FIRE ALARM INSPECTION
REPORT
SITE: Herlong Federal Prison/Tahoe
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
101 SD A VENDING PHONE RM 160 TESTED 7/11/2017 PASSED
102 SD A TV ACTIVITY RM 159 TESTED 7/11/2017 PASSED
103 SD A TELEVISION ACTIVITY RM 157 TESTED 7/11/2017 PASSED
104 SD A DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED
105 SD A TV ACTIVITY RM 243 TESTED 7/11/2017 PASSED
106 SD A TV ACTIVITY RM 244 TESTED 7/11/2017 PASSED
107 SD A TV ACTIVITY RM 246 TESTED 7/11/2017 PASSED
108 SD A ENTRY VESTIBULE RM 165 TESTED 7/11/2017 PASSED
109 SD A INMATE PHONE RM 249 TESTED 7/11/2017 PASSED
112 SD A DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
113 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
114 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
115 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
116 SD A DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
117 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
118 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
119 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
120 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
121 SD A DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
122 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
123 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED
124 SD B VENDING PH RM 137 TESTED 7/11/2017 PASSED
125 SD B TV ACTIVITY RM 138 TESTED 7/11/2017 PASSED
126 SD B TV ACTIVITY RM 140 TESTED 7/11/2017 PASSED
127 SD B DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED
128 SD B TV ACTIVITY RM 235 TESTED 7/11/2017 PASSED
129 SD B TV ACTIVITY RM 237 TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/Tahoe
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
130 SD B TV ACTIVITY RM 238 TESTED 7/11/2017 PASSED
131 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
132 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
133 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
134 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
135 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
136 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
137 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
138 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
139 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
140 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
141 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
142 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
143 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED
144 SD A REFUGE RM 153 TESTED 7/11/2017 PASSED
145 SD A SECRETARY RM 151 TESTED 7/11/2017 PASSED
146 SD A CORE CORRIDOR TESTED 7/11/2017 PASSED
147 SD A CORE CORRIDOR TESTED 7/11/2017 PASSED
149 SD B MECH RM 239 TESTED 7/11/2017 PASSED
150 SD B SECURITY ELECTRONICS RM 240 TESTED 7/11/2017 PASSED
153 DD MECH AHU-H-3-1 SUPPLY 2 TESTED 7/11/2017 PASSED
154 DD MECH AHU H-3-1 SUPPLY 3 TESTED 7/11/2017 PASSED
155 DD MECH AHU H-3-1 SUPPLY 4 TESTED 7/11/2017 PASSED
156 DD MECH AHU H-3-1 SUPPLY 5 TESTED 7/11/2017 PASSED
157 DD MECH AHU H-3-1 SUPPLY 6 TESTED 7/11/2017 PASSED
158 DD MECH AHU H-3-1 SUPPLY 7 TESTED 7/11/2017 PASSED
159 SD C ENTRY VESTIBULE RM 365 TESTED 7/11/2017 PASSED
160 SD C INMATE PHONE RM 449 TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/Tahoe
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
163 DD MECH AHU H-3-1 RETURN A TESTED 7/11/2017 PASSED
164 DD MECH AHU H-3-1 RETURN B TESTED 7/11/2017 PASSED
222 PS A OFFICERS DESK H 167 TESTED 7/11/2017 PASSED
223 PS A DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED
224 PS A ENTRY VESTIBULE RM 165 TESTED 7/11/2017 PASSED
226 PS B OFFICERS DEK RM 166 TESTED 7/11/2017 PASSED
227 PS B DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED
228 PS D1 PLUMBING RM 149 TESTED 7/11/2017 PASSED
229 PS A REFUGE RM 153 TESTED 7/11/2017 PASSED
230 PS A MECH RM 239 EAST TESTED 7/11/2017 PASSED
231 PS A MECH RM 239 NORHT TESTED 7/11/2017 PASSED
232 PS A MECH RM 239 TESTED 7/11/2017 PASSED
233 DD A SUPPLY 1 TESTED 7/11/2017 PASSED
234 DD A SUPPLY 2 TESTED 7/11/2017 PASSED
235 DD A SUPPLY 3 TESTED 7/11/2017 PASSED
236 DD A SUPPLY 4 TESTED 7/11/2017 PASSED
237 DD A AHU-H31 SUPPLY 5 TESTED 7/11/2017 PASSED
238 DD A AHU-H31 SUPPLY 6 TESTED 7/11/2017 PASSED
239 DD A AHU-H31 SUPPLY 7 TESTED 7/11/2017 PASSED
240 WF 1 PLUMBING RM 148 TESTED 7/11/2017 PASSED
241 TS 1 PLUMBING RM 149 TESTED 7/11/2017 PASSED
249 PS 1 ENTRY VESTIBULE TESTED 7/11/2017 PASSED
250 DD 1 RETURN A TESTED 7/11/2017 PASSED
251 TS 1 PLUMBING RM 149 TESTED 7/11/2017 PASSED
256 DD 1 RETURN B TESTED 7/11/2017 PASSED
301 SD B ENTRY VESTIBULE TESTED 7/11/2017 PASSED
302 SD B INMATE PHONE RM 242 TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/Tahoe
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
305 SD C VENDING PH RM 360 TESTED 7/11/2017 PASSED
306 SD C TV ACTIVITY RM 359 TESTED 7/11/2017 PASSED
307 SD C TV ACTIVITY RM 357 TESTED 7/11/2017 PASSED
308 SD C DAYROOM CORE RM TESTED 7/11/2017 PASSED
309 SD C TV ACTIVITY RM 446 TESTED 7/11/2017 PASSED
310 SD C TV ACTIVITY RM 444 TESTED 7/11/2017 PASSED
311 SD C TV ACTIVITY RM 443 TESTED 7/11/2017 PASSED
312 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
313 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
314 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
315 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
316 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
317 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
318 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
319 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
320 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
321 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
322 SD D VENDING PHONE RM 337 TESTED 7/11/2017 PASSED
323 SD D TV ACTIVITY RM 338 TESTED 7/11/2017 PASSED
324 SD D TV ACTIVITY RM 340 TESTED 7/11/2017 PASSED
325 SD D DAY ROOM TO CORE ENTRY TESTED 7/11/2017 PASSED
326 SD D TV ACTIVITY RM 438 TESTED 7/11/2017 PASSED
327 SD D TV ACTIVITY RM 437 TESTED 7/11/2017 PASSED
328 SD D TV ACTIVITY RM 435 TESTED 7/11/2017 PASSED
329 SD D ENTRY VESTIBULE RM 356 TESTED 7/11/2017 PASSED
330 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
333 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
334 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/Tahoe
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
335 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
336 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
337 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
338 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
339 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
340 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
341 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
342 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED
343 SD D CORE CORRIDOR TESTED 7/11/2017 PASSED
344 SD D REFUGE RM 353 TESTED 7/11/2017 PASSED
345 SD D SECRETARY RM 351 TESTED 7/11/2017 PASSED
346 SD D CORE CORRIDOR TESTED 7/11/2017 PASSED
347 SD D CORRIDOR NEAR STAIRS RM 268 TESTED 7/11/2017 PASSED
403 PS A CORRIDOR NEAR STAIRS RM 267 TESTED 7/11/2017 PASSED
404 PS B ENTRY VESTIBULE RM 156 TESTED 7/11/2017 PASSED
406 PS B CORRIDOR NEAR STAIRS RM 266 TESTED 7/11/2017 PASSED
407 PS C OFFICERS DESK RM 367 TESTED 7/11/2017 PASSED
408 PS C Day Room TESTED 7/11/2017 PASSED
409 PS C DAYROOM NEAR STAIRWELL TESTED 7/11/2017 PASSED
410 PS C CORRIDOR NEAR STAIR RM 467 TESTED 7/11/2017 PASSED
411 PS D OFFICERS DESK RM 368 TESTED 7/11/2017 PASSED
412 PS D DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED
413 PS D ENTRY VESTIBULE RM 356 TESTED 7/11/2017 PASSED
414 PS D DAYROOM NEAR STAIRWELL TESTED 7/11/2017 PASSED
415 PS D CORRIDOR NEAR STAIR RM 468 TESTED 7/11/2017 PASSED
416 PS D REFUGE RM 353 TESTED 7/11/2017 PASSED
417 PS C MECH RM 439 EAST TESTED 7/11/2017 PASSED
418 PS C MECH RM 439 NORTH TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/Tahoe
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
419 PS C MECH RM 439 WEST TESTED 7/11/2017 PASSED
420 DD MECH AHU H3-2 SUPPLY 1 TESTED 7/11/2017 PASSED
421 DD MECH TESTED 7/11/2017 PASSED
422 DD MECH AHU H3-2 SUPPLY 3 TESTED 7/11/2017 PASSED
423 DD MECH AHU H3-2 SUPPLY 4 TESTED 7/11/2017 PASSED
424 DD MECH AHU H3-2 SUPPLY 5 TESTED 7/11/2017 PASSED
425 DD MECH AHU H3-2 RETURN SIDE B TESTED 7/11/2017 PASSED
426 DD MECH AHU H3-3 SUPPLY 1 TESTED 7/11/2017 PASSED
427 DD MECH AHU H3-3 SUPPLY 2 TESTED 7/11/2017 PASSED
428 DD MECH AHU H3-3 SUPPLY 3 TESTED 7/11/2017 PASSED
429 DD MECH AHU H3-3 SUPPLY 4 TESTED 7/11/2017 PASSED
430 DD MECH AHU H3-3 SUPPLY 5 TESTED 7/11/2017 PASSED
431 DD MECH AHU H3-3 RETURN SIDE A TESTED 7/11/2017 PASSED
ANN A A ENTRANCE TESTED 7/11/2017 PASSED
ANN B B ENTRANCE TESTED 7/11/2017 PASSED
ANN C C ENTRANCE TESTED 7/11/2017 PASSED
ANN D D ENTRANCE TESTED 7/11/2017 PASSED
AHU H3-2 SUPPLY 2
SITE: Herlong Federal Prison/FOOD SERVICE
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer DT Duct Test Switch VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP 1 EST 2 TESTED 7/11/2017 PASSED
101 SD 1 FACP ROOM TESTED 7/11/2017 PASSED
107 SD 1 SECURITY ELEC TESTED 7/11/2017 PASSED
114 PS 1 VESTABULE TESTED 7/11/2017 PASSED
216 PS 1 FS ELECTRICAL ROOM TESTED 7/11/2017 PASSED
217 PS 1 RECEIVING RM 1 RM 144 TESTED 7/11/2017 PASSED
218 PS 1 CAN WASH RM 116 TESTED 7/11/2017 PASSED
219 PS 1 STAFF DINING RM 110 TESTED 7/11/2017 PASSED
220 PS 1 DINING RM 133 NE TESTED 7/11/2017 PASSED
221 PS 1 DINING RM 133 NW TESTED 7/11/2017 PASSED
222 PS 1 MECH ROOM 142 TESTED 7/11/2017 PASSED
223 DD 1 AHU-FC-FS-1 SUPPLY TESTED 7/11/2017 PASSED
224 DD 1 AHU-FS-2 SUPPLY TESTED 7/11/2017 PASSED
225 DD 1 AHU-FS-1 SUPPLY TESTED 7/11/2017 PASSED
226 DD 1 MAU-FS-1 SUPPLY RM 1 TESTED 7/11/2017 PASSED
227 DD 1 MAU-FS-2 SUPPLY RM 101 TESTED 7/11/2017 PASSED
228 DD 1 KIT HOOD SUPPLY BAKERY TESTED 7/11/2017 PASSED
230 DD 1 T5100 NORTH KIT 1800 SUPPLY TESTED 7/11/2017 PASSED
232 KIT HOOD STAFF LOUNGE TESTED 7/11/2017 PASSED
233 WF 1 MECH ROOM 4" TESTED 7/11/2017 PASSED
234 TS FS MECH ROOM TESTED 7/11/2017 PASSED
235 TS FS ISO VALVE TESTED 7/11/2017 PASSED
241 PS FS/PS SECURITY ELEC TESTED 7/11/2017 PASSED
242 PS FS/PS ELECTRICAL ROOM TESTED 7/11/2017 PASSED
243 PS FS/PS MECH RM PS 136 N TESTED 7/11/2017 PASSED
244 PS FS/PS LOBBY PS 133 W TESTED 7/11/2017 PASSED
245 PS FS/PS LOBBY PS 133 E TESTED 7/11/2017 PASSED
246 PS FS/PS WORKROOM CLERK TESTED 7/11/2017 PASSED
247 PS PULL INSIDE WHSE PS117N TESTED 7/11/2017 PASSED
248 PS PULL BARBER TESTED 7/11/2017 PASSED
249 PS PS VESTIBLE TESTED 7/11/2017 PASSED
250 PS FS/PS SALES LOBBY PS 113 E TESTED 7/11/2017 PASSED
251 PS FS/PS SALES LOBBY PS 113 E TESTED 7/11/2017 PASSED
252 PS FS/PS COMM STORAGE PS 102 TESTED 7/11/2017 PASSED
253 PS FS/PS INSIDE WHSE PS 117 S TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/FOOD SERVICE
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
254 PS FS/PS LAUNDRY PS 129 TESTED 7/11/2017 PASSED
255 PS FS/PS MECH RM PS 136 TESTED 7/11/2017 PASSED
256 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED
257 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED
258 WF FS/PS MECH RM PS 136 4' 195/105/115 TESTED 7/11/2017 PASSED
259 TS FS/PS DRY SYSTEM LOADING DOCK TESTED 7/11/2017 PASSED
260 TS FS/PS ISO VALVE RM PS 136 TESTED 7/11/2017 PASSED
270 WF FS/PS ISO VALVE RM PS 136 TESTED 7/11/2017 PASSED
271 DRY FS/PS DRY SYSTEM TO AIR DOCK MECH RM 126 TESTED 7/11/2017 PASSED
274 TS FS/PS ISO VALVE RM PS 136 TESTED 7/11/2017 PASSED
275 DD 1 AHU-FS-1 RETURN TESTED 7/11/2017 PASSED
276 DD 1 AHU-FS-2 RETURN TESTED 7/11/2017 PASSED
277 DD 1 AHU-FC-1 RETURN TESTED 7/11/2017 PASSED
278 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED
279 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED
292 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED
293 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED
294 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED
295 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED
296 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED
403 PS MS MECHANICAL ROOM MS 112 TESTED 7/11/2017 PASSED
404 PS MS ELECTRICAL ROOM TESTED 7/11/2017 PASSED
405 PS MS OPEN SHOP FAB 118 TESTED 7/11/2017 PASSED
406 PS MS CARPENTER SHOP 119 TESTED 7/11/2017 PASSED
407 PS MS STORAGE RM 120 TESTED 7/11/2017 PASSED
408 PS MS CORRIDOR MS 100 TESTED 7/11/2017 PASSED
409 DD MS AHU MS-1 SUPPLY MS 112 TESTED 7/11/2017 PASSED
410 TS MS TAMPER 2 SPRINKLER RM 123 TESTED 7/11/2017 PASSED
415 PS SG SECURITY ELECTRONICS SG 104 TESTED 7/11/2017 PASSED
416 PS SG OFFICERS DESK SG 100 TESTED 7/11/2017 PASSED
417 WF SG BLDG SG 102 2" TESTED 7/11/2017 PASSED
418 TS MS STORAGE SG 102 TESTED 7/11/2017 PASSED
419 DD MS AHU MS-1 RETURN 112 TESTED 7/11/2017 PASSED
420 WF MS SPRINKLER RM MS 123 4" TESTED 7/11/2017 PASSED
421 TS MS SPRINKLER RM 123 TESTED 7/11/2017 PASSED
422 TS SG STORAGE SG 102 TESTED 7/11/2017 PASSED
ANN FS/PS TESTED 7/11/2017 PASSED
SITE: Herlong Federal Prison/SIERRA
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP 2 EST2 TESTED 7/12/2017 PASSED
101 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
102 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
103 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
104 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
105 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
106 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
107 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
108 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
109 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
110 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
111 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
112 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
113 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
122 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
123 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
124 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
125 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
126 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
127 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
128 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
129 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
130 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
131 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
132 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
133 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
134 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/SIERRA
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
135 SD A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED
136 SD A INMATE PHONES RM 249 TESTED 7/12/2017 PASSED
137 SD C INMATE PHONE RM 442 TESTED 7/12/2017 PASSED
138 SD C ENTRY VETIBULE RM 365 TESTED 7/12/2017 PASSED
139 SD A ELEVATOR MECH SUPPLY 2 TESTED 7/12/2017 PASSED
140 SD A TV ACTIVITY RM TESTED 7/12/2017 PASSED
141 SD A TV ACTIVITY RM 244 TESTED 7/12/2017 PASSED
142 SD A TV ACTIVITY RM 246 TESTED 7/12/2017 PASSED
143 SD A TV ACTIVITY RM 235 TESTED 7/12/2017 PASSED
144 SD B TV ACTIVITY RM 237 TESTED 7/12/2017 PASSED
145 SD B TV ACTIVITY RM 238 TESTED 7/12/2017 PASSED
146 SD A MECH RM 239 TESTED 7/12/2017 PASSED
147 SD A ELECTRONICS RM 240 TESTED 7/12/2017 PASSED
212 PS A MECH RM 239 SOUTH TESTED 7/12/2017 PASSED
213 PS A MECH RM 239 WEST TESTED 7/12/2017 PASSED
214 PS A MECH RM 239 NORTH TESTED 7/12/2017 PASSED
224 DD A AHU-H2-1 SUPPLY 1 TESTED 7/12/2017 PASSED
226 DD A AHU-H2-1 SUPPLY 2 TESTED 7/12/2017 PASSED
227 DD A AHU-H2-1 SUPPLY 4 TESTED 7/12/2017 PASSED
228 DD A AHU-H2-1 SUPPLY 5 TESTED 7/12/2017 PASSED
229 DD A AHU-H2-1 SUPPLY 6 TESTED 7/12/2017 PASSED
230 DD A AHU-H2-1 SUPPLY 7 TESTED 7/12/2017 PASSED
231 DD A AHU-H2-1 SUPPLY 8 TESTED 7/12/2017 PASSED
232 PS C ENTRY VESTIBULE RM 365 TESTED 7/12/2017 PASSED
233 PS A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED
234 PS A OFFICERS DESK RM 167 TESTED 7/12/2017 PASSED
235 PS C OFFICERS DESK RM 367 TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/SIERRA
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
240 DD A AHU-H2-1 RETURN A TESTED 7/12/2017 PASSED
242 DD A AHU-H2-1 RETURN B TESTED 7/12/2017 PASSED
252 SD B TV ACTIVITY RM 138 TESTED 7/12/2017 PASSED
301 SD B INMATE PHONES RM 242 TESTED 7/12/2017 PASSED
302 SD D INMATE PHONE RM 442 TESTED 7/12/2017 PASSED
303 SD D ENTRY VESTIBULE RM 356 TESTED 7/12/2017 PASSED
304 SD B ENTRY VESTIBULE TESTED 7/12/2017 PASSED
305 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
306 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
307 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
308 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
309 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
310 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
311 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
312 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
313 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
314 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED
321 SD C ELEVATOR LOBBY RM 439 TESTED 7/12/2017 PASSED
328 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
329 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
330 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
331 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
332 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
333 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
338 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
339 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
340 SD C DAYROOM HI-BAY RM 340 TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/SIERRA
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
341 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED
342 SD B DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED
343 SD B CORRIDOR RM 151 NORTH TESTED 7/12/2017 PASSED
344 SD B CORRIDOR RM 151 SOUTH TESTED 7/12/2017 PASSED
345 SD A DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED
346 SD A VENDING PHONE RM 160 TESTED 7/12/2017 PASSED
347 SD A TV ACTIVITY RM 159 TESTED 7/12/2017 PASSED
348 SD A TV ACTIVITY RM 157 TESTED 7/12/2017 PASSED
349 SD A SECRETARY WAITING RM 151 TESTED 7/12/2017 PASSED
350 SD B REFUGE RM 153 TESTED 7/12/2017 PASSED
351 SD B TV ACTIVITY RM 140 TESTED 7/12/2017 PASSED
352 SD B TV ACTIVITY RM 138 TESTED 7/12/2017 PASSED
353 SD B VENDING PHONE RM 137 TESTED 7/12/2017 PASSED
354 SD D TV ACTIVITY RM 438 TESTED 7/12/2017 PASSED
355 SD D TV ACTIVITY RM 435 TESTED 7/12/2017 PASSED
356 SD D TV ACTIVITY RM 437 TESTED 7/12/2017 PASSED
357 SD C TV ACTIVITY RM 443 TESTED 7/12/2017 PASSED
358 SD C TV ACTIVITY RM 444 TESTED 7/12/2017 PASSED
359 SD C TV ACTIVITY RM 446 TESTED 7/12/2017 PASSED
360 SD D DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED
361 SD C CORRIDOR RM 351 SOUTH TESTED 7/12/2017 PASSED
362 SD C DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED
363 SD C TV ACTIVITY RM 357 TESTED 7/12/2017 PASSED
364 SD C VENDING PHONE RM 360 TESTED 7/12/2017 PASSED
365 SD C TV ACTIVITY RM 359 TESTED 7/12/2017 PASSED
366 SD C REFUGE RM 353 TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/SIERRA
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
367 SD D SECRETARY WAITING RM 351 TESTED 7/12/2017 PASSED
368 SD D VENDING PHONE RM 337 TESTED 7/12/2017 PASSED
369 SD D TV ACTIVITY RM 338 TESTED 7/12/2017 PASSED
370 SD D TV ACTIVITY RM 340 TESTED 7/12/2017 PASSED
375 SD C CORRIDOR RM 351 NORTH TESTED 7/12/2017 PASSED
403 PS D ENTRY RM 356 TESTED 7/12/2017 PASSED
404 PS B ENTRY VESTIBULE 156 TESTED 7/12/2017 PASSED
405 PS D OFFICERS DESK RM 366 TESTED 7/12/2017 PASSED
406 PS D DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
407 PS D DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
408 PS B DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
409 DD D AHU-H2 SUPPLY 3 TESTED 7/12/2017 PASSED
410 DD C AHU-H2-2 RETURN TESTED 7/12/2017 PASSED
411 DD C AHU-H2--2 SUPPLY 5 TESTED 7/12/2017 PASSED
412 DD D AHU-H2-2 SUPPLY 4 TESTED 7/12/2017 PASSED
413 DD D AHU-H2-2 SUPPLY 1 TESTED 7/12/2017 PASSED
414 DD D AHU-H2-2 SUPPLY 2 TESTED 7/12/2017 PASSED
419 DD C AHU-H2-3 SUPPLY 2 TESTED 7/12/2017 PASSED
420 DD C AHU-H2-3 SUPPLY 3 TESTED 7/12/2017 PASSED
421 DD C AHU-H2-3 RETURN TESTED 7/12/2017 PASSED
422 DD C AHU-H2-3 SUPPLY 5 TESTED 7/12/2017 PASSED
423 DD C AHU-H2-3 SUPPLY 4 TESTED 7/12/2017 PASSED
424 DD C AHU-H2-3 SUPPLY 1 TESTED 7/12/2017 PASSED
426 PS C NEAR STAIRWELL TESTED 7/12/2017 PASSED
427 PS A DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
428 PS C DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
429 PS A DAROOM TO CORE TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/SIERRA
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
431 PS B REFUGE RM 153 TESTED 7/12/2017 PASSED
432 WF A PLUMBING RM 149 4" TESTED 7/12/2017 PASSED
433 TS A PLUMBING RM 149 TESTED 7/12/2017 PASSED
434 PS A PLUMBING RM 149 TESTED 7/12/2017 PASSED
435 PS B DAYROOM TO CORE TESTED 7/12/2017 PASSED
436 PS D MECH RM 439 NORTH TESTED 7/12/2017 PASSED
437 PS C MECH RM 439 WEST TESTED 7/12/2017 PASSED
438 PS C MECH RM 439 SOUTH TESTED 7/12/2017 PASSED
439 PS C DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
441 PS C REFUGE RM 353 TESTED 7/12/2017 PASSED
443 PS D DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
445 PS B OFFICE DESK RM 166 TESTED 7/12/2017 PASSED
447 TS A PLUMBING RM 149 TESTED 7/12/2017 PASSED
ANN A TESTED 7/12/2017 PASSED
ANN B TESTED 7/12/2017 PASSED
ANN C TESTED 7/12/2017 PASSED
ANN D TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/RENO
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP 2 EST2 TESTED 7/12/2017 PASSED
101 SD A TV ACTIVITY RM 246 TESTED 7/12/2017 PASSED
102 SD A TV ACTIVITY RM 244 TESTED 7/12/2017 PASSED
103 SD A TV ACTIVITY RM 243 TESTED 7/12/2017 PASSED
104 SD B TV ACTIVITY RM 238 TESTED 7/12/2017 PASSED
105 SD B TV ACTIVITY RM 237 TESTED 7/12/2017 PASSED
106 SD B TV ACTIVITY RM 235 TESTED 7/12/2017 PASSED
107 SD A MECH RM 239 TESTED 7/12/2017 PASSED
108 SD A EQUIPMENT RM 240 TESTED 7/12/2017 PASSED
113 SD A INMATE PHONE RM 446 TESTED 7/12/2017 PASSED
114 SD C ENTRY VESTIBULE 365 TESTED 7/12/2017 PASSED
115 SD A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED
116 SD A INMATE PHONE RM 160 TESTED 7/12/2017 PASSED
117 SD A VENDING PHONE RM 160 TESTED 7/12/2017 PASSED
118 SD A TV ACTIVITY RM 159 TESTED 7/12/2017 PASSED
119 SD A TV ACTIVITY RM 157 TESTED 7/12/2017 PASSED
120 SD A DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
121 SD A SECRETARY WAITING RM151 TESTED 7/12/2017 PASSED
122 SD B REFUGE RM 153 TESTED 7/12/2017 PASSED
123 SD B CORRIDOR 151 NORTH TESTED 7/12/2017 PASSED
124 SD B CORRIDOR 151 SOUTH TESTED 7/12/2017 PASSED
125 SD B DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
126 SD B TV ACTIVITY RM 140 TESTED 7/12/2017 PASSED
127 SD B TV ACTIVITY RM TESTED 7/12/2017 PASSED
128 SD B VENDING PHONE RM 137 TESTED 7/12/2017 PASSED
129 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
130 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
131 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/RENO
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
132 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
133 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
134 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
135 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
136 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
137 SD A DAYROOM HI-BAY TESTED 7/12/2017 PASSED
138 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
139 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
140 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
141 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
142 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
143 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
144 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
145 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
146 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
147 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
148 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
149 SD A ELEVATOR MECH RM 241 TESTED 7/12/2017 PASSED
150 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
151 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED
152 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
153 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
154 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
155 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED
222 PS A OFFICERS DESK RM 157 TESTED 7/12/2017 PASSED
223 PS B OFFICERS DESK 156 TESTED 7/12/2017 PASSED
224 PS A MECH RM 239 SOUTH TESTED 7/12/2017 PASSED
225 PS A MECH RM 239 WEST TESTED 7/12/2017 PASSED
226 PS A MECH RM 239 NORTH TESTED 7/12/2017 PASSED
227 PS C NEAR STAIR 467 TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/RENO
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
228 PS A CORE 267 NEAR STAIR TESTED 7/12/2017 PASSED
229 PS C DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
231 PS A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED
232 PS C ENTRY VESTIBULE RM 235 TESTED 7/12/2017 PASSED
233 PS A DAYROOM CORE TO ENTRY TESTED 7/12/2017 PASSED
234 PS B REFUGE RM 153 TESTED 7/12/2017 PASSED
235 PS A MECH PLUMBING RM 149 TESTED 7/12/2017 PASSED
236 PS B DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
237 DD A AHU H1-1 SUPPLY 1 TESTED 7/12/2017 PASSED
238 DD A AHU H1-1 SUPPLY 2 TESTED 7/12/2017 PASSED
239 DD A AHU H1-1 SUPPLY 3 TESTED 7/12/2017 PASSED
240 DD A AHU H1-1 SUPPLY 4 TESTED 7/12/2017 PASSED
241 DD A AHU H1-1 SUPPLY 5 TESTED 7/12/2017 PASSED
242 DD A AHU H1-1 SUPPLY 6 TESTED 7/12/2017 PASSED
243 DD A AHU H1-1 SUPPLY 7 TESTED 7/12/2017 PASSED
244 DD A AHU H1-1 RETURN A TESTED 7/12/2017 PASSED
245 WF A MECH PLUMBING RM 149 4" TESTED 7/12/2017 PASSED
246 TS A PLUMBING MECH RM TESTED 7/12/2017 PASSED
248 TS A PLUMBING MECH RM 149 TESTED 7/12/2017 PASSED
258 DD A AHU H1-1 RETURN B TESTED 7/12/2017 PASSED
301 SD C TV ACTIVITY RM 446 TESTED 7/12/2017 PASSED
302 SD C TV ACTIVITY RM 404 TESTED 7/12/2017 PASSED
303 SD C TV ACTIVITY RM 443 TESTED 7/12/2017 PASSED
304 SD D TV ACTIVITY RM 438 TESTED 7/12/2017 PASSED
306 SD D TV ACTIVITY RM TESTED 7/12/2017 PASSED
305 SD D TV ACTIVITY RM 437 TESTED 7/12/2017 PASSED
307 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
308 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
309 SD C HSG-HI-4-2 TESTED 7/12/2017 PASSED
310 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
311 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
312 SD C DAYROOM HI BAY TESTED 7/20/2016 PASSED
313 SD C DAYROOM HI BAY TESTED 7/20/2016 PASSED
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
314 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
315 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
316 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED
317 SD C MECH RM 439 TESTED 7/12/2017 PASSED
318 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
319 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
320 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
321 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
322 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
323 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
324 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
325 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
326 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
327 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED
332 SD D CORRIDOR 351 NORTH TESTED 7/12/2017 PASSED
333 SD D DAYROOM TO CORE ENTRY D TESTED 7/12/2017 PASSED
334 SD C DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED
335 SD D CORRIDOR 351 SOUTH TESTED 7/12/2017 PASSED
336 SD C VENDING PHONE 360 TESTED 7/12/2017 PASSED
337 SD C TV ACTIVITY RM 359 TESTED 7/12/2017 PASSED
338 SD C TV ACTIVITY RM 357 TESTED 7/12/2017 PASSED
339 SD D SECRITARY ROOM CORRIDOR TESTED 7/12/2017 PASSED
340 SD D REFUGE RM 353 TESTED 7/12/2017 PASSED
341 SD D VENDING PHONE 341 TESTED 7/12/2017 PASSED
342 SD D TV ACTIVITY RM 338 TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/RENO
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
343 SD D TV ACTIVITY RM 340 TESTED 7/12/2017 PASSED
344 SD D INMATE PHONE RM 442 TESTED 7/12/2017 PASSED
345 SD D ENTRY VESTIBULE 356 TESTED 7/12/2017 PASSED
346 SD B INMATE PHONE RM 242 TESTED 7/12/2017 PASSED
347 SD B ENTRY VESTIBULE 156 TESTED 7/12/2017 PASSED
403 PS C OFFICERS DESK 367 TESTED 7/12/2017 PASSED
404 PS D OFFICERS DESK TESTED 7/12/2017 PASSED
405 PS C MECH RM 439 SOUTH TESTED 7/12/2017 PASSED
406 PS C MECH RM 439 WEST TESTED 7/12/2017 PASSED
407 PS C MECH RM 439 NORTH TESTED 7/12/2017 PASSED
408 PS D DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED
409 PS D CORRIDOR NEAR STAIRS TESTED 7/12/2017 PASSED
410 PS C CORE 266 NEAR STAIRS TESTED 7/12/2017 PASSED
412 PS C DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
413 PS D REFUGE RM 353 TESTED 7/12/2017 PASSED
414 PS D DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED
415 PS D ENTRY VESTIBULE 358 TESTED 7/12/2017 PASSED
416 PS D ENTRY VESTIBULE 358 TESTED 7/12/2017 PASSED
418 DD D AHU-HI-3 SUPPLY 4 SIDE A TESTED 7/12/2017 PASSED
420 DD D AHU-HI-3 SUPPLY 2 SIDE A TESTED 7/12/2017 PASSED
421 DD C SUPPLY 5 SIDE A TESTED 7/12/2017 PASSED
422 DD C RETURN SIDE A TESTED 7/12/2017 PASSED
423 DD C SUPPLY 1 SIDE B TESTED 7/12/2017 PASSED
424 DD C SUPPLY 5 SIDE A TESTED 7/12/2017 PASSED
425 DD C SUPPLY 3 SIDE B TESTED 7/12/2017 PASSED
426 DD C RETURN SIDE A TESTED 7/12/2017 PASSED
427 DD C SUPPLY 1 SIDE B TESTED 7/12/2017 PASSED
428 DD C SUPPLY 3 SIDE B TESTED 7/12/2017 PASSED
ANN A TESTED 7/12/2017 PASSED
ANN B TESTED 7/12/2017 PASSED
ANN C TESTED 7/12/2017 PASSED
ANN D TESTED 7/12/2017 PASSED
SITE: Herlong Federal Prison/RENO
SITE: Herlong Federal Prison/EM
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP 1 EST 2 TESTED 7/13/2017 PASSED
103 SD AI ELECTRONICS RM 142 TESTED 7/13/2017 PASSED
108 SD VT S & C ELECTRICAL ROOM TESTED 7/13/2017 PASSED
204 DD BT BT1 107 RETURN TESTED 7/13/2017 PASSED
213 DD BT AHU-A1-1 TESTED 7/13/2017 PASSED
216 DD EM MECHANICAL RM 110 RETURN TESTED 7/13/2017 PASSED
217 TS VT SPRINKLER VT 111 TESTED 7/13/2017 PASSED
218 PS VT VOCATIONAL TRAINING TESTED 7/13/2017 PASSED
219 PS VT VOCATIONAL TRAINING TESTED 7/13/2017 PASSED
220 PS VT SPRINKLER ROOM 111 TESTED 7/13/2017 PASSED
221 PS BT MECHANICAL RM 107 TESTED 7/13/2017 PASSED
222 PS VT VOCATIONAL SHOP VT 100 E TESTED 7/13/2017 PASSED
223 PS VT VOCATIONAL SHOP VT 100 W TESTED 7/13/2017 PASSED
224 TS AI SPRINKLER MECH RM 141 TESTED 7/13/2017 PASSED
225 PS EM ENTRY VESTIBULE EM 100 TESTED 7/13/2017 PASSED
226 PS EM ENTRY VESTIBULE EM 141 TESTED 7/13/2017 PASSED
228 PS EM MAIN CLASSROOM ENTRY VESTIBULE EM 123 TESTED 7/13/2017 PASSED
229 PS EM CLASSROOM EM LAW TESTED 7/13/2017 PASSED
230 PS EM CLASSROOM EM ELECT RM 120 TESTED 7/13/2017 PASSED
231 PS AI VISITING RM 128 WEST TESTED 7/13/2017 PASSED
232 PS AI VISITING AL MECH RM 141 TESTED 7/13/2017 PASSED
233 PS AI CORRIDOR 140 TESTED 7/13/2017 PASSED
234 PS AI VISITING CORRIDOR RM 119 TESTED 7/13/2017 PASSED
235 PS AI SECRETARY VISITING RM 118 TESTED 7/13/2017 PASSED
236 PS AI SALLY PORT MAIN VISITING RM 132 TESTED 7/13/2017 PASSED
237 TS EM2 SPRINKLER MECHANICAL 110 TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/EM
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
238 PS AI VISITING RM 128 TESTED 7/13/2017 PASSED
239 PS EM CLASSROOM LEARNING CENTER EM 118 TESTED 7/13/2017 PASSED
240 PS EM RELIGION/CLASS SPRINKLER 110 TESTED 7/13/2017 PASSED
241 PS EM RELIGION/CLASS TESTED 7/13/2017 PASSED
243 DD BT AHU BT 1 MECH RM 107 SUPPLY TESTED 7/13/2017 PASSED
244 DD AI MECH AI SUPPLY 141 TESTED 7/13/2017 PASSED
245 DD AL AHU AL 1 MECH ROOM SUPPLY TESTED 7/13/2017 PASSED
246 DD PS AHU-A1-1 SUPPLY TESTED 7/13/2017 PASSED
247 DD EM MECHANICAL RM 110 SUPPLY TESTED 7/13/2017 PASSED
248 WF VT VOC TRAINING BUILDING TESTED 7/13/2017 PASSED
249 TS VT 31 VT 111 TESTED 7/13/2017 PASSED
250 DD EM AHU-A1-1 SUPPLY 4 TESTED 7/13/2017 PASSED
252 WF AI SPRINKLER MECH RM 141 2.5" TESTED 7/13/2017 PASSED
253 TS AI SPRINKLER MECH RM 141 TESTED 7/13/2017 PASSED
256 WF EM RELIGION/CLASS SPRINKLER 110 4" TESTED 7/13/2017 PASSED
257 TS EM1 SPRINKLER MECHANICAL 110 TESTED 7/13/2017 PASSED
301 SD UF SECURITY ELECTRIC ROOM TESTED 7/13/2017 PASSED
302 SD UF ELEVATOR LOBBY UF 204 TESTED 7/13/2017 PASSED
303 SD UF ELEVATOR LOBBY 126 TESTED 7/13/2017 PASSED
408 WF UF SPRINKLER RM 115 6" TESTED 7/13/2017 PASSED
409 TS UF #1 SPRINKLER RM 115 TESTED 7/13/2017 PASSED
410 PS UF OPEN OFFICE UF 200 W TESTED 7/13/2017 PASSED
411 PS UF MECH RM UF 216 TESTED 7/13/2017 PASSED
412 PS UF OPEN OFFICE UF 200 E TESTED 7/13/2017 PASSED
413 PS UF SCREENING ENTRY UFT 100 TESTED 7/13/2017 PASSED
414 PS UF STAIRWELL TESTED 7/13/2017 PASSED
415 PS UF FACTORY AREA UF 101 WN TESTED 7/13/2017 PASSED
416 PS UF FACTORY AREA 101 W TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/EM
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
417 PS UF FATORY AREA UF 101 WS TESTED 7/13/2017 PASSED
418 PS UF FACTORY AREA UF 101 WS TESTED 7/13/2017 PASSED
419 PS UF MAIN FACTORY AREA UF 101 SE TESTED 7/13/2017 PASSED
420 PS PS FACTORY AREA UF 101E TESTED 7/13/2017 PASSED
422 PS UF UNICOR ELECTRIC ROOM TESTED 7/13/2017 PASSED
423 PS UF SPRINKLER RM UF 115 TESTED 7/13/2017 PASSED
424 DD UF MECH RM 113 RETURN TESTED 7/13/2017 PASSED
425 DD UF MECH RM 113 SUPPLY TESTED 7/13/2017 PASSED
426 DD UF MECH RM 216 SUPPLY TESTED 7/13/2017 PASSED
427 DD UF MECH RM 216 RETURN TESTED 7/13/2017 PASSED
428 DD UF MECH RM 216 RETURN TESTED 7/13/2017 PASSED
429 TS UF #2 SPRINKLER RM 115 TESTED 7/13/2017 PASSED
430 DD UF MECH RM 216 SUPPLY TESTED 7/13/2017 PASSED
434 PS UF PAINT BOOTH AREA TESTED 7/13/2017 PASSED
435 PS UF PAINT BOOTH AHU-UF-4-RET TESTED 7/13/2017 PASSED
436 PS UF PAINT BOOTH AHU-UF-4-SUP TESTED 7/13/2017 PASSED
ANN UF TESTED 7/13/2017 PASSED
ANN VT TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/SH
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP SH EST 2 TESTED 7/13/2017 PASSED
101 SD SH SALLY PORT SH 167 TESTED 7/13/2017 PASSED
102 SD SH LOBBY SH 162 TESTED 7/13/2017 PASSED
103 SD SH HEARING ROOM SH 171 TESTED 7/13/2017 PASSED
104 SD SH CORRIDOR SH 163 TESTED 7/13/2017 PASSED
106 SD SH MULTI-PURPOSE SH 156 TESTED 7/13/2017 PASSED
107 SD SH LOBBY SH 162 TESTED 7/13/2017 PASSED
108 SD SH CORRIDOR SH 158 W TESTED 7/13/2017 PASSED
109 SD SH CORRIDOR SH 158 MID TESTED 7/13/2017 PASSED
110 SD SH CORRIDOR SH 158 E TESTED 7/13/2017 PASSED
111 SD SH STAIRWELL SH 157 TESTED 7/13/2017 PASSED
112 SD SH MULTI-PURPOSE SH 256 TESTED 7/13/2017 PASSED
113 SD SH LOBBY SH 153 E TESTED 7/13/2017 PASSED
114 SD SH LOBBY SH 153 W TESTED 7/13/2017 PASSED
115 SD SH CORRIDOR 253 E TESTED 7/13/2017 PASSED
116 SD SH CORRIDOR SH 258 W TESTED 7/13/2017 PASSED
117 SD SH CORRIDOR SH 258 MID TESTED 7/13/2017 PASSED
118 SD SH CORRIDOR 258 E TESTED 7/13/2017 PASSED
119 SD SH STAIRWELL SH 257 TESTED 7/13/2017 PASSED
120 SD SH MULTI- PURPOSE SH 154 TESTED 7/13/2017 PASSED
121 SD SH LOBBY SH 153 NE TESTED 7/13/2017 PASSED
122 SD SH MULTI-PURPOSE SH 155 TESTED 7/13/2017 PASSED
123 SD SH CORRIDOR SH 191 SW TESTED 7/13/2017 PASSED
124 SD SH CORRIDOR SH 191 MID TESTED 7/13/2017 PASSED
125 SD SH CORRIDOR SH 191 E TESTED 7/13/2017 PASSED
126 SD SH STAIRWELL SH 190 TESTED 7/13/2017 PASSED
127 SD SH MULTI- PURPOSE SH 254 TESTED 7/13/2017 PASSED
128 SD SH CORRIDOR SH 253 NE TESTED 7/13/2017 PASSED
129 SD SH MULTI-PURPOSE SH 255 TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/SH
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
130 SD SH CORRIDOR SH 253 NE TESTED 7/13/2017 PASSED
131 SD SH CORRIDOR SH 291 MID TESTED 7/13/2017 PASSED
132 SD SH CORRIDOR SH 291 NE TESTED 7/13/2017 PASSED
133 SD SH STAIRWELL SH 290 TESTED 7/13/2017 PASSED
134 SD SH LOBBY SH 153 N TESTED 7/13/2017 PASSED
135 SD SH CORRIDOR SH 150 S TESTED 7/13/2017 PASSED
136 SD SH CORRIDOR SH 150 MID TESTED 7/13/2017 PASSED
137 SD SH CORRIDOR SH 150 N TESTED 7/13/2017 PASSED
138 SD SH STAIRWELL SH 149 TESTED 7/13/2017 PASSED
139 SD SH CORRIDOR SH 253 W TESTED 7/13/2017 PASSED
140 SD SH CORRIDOR SH 250 S TESTED 7/13/2017 PASSED
141 SD SH CORRIDOR SH 250 MID TESTED 7/13/2017 PASSED
142 SD SH CORRIDOR SH 250 N TESTED 7/13/2017 PASSED
143 SD SH STAIRWELL SH 249 TESTED 7/13/2017 PASSED
151 SD SH CORRIDOR SH 291 MID TESTED 7/13/2017 PASSED
213 PS SH SALLYPORT SH 167 TESTED 7/13/2017 PASSED
214 PS SH OFFICERS STATION TESTED 7/13/2017 PASSED
215 PS SH LOBBY SH 158 TESTED 7/13/2017 PASSED
216 PS SH STAIRWELL SH 157 TESTED 7/13/2017 PASSED
217 PS SH MECH RM SHU 293 TESTED 7/13/2017 PASSED
218 PS SH CORRIDOR SH 253 E TESTED 7/13/2017 PASSED
219 PS SH CORRIDOR 258 E TESTED 7/13/2017 PASSED
220 PS SH CORRIDOR 191 SW TESTED 7/13/2017 PASSED
221 PS SH STAIRWELL SH 190 TESTED 7/13/2017 PASSED
222 PS SH CORRIDOR SH 291 SW TESTED 7/13/2017 PASSED
223 PS SH CORRIDOR SH 291 NE TESTED 7/13/2017 PASSED
224 PS SH CORRIDOR SH 150 S TESTED 7/13/2017 PASSED
225 PS SH STAIRWELL SH 190 TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/SH
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
226 PS SH CORRIDOR 250 S TESTED 7/13/2017 PASSED
227 PS SH CORRIDOR SH 250 N TESTED 7/13/2017 PASSED
228 DD SH AHU SHU-1 SUPPLY 1 TESTED 7/13/2017 PASSED
229 DD SH AHU SHU-1 SUPPLY 2 TESTED 7/13/2017 PASSED
230 DD SH AHU SHU-1 SUPPLY 3 TESTED 7/13/2017 PASSED
231 DD SH AHU SHU-1 SUPPLY 4 TESTED 7/13/2017 PASSED
232 DD SH AHU SHU-1 SUPPLY 5 TESTED 7/13/2017 PASSED
233 DD SH AHU SHU-1 SUPPLY 6 TESTED 7/13/2017 PASSED
234 DD SH AHU SHU-1 RETURN TESTED 7/13/2017 PASSED
235 WF SH MECH RM SPECIAL HOUSING 293 4" TESTED 7/13/2017 PASSED
236 TS SH RECREATION SVCS TESTED 7/13/2017 PASSED
237 WF SH MECH RM SPECIAL HOUSING 293 4" TESTED 7/13/2017 PASSED
238 TS SH MECHANICAL RM 293 RECREATIONAL SVCS TESTED 7/13/2017 PASSED
239 TS SH SH 293 ISO VALVE TESTED 7/13/2017 PASSED
247 PS RS GYM NE TESTED 7/13/2017 PASSED
301 SD HS SECURITY HS 186 TESTED 7/13/2017 PASSED
303 SD RS SEC. ELECTRONIC RE 115 TESTED 7/13/2017 PASSED
404 PS HS SPRINKLER RM 113 TESTED 7/13/2017 PASSED
405 PS RC REC SVCS STAFF ASSEMBLY AI 101 TESTED 7/13/2017 PASSED
406 PS HS CORRIDOR HS 115 TESTED 7/13/2017 PASSED
407 PS HS CORRIDOR HS 142 TESTED 7/13/2017 PASSED
408 PS HS MECH ROOM HS 143 TESTED 7/13/2017 PASSED
409 PS HS ENTRY HS 173 TESTED 7/13/2017 PASSED
410 PS HS MAIL ROOM HS 187 TESTED 7/13/2017 PASSED
411 PS HS HEALTH SVCS HS 189 TESTED 7/13/2017 PASSED
412 PS HS VESTIBULE HS 100 TESTED 7/13/2017 PASSED
413 PS HS WAITING RM HS 101 TESTED 7/13/2017 PASSED
414 DD HS AHU HS 1 SUPPLY TESTED 7/13/2017 PASSED
415 WF HS SPRINKLER RM HS 113 TESTED 7/13/2017 PASSED
416 TS HS TAMPER 2 SPRINKLER RM 113 TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/SH
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
418 PS AI VISITING VESTIBULE AI 100 TESTED 7/13/2017 PASSED
419 PS AI VISITING CLERK WAITING AI 108 TESTED 7/13/2017 PASSED
425 PS RS MECH RM RE 114 TESTED 7/13/2017 PASSED
426 PS RS ELECTRICAL ROOM 116 TESTED 7/13/2017 PASSED
427 PS RS OPEN ACTIVITY RE 100 S TESTED 7/13/2017 PASSED
428 PS RS OPEN ACTIVITY RE 100 M TESTED 7/13/2017 PASSED
429 PS RS TESTED 7/13/2017 PASSED
430 PS RS INMATE TOILET 118 TESTED 7/13/2017 PASSED
431 DD RS AHU RE-1 SUPPLY TESTED 7/13/2017 PASSED
433 DD HS AHU 1 HS RETURN TESTED 7/13/2017 PASSED
434 DD RS AHU-RE-1 RETURN TESTED 7/13/2017 PASSED
435 TS HS AI-1 SPRINKLER HS 113 TESTED 7/13/2017 PASSED
ANN R&D TESTED 7/13/2017 PASSED
ANN HS TESTED 7/13/2017 PASSED
ANN SH TESTED 7/13/2017 PASSED
ANN RC TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/AO
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DIAL Dialer HD Heat Detector
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP AO EST 2 TESTED 7/13/2017 PASSED
101 SD AO CONTROL CENTER AO 104 TESTED 7/13/2017 PASSED
102 SD AO CONTROL CENTER AO 104 TESTED 7/13/2017 PASSED
103 SD AO ELECTRONICS SHOP AO 146 TESTED 7/13/2017 PASSED
104 SD AO ELECTRONICS EQUIP 145 TESTED 7/13/2017 PASSED
204 DD AO MECH RM AO 147 RETURN TESTED 7/13/2017 PASSED
205 TS AO TAMPER 2 AO 104 TESTED 7/13/2017 PASSED
206 WF AO WATERFLOW CONTROL RM SALLY PORTTESTED 7/13/2017 PASSED
209 PS AO ADMIN. ELECTRICAL ROOM TESTED 7/13/2017 PASSED
210 PS AO ADMIN CONTROL AO 104 TESTED 7/13/2017 PASSED
211 PS AO WAITING RM AO 102 TESTED 7/13/2017 PASSED
212 PS AO AO CORRIDOR AO 166 TESTED 7/13/2017 PASSED
213 PS AO RECEPTION WAITING AO 101 TESTED 7/13/2017 PASSED
214 PS AO RECEPTION WAITING AO 101 TESTED 7/13/2017 PASSED
215 PS AO CORRIDOR AO 130 TESTED 7/13/2017 PASSED
216 PS AO MECH RM AO 147 TESTED 7/13/2017 PASSED
217 PS AO ADMIN. ELECTRICAL ROOM TESTED 7/13/2017 PASSED
218 DD AO MECH RM AO 147 SUPPLY 1 TESTED 7/13/2017 PASSED
219 WF AO MECH AO 147 4" TESTED 7/13/2017 PASSED
220 TS AO MECH RM 147 TESTED 7/13/2017 PASSED
222 TS AO SALLY PORT TESTED 7/13/2017 PASSED
223 DD AO MECH RM AO 147 SUPPLY 2 TESTED 7/13/2017 PASSED
227 DD AO AHU-AO1 TESTED 7/13/2017 PASSED
228 DD AO AHU-MECH RM TESTED 7/13/2017 PASSED
229 DD AO AHU-MECH RM TESTED 7/13/2017 PASSED
ANN AO TESTED 7/13/2017 PASSED
SITE: Herlong Federal Prison/CAMPHOUSE
SD Smoke Detector DD Duct Dector AUD Audible
AS Air Sampling WF Waterflow DH Door Holder
AV Audible/Visual FP Fire Phone FAN Fan Control Panel
PTR Printer VDT Display Terminal VIS Visual
PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel
PS Pull Station BD Beam Detector NCC NCC
TS Tamper Switch FSD Fire Smoke Damper
SPKR Voice Evac Speaker FJ Fire Jack
ANN Annuciator EVAC Voice Evac Panel
DEV SERVICE TEST
ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED
FACP 1 EST 2 TESTED 7/13/2017 PASSED
101 SD CH SMOKE ELECTRICAL ROOM TESTED 7/13/2017 PASSED
102 SD CH TV ACTIVITY CH 113 TESTED 7/13/2017 PASSED
103 SD CH TV ACTIVITY CH 112 TESTED 7/13/2017 PASSED
104 SD CH TV ACTIVITY CH 111 TESTED 7/13/2017 PASSED
105 SD CH VESTIBULE CH 100…