1431-14 RPA Ops Final DRAWINGS.pdf
PDF 41 MB Posted
- Attached to
- Construct Consolidated RPA Operations Facility
- Solicitation number
- W901UZ-21-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document provides details for a federal solicitation to construct a consolidated remotely piloted aircraft operations facility. The solicitation seeks a single firm fixed-price contract for construction services including a approximately 25,600 square foot single story building for administrative functions, training and operations. Site work includes clearing, grading, paving, utilities and landscaping. The building features precast concrete bearing walls, steel bar joists, and metal deck roofing. Interior finishes comprise floors, walls, ceilings and mechanical, electrical and plumbing systems. The project must achieve Guiding Principles Certification and has a 455 calendar day performance period. The solicitation will be issued on March 30th with the pre-bid conference on April 15th and bids due on April 29th. The opportunity is 100% set aside for small businesses and located in Fargo, North Dakota.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSOLIDATED RPA
OPERATIONS FACILITY
Fargo, North Dakota
SHEET INDEX
COVER
Sheet Index, Site Plan, Site Security Plan
CIVIL
C1.0 Demolition Plan
C2.0 Erosion Control/Storm Sewer Plan
C2.1 Sanitary Sewer/Watermain Plan
C3.0 Grading Plan
C4.0 Paving Plan
C5.0 Jointing Plan
C6.0 Details
C6.1 Details
LANDSCAPE
L100 Landscape Plan, Plant Schedule, Details
L101 Dumpster Screen Details, Pergola Details, Architectural Fence Details
ARCHITECTURAL
A000 Main Level Code Plan, Code Review Summary, Code Plan Legend
A090 Building 400/410 Key Plan, Building 410 Main
Level Demo Plan, Demolition Notes, Building
410 Main Level Plan, Room Finish Schedule, Door Schedule, Details
A091 Bldg 410 Reflected Ceiling Plan, Interior
Elevation, Wall Section, Details
A100 Main Level Floor Plan, Wall Types, Details
A101 Room Finish Schedule, Details
A102 Main Level Finish Plan, Details
A200 Building Elevations
A300 Building Sections, Details
A400 Wall Sections, Details
A600 Roof Plan, Details
A700 Door Schedule, Door Types, Frame Types, Details
A701 Building Section, Details
A800 Main Level Reflected Ceiling Plan, RCP Legend, Details
A900 Enlarged Floor Plans, Interior Elevations
A901 Enlarged Floor Plan, Framing Plan, Interior
Elevations, Details
A902 Interior Elevations, Details
STRUCTURAL
S001 Structural Notes
S101 Footing & Foundation Plan
S102 ABI-1: Building 410 Footing & Foundation Plan, Building 410 Roof Framing Plan
S201 Roof Framing Plan
S301 Footing & Foundation Details
S401 Framing Details
S402 Framing Details
MECHANICAL
M001 Mechanical Legend & Symbols, Schedules
M002 Site Plan
M100 Building 410 Plan - Mechanical Demolition, Building 130 Plan - Mechanical Demolition
M200 Foundation Plan - Underground Plumbing
M201 Main Floor Plan - Plumbing
M202 Plumbing Riser Diagrams
M300 Main Floor Plan - Ventilation
M400 Main Floor Plan - Hydronic
M500 Fire Sprinkler
M600 Mechanical Details
M601 Mechanical Details
M602 Mechanical Details
M603 Mechanical Details
ELECTRICAL
E001 Electrical Symbol Legend & Luminaire Schedule
E002 Site Plan - Electrical
E003 Partial Site Plan - Electrical
E004 Building 410 - Electrical Demolition, Electrical
E100 Main Floor Plan - Lighting
E200 Main Floor Plan - Power
E201 Large Scale Partial Main Floor Plan - Power
E202 Roof Plan - Power
E300 Main Floor Plan - Systems
E400 Main Floor Plan - Fire Alarm
E500 Electrical One Line & Details
E501 23.9KV Electrical One Line & Details
E600 Electrical Schedules
E601 Electrical Schedules
E700 Electrical Details
E701 Electrical Details
E702 Electrical Details
E703 Electrical Details
F.F. 898.00
S
S
W
W W
ST
ST
WW
BLDG 217
BLDG 217A
BLDG 218
BLDG 400
BLDG 420
W
MUSTANG DRIVE
MUSTANG DRIVE
T H
S T R E E T
ST
W
BLDG 223
BLDG 220
BLDG 241
BLDG 242
BLDG 243
B L D
G
B L D
G
BLDG 244
BLDG 245
BLDG 246
F.F. 898.00
S
S
W
W W
ST
ST
WW
X
COVER
SHEET INDEX
SITE PLAN
SITE SECURITY PLAN
SITE PLAN
Scale: 1" = 100'-0"
A14
A090
ABI-1: BUILDINGS TO BE
DEMOLISHED - SEE CIVIL
A14
A100
ABI-1: BUILDING TO BE
DEMOLISHED - SEE CIVIL & ELEC
ABI-7: OLD MAIN GATE ROAD TO
BE DEMOLISHED - SEE CIVIL
SITE SECURITY PLAN
Scale: 1" = 50'-0"
CONTRACTOR PARKING
PRIMARY AREA OF WORK
SECURE MATERIALS
STORAGE
FIRST BAY OF EXISTING
ARCHITECTURAL FENCE TO
BE DEMOLISHED - SEE CIVIL
FOR EXTENTS
EXISTING CHAIN LINK FENCE
TO BE DEMOLISHED - SEE
CIVIL FOR EXTENTS
ROPE BARRIER BY OWNER
CONTRACTOR TRAILER
OPTION
SECURITY
SHACK
WALK THROUGH GATE
CONTRACTOR ENTRANCE
TEMPORARY SECURITY FENCE
ABI-1: PARTIAL BUILDING
410 DEMOLITION
Date
Drawing Title
March 19, 2021 1431-14
Consolidated RPA
Operations Facility
Project No. KKGA 169022
Fargo, North Dakota
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
I J
J K
Shultz & Associates
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
GENERAL NOTES
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
Registration # 2580Date: March 19, 2021
I hereby certify that this architectural document was prepared by me or under my direct supervision and that I am a duly registered Architect under the laws of the State of
North Dakota.
Jared M. Jensen
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BM#1
AutoCAD SHX Text
MUSTANG DRIVE
AutoCAD SHX Text
14TH STREET
AutoCAD SHX Text
LAW ENFORCEMENT CENTER
AutoCAD SHX Text
14TH STREET
AutoCAD SHX Text
STARFIRE AVENUE
AutoCAD SHX Text
PHANTOM DRIVE
AutoCAD SHX Text
EXISTING ELECTRICAL CABINET
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
GRAVEL
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BM#1
AutoCAD SHX Text
14TH STREET
AutoCAD SHX Text
PHANTOM DRIVE
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
PLAN NOTES:
BENCHMARKS:
SCALE: 1 INCH = 40 FEET
40200 80
S
E
N
W
PLAN NOTES:
REMOVE EXISTING CONCRETE PAVEMENT
REMOVE EXISTING CONCRETE CURB & GUTTER
REMOVE EXISTING FENCE
C1.0
ABI NO.1
ABI NO.7
REMOVE EXISTING BUILDING (ABI NO.1)
REMOVE EXISTING CONCRETE PAVEMENT (ABI NO.7)
REMOVE EXISTING ASPHALT PAVEMENT (ABI NO.7)
REMOVE EXISTING CONCRETE CURB & GUTTER (ABI NO.7)
DEMOLITION PLAN
REMOVE EXISTING CONCRETE PAVEMENT (ABI NO.1)
1. ALL WORK SHALL COMPLY WITH THE MOST RECENT CITY OF FARGO
STANDARD SPECIFICATIONS FOR CONSTRUCTION OF PUBLIC
UTILITIES.
2. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES FOR UNDERGROUND
LOCATIONS 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
NORTH DAKOTA ONE CALL PHONE NUMBER: 1-800-795-0555
3. CONTRACTOR SHALL CONTACT NDANG BASE WORK CONTROL OFFICE
AT 701-451-2860 PRIOR TO BEGINNING CONSTRUCTION.
4. CONTRACTOR SHALL PROTECT ALL PROPERTY PINS. PROPERTY PINS
DESTROYED OR DISTURBED SHALL BE REPLACED AT CONTRACTORS
EXPENSE.
5. CONTRACTOR SHALL OBTAIN A STORM WATER POLLUTION PERMIT
SHALL BE ACQUIRED BY THE CONTRACTOR AND OWNER FROM THE
NORTH DAKOTA STATE HEALTH DEPARTMENT SEVEN (7) DAYS PRIOR
TO CONSTRUCTION.
6. CONTRACTOR SHALL MAINTAIN TEMPORARY EROSION CONTROL UNTIL
PERMANENT EROSION CONTROL IS ESTABLISHED.
7. ALL PAVEMENT MARKED FOR DEMOLITION SHALL BE FULL DEPTH
SAW CUT PRIOR TO REMOVAL.
8. ALL GRASSED AREAS DISTURBED BY CONSTRUCTION SHALL BE
TOPSOILED (6" DEPTH), GRADED, SEEDED, AND HYDRO-MULCHED.
9. ALL EXTERIOR VAULTS AND MANHOLES MUST BE LOCKABLE.
10. CONTRACTOR SHALL SWEEP/VAC ALL PAVED AREAS PRIOR TO
INSTALLING PAVEMENT MARKINGS.
11. FENCING SHALL BE 7' W/ 6 STRAND BARBED WIRE W/ CONCRETE
MOW STRIP. GROUND EVERY 500'
EXISTING STORM INLET
EXISTING MANHOLE
EXISTING FIRE HYDRANT
EXISTING GATE VALVE
EXISTING LIGHT POLE
EXISTING TREE
EXISTING FENCE
EXISTING SANITARY SEWER LINE
EXISTING STORM SEWER LINE
REMOVE EXISTING GAS LINE (ABI NO.8)
(COORDINATE W/ UTILITY PROVIDER)
EXISTING TELEPHONE RISER
EXISTING SIGN
EXISTING UNDERGROUND ELECTRIC LINE
EXISTING UNDERGROUND FIBER OPTIC LINE
BM: TOP NUT OF HYDRANT
ELEV: 899.32 (NAVD 1988)
REMOVE EXISTING STORM INLET
REMOVE EXISTING FIRE HYDRANT
SALVAGE & REINSTALL EXISTING TREE
(FINAL LOCATION DETERMINED BY OWNER)
REMOVE EXISTING STORM SEWER LINE
RELOCATE EXISTING UNDERGROUND ELECTRIC LINE
REMOVE EXISTING UNDERGROUND FIBER OPTIC LINE
EXISTING ELECTRICAL PLUG IN
REMOVE EXISTING LIGHT POLE
REMOVE EXISTING TELEPHONE RISER
REMOVE EXISTING ELECTRICAL PLUG IN
S T
W W
W W
W W
S S
S S
ST
ST
ST
ST
W W
SF
S T
S T
S T
SF
SF
SF
50'x30'
CONSTRUCTION
ENTRANCE CONCRETE
WASHOUT
AREA
BR
ST MH #1 (60") W/
SOLID COVER
RIM 897.15
INV SW 894.74 (12" HDPE)
INV N 891.31 (24" RCP)
INV E 891.31± (24" RCP)
216LF-24" CL III
RCP ST @ 0.35%
ST MH #3 (60") W/
SOLID COVER
RIM 897.20
INV S 890.90 (24" RCP)
INV W 890.90 (24" RCP)ST MH #4 (60") W/
SOLID COVER
RIM 896.30
INV S 890.14 (24" RCP)
INV W 890.14 (24" RCP)
ST INLET #5 (27")
RIM 895.10
INV 893.00 (10" PVC)
FF 898.00
X X
X X
X
X
X X
X
CONNECT TO EXISTING
ST INLET
INV N 892.32 (10" PVC)
INV S 892.32 (10" PVC)
SF
ST MH #8 (48") W/ INLET
CASTING & GRATE
RIM 895.30
INV N/S 893.38± (12" RCP)
S
143LF-10" SDR35
PVC ST @ 0.48%
T
G
C
ST
ST
ST
S T
S T
ST
ST
84LF-24" CLIII RCP ST @ 0.35%
30LF-24" CLIII RCP ST @ 0.35%
ST MH #2 (48") W/
SOLID COVER
RIM 897.50
INV W 893.37 (12" HDPE)
INV S 891.01 (24" RCP)
INV N 891.01 (24" RCP)
ST
X X
X X
X
S
ST
ST
ST
ST
ST
42LF-24" CL III
RCP ST @ 0.35%
ST
ST
24" RCP FES W/
TRASH GUARD
INV 889.00
12"-90° BEND
11LF-12" HDPE
ST @ 1.0%
INV 894.89
PVC INLETS (14)
RIM 898.00
INV 895.00
26LF-12" HDPE ST @ 1.0%
12"x12" TEE
11LF-12" HDPE
ST @ 1.0%
0.45'-12" RISER
TOP INV 894.89
BTM INV 894.44
152LF-12" HDPE ST
@ 1.0%
12"x12" TEE
11LF-12" HDPE
ST @ 1.0%
0.90'-12" RISER
TOP INV 894.89
BTM INV 893.99
12"x12" TEE
11LF-12" HDPE
ST @ 1.0%
1.35'-12" RISER
TOP INV 894.89
BTM INV 893.54
CONNECT TO EXISTING ST MH
INV S 890.32 (12" HDPE)
INV NW 888.84 (24" RCP)
47LF-24" CL III
RCP ST @ 0.35%
37LF-12" HDPE
ST @ 1.0%
65LF-12" HDPE
ST @ 1.0%
ST MH #5 (48") W/
SOLID COVER
RIM 897.50
INV E 890.69 (12" HDPE)
INV N 890.69 (12" HDPE)
ST MH #6 (48") W/
SOLID COVER
RIM 897.20
INV N 894.85 (12" HDPE)
INV NE 894.52 (12" HDPE)
INV E 891.34 (12" HDPE)
INV W 891.34 (12" HDPE)
15LF-12" HDPE
ST @ 1.0%
12"-90° BEND
36LF-12" HDPE ST @ 1.0%
INV 891.70
48LF-12" HDPE
ST @ 1.0%
12" HDPE ST INV 891.84
4"/6" PVC WM T.O.P. 889.00
12" HDPE ST INV 891.22
6" PVC WM T.O.P. 889.00
12"x12" TEE
10LF-12" HDPE ST @ 1.0%
2.34'-12" RISER
TOP INV 894.90
BTM INV 892.56
12"-90° BEND
20LF-12" HDPE ST @ 1.0%
2.00'-12" RISER
TOP INV 894.80
BTM INV 892.80
110LF-12" HDPE
ST @ 1.0%
ST MH #7 (48") W/
SOLID COVER
RIM 897.60
INV W 894.13 (12" HDPE)
INV N 894.13 (12" HDPE)
12"-45° BEND
14LF-12" HDPE
ST @ 1.0%
INV 894.86
12"-90° BEND
25LF-12" HDPE
ST @ 1.0%
INV 894.61
48LF-12" HDPE
ST @ 1.0%
CONNECT TO EXISTING ST INLET
INV S 892.77 (12" HDPE)
12" HDPE ST INV 893.65
6" PVC SAN T.O.P. 892.50
(INSTALL 2" POLYSTYRE
INSULATION BETWEEN PIPES)
107LF-12" HDPE
ST @ 1.27%
12"x12" TEE
10LF-12" HDPE ST @ 1.0%
0.27'-12" RISER
TOP INV 894.90
BTM INV 894.63 12"x12" TEE
10LF-12" HDPE ST @ 1.0%
0.63'-12" RISER
TOP INV 894.90
BTM INV 894.27
12"x12" TEE
15LF-12" HDPE
ST @ 1.0%
1.48'-12" RISER
TOP INV 894.85
BTM INV 893.37
24" RCP ST INV 890.33
6" PVC WM T.O.P. 888.50
(INSTALL 2" POLYSTYRENE
INSULATION BETWEEN PIPES)
M
M
4" PVC ST
INV 892.02
(COORD. W/ MECH.)
NOTE:
EROSION CONTROL BLANKET
SHALL BE APPLIED TO
SLOPES STEEPER THAN 6:1
24" RCP FES W/ TRASH GUARD
INV 890.00
INSTALL NEW RIP-RAP
(SEE DETAIL 20/C6.0)
E
M
ST
12"x12" TEE
10LF-12" HDPE ST @ 1.0%
2.85'-12" RISER
TOP INV 894.90
BTM INV 892.05
12"x4" SEWER WYE
10LF-4" SDR35 PVC ST @ 1.0%
INV 891.92
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
PLAN NOTES:
SCALE: 1 INCH = 40 FEET
40200 80
S
E
N
W
PLAN NOTES:
NEW WATERMAIN LINE
NEW SANITARY SEWER LINE
NEW STORM SEWER LINE
NEW STORM MANHOLE
NEW STORM INLET
NEW FIRE HYDRANT
NEW GATE VALVE
NEW SANITARY MANHOLE
ST
ST
S
W
W
W
S
ST
NEW FENCEX
NEW INLET PROTECTION
SF
NEW CONSTRUCTION ENTRANCE
NEW BIOROLL
BR
C2.0
EROSION CONTROL /
STORM SEWER PLAN
BENCHMARKS:
BM: TOP NUT OF HYDRANT
ELEV: 899.32 (NAVD 1988)
1. ALL WORK SHALL COMPLY WITH THE MOST RECENT CITY OF FARGO
STANDARD SPECIFICATIONS FOR CONSTRUCTION OF PUBLIC
UTILITIES.
2. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES FOR UNDERGROUND
LOCATIONS 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
NORTH DAKOTA ONE CALL PHONE NUMBER: 1-800-795-0555
3. CONTRACTOR SHALL CONTACT NDANG BASE WORK CONTROL OFFICE
AT 701-451-2860 PRIOR TO BEGINNING CONSTRUCTION.
4. CONTRACTOR SHALL PROTECT ALL PROPERTY PINS. PROPERTY PINS
DESTROYED OR DISTURBED SHALL BE REPLACED AT CONTRACTORS
EXPENSE.
5. CONTRACTOR SHALL OBTAIN A STORM WATER POLLUTION PERMIT
SHALL BE ACQUIRED BY THE CONTRACTOR AND OWNER FROM THE
NORTH DAKOTA STATE HEALTH DEPARTMENT SEVEN (7) DAYS PRIOR
TO CONSTRUCTION.
6. CONTRACTOR SHALL MAINTAIN TEMPORARY EROSION CONTROL UNTIL
PERMANENT EROSION CONTROL IS ESTABLISHED.
7. ALL GRASSED AREAS DISTURBED BY CONSTRUCTION SHALL BE
TOPSOILED (6" DEPTH), GRADED, SEEDED, AND HYDRO-MULCHED.
8. ALL EXTERIOR VAULTS AND MANHOLES MUST BE LOCKABLE.
9. CONTRACTOR SHALL SWEEP/VAC ALL PAVED AREAS PRIOR TO
INSTALLING PAVEMENT MARKINGS.
10. FENCING SHALL BE 7' W/ 6 STRAND BARBED WIRE W/ CONCRETE
MOW STRIP. GROUND EVERY 500'
EXISTING STORM INLET
EXISTING MANHOLE
EXISTING FIRE HYDRANT
EXISTING GATE VALVE
EXISTING FENCE
EXISTING SANITARY SEWER LINE
EXISTING STORM SEWER LINE
EXISTING GAS LINE
EXISTING UNDERGROUND ELECTRIC LINE
EXISTING UNDERGROUND FIBER OPTIC LINE
ST NEW PVC STORM INLET
NEW ACCESSIBLE SIGN
EXISTING LIGHT POLE
EXISTING TREE
EXISTING TELEPHONE RISER
EXISTING SIGN
EXISTING ELECTRICAL PLUG IN
896 NEW POND CONTOUR LINE
NEW FLARED END SECTION
NEW RIP RAP
NEW LIGHT POLE (SEE ELEC. PLANS)
T
W W
W W
W W
S S
S S
ST
ST
ST
ST
W W
S T
S T
S T
REINSTALL SALVAGED
FIRE HYDRANT
F.G. 897.00
10LF-6" DR18 C900 PVC WM
CONNECT TO EXISTING 6" PVC WM
6"x6" TEE
6" GATE VALVE W/ POST INDICATOR & BOX
T.O.P. 888.50
301LF-6" DR18
C900 PVC WM
CONNECT TO EXISTING
SAN SEWER
SAN MH #1 (48")
RIM 896.50
INV W 890.83 (8" PVC)
INV N/S 890.83± (24" RCP)
(FIELD VERIFY ELEVATION &
LOCATION)
222LF-8" SDR26
PVC SAN @ 0.4%
SAN MH #2 (48")
RIM 897.30
INV W 891.72 (6" PVC)
INV E 891.72 (8" PVC)
FF 898.00
6"x6" TEE
6" GATE VALVE W/ POST
INDICATOR & BOX
57LF-6" DR18 C900 PVC WM
T.O.P. 889.00
(COORDINATE W/ MECH.)
(PLUG END)
6"x4" TEE
4" GATE VALVE W/ POST
INDICATOR & BOX
57LF-4" DR18 C900 PVC WM
T.O.P. 889.00
(COORDINATE W/ MECH.)
(PLUG END)
X X
X X
X
X
X X
X
S
T
G
C
12" RCP ST INV 892.56
8" PVC SAN T.O.P. 891.84
(INSTALL 2" POLYSTYRENE
INSULATION BETWEEN PIPES)
ST
ST
ST
S T
S T
ST
ST
ST
6" PVC SAN
22LF-6" SDR26
PVC SAN @ 1.0%
INV 891.94
(COORDINATE W/ MECH.)
(PLUG END)
X X
X X
X
S
ST
ST
ST
ST
ST
ST
ST
12" HDPE ST INV 891.84
4"/6" PVC WM T.O.P. 889.00
12" HDPE ST INV 891.22
6" PVC WM T.O.P. 889.00
12" HDPE ST INV 893.65
6" PVC SAN T.O.P. 892.50
(INSTALL 2" POLYSTYRE
INSULATION BETWEEN PIPES)
24" RCP ST INV 890.33
6" PVC WM T.O.P. 888.50
(INSTALL 2" POLYSTYRENE
INSULATION BETWEEN PIPES)
M
M
FIRE HYDRANT
F.G. 897.00
6" GATE VALVE W/
POST INDICATOR & BOX
T.O.P. 889.00
UNDERGROUND MECH. LINES
(SEE MECH.)
UNDERGROUND MECH. LINES
(SEE MECH.)
E
M
ST
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
PLAN NOTES:
SCALE: 1 INCH = 40 FEET
40200 80
S
E
N
W
PLAN NOTES:
NEW WATERMAIN LINE
NEW SANITARY SEWER LINE
NEW STORM SEWER LINE
NEW STORM MANHOLE
NEW STORM INLET
NEW FIRE HYDRANT
NEW GATE VALVE
NEW SANITARY MANHOLE
ST
ST
S
W
W
W
S
ST
NEW FENCEX
C2.1
SANITARY SEWER /
WATERMAIN PLAN
BENCHMARKS:
BM: TOP NUT OF HYDRANT
ELEV: 899.32 (NAVD 1988)
1. ALL WORK SHALL COMPLY WITH THE MOST RECENT CITY OF FARGO
STANDARD SPECIFICATIONS FOR CONSTRUCTION OF PUBLIC
UTILITIES.
2. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES FOR UNDERGROUND
LOCATIONS 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
NORTH DAKOTA ONE CALL PHONE NUMBER: 1-800-795-0555
3. CONTRACTOR SHALL CONTACT NDANG BASE WORK CONTROL OFFICE
AT 701-451-2860 PRIOR TO BEGINNING CONSTRUCTION.
4. CONTRACTOR SHALL PROTECT ALL PROPERTY PINS. PROPERTY PINS
DESTROYED OR DISTURBED SHALL BE REPLACED AT CONTRACTORS
EXPENSE.
5. CONTRACTOR SHALL OBTAIN A STORM WATER POLLUTION PERMIT
SHALL BE ACQUIRED BY THE CONTRACTOR AND OWNER FROM THE
NORTH DAKOTA STATE HEALTH DEPARTMENT SEVEN (7) DAYS PRIOR
TO CONSTRUCTION.
6. CONTRACTOR SHALL MAINTAIN TEMPORARY EROSION CONTROL UNTIL
PERMANENT EROSION CONTROL IS ESTABLISHED.
7. ALL GRASSED AREAS DISTURBED BY CONSTRUCTION SHALL BE
TOPSOILED (6" DEPTH), GRADED, SEEDED, AND HYDRO-MULCHED.
8. ALL EXTERIOR VAULTS AND MANHOLES MUST BE LOCKABLE.
9. CONTRACTOR SHALL SWEEP/VAC ALL PAVED AREAS PRIOR TO
INSTALLING PAVEMENT MARKINGS.
10. FENCING SHALL BE 7' W/ 6 STRAND BARBED WIRE W/ CONCRETE
MOW STRIP. GROUND EVERY 500'
EXISTING STORM INLET
EXISTING MANHOLE
EXISTING FIRE HYDRANT
EXISTING GATE VALVE
EXISTING FENCE
EXISTING SANITARY SEWER LINE
EXISTING STORM SEWER LINE
EXISTING GAS LINE
EXISTING UNDERGROUND ELECTRIC LINE
EXISTING UNDERGROUND FIBER OPTIC LINE
ST NEW PVC STORM INLET
NEW ACCESSIBLE SIGN
EXISTING LIGHT POLE
EXISTING TREE
EXISTING TELEPHONE RISER
EXISTING SIGN
EXISTING ELECTRICAL PLUG IN
NEW FLARED END SECTION
896 NEW POND CONTOUR LINE
NEW RIP RAP
FF 898.00
X X
X X
X
X
X X
X
S
T
G
CONTRACTOR TO MATCH
EXISTING GRADES
C
X X
X X
X
S
ME
ME
ME
ST
ST
ST
ST
ST
ST
ST
M
M
CONCRETE PADS
898.00
CONCRETE PAD 897.50
E
0.41%
0.65%
0.60%
0.92% 0.8%
M
ST
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
PLAN NOTES:
SCALE: 1 INCH = 40 FEET
40200 80
S
E
N
W
PLAN NOTES:
NEW GATE VALVEW
NEW FENCEX
EXISTING SPOT ELEVATION
EXISTING CONTOUR LINE
NEW RIM ELEVATION
NEW INVERT ELEVATION
NEW SIDEWALK ELEVATION
MATCH EXISTING ELEVATION
897.50RIM
890.00INV
896.95SW
895.77ME
NEW TOP OF PAVMENT ELEVATION
NEW GUTTER ELEVATION
NEW TOP OF CURB ELEVATION
897.44TP
895.70G
896.05TC
896 NEW POND CONTOUR LINE
C3.0
GRADING PLAN
EXISTING STORM INLET
EXISTING MANHOLE
EXISTING FIRE HYDRANT
EXISTING GATE VALVE
EXISTING FENCE
BENCHMARKS:
BM: TOP NUT OF HYDRANT
ELEV: 899.32 (NAVD 1988)
1. ALL WORK SHALL COMPLY WITH THE MOST RECENT CITY OF FARGO
STANDARD SPECIFICATIONS FOR CONSTRUCTION OF PUBLIC
UTILITIES.
2. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES FOR UNDERGROUND
LOCATIONS 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
NORTH DAKOTA ONE CALL PHONE NUMBER: 1-800-795-0555
3. CONTRACTOR SHALL CONTACT NDANG BASE WORK CONTROL OFFICE
AT 701-451-2860 PRIOR TO BEGINNING CONSTRUCTION.
4. CONTRACTOR SHALL PROTECT ALL PROPERTY PINS. PROPERTY PINS
DESTROYED OR DISTURBED SHALL BE REPLACED AT CONTRACTORS
EXPENSE.
5. CONTRACTOR SHALL OBTAIN A STORM WATER POLLUTION PERMIT
SHALL BE ACQUIRED BY THE CONTRACTOR AND OWNER FROM THE
NORTH DAKOTA STATE HEALTH DEPARTMENT SEVEN (7) DAYS PRIOR
TO CONSTRUCTION.
6. CONTRACTOR SHALL MAINTAIN TEMPORARY EROSION CONTROL UNTIL
PERMANENT EROSION CONTROL IS ESTABLISHED.
7. ALL GRASSED AREAS DISTURBED BY CONSTRUCTION SHALL BE
TOPSOILED (6" DEPTH), GRADED, SEEDED, AND HYDRO-MULCHED.
8. ALL EXTERIOR VAULTS AND MANHOLES MUST BE LOCKABLE.
9. CONTRACTOR SHALL SWEEP/VAC ALL PAVED AREAS PRIOR TO
INSTALLING PAVEMENT MARKINGS.
10. FENCING SHALL BE 7' W/ 6 STRAND BARBED WIRE W/ CONCRETE
MOW STRIP. GROUND EVERY 500'
NEW STORM MANHOLE
NEW STORM INLET
NEW FIRE HYDRANT
NEW SANITARY MANHOLE
ST
ST
S
W
ST NEW PVC STORM INLET
NEW ACCESSIBLE SIGN
EXISTING LIGHT POLE
EXISTING TREE
EXISTING TELEPHONE RISER
EXISTING SIGN
EXISTING ELECTRICAL PLUG IN
NEW FLARED END SECTION
NEW SLOPE & DIRECTION OF FLOW
1.0%
6.0'
X X
X X
X
INSTALL 368LF-7' HIGH
CHAINLINK FENCE W/ 6
STRAND BARBED WIRE & 2'
WIDE CONCRETE MOW STRIP
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
INSTALL 259LF-7' HIGH
CHAINLINK FENCE W/ 6
STRAND BARBED WIRE & 2'
WIDE CONCRETE MOW STRIP
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
10@9.0'=90.0'
18.0' 18.0'27.0'18.0'
27.0' 18.0'
17@9.0'=153.0'
18.0' 27.0' 18.0' 18.0' 27.0' 18.0' 18.0'
27.0'
R5 .0
R5 .0
R5.0'
R3 .0
R5.0'
6.0'
X
X X
INSTALL 99LF-7' HIGH
CHAINLINK FENCE W/ 6
STRAND BARBED WIRE & 2'
WIDE CONCRETE MOW STRIP
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
X
18.0'
PROVIDE 7' HIGH / 6'
WIDE SWING GATE W/ 6
STRAND BARBED WIRE
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
33.0' UNOBSTRUCTE
D
ZONE
S
PROVIDE 7' HIGH / 6'
WIDE SWING GATE W/ 6
STRAND BARBED WIRE
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
PROVIDE 7' HIGH / 6'
WIDE SWING GATE W/ 6
STRAND BARBED WIRE
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
PROVIDE 7' HIGH / 6'
WIDE SWING GATE W/ 6
STRAND BARBED WIRE
@ BASE BID, SEE ARCH
FOR FENCE @ ABI-5
T
G
C
6.0'
6.0'
INSTALL 9LF DROP CURB
SECTION W/ 6' FLARES
INSTALL TWO (2) NEW
ACCESSIBLE SIGNS
X X
X X
X
S
ST
ST
ST
ST
ST
ST
ST
R1 5.
0'
R
M
M
NEW MECHANICAL EQUIPMENT
PAD ELEV 897.50
NEW CHILLER
PAD ELEV 898.00
NEW GENERATOR
PAD ELEV 898.00
NEW TRANSFORMER
PAD ELEV 898.00
E
6.0'
6.0'
R5.0'
R5 .0
6.0'
M
NEW MECH. EQUIPMENT
(SEE MECH.)
NEW 46LF-9' HIGH
CHAINLINK FENCE W/
CHAINLINK COVER
(SEE DETAIL 24/C6.1)
PROVIDE 4' WIDE GATE
(SEE DETAIL 23/C6.1)
PROVIDE 10' WIDE
DOUBLE SWING GATE
(SEE DETAIL 25/C6.1)
TRASH ENCLOSURE
SEE L101 @ ABI-10
R5.0'
R5 .0
26.0'
6.0'
ST
INSTALL 22LF-7' HIGH
CHAINLINK FENCE W/ 6
STRAND BARBED WIRE & 2'
WIDE CONCRETE MOW STRIP
NOTE:
PROTECT EXISTING F-4
JET DURING CONSTRUCTION
X
INSTALL 23LF-7' HIGH
CHAINLINK FENCE W/ 6
STRAND BARBED WIRE & 2'
WIDE CONCRETE MOW STRIP
NOTE:
PROTECT EXISTING F-4
JET DURING CONSTRUCTION
INSTALL 23LF-7' HIGH
CHAINLINK FENCE W/ 6
STRAND BARBED WIRE & 2'
WIDE CONCRETE MOW STRIP
X X
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
PLAN NOTES:
SCALE: 1 INCH = 40 FEET
40200 80
S
E
N
W
PLAN NOTES:
NEW GATE VALVEW
NEW FENCEX
NEW 4" REINFORCED CONCRETE SIDEWALK
NEW 8" REINFORCED CONCRETE PAVEMENT
(FIELD VERIFY)
NEW TYPE 1 STANDARD CONCRETE CURB & GUTTER
NEW TYPE 2 STANDARD CONCRETE CURB & GUTTER
NEW 6" NON-REINFORCED CONCRETE PAVEMENT
C4.0
NEW 18" NON-REINFORCED CONCRETE PAVEMENT
(FIELD VERIFY) (ABI NO.1)
ABI NO.1
ABI NO.7
NEW SEEDING AREA (ABI NO.1)
PAVING PLAN
NEW SEEDING AREA (ABI NO.7)
BENCHMARKS:
BM: TOP NUT OF HYDRANT
ELEV: 899.32 (NAVD 1988)
1. ALL WORK SHALL COMPLY WITH THE MOST RECENT CITY OF FARGO
STANDARD SPECIFICATIONS FOR CONSTRUCTION OF PUBLIC
UTILITIES.
2. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES FOR UNDERGROUND
LOCATIONS 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
NORTH DAKOTA ONE CALL PHONE NUMBER: 1-800-795-0555
3. CONTRACTOR SHALL CONTACT NDANG BASE WORK CONTROL OFFICE
AT 701-451-2860 PRIOR TO BEGINNING CONSTRUCTION.
4. CONTRACTOR SHALL PROTECT ALL PROPERTY PINS. PROPERTY PINS
DESTROYED OR DISTURBED SHALL BE REPLACED AT CONTRACTORS
EXPENSE.
5. CONTRACTOR SHALL OBTAIN A STORM WATER POLLUTION PERMIT
SHALL BE ACQUIRED BY THE CONTRACTOR AND OWNER FROM THE
NORTH DAKOTA STATE HEALTH DEPARTMENT SEVEN (7) DAYS PRIOR
TO CONSTRUCTION.
6. CONTRACTOR SHALL MAINTAIN TEMPORARY EROSION CONTROL UNTIL
PERMANENT EROSION CONTROL IS ESTABLISHED.
7. ALL GRASSED AREAS DISTURBED BY CONSTRUCTION SHALL BE
TOPSOILED (6" DEPTH), GRADED, SEEDED, AND HYDRO-MULCHED.
8. ALL EXTERIOR VAULTS AND MANHOLES MUST BE LOCKABLE.
9. CONTRACTOR SHALL SWEEP/VAC ALL PAVED AREAS PRIOR TO
INSTALLING PAVEMENT MARKINGS.
10. FENCING SHALL BE 7' W/ 6 STRAND BARBED WIRE W/ CONCRETE
MOW STRIP. GROUND EVERY 500'
EXISTING STORM INLET
EXISTING MANHOLE
EXISTING FIRE HYDRANT
EXISTING GATE VALVE
EXISTING FENCE
NEW STORM MANHOLE
NEW STORM INLET
NEW FIRE HYDRANT
NEW SANITARY MANHOLE
ST
ST
S
W
ST NEW PVC STORM INLET
NEW ACCESSIBLE SIGN
EXISTING LIGHT POLE
EXISTING TREE
EXISTING TELEPHONE RISER
EXISTING SIGN
EXISTING ELECTRICAL PLUG IN
NEW FLARED END SECTION
NEW 6" REINFORCED CONCRETE PAVEMENT
NEW 6" REINFORCED CONCRETE PAVEMENT (ABI NO.7)
X X
X X
X
C
C
C
H
I
H
C
H
X
X X
X
S
T
G
C
2@9.0' 8@10.9'2@9.0'
I
CCC
H
H
H
H
H
H
H
H
H
2@9.0'
2@9.1' 14@10.0'
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
I
CCCCCCC
X X
X X
X
S
ST
ST
ST
ST
ST
ST
ST
M
M
I
MATCH EXISTING
JOINTING PATTERN
E
MATCH EXISTING
JOINTING PATTERN
CONCRETE SIDEWALK
JOINTING PATTERN
SHALL BE 6'x6'
(TYP.)
CONCRETE SIDEWALK
JOINTING PATTERN
SHALL BE 6'x6'
(TYP.)
M
2@9.2'
I
H
H
H
6@10.8'
ST
H H
2@10.0'
H H H H H
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
PLAN NOTES:
SCALE: 1 INCH = 40 FEET
40200 80
S
E
N
W
PLAN NOTES:
NEW GATE VALVEW
NEW FENCEX
NEW TIED CONSTRUCTION JOINTC
NEW CONSTRUCTION JOINTH
NEW ISOLATION JOINTI
C5.0
JOINTING PLAN
EXISTING STORM INLET
EXISTING MANHOLE
EXISTING FIRE HYDRANT
EXISTING GATE VALVE
EXISTING FENCE
BENCHMARKS:
BM: TOP NUT OF HYDRANT
ELEV: 899.32 (NAVD 1988)
1. ALL WORK SHALL COMPLY WITH THE MOST RECENT CITY OF FARGO
STANDARD SPECIFICATIONS FOR CONSTRUCTION OF PUBLIC
UTILITIES.
2. CONTRACTOR SHALL NOTIFY UTILITY COMPANIES FOR UNDERGROUND
LOCATIONS 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
NORTH DAKOTA ONE CALL PHONE NUMBER: 1-800-795-0555
3. CONTRACTOR SHALL CONTACT NDANG BASE WORK CONTROL OFFICE
AT 701-451-2860 PRIOR TO BEGINNING CONSTRUCTION.
4. CONTRACTOR SHALL PROTECT ALL PROPERTY PINS. PROPERTY PINS
DESTROYED OR DISTURBED SHALL BE REPLACED AT CONTRACTORS
EXPENSE.
5. CONTRACTOR SHALL OBTAIN A STORM WATER POLLUTION PERMIT
SHALL BE ACQUIRED BY THE CONTRACTOR AND OWNER FROM THE
NORTH DAKOTA STATE HEALTH DEPARTMENT SEVEN (7) DAYS PRIOR
TO CONSTRUCTION.
6. CONTRACTOR SHALL MAINTAIN TEMPORARY EROSION CONTROL UNTIL
PERMANENT EROSION CONTROL IS ESTABLISHED.
7. ALL GRASSED AREAS DISTURBED BY CONSTRUCTION SHALL BE
TOPSOILED (6" DEPTH), GRADED, SEEDED, AND HYDRO-MULCHED.
8. ALL EXTERIOR VAULTS AND MANHOLES MUST BE LOCKABLE.
9. CONTRACTOR SHALL SWEEP/VAC ALL PAVED AREAS PRIOR TO
INSTALLING PAVEMENT MARKINGS.
10. FENCING SHALL BE 7' W/ 6 STRAND BARBED WIRE W/ CONCRETE
MOW STRIP. GROUND EVERY 500'
NEW STORM MANHOLE
NEW STORM INLET
NEW FIRE HYDRANT
NEW SANITARY MANHOLE
ST
ST
S
W
ST NEW PVC STORM INLET
NEW ACCESSIBLE SIGN
EXISTING LIGHT POLE
EXISTING TREE
EXISTING TELEPHONE RISER
EXISTING SIGN
EXISTING ELECTRICAL PLUG IN
NEW FLARED END SECTION
NOTE:
PLUG
30°
MAX.
TABLE OF REQUIRED BEARING AREAS
4"
8"
10"
12"
16"
18"
2' SQ.
3' SQ.
5' SQ.
8' SQ.
11' SQ.
20' SQ.
25' SQ. 14' SQ.
11' SQ.
6' SQ.
4' SQ.
3' SQ.
2' SQ.
2' SQ. 2' SQ.
2' SQ.
2' SQ.
3' SQ.
3' SQ.
6' SQ.
7' SQ. 4' SQ.
4' SQ.
2' SQ.
2' SQ.
2' SQ.
2' SQ.
2' SQ. 2' SQ.
3' SQ.
4' SQ.
6' SQ.
8' SQ.
15' SQ.
18' SQ.
SIZE OF
PIPE
90° BEND 45° BEND 22 1/2° 11 1/4° TEE
1 WATER MAIN THRUST BLOCKING DETAIL
C6.0 NOT-TO-SCALE
NOTE:
CONCRETE BLOCKING TO BE POURED AGAINST
UNDISTURBED EARTH. BELLS AND BOLTS TO BE
KEPT FREE OF CONCRETE.
6"
TEE & PLUG BLOCKING SHOWN,
TAPPING SLEEVE BLOCKING
SIMILIAR
NOTE:
ALL FITTINGS TO WRAPPED IN
POLYETHYLENE (8 MIL MIN.)
THRUST
BLOCKNEW WATER
MAIN
CONCRETE BLOCK
(4" x 6" x 12")
THIS BEARING AREA
BASED ON PIPE DIA.
OPPOSITE
THRUST
BLOCK
BEDDING
SAND
CONCRETE BLOCK
(4"x6"x12")
NEW WATER
MAIN
CONCRETE BLOCK
(4" x 6" x 12")
THRUST
BLOCK
48" 5"5"
V A R I E S
27"
4' ECCENTRIC CONE
REQUIRED
NOTE: LIFT HOLES TO BE
MANUFACTURED WATER PROOF
MANHOLE COVER SHALL HAVE
-CONCEALED PICK BAR
-"O" RING GASKET
CASTING FRAME & COVER
NEENAH FOUNDRY CO.
R-1733 OR EAST JORDAN
1205-AGSSA OR APPROVED
EQUAL
BUTYL RUBBER GASKET ON
ALL JOINTS (JOINT TO
MEET ASTM 433
REQUIREMENT)
MANHOLE STEP 12" O.C.
(SEE DETAIL)
3-2" ADJUSTING RINGS
48" DIA. PRECAST
CONCRETE MANHOLE
PRECAST MONOLITHIC
MANHOLE W/ GASKET
ASSEMBLY FOR
8" TO 15" DIA. MAINS
3/4" CRUSHED ROCK
TO BE USED TO
SUPPORT PIPE IN
OVEREXCAVATED AREA
14-20 MILS OF COAL TAR
EPOXY OR APPROVED EQUAL
ON BOTTOM SECTION OF
MANHOLEV
A R I E S
T O
6 SANITARY SEWER MANHOLE (48") DETAIL
C6.0 NOT-TO-SCALE
REBAR
MANHOLE
STEP
INTERIOR WALL
OF MANHOLE
INTERIOR WALL
OF MANHOLE
MANHOLE
STEP
NOTE:
STEP SHALL BE CONSTRUCTED OF 1/2" REINFORCING ROD AND COMPLETELY ENCASED
IN A CORROSION RESISTANT RUBBER OR POLYPROPYLENE PLASTIC, WHICH WILL
RESIST DETERIORATION FROM HYDROGEN SULFIDE OR OTHER CHEMICALS AND GASES
ENCOUNTERED IN MANHOLE APPLICATION. ALSO, STEP SHALL HAVE A VERTICAL
RESISTANCE OF 400 LBS., AND A PULLOUT RESISTANCE OF 1000 LBS. SUCH AS:
THE WEDG-LOC STEP BY DELTA PIPE PRODUCTS OR APPROVED EQUAL.
11 MANHOLE STEP DETAIL
C6.0 NOT-TO-SCALE
INLET GRATE
INLET FRAME
LIFT STRAPS
OVERFLOW HOLES
LIFT STRAPS
C O N T A I N M E N T
A R E A
REINFORCED CORNERS
MAINTENANCE:
INSTALLATION:
17 INLET PROTECTION DETAIL
C6.0 NOT-TO-SCALE
• REMOVE THE INLET GRATE.
• STAND THE GRATE UPRIGHT. INSTALL THE GRATE BETWEEN
THE LIFT STRAPS.
• PLACE THE BAG IN THE INLET & LOWER THE BAG AND
GRATE USING THE LIFT STRAPS.
• CHECK BAG REGULARLY & AFTER RAIN EVENTS. IF
THE BAG IS FILLED WITH 1/3 OF ITS CAPACITY WITH
SEDIMENT, EMPTY THE BAG.
• REMOVE DEBRIS AROUND THE INLET GRATE PRIOR TO
REMOVING BAG.
• USE THE LIFT HANDLES TO REMOVE THE BAG AND USE
THE HANDLES ON THE BOTTOM TO EMPTY BAG.
15 SILT FENCE DETAIL
C6.0 NOT-TO-SCALE
T P O S T
STANDARD MACHINE SLICED
DIRECTION OF FLOW
M I N
BACKFILLED TRENCH
5.0' POSTS @ 6.0' MAX
SPACING. MAY BE
ALTERNATED ON GRADES LESS
THAN 2.0%
PLASTIC ZIP TIES
(50 LB. TENSILE)
LOCATED IN TOP 8" POST LENGTH, 5 FT. MIN.
AT 6 FT. MAX. SPACING
GEOTEXTILE FABRIC, 36" WIDTHDIRECTION OF
RUNOFF FLOW
M I N
P O S T
E M B E D M E N T
MACHINE SLICE
8"-12" DEPTH (PLUS
6" FLAP)
D
A G G R E G A T E
B E D D I N G
D
1'
MIN.
1'
MIN.
A G G R E G A T E
B E D D I N G
D
D
SUBGRADE
SUBGRADE
1'
MIN.
1'
MIN.
12 AGGREGATE BEDDING DETAIL
C6.0 NOT-TO-SCALE
INITIAL COMPACTION AT
MIDPOINT OF PIPE WITH
MECHANICAL TAMPER.
SLOPE AS REQUIRED
BY OSHA
INITIAL COMPACTION AT
MIDPOINT OF PIPE WITH
MECHANICAL TAMPER.
SLOPE AS REQUIRED
BY OSHA
PVC, PE, & CS PIPE
RC PIPE
'A''B' 'B'
'C'
SEAL VOID AROUND PIPE
WITH CONCRETE
MANHOLE FRAME
& COVER
3-2" ADJUSTING
RINGS
MANHOLE STEPS
(SEE DETAIL)
CONCRETE
SHELF
PRECAST CONCRETE
MANHOLE - 'A' DIAMETER
NOTE:
MANHOLE CASTING FRAME AND COVER
SHALL BE NEENAH FOUNDRY CO. R-1733
OR EAST JORDAN 1205-AGSSA OR
APPROVED EQUAL
NOTE:
ALL JOINTS AND LIFTING HOLES TO BE
MORTARED
PRECAST CONCRETE BASE - 'D' THICKNESS x
'F' DIAMETER (NO. 4 BARS, 12" O.C.
E.W., SINGLE MAT FOR 8" SLAB AND DOUBLE
MAT FOR 12" SLAB)
1 1/4" CRUSHED ROCK IN
OVER-EXCAVATED AREAS
NOTE:
BUTYL RUBBER GASKET ON
ALL JOINTS (JOINT TO MEET
ASTM 433 REQUIREMENT)
8 STORM MANHOLE (48" - 120") DETAIL
C6.0 NOT-TO-SCALE
NOTE:
PVC CONNECTIONS TO STORM MANHOLES
AND INLETS SHALL BE MADE WITH GPK
MANHOLE ADAPTER OR APPROVED EQUAL.
DIMENSION TABLE
A
27"6"60"
72" 7" 27"
B C
84" 8" 27"
96" 9" 27"
108" 10" 27"
120" 11" 27"
D
8"
8"
8"
8"
12"
12"
'D'
'D'
27"5"48" 8"
PRECAST CONCRETE
COVER 'D' THICKNESS
x 'E' DIAMETER
E
72"
86"
100"
114"
128"
142"
58"
F
78"
92"
106"
120"
140"
154"
64"
NOTE:
IF INLET CASTING & GRATE IS
REQUIRED: NEENAH R-3405 OR
APPROVED EQUAL
NOTE:
HDPE CONNECTIONS TO STORM MANHOLES
AND INLETS SHALL BE MADE WITH
PRESS SEAL GASKET CORP. WATERSTOP
OR APPROVED EQUAL.
4" MAX
12" MIN
4" MAX
12" MIN
ROPE TIE
ROPE TIE
FIBER ROLL
16 BIOROLL DETAIL
C6.0 NOT-TO-SCALE
SLOPE VARIES
2" X 2"
WOOD STAKES WOOD
STAKES
FIBER ROLL
9" MINSLOPE
VARIES
2" X 2" WOOD
STAKES OR PINS MAX
4.0' SPACING
4.
0' M
AX
FIBER ROLLS
4.
0' M
AX
4.
0' M
AX
4.
0' M
AX
NOTE:
VERTICAL SPACING
MEASURED ALONG THE
FACE OF THE SLOPE
VARIES BETWEEN
10.0 FT & 100.0 FT
INSTALL FIBER ROLL
ALONG A LEVEL CONTOUR
INSTALL A FIBER ROLL NEAR
SLOPE WHERE IT TRANSITIONS
INTO A STEEPER SLOPE
FIBER ROLL 9" MIN
18" MIN.
5 HYDRANT MARKER DETAIL
C6.0 NOT-TO-SCALE
2 LB./FT. "U" CHANNEL
(MINIMUM)
ENGINEERING GRADE
REFLECTIVE SHEETING
(4"X7"X 0.063" ALUMINUM)
RED HYDRANT SYMBOL
W/WHITE BACKGROUND
TWO SIGNS (MOUNTED
BACK TO BACK)
C O V E R
M I N
2"
4 WATEROUS HYDRANT DETAIL
C6.0 NOT-TO-SCALE
6" TEE
HYDRANT
LEAD PIPE
WATEROUS FIRE
HYDRANT
1/2"
PLYWOOD
BEARING
SUFACE
CONCRETE
BLOCK
DRAINAGE
ROCK
6" GATE
VALVE
WATEROUS FIRE
HYDRANT
2 1/2" HOSE CONNECTION
(NATIONAL STANDARD THREADS)
4 1/2" PUMPER NOZZLE
(NATIONAL STANDARD THREADS)
GROUND LINE16" TRAFFIC FLANGE
BREAK-OFF SECTION
DRAINAGE
ROCK
CONCRETE
BLOCK
HYDRANT
LEAD PIPE
6" GATE
VALVE
HYDRANT
LEAD
PIPE
6" TEE
1/2" PLYWOOD
BEARING SURFACE
NOTE:
OPERATING & CAP NUTS:
CITY OF FARGO STANDARDS
BOLTS BELOW GROUND TO BE
STAINLESS STEEL
24' (M
IN.
50' (MIN.)
NOTE:
14 CONSTRUCTION ENTRANCE DETAIL
C6.0 NOT-TO-SCALE
NOTES:
1. A TEMPORARY CONSTRUCTION ENTRANCE SHALL BE CONSTRUCTED AT ALL LOCATIONS
WHERE CONSTRUCTION VEHICLES OR EQUIPMENT ENTER OR EXIT THE CONSTRUCTION
SITES THAT ARE OVER 5 ACRES AND MAY BE REQUIRED BETWEEN 1 AND 5 ACRES AS
DIRECTED BY THE ENGINEER.
2.UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL REMOVE THE TEMPORARY
CONSTRUCTION ENTRANCE UNLESS NOTED OTHERWISE, AND THE SITE SHALL BE
RESTORED TO IT'S PREVIOUS CONDITION.
3.ENTRANCES SHALL BE MAINTAINED IN A MANNER TO MINIMIZE THE TRACKING OF
SEDIMENT ONTO PAVED SURFACES.
4.THE LOCATION OF TEMPORARY ENTRANCES SHALL BE AS SHOWN ON THE PLANS. IF NOT
SHOWN ON THE PLANS, THE CONTRACTOR SHALL COORDINATE THE LOCATIONS WITH THE
ENGINEER.
TEMPORARY CONSTRUCTION ENTRANCE
TO BE 6" (MIN. DEPTH) OF 1" TO 2"
CRUSHED ROCK, CRUSHED CONCRETE
OR WOOD MATERIAL (5" OR LESS
PARTICLE SIZE) ON TOP OF
ENGINEERING FABRIC
RADIUS AS
REQUIRED
TEMPORARY ROCK
CONSTRUCTION ENTRANCE
EXISTING PAVED
ROAD
TEMPORARY ACCESS OVER
CURB & GUTTER
TEMPORARY ACCESS OVER EXISTING CURB &
GUTTER SHOULD BE LOCATED AT HIGH
POINTS IN THE STREET (IF POSSIBLE) TO
MAINTAIN STREET DRAINAGE
CONSTRUCT TEMPORARY RAMP
USING CRUSHED CONCRETE OR
RECYCLED ASPHALT (CLAY SHALL
NOT BE ALLOWED)
PVC PIPE
IF NEEDED
ENGINEERING
FABRIC
6" MIN.
2" TO 12" DIA. 14" TO 36" DIA.
RESTRAINER
SERRATIONSPIPE PIPE SERRATIONS
RESTRAINER
PVC PIPE
GATE VALVE
TEE
PVC PIPE
TYPICAL INSTALLATIONS
L
L
6"
8"
10"
12"
16"
19'
25'
31'
36'
47'
8'
11'
13'
15'
20'
4'
5'
6'
8'
10'
2'
3'
3'
4'
5'
2'
13'
23'
33'
52'
35'
45'
55'
65'
84'
6"
8"
10"
12"
16"
SIZE
15'/8'
19'/11'
23'/13'
27'/15'
35'/20'
7'/4'
9'/5'
11'/6'
13'/8'
17'/10'
RESTRAINED LENGTHS OF PVC PIPE
2 RESTRAINT DEVICE FOR PVC PIPE BELL JOINTS DETAIL
C6.0 NOT-TO-SCALE
22 1/2° VERT.
OFFSET* (L)
• RESTRAINING DEVICES SHALL MEET OR
EXCEED THE REQUIREMENTS OF ASTM F 1694
• APPROVED TYPES ARE UNIFLANGE
PVC PIPE RESTRAINTS & EEBA
IRON SERIES 2000 PV
• ALL METAL FITTINGS AND RESTRAINING
DEVICES TO BE WRAPPED IN POLYETHLENE
PLASTIC (8 MIL MIN.)
* RECOMMENDED RESTRAINED LENGTHS FOR TEES ARE FOR THE
BRANCH OUTLET AND ASSUME A MINIMUM 10 FT. SECTION OF
PIPE ATTACHED TO EACH SIDE OF THE RUN. RESTRAINT DEVICES
ARE ALSO REQUIRED ON BOTH RUN JOINTS OF THE TEE ITSELF.
* FIRST NUMBER IS THE RECOMMENDED RESTRAINED LENGTH ON
EACH SIDE OF THE DOWN BEND, THE SECOND NUMBER IS THE
LENGTH FOR EACH SIDE OF THE UP BEND.
NOTE:
ADDITIONAL LENGTH OF PIPE TO
BE RESTRAINED ON EACH SIDE
OF ANY RESTRAINED FITTINGS
(SEE TABLE)
RESTRAINING
ROD
RESTRAINING
ROD
HYDRANT
RISER
45° VERT. OFFSET*
(L)
VALVE/
DEAD-
END(L)
SIZE ON
SIZE
TEE(L)*
11.25°
BEND
(L)
22.5°
BEND
(L)
45°
BEND
(L)
90°
BEND
(L)
NOM.
PIPE
SIZE
HYDRANT
LEAD PIPE
FIRE
HYDRANT
1/2"
PLYWOOD
BEARING
SUFACE
CONCRETE
BLOCK DRAINAGE
ROCK
RESTRAINED JOINT
W/STAINLESS STEEL BOLTS
6" GATE
VALVE
6" TEE
C O V E R
M I N
FIRE HYDRANT
3 RESTRAINED MECHANICAL JOINT DETAIL
C6.0 NOT-TO-SCALE
NOTE:
OPERATING & CAP NUTS: CITY
OF FARGO STANDARDS BOLTS
BELOW GROUND TO BE
STAINLESS STEEL
2 1/2" HOSE CONNECTION
(NATIONAL STANDARD THREADS)
4 1/2" PUMPER NOZZLE
(NATIONAL STANDARD THREADS)
16" TRAFFIC FLANGE
BREAK-OFF SECTION
GROUND
LINE
6" GATE
VALVE HYDRANT
LEAD PIPE 6" TEE
RESTRAINED JOINT
W/STAINLESS
STEEL BOLTS
HYDRANT
LEAD PIPE
CONCRETE
BLOCK
DRAINAGE
ROCK
LOWER STANDPIPE OF
HYDRANTS SHALL BE WRAPPED
WITH POLYETHLENE
POLYETHYLENE
FILM
LOWER
STANDPIPE
UTILITY LINE
4' WIDE POLYSTYRENE
INSULATION (SEE PLANS
FOR THICKNESS)
UTILITY LINE
13 POLYSTYRENE INSULATION DETAIL
C6.0 NOT-TO-SCALE
V A R I E S
27"
27" DIA. PRECAST CONCRETE BARREL
(REINFORCE SAME AS 27" RCP ASTM
DESIGNATION C76-68)
4" FILLET
AROUND
INTERIOR
3'-3" DIAMETER CONCRETE BASE
(REINFORCE AS PER ASTM C478)
3-2" ADJUSTING
RINGS
INLET CASTING & GRATE
NOTE:
IF MANHOLE CASTING FRAME AND COVER
IS REQUIRED: NEENAH FOUNDRY CO.
R-1733 OR EAST JORDAN 1205-AGSSA
OR APPROVED EQUAL
NOTE:
ALL JOINTS AND LIFTING HOLES TO BE
MORTARED
NOTE:
INLET CASTING & GRATE SHALL BE
NEENAH R-3405 OR APPROVED EQUAL
OPENING CAST IN BARREL
FOR INLET LEAD
NOTE:
PVC CONNECTIONS TO STORM MANHOLES
AND INLETS SHALL BE MADE WITH GPK
SANDED MANHOLE ADAPTER OR APPROVED
EQUAL.
NOTE:
HDPE CONNECTIONS TO STORM MANHOLES
AND INLETS SHALL BE MADE WITH
PRESS SEAL GASKET CORP. WATERSTOP
OR APPROVED EQUAL.
7 STORM INLET (27") DETAIL
C6.0 NOT-TO-SCALE
NOTES
1.
60°60°60°60°
RCP
32"(ADJ.±1 1/2" MIN.)
2"MAX.
TOP VIEW
RCP
32"(ADJ.±1 1/2" MIN.)
2"MAX.
32"(ADJ.±1 1/2" MIN.)
2"MAX.
32"± AS REQ'D FOR
SEE DETAIL "A"
ACCEPTABLE JOINT
PIPE TIES
RCP
RCP
4 1/4"
3 1/2"
THREAD DIA. E.S. PIPE DIA
5/8" 3/4" 1"
3/4" 1" 1 1/4"
REQUIRED SIZE OF TIE BOLTS
5/8"
SEE
NOTE
TWO
3/4" 1"
9 CONCRETE PIPE TIES DETAILS
C6.0 NOT-TO-SCALE
PIPE SIZE LISTED IS INSIDE DIAMETER OF ROUND PIPE OR
EQUIVALENT DIAMETER OF PIPE ARCH.
NUTS AND WASHERS ARE NOT REQUIRED ON INSIDE OF 21"
DIAMETER PIPE OR LESS.
TIES TO BE USED ONLY TO HOLD PIPE SECTIONS TOGETHER,
NOT FOR PULLING SECTIONS TIGHT.
TIE BOLTS SHALL BE PAINTED AFTER FABRICATION WITH
ONE COAT OF ZINC CHROMATE IRON OXIDE PAINT. THREADED
PORTIION OF RODS DO NOT HAVE TO BE PAINTED.
HOLES IN PIPE TO ACCOMMODATE THE TIE BOLTS CAN BE
PRECAST OR DRILLED. TAPERED HOLES WILL BE PERMITTED
WHEN PRECAST. WHEN EXISTING PIPE ARE EXTENDED OR
SALVAGED AND RELAYED, THE CONTRACTOR WILL BE
REQUIRED TO DRILL THE NECESSARY HOLES.
THE CONTRACTOR HAS THE OPTION OF SELECTING THE TYPE
OF TIE BOLT TO BE USED. THE TYPE SELECTED SHALL BE
APPPROVED BY THE ENGINEER.
THE COST OF PRECASTING OR DRILLING THE REQUIRED HOLES
AND FURNISHING AND INSTALLING THE TIE BOLTS SHALL BE
INCLUDED IN THE PRICE BID FOR REINFORCED CONCRETE
PIPE CULVERTS.
TIE BOLTS ARE NOT REQUIRED ON STORM SEWER PIPE UNLESS
SPECIFICALLY NOTED IN THE PLANS.
IE BOLTS ARE REQUIRED ON END SECTIONS (4 SECTIONS)
FOR ALL R.C.P. CULVERTS. ON CULVERTS WITHOUT FLARED
END SECTIONS, THE THREE END SECTIONS OF THE CULVERT
SHALL BE TIED TOGETHER IN THE SAME MANNER FOR EACH
END.
2.
3.
4.
5.
6.
7.
8.
9.
THREAD
DIA.
PIPE
SIZE
(INCHES)
THREAD
DIA.
PIPE
SIZE
(INCHES)
THREAD
DIA.
PIPE
SIZE
(INCHES)
WELD COUPLER
TO BOLT
WELDED EYE OR
APPROVED EQUAL
RCP
RCP
PIPE TIES
OPTIONAL
CANOPY TIE
EXTRA STRONG PIPE
(SEE TABLE)
ADJUSTABLE TIE
EYE BOLT TIE
WELDED PIPE TIE
U BOLT TIE
TIE LOCATIONS
DETAIL "A"
ROUND PIPE
12"
15"
18"-24"
27"-36"
42"-54"
60"-72"
78"-90" 8"
7"
6"
5"
4"
3"
2 1/2"
PIPE
SIZE
H
ARCH PIPE
H
SIZE
PIPE
4"
5"
6"
7"73"-88"
51"-55"
36"-44"
22"-29"
VALUES FOR "H"
BAR SIZES
STANDARD DESIGN HEAVY DESIGN
PIPE
R O U N D
REQ'D
HOLE DIA. BOLT
DIA. SIZE
BAR
12"-24"
27"-48"
54"-90"
22"-29"
36"-59"
65"-88" 1 1/8"
7/8"
3/4"
1 1/8"
7/8"
3/4" 5/8"
3/4"
1"
5/8"
3/4"
1" 1"
3/4"
5/8"
1"
3/4"
5/8"
SIZE
A R C H
A R C H
SIZE
3/4"
1"
1 1/4"
3/4"
1"
1 1/4"1"
3/4"
5/8"
1"
3/4"
5/8"3/4"
7/8"
1 1/8"
3/4"
7/8"
1 1/8"59"-88"
29"-51"
22"
48"-90"
21"-42"
12"-18"
BAR
SIZEDIA.
BOLTHOLE DIA.
REQ'D
R O U N D
PIPE
BOLT LG. = PIPEWALL THICKNESS + 2 1/2"
6" MIN.
"H" (SEE TABLE)
10 TRASH GUARD FOR FLARED END SECTION DETAIL
C6.0 NOT-TO-SCALE
ALL TRASH GUARDS TO HAVE (1) CROSS BAR
60" DIA. & UP TO HAVE (2) BARS EQUALLY
SPACED
HOT DIP GALVANIZED PER MN/DOT 3392
OR ASTM-A153
HINGED
CONNECTIONS
HINGED
CONNECTIONS
GUTTER
STREET
15' TYP
T Y P
2' DEEP
1' - 2' DEEP
1' DEEP
3' - 4' DEEP
BACK OF CURB
9" FIBER ROLL
BACK OF CURB
18 CONCRETE WASHOUT DETAIL
C6.0 NOT-TO-SCALE
BARRIER
FENCEEXISTING
GROUND
MAY BE UP
TO 4' DEEP
CLEAN OUT @
80% OF CAPACITY
BARRIER FENCE
(NEED NOT BE
SILT FENCE)
9" FIBER ROLLS MAX
4.0' SPACING FOR
STAKES
SECTION A-A
PLAN VIEW
19 PVC INLET DETAIL
C6.0 NOT-TO-SCALE
12"-90° BEND
12" STORM SEWER
ADS 2712AG ADAPTOR
ADS 1299CGS INLET
CASTING & GRATE
NEW 12" STORM SEWER
FINISHED GROUND
EXTERIOR WALL OF BUILDING
ROOF DOWNSPOUT
2.8
2.9
3.9
4.28.4
7.8
5.8
5.5
20 RIP RAP DETAIL
C6.0 NOT-TO-SCALE
PIPE
DIA
(IN)
L
(FT)
24" DEPTH
RIP RAP
(CY)
12" DEPTH
AGG. CUSH.
(CY)
11.0
11.6
14.5
16.4
18.3
21.7
25.8
5.5
5.8
7.3
7.8
9.2
10.9
12.9
PIPE
DIA.
A A
B
B
L
RIP RAP
AGGREGATE CUSHIONNON-WOVEN
GEOTEXTILE FABRIC
1"
AGGREGATE CUSHION
GEOTEXTILE
FABRIC
RIP RAP
1"
Date
Drawing Title
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J J
K K
March 19, 2021 1431-14
Shultz + Associates Architects
612 1/2 Main Avenue
Fargo, North Dakota
701.476.0714 p
701.476.0709 f
ARCHITECT
CIVIL ENGINEER
STRUCTURAL ENGINEER
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
MBN Engineering
503 7th St. N., Suite 200
Fargo, North Dakota
701.478.6336 p
701.478.6340 f
Heyer Engineering
1020 36th Street S Suite A
Fargo, North Dakota
701.280.0949 p
701.280.9686 f
Consolidated RPA
Operations Facility
E N G I N E E R I N G
3-19-21
C6.0
DETAILS
24"Min.
2' O.C. EACH WAY
#3 REBAR
8"
2" SAND BASE2' O.C.
1'-#3 REBAR
*6" ADA RAMP
SIDEWALK
PAVEMENT
* USE STANDARD CONCRETE MIX (NO COLORING ADDED)
2 ADA RAMP DETAIL
C6.1 NOT-TO-SCALE
CURB & GUTTER
ADA DETECTABLE
WARNING PANEL
1'-#3 REBAR
2' O.C.
ANCHOR UNIT (48")
13 SINGLE BREAKAWAY DETAIL
C6.1 NOT-TO-SCALE
NOTES:
1. ALL POSTS AND ANCHORS SHALL BE 12
GAUGE WITH HOLES ON ALL FOUR SIDES.
2. LEAVE 1 TO 2 HOLES EXPOSED ABOVE
FINISH GROUND LINE FOR CONNECTION
OF POST TO ANCHOR.
1 1/2"x1 1/2"
SIGN POST
FINISHED GROUND
LINE
1 3/4"x1 3/4"
ANCHOR
3/8" DIA. BOLT WITH
WASHER & LOCKWASHER
VARIABLE
2" SAND BASE
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
#3 BARS @ 24" O.C. E.W.
3 4" REINFORCED CONCRETE SIDEWALK DETAIL
C6.1 NOT-TO-SCALE
FINISH GROUND LINE
11 ACCESSIBLITY SIGN DETAIL
C6.1 NOT-TO-SCALE
R7-8(MODIFIED) 12"x18"
R7-8AP PLAQUE 12"X6" (INCLUDE
'VAN ACCESSIBLE' PLAQUE WHEN
ADJACENT TO 8 FT OR WIDER
STRIPED ACCESS AISLE.)
R7-8NDP PLAQUE 12"X12"
NOTES:
1. SHEETING SHALL BE ENGINEER GRADE.
2. SIGN PLATE SHALL BE 80 GAUGE ALUMINUM.
3. SIGNS SHALL BE IN ACCORDANCE WITH THE
MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES.
SIGN ASSEMBLY DETAIL
12 ACCESSIBILITY SYMBOL DETAIL
C6.1 NOT-TO-SCALE
6"
T Y P
10" 4"
5" R
12"
20"
9.0°
"R
24"
R
4"
1'-6 3/4"
BLUE HIGHWAY PAINT
BACKGROUND - 2
COATS (TYPICAL)
INTERNATIONAL SYMBOL OF
ACCESSIBILITY APPLIED TO THE
CENTER OF EACH REQUIRED
ACCESSIBLE SPACE WITH BLUE PAINT
BACKGROUND AND WHITE PAINT FOR
SYMBOL AND PERIMETER EDGE
5" WIDE WHITE STRIPING -
2 COATS (TYPICAL)
(TYPICAL)
L L
4" 24"
14 ACCESSIBLE STRIPING DETAIL
C6.1 NOT-TO-SCALE
NOTES:
1. L = DIMENSIONS AS SHOWN ON PLANS.
CENTER OF STRIPE TO CENTER OF
STRIPE.
2. STRIPING ADJACENT TO ACCESSIBLE
PARKING SHALL BE BLUE.
3. DIMENSION ACCESSIBLE SYMBOLS AS PER
INTERNATIONAL SYMBOL OF
ACCESSIBILITY DETAIL.
4" SOLID LINE,
BLUE-PAINT (TYPICAL)
4 6" NON-REINFORCED CONCRETE PAVEMENT DETAIL
C6.1 NOT-TO-SCALE
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
6" ND CLASS 5
AGGREGATE BASE
FINISH GRADE
TERMINAL OR CORNER POSTS
4" O.D. SCH.40 STEEL PIPE
(OR AS SPECIFIED)
1-5/8" O.D. TOP RAIL (TYP.)
2" MESH, CHAIN LINK FABRIC,
9 GA. (FOR GALVANIZED FENCES)
FABRIC @ 1-1/2" (MAX.)
FROM FINISHED GRADE
3" O.D. LINE POSTS
(OR AS SPECIFIED)
6 GA. ALUM. WIRE TIES
@ 12" O.C. (TYP.)
SLOPE TO DRAIN (TYP.)
CONCRETE FOOTING
COMPACTED SUBGRADE
1-5/8" O.D. BOTTOM RAIL (TYP.)
6 GA. ALUM. TIES ALONG TOP &
BOTTOM RAILS @ 12" O.C. (TYP.)
TENSION BAR
BANDS/CLIPS @ 12" O.C.
(TYP.)
TENSION BAR (TYP.)
15"
MAX. 10'-0"
O
7' HIGH CHAIN LINK FENCE W/ 6 STRAND BARBED WIRE
NOT-TO-SCALE
C6.1
NOTE:
1.LINE POSTS SHALL BE DRIVEN TO A DEPTH OF 84".
OUTRIGGER WITH 3 STRANDS
BARBED WIRE EACH SIDE
15"
O
SONOTUBE
SONOTUBE
CONCRETE FOOTING
OUTRIGGER WITH 3 STRANDS
BARBED WIRE EACH SIDE
TERMINAL OR CORNER POSTS
4" O.D. SCH.40 STEEL PIPE
(OR AS SPECIFIED)
SLOPE TO DRAIN (TYP.)
ACCESS GATE DETAIL
NOT-TO-SCALE
C6.1
BALL CAP WITH SET SCREW OR
SPOT WELDED
GATE POST
12"
6"
12"
6"
LOCKING
GATE HASP
GRADE
4'-0"
CONCRETE FOOTING
SONOTUBE
SONOTUBE
TERMINAL OR CORNER POSTS
4" O.D. SCH.40 STEEL PIPE
2" MESH, CHAIN LINK FABRIC,
9 GA. (FOR GALVANIZED FENCES)
OUTRIGGER WITH 3 STRANDS
BARBED WIRE EACH SIDE
O
30"
12" 3/16"
1/2" SLOPE
1 1/2"2 1/2"
3 1/4"
1"
1"
TYPE I MOUNTABLE CURB & GUTTER
3"
1 (TYPE I OR TYPE II) MOUNTABLE CONCRETE CURB AND GUTTER DETAIL
C6.1 NOT-TO-SCALE
NOTE:
1. 1/2" x 18" DEFORMED BARS AT
30" O.C. & KEYWAY REQUIRED
WHEN SEPARATE CURB IS
INSTALLED WITH CONCRETE PAVING
2. 1" EXPANSION JOINTS TO MATCH
EXPANSION JOINTS ON CONCRETE
PAVEMENT.
6" ND CLASS 5
AGGREGATE BASE
3 NOTE:
1. DIMENSION "A" SHALL MATCH THE
THICKNESS OF THE ADJOINING
PAVEMENT WITH EITHER INTEGRAL
OR SEPARATE CURB
12"
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
30"
12" 3/16"
1/2" SLOPE
1 1/2"2 1/2"
3 1/4"
1"
1"
TYPE II MOUNTABLE CURB & GUTTER
3"
6" ND CLASS 5
AGGREGATE BASE
12"
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
NOTE:
1. PLACE DUMMY JOINT TO MATCH
PANEL SPACING FOR CONCRETE
PAVEMENT.
A
A
2'-0"
12" SCARIFY &
RECOMPACT TO
95% STANDARD
PROCTOR
DENSITY
1/2"
2" SAND BASE
8 2' WIDE CONCRETE MOW STRIP DETAIL
C6.1 NOT-TO-SCALE
PVC SLEEVE
CONTRACTION JOINT
PLAN VIEW
SECTION VIEW
SEAL VOID BETWEEEN
PIPE AND PVC SLEEVE
PVC SLEEVE
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
12" ND CLASS 5
AGGREGATE BASE
7 18" NON-REINFORCED CONCRETE PAVEMENT DETAIL
C6.1 NOT-TO-SCALE
DRILL AND INSERT 12"x30" #4
SMOOTH DOWELS @ 18" O.C. TO
CONNECT ADJACENT SLABS.
USE 12"X30" #4 DEFORMED BARS
@ 18" O.C. TO CONNECT FULL
DEPTH PATCHING IN SAME SLAB
NEW CONCRETE
PAVEMENT
9 FULL-DEPTH CONCRETE REPAIR DETAIL
C6.1 NOT-TO-SCALE
FULL-DEPTH SAW CUT
EXISTING PANEL AT JOINTS
PRIOR TO REMOVAL
NEW JOINT
SEALANT
ORIGINAL
SPALL EDGE
SAW CUT 2" MINIMUM OR 12"
INTO VISUALLY SOUND
CONCRETE, WHICHEVER IS
DEEPER.
NEW PORTLAND
CEMENT CONCRETE
BOND BREAKING MEDIUM TO
MAINTAIN EXISTING JOINT.
SPALL REPAIR SHALL NOT
BRIDGE A JOINT.
10 PARTIAL-DEPTH CONCRETE REPAIR DETAIL
C6.1 NOT-TO-SCALE
2" MIN.
F I E L D
V E R I F Y
NOTE:
MINIMUM LENGTH AND WIDTH
OF A RECTANGULAR SAWCUT
BOUNDARY AROUND A SPALLED
JOITN IS 6".
REESTABLISH
EXISTING JOINTS
ALONG ALL PATCHES
REESTABLISH
EXISTING JOINTS
ALONG ALL PATCHES
NOTE:
USE 12"X30" #4 DEFORMED
BARS @ 18" O.C. TO CONNECT
FULL DEPTH PATCHING WITHIN
SAME SLAB
NOTE:
ENSURE REMOVAL OF DEFICIENT
CONCRETE BY SOUNDING THE BOTTOM OF
THE CAVITY WITH CHAINS OR A HAMMER
TO DETERMINE IF DELAMINATED
CONCRETE HAS BEEN REMOVED.
GEOTEXTILE FABRIC
GEOTEXTILE FABRIC
O R
20 TYPE 'H' CONSTRUCTION JOINT DETAIL
C6.1 NOT-TO-SCALE
8"
1/2" ROD BACK-UP MATERIAL
SAWED JOINT FACE
RECESS SEALANT 1/4"-3/8"
BELOW PAVEMENT
INITIAL SAWCUT (REFER TO
DIMENSION TABLE) 6"-10"
THICK PCC = T/4
1/4"-3/8" MIN.
SEALANT DEPTH
19 TYPE 'H' DETAIL
C6.1 NOT-TO-SCALE
O R
O R
#4 x 30" DEF.
BARS @ 24" O.C.
16 TYPE 'C' TIED CONSTRUCTION JOINT DETAIL
C6.1 NOT-TO-SCALE
O R
NON-EXTRUDING PREMOLDED
COMPRESSIBLE MATERIAL
18 TYPE 'I' ISOLATION JOINT DETAIL
C6.1 NOT-TO-SCALE
4"
BOND BREAKER MATERIAL
RECESS SEALANT
1/4"-3/8"
BELOW PAVEMENT
NON-EXTRUDING PREMOLDED
COMPRESSIBLE MATERIAL
17 TYPE 'I' DETAIL
C6.1 NOT-TO-SCALE
#4 x 30" DEF.
BARS @ 24" O.C.
8"
SAWED JOINT FACE
RECESS SEALANT
1/4"-3/8"
BELOW PAVEMENT
1/4"-3/8" MIN.
SEALANT DEPTH
1/2" ROD BACK-UP
MATERIAL
15 TYPE 'C' DETAIL
C6.1 NOT-TO-SCALE
#4 BARS @ 24" O.C. E.W.
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
6" ND CLASS 5
AGGREGATE BASE
5 6" REINFORCED CONCRETE PAVEMENT DETAIL
C6.1 NOT-TO-SCALE
GEOTEXTILE FABRIC
#4 BARS @ 24" O.C. E.W.
12" SCARIFY &
RECOMPACT SUBGRADE
TO 95% STANDARD
PROCTOR DENSITY
6" ND CLASS 5
AGGREGATE BASE
6 8" REINFORCED CONCRETE PAVEMENT DETAIL
C6.1 NOT-TO-SCALE
GEOTEXTILE FABRIC
FINISH GRADE
TERMINAL OR CORNER POSTS
4" O.D. SCH.40 STEEL PIPE
(OR AS SPECIFIED)
BALL CAP WITH SET SCREW OR
SPOT WELDED
1-5/8" O.D. TOP RAIL (TYP.)
1-5/8" O.D. INTERMEDIATE RAIL (TYP.)
KNUCKLED SELVAGE @
TOP & BOTTOM (TYP.)
2" MESH, CHAIN LINK FABRIC FOR
SIDES AND TOP OF CAGE,
9 GA. (FOR GALVANIZED FENCES)
FABRIC @ 1-1/2" (MAX.)
FROM FINISHED GRADE
3" O.D. LINE POSTS (OR AS SPECIFIED)
6 GA. ALUM. WIRE TIES @ 12" O.C. (TYP.)
SLOPE TO DRAIN (TYP.)
CONCRETE FOOTING
COMPACTED SUBGRADE
1-5/8" O.D. BOTTOM RAIL (TYP.)
6 GA. ALUM. TIES ALONG TOP, INTERMEDIATE,
& BOTTOM RAILS @ 12" O.C. (TYP.)
TENSION BAR BANDS/CLIPS @ 12" O.C. (TYP.)
TENSION BAR (TYP.)
12"
84"
MAX. 10'-0"
O
9' HIGH CHAIN LINK FENCE DETAIL
NOT-TO-SCALE
C6.1
SONOTUBE
NOTE:
1. LINE POSTS SHALL BE DRIVEN TO A DEPTH OF 84".
2.CHAINLINK COVER OF CHILLER ENCLOSURE SHALL CONSIST OF
1-5/8" O.D. RAILS PLACED PERPENDICULAR TO TOP RAILS
AT SAME SPACING AS LINE POSTS WITH 2" MESH, 9 GA
CHAINLINK FABRIC
LOCKING
GATE HASP
GATE
TENSION
BAR BANDS
@ 18"O.C.
TENSION
BARS
4" O.D.
GATE POSTS
BOTTOM HINGE
(180° SWING)
CONC. FOOTING
COMPACTED
SUBGRADE
1-5/8" O.D. TOP,
MIDDLE & BOTTOM
RAILS
4'-0"
12" 12"
84" 84"
23 9' HIGH CHAIN LINK FENCE WITH 4' WIDE GATE DETAIL
C6.1 NOT-TO-SCALE
O
O
TOP HINGE
(180° SWING)
1-5/8" O.D.
GATE FRAME
SONOTUBESONOTUBE
4" O.D.
GATE POSTS
GATE POST
GATE CORNER
3/8" ADJ
TRUSS RODS
GATE FRAME
GATE POST
CENTER STOP
12" X 12" X 12"
12"
6"
12"
6"
DOUBLE SWING GATE DETAIL
NOT-TO-SCALE
C6.1
SONOTUBE SONOTUBE
TERMINAL OR CORNER POSTS
4" O.D. SCH.40 STEEL…