This is a Statement of Work/Request for Quote issued by the Federal Bureau of Prisons (FBOP) for Project 26Z6AL1 at FCC Lompoc, California. The document was approved by the Construction and Environmental Review Section on May 7, 2026, and is limited specifically to the replacement of fire escape doors at FCI 1, with no expansion intended for future unrelated work.

FBOP seeks quotes from qualified vendors for supply and delivery of nine complete fire escape door assemblies comprising four left-hand outswing and five right-hand outswing units. Each assembly must measure 36" wide x 80" high x 2" thick and consist of hollow metal doors constructed from minimum 12-gauge galvanneal steel with ribbed, insulated mineral cores. The complete door assembly must achieve a 90-minute fire rating and comply with NFPA 80, NFPA 101, International Building Code (IBC), International Fire Code (IFC), OSHA exit route requirements, and UL 10C or NFPA 252 standards. Frames must be minimum 12-gauge galvanneal steel, fire-rated and labeled, either knock-down or welded depending on wall type, and factory-prepped for 80-series locks and panic hardware. All components must be U.L. Listed or labeled by recognized testing agencies acceptable to the Authority Having Jurisdiction. Hardware requirements include three UL-Listed steel ball bearing hinges per door, panic hardware operable with 15 pounds force or less, 80-series keyed locks with surface pulls, heavy-duty adjustable surface-mounted door closers, and smoke/draft control seals. Vendors must submit itemized pricing, proposed lead times, compliance confirmations, and product cut sheets. Deliveries to FCC Lompoc are accepted only between 7:30 a.m. and 2:00 p.m., Monday through Friday, excluding Federal Holidays, with Mr. Fernando Pena (FXPena@bop.gov, 805-735-2771) as the point of contact.

View the file

Other files

File Type Posted
15B61727Q00000002-BRQ.pdf PDF
FCC Lompoc Fire Door Assembly Combined Synopsis.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. Department of Justice Federal Bureau of Prisons

Facilities Management

Washington, DC 20534

May 7, 2026

MEMORANDUM FOR JOHN CALTON, FACILITY MANAGER

FCC LOMPOC

THRU: Kimberly Hudson, Chief Construction and Environmental Review Section

FROM: Julius Buyag, Engineering Technician Construction and Environmental Review Section

SUBJECT: Statement of Work Approval for Project 26Z6AL1 Replace Fire Escape Doors FCI 1

The Construction and Environmental Review Section, Facilities Management, has reviewed and approved the Statement of Work to be used for solicitation services at FCC Lompoc for Project 26Z6AL1, Replace Fire Escape Doors FCI 1. There are no additional square footage or modifications to the primary structure, nor changes to the utilities to this project.

This Statement of Work specifically addresses the Replace Fire Escape Doors FCI 1 under Project 26Z6AL1 as defined herein and should not be interpreted as an open-ended approval for future, unrelated work.

If you have any additional questions or concerns, please email Julius Buyag, Engineering Technician, at jbuyag@bop.gov.

Cc: Regional Facilities Administrator

FEDERAL BUREAU OF PRISONS

FCC LOMPOC

B&F PROJECT # 26Z6AL1 REPLACE FIRE ESCAPE DOORS FCI I

STATEMENT OF WORK / REQUEST FOR QUOTE

A. INTRODUCTION:

1. The Federal Bureau of Prisons (FBOP), FCC Lompoc, 3901 Klein Blvd., Lompoc, CA 93436, is seeking quotes from qualified vendors for the supply and delivery of nine (9) complete fire escape door assemblies, including doors, frames, and all required hardware. The doors are for a prison facility application and must meet all relevant local, state, and federal fire and life safety codes.

2. "Equal or Better" Product Substitution: Proposals must meet or exceed the specified product quality. If an alternative product or component is offered, the vendor must submit all technical documentation, certifications, and test results for consideration.

3. Government's Right of Final Technical Acceptance: The government retains the sole and final authority to determine technical acceptance for all submitted products, based on the provided documentation and compliance with stated standards.

B. SCOPE OF WORK:

1. The vendor shall provide all materials as specified below. All components must be new, U.L.

Listed or labeled by a recognized testing agency acceptable to the Authority Having Jurisdiction (AHJ) and conform to the standards referenced herein.

C. TECHNICAL SPECIFICATIONS:

TABLE 1: COMPONENTS: All units shall be identical unless otherwise noted.

Component Requirement Quantity 9 Complete Door Assemblies Door Size 36" wide x 80" high x 2" thick Door Material Hollow Metal Door, minimum 12 Gauge galvanneal steel Core Ribbed and Insulated (mineral core for fire rating is acceptable/preferred) Fire Rating Rating must be compatible with the wall's fire resistance rating, typically 75% of the wall's rating. See required fire rating for correctional facilities on Table 2 Handing 4 Left Hand Outswing, 5 Right Hand Outswing.

Frame Material Minimum 12 Gauge galvanneal steel, fire-rated and labeled Frame Type Knock-down (KD) for drywall/unit masonry or welded for masonry. Frames are to be prepared for 80 series lock, keyed 2 sides strike, surface pull on both sides and prepped for PA closer.

Finish Factory primed for field painting

TABLE 2: FIRE RATING:

The complete door assembly (door, frame, and all hardware) shall be 90 minutes fire rated. This rating must be compatible with the fire-resistance rating of the specific wall assembly in which the door will be installed, as dictated by the building's fire safety plan and local code requirements.

Category Requirement Description Applicable Standards & Agencies

Listing & Labeling

All components must be listed and labeled by a recognized third-party testing agency acceptable to the Authority Having Jurisdiction (AHJ).

Underwriters Laboratories (UL), Intertek (WH), Factory Mutual (FM)

Testing Standard

Assemblies shall be tested under positive pressure conditions.

NFPA 252, ANSI/UL 10C

Labeling Visibility

A permanent, legible fire rating label must be affixed to both the door and the frame and remain visible after installation for inspection purposes.

N/A

Code Compliance

Vendor must confirm that all components, when installed as an assembly, comply with relevant building and safety codes for correctional facilities (Group I-3 Occupancies, IBC).

NFPA 80 (Standard for Fire Doors and Other Opening Protectives) International Building Code

(IBC)

TABLE 3: HARDWARE SPECIFICATIONS:

All hardware must be "listed" or "labeled" for use on a fire-rated assembly, compatible with the specified fire rating, and factory-prepped for ANSI/BHMA Grade 1 standards.

Item Requirement Quantity per Door

Notes

Hinges Heavy-duty steel ball bearing hinges, UL Listed 3 Exit Device

Panic Hardware/Fire Exit Hardware (rim or mortise type) self-latching

1 set Must be a crossbar or touch bar device, operable with an applied force of 15 lbs or less.

Locking Must be openable from the egress side at all times without special knowledge or tools.

Keyed access from the exterior is permitted.

1 set 80 series lock, keyed 2 sides strike, surface pull on both sides and prepped for PA closer.

Door Closer

Heavy-duty, adjustable, surface-mounted, UL Listed

1 unit Must be self-closing and ensure positive latching.

Seals Smoke and draft control gasketing/seals 1 set Required for a complete smoke-rated assembly.

Threshold [Specify if required, e.g., 1/2" beveled aluminum, non-combustible]

1 unit (if required)

D. CODE AND STANDARD REQUIREMENTS:

1. All supplied materials and the complete assembly must comply with the latest editions of the following codes and standards (or local equivalents as adopted by the AHJ):

NFPA 80: Standard for Fire Doors and Other Opening Protectives NFPA 101: Life Safety Code

International Building Code (IBC) International Fire Code (IFC) OSHA requirements for exit routes

UL 10C or NFPA 252: Standard for positive pressure fire testing of door assemblies UL 1784: Standard for Air Leakage Tests of Door Assemblies (if smoke rating is required)

2. Vendors must confirm that all components, when installed as an assembly, will bear a permanent, legible label from a recognized third-party testing agency (e.g., UL, Intertek/WH, FM).

E. SUBMISSION REQUIREMENTS:

1. Itemized pricing for doors, frames, hardware, and any included accessories.

2. Proposed lead time for manufacturing and delivery to FCC Lompoc

3. Confirmation of compliance with all referenced codes and standards.

4. Cut sheets/product data for all proposed items.

F. DELIVERY OF MATERIALS:

1. Deliveries shipped directly to FCC LOMPOC can only be received between 7:30 a.m. and 2:00 p.m., Monday through Friday, excluding Federal Holidays.

2. POC: Mr. Fernando Pena, BOP Engineering Technician, FXPena@bop.gov, or 805-735-2771

3. FBOP will be responsible for receiving or signing deliveries.

4. FCC LOMPOC will provide resources for loading and unloading materials or equipment upon arrival.

File details come from the government source that posted it. Updated .