
(CFM)
PROVIDED
OUTDOOR
AIRFLOW
(CFM)ROOM SQFT
BREAK ROOM 103 125 0 0 0 0 0 25 3 0 5 23
BREAK ROOM 208 310 0 0 0 0 0 25 8 0 5 57
CIS OFFICE 206 318 0 0 0 0 0 5 2 0 5 27
CONFERENCE ROOM 110 238 0 0 0 0 0 50 12 0 5 74
CONFERENCE ROOM 201 1000 0 0 0 0 0 50 50 0 5 310
CONFERENCE ROOM 201 CIRC
SPACE 460 0 0 0 0 0 0 0 0 0 28
CORRIDOR 207B 905 0 0 0 0 0 0 0 0 0 54
CORRIDOR 105 1330 0 0 0 0 0 0 0 0 0 80
CORRIDOR 207A 1246 0 0 0 0 0 0 0 0 0 75
CORRIDOR 214 906 0 0 0 0 0 0 0 0 0 54
CORRIDOR SOS 114A 87 0 0 0 0 0 0 0 0 0 5
DTMB FACILITIES 122 1100 0 0 0 0 0 5 6 0 5 94
ELEVATOR 181 0 0 0 0 0 0 0 0 0 0
ELEVATOR 72 0 0 0 0 0 0 0 0 0 0
ENTRY 465 0 0 0 0 0 0 0 0 5 0
FIA BLIND 120 120 0 0 0 0 0 5 1 0 5 10
FIA CONFERENCE 119 113 0 0 0 0 0 50 6 0 5 35
FIA OFFICE 118 1095 0 0 0 0 0 5 5 0 5 93
FIA OPEN OFFICE 215 3700 0 0 0 0 0 5 19 0 5 315
JANITOR 104 76 0 0 0 0 0 0 0 0 0 0
JANITOR 204 38 0 0 0 0 0 0 0 0 0 0
LOBBY 101 1205 0 0 0 0 0 10 12 0 5 133
LOBBY OFFICE 101A 94 0 0 0 0 0 5 0 0 5 8
MEN 107 244 0 50 3 150 150 0 0 0 0 0
MEN'S 202 231 0 50 3 150 150 0 0 0 0 0
OFFICE NEAR FIA 216A 282 0 0 0 0 0 5 1 0 5 24
PASSAGE 102 105 0 0 0 0 0 0 0 0 0 0
REG ACC 216 632 0 0 0 0 0 5 3 0 5 54
SERVER 109 79 0 0 0 0 0 0 0 0 5 0
SOS 114 1161 0 0 0 0 0 5 6 0 5 99
SOS BREAK ROOM 117 93 0 0 0 0 0 25 2 0 5 17
SOS DEALER 112 352 0 0 0 0 0 5 1 0 5 26
SOS MANAGER 115 157 0 0 0 0 0 5 1 0 5 13
SOS OFFICE CIRCULATION 1205 0 0 0 0 0 0 0 0 0 72
SOS STORAGE 116 90 0 0 0 0 0 0 0 0 5 5
SOS VIDEO OFFICE 113 180 0 0 0 0 0 5 1 0 5 15
STAIR 282 0 0 0 0 0 0 0 0 0 0
STAIR 2 213 0 0 0 0 0 0 0 0 0 13
STAIR 213 417 0 0 0 0 0 0 0 0 0 0
STORAGE 205 134 0 0 0 0 0 0 0 0 5 8
STORAGE 214 41 0 0 0 0 0 0 0 0 5 2
VESTIBULE 100 229 0 0 0 0 0 0 0 0 0 0
WOMEN 106 233 0 50 3 150 150 0 0 0 0 0
WOMENS 203 242 0 50 3 150 150 0 0 0 0 0
WORKMANS COMP OFFICE 108 850 0 0 0 0 0 5 4 0 5 72
TOTAL 1896
ROOF TOP UNIT SCHEDULE
SUPPLY FAN COOLING GAS HEATING ELECTRICAL FILTER
MARK SERVICE LOCATION SA CFM OA CFM ESP (IN-WG) TYPE QUANTITY MOTOR HP RPM ESP (IN-WG) TYPE
TOTAL CAPACITY
(MBH)
SENSIBLE CAPACITY
(MBH)
EAT DB/WB (°F) LAT DB/WB (°F) TYPE EDB (°F) LDB (°F) INPUT (MBH) OUTPUT (MBH)
MIN
EFFICENCY
V/PH/HZ MCA MOCP TYPE MANUFACTURER MODEL NOTES
RTU-1 VAV BOXES ROOF 13500 1900 1.5 FORWARD CURVE 1 15 1300 1.5 DX 312 227 71.6/60.2 55.2/51.7 INDIRECT GAS 55 86 800 648 81% 460/3/60 88 110 4" MERV 13 CARRIER 48K3HM30-2-6A1F6D0 1,2,3,4,5,6,7,8,9,10
NOTES: 1. PROVIDE WITH MULTI STAGE HIGH GAS HEAT WITH SS HEAT EXCHANGER.
2. PROVIDE WITH DIGITAL SCROLL MODULATING COOLING.
3. PROVIDE VFD WITH BYPASS ON SUPPLY FAN.
4. PROVIDE VFD WITH BYPASS CONTROLLED EXHAUST FAN.
5. PROVIDE WITH 100% COMPARATIVE ENTHALPY CONTROLLED ECONOMIZER.
6. PROVIDE WITH HOT GAS REHEAT COIL (MODULATING CONTROL).
7. PROVIDE WITH MSTP BACNET CONTROL INTERFACE.
8. PROVIDE WITH PHASE MONITORING.
9. PROVIDE WITH CURB TO ADAPT TO EXISTNG OPENINGS AND ROOF SUPPORTS.
10. UNIT TO PROVIDE FACTORY REFRIGERANT LEAK DETECTION AND ISOLATION.
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
M-601
M E
C H
A N
IC
A
L S
C H
E D
U
LE
S
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
AIR TERMINAL SCHEDULE
MARK SUPPLY RETURN EXHAUST
FLOW
(CFM)
DIMENSIONS
(IN)
DUCT
CONNECTOR (IN) MANUFACTURER MODEL NOTES
101.1 X 200 24x24 --- --- --- EXISTING
101.2 X 200 24x24 --- --- --- EXISTING
103.1 X 150 24x24 --- --- --- EXISTING
106.1 X 125 24x24 --- --- --- EXISTING
107.1 X 100 24x24 --- --- --- EXISTING
108.1 X 200 24x24 --- --- --- EXISTING
108.2 X 200 24x24 --- --- --- EXISTING
108.3 X 150 24x24 --- --- --- EXISTING
108.4 X 200 24x24 --- --- --- EXISTING
110.1 X 250 24x24 --- --- --- EXISTING
111.1 X 250 24x24 --- --- --- EXISTING
111.2 X 250 24x24 --- --- --- EXISTING
112.1 X 150 24x24 --- --- --- EXISTING
113.1 X 150 24x24 --- --- --- EXISTING
114.1 X 200 24x24 --- --- --- EXISTING
114.2 X 200 24x24 --- --- --- EXISTING
114.3 X 250 24x24 --- --- --- EXISTING
114.4 X 200 24x24 --- --- --- EXISTING
114.5 X 100 24x24 --- --- --- EXISTING
114.6 X 200 24x24 --- --- --- EXISTING
114.7 X 150 24x24 --- --- --- EXISTING
114.8 X 150 24x24 --- --- --- EXISTING
115.1 X 125 24x24 --- --- --- EXISTING
116.1 X 75 24x24 --- --- --- EXISTING
117.1 X 75 24x24 --- --- --- EXISTING
118.1 X 150 24x24 --- --- --- EXISTING
118.2 X 150 24x24 --- --- --- EXISTING
118.3 X 125 24x24 --- --- --- EXISTING
118.4 X 150 24x24 --- --- --- EXISTING
118.5 X 125 24x24 --- --- --- EXISTING
118.6 X 125 24x24 --- --- --- EXISTING
119.1 X 125 24x24 --- --- --- EXISTING
120.1 X 125 24x24 --- --- --- EXISTING
121.1 X 125 24x24 --- --- --- EXISTING
121.2 X 125 24x24 --- --- --- EXISTING
121.3 X 125 24x24 --- --- --- EXISTING
121.4 X 150 24x24 --- --- --- EXISTING
121.5 X 150 24x24 --- --- --- EXISTING
201.1 X 300 24x24 --- --- --- EXISTING
201.2 X 300 24x24 --- --- --- EXISTING
201.3 X 300 24x24 --- --- --- EXISTING
201.4 X 300 24x24 --- --- --- EXISTING
202.1 X 125 24x24 --- --- --- EXISTING
203.1 X 125 24x24 --- --- --- EXISTING
206.1 X 125 24x24 --- --- --- EXISTING
206.2 X 100 24x24 --- --- --- EXISTING
207.1 X 150 24x24 --- --- --- EXISTING
207.2 X 225 24x24 --- --- --- EXISTING
207.3 X 225 24x24 --- --- --- EXISTING
207.4 X 320 24x24 --- --- --- EXISTING
207.5 X 320 24x24 --- --- --- EXISTING
207.6 X 320 24x24 --- --- --- EXISTING
207.7 X 320 24x24 --- --- --- EXISTING
207.8 X 320 24x24 --- --- --- EXISTING
207.9 X 320 24x24 --- --- --- EXISTING
207.10 X 225 24x24 --- --- --- EXISTING
207.11 X 200 24x24 --- --- --- EXISTING
207.12 X 225 24x24 --- --- --- EXISTING
207.13 X 200 24x24 --- --- --- EXISTING
207.14 X 320 24x24 --- --- --- EXISTING
207.15 X 320 24x24 --- --- --- EXISTING
207.16 X 0 60x36 --- --- --- EXISTING
208.1 X 200 24x24 --- --- --- EXISTING
208.2 X 150 24x24 --- --- --- EXISTING
214.1 X 150 24x24 --- --- --- EXISTING
214.2 X 150 24x24 --- --- --- EXISTING
214.3 X 150 24x24 --- --- --- EXISTING
216.1 X 320 24x24 --- --- --- EXISTING
216.2 X 200 24x24 --- --- --- EXISTING
216.3 X 0 72x60 --- --- --- EXISTING
EA
SAOA
RA
ROOFTOP UNIT SEQUENCE OF OPERATION:
RUN CONDITIONS:
THE UNIT SHALL RUN ON AN OCCUPANCY SCHEDULE FROM THE EXISTING BAS SYSTEM AND SENT TO THE RTU AS A BINARY SIGNAL
FREEZE PROTECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.
ALARM ON ACTIVATION (ALARM SHALL BE SENT TO THE EXISTING BAS)
HIGH STATIC SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC SHUTDOWN SIGNAL.
ALARM ON ACTIVATION (ALARM SHALL BE SENT TO THE EXISTING BAS)
RETURN AIR SMOKE DETECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A RETURN AIR SMOKE DETECTOR STATUS.
ALARM ON ACTIVATION (ALARM SHALL BE SENT TO THE EXISTING BAS)
SUPPLY FAN:
THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.)
MINIMUM RUNTIME.
ALARMS SHALL BE PROVIDED AS FOLLOWS (ALARMS SHALL BE SENT TO THE EXISTING BAS):
SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE CONTROLLER SHALL MONITOR DUCT STATIC PRESSURE SIGNAL FROM EXISTING BAS SYSTEM AND MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT. THE SPEED SHALL NOT DROP BELOW 30% (ADJ.). THE STATIC PRESSURE SETPOINT SHALL BE RESET BASED UPON THE POSITION OF THE ZONE DAMPERS, WITH A GOAL OF REDUCING THE STATIC PRESSURE
UNTIL AT LEAST ONE VAV DAMPER IS NEARLY WIDE OPEN.
THE INITIAL DUCT STATIC PRESSURE SETPOINT SHALL BE 1.5 IN H2O (ADJ.).
IF NO VAV DAMPER IS NEARLY WIDE OPEN, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 1.3 IN H2O (ADJ.) .
AS ONE OR MORE DAMPERS NEARS THE WIDE OPEN POSITION, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 1.8 IN H2O (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.
LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.
SUPPLY FAN VFD FAULT.
EXHAUST FAN:
THE EXHAUST FAN SHALL RUN WHENEVER THE SUPPLY FAN RUNS.
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
EXHAUST FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
EXHAUST FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
EXHAUST FAN VFD FAULT.
BUILDING STATIC PRESSURE CONTROL:
THE CONTROLLER SHALL MONITOR BUILDING STATIC PRESSURE SIGNAL PROVIDED BY EXISTING BAS AND MODULATE THE RETURN FAN VFD SPEED TO MAINTAIN A BUILDING STATIC PRESSURE SETPOINT
OF 0.05IN H2O (ADJ.). THE RETURN FAN VFD SPEED SHALL NOT DROP BELOW 20% (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH BUILDING STATIC PRESSURE: IF THE BUILDING AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.
LOW BUILDING STATIC PRESSURE: IF THE BUILDING AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.
SUPPLY AIR TEMPERATURE SETPOINT - OUTSIDE AIR RESET:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL RESET SUPPLY AIR TEMPERATURE SETPOINT RESET BASED ON OUTSIDE AIR TEMPERATURE.
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET FOR COOLING AS FOLLOWS:
AS OUTSIDE AIR TEMPERATURE RISES FROM 50°F (ADJ.) TO 85°F (ADJ.)
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET DOWNWARDS FROM 65°F (ADJ.) TO 55°F (ADJ.).
IF THE RETURN AIR TEMPERATURE DROPS BELOW 68°F (ADJ.), THEN THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR HEATING AS FOLLOWS:
AS OUTSIDE AIR TEMPERATURE DROPS FROM 50°F (ADJ.) TO 20°F (ADJ.).THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET UPWARDS FROM 75°F (ADJ.) TO 95°F (ADJ.)
COOLING:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COOLING TO MAINTAIN ITS COOLING SETPOINT.
THE COOLING SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).
AND THE ECONOMIZER IS DISABLED OR FULLY OPEN.
AND THE SUPPLY FAN STATUS IS ON.
AND THE HEATING IS NOT ACTIVE.
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN SETPOINT.
HEATING:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND STEP THE GAS VALVE TO MAINTAIN ITS HEATING SETPOINT.
THE HEATING SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).
AND THE SUPPLY FAN STATUS IS ON.
AND THE COOLING IS NOT ACTIVE.
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) LESS THAN SETPOINT.
ECONOMIZER:
THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE MIXED AIR DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).
AND THE OUTSIDE AIR ENTHALPY IS LESS THAN 22BTU/LB (ADJ.)
AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE.
AND THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY.
AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER:
THE FREEZESTAT IS ON.
OR ON LOSS OF SUPPLY FAN STATUS.
THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE MIXED AIR DAMPER SHALL OPEN WHEN THE UNIT IS OFF.
MINIMUM OUTSIDE AIR VENTILATION - CARBON DIOXIDE (CO2) CONTROL:
WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL MEASURE THE RETURN AIR CO2 CONCENTRATION AND MODULATE THE OUTSIDE AIR DAMPERS OPEN ON RISING CO2 CONCENTRATIONS, OVERRIDING NORMAL DAMPER OPERATION TO MAINTAIN A CO2 SETPOINT OF 750 PPM (ADJ.).
OPTIMAL START (HEATING AND COOLING):
THE UNIT SHALL START PRIOR TO SCHEDULED OCCUPANCY ON A SIGNAL FROM THE EXISTING BAS AS NECESSARY FOR THE ZONES TO REACH THEIR OCCUPIED SETPOINTS. DURING HEATING THE SUPPLY AIR DISCHARGE SETPOINT SHALL BE 100 DEG F (ADJ.) AND DURING COOLING 55 DEG F (ADJ.) THE UNIT SHALL REMAIN IN THIS MODE UNTIL THE SIGNAL IS NO LONGER RECEIVED FROM THE
EXISTING BAS,
DEHUMIDIFICATION:
THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND OVERRIDE THE COOLING SEQUENCE TO RUN THE COOLING COMPRESSOR AND MODULATE THE HOT GAS REHEAT TO MAINTAIN RETURN AIR HUMIDITY AT OR BELOW 60% RH (ADJ.). WITHOUT COMPROMISING THE SUPPLY AIR SETPOINT. DEHUMIDIFICATION SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON.
FILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER.
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
MIXED AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE MIXED AIR TEMPERATURE AND USE AS REQUIRED FOR ECONOMIZER CONTROL OR PREHEATING CONTROL
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
LOW MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
RETURN AIR HUMIDITY:
THE CONTROLLER SHALL MONITOR THE RETURN AIR HUMIDITY AND USE AS REQUIRED FOR ECONOMIZER CONTROL OR HUMIDITY CONTROL
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH RETURN AIR HUMIDITY: IF THE RETURN AIR HUMIDITY IS GREATER THAN 70% (ADJ.).
RETURN AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE RETURN AIR TEMPERATURE AND USE AS REQUIRED FOR SETPOINT CONTROL OR ECONOMIZER CONTROL (IF PRESENT).
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
SUPPLY AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS: (ALARMS SHALL BE SENT TO THE EXISTING BAS)
HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
AI
SA TEMP
AI
FILTER STATUS
H L
EF
BI
SUPPLY FAN
STATUS
L H
AI
OA PRESS
L H
SPACE PRESS
BO SUPPLY FAN VFD START/STOPS/S
AO SUPPLY FAN VFD SPEEDSPD
BI
EXHAUST FAN
STATUS
HL
BOEXHAUST FAN VFD START/STOP S/S
AOEXHAUST FAN VFD SPEED SPD
BO S/S
BO
MODULATION
VALVE
GAS
AO
CONDENSER
C
DX
AI
MIXED AIR TEMP
AI
RA TEMP
AI
RA HUMIDITY
AO
MIXED AIR
DAMPERS
EF VFD
SF VFD
AI
OA HUMIDITY
AI
OA TEMP INTLK
LOW LIMIT
BI
FROM EX.
BAS
BO
BO
BO
AI
RA CO2
AI
H L
DUCT PRESSURE
(FROM EX. BAS)
BI
S
OCCUPANCY
(FROM EX. BAS)
AO
HGR
BI
SMOKE
DETECTOR
S
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:0
9:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.rv t
M-602
M E
C H
A N
IC
A
L D
IA
G
R A
M S
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
EX. DUCT DETECTOR
IS IN DUCT AND NOT
PROVIDED WITH UNIT.
CABLE TV, TELEPHONE,
DATA OR DUPLEX RECEPT
OUTLET (UNLESS NOTED)
TOP OF
COUNTER
BASEBOARD RADIATOR
FIRE ALARM
HORN/SPEAKER/STROBE
SWITCHES,
THERMOSTAT, WALL
OCCUPANCY SENSOR,
FIRE ALARM PULL
STATION
FLOOR
ELECTRIC WATER COOLER
CEILING
CL
7'
4'
6" M
IN
ELECTRICAL OUTLET
6"
6"
CL
/4
RECOMMENDATIONS
PER MANUFACTURERS
PANEL BOARD
POWER CIRCUIT WIRING
UNDERGROUND WIRING
SWITCH LOOP WIRING
UN-SWITCHED HOT WIRING
LOW VOLTAGE WIRING
DATA WIRING
PROPOSED EXISTING DEMOLISH
TYPICAL 3⌀ 4-WIRE
DRY-TYPE UTILITY
TRANSFORMER
T-X
TYPICAL 3⌀ 4-WIRE
DRY-TYPE TRANSFORMER
SERVICE FROM SERVICE PANEL
T-X
BRANCH PANEL
CONNECTIONS BY
UTILITY
SUPPLY-SIDE
BONDING JUMPER
SERVICE
PANEL
G
NEU. NEU.
G
BRANCH PANEL
GROUNDED CONDUCTOR
GROUNDING ELECTRODE
CONDUCTOR
GROUNDING ELECTRODE
REFER TO NOTE 2
EQUIPMENT GROUNDING
CONDUCTOR
MAIN BUILDING JUMPER
GRADE
GROUNDED CONDUCTOR SYSTEM BONDING
JUMPER
SUPPLY-SIDE
BONDING
JUMPER
SEPARATELY DERIVED SYSTEM
G
NEU.
1. SIZE GROUNDING/BONDING CONDUCTORS PER NEC ARTICLE 250
2. GROUNDING ELECTRODE SYSTEM AS PER NEC ARTICLE 250 SECTION III.
NOTES
1. ALL ELECTRICAL INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE, CURRENT STATE OF MICHIGAN ELECTRICAL
CODE (PART 8), AND ANY LOCAL AMENDMENTS.
2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACQUISITION OF AN ELECTRICAL PERMIT AND SCHEDULING OF THE NECESSARY INSPECTIONS. UPON COMPLETION OF THE WORK THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE OWNER EVIDENCE OF INSPECTION APPROVAL.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION REQUIRED WITH THE ELECTRIC UTILITY SERVING THE FACILITY. UTILITY
COSTS SHALL BE PAID SEPARATELY BY THE OWNER.
GENERAL NOTES - ELECTRICAL
SURFACE / CEILING MOUNT
EMERGENCY SURFACE / CEILING
MOUNT
PENDANT / CHAIN MOUNT
EMERGENCY PENDANT / CHAIN
MOUNT
RECESSED MOUNT
EMERGENCY RECESSED MOUNT
COMBINATION FAN / LIGHT
TRACK STRIP
WALL MOUNT
EMERGENCY WALL MOUNT
EXTERIOR POLE MOUNT
EXTERIOR POST MOUNT
EMERGENCY WALL PACK
EXIT SIGN
CEILING FAN
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MOTOR STARTER
WITH DISCONNECT SWITCH
MOTOR STARTER
ELECTRICAL METER
DISTRIBUTION PANEL
ELECTRICAL POWER PANEL
SURFACE MOUNT
ELECTRICAL POWER PANEL
FLUSH MOUNT
LIGHITNG CONTROL PANEL
RELAY
ELECTRICAL TRANSFORMER
ELECTRICAL PULL BOX
JUNCTION BOX
SINGLE PHASE MOTOR
THREE PHASE MOTOR
VARIABLE FREQUENCY DRIVE
X = NUMBER AND TYPE OF PORTS
C COAXIAL PORT
D DATA PORT
H HDMI PORT
P PHONE PORT
W WIRELESS ACCESS POINT
X
X H Z
SENSORS
J J
PC
IC
PS
K
CR
DL
M
R
A
CO
HD
F F
F F
F
T
PB
1. MINIMUM SIZE OF RIGID CONDUIT SHALL BE 3/4".
2. MINIMUM SIZE OF FLEX CONDUIT SHALL BE 1/2".
3. MINIMUM SIZE WALL BOX IN CMU SHALL BE
4"X4".
4. MINIMUM SIZE OF UNDERGROUND CONDUIT
SHALL BE 1 1/4".
5. CONDUIT AND CONDUCTORS NOT CALLED OUT
ON PLANS SHALL BE 3/4" CONDUIT
w/(2) #12AWG + #12 GND, UNO.
J
(WALL) (CEILING)
NURSE
N
N
FACP
FAA
FS
TS
PS
DH
C
P
(LIGHT)(NO LIGHT)
CARD READER
MAGNETIC SWITCH (DOOR CONTACT)
ELECTRONIC DOOR LOCK
MOTORIZED DOOR OPERATOR
ELECTRIC STRIKE
KEYPAD ENTRY DEVICE
ENTRANCE CALL SYSTEM
SECURITY CAMERA
PANIC ALARM SPEAKER/STROBE
ES
DP##
PP##
PP##
(WALL)
(CLG)
(FLR)
B
M
WG
F F
HSS
OUTDOOR BELL / CHIME
SMOKE DETECTOR
SMOKE DETECTOR WITH AUDIBLE BASE
SMOKE/CARBON MONOXIDE DETECTOR
DUCT SMOKE DETECTOR
HEAT DETECTOR
FIRE ALARM HORN/STROBE
FIRE ALARM STROBE
FIRE ALARM SPEAKER
FIRE ALARM SPEAKER/STROBE
FIRE ALARM PULL STATION
ELECTROMAGNETIC DOOR HOLD OPEN
END OF LINE RESISTOR
FIRE ALARM FLOW SWITCH
FIRE ALARM PRESSURE SWITCH
FIRE ALARM TAMPER SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
HOOD SUPPRESSION SYSTEM FIRE ALARM
CONTACT
ELR
I/C
DC
DO
SWITCHES: X = DESIGNATION BELOW
H = HUB CONTROLLER
Z = LIGHTING ZONE
PUSH BUTTON
EMERGENCY STOP BUTTON
PHOTOCELL
CEILING MOUNTED PULL SWITCH
WIRELESS NETWORK LIGHTING CONTROLLER
(HUB) H# = CONTROLLER INDICATOR
LIGHTING CONTROL SCHEME NUMBER
SINGLE POLE
2 TWO POLE
3 THREE WAY
4 FOUR WAY
DM DIMMER
F FAN
K KEY OPERATED
LV LOW VOLTAGE
M MOTION DETECTION
O OCCUPANCY SENSOR
P PILOT LIGHT
T TIMER
F F
S S
X
X X
(FURN)
SPEAKER
INTERCOM CALL BOX
BELL
MICROPHONE JACK
POWER SUPPLY
REQUIRES WIRE GUARD
NURSE CALL MAIN PANEL
NURSE CALL PULL STATION
NURSE CALL LIGHT
CLOCK
SIMPLEX RECEPTACLE
DUPLEX GROUNDED RECEPTACLE
208/240/480V, 1ϕ STRAIGHT BLADE RECEPTACLE
QUADRUPLEX RECEPTACLE
DUPLEX RECEPTACLE ON EMERGENCY POWER
FLOOR BOX
CEILING BOX
SPECIALTY RECEPTACLE
CTR MOUNTED ABOVE COUNTER
G GROUND FAULT CIRCUIT INTERRUPTER
GC GFCI - MOUNTED ABOVE COUNTER
T TAMPER-PROOF
U DUAL USB PORTS
UC DUAL USB PORTS ABOVE COUNTER
WP WEATHERPROOF RECEPT & COVER, GFI
H##
D DAYLIGHT
M MOTION DETECTION
O OCCUPANCY
V VACANCY
H = HUB CONTROLLER
Z = LIGHTING ZONE
XS X
H Z
S X H Z
LP##
(CEILING) (WALL)
(CEILING) (WALL)
(CEILING)
(WALL)
(WALL)(CLG)
(CLG) (WALL) (FLR)
ELECTRICAL SYMBOLS LEGEND
VFD
XX-X EQUIPMENT INDICATOR
INDICATES EXISTING
e LF-1
H Z
LIGHT FIXTURE INDICATOR
HUB CONTROLLER
LIGHTING ZONE
e
RACEWAY / CONDUCTOR NOTES
WIRES
OTHER SYMBOLS
TELEPHONE/COMMUNICATIONS
FIRE ALARM SYSTEMRECEPTACLE OUTLETS
SECURITY
POWER DISTRIBUTION
LIGHT FIXTURES
SWITCHES
(360 VIEW)
P P
SX
(W/ LIGHTS)
(INT.) (EXT.)
(INT.) (EXT.)
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
8/ 1/
:1
0:
P M
A ut od es k D oc s:
//7
6-
-0
E sc an ab a
S O
B R
T U
R ep l/7
0_
F P
M E
_E sc an ab aS O
B _R
T U
_2
3_ C
E N
.r vt
E-001
E
LE
C T
R
IC
A L
N O
T E
S A
N D
S Y
M B
O
LS
Lu di ng to n S t, E sc an ab a, M I 4
E S
C A
N A
B A
S T
A T
E O
F F
IC
E
B U
IL
D
IN
G
R O
O F
T O
P U
N
IT
R E
P
LA
C E
M E
N T
B
ID
S
-2 4-
LM
/0 8/
1/
8.
JB
B
D T
M B
F ile
N o.
N.T.S
TYPICAL MOUNTING HEIGHTS
ELECTRICAL
ABBREVIATIONS
_SPECIAL
Φ PHASE
A
A AMPERE
AFF ABOVE FINISHED FLOOR
C
C CONDUIT
CAT CATALOGUE
CB CIRCUIT BREAKER
CKT CIRCUIT
CMU CONCRETE MASONRY UNIT
CO. COMPANY
CUH CABINET UNIT HEATER
E
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EWC ELECTRIC WATER COOLER
F
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
G
G GROUND FAULT CIRCUIT
INTERRUPTER
GND EQUIPMENT GROUND
H
HVAC HEATING VENTILATING & AIR
CONDITIONING
K
K KEY OPERATED DEVICE
KVA KILOVOLT-AMPERES
KW KILOWATTS
L
LED LIGHT EMITTING DIODE
M
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MTD MOUNTED
N
NEU NEUTRAL
No. NUMBER
P
PL PILOT
R
RECEPT RECEPTACLE
T
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
U
UGE UNDERGROUND ELECTRIC
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V
V VOLT
VA VOLT-AMPERES
W
W WIRE
WAP WIRELESS ACCESS POINT
WP WEATHERPROOF
X
XFMR TRANSFORMER
N.T.S
GROUNDING BONDING DIAGRAM
EP1
MDP1
MDP2
SECRETARY OF STATE
SOS STOR.
SOS BREAK
SOS MANAGER
SOS VIDEO
SOS DEALER
H.C. ACCESS RAMP
ENTRY
MECHANICAL
FIA
CORRIDOR
WORKMAN'S COMP
108CONFERENCE
SERVER
MEN
WOMEN
BREAK ROOM
JANITOR
PASSAGE
CORRIDOR
Room
FIA CONF.
FIA BLIND
LOBBY
VESTIBULE
EXISTING PANELS TO REMAIN.
RE-FEED FROM NEW PANEL MDP
PDP
EXISTING PANELS TO REMAIN,
RE-FEED FROM NEW PANEL PDP
200A FUSED DISCONNECT
1. DRAWINGS SHOW MAJOR DEMOLITION ONLY; THE CONTRACTOR SHALL PROVIDE ALL DEMOLITION
FOR THE COMPLETION OF THE WORK WHETHER EXPLICITLY SHOWN OR NOT.
2. THE OWNER RESERVES THE RIGHT TO KEEP ANY REMOVED EQUIPMENT OR MATERIALS. ALL
DEMOLITION DEBRIS TO BE REMOVED FROM THE SITE AND DISPOSED OF IN AN APPROVED LANDFILL.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TEMPORARY EXTERIOR OPENINGS MADE FROM
DEMOLITION WORK TO ENSURE THEY ARE WEATHER TIGHT AT THE END OF EACH DAY.
4. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING WHERE CONDUITS AND
JUNCTION BOXES ARE REMOVED UNLESS OTHERWISE NOTED.
5. ANY JUNCTION BOXES REMAINING IN PLACE THAT HAVE HAD DEVICES…