Summary of Palm Beach County Fire Station No. 40 Construction Documents
This document is Addendum One to the bid package for Palm Beach County Fire Rescue Fire Station No. 40 (Project No. 16214), issued by the Board of County Commissioners, Palm Beach County, Florida, Facilities Development and Operations Department on April 7, 2021. The project involves the design and construction of a new fire station in Boynton Beach/Westlake, Florida, with a scope including structural concrete, masonry, structural steel framing, metal decking, roofing systems (both standing seam metal and SBS-modified bituminous membrane), insulation, flashing, interior finishes, mechanical and electrical systems, and site work. The addendum modifies the original bid documents by extending the sealed bid due date to May 5, 2021 at 2:00 P.M., with bids to be opened the following day at the same time. The addendum includes comprehensive replacements of 58 architectural and engineering drawing sheets across multiple divisions (general, civil, structural, mechanical, and electrical work) and adds Special Condition 12 regarding the geotechnical report and site lighting foundation engineering requirements, a flow test provision, and temporary construction fencing requirements.
The contract documents include detailed specifications for all major building systems, referencing standards from ASTM, ACI, AISC, AWS, ASCE, NFPA, UL, and the Florida Building Code (2017, 6th Edition, with references to 2020, 7th Edition). The project emphasizes compliance with Miami-Dade County wind and hurricane standards (HVHZ requirements), requiring design certifications from Florida-licensed professional engineers and manufacturer approvals for roofing, metal panel, and structural systems. A geotechnical report prepared by Tierra South Florida, Inc. is included in the bid documents, which recommends shallow spread foundations with a 3,000 psf allowable bearing pressure and conventional slab-on-grade construction following proper site preparation. The contractor is responsible for selecting a qualified testing laboratory for concrete, masonry, and soils testing throughout construction, with the Owner paying for testing services except for concrete mix design. Manufacturer's warranties are required, including 25-year warranties on metal roofing substrate, 35-year warranties on paint finishes, 20-year system guarantees for roofing assemblies, and two-year installer warranties for workmanship.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOARD OF COUNTY COMMISSIONERS
PALM BEACH COUNTY, FLORIDA
FACILITIES DEVELOPMENT AND OPERATIONS DEPARTMENT
PROCUREMENT & PROJECT IMPLEMENTATION GROUP
PROJECT NAME: Fire Station 40
PROJECT NUMBER: 16214
ADDENDUM NUMBER: ONE
DATE OF ISSUANCE: April 7, 2021
TO: Prospective Bidders
This addendum forms a part of the contract documents, modifies the original bid documents and shall be as binding as if contained therein.
This Addendum consists of two (2) pages and two (2) attachments.
CHANGE TO BID DATE(S):
1. Sealed Bids, consisting of the Primary Bid Documents, will be received by the
Board of County Commissioners, Palm Beach County, Florida, until 2:00 P.M. on May 5, 2021, (“Bid Due Date”) at Palm Beach County Facilities Development and Operations Department, Capital Improvements Division at 2633 Vista Parkway, West Palm Beach, Florida. The Bid Documents received by the Bid Due Date will be opened on the following day at 2:00 p.m. at a public meeting at the above address.
CHANGE TO ATTACHMENTS:
2. Delete Exhibit “1” and replace with the attached Exhibit “1R”.
3. Delete the following pages from Exhibit “2” and replace and/or insert with the attached pages, reference Exhibit “2R”:
1. Cover Sheet
2. G-1
3. ASP-1
4. LS-1
5. C-3
6. C-4
7. C-5
8. C-6
9. C-7
10. FLP1 of 2
11. FLP2 of 2
12. Signalization
Plan Key Sheet (Sheet T-1)
13. Signalization Plan (Sheet T-5)
14. A1.0
15. A2.0
16. A3.0
17. A4.0
18. A5.0
19. A5.1
20. A6.0
21. A6.1
22. A6.2
23. A7.0
24. A8.0
25. A9.0
26. A10.0
27. S-2.1
28. S-3
29. S-3.1
30. S-4
31. M0.1
32. M0.2
33. M0.3
34. M1.0
35. M2.0
36. M3.0
37. M4.1
38. M4.2
39. M5.1 (New)
40. P0.1
41. P2.0
42. P2.1
43. P3.0
44. P3.1
45. FP0.1
46. FP1.0
47. FP2.0
48. E0.1
49. E1.0
50. E2.0
51. E2.1
52. E2.2
53. E2.3
54. E3.0
55. E4.0
56. E4.1
57. E5.0
58. E6.1
ADD1-2
CHANGE TO SPECIAL CONDITIONS
4. Insert SC 12 SCOPE OF WORK, as follows:
SC 12 SCOPE OF WORK
12.1 The Geotechnical Report is included in Exhibit “1R”. Contractor to verify whether an engineer will be retained for the Site Lighting Foundation after review of the Geotechnical Report.
12.2 Flow test will be provided to the winning bidder at a later date.
12.3 Contractor to provide a temporary construction fence to secure construction site.
IT IS REQUIRED THAT THIS ADDENDUM NO. ONE (1), AND ANY PREVIOUSLY
ISSUED ADDENDUM(S), BE SIGNED IN THE ACKNOWLEDGMENT OF RECEIPT
BELOW, AND ATTACHED TO THE BID FORMS AND BECOMES PART OF BID
FORMS AND CONTRACT DOCUMENTS.
ACKNOWLEDGMENT OF RECEIPT: _____________________________________
END OF ADDENDUM
Palm Beach County Fire Rescue
Fire Station No. 40
Architects Project No. 18.031
Palm Beach County Project No. 16214
14 December 2020
100% Construction Documents
Specifications
Stephen L. Boruff, AIA, Architects + Planners, Inc.
901 Northpoint Parkway, Suite 101 West Palm Beach, Florida 33407
Phone: (561) 471-8520 Fax: (561) 471-8539
EXHIBIT "1R"
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
PROJECT INFORMATION 000001-1
DOCUMENT 00 00 01 – PROJECT INFORMATION
PROJECT NAME & LOCATION OWNER
Palm Beach County Fire Rescue Palm Beach County Fire Station No. 40 Capital Improvements Division Westlake, Florida 2633 Vista Parkway
West Palm Beach, Florida 33411 Contact: Sunil Jagoo, Project Manager
Phone: 561-233-0271 Fax: 561-233-0270 e-mail: SJagoo@pbcgov.org
ARCHITECT STRUCTURAL ENGINEER
Stephen L. Boruff Nelo Robert Freijomel, Project Architect Phillip J. Rizzo, P.E.
Stephen Boruff, AIA O’Donnell, Naccarato, Mignogna and Jackson Architects + Planners, Inc. 1655 Palm Beach Lakes Boulevard 901 Northpoint Parkway, Suite 101 Suite 204 West Palm Beach, Florida 33407 West Palm Beach, Florida 33401 Phone: 561-471-8520 Phone: 561-835-9994 Fax: 561-471-8539 Fax: 561-835-8255 e-mail: nelo@sba-arch.com e-mail: prizzo@onmj.net
MECHANICAL ENGINEER ELECTRICAL ENGINEER
Keith Lorinos Jason Stinchcomb Johnson, Levinson, Ragan, Davila, Inc. Johnson, Levinson, Ragan, Davila, Inc.
1450 Centrepark Drive 1450 Centrepark Drive West Palm Beach, Florida 33401 West Palm Beach, Florida 33401 Phone: 561-689-2303 Phone: 561-689-2303 Fax: 561-689-2302 Fax: 561-689-2302 e-mail: klorinos@jlrdinc.com e-mail: jstinchcomb@jlrdinc.com
SITE/CIVIL ENGINEER LAND PLANNER / LANDSCAPE ARCHITECT
Frederick Roth, P.E. Alex Ahrenholz Michael B. Schora & Associates, Inc. Cotleur & Hearing 1850 Forest Hilld Blvd 1934 Commerce Lane Suite 206 Suite 1 West Palm Beach, FL 33406 Jupiter, FL 33458 Phone: 561-968-0080 Phone: 561-747-6336 Email: froth@schorah.com e-mail: aahrenholz@cotleur-hearing.com
END OF SECTION 00 00 01
mailto:SJagoo@pbcgov.org mailto:nelo@sba-arch.com mailto:prizzo@onmj.net mailto:klorinos@jlrdinc.com mailto:jstinchcomb@jlrdinc.com mailto:froth@schorah.com mailto:aahrenholz@cotleur-hearing.com
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
TABLE OF CONTENTS 000010-1
1REV1 – BUILDING DEPT. COMMENT RESPONSES 02 APRIL 2021
TABLE OF CONTENTS
TO THE
PROJECT MANUAL FOR
PALM BEACH COUNTY FIRE RESCUE
FIRE STATION NO. 40
PALM BEACH COUNTY, FLORIDA
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
TABLE OF CONTENTS 000010-2
1REV1 – BUILDING DEPT. COMMENT RESPONSES 02 APRIL 2021
THE CONTRACTOR IS REQUIRED TO COMPARE THIS PROJECT MANUAL WITH THE TABLE OF
CONTENTS BELOW FOR COMPLETENESS.
GENERAL NOTE: WHERE APPLICABLE THE BASIS OF DESIGN MATERIAL/PRODUCT HAS BEEN
LISTED. ALTERNATE MANUFACTURERS WITH “EQUAL” CHARACTERISTICS WILL NEED TO BE
SUBMITTED FOR REVIEW & APPROVAL PRIOR TO BID SUBMISSION. THE EXCEPTION TO THIS WILL
BE SPECIFICATION SECTIONS NOTED WITH NO ALTERNATE ALLOWED.
DIVISION 00 00 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
000000 COVER
000001 PROJECT INFORMATION
000010 TABLE OF CONTENTS
DIVISION 02 00 00 – EXISTING CONDITIONS
020600 DEMOLITION
022010 GEOTECHNICAL DATA
DIVISION 03 00 00 - CONCRETE
030816 CONCRETE CONTROL & TESTING
031100 CONCRETE WORK
032000 CONCRETE REINFORCING
033000 CAST-IN-PLACE CONCRETE
033300 ARCHITECTURAL CONCRETE
DIVISION 04 00 00 - MASONRY
042200 CONCRETE UNIT MASONRY
DIVISION 05 00 00 - METALS
051200 STRUCTURAL STEEL FRAMING
053100 STEEL DECKING
054110 LIGHT GAUGE STEEL FRAMING AND PREFABRICATED STEEL ROOF TRUSSES
055000 METAL FABRICATIONS
DIVISION 06 00 00 - WOOD, PLASTICS, AND COMPOSITES
061053 MISCELLANEOUS ROUGH CARPENTRY
064023 INTERIOR ARCHITECTURAL WOODWORK
DIVISION 07 00 00 - THERMAL AND MOISTURE PROTECTION
0716001 POLYMER MODIFIED CEMENT WATERPROOFING1
072100 THERMAL AND SOUND ATTENUATION INSULATION
072119 FOAMED-IN-PLACE INSULATION (ICYNENE)
072140 FOAMED-IN-PLACE MASONRY INSULATION
0727251 FLUID-APPLIED MEMBRANE AIR AND VAPOR BARRIER1
0727261 FLUID-APPLIED FLASHING MEMBRANE1
074100 STANDING SEAM METAL ROOFING
075216 STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING
076200 SHEET METAL FLASHING AND TRIM
078413 PENETRATION FIRESTOPPING
079200 JOINT SEALANTS
DIVISION 08 00 00 - OPENINGS
081113 HOLLOW METAL DOORS AND FRAMES
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
TABLE OF CONTENTS 000010-3
1REV1 – BUILDING DEPT. COMMENT RESPONSES 02 APRIL 2021
081416 FLUSH WOOD DOORS
083113 ACCESS DOORS & FRAMES
083980 FOUR FOLD METAL DOORS
084113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
087111 FINISH HARDWARE
088000 GLAZING
089000 LOUVERS AND VENTS
DIVISION 09 00 00 – FINISHES
090600 PAINT, COLOR AND MATERIALS FINISH SCHEDULE
092216 NON-STRUCTURAL METAL FRAMING
092400 PORTLAND CEMENT PLASTERING
092900 GYPSUM BOARD
093000 TILING
095113 ACOUSTICAL PANEL CEILINGS
096513 RESILIENT BASE AND ACCESSORIES
096536 STATIC-CONTROL RESILIENT FLOORING
096623.16 EPOXY-RESIN TERRAZZO FLOORING
096813 TILE CARPETING
097300 SEAMLESS EPOXY FLOORING
099113 EXTERIOR PAINTING
099123 INTERIOR PAINTING
DIVISION 10 00 00 - SPECIALTIES
101400 INTERIOR AND EXTERIOR SIGNAGE AND GRAPHICS
1021161 PLASTIC SHOWER COMPARTMENTS1
102600 WALL AND DOOR PROTECTION
102800 TOILET AND BATH ACCESSORIES
104413 FIRE EXTINGUISHER CABINETS
104416 FIRE EXTINGUISHERS
105115 METAL GEAR LOCKERS
107500 FLAGPOLES
DIVISION 11 00 00 - EQUIPMENT
114000 FOOD SERVICE AND LAUNDRY EQUIPMENT
DIVISION 12 00 00 - FURNISHINGS
124813 ENTRANCE FLOORING GRID SYSTEM
DIVISION 14 00 00 – CONVEYING EQUIPMENT
NOT USED
DIVISION 21 00 00 - FIRE SUPPRESSION
210000 WET SPRINKLER SYSTEM
DIVISION 22 00 00 - PLUMBING
220001 PLUMBING SYSTEMS
220200 BASIC MATERIALS AND METHODS FOR PLUMBING
220500 COMMON WORK RESULTS FOR PLUMBING SYSTEMS
220523 VALVES FOR PLUMBING PIPING
220529 HANGERS AND SUPPORTS FOR PLUBMING PIPING AND EQUIPMENT
220576 FACILITY DRAINAGE PIPING CLEANOUTS
220577 FACILITY PLUMBING DRAINS AND ACCESSORIES
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
TABLE OF CONTENTS 000010-4
1REV1 – BUILDING DEPT. COMMENT RESPONSES 02 APRIL 2021
220700 PLUMBING INSULATION
221100 POTABLE WATER SYSTEMS
221116 DOMESTIC WATER PIPING
221117 DISINFECTION OF DOMESTIC WATER LINES
221313 SOIL, WASTE AND VENT SYSTEMS
221316 SANITARY DRAIN, WASTE AND VENT PIPING
221700 PUMPS FOR PLUMBING SYSTEMS
223300 ELECTRIC DOMESTIC WATER HEATERS
DIVISION 23 00 00 - HEATING VENTILATING AND AIR CONDITIONING
230500 GENERAL PROVISIONS
230501 PIPE AND PIPE FITTINGS
230529 HANGERS AND SUPPORTS
230548 VIBRATION ISOLATION
230553 IDENTIFICATION
230593 TESTING, ADJUSTING AND BALANCING (TAB) OF HEATING, VENTILATING & AIR
CONDITIONING (HVAC) SYSTEMS
230595 TESTS – PIPING SYSTEMS
230713 DUCT INSULATION
230716 PIPE AND EQUIPMENT INSULATION
232313 REFRIGERATION PIPING AND ACCESSORIES
233100 DUCTWORK
233300 DUCTWORK ACCESSORIES
233400 FANS AND KITCHEN HOOD
233713 GRILLS, REGISTERS, DIFFUSERS, LOUVERS
234000 AIR FILTERS
237300 AIR HANDLING UNITS
238126 DUCTLESS DX SPLIT SYSTEM
238128 AIR COOLED CONDENSING UNITS
DIVISION 25 00 00 – INTERGRATED AUTOMATION
255000 ENERGY MANAGEMENT AND CONTROL SYSTEM
DIVISION 26 00 00 - ELECTRICAL
260000 SCOPE OF WORK
260126 TESTING
260500 BASIC ELECTRICAL MATERIALS AND METHODS
260501 CODES, FEES, AND STANDARDS
260513 WIRES & CABLES
260526 GROUNDING
260529 HANGARS AND SUPPORTS
260533 RACEWAYS
260534 BOXES
260553 ELECTRICAL SYSTEMS IDENTIFICATION
260900 ELECTRICAL CONTROLS AND RELAYS
260923 LIGHTING CONTROLS
262416 CIRCUIT BREAKER PANELBOARDS
262716 ELECTRICAL CABINETS AND ENCLOSURES
262726 WIRING DEVICES
262800 OVERCURRENT PROTECTIVE DEVICES
262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS
262817 CIRCUIT & MOTOR DISCONNECTS
262840 MOTOR CONTROL
262923 ADJUSTABLE FREQUENCE (VARIABLE SPEED) DRIVE UNITS
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
TABLE OF CONTENTS 000010-5
1REV1 – BUILDING DEPT. COMMENT RESPONSES 02 APRIL 2021
263513 STANDBY POWER GENERATOR SYSTEM
263623 AUTOMATIC TRANSFER SWITCH
264100 LIGHTNING PROTECTION FOR STRUCTURES
265113 INTERIOR LIGHTING
265200 EMERGENCY LIGHTING EQUIPMENT
DIVISION 27 00 00 - COMMUNICATIONS
270500 TELEPHONE AND DATA RACEWAY SYSTEM
270640 GENERAL MULT-MEDIA STANDARD (PBC SECTION)
274171 GENERAL CABLE TV SYSTEMS STANDARD (PBC ESS SECTION)
DIVISION 28 00 00 - ELECTRONIC SAFETY AND SECURITY
281300 ACCESS CONTROL SYSTEM (PBC SECTION)
283100 FIRE DETECTION AND ALARM GUIDELINES (PBC SECTION)
DIVISION 31 00 00 - EARTHWORK
313116 TERMITE CONTROL
SEE ENGINEERS SPECIFICATIONS FOR REMAINDER OF DIVISION 31 - EARTHWORK
DIVISION 32 00 00 – EXTERIOR IMPROVEMENTS
323300 SITE FURNISHINGS
SEE ENGINEERS SPECIFICATIONS FOR REMAINDER OF DIVISION 32 – EXTERIOR
IMPROVEMENTS
DIVISION 33 00 00 – UTILITIES
SEE ENGINEERS SPECIFICATIONS FOR REMAINDER OF DIVISION 33 – UTILITIES
DIVISION 40 00 00 – PROCESS INTERCONNECTIONS
402116 GASOLINE PROCESS PIPING
402123 FUEL OIL PROCESS PIPING
END OF TABLE OF CONTENTS
Architect’s Project No. 18-031 Palm Beach County Project No. 16214
TABLE OF CONTENTS 000010-6
1REV1 – BUILDING DEPT. COMMENT RESPONSES 02 APRIL 2021
Architect’s Project No. 18-031
Palm Beach County Project No. 16214
DEMOLITION 020600 - 1
SECTION 02 06 00 – DEMOLITION
PART 1 - GENERAL
1.1 SUMMARY
A. Provide all labor, materials, tools, fabrications, reinforcement, equipment and services for demolition as specified herein and or as shown, detailed, scheduled, implied, required or otherwise indicated to provide a complete and proper installation.
B. Completely coordinate with Work of all other trades.
C. Related Work
1. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, shall govern work of this Section.
1.2 DESCRIPTION OF WORK
A. This Contractor shall include the careful removal of all designated salvage or waste materials and debris from the building property, and temporary protection from infiltration of construction dust run off, and solid erosion into adjacent areas. This also includes, but may not be limited to, the following items:
1. Protect against damage and nuisances, both on-site and off-site. Protect and hold the Owner harmless from all suits and legal costs arising from this Work.
2. Provide, erect and maintain barricades, fences, planking, scaffolding, bridging, lights, warning signs and guards as necessary for the protection of persons, buildings, streets, sidewalks, and property adjoining the project site.
B. All demolition work shall comply with the latest edition of NFPA 241 – Standard for Safeguarding Construction, Alteration, and Demolition Activities.
1.3 JOB CONDITIONS
A. This contractor shall inspect job conditions prior to starting Work and his starting constitutes approval of conditions.
B. The Owner assumes no responsibility for actual condition of items or structures affected by demolition work.
1.4 RELATED WORK SPECIFIED IN OTHER SECTIONS
A. Relocation of existing pipes, conduits, ducts or other mechanical, plumbing and electrical Work shall be by the respective trades and divisions.
1.5 PROTECTION
Architect’s Project No. 18-031
Palm Beach County Project No. 16214
DEMOLITION 020600 - 2
A. Provide temporary barricades and other forms of protection as required to protect general public from injury due to site Work.
1.6 DAMAGES
A. Promptly repair damages caused to adjacent facilities by demolition Work at no cost to Owner.
1.7 TRAFFIC
A. Conduct all construction operations and debris removal in a manner to ensure minimum interference with existing drives, walks, and other adjacent occupied or used facilities.
1.8 UTILITY SERVICES
A. Maintain existing utilities indicated to remain, keep in service, and protect against damage during demolition operations.
B. Do not interrupt existing utilities serving adjacent occupied or used facilities, except when authorized in writing by authorities having jurisdiction. Provide temporary services during interruptions to existing utilities, as acceptable to governing authorities.
1.9 ENVIRONMENTAL CONTROLS
A. Use water sprinkling, temporary enclosures, and other suitable methods to limit dust and dirt rising and scattering in air to lowest practical level. Comply with governing regulations pertaining to environmental protection.
B. Do not use water when it may create hazardous or objectionable conditions such as ice, flooding and pollution.
1.10 PROHIBITIONS
A. No burning shall be permitted.
B. No on-site sale of removed items shall be permitted. Removed items may be sold by the Contractor as long as the full credit for sold items and materials is passed on to the Owner.
C. No explosives shall be permitted.
PART 2 - PRODUCTS
Not Applicable
PART 3 - EXECUTION
3.1 NOTICES
Architect’s Project No. 18-031
Palm Beach County Project No. 16214
DEMOLITION 020600 - 3
A. The Contractor shall give notice to all municipalities, utility companies and other authorities before removing poles, transformers, wire, conduits, piping, or other equipment owned by them which will interfere with the Work.
B. All existing utilities shall be left capped in a legal manner.
3.2 DISPOSAL
A. The Contractor shall be responsible for the legal disposal of excess and demolition materials in an area or areas away from the jobsite without incurring, now or ever, any liability against the Owner.
3.3 ADJUST AND CLEAN
A. Upon completion of the Work, the Contractor shall remove all barricades, materials, debris, rubbish, tools and equipment, leaving the grounds clean and in a condition acceptable to the Owner.
END OF SECTION 02 06 00
Architect’s Project No. 18-031
DEMOLITION 020600 - 4
Architect’s Project No. 18-031
Palm Beach County Project No. 16214
GEOTECHNICAL DATA 022010-1
SECTION 02 20 10 – GEOTECHNICAL DATA
PART 1 - GENERAL
1.1 REQUIREMENTS INCLUDED
A. A subsurface investigation and report has been prepared specifically for this site and the Work required.
B. This subsurface investigation and report includes recommendations for the foundation system for the Work.
C. The complete investigation and report is herein provided for the information of all bidders as part of this Section.
D. This independent vendor has prepared this investigation and report which was obtained for the Architect for use in design.
E. Bidders should visit the site and acquaint themselves with the existing site conditions.
F. Bidders may, prior to bidding, make their own subsurface exploration of existing site conditions.
G. The successful bidder may, after contract award, make his own subsurface exploration of existing site conditions at his own expense.
PART 2 - PRODUCTS
Not Used
PART 3 - EXECUTION
Not Used
END OF SECTION 02 20 10
Architect’s Project No. 18-031
GEOTECHNICAL DATA 022010-2
May 7, 2019
Stephen Boruff AIA, Architects+ Planners, Inc.
901 Northpoint Parkway, Suite 100 West Palm Beach, Florida 33407
Attention: Mr. Steve Boruff, AIA
Re: Geotechnical Engineering Study
Boynton Beach Fire Station No. 40, Boynton Beach, Florida
TSF Project No. 7111-19-158
Dear Steve:
TIERRA SOUTH FLORIDA, INC. (TSF) is pleased to transmit our Geotechnical Engineering Services Report for the referenced project. This report includes the results of field exploration and laboratory testing, geotechnical recommendations for foundation and pavement subgrade design, as well as general site development.
We appreciate the opportunity to perform this Geotechnical Study and look forward to continued participation during the design and construction phases of this project. If you have any questions pertaining to this report, or if we may be of further service, please contact our office.
Respectfully submitted, TIERRA SOUTH FLORIDA, INC.
Maximo Peralta Alvarez, P.E. Ramakumar Vedula, P.E.
Geotechnical Engineer Principal Engineer FL. Registration No. 84213 FL. Registration No. 54873
MPA/KV:
TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY
2.0 PROJECT INFORMATION
2.1 Project Authorization
2.2 Project Description
2.3 Purpose and Scope of Services
3.0 SITE AND SUBSURFACE CONDITIONS
3.1 Site Location and Description
3.2 Subsurface Conditions
3.3 Groundwater Information
3.4 Borehole Permeability (BHP) Test Results
4.0 EVALUATION AND RECOMMENDATIONS
4.1 Geotechnical Discussion
4.2 Site Preparation
4.3 Foundation Recommendations
4.4 Floor Slab Recommendations
4.5 Utilities
5.0 PAVEMENT RECOMMENDATIONS
6.0 CONSTRUCTION CONSIDERATIONS
6.1 Excavations
7.0 INSPECTIONS/QUALITY CONTROL TESTING
8.0 REPORT LIMITATIONS
APPENDIX - BOREHOLE PERCOLATION TEST RESULTS
BORING LOCATION PLAN– SHEET 1
SOIL PROFILES – SHEET 2 & 3
Fire Station No. 40 Tierra South Florida, Inc.
TSF File No. 7111-19-158
1.0 EXECUTIVE SUMMARY
A geotechnical exploration and evaluation of the subsurface conditions have been completed for the design and construction of the proposed Boynton Beach Fire Station No. 40 to be constructed in Boynton Beach, Florida.
Based on visual classifications underneath the existing topsoil, the subsurface condition encountered in the borings consisted of sandy soils followed by sandy limestone to de boring termination depth. Standard Penetration N-Values indicated the sandy soils to be in loose to medium dense conditions and the limestone to be in moderate hard condition. The groundwater was, typically, encountered at approximately 3.5 to 4 feet below the ground surface.
We found concrete debris on the Boring B-1 within 2 feet depth from ground surface, we recommend that all construction debris be removed prior to start of construction, so that the debris does not interfere with foundation construction and utility construction. All debris removal areas should be properly backfilled and compacted as discussed herein. We recommend test pits be performed to investigate the extension /or presence of debris.
The geotechnical study completed for the proposed construction confirms that the site will be suitable for the planned construction when viewed from a soil mechanics and foundation engineering perspective. After following proper site preparation procedures, the structure may be supported on shallow spread foundations and employ conventional slab-on-grade for the ground floors. Details related to site development, foundation design, and construction considerations are included in subsequent sections of this report.
The owner/designer should not rely solely on this Executive Summary and must read and evaluate the entire contents of this report prior to utilizing our engineering recommendations in preparation of design/construction documents.
TSF File No. 7111-19-158
2.0 PROJECT INFORMATION
2.1 Project Authorization
TSF has completed a geotechnical exploration for the proposed Fire Station No. 40 to be constructed in Boynton Beach, Florida. This geotechnical service was performed in accordance with TSF’s Proposal No. 1804-191 dated April 4, 2018 and subsequently authorized by Stephen Boruff AIA, Architects+ Planners, Inc.
2.2 Project Description
Our understanding of the project is based on general information obtained from Stephen Boruff AIA, Architects+ Planners, Inc, as well as Site Plans indicating the proposed building. We understand that the proposed construction will include 5,500 square feet, one-story fire station and associated parking and driveway. Loading information has not been provided at this time. However we assume that maximum column and wall loads will be on the order of 150 kips and 2.5 kip per linear feet and floor slab will be 125 psf. It is also assumed that the site is at design grade.
The geotechnical recommendations presented in this report are based on the available project information, building location, and the subsurface materials described in this report. If any of the noted information is incorrect, please inform TSF in writing so that we may amend the recommendations presented in this report if appropriate and if desired by the client. TSF will not be responsible for the implementation of its recommendations when it is not notified of changes in the project.
2.3 Purpose and Scope of Services
The purpose of this study was to explore the subsurface conditions at the site which is currently accessible to enable an evaluation of acceptable foundation and pavement systems for the proposed construction. This report briefly outlines the testing procedures, describes the site and subsurface conditions, and presents geotechnical recommendations for foundation design and general site development.
Our scope of services included drilling a total of five (5) Standard Penetration Test (SPT) borings to a depth of about 25 feet from ground surface, a total of seven (7) Auger boring to a depth of about 10 feet from ground surface, performing two (2) Borehole Permeability (BHP) tests to a depth of 10 feet, plus the preparation of this geotechnical report.
This report briefly outlines the testing procedures, presents available project information, describes the site and subsurface conditions, and presents geotechnical recommendations regarding the following:
- Foundation soil preparation requirements.
- Foundation types, depths, allowable bearing capacities, and an estimate of potential settlement.
TSF File No. 7111-19-158
- Pavement Subgrade Design Recommendations.
- Comments regarding factors that may impact construction and performance of the proposed construction.
The scope of services did not include an environmental assessment for determining the presence or absence of wetlands or hazardous or toxic materials in the soil, bedrock, surface water, groundwater, or air on or below, or around this site. Any statements in this report or on the boring logs regarding odors, colors, and unusual or suspicious items or conditions are strictly for information purposes only.
TSF File No. 7111-19-158
3.0 SITE AND SUBSURFACE CONDITIONS
3.1 Site Location and Description
The project site is located at the approximate 4698-45000 White Feather trail in Boynton Beach, Florida. At the time of field exploration, the area was observed to be fairly level. The site is currently vacant and cover by grass.
3.2 Subsurface Conditions
Review of the “Soil Survey of Palm Beach County, Florida”, prepared by the United States Department of Agriculture (USDA) Soil Conservation Service (SCS), indicates the site is mapped as Myakka- Urban Land Complex.
Subsurface conditions at the site were explored with engineering borings located as shown on the Boring Location Plan, Sheet 1 in the Appendix. The study included the drilling of five (5) Standard Penetration Test (SPT) borings to a depth of about 25 feet, seven (7) auger boring and performing two (2) Borehole Permeability (BHP) tests to a depth of 10 feet. The soil test boring profiles are presented on Sheet 2 & 3 in the Appendix. Samples of the in-place materials were recovered at frequent intervals using a standard split spoon driven with a 140-pound hammer freely falling 30 inches (the SPT after ASTM D 1586). Samples of the in-place soils were returned to our laboratory for classification by a geotechnical engineer, in general accordance with the Unified Soil Classification System (ASTM D 2487).
At the time of our field exploration, based on visual classifications underneath the existing topsoil, the subsurface condition encountered in the borings consisted of sandy soils followed by sandy limestone to de boring termination depth. Standard Penetration N-Values indicated the sandy soils to be in loose to medium dense conditions and the limestone to be in moderate hard condition. The groundwater was, typically, encountered at approximately 3.5 to 4 feet below the ground surface.
The above subsurface description is of a generalized nature intended to highlight the major subsurface stratification features and material characteristics. The boring logs should be reviewed for specific information at individual boring locations. These records include soil descriptions, stratifications, and penetration resistances. The stratifications shown on the boring logs represent the conditions only at the actual boring locations. Variations may occur and should be expected between boring locations.
The stratifications represent the approximate boundary between subsurface materials, and the actual transition may be gradual. Water level information obtained during field operations is also shown on the boring logs. The samples that were not altered by laboratory testing will be retained for 30 days from the date of this report and then will be discarded.
3.3 Groundwater Information
Groundwater levels were measured in the borings when first encountered. The groundwater was, typically, encountered at approximately 3.5 to 4 feet below the ground surface. Groundwater levels
TSF File No. 7111-19-158 are expected to fluctuate with seasonal fluctuations. We expect the groundwater to, typically, fluctuate within about 2 feet from where it was encountered during the drilling operation.
In general, the seasonal high groundwater level is not intended to define a limit or ensure that future seasonal fluctuations in groundwater levels will not exceed the estimated levels. Post-development groundwater levels could exceed the normal seasonal high groundwater level estimate as a result of a series of rainfall events, changed conditions at the site that alter surface water drainage characteristics, or variations in the duration, intensity, or total volume of rainfall. We recommend that the Contractor determine the actual groundwater levels at the time of the construction to determine groundwater impact on his or her construction procedures.
3.4 Borehole Permeability (BHP) Test Results
Two (2) BHP test were performed using the usual open-hole, constant head methodology per South Florida Water Management District Standard. The holes were 10 feet deep, and were drilled with a solid stem auger so that soil samples could be retrieved for visual classification by an engineer. The borings were completed as open well with gravel pack (6-20 silica sand). The well screen slot widths were 0.020 inches. Water from the drill rig tank was then pumped into the open well, and the amount of water required maintaining constant head was recorded.
The results of our field permeability tests are attached in the Appendix.
TSF File No. 7111-19-158
4.0 EVALUATION AND RECOMMENDATIONS
4.1 Geotechnical Discussion
The geotechnical study completed for the proposed construction confirms that the site will be suitable for the planned construction when viewed from a soil mechanics and foundation engineering perspective. After following proper site preparation procedures as recommend Section 4.2 in this report, the structure may be supported on shallow spread foundations with an allowable bearing pressure of 3,000 pounds per square foot (psf) and employ conventional slab-on-grade for the ground floors.
We found concrete debris on the Boring B-1 within 2 feet depth from ground surface, we recommend that all construction debris be removed prior to start of construction, so that the debris does not interfere with foundation construction and utility construction. All debris removal areas should be properly backfilled and compacted as discussed herein. We recommend test pits be performed to investigate the extension /or presence of debris.
Recommendations for the geotechnical aspects of site preparation, foundation design and related construction are presented in the following sections of this report.
4.2 Site Preparation
To prepare for construction, we recommend that any topsoil, foundation remnants, debris, and existing vegetation including trees, roots, and any organic soils be removed in its entirety from the footprint of the proposed construction and wasted. Existing utilities, if any, should be removed from the building foot print area. The building footprint should be compacted with a self-propelled roller (Ingersoll-Rand SD-100D or equivalent) with at least 20 passes (with an operating vibration frequency of 31.5 Hz/1890 VPM and average speed of 1.4 mph) and until the subsoils achieve 95 percent of maximum dry density per ASTM D 1557 (Modified Proctor) to a depth of at least 12 inches below the existing grade. Unsuitable soil and material such as organics or muck if any encountered under the proposed construction should also be removed and replaced with properly compacted structural fill as recommended in this report. The soil densification should encompass the entire footprint of the structure plus a 10-foot wide perimeter that extends beyond the maximum lines of the superstructure.
Rolled subgrade should be visually observed for signs of pumping, weaving or other types of instability. Signs of such instability could be due to the existence of weak and/or compressible subsoils. Corrective action for this condition should include excavation of weak subsoils followed by replacement with clean granular fill compacted to 95 percent of the ASTM D 1557 maximum dry density. Structural fill used to raise the site to structure bottom levels should consist of clean sand and/or sand and gravel (ASTM D 2487), with a maximum of 12 percent passing the U.S. Standard No. 200 sieve. The structural fill should be placed in thin lifts (12-inch thick loose measure), near the optimum moisture content for compaction, and be compacted to at least 95 percent of maximum dry density (ASTM D 1557).
TSF File No. 7111-19-158
Near existing structures (within 50 feet), proofrolling should be performed in static mode. Ground vibrations induced by the compaction operations should be closely monitored to assess if there is a potential impact to the existing structures. Ground vibrations induced by the compaction operations should be closely monitored to assess if there is a potential impact to the existing buildings.
Following site preparation as discussed herein, the foundation areas should be excavated and the footing subgrade should be compacted with a heavy roller or at least a heavy plate compactor to the above mentioned 95% criteria. Unsuitable material or organic soils (if any) found at foundation bottoms should be removed and replaced with structural fill, as discussed above. In areas where footings bear at lower elevations (possibly close to or slightly below the water table) such as the truck well area, the footing excavation should be dewatered and the footing subgrade should be compacted in the dry with a heavy roller or at least a heavy plate compactor to the above mentioned 95% criteria to a depth of at least 12 inches below the existing grade. The footings should be formed and poured in-the-dry. Prior to placing the steel for the footings, the footing subgrade should be inspected by a TSF representative.
If additional structural fill is required to achieve design grade, each lift of compacted engineered fill should be tested by a representative of the geotechnical engineer prior to placement of subsequent lifts. The edges of compacted fill should extend 5 feet beyond the edges of buildings prior to sloping.
4.3 Foundation Recommendations
Conventional spread footings are generally most economical when the existing soil conditions allow them to be founded at shallow depths. Following completion of site preparation as discussed herein, we recommend supporting the planned structures on conventional spread foundations based in engineered fill and/or the surficial granular soils of the site. The footings may be designed and proportioned for a maximum bearing pressure of 3,000 pounds per square foot (psf). Footings widths and depths should follow, as a minimum, Florida Building Code guidelines when the geometry produces a bearing pressure less than the allowable.
Settlement of foundations based in the in-situ granular soils and/or engineered fill will occur as an elastic response of the soils to the building loads applied. For foundations that are based on soils prepared as discussed herein, we estimate that total and differential average foundation settlements should be on the order of 1 inch and ½ inch, respectively. In our opinion, these settlements are within the range considered tolerable for the type of structure planned. The settlement forecast is based on imposed soil bearing pressure of 3,000 pounds per square foot. Because the subsoils at the site are granular in nature, settlement should occur as the loads are applied to foundations and should essentially be complete by the time the building construction is finished.
Excavating equipment may disturb the granular bearing soil in foundation areas. The upper 12 inches of the footing subgrade should be compacted to achieve not less than 95 percent of the maximum dry density as determined by ASTM D 1557 immediately prior to reinforcing and concrete placement.
TSF File No. 7111-19-158
The site preparation and foundation excavations should be observed by a representative of TSF prior to steel or concrete placements to assess those foundation materials are capable of supporting the design loads and are consistent with the materials discussed in this report. Loose soil zones encountered at the bottom of the footing excavations should be removed to the level of medium dense soils or adequately compacted structural fill as directed by the geotechnical engineer.
4.4 Floor Slab Recommendations
Following stripping and surface soil preparation as described herein, the building pad area should be leveled and filled to subfloor elevation before placing concrete. Slab subgrade should consist of clean sand and/or sand and gravel (ASTM D 2487), with a maximum of 12 percent passing the U.S.
Standard No. 200 sieve, and compacted to at least 95 percent of maximum dry density per ASTM D 1557 (Modified Proctor) to a depth of at least 12 inches below the slab grade. Structural fill used to raise the site to floor slab bottom levels should consist of clean granular fill as described above. The structural fill should be placed in thin lifts (12-inch thick loose measure), near the optimum moisture content for compaction, and be compacted to at least 95 percent of maximum dry density (ASTM D 1557).
Our experience indicates that floor slabs constructed without a vapor barrier will often experience future problems associated with moisture and mildew. Therefore, we recommend interior floor slab subgrade soils be covered with a vapor barrier (such as visqueen, normally 6 mil thick) before constructing the slab-on-grade floor.
Slab-on-grade construction may be used for the ground floor slabs of the structure. The slabs should be adequately reinforced to carry the loads that are to be applied. The floor slab design, if based on elastic methods, should employ a modulus of subgrade reaction of 150 pounds per cubic inch (pci).
To help avoid potential problems with cracking because of differential loadings, the floor slabs should be liberally jointed and separated from columns and walls.
The friction factor between the soil and floor slabs should be taken as 0.35 without the vapor barrier.
A friction factor of 0.21 should be used for the vapor barrier-soil interface.
4.5 Utilities
All utilities should be installed per the requirements of the Civil Engineering drawings and specifications. When backfilling over utility lines, clean granular fill should be placed in no more than 6 to 12-inch thick loose lifts and compacted to at least 95% of the material’s maximum dry density as determined by the Modified Proctor Compaction Test (ASTM D 1557).
TSF File No. 7111-19-158
5.0 PAVEMENT RECOMMENDATIONS
The parking lot and driveway areas should be prepared and densified as indicated in the Site Preparation section of this report. Flexible pavement sections in this geographic area typically consist of an asphaltic concrete wearing course, limerock base course and a stabilized subgrade.
The following pavement component thickness could be utilized in the pavement design for light-duty truck. Final pavement recommendation should be provided by the Civil Engineer based on actual vehicular loading information.
TYPE OF
PAVEMENT
MATERIAL
DESCRIPTION
LAYER THICKNESS (INCHES)
PARKING
AREAS
DRIVEWAY
AREAS
Flexible Asphaltic Concrete 1.5 2.0
Base Course
(LBR = 100)
6 8
Stabilized Subgrade
(LBR = 40)
8 10
The base course materials in the pavements should consist of limerock, having a minimum Limerock Bearing Ratio (LBR) of 100. Base materials should meet the requirements presented in the latest revisions of the Florida Department of Transportation (FDOT) "Specifications for Road and Bridge Construction," Section 911 (limerock). The base course should be compacted to at least 98 percent of maximum dry density (AASHTO 180).
The subgrade should have a minimum LBR of 40. The stabilized subgrade should be compacted to at least 95 percent of maximum dry density (AASHTO 180).
If dumpsters are to be parked on the pavement, it is recommended that rigid concrete pavement be constructed. In addition, the apron utilized for unloading the dumpsters by heavy-duty trucks should also be provided with a rigid pavement. A minimum Portland concrete pavement thickness of 6 inches is recommended for the project if a rigid pavement is employed. The concrete should be reinforced to withstand the traffic loadings anticipated and should be jointed to reduce the chances for crack development. The minimum rigid pavement thickness recommended above is based upon concrete with an unconfined compressive strength of 3,500 psi and a modulus of rupture of 450 psi.
Actual pavement section thickness should be provided by the Design Civil Engineer based on traffic loads, volume, and the owner's design life requirements. The noted sections represent minimum thickness representative of typical local construction practices and, as such, periodic maintenance should be anticipated. All pavement materials and construction procedures should conform to FDOT, American Concrete Institute (ACI), or appropriate city/county requirements.
TSF File No. 7111-19-158
6.0 CONSTRUCTION CONSIDERATIONS
It is recommended that TSF be retained to provide observation and testing of construction activities involved in the foundation, earthwork, and related activities of this project. TSF cannot accept any responsibility for any conditions that deviate from those described in this report, nor for the performance of the foundation if not engaged to also provide construction observation and testing for this project.
6.1 Excavations
In Federal Register, Volume 54, No. 209 (October 1989), the United States Department of Labor, Occupational Safety and Health Administration (OSHA) amended its "Construction Standards for Excavations, 29 CFR, part 1926, Subpart P.” This document was issued to better ensure the safety of workmen entering trenches or excavations. It is mandated by this federal regulation that excavations, whether they be utility trenches, basement excavations or footing excavations, be constructed in accordance with the new OSHA guidelines. It is our understanding that these regulations are being strictly enforced and if they are not closely adhered, the owner and the contractor could be liable for substantial penalties.
The contractor is solely responsible for designing and constructing stable, temporary excavations and should shore, slope, or bench the sides of the excavations as required to maintain stability of both the excavation sides and bottoms. The contractor's "responsible person,” as defined in 29 CFR Part 1926, should evaluate the soil exposed in the excavations as part of the contractor's safety procedures. In no case should slope height, slope inclination, or excavation depth, including utility trench excavation depth, exceed those specified in local, state, and federal safety regulations.
We are providing this information solely as a service to our client. TSF does not assume responsibility for construction site safety or the contractor's or other parties’ compliance with local, state, and federal safety or other regulations.
TSF File No. 7111-19-158
7.0 INSPECTIONS/QUALITY CONTROL TESTING
During construction it is important that work be performed under qualified inspection to ensure proper procedures are followed. We will perform all foundation and earthwork related inspections, and reports will be prepared for your records and submission to the appropriate governmental agencies.
We can also perform testing services, soils, concrete and asphalt for compliance with project requirements.
TSF File No. 7111-19-158
8.0 REPORT LIMITATIONS
The recommendations submitted are based on the available subsurface information obtained by TSF and design details furnished by Stephen Boruff, AIA Architects & Planners, Inc. for the proposed project. If there are any revisions to the plans for this project or if deviations from the subsurface conditions noted in this report are encountered during construction, TSF should be notified immediately to determine if changes in the foundation recommendations are required. If TSF is not retained to perform these functions, TSF will not be responsible for the impact of those conditions of the project.
It is imperative that TSF, be present for observation and testing during construction in order to provide written confirmation (certifications) that the geotechnical engineering study report have been complied with.
The geotechnical engineer warrants that the findings, recommendations, specifications, or professional advice contained herein have been made in accordance with generally accepted professional geotechnical engineering practices in the local area. No other warranties are implied or expressed.
After the plans and specifications are more complete, the geotechnical engineer should be retained and provided the opportunity to review the final design plans and specifications to check that our engineering recommendations have been properly incorporated into the design documents. At that time, it may be necessary to submit supplementary recommendations.
This report has been prepared for the exclusive use of Stephen Boruff, AIA Architects & Planners, Inc. for the proposed Fire Station No. 40 to be constructed in Boynton Beach, Florida.
APPENDIX
Borehole Percolation Test Results Boring Location Plan – Sheet 1
Soil Profiles – Sheet 2 & 3
Test Date Diameter Depth of Depth to Groundwater Level Hydraulic Saturated Hole Average Location Performed Hole Casing Hole Below Ground Surface (Feet) Head, H2 Depth, Ds Flow Rate, Q
(Inches) (Inches) (Feet) Prior to Test During Test (Feet) (Feet) (gpm)
BHP-1 4/23/2019 6 4 10.0 3.9 0.0 3.9 6.1 1.60
BHP-2 4/23/2019 6 4 10.0 3.7 0.0 3.7 6.3 1.90
Note:
(1) The above hydraulic conductivity values represent an ultimate value. The designer should decide on the required factor of safety
(2) The hydraulic conductivity values were calculated based on the South Florida Water Management Districts's USUAL OPEN HOLE CONSTANT
HEAD percolation test procedure.
(3) Casing diameter was used for the calculation of hydraulic conductivity values.
(4) Soils at all locations noted as Light Brown Sand with USCS Classification of SP
(ft3/sec/ft2-ft Head) 1.07E-04
Hydraulic Conductivity (K)
1.34E-04
Summary of Borohole Permeability Test Results Fire Station No. 40
Boynton Beach, Florida
TSF Project No. 7111-19-158
NG
JO
RK
NTS
Sheet:
5/7/2019 11:24:23 AM J:\Tierra Documents\Projects\TSF 2019\7111-19-158.Fire Station No40 (Stephen Boruff)\7111-19-158_Splan_Sprofiles.DGNjoliva
7111-19-158
04-16-2019
ENGINEER OF RECORD:
PROJECT NUMBER:
SCALE:APPROVED BY:
DATE:
DRAWN BY:
CHECKED BY:
53567
FLORIDA LICENSE NO.:
RAJ KRISHNASAMY, P.E.
Approximate Location of SPT Boring
BORING LOCATION PLAN
N
N T
S
RAJ KRISHNASAMY, P.E.
P.E. LICENSE NUMBER 53567
TIERRA SOUTH FLORIDA
2765 VISTA PARKWAY, S-10
WEST PALM BEACH, FL 33411
CERTIFICATE OF AUTHORIZATION 28073
BORING LOCATION PLAN AND SOIL PROFILES
B-2B-1
BHP-2
BHP-1
Approximate Location of BHP Test
BOYNTON BEACH, FLORIDA
B-4
B-3
B-5
AB-1
AB-2
AB-3
AB-4
AB-5
AB-6
AB-7
Approximate Location of Auger Boring
FIRE STATION No. 40
N
TOPSOIL
CRUSHED CONCRETE
DARK BROWN SAND (SP)
66/11"
RIG
HAMMER
DATE
BOR #
CME-55
Auto 4/23/2019 B-1 at Depth of 25ft Boring Terminated
N
TOPSOIL
RIG
HAMMER
DATE
BOR #
CME-55
Auto 4/23/2019 B-2 at Depth of 25ft Boring Terminated
N
TOPSOIL
LIGHT BROWN SAND (SP)
RIG
HAMMER
DATE
BOR #
CME-55
Auto 4/23/2019 B-3 at Depth of 25ft Boring Terminated
N
TOPSOIL
RIG
HAMMER
DATE
BOR #
CME-55
Auto 4/23/2019 B-4 at Depth of 25ft Boring Terminated
N
TOPSOIL
RIG
HAMMER
DATE
BOR #
CME-55
Auto 4/23/2019 B-5 at Depth of 25ft Boring Terminated
LIGHT GRAY SAND (SP)
LIGHT BROWN TO
WITH TRACE SHELL (SP)
LIGHT BROWN SAND
TRACE LIMEROCK (SP)
BROWN SAND WITH
TRACE LIMESTONE (SP)
OCCASIONALLY WITH
LIGHT GRAY SAND
LIGHT BROWN TO
WITH TRACE ORGANIC (SP)
DARK BROWN SAND
TRACE SHELL (SP)
OCCASIONALLY WITH
BROWN SAND
BROWN TO LIGHT
SANDY LIMESTONE
LIGHT BROWN
WITH TRACE ORGANIC (SP)
DARK BROWN SAND
TRACE SHELL (SP)
OCCASIONALLY WITH
BROWN SAND
BROWN TO LIGHT
SILTY SAND (SP-SM)
DARK BROWN SLIGHTLY
BROWN SAND (SP)
BROWN TO LIGHT
TRACE SHELL (SP)
OCCASIONALLY WITH
BROWN SAND
BROWN TO LIGHT
BROWN SAND (SP)
BROWN TO LIGHT
TRACE SHELL (SP)
OCCASIONALLY WITH
LIGHT BROWN SAND
SILTY SAND (SP-SM)
DARK BROWN SLIGHTLY
NG
JO
RK
NTS
Sheet:
5/7/2019 11:24:29 AM J:\Tierra Documents\Projects\TSF 2019\7111-19-158.Fire Station No40 (Stephen Boruff)\7111-19-158_Splan_Sprofiles.DGNjoliva
7111-19-158
05-01-2019
ENGINEER OF RECORD:
PROJECT NUMBER:
SCALE:APPROVED BY:
DATE:
DRAWN BY:
CHECKED BY:
53567
FLORIDA LICENSE NO.:
RAJ KRISHNASAMY, P.E.
RAJ KRISHNASAMY, P.E.
P.E. LICENSE NUMBER 53567
TIERRA SOUTH FLORIDA
2765 VISTA PARKWAY, S-10
WEST PALM BEACH, FL 33411
CERTIFICATE OF AUTHORIZATION 28073
BORING LOCATION PLAN AND SOIL PROFILES
BOYNTON BEACH, FLORIDA
FIRE STATION No. 40
LEGEND
NOTES
ENCOUNTERED GROUNDWATER TABLE
EXISTING GROUND SURFACE
DENOTES DEPTH IN FEET FROM
NUMBERS TO THE LEFT OF BORINGS INDICATE
SPT VALUE FOR 12" PENETRATION.
N
Topsoil
Sand
Concrete
Limestone
25 LIMESTONE (SP)
WITH TRACE
LIGHT BROWN SAND
LIMESTONE (SP)
WITH TRACE
LIGHT BROWN SAND
D e p t h
(f e e t
D e p t h
(f e e t
LEGEND
NOTES
ENCOUNTERED GROUNDWATER TABLE
EXISTING GROUND SURFACE
DENOTES DEPTH IN FEET FROM
NUMBERS TO THE LEFT OF BORINGS INDICATE
SPT VALUE FOR 12" PENETRATION.
N
NG
JO
RK
NTS
Sheet:
5/7/2019 11:24:30 AM J:\Tierra Documents\Projects\TSF 2019\7111-19-158.Fire Station No40 (Stephen Boruff)\7111-19-158_Splan_Sprofiles.DGNjoliva
7111-19-158
05-01-2019
ENGINEER OF RECORD:
PROJECT NUMBER:
SCALE:APPROVED BY:
DATE:
DRAWN BY:
CHECKED BY:
53567
FLORIDA LICENSE NO.:
RAJ KRISHNASAMY, P.E.
RAJ KRISHNASAMY, P.E.
P.E. LICENSE NUMBER 53567
TIERRA SOUTH FLORIDA
2765 VISTA PARKWAY, S-10
WEST PALM BEACH, FL 33411
CERTIFICATE OF AUTHORIZATION 28073
BORING LOCATION PLAN AND SOIL PROFILES
BOYNTON BEACH, FLORIDA
TOPSOIL
BROWN SAND (SP)
DATE
BOR #
4/24/2019
AB-1
TOPSOIL
BROWN SAND (SP)
DATE
BOR #
4/24/2019
AB-2
TOPSOIL
DATE
BOR #
4/23/2019
AB-3
TOPSOIL
DATE
BOR #
4/24/2019
AB-4
TOPSOIL
BROWN SAND (SP)
DARK BROWN SAND (SP)
DATE
BOR #
4/23/2019
AB-5
TOPSOIL
DATE
BOR #
4/23/2019
AB-6
TOPSOIL
LIGHT GRAY SAND (SP)
LIGHT BROWN SAND (SP)
DATE
BOR #
4/23/2019
AB-7
Topsoil
Sand
Concrete
WITH TRACE SHELL (SP)
LIGHT GRAY SAND
WITH TRACE SHELL (SP)
LIGHT GRAY SAND
LIMEROCK (SP)
WITH FEW
OCCASIONALLY
BROWN SAND
WITH TRACE SHELL (SP)
LIGHT GRAY SAND
TRACE SHELL (SP)
OCCASIONALLY WITH
LIGHT GRAY SAND
LIGHT BROWN TO
SILTY SAND (SP-SM)
DARK BROWN SLIGHTLY
BROWN SAND (SP)
BROWN TO LIGHT
TRACE LIMESTONE (SP)
OCCASIONALLY WITH
BROWN SAND
BROWN TO LIGHT
WITH TRACE ORGANIC (SP)
DARK BROWN SAND
TRACE SHELL (SP)
OCCASIONALLY WITH
LIGHT GRAY SAND
LIGHT BROWN TO
SANDY LIMESTONE
LIGHT BROWN
WITH TRACE ORGANIC (SP)
DARK BROWN SAND
Limestone
FIRE STATION No. 40
D e p t h
(f e e t
D e p t h
(f e e t
D e p t h
(f e e t
D e p t h
(f e e t
PALM BEACH COUNTY
FIRE RESCUE STATION NO. 40
PALM BEACH COUNTY PROJECT NO. 16214
CONCRETE TESTING AND CONTROL PAGE-1
SECTION 03 08 16 - CONCRETE TESTING AND CONTROL
PART 1 - GENERAL
1.01 RELATED DOCUMENTS:
A. Drawings and general provisions of contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to work of this Section.
1.02 DESCRIPTION OF WORK:
A. This section includes the laboratory,…