1250 KW BALDOR GENERATORS MONTHLY GENERATOR MAINTENANCE LOG PAGE 1 OF 3

WORK TO BE PERFORMED OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG SEP

MONTHLY

RECORD HOURS OF OPERATION

BEFORE GENERATOR START-UP:

CONDUCT EXTERNAL INSPECTION (CHECK FOR LEAKAGE OF FUEL, OIL, COOLANT)

CHECK FUEL LEVEL AND RECORD READINGS IN LOG. NOTIFY COR IF 1/2 TANK

OR BELOW.

CHECK ENGINE OIL LEVEL (CHECK FOR MIXING OF OIL AND WATER)

CHECK AIR COOLER FOR LEAKS

CHECK ALL BATTERY CONNECTIONS AND ELECTROLYTE LEVELS

RECORD ANTI-FREEZE STRENGTH (CHECK FOR OIL IN COOLANT)

INSPECT FUEL CONTROL LINKAGES AND BALL JOINTS

CLEAN FUEL FILTER (WIRE ELEMENT TYPE) TURN HANDLE ONE OR TWO TIMES

CHECK BELTS FOR WEAR AND REPLACE AS NEEDED

CLEAN INTERIOR OF GENERATOR ENCLOSURE

BLOW OUT GENERATOR WINDINGS

CHECK ALL FUEL LINES FOR LEAKS

CHECK FUEL PUMPS FOR LEAKS AND TEST RUN FOR PROPER OPERATION

CHECK FOR WATER IN ALL FUEL TANKS

WHILE GENERATOR IS RUNNING FOR 1/2 HOUR UNDER LOAD

CHECK FOR EASE OF STARTING, COLOR OF EXHAUST SMOKE, ABNORMAL

VIBRATION, NOISE, SMELL, ETC., AND GAUGE INDICATION OF A PROBLEM

RECORD EXHAUST TEMPERATURE GAUGE, IF PRESENT

RECORD TACHOMETER

RECORD OIL PRESSURE (psi) RECORD FUEL PRESSURE (psi) RECORD FREQUENCY (rpm)

RECORD GENERATED VOLTAGE

RECORD CHARGING AMPERAGE

CHECK GOVERNOR OPERATION

RECORD OUTPUT POWER (KW)

CHECK FUEL INJECTION PUMP AND HYDRAULIC AND ELECTRONIC GOVERNOR

RACK MOVEMENT

INSPECT PARALELLING GEAR FOR PROPER OPERATION; ADJUST AS NEEDED

MANUALLY STICK ABOVEGROUND FUEL TANK AND RECORD READINGS IN LOG

TANK AND RECORD READINGS ON LOG

JADAMS

Typewritten Text

1250 KW BALDOR GENERATORS MONTHLY MAINTENANCE LOG

JADAMS

Typewritten Text

JADAMS

Typewritten Text

JADAMS

Typewritten Text

JADAMS

Typewritten Text

1250 KW BALDOR GENERATORS SEMI-ANNUAL & ANNUAL GENERATOR MAINTENANCE LOG PAGE 2 OF 3

WORK TO BE PERFORMED OCT NOV DEC JAN FEB MAR APR MAY JUN JUL AUG SEP

SEMI-ANNUALLY (OCT, APR)

PERFORM MONTHLY MAINTENANCE

REPLACE AIR FILTERS IF NEEDED

CHECK CONTROL PANEL FOR LOOSE WIRING

CHECK INTAKE/EXHAUST AREAS

CHECK HOLD DOWN BOLTS

CHECK LLC CONCENTRATION IN THE COOLANT

CLEAN THE INSIDE OF THE COOLANT TANK

ANNUALLY (OCT)

PERFORM MONTHLY & SEMI-ANNUAL MAINTENANCE

INSPECT V BELT. ADJUST TENSION AS NEEDED. REPLACE BELTS

AS NEEDED.

INSPECT AND TIGHTEN EXTERNAL NUTS, BOLTS.

INSPECT AND ADJUST VALVE CLEARANCE AND RELATED PARTS

INSPECT VIBRATION ISOLATING RUBBER COMPONENTS

INSPECT FOUNDATION ANCHOR NUTS, BOLTS

INSPECT COUPLINGS. REPLACE COUPLINGS AS NEEDED

DRAIN WATER AND SEDIMENT FROM ALL FUEL TANKS

DRAIN WATER FROM WIRE ELEMENT-TYPE FUEL FILTERS

INSPECT AND ADJUST FUEL INJECTION NOZZLE SPRAY CONDITION

AND SPRAY PRESSURE

INSPECT AND ADJUST FUEL INJECTION TIMING

PERFORM ENGINE OIL SAMPLING AND ANALYSIS

INSPECT AND ADJUST ENGINE OIL PRESSURE

INSPECT WATER PUMP

INSPECT AND CLEAN STRAINER FOR COOLANT

ANALYZE COOLANT PROPERTIES AND REPLACE AS NEEDED

INSPECT AIR FILTER. REPLACE AIR FILTER AS NEEDED.

INSPECT STARTER(S)

INSPECT ALTERNATOR

CHECK SPECIFIC GRAVITY OF BATTERY ELECTROLYTE

INSPECT AIR HEATER

CHECK FOR ANY LOOSE WIRES OR LOOSE CONNECTIONS

CHECK DEVICES FOR PROPER OPERATION: HIGH TEMP, LOW OIL

PRESSURE, OVERSPEED, START FAILURE, WATER SUPPLY FAILURE,

UNDERVOLTAGE, OVERVOLTAGE, OVERCURRENT, LOW COOLANT

LEVEL, LOW FUEL LEVEL, ETC.

CHECK AUXILIARY DEVICES FOR PROPER OPERATION: FUEL

CONTROL SOLENOIDS, FUEL SUPPLY PUMPS, UNIT HEATERS,

WATER JACKET HEATERS, BATTERY CHARGERS, ETC.

AFTER GENERATORS RUN:

CHECK OIL LEVEL

CHECK FOR LEAKS-WATER, FUEL, OIL

CHECK TO INSURE STATUS IN AUTO-START MODE & BREAKERS SET

RECORD SERVICE METER

MAKE ANY REPAIRS OR ADJUSTMENTS AS

NEEDED

TAKE FUEL SAMPLES OF ALL TANKS

IN NOVEMBER AND MAY

JADAMS

Typewritten Text

JADAMS

Typewritten Text

JADAMS

Typewritten Text

1250 KW BALDOR GENERATOR MONTHLY MAINTENACNE LOG

JADAMS

1250 KW BALDOR GENERATORS TWO-YEAR AND FOUR-YEAR GENERATOR MAINTENANCE LOG

WORK TO BE PERFORMED DURING TWO-YEAR MAINTENANCE: 2012 2014 2016 2018 2020 2022

PERFORM MONTHLY, SEMI-ANNUAL, AND ANNUAL

MAINTENANCE (OCT)

CHANGE ENGINE OIL, OIL FILTERS, AND BYPASS OIL

SAMPLE AND ANALYZE ENGINE OIL PROPERTIES

CLEAN WIRE ELEMENT FUEL FILTERS

CHANGE NON-WIRE ELEMENT FUEL FILTERS

DRAIN & CLEAN COOLING SYSTEM

REPLACE THERMOSTATS, GASKETS, AND SEALS

REFILL COOLING SYSTEM

REPLACE RUBBER BELTS & HOSES

REPLACE BATTERIES

CHECK/INSPECT TURBOCHARGERS

WORK TO BE PERFORMED DURING FOUR-YEAR MAINTENANCE: 2012 2016 2020

PERFORM MONTHLY, SEMI-ANNUAL, ANNUAL, AND TWO-YEAR

MAINTENANCE (OCT)

CHECK OIL COOLER FOR SOILING, CLOGGING, AND LEAKAGE

CHECK OIL PUMP FOR DISCOLORATION AND OTHER EXTERNAL

DEFECTS

INSPECT AND TEST GOVERNOR. REPAIR AS NEEDED.

INSPECT AND CLEAN FUEL TANK

INSPECT AND TEST FUEL INJECTION PUMP. REPAIR AS NEEDED.

REPLACE RUBBER HOSES.

INSPECT AND CLEAN AIR CLEANER ELEMENT

INSPECT AND CLEAN PRE-CLEANER

INSPECT ALL GAUGES. REPAIR AS NEEDED.

JADAMS

Typewritten Text

JADAMS

Typewritten Text

JADAMS

1250 KW BALDOR GENERATOR MONTHLY MAINTENACNE LOG