This addendum to a statement of work concerns repairs to boilers 2 and 3 at the Federal Correctional Institution in Otisville, New York. The Bureau of Prisons seeks a contractor to perform repairs on boiler 3 to place it into service, after which the bureau will take boiler 2 offline for the contractor to complete repairs. The addendum provides revised language regarding the current operational status and observed issues with boilers 2 and 3. It also outlines responsibilities for the bureau to remove boiler 2 from service after boiler 3 repairs are finished, and responsibilities for the contractor to proceed with boiler 2 repairs thereafter. The related federal contract opportunity is solicitation number 15B21124PR000016 to repair boilers 2 and 3 at the Otisville facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| WageRatesFY24.pdf | ||
| PICTURES.pdf | ||
| OTV_23Z2AK9_SOW_Boiler2-3_10262023_FA_Approved.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM TO STATEMENT OF WORK (SOW)
REPAIR BOILERS 2 & 3
B&F PROJECT 23Z2AL9: EMG Repair Boilers 1, 2 & 3
FCI OTISVILLE
OTISVILLE, NEW YORK
November 15, 2023
The following changes are made to the SOW:
1. Page 2 of 6, Paragraph 1.01.D.1.a. is changed to read as follows:
Boiler is currently in service.
2. Page 2 of 6, Paragraph 1.01.D.1.b. is changed to read as follows:
Front and rear doors of boilers are closed.
3. Page 2 of 6, Paragraph 1.01.D.1.c. is changed to read as follows:
Boiler tubes showing signs of corrosion and fa gue. Mechanical boiler tube plugs installed in three boiler tubes for boiler to be put into service.
4. Page 2 of 6, Paragraph 1.01.D.1.d. is changed to read as follows:
Front intermediate door insula on patched where it had failed for boiler to be put into service.
5. Page 2 of 6, Paragraph 1.01.D.2.g. is removed.
Remove the following: Rear davit hinge bearings have failed.
6. Page 5 of 6, 2.02, FBOP RESPONSIBILITIES, add Paragraph 2.02.A.5. to read as follows:
FBOP will take Boiler 2 out of service a er Contractor completes all repairs to Boiler 3 and it is placed into service.
7. Page 6 of 6, 2.03 CONTRACTOR RESPONSIBILITIES, add Paragraph 2.03.B.9 to read as follows:
Contractor shall proceed with Boiler 2 repairs a er FBOP takes Boiler 2 out of service.
NERO APPROVAL:
FACILITIES ADMINISTRATOR: _______________________ DATE: ____________
MICHAEL C. BOND
INSTITUTION APPROVAL:
FACILITY MANAGER: _______________________ DATE: ____________
A. CHURCHILL
| 2023-11-15T12:00:17-0500 | |
| AARON CHURCHILL |
| 2023-11-15T17:58:05-0500 | |
| MICHAEL BOND |
File details come from the government source that posted it. Updated .