This document appears to be a federal solicitation for the procurement of two (2) PVI water heaters and replacement parts for a PVI heat exchanger for the Federal Correctional Complex (FCC) Florence. The key requirements include the water heaters, replacement parts, technician start-up observation services, comprehensive warranty, and FOB delivery to FCC Florence with shipping costs included. The solicitation will be available on or about September 19, 2024, and quotes are due by September 30, 2024 at 12:00 PM Mountain Time. Payment will be made using Electronic Funds Transfer, and the award will be based on the Lowest Price Technically Acceptable criteria, evaluating factors such as past performance and availability. This procurement is set aside for small businesses and will be conducted in accordance with the Federal Acquisition Regulations Part 12 for the acquisition of commercial items.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Btu Input 1,000,000

Recovery GPH 70°F to 140°F 1652 (96% ET)

Recovery GPH 40°F to 140°F 1175 (97.5% ET)

Storage Capacity - gallons 310

Gas Pressure Maximum Static 14" W.C.

Gas Pressure Minimum Flow 3.5" W.C.

Amperage (120VAC, 60Hz.) 11

Max. Inlet Air Duct Length @ 6" dia. 100 ft. with four 90° ells

Max. Vent Length @ 6" dia. 100 ft. with four 90° ells

Shipping Weight lbs. 1890

Recommended Service Clearance: 18" from all sides, 12" from the top. Consult factory for heat exchanger pull space requirements.

Minimum Clearances: 6" from all sides and top, 24" from the front.

Per DOE, 10 CFR 431 (ANSI Z21.10.3 @ 70°F to 140°F)

Listed for category IV venting through PVC, CPVC, polypropylene, or single-wall stainless steel vent

Refer to manual for design requirements

Longer vents available with larger diameter