FCI_Herlong_Alarm_Reports_7.13.17.pdf

PDF 729 KB Posted

Attached to
Fire Detection/Alarm Systems Services Federal contract opportunity
Solicitation number
15B61918Q00000002
Issued by
Department of Justice Bureau of Prisons Federal Correctional Institution Herlong

About this file

Fire Alarm

View the file

Other files for this federal contract opportunity

Other files attached to Fire Detection/Alarm Systems Services, newest first.
File Type Posted
Semi-Annul_Inspection_Report.pdf PDF
FCI_Herlong_Sprinkler_Reports_7.13.17.pdf PDF
BP_A0660_NCIC_Check.pdf PDF
Attachments_-_Business_Management_Questionnaire_1.pdf PDF
15B61918Q00000002.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM INSPECTION

REPORT

SITE: Herlong Federal Prison/Tahoe

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

101 SD A VENDING PHONE RM 160 TESTED 7/11/2017 PASSED

102 SD A TV ACTIVITY RM 159 TESTED 7/11/2017 PASSED

103 SD A TELEVISION ACTIVITY RM 157 TESTED 7/11/2017 PASSED

104 SD A DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED

105 SD A TV ACTIVITY RM 243 TESTED 7/11/2017 PASSED

106 SD A TV ACTIVITY RM 244 TESTED 7/11/2017 PASSED

107 SD A TV ACTIVITY RM 246 TESTED 7/11/2017 PASSED

108 SD A ENTRY VESTIBULE RM 165 TESTED 7/11/2017 PASSED

109 SD A INMATE PHONE RM 249 TESTED 7/11/2017 PASSED

112 SD A DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

113 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

114 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

115 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

116 SD A DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

117 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

118 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

119 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

120 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

121 SD A DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

122 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

123 SD A DAYROOM HI-BAY TESTED 7/11/2017 PASSED

124 SD B VENDING PH RM 137 TESTED 7/11/2017 PASSED

125 SD B TV ACTIVITY RM 138 TESTED 7/11/2017 PASSED

126 SD B TV ACTIVITY RM 140 TESTED 7/11/2017 PASSED

127 SD B DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED

128 SD B TV ACTIVITY RM 235 TESTED 7/11/2017 PASSED

129 SD B TV ACTIVITY RM 237 TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/Tahoe

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

130 SD B TV ACTIVITY RM 238 TESTED 7/11/2017 PASSED

131 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

132 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

133 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

134 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

135 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

136 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

137 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

138 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

139 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

140 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

141 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

142 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

143 SD B DAYROOM HI-BAY TESTED 7/11/2017 PASSED

144 SD A REFUGE RM 153 TESTED 7/11/2017 PASSED

145 SD A SECRETARY RM 151 TESTED 7/11/2017 PASSED

146 SD A CORE CORRIDOR TESTED 7/11/2017 PASSED

147 SD A CORE CORRIDOR TESTED 7/11/2017 PASSED

149 SD B MECH RM 239 TESTED 7/11/2017 PASSED

150 SD B SECURITY ELECTRONICS RM 240 TESTED 7/11/2017 PASSED

153 DD MECH AHU-H-3-1 SUPPLY 2 TESTED 7/11/2017 PASSED

154 DD MECH AHU H-3-1 SUPPLY 3 TESTED 7/11/2017 PASSED

155 DD MECH AHU H-3-1 SUPPLY 4 TESTED 7/11/2017 PASSED

156 DD MECH AHU H-3-1 SUPPLY 5 TESTED 7/11/2017 PASSED

157 DD MECH AHU H-3-1 SUPPLY 6 TESTED 7/11/2017 PASSED

158 DD MECH AHU H-3-1 SUPPLY 7 TESTED 7/11/2017 PASSED

159 SD C ENTRY VESTIBULE RM 365 TESTED 7/11/2017 PASSED

160 SD C INMATE PHONE RM 449 TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/Tahoe

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

163 DD MECH AHU H-3-1 RETURN A TESTED 7/11/2017 PASSED

164 DD MECH AHU H-3-1 RETURN B TESTED 7/11/2017 PASSED

222 PS A OFFICERS DESK H 167 TESTED 7/11/2017 PASSED

223 PS A DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED

224 PS A ENTRY VESTIBULE RM 165 TESTED 7/11/2017 PASSED

226 PS B OFFICERS DEK RM 166 TESTED 7/11/2017 PASSED

227 PS B DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED

228 PS D1 PLUMBING RM 149 TESTED 7/11/2017 PASSED

229 PS A REFUGE RM 153 TESTED 7/11/2017 PASSED

230 PS A MECH RM 239 EAST TESTED 7/11/2017 PASSED

231 PS A MECH RM 239 NORHT TESTED 7/11/2017 PASSED

232 PS A MECH RM 239 TESTED 7/11/2017 PASSED

233 DD A SUPPLY 1 TESTED 7/11/2017 PASSED

234 DD A SUPPLY 2 TESTED 7/11/2017 PASSED

235 DD A SUPPLY 3 TESTED 7/11/2017 PASSED

236 DD A SUPPLY 4 TESTED 7/11/2017 PASSED

237 DD A AHU-H31 SUPPLY 5 TESTED 7/11/2017 PASSED

238 DD A AHU-H31 SUPPLY 6 TESTED 7/11/2017 PASSED

239 DD A AHU-H31 SUPPLY 7 TESTED 7/11/2017 PASSED

240 WF 1 PLUMBING RM 148 TESTED 7/11/2017 PASSED

241 TS 1 PLUMBING RM 149 TESTED 7/11/2017 PASSED

249 PS 1 ENTRY VESTIBULE TESTED 7/11/2017 PASSED

250 DD 1 RETURN A TESTED 7/11/2017 PASSED

251 TS 1 PLUMBING RM 149 TESTED 7/11/2017 PASSED

256 DD 1 RETURN B TESTED 7/11/2017 PASSED

301 SD B ENTRY VESTIBULE TESTED 7/11/2017 PASSED

302 SD B INMATE PHONE RM 242 TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/Tahoe

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

305 SD C VENDING PH RM 360 TESTED 7/11/2017 PASSED

306 SD C TV ACTIVITY RM 359 TESTED 7/11/2017 PASSED

307 SD C TV ACTIVITY RM 357 TESTED 7/11/2017 PASSED

308 SD C DAYROOM CORE RM TESTED 7/11/2017 PASSED

309 SD C TV ACTIVITY RM 446 TESTED 7/11/2017 PASSED

310 SD C TV ACTIVITY RM 444 TESTED 7/11/2017 PASSED

311 SD C TV ACTIVITY RM 443 TESTED 7/11/2017 PASSED

312 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

313 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

314 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

315 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

316 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

317 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

318 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

319 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

320 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

321 SD C DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

322 SD D VENDING PHONE RM 337 TESTED 7/11/2017 PASSED

323 SD D TV ACTIVITY RM 338 TESTED 7/11/2017 PASSED

324 SD D TV ACTIVITY RM 340 TESTED 7/11/2017 PASSED

325 SD D DAY ROOM TO CORE ENTRY TESTED 7/11/2017 PASSED

326 SD D TV ACTIVITY RM 438 TESTED 7/11/2017 PASSED

327 SD D TV ACTIVITY RM 437 TESTED 7/11/2017 PASSED

328 SD D TV ACTIVITY RM 435 TESTED 7/11/2017 PASSED

329 SD D ENTRY VESTIBULE RM 356 TESTED 7/11/2017 PASSED

330 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

333 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

334 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/Tahoe

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

335 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

336 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

337 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

338 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

339 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

340 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

341 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

342 SD D DAY ROOM HI-BAY TESTED 7/11/2017 PASSED

343 SD D CORE CORRIDOR TESTED 7/11/2017 PASSED

344 SD D REFUGE RM 353 TESTED 7/11/2017 PASSED

345 SD D SECRETARY RM 351 TESTED 7/11/2017 PASSED

346 SD D CORE CORRIDOR TESTED 7/11/2017 PASSED

347 SD D CORRIDOR NEAR STAIRS RM 268 TESTED 7/11/2017 PASSED

403 PS A CORRIDOR NEAR STAIRS RM 267 TESTED 7/11/2017 PASSED

404 PS B ENTRY VESTIBULE RM 156 TESTED 7/11/2017 PASSED

406 PS B CORRIDOR NEAR STAIRS RM 266 TESTED 7/11/2017 PASSED

407 PS C OFFICERS DESK RM 367 TESTED 7/11/2017 PASSED

408 PS C Day Room TESTED 7/11/2017 PASSED

409 PS C DAYROOM NEAR STAIRWELL TESTED 7/11/2017 PASSED

410 PS C CORRIDOR NEAR STAIR RM 467 TESTED 7/11/2017 PASSED

411 PS D OFFICERS DESK RM 368 TESTED 7/11/2017 PASSED

412 PS D DAYROOM TO CORE ENTRY TESTED 7/11/2017 PASSED

413 PS D ENTRY VESTIBULE RM 356 TESTED 7/11/2017 PASSED

414 PS D DAYROOM NEAR STAIRWELL TESTED 7/11/2017 PASSED

415 PS D CORRIDOR NEAR STAIR RM 468 TESTED 7/11/2017 PASSED

416 PS D REFUGE RM 353 TESTED 7/11/2017 PASSED

417 PS C MECH RM 439 EAST TESTED 7/11/2017 PASSED

418 PS C MECH RM 439 NORTH TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/Tahoe

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

419 PS C MECH RM 439 WEST TESTED 7/11/2017 PASSED

420 DD MECH AHU H3-2 SUPPLY 1 TESTED 7/11/2017 PASSED

421 DD MECH TESTED 7/11/2017 PASSED

422 DD MECH AHU H3-2 SUPPLY 3 TESTED 7/11/2017 PASSED

423 DD MECH AHU H3-2 SUPPLY 4 TESTED 7/11/2017 PASSED

424 DD MECH AHU H3-2 SUPPLY 5 TESTED 7/11/2017 PASSED

425 DD MECH AHU H3-2 RETURN SIDE B TESTED 7/11/2017 PASSED

426 DD MECH AHU H3-3 SUPPLY 1 TESTED 7/11/2017 PASSED

427 DD MECH AHU H3-3 SUPPLY 2 TESTED 7/11/2017 PASSED

428 DD MECH AHU H3-3 SUPPLY 3 TESTED 7/11/2017 PASSED

429 DD MECH AHU H3-3 SUPPLY 4 TESTED 7/11/2017 PASSED

430 DD MECH AHU H3-3 SUPPLY 5 TESTED 7/11/2017 PASSED

431 DD MECH AHU H3-3 RETURN SIDE A TESTED 7/11/2017 PASSED

ANN A A ENTRANCE TESTED 7/11/2017 PASSED

ANN B B ENTRANCE TESTED 7/11/2017 PASSED

ANN C C ENTRANCE TESTED 7/11/2017 PASSED

ANN D D ENTRANCE TESTED 7/11/2017 PASSED

AHU H3-2 SUPPLY 2

SITE: Herlong Federal Prison/FOOD SERVICE

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer DT Duct Test Switch VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP 1 EST 2 TESTED 7/11/2017 PASSED

101 SD 1 FACP ROOM TESTED 7/11/2017 PASSED

107 SD 1 SECURITY ELEC TESTED 7/11/2017 PASSED

114 PS 1 VESTABULE TESTED 7/11/2017 PASSED

216 PS 1 FS ELECTRICAL ROOM TESTED 7/11/2017 PASSED

217 PS 1 RECEIVING RM 1 RM 144 TESTED 7/11/2017 PASSED

218 PS 1 CAN WASH RM 116 TESTED 7/11/2017 PASSED

219 PS 1 STAFF DINING RM 110 TESTED 7/11/2017 PASSED

220 PS 1 DINING RM 133 NE TESTED 7/11/2017 PASSED

221 PS 1 DINING RM 133 NW TESTED 7/11/2017 PASSED

222 PS 1 MECH ROOM 142 TESTED 7/11/2017 PASSED

223 DD 1 AHU-FC-FS-1 SUPPLY TESTED 7/11/2017 PASSED

224 DD 1 AHU-FS-2 SUPPLY TESTED 7/11/2017 PASSED

225 DD 1 AHU-FS-1 SUPPLY TESTED 7/11/2017 PASSED

226 DD 1 MAU-FS-1 SUPPLY RM 1 TESTED 7/11/2017 PASSED

227 DD 1 MAU-FS-2 SUPPLY RM 101 TESTED 7/11/2017 PASSED

228 DD 1 KIT HOOD SUPPLY BAKERY TESTED 7/11/2017 PASSED

230 DD 1 T5100 NORTH KIT 1800 SUPPLY TESTED 7/11/2017 PASSED

232 KIT HOOD STAFF LOUNGE TESTED 7/11/2017 PASSED

233 WF 1 MECH ROOM 4" TESTED 7/11/2017 PASSED

234 TS FS MECH ROOM TESTED 7/11/2017 PASSED

235 TS FS ISO VALVE TESTED 7/11/2017 PASSED

241 PS FS/PS SECURITY ELEC TESTED 7/11/2017 PASSED

242 PS FS/PS ELECTRICAL ROOM TESTED 7/11/2017 PASSED

243 PS FS/PS MECH RM PS 136 N TESTED 7/11/2017 PASSED

244 PS FS/PS LOBBY PS 133 W TESTED 7/11/2017 PASSED

245 PS FS/PS LOBBY PS 133 E TESTED 7/11/2017 PASSED

246 PS FS/PS WORKROOM CLERK TESTED 7/11/2017 PASSED

247 PS PULL INSIDE WHSE PS117N TESTED 7/11/2017 PASSED

248 PS PULL BARBER TESTED 7/11/2017 PASSED

249 PS PS VESTIBLE TESTED 7/11/2017 PASSED

250 PS FS/PS SALES LOBBY PS 113 E TESTED 7/11/2017 PASSED

251 PS FS/PS SALES LOBBY PS 113 E TESTED 7/11/2017 PASSED

252 PS FS/PS COMM STORAGE PS 102 TESTED 7/11/2017 PASSED

253 PS FS/PS INSIDE WHSE PS 117 S TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/FOOD SERVICE

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

254 PS FS/PS LAUNDRY PS 129 TESTED 7/11/2017 PASSED

255 PS FS/PS MECH RM PS 136 TESTED 7/11/2017 PASSED

256 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED

257 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED

258 WF FS/PS MECH RM PS 136 4' 195/105/115 TESTED 7/11/2017 PASSED

259 TS FS/PS DRY SYSTEM LOADING DOCK TESTED 7/11/2017 PASSED

260 TS FS/PS ISO VALVE RM PS 136 TESTED 7/11/2017 PASSED

270 WF FS/PS ISO VALVE RM PS 136 TESTED 7/11/2017 PASSED

271 DRY FS/PS DRY SYSTEM TO AIR DOCK MECH RM 126 TESTED 7/11/2017 PASSED

274 TS FS/PS ISO VALVE RM PS 136 TESTED 7/11/2017 PASSED

275 DD 1 AHU-FS-1 RETURN TESTED 7/11/2017 PASSED

276 DD 1 AHU-FS-2 RETURN TESTED 7/11/2017 PASSED

277 DD 1 AHU-FC-1 RETURN TESTED 7/11/2017 PASSED

278 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED

279 DT FS/PS MECH ROOM TESTED 7/11/2017 PASSED

292 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED

293 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED

294 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED

295 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED

296 DD 1 FOODSERVICE TESTED 7/11/2017 PASSED

403 PS MS MECHANICAL ROOM MS 112 TESTED 7/11/2017 PASSED

404 PS MS ELECTRICAL ROOM TESTED 7/11/2017 PASSED

405 PS MS OPEN SHOP FAB 118 TESTED 7/11/2017 PASSED

406 PS MS CARPENTER SHOP 119 TESTED 7/11/2017 PASSED

407 PS MS STORAGE RM 120 TESTED 7/11/2017 PASSED

408 PS MS CORRIDOR MS 100 TESTED 7/11/2017 PASSED

409 DD MS AHU MS-1 SUPPLY MS 112 TESTED 7/11/2017 PASSED

410 TS MS TAMPER 2 SPRINKLER RM 123 TESTED 7/11/2017 PASSED

415 PS SG SECURITY ELECTRONICS SG 104 TESTED 7/11/2017 PASSED

416 PS SG OFFICERS DESK SG 100 TESTED 7/11/2017 PASSED

417 WF SG BLDG SG 102 2" TESTED 7/11/2017 PASSED

418 TS MS STORAGE SG 102 TESTED 7/11/2017 PASSED

419 DD MS AHU MS-1 RETURN 112 TESTED 7/11/2017 PASSED

420 WF MS SPRINKLER RM MS 123 4" TESTED 7/11/2017 PASSED

421 TS MS SPRINKLER RM 123 TESTED 7/11/2017 PASSED

422 TS SG STORAGE SG 102 TESTED 7/11/2017 PASSED

ANN FS/PS TESTED 7/11/2017 PASSED

SITE: Herlong Federal Prison/SIERRA

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP 2 EST2 TESTED 7/12/2017 PASSED

101 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

102 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

103 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

104 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

105 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

106 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

107 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

108 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

109 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

110 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

111 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

112 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

113 SD B DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

122 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

123 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

124 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

125 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

126 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

127 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

128 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

129 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

130 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

131 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

132 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

133 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

134 SD A DAYROOM HIGH BAY TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/SIERRA

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

135 SD A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED

136 SD A INMATE PHONES RM 249 TESTED 7/12/2017 PASSED

137 SD C INMATE PHONE RM 442 TESTED 7/12/2017 PASSED

138 SD C ENTRY VETIBULE RM 365 TESTED 7/12/2017 PASSED

139 SD A ELEVATOR MECH SUPPLY 2 TESTED 7/12/2017 PASSED

140 SD A TV ACTIVITY RM TESTED 7/12/2017 PASSED

141 SD A TV ACTIVITY RM 244 TESTED 7/12/2017 PASSED

142 SD A TV ACTIVITY RM 246 TESTED 7/12/2017 PASSED

143 SD A TV ACTIVITY RM 235 TESTED 7/12/2017 PASSED

144 SD B TV ACTIVITY RM 237 TESTED 7/12/2017 PASSED

145 SD B TV ACTIVITY RM 238 TESTED 7/12/2017 PASSED

146 SD A MECH RM 239 TESTED 7/12/2017 PASSED

147 SD A ELECTRONICS RM 240 TESTED 7/12/2017 PASSED

212 PS A MECH RM 239 SOUTH TESTED 7/12/2017 PASSED

213 PS A MECH RM 239 WEST TESTED 7/12/2017 PASSED

214 PS A MECH RM 239 NORTH TESTED 7/12/2017 PASSED

224 DD A AHU-H2-1 SUPPLY 1 TESTED 7/12/2017 PASSED

226 DD A AHU-H2-1 SUPPLY 2 TESTED 7/12/2017 PASSED

227 DD A AHU-H2-1 SUPPLY 4 TESTED 7/12/2017 PASSED

228 DD A AHU-H2-1 SUPPLY 5 TESTED 7/12/2017 PASSED

229 DD A AHU-H2-1 SUPPLY 6 TESTED 7/12/2017 PASSED

230 DD A AHU-H2-1 SUPPLY 7 TESTED 7/12/2017 PASSED

231 DD A AHU-H2-1 SUPPLY 8 TESTED 7/12/2017 PASSED

232 PS C ENTRY VESTIBULE RM 365 TESTED 7/12/2017 PASSED

233 PS A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED

234 PS A OFFICERS DESK RM 167 TESTED 7/12/2017 PASSED

235 PS C OFFICERS DESK RM 367 TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/SIERRA

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

240 DD A AHU-H2-1 RETURN A TESTED 7/12/2017 PASSED

242 DD A AHU-H2-1 RETURN B TESTED 7/12/2017 PASSED

252 SD B TV ACTIVITY RM 138 TESTED 7/12/2017 PASSED

301 SD B INMATE PHONES RM 242 TESTED 7/12/2017 PASSED

302 SD D INMATE PHONE RM 442 TESTED 7/12/2017 PASSED

303 SD D ENTRY VESTIBULE RM 356 TESTED 7/12/2017 PASSED

304 SD B ENTRY VESTIBULE TESTED 7/12/2017 PASSED

305 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

306 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

307 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

308 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

309 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

310 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

311 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

312 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

313 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

314 SD D DAYROOM HI-BAY TESTED 7/12/2017 PASSED

321 SD C ELEVATOR LOBBY RM 439 TESTED 7/12/2017 PASSED

328 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

329 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

330 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

331 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

332 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

333 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

338 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

339 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

340 SD C DAYROOM HI-BAY RM 340 TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/SIERRA

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

341 SD C DAYROOM HI-BAY TESTED 7/12/2017 PASSED

342 SD B DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED

343 SD B CORRIDOR RM 151 NORTH TESTED 7/12/2017 PASSED

344 SD B CORRIDOR RM 151 SOUTH TESTED 7/12/2017 PASSED

345 SD A DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED

346 SD A VENDING PHONE RM 160 TESTED 7/12/2017 PASSED

347 SD A TV ACTIVITY RM 159 TESTED 7/12/2017 PASSED

348 SD A TV ACTIVITY RM 157 TESTED 7/12/2017 PASSED

349 SD A SECRETARY WAITING RM 151 TESTED 7/12/2017 PASSED

350 SD B REFUGE RM 153 TESTED 7/12/2017 PASSED

351 SD B TV ACTIVITY RM 140 TESTED 7/12/2017 PASSED

352 SD B TV ACTIVITY RM 138 TESTED 7/12/2017 PASSED

353 SD B VENDING PHONE RM 137 TESTED 7/12/2017 PASSED

354 SD D TV ACTIVITY RM 438 TESTED 7/12/2017 PASSED

355 SD D TV ACTIVITY RM 435 TESTED 7/12/2017 PASSED

356 SD D TV ACTIVITY RM 437 TESTED 7/12/2017 PASSED

357 SD C TV ACTIVITY RM 443 TESTED 7/12/2017 PASSED

358 SD C TV ACTIVITY RM 444 TESTED 7/12/2017 PASSED

359 SD C TV ACTIVITY RM 446 TESTED 7/12/2017 PASSED

360 SD D DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED

361 SD C CORRIDOR RM 351 SOUTH TESTED 7/12/2017 PASSED

362 SD C DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED

363 SD C TV ACTIVITY RM 357 TESTED 7/12/2017 PASSED

364 SD C VENDING PHONE RM 360 TESTED 7/12/2017 PASSED

365 SD C TV ACTIVITY RM 359 TESTED 7/12/2017 PASSED

366 SD C REFUGE RM 353 TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/SIERRA

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

367 SD D SECRETARY WAITING RM 351 TESTED 7/12/2017 PASSED

368 SD D VENDING PHONE RM 337 TESTED 7/12/2017 PASSED

369 SD D TV ACTIVITY RM 338 TESTED 7/12/2017 PASSED

370 SD D TV ACTIVITY RM 340 TESTED 7/12/2017 PASSED

375 SD C CORRIDOR RM 351 NORTH TESTED 7/12/2017 PASSED

403 PS D ENTRY RM 356 TESTED 7/12/2017 PASSED

404 PS B ENTRY VESTIBULE 156 TESTED 7/12/2017 PASSED

405 PS D OFFICERS DESK RM 366 TESTED 7/12/2017 PASSED

406 PS D DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

407 PS D DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

408 PS B DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

409 DD D AHU-H2 SUPPLY 3 TESTED 7/12/2017 PASSED

410 DD C AHU-H2-2 RETURN TESTED 7/12/2017 PASSED

411 DD C AHU-H2--2 SUPPLY 5 TESTED 7/12/2017 PASSED

412 DD D AHU-H2-2 SUPPLY 4 TESTED 7/12/2017 PASSED

413 DD D AHU-H2-2 SUPPLY 1 TESTED 7/12/2017 PASSED

414 DD D AHU-H2-2 SUPPLY 2 TESTED 7/12/2017 PASSED

419 DD C AHU-H2-3 SUPPLY 2 TESTED 7/12/2017 PASSED

420 DD C AHU-H2-3 SUPPLY 3 TESTED 7/12/2017 PASSED

421 DD C AHU-H2-3 RETURN TESTED 7/12/2017 PASSED

422 DD C AHU-H2-3 SUPPLY 5 TESTED 7/12/2017 PASSED

423 DD C AHU-H2-3 SUPPLY 4 TESTED 7/12/2017 PASSED

424 DD C AHU-H2-3 SUPPLY 1 TESTED 7/12/2017 PASSED

426 PS C NEAR STAIRWELL TESTED 7/12/2017 PASSED

427 PS A DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

428 PS C DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

429 PS A DAROOM TO CORE TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/SIERRA

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

431 PS B REFUGE RM 153 TESTED 7/12/2017 PASSED

432 WF A PLUMBING RM 149 4" TESTED 7/12/2017 PASSED

433 TS A PLUMBING RM 149 TESTED 7/12/2017 PASSED

434 PS A PLUMBING RM 149 TESTED 7/12/2017 PASSED

435 PS B DAYROOM TO CORE TESTED 7/12/2017 PASSED

436 PS D MECH RM 439 NORTH TESTED 7/12/2017 PASSED

437 PS C MECH RM 439 WEST TESTED 7/12/2017 PASSED

438 PS C MECH RM 439 SOUTH TESTED 7/12/2017 PASSED

439 PS C DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

441 PS C REFUGE RM 353 TESTED 7/12/2017 PASSED

443 PS D DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

445 PS B OFFICE DESK RM 166 TESTED 7/12/2017 PASSED

447 TS A PLUMBING RM 149 TESTED 7/12/2017 PASSED

ANN A TESTED 7/12/2017 PASSED

ANN B TESTED 7/12/2017 PASSED

ANN C TESTED 7/12/2017 PASSED

ANN D TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/RENO

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP 2 EST2 TESTED 7/12/2017 PASSED

101 SD A TV ACTIVITY RM 246 TESTED 7/12/2017 PASSED

102 SD A TV ACTIVITY RM 244 TESTED 7/12/2017 PASSED

103 SD A TV ACTIVITY RM 243 TESTED 7/12/2017 PASSED

104 SD B TV ACTIVITY RM 238 TESTED 7/12/2017 PASSED

105 SD B TV ACTIVITY RM 237 TESTED 7/12/2017 PASSED

106 SD B TV ACTIVITY RM 235 TESTED 7/12/2017 PASSED

107 SD A MECH RM 239 TESTED 7/12/2017 PASSED

108 SD A EQUIPMENT RM 240 TESTED 7/12/2017 PASSED

113 SD A INMATE PHONE RM 446 TESTED 7/12/2017 PASSED

114 SD C ENTRY VESTIBULE 365 TESTED 7/12/2017 PASSED

115 SD A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED

116 SD A INMATE PHONE RM 160 TESTED 7/12/2017 PASSED

117 SD A VENDING PHONE RM 160 TESTED 7/12/2017 PASSED

118 SD A TV ACTIVITY RM 159 TESTED 7/12/2017 PASSED

119 SD A TV ACTIVITY RM 157 TESTED 7/12/2017 PASSED

120 SD A DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

121 SD A SECRETARY WAITING RM151 TESTED 7/12/2017 PASSED

122 SD B REFUGE RM 153 TESTED 7/12/2017 PASSED

123 SD B CORRIDOR 151 NORTH TESTED 7/12/2017 PASSED

124 SD B CORRIDOR 151 SOUTH TESTED 7/12/2017 PASSED

125 SD B DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

126 SD B TV ACTIVITY RM 140 TESTED 7/12/2017 PASSED

127 SD B TV ACTIVITY RM TESTED 7/12/2017 PASSED

128 SD B VENDING PHONE RM 137 TESTED 7/12/2017 PASSED

129 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

130 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

131 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/RENO

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

132 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

133 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

134 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

135 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

136 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

137 SD A DAYROOM HI-BAY TESTED 7/12/2017 PASSED

138 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

139 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

140 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

141 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

142 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

143 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

144 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

145 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

146 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

147 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

148 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

149 SD A ELEVATOR MECH RM 241 TESTED 7/12/2017 PASSED

150 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

151 SD A DAYROOM HI BAY TESTED 7/12/2017 PASSED

152 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

153 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

154 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

155 SD B DAYROOM HI BAY TESTED 7/12/2017 PASSED

222 PS A OFFICERS DESK RM 157 TESTED 7/12/2017 PASSED

223 PS B OFFICERS DESK 156 TESTED 7/12/2017 PASSED

224 PS A MECH RM 239 SOUTH TESTED 7/12/2017 PASSED

225 PS A MECH RM 239 WEST TESTED 7/12/2017 PASSED

226 PS A MECH RM 239 NORTH TESTED 7/12/2017 PASSED

227 PS C NEAR STAIR 467 TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/RENO

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

228 PS A CORE 267 NEAR STAIR TESTED 7/12/2017 PASSED

229 PS C DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

231 PS A ENTRY VESTIBULE RM 165 TESTED 7/12/2017 PASSED

232 PS C ENTRY VESTIBULE RM 235 TESTED 7/12/2017 PASSED

233 PS A DAYROOM CORE TO ENTRY TESTED 7/12/2017 PASSED

234 PS B REFUGE RM 153 TESTED 7/12/2017 PASSED

235 PS A MECH PLUMBING RM 149 TESTED 7/12/2017 PASSED

236 PS B DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

237 DD A AHU H1-1 SUPPLY 1 TESTED 7/12/2017 PASSED

238 DD A AHU H1-1 SUPPLY 2 TESTED 7/12/2017 PASSED

239 DD A AHU H1-1 SUPPLY 3 TESTED 7/12/2017 PASSED

240 DD A AHU H1-1 SUPPLY 4 TESTED 7/12/2017 PASSED

241 DD A AHU H1-1 SUPPLY 5 TESTED 7/12/2017 PASSED

242 DD A AHU H1-1 SUPPLY 6 TESTED 7/12/2017 PASSED

243 DD A AHU H1-1 SUPPLY 7 TESTED 7/12/2017 PASSED

244 DD A AHU H1-1 RETURN A TESTED 7/12/2017 PASSED

245 WF A MECH PLUMBING RM 149 4" TESTED 7/12/2017 PASSED

246 TS A PLUMBING MECH RM TESTED 7/12/2017 PASSED

248 TS A PLUMBING MECH RM 149 TESTED 7/12/2017 PASSED

258 DD A AHU H1-1 RETURN B TESTED 7/12/2017 PASSED

301 SD C TV ACTIVITY RM 446 TESTED 7/12/2017 PASSED

302 SD C TV ACTIVITY RM 404 TESTED 7/12/2017 PASSED

303 SD C TV ACTIVITY RM 443 TESTED 7/12/2017 PASSED

304 SD D TV ACTIVITY RM 438 TESTED 7/12/2017 PASSED

306 SD D TV ACTIVITY RM TESTED 7/12/2017 PASSED

305 SD D TV ACTIVITY RM 437 TESTED 7/12/2017 PASSED

307 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

308 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

309 SD C HSG-HI-4-2 TESTED 7/12/2017 PASSED

310 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

311 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

312 SD C DAYROOM HI BAY TESTED 7/20/2016 PASSED

313 SD C DAYROOM HI BAY TESTED 7/20/2016 PASSED

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

314 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

315 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

316 SD C DAYROOM HI BAY TESTED 7/12/2017 PASSED

317 SD C MECH RM 439 TESTED 7/12/2017 PASSED

318 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

319 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

320 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

321 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

322 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

323 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

324 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

325 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

326 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

327 SD D DAYROOM HI BAY TESTED 7/12/2017 PASSED

332 SD D CORRIDOR 351 NORTH TESTED 7/12/2017 PASSED

333 SD D DAYROOM TO CORE ENTRY D TESTED 7/12/2017 PASSED

334 SD C DAYROOM CORE ENTRY TESTED 7/12/2017 PASSED

335 SD D CORRIDOR 351 SOUTH TESTED 7/12/2017 PASSED

336 SD C VENDING PHONE 360 TESTED 7/12/2017 PASSED

337 SD C TV ACTIVITY RM 359 TESTED 7/12/2017 PASSED

338 SD C TV ACTIVITY RM 357 TESTED 7/12/2017 PASSED

339 SD D SECRITARY ROOM CORRIDOR TESTED 7/12/2017 PASSED

340 SD D REFUGE RM 353 TESTED 7/12/2017 PASSED

341 SD D VENDING PHONE 341 TESTED 7/12/2017 PASSED

342 SD D TV ACTIVITY RM 338 TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/RENO

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

343 SD D TV ACTIVITY RM 340 TESTED 7/12/2017 PASSED

344 SD D INMATE PHONE RM 442 TESTED 7/12/2017 PASSED

345 SD D ENTRY VESTIBULE 356 TESTED 7/12/2017 PASSED

346 SD B INMATE PHONE RM 242 TESTED 7/12/2017 PASSED

347 SD B ENTRY VESTIBULE 156 TESTED 7/12/2017 PASSED

403 PS C OFFICERS DESK 367 TESTED 7/12/2017 PASSED

404 PS D OFFICERS DESK TESTED 7/12/2017 PASSED

405 PS C MECH RM 439 SOUTH TESTED 7/12/2017 PASSED

406 PS C MECH RM 439 WEST TESTED 7/12/2017 PASSED

407 PS C MECH RM 439 NORTH TESTED 7/12/2017 PASSED

408 PS D DAYROOM NEAR STAIRWELL TESTED 7/12/2017 PASSED

409 PS D CORRIDOR NEAR STAIRS TESTED 7/12/2017 PASSED

410 PS C CORE 266 NEAR STAIRS TESTED 7/12/2017 PASSED

412 PS C DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

413 PS D REFUGE RM 353 TESTED 7/12/2017 PASSED

414 PS D DAYROOM TO CORE ENTRY TESTED 7/12/2017 PASSED

415 PS D ENTRY VESTIBULE 358 TESTED 7/12/2017 PASSED

416 PS D ENTRY VESTIBULE 358 TESTED 7/12/2017 PASSED

418 DD D AHU-HI-3 SUPPLY 4 SIDE A TESTED 7/12/2017 PASSED

420 DD D AHU-HI-3 SUPPLY 2 SIDE A TESTED 7/12/2017 PASSED

421 DD C SUPPLY 5 SIDE A TESTED 7/12/2017 PASSED

422 DD C RETURN SIDE A TESTED 7/12/2017 PASSED

423 DD C SUPPLY 1 SIDE B TESTED 7/12/2017 PASSED

424 DD C SUPPLY 5 SIDE A TESTED 7/12/2017 PASSED

425 DD C SUPPLY 3 SIDE B TESTED 7/12/2017 PASSED

426 DD C RETURN SIDE A TESTED 7/12/2017 PASSED

427 DD C SUPPLY 1 SIDE B TESTED 7/12/2017 PASSED

428 DD C SUPPLY 3 SIDE B TESTED 7/12/2017 PASSED

ANN A TESTED 7/12/2017 PASSED

ANN B TESTED 7/12/2017 PASSED

ANN C TESTED 7/12/2017 PASSED

ANN D TESTED 7/12/2017 PASSED

SITE: Herlong Federal Prison/RENO

SITE: Herlong Federal Prison/EM

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP 1 EST 2 TESTED 7/13/2017 PASSED

103 SD AI ELECTRONICS RM 142 TESTED 7/13/2017 PASSED

108 SD VT S & C ELECTRICAL ROOM TESTED 7/13/2017 PASSED

204 DD BT BT1 107 RETURN TESTED 7/13/2017 PASSED

213 DD BT AHU-A1-1 TESTED 7/13/2017 PASSED

216 DD EM MECHANICAL RM 110 RETURN TESTED 7/13/2017 PASSED

217 TS VT SPRINKLER VT 111 TESTED 7/13/2017 PASSED

218 PS VT VOCATIONAL TRAINING TESTED 7/13/2017 PASSED

219 PS VT VOCATIONAL TRAINING TESTED 7/13/2017 PASSED

220 PS VT SPRINKLER ROOM 111 TESTED 7/13/2017 PASSED

221 PS BT MECHANICAL RM 107 TESTED 7/13/2017 PASSED

222 PS VT VOCATIONAL SHOP VT 100 E TESTED 7/13/2017 PASSED

223 PS VT VOCATIONAL SHOP VT 100 W TESTED 7/13/2017 PASSED

224 TS AI SPRINKLER MECH RM 141 TESTED 7/13/2017 PASSED

225 PS EM ENTRY VESTIBULE EM 100 TESTED 7/13/2017 PASSED

226 PS EM ENTRY VESTIBULE EM 141 TESTED 7/13/2017 PASSED

228 PS EM MAIN CLASSROOM ENTRY VESTIBULE EM 123 TESTED 7/13/2017 PASSED

229 PS EM CLASSROOM EM LAW TESTED 7/13/2017 PASSED

230 PS EM CLASSROOM EM ELECT RM 120 TESTED 7/13/2017 PASSED

231 PS AI VISITING RM 128 WEST TESTED 7/13/2017 PASSED

232 PS AI VISITING AL MECH RM 141 TESTED 7/13/2017 PASSED

233 PS AI CORRIDOR 140 TESTED 7/13/2017 PASSED

234 PS AI VISITING CORRIDOR RM 119 TESTED 7/13/2017 PASSED

235 PS AI SECRETARY VISITING RM 118 TESTED 7/13/2017 PASSED

236 PS AI SALLY PORT MAIN VISITING RM 132 TESTED 7/13/2017 PASSED

237 TS EM2 SPRINKLER MECHANICAL 110 TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/EM

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

238 PS AI VISITING RM 128 TESTED 7/13/2017 PASSED

239 PS EM CLASSROOM LEARNING CENTER EM 118 TESTED 7/13/2017 PASSED

240 PS EM RELIGION/CLASS SPRINKLER 110 TESTED 7/13/2017 PASSED

241 PS EM RELIGION/CLASS TESTED 7/13/2017 PASSED

243 DD BT AHU BT 1 MECH RM 107 SUPPLY TESTED 7/13/2017 PASSED

244 DD AI MECH AI SUPPLY 141 TESTED 7/13/2017 PASSED

245 DD AL AHU AL 1 MECH ROOM SUPPLY TESTED 7/13/2017 PASSED

246 DD PS AHU-A1-1 SUPPLY TESTED 7/13/2017 PASSED

247 DD EM MECHANICAL RM 110 SUPPLY TESTED 7/13/2017 PASSED

248 WF VT VOC TRAINING BUILDING TESTED 7/13/2017 PASSED

249 TS VT 31 VT 111 TESTED 7/13/2017 PASSED

250 DD EM AHU-A1-1 SUPPLY 4 TESTED 7/13/2017 PASSED

252 WF AI SPRINKLER MECH RM 141 2.5" TESTED 7/13/2017 PASSED

253 TS AI SPRINKLER MECH RM 141 TESTED 7/13/2017 PASSED

256 WF EM RELIGION/CLASS SPRINKLER 110 4" TESTED 7/13/2017 PASSED

257 TS EM1 SPRINKLER MECHANICAL 110 TESTED 7/13/2017 PASSED

301 SD UF SECURITY ELECTRIC ROOM TESTED 7/13/2017 PASSED

302 SD UF ELEVATOR LOBBY UF 204 TESTED 7/13/2017 PASSED

303 SD UF ELEVATOR LOBBY 126 TESTED 7/13/2017 PASSED

408 WF UF SPRINKLER RM 115 6" TESTED 7/13/2017 PASSED

409 TS UF #1 SPRINKLER RM 115 TESTED 7/13/2017 PASSED

410 PS UF OPEN OFFICE UF 200 W TESTED 7/13/2017 PASSED

411 PS UF MECH RM UF 216 TESTED 7/13/2017 PASSED

412 PS UF OPEN OFFICE UF 200 E TESTED 7/13/2017 PASSED

413 PS UF SCREENING ENTRY UFT 100 TESTED 7/13/2017 PASSED

414 PS UF STAIRWELL TESTED 7/13/2017 PASSED

415 PS UF FACTORY AREA UF 101 WN TESTED 7/13/2017 PASSED

416 PS UF FACTORY AREA 101 W TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/EM

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

417 PS UF FATORY AREA UF 101 WS TESTED 7/13/2017 PASSED

418 PS UF FACTORY AREA UF 101 WS TESTED 7/13/2017 PASSED

419 PS UF MAIN FACTORY AREA UF 101 SE TESTED 7/13/2017 PASSED

420 PS PS FACTORY AREA UF 101E TESTED 7/13/2017 PASSED

422 PS UF UNICOR ELECTRIC ROOM TESTED 7/13/2017 PASSED

423 PS UF SPRINKLER RM UF 115 TESTED 7/13/2017 PASSED

424 DD UF MECH RM 113 RETURN TESTED 7/13/2017 PASSED

425 DD UF MECH RM 113 SUPPLY TESTED 7/13/2017 PASSED

426 DD UF MECH RM 216 SUPPLY TESTED 7/13/2017 PASSED

427 DD UF MECH RM 216 RETURN TESTED 7/13/2017 PASSED

428 DD UF MECH RM 216 RETURN TESTED 7/13/2017 PASSED

429 TS UF #2 SPRINKLER RM 115 TESTED 7/13/2017 PASSED

430 DD UF MECH RM 216 SUPPLY TESTED 7/13/2017 PASSED

434 PS UF PAINT BOOTH AREA TESTED 7/13/2017 PASSED

435 PS UF PAINT BOOTH AHU-UF-4-RET TESTED 7/13/2017 PASSED

436 PS UF PAINT BOOTH AHU-UF-4-SUP TESTED 7/13/2017 PASSED

ANN UF TESTED 7/13/2017 PASSED

ANN VT TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/SH

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP SH EST 2 TESTED 7/13/2017 PASSED

101 SD SH SALLY PORT SH 167 TESTED 7/13/2017 PASSED

102 SD SH LOBBY SH 162 TESTED 7/13/2017 PASSED

103 SD SH HEARING ROOM SH 171 TESTED 7/13/2017 PASSED

104 SD SH CORRIDOR SH 163 TESTED 7/13/2017 PASSED

106 SD SH MULTI-PURPOSE SH 156 TESTED 7/13/2017 PASSED

107 SD SH LOBBY SH 162 TESTED 7/13/2017 PASSED

108 SD SH CORRIDOR SH 158 W TESTED 7/13/2017 PASSED

109 SD SH CORRIDOR SH 158 MID TESTED 7/13/2017 PASSED

110 SD SH CORRIDOR SH 158 E TESTED 7/13/2017 PASSED

111 SD SH STAIRWELL SH 157 TESTED 7/13/2017 PASSED

112 SD SH MULTI-PURPOSE SH 256 TESTED 7/13/2017 PASSED

113 SD SH LOBBY SH 153 E TESTED 7/13/2017 PASSED

114 SD SH LOBBY SH 153 W TESTED 7/13/2017 PASSED

115 SD SH CORRIDOR 253 E TESTED 7/13/2017 PASSED

116 SD SH CORRIDOR SH 258 W TESTED 7/13/2017 PASSED

117 SD SH CORRIDOR SH 258 MID TESTED 7/13/2017 PASSED

118 SD SH CORRIDOR 258 E TESTED 7/13/2017 PASSED

119 SD SH STAIRWELL SH 257 TESTED 7/13/2017 PASSED

120 SD SH MULTI- PURPOSE SH 154 TESTED 7/13/2017 PASSED

121 SD SH LOBBY SH 153 NE TESTED 7/13/2017 PASSED

122 SD SH MULTI-PURPOSE SH 155 TESTED 7/13/2017 PASSED

123 SD SH CORRIDOR SH 191 SW TESTED 7/13/2017 PASSED

124 SD SH CORRIDOR SH 191 MID TESTED 7/13/2017 PASSED

125 SD SH CORRIDOR SH 191 E TESTED 7/13/2017 PASSED

126 SD SH STAIRWELL SH 190 TESTED 7/13/2017 PASSED

127 SD SH MULTI- PURPOSE SH 254 TESTED 7/13/2017 PASSED

128 SD SH CORRIDOR SH 253 NE TESTED 7/13/2017 PASSED

129 SD SH MULTI-PURPOSE SH 255 TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/SH

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

130 SD SH CORRIDOR SH 253 NE TESTED 7/13/2017 PASSED

131 SD SH CORRIDOR SH 291 MID TESTED 7/13/2017 PASSED

132 SD SH CORRIDOR SH 291 NE TESTED 7/13/2017 PASSED

133 SD SH STAIRWELL SH 290 TESTED 7/13/2017 PASSED

134 SD SH LOBBY SH 153 N TESTED 7/13/2017 PASSED

135 SD SH CORRIDOR SH 150 S TESTED 7/13/2017 PASSED

136 SD SH CORRIDOR SH 150 MID TESTED 7/13/2017 PASSED

137 SD SH CORRIDOR SH 150 N TESTED 7/13/2017 PASSED

138 SD SH STAIRWELL SH 149 TESTED 7/13/2017 PASSED

139 SD SH CORRIDOR SH 253 W TESTED 7/13/2017 PASSED

140 SD SH CORRIDOR SH 250 S TESTED 7/13/2017 PASSED

141 SD SH CORRIDOR SH 250 MID TESTED 7/13/2017 PASSED

142 SD SH CORRIDOR SH 250 N TESTED 7/13/2017 PASSED

143 SD SH STAIRWELL SH 249 TESTED 7/13/2017 PASSED

151 SD SH CORRIDOR SH 291 MID TESTED 7/13/2017 PASSED

213 PS SH SALLYPORT SH 167 TESTED 7/13/2017 PASSED

214 PS SH OFFICERS STATION TESTED 7/13/2017 PASSED

215 PS SH LOBBY SH 158 TESTED 7/13/2017 PASSED

216 PS SH STAIRWELL SH 157 TESTED 7/13/2017 PASSED

217 PS SH MECH RM SHU 293 TESTED 7/13/2017 PASSED

218 PS SH CORRIDOR SH 253 E TESTED 7/13/2017 PASSED

219 PS SH CORRIDOR 258 E TESTED 7/13/2017 PASSED

220 PS SH CORRIDOR 191 SW TESTED 7/13/2017 PASSED

221 PS SH STAIRWELL SH 190 TESTED 7/13/2017 PASSED

222 PS SH CORRIDOR SH 291 SW TESTED 7/13/2017 PASSED

223 PS SH CORRIDOR SH 291 NE TESTED 7/13/2017 PASSED

224 PS SH CORRIDOR SH 150 S TESTED 7/13/2017 PASSED

225 PS SH STAIRWELL SH 190 TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/SH

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

226 PS SH CORRIDOR 250 S TESTED 7/13/2017 PASSED

227 PS SH CORRIDOR SH 250 N TESTED 7/13/2017 PASSED

228 DD SH AHU SHU-1 SUPPLY 1 TESTED 7/13/2017 PASSED

229 DD SH AHU SHU-1 SUPPLY 2 TESTED 7/13/2017 PASSED

230 DD SH AHU SHU-1 SUPPLY 3 TESTED 7/13/2017 PASSED

231 DD SH AHU SHU-1 SUPPLY 4 TESTED 7/13/2017 PASSED

232 DD SH AHU SHU-1 SUPPLY 5 TESTED 7/13/2017 PASSED

233 DD SH AHU SHU-1 SUPPLY 6 TESTED 7/13/2017 PASSED

234 DD SH AHU SHU-1 RETURN TESTED 7/13/2017 PASSED

235 WF SH MECH RM SPECIAL HOUSING 293 4" TESTED 7/13/2017 PASSED

236 TS SH RECREATION SVCS TESTED 7/13/2017 PASSED

237 WF SH MECH RM SPECIAL HOUSING 293 4" TESTED 7/13/2017 PASSED

238 TS SH MECHANICAL RM 293 RECREATIONAL SVCS TESTED 7/13/2017 PASSED

239 TS SH SH 293 ISO VALVE TESTED 7/13/2017 PASSED

247 PS RS GYM NE TESTED 7/13/2017 PASSED

301 SD HS SECURITY HS 186 TESTED 7/13/2017 PASSED

303 SD RS SEC. ELECTRONIC RE 115 TESTED 7/13/2017 PASSED

404 PS HS SPRINKLER RM 113 TESTED 7/13/2017 PASSED

405 PS RC REC SVCS STAFF ASSEMBLY AI 101 TESTED 7/13/2017 PASSED

406 PS HS CORRIDOR HS 115 TESTED 7/13/2017 PASSED

407 PS HS CORRIDOR HS 142 TESTED 7/13/2017 PASSED

408 PS HS MECH ROOM HS 143 TESTED 7/13/2017 PASSED

409 PS HS ENTRY HS 173 TESTED 7/13/2017 PASSED

410 PS HS MAIL ROOM HS 187 TESTED 7/13/2017 PASSED

411 PS HS HEALTH SVCS HS 189 TESTED 7/13/2017 PASSED

412 PS HS VESTIBULE HS 100 TESTED 7/13/2017 PASSED

413 PS HS WAITING RM HS 101 TESTED 7/13/2017 PASSED

414 DD HS AHU HS 1 SUPPLY TESTED 7/13/2017 PASSED

415 WF HS SPRINKLER RM HS 113 TESTED 7/13/2017 PASSED

416 TS HS TAMPER 2 SPRINKLER RM 113 TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/SH

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

418 PS AI VISITING VESTIBULE AI 100 TESTED 7/13/2017 PASSED

419 PS AI VISITING CLERK WAITING AI 108 TESTED 7/13/2017 PASSED

425 PS RS MECH RM RE 114 TESTED 7/13/2017 PASSED

426 PS RS ELECTRICAL ROOM 116 TESTED 7/13/2017 PASSED

427 PS RS OPEN ACTIVITY RE 100 S TESTED 7/13/2017 PASSED

428 PS RS OPEN ACTIVITY RE 100 M TESTED 7/13/2017 PASSED

429 PS RS TESTED 7/13/2017 PASSED

430 PS RS INMATE TOILET 118 TESTED 7/13/2017 PASSED

431 DD RS AHU RE-1 SUPPLY TESTED 7/13/2017 PASSED

433 DD HS AHU 1 HS RETURN TESTED 7/13/2017 PASSED

434 DD RS AHU-RE-1 RETURN TESTED 7/13/2017 PASSED

435 TS HS AI-1 SPRINKLER HS 113 TESTED 7/13/2017 PASSED

ANN R&D TESTED 7/13/2017 PASSED

ANN HS TESTED 7/13/2017 PASSED

ANN SH TESTED 7/13/2017 PASSED

ANN RC TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/AO

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DIAL Dialer HD Heat Detector

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP AO EST 2 TESTED 7/13/2017 PASSED

101 SD AO CONTROL CENTER AO 104 TESTED 7/13/2017 PASSED

102 SD AO CONTROL CENTER AO 104 TESTED 7/13/2017 PASSED

103 SD AO ELECTRONICS SHOP AO 146 TESTED 7/13/2017 PASSED

104 SD AO ELECTRONICS EQUIP 145 TESTED 7/13/2017 PASSED

204 DD AO MECH RM AO 147 RETURN TESTED 7/13/2017 PASSED

205 TS AO TAMPER 2 AO 104 TESTED 7/13/2017 PASSED

206 WF AO WATERFLOW CONTROL RM SALLY PORTTESTED 7/13/2017 PASSED

209 PS AO ADMIN. ELECTRICAL ROOM TESTED 7/13/2017 PASSED

210 PS AO ADMIN CONTROL AO 104 TESTED 7/13/2017 PASSED

211 PS AO WAITING RM AO 102 TESTED 7/13/2017 PASSED

212 PS AO AO CORRIDOR AO 166 TESTED 7/13/2017 PASSED

213 PS AO RECEPTION WAITING AO 101 TESTED 7/13/2017 PASSED

214 PS AO RECEPTION WAITING AO 101 TESTED 7/13/2017 PASSED

215 PS AO CORRIDOR AO 130 TESTED 7/13/2017 PASSED

216 PS AO MECH RM AO 147 TESTED 7/13/2017 PASSED

217 PS AO ADMIN. ELECTRICAL ROOM TESTED 7/13/2017 PASSED

218 DD AO MECH RM AO 147 SUPPLY 1 TESTED 7/13/2017 PASSED

219 WF AO MECH AO 147 4" TESTED 7/13/2017 PASSED

220 TS AO MECH RM 147 TESTED 7/13/2017 PASSED

222 TS AO SALLY PORT TESTED 7/13/2017 PASSED

223 DD AO MECH RM AO 147 SUPPLY 2 TESTED 7/13/2017 PASSED

227 DD AO AHU-AO1 TESTED 7/13/2017 PASSED

228 DD AO AHU-MECH RM TESTED 7/13/2017 PASSED

229 DD AO AHU-MECH RM TESTED 7/13/2017 PASSED

ANN AO TESTED 7/13/2017 PASSED

SITE: Herlong Federal Prison/CAMPHOUSE

SD Smoke Detector DD Duct Dector AUD Audible

AS Air Sampling WF Waterflow DH Door Holder

AV Audible/Visual FP Fire Phone FAN Fan Control Panel

PTR Printer VDT Display Terminal VIS Visual

PWK Aux Power Supply FSI FSI Interface FACP Fire Alarm Panel

PS Pull Station BD Beam Detector NCC NCC

TS Tamper Switch FSD Fire Smoke Damper

SPKR Voice Evac Speaker FJ Fire Jack

ANN Annuciator EVAC Voice Evac Panel

DEV SERVICE TEST

ZONE TYPE FLOOR DEVICE LOCATION PERFORMED PERFORMED

FACP 1 EST 2 TESTED 7/13/2017 PASSED

101 SD CH SMOKE ELECTRICAL ROOM TESTED 7/13/2017 PASSED

102 SD CH TV ACTIVITY CH 113 TESTED 7/13/2017 PASSED

103 SD CH TV ACTIVITY CH 112 TESTED 7/13/2017 PASSED

104 SD CH TV ACTIVITY CH 111 TESTED 7/13/2017 PASSED

105 SD CH VESTIBULE CH 100…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.