This document appears to be an amendment to a solicitation from the Federal Bureau of Prisons (BOP) for the FCI Englewood Emergency Electrical Repairs project. The BOP is seeking a contractor to remove and replace the vacuum interrupters in 12 existing circuit breakers at the FCI Englewood facility in Littleton, Colorado. The contractor will be responsible for all processes to refurbish and re-install the breaker assemblies with new vacuum interrupters, as well as replace the secondary terminal blocks for 3 specific breakers. The solicitation is a small business set-aside with a NAICS code of 238210 and an estimated project value between $250,000 and $500,000. A pre-bid site visit has been scheduled, and bids must be submitted electronically. The contractor will be required to comply with all local, state, and federal regulations for the work.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FCI ENGLEWOOD – EMERGENCY ELECTRICAL REPAIRS

PROJECT 24Z4AU9 - QUESTIONS & ANSWERS

SOLICITATION 15BFA024B00000023

FROM CBIONE:

1. Would the customer be open to no on-site support?

CLARIFICATION: No, on-site support is required.

2. Can the customer work with a vendor to ship the batches of breakers to our facility, we receive them and perform test & inspection, provide the report with our findings and recommendations? After approvals, we would then proceed to repair any additional parts that may be found to be needed, along with replacement of all vacuum interrupters (per the contract requirements). We would then ship the breakers back to the customer along with their Final Test Reports. We would then repeat this cycle to complete all breakers for the customer. This would not required any on-site contractor support.

CLARIFICATION: No, removal/installation, shipping/handling shall be coordinated and conducted by the contractor at their expense.

FROM MP PREDICTIVE TECHNOLOGIES INC:

3. I see you guys are looking to replace only the vacuum bottles on the breakers, but that is not what the manufacturer recommends as there are cases in which you replace the bottles and not the entire assembly and the breaker still will not work. We would not be comfortable going against the manufacturer’s recommendations, so I wanted to ask you if they would accept replacing the entire vacuum interrupter assemblies rather than only the bottles?

CLARIFICATION: The replacement with all new vacuum interrupters is required as stated in Specification, Part 1.1 Summary of Work, third paragraph.

FROM LG ELECTRICAL:

4. Will the switchgear room be allowed to be utilized for servicing of the breakers?

CLARIFICATION: Yes, the switchgear room can be utilized.

5. If not, is there a facility nearby that can be used for service?

CLARIFICATION: N/A

6. If the breakers are to be serviced off the installation, is there a time restriction on how long they can be off-site for?

CLARIFICATION: All work shall be completed within the period of performance.

7. Normally, we would test the vacuum bottle integrity, contact resistance, contact erosion, and insulation resistance to ensure the breaker needs to be repaired. This solicitation is asking for only the bottles to be changed and secondary contacts on the specified breakers. Does that mean no as found testing is necessary?

CLARIFICATION: See Attachment #1, testing and inspection report attachment.

8. Should this bid include acceptance testing after the vacuum bottles are changed?

CHANGE: See Attachment #2, Addendum to Specification.

FROM UTILITY SYSTEMS SOLUTIONS, INC.

9. Page 4 of the Instructions to Bidders, Part IV-2 requires a bank reference questionnaire. We are frequently bidding

FBOP opportunities that require this form. To lessen the burden on our bank representative, can the questionnaire information on the bank letterhead submitted with our proposal suffice in place of the form?

CLARIFICATION: The completed reference document must come from your reference, not from an email address in your firm.

10. Will you please provide a copy of the sign-in sheet from the pre-bid site visit?

CLARIFICATION: The sign-in sheet was included with solicitation amendment 0001.

11. On page 4 of Instruction to Bidders, part IV-, Past Performance Requirements, restricts project references to the last 24 months. Will you consider extending this to 48 months so that we can submit CPARS for completed projects in lieu of PPQs?

CLARIFICATION: CPARS evaluations are acceptable in lieu of past performance questionnaires.

12. Since this project is located outside of the secured perimeter (powerhouse), what level of background clearance and badging will be required? Will this be NCIC + Memo or full contractor badging?

CLARIFICATION: This will require NCIC clearance.

FROM BOLD NEW SOLUTIONS, INC:

13. How old are the breakers?

CLARIFICATION: Breakers were installed in 2006.

14. Was there a failure that necessitated this repair?

CLARIFICATION: Testing indicated low vacuum levels.

15. Can you provide one-line diagrams?

CLARIFICATION: See Attachment #3 for diagram.

From HD INC.:

16. Is this project tax exempt?

CLARIFICATION: See Solicitation Page 4: The successful contractor shall be responsible for all applicable federal, state, and local taxes. No tax exemption certification will be issued by the Federal Bureau of Prisons.

17. Are restrooms available for contractor use?

CLARIFICATION: Yes, restroom will be available onsite.

18. Referring to the SOW “…and approved breaker refurbishment shall be completed.” The parts and pieces are unknown until the work takes place. Can the Owner provide a detailed breakdown of parts and pieces that are to be part of the refurbishment of the approved breakers?

CLARIFICATION: No.

ATTACHMENT #1

4.1 Upon inspection of the switchgear, Feeder Breaker 3A, Feeder Breaker 4A and Feeder Breaker 1B had Broken Secondary terminal blocks. recommends replacing the terminal blocks.

FCI ENGLEWOOD

Recommendations

1. Breaker UTILITY MAIN 1: 0197A1307-001-16

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A phase VI is at a level approaching the point of failure.

The internal pressure reading of A phases VI would lead us to recommend that A phase VI be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-16

DoM 04/06 VI Type 41A2

MAC Result A 5.09E-02 Pa MAC Result B 7.10E-04 Pa MAC Result C 9.38E-04 Pa

2. Breaker GEN 1: 0197A1307-001-03

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A phase VI is at a level approaching the point of failure.

The internal pressure reading of A phases VI would lead us to recommend that A phase VI be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-03

DoM 04/06 VI Type 41A2

MAC Result A 1.81E-03 Pa MAC Result B 1.33E-02 Pa MAC Result C 9.78E-04 Pa

3. Breaker FEEDER 1A: 0197A13C7-001-06

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

4. Breaker FEEDER 2A: 0197A1307-001-12

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A13C7-001-06

DoM 04/06 VI Type 41A2

MAC Result A 1.29E-01 Pa MAC Result B 3.52E-02 Pa MAC Result C 4.05E-02 Pa

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A13C7-001-12

DoM 04/06 VI Type 41A2

MAC Result A 2.15E-02 Pa MAC Result B 1.53E-02 Pa MAC Result C 2.89E-02 Pa

5. Breaker FEEDER 4A: 0197A1307-001-17

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

6. Breaker FEEDER 3A: 0197A1307-001-01

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-17

DoM 04/06 VI Type 41A2

MAC Result A 2.81E-02 Pa MAC Result B 2.20E-02 Pa MAC Result C 3.76E-01 Pa

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-01

DoM 04/06 VI Type 41A2

MAC Result A 6.44E-03 Pa MAC Result B 3.03E-02 Pa MAC Result C 4.66E-02 Pa

7. Breaker FEEDER 5A: 0197A1307-001-15

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

8. Breaker FEEDER 6A: 0197A1307-001-09

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-01

DoM 04/06 VI Type 41A2

MAC Result A 2.49E-02 Pa MAC Result B 6.04E-02 Pa MAC Result C 6.19E-02 Pa

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-09

DoM 04/06 VI Type 41A2

MAC Result A 1.23E-02 Pa MAC Result B 1.52E-02 Pa MAC Result C 1.28E-02 Pa

9. Breaker FEEDER 6B: 0197A1307-001-08

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

10. Breaker FEEDER 4B: 0197A1307-001-13

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in C phase VI i s at a level approaching the point of failure. The internal pressure reading of C phase VI would lead us to recommend that C phase VI be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-08

DoM 04/06 VI Type 41A2

MAC Result A 1.74E-02 Pa MAC Result B 2.40E-02 Pa MAC Result C 4.25E-02 Pa

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-13

DoM 04/06 VI Type 41A2

MAC Result A 2.56E-03 Pa MAC Result B 3.80E-03 Pa MAC Result C 1.95E-02 Pa

11. Breaker FEEDER 3B: 0197A1307-000-04

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

12. Breaker FEEDER 2B: 0197A1307-001-02

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-000-04

DoM 04/06 VI Type 41A2

MAC Result A 2.16E-02 Pa MAC Result B 1.02E-02 Pa MAC Result C 4.65E-02 Pa

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-01

DoM 04/06 VI Type 41A2

MAC Result A 2.77E-02 Pa MAC Result B 5.65E-02 Pa MAC Result C 1.16E-02 Pa

13. Breaker FEEDER 1B: 0197A1307-001-10

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

14. Breaker GEN 2: 0197A1307-001-05

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A a n d C phases VIs would lead us to recommend that A a n d C phase VIs be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-10

DoM 04/06 VI Type 41A2

MAC Result A 2.35E-02 Pa MAC Result B 2.19E-02 Pa MAC Result C 2.56E-02 Pa

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-05

DoM 04/06 VI Type 41A2

MAC Result A 1.13E-02 Pa MAC Result B 4.11E-03 Pa MAC Result C 2.07E-02 Pa

15. Breaker UTILITY MAIN 2: 0197A1307-001-11

Breaker Data:

This GE/Power Vac was tested using the MAC-TS4 and R i g i d coil. From the research we’ve conducted, the pressure in A , B , a n d C phase VIs are at a level approaching the point of failure. The internal pressure reading of A , B , a n d C phases VIs would lead us to recommend that A , B , a n d C phase VIs be replaced.

Manufacturer GE/POWER VAC Model VB1 13.8-750-3

Rated Current 1200 A S/N 0197A1307-001-11

DoM 04/06 VI Type 41A2

MAC Result A 1.99E-02 Pa MAC Result B 2.97E-02 Pa MAC Result C 6.76E-02 Pa

VACUUM INTERRUPTER

INFORMATION

POWER HOUSE MEDIUM

VOLTAGE CIRCUIT

BREAKERS

100 ― 140 70 ― 140

± 50 % MFR MAX (µΩ)

PASS PASS

B ↔ B C ↔ C RATINGA ↔ A

A → G

A

CALC. MAX Δ

0.0

RATING

1200 Amps

58 kA

15 kVac

Vdc Vdc

X A

3/16/23

COIL PICKUP

RATING

MIN MAX RESULT** MIN MAX RESULT**

B (µΩ) C (µΩ)

A (µΩ)

7 25 5.00E-02 5.09E-02 7.10E-04 9.38E-04

RATING

U

95 kVac S-C CURRENT 26 kA

ELECTRICAL TESTS

NAMEPLATE DATA

ANCH. / ALIGNMENT & GROUNDING X A N/A

PHYSICAL / MECH. CONDITION X A

MECH. OPERATION / MANUAL TRIP

CONTACT RESISTANCE

A ↔ A (Pa) B ↔ B (Pa)

B C

CLOSE COIL - PICKUP TRIP COIL - PICKUP

RH% 23% TECHNICIAN(S)

TIMER ASSET-CAL N/A

MAC ASSET-CAL

N/A

RATING

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa)

VACUUM BOTTLE ASSEMBLY

N/A N/A

MANUFACTURER GE SYSTEM VOLTAGE MOTOR VOLTAGE 125 Vdc

A

MAINTENANCE DEVICES AVAILABLE

X

OVERALL CLEANLINESS

N/A N/A

N/A N/A

NAMEPLATE DATA

13.8 kVac

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE CONT. CURRENT

7.6.3NETA SECTION

JOB NUMBER

MV VACUUM BREAKER FORM

CUSTOMER FCI Englewood DATE 12/5/23 ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F

UTILITY MAIN BRKR 1

SUBSTATION POWER HOUSE POSITION 101 EQUIP. ID UTILITY MAIN BRKR 1

CLOSE to OPEN

A B C A MIN / MAX MIN / MAX

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

5TRIP COIL INT. TIME (CYCLES)

X

USER / OWNER REP

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

PASS

A ↔ A B ↔ B C → GC ↔ C A → B

BULLETIN / MANUAL GEK-86132

STYLE VB113.8-750-3

SERIAL No. 0197A1307-001-16 CLOSE COIL C&L CURRENT

IMPULSE VOLTAGE

vACUUM BOTTLE ASSEMBLY

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

COUNTER - AF / AL

AS-FOUND AS-LEFT RATING

997 10007 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

DEFICIENCIES The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

TIMING TESTS***

OPEN to CLOSE

C ↔ C (Pa)

RACKING MECHANISM OPERATION

N/A X A

A

B → C C → A A → G B → G

APPROPRIATE LUBRICATION

POWER / DISSIPATION FACTOR***

CONTACT TIMING TESTS

TIME-TRAVEL ANALYSIS***

RATING

PHASE to GROUND (MΩ)

X A

HEATER OPERATION

X A

INS-RES / CONTROL WIRING***

X U

CHARGING MOTOR

N/A N/A A

COUNTER CONDITION

X X A

CELL FIT & ALIGNMENT

NETA MTS OPTION***

kVdc

DIELECTRIC WITHSTAND TEST VOLTAGE

CRITICAL DISTANCES / CONTACT GAP

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ)

MAX Δ %

MTS OPTION***

TEST Amps

C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE

B → G

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR6A

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR6A

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION OLD POWER HOUSE

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-09 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

A ↔ A B ↔ B

C → G

C ↔ C A → B B → C C → A A → G B → G

PASS A

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RESULT**COIL PICKUP

CLOSE COIL - PICKUP TRIP COIL - PICKUP

TIMING TESTS***

OPEN to CLOSE CLOSE to OPEN

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 1.23E-02 1.52E-02 1.28E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

DEFICIENCIES

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR5A

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR5A

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 32-XF-001

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-15 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.49E-02 6.04E-02 6.19E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

809 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR. 3A

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR. 3A

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 103

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-01 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 6.44E-03 3.03E-02 4.66E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

422 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

Upon initial inspection of the cabinet the secondary terminal block is broken and needs replaced.

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR. 4A

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR. 4A

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 104

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-17 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.81E-02 2.20E-02 3.76E-01

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

403 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR 2A

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR 2A

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 103

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0137A1307-001-12 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.15E-02 1.53E-02 2.89E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

654 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

DEFICIENCIES

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

799 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 1.81E-03 1.33E-02 9.78E-04

MIN / MAX A B C MIN / MAX A B

COIL PICKUP

RATING

C

MTS OPTION***

RATING

MIN MAX RESULT** MIN MAX

100 0.0

RESULT**

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS PASS A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

RATING

A ↔ A B ↔ B

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-03 CLOSE COIL Vdc C&L CURRENT 58 kA

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 102 EQUIP. ID GEN BRKR 1

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL

MV VACUUM BREAKER FORM

GEN BRKR 1

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

70 ― 140

± 50 %

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

DEFICIENCIES

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

259 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 1.29E-01 3.52E-02 4.05E-02

MIN / MAX A B C MIN / MAX A B

COIL PICKUP

RATING

C

MTS OPTION***

RATING

MIN MAX RESULT** MIN MAX

100 0.0

RESULT**

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS PASS A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

RATING

A ↔ A B ↔ B

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A13C7-001-06 CLOSE COIL Vdc C&L CURRENT 58 kA

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 101 EQUIP. ID FEEDER BRK.1A

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL

MV VACUUM BREAKER FORM

FEEDER BRK.1A

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

UTILITY MAIN-2

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID UTILITY MAIN-2

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 110

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-11 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 1.99E-02 2.97E-02 6.76E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

1095 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR 4B

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR 4B

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 108

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-13 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.56E-03 3.80E-03 1.95E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

373 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR 2B

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR 2B

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 108

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-02 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.77E-02 5.65E-02 1.16E-01

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

447 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

GEN BRKR2

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID GEN BRKR2

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 109

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-05 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 1.13E-02 4.11E-03 2.07E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

815 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR 1B

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR 1B

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 107

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-10 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.35E-02 2.19E-02 2.56E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

286 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR 3B

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR 3B

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 107

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-000-04 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 2.16E-02 1.02E-02 4.65E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

391 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

70 ― 140

± 50 %

MV VACUUM BREAKER FORM

FEEDER BRKR 6B

CUSTOMER FCI Englewood DATE 12/5/23 NETA SECTION 7.6.3

EQUIP. ID FEEDER BRKR 6B

MAC ASSET-CAL 3/16/23

USER / OWNER REP RH% 23% TECHNICIAN(S)

ADDRESS 9595 W Quincy Ave, Littleton, CO 80123 TEMP 62 °F JOB NUMBER

INS-RES ASSET-CAL 3/16/2023 PWR SPLY ASSET-CAL N/A

SUBSTATION POWER HOUSE POSITION 107

N/A

NAMEPLATE DATA

MANUFACTURER GE SYSTEM VOLTAGE 13.8 kVac MOTOR VOLTAGE 125 Vdc

DLRO ASSET-CAL 3/16/23 HI-POT ASSET-CAL N/A TIMER ASSET-CAL

TYPE or CAT No. POWER/VAC RATED VOLTAGE 15 kVac CONT. CURRENT 1200 Amps

BULLETIN / MANUAL GEK-86132 TRIP COIL Vdc INT. TIME (CYCLES) 5

26 kA SERIAL No. 0197A1307-001-08 CLOSE COIL Vdc C&L CURRENT 58 kA STYLE VB113.8-750-3 IMPULSE VOLTAGE 95 kVac S-C CURRENT vACUUM BOTTLE ASSEMBLY

DESCRIPTION INSPECTED CONDITION DESCRIPTION INSPECTED CONDITION

PHYSICAL / MECH. CONDITION X A APPROPRIATE LUBRICATION X A

NAMEPLATE DATA X A RACKING MECHANISM OPERATION X A

OVERALL CLEANLINESS X A INS-RES / CONTROL WIRING*** X A

MAINTENANCE DEVICES AVAILABLE N/A N/A TIME-TRAVEL ANALYSIS*** N/A N/A

ANCH. / ALIGNMENT & GROUNDING X A CONTACT TIMING TESTS N/A N/A

MECH. OPERATION / MANUAL TRIP X A COUNTER CONDITION X A

VACUUM BOTTLE ASSEMBLY X U POWER / DISSIPATION FACTOR*** N/A N/A

CELL FIT & ALIGNMENT X A HEATER OPERATION N/A N/A

CRITICAL DISTANCES / CONTACT GAP X A CHARGING MOTOR X A

ELECTRICAL TESTS

INSULATION RESISTANCE LINE to LOAD (MΩ) PHASE to PHASE (MΩ) PHASE to GROUND (MΩ)

DIELECTRIC WITHSTAND TEST VOLTAGE A → G B → G C → G RATING

VACUUM BOTTLE

INTEGRITY

TEST VOLTAGE A ↔ A B ↔ B C ↔ C RATING

25 kVdc PASS PASS

CONTACT RESISTANCE

TEST Amps MAX Δ % MFR MAX (µΩ) A (µΩ) B (µΩ) C (µΩ) CALC. MAX Δ RATING

NETA MTS OPTION***

MIN MAX RESULT** MIN MAX

100 0.0

RATING

C

MTS OPTION***

RATING

MIN / MAX A B C MIN / MAX A B

AS-FOUND AS-LEFT RATING

7 25 5.00E-02 1.74E-02 2.40E-02 4.25E-02

The vacuum bottle has been tested and determined that the internal pressure is very high and its expected service life is less than 5 years. recommends annual retesting of the circuit breaker vacuum bottles and monitoring while in operation.

737 A

COMMENTS

Breaker has been cleaned, lubricated, MAC tested and inspected in accordance to NEATA MTS specifications.

MAGNETRON

ATMOSPHERIC

CONDITION***

CURVE No. HV No. MINIMUM (Pa) A ↔ A (Pa) B ↔ B (Pa) C ↔ C (Pa) RATING U

COUNTER - AF / AL

LEGEND: A - ACCEPTABLE U - UNACCEPTABLE I - INVESTIGATE N/A - NOT APPLICABLE *** NETA OPTIONAL TESTS ***

PROJECT 24Z4AU9

EMERGENCY ELECTRICAL REPAIRS

ADDENDUM TO SPECIFICATION

The following changes are made to the specification:

1. Page 2; Section 1.1, A, Summary of Work, paragraph 3 is changed to read as follows:

Contracto…