This document is a detailed specification for a CRSP SCADA Sandbox Programmable Controller and Software procurement for the U.S. Bureau of Reclamation's Upper Colorado Basin Region. The solicitation requires the purchase of specific Rockwell Automation components, including 2 controllers (1756-L81E), 5 chassis (1756-A7), 6 blank slot fillers, 5 analog output modules, 17 digital output modules, 5 digital input modules, 5 EtherNet/IP communication modules, 6 power supplies, terminal blocks, 2 Studio 5000 Full Edition perpetual licenses, 2 activation dongles, and 2 ProSoft DNP 3.0 Master/Slave Network Interface Modules.
The specification outlines rigorous technical requirements for the equipment, including environmental durability (operating temperatures from 0°C to 60°C), performance specifications (10ms scan cycle time), time synchronization protocols, cybersecurity features (AES-256 encryption, role-based access control), and a minimum 3-year warranty. Delivery is specified to the Denver Federal Center, with instructions for offerers to carefully review all attachments and provide complete quotes. The components are intended to be part of the same platform family to ensure interoperability and seamless integration within the SCADA sandbox environment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Updated_AMD_0002_Clauses_and_Provisions_140R4025Q0055_0002.docx | DOCX document | |
| Sol_140R4025Q0055_Amd_0002.pdf | ||
| Sol_140R4025Q0055_Amd_0001.pdf | ||
| 140R4025Q0055_Questions_and_Answers_0001.docx | DOCX document | |
| Attachment_A_Specifications.pdf | ||
| Sol_140R4025Q0055.pdf | ||
| Clauses_and_Provisions_140R4025Q0055.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CRSP SCADA Sandbox Programmable Controller and Software
Upper Colorado Basin Region
CRSP SCADA Sandbox Programmable Controller and So�ware
U.S. Department of the Interior
Bureau of Reclamation
Upper Colorado Basin
Salt Lake City, Utah bmurphy Inserted Text luatil
Upper Colorado Basin Region
1.0 BACKGROUND:
The Bureau of Reclama�on is a water management agency overseeing 600 dams in 17 western states. Renowned for construc�ng dams, power plants, and canals, notable projects include Hoover Dam on the Colorado River, Grand Coulee Dam on the Columbia River, and Folsom Dam on the American River. Reclama�on is the largest wholesaler of water in the United States and the second-largest producer of hydroelectric power in the western U.S., organized into five regions, including the Upper Colorado Basin.
2.0 INTRODUCTION:
The Upper Colorado Basin (UCB) Region is seeking to purchase a programmable logic controller, associated modules, and so�ware for the inclusion into the CRSP SCADA sandbox. The specifica�on and system design are based on Rockwell Automa�on’s 1756 ControlLogix pla�orm. The equipment provided shall be the latest newly manufactured, pre-installed with the latest stable firmware version. EQUAL products that meet or exceed the specified product’s technical specifica�ons and the requirements listed with in this specifica�on will be considered.
3.0 REQUIREMENTS:
3.1 Environmental Durability
• In accordance with IEC 61131-2 standards for programmable controllers.
• Operating Temperature: 0°C to 60°C (32°F to 140°F)
• Storage Temperature: -40°C to 85°C (-40°C to 185°F)
• Humidity: 5-95% non-condensing
• Ingress Protection: IP20
• Shock and Vibration: Modules shall be compliant with IEC 60068.
3.2 Performance Specifica�ons
• Cycle Time and Determinism: Shall support a scan cycle time of 10ms or better.
• Real-Time Diagnostics: shall provide real-time diagnostics for monitoring network health, I/O performance, and identifying fault conditions at the module level.
• Timestamping: resolution of 1ms
• Data Retention: Event logs shall provide export or transfer to external logging systems for a minimum 30-day retention.
Upper Colorado Basin Region
3.3 Time Synchroniza�on
• Supported Protocols: Shall support Precision Time Protocol (PTP) (IEEE 1588) and
Network Time Protocol (NTP) for time synchronization.
• Precision: Must be +/- 1ms precision for time-stamping capabilities across modules.
3.4 Protocol Support
• EtherNet/IP: Shall support EtherNet/IP in accordance with IEC 61158 for industrial communication networks.
• DNP3 (serial and ethernet): Support DNP3 protocol natively or via a compatible communication module.
3.5 Modular Design
• Chassis Capacity: Standard 7-slot chassis to allow modular expandability and accommodate additional modules as needed.
• Hot Swappable: Hot swappable I/O modules.
• Backplane shall provide at a minimum of 2Mbps inter-module communication data transfer rate.
• Removable terminal blocks shall be provided to allow for a flexible interconnection between plant wiring and I/O modules. Terminal blocks shall be provided with screw-clamp connections.
3.6 Cybersecurity
• Access Control: shall provide integrated role-based access control (RBAC) to restrict access by user roles and permissions.
• Encryption Standards: Built-in AES-256 encryption for EtherNet/IP communication to secure data in transit.
• Patch Management: Shall support secure firmware patching via Rockwell’s
ControlFLASH or equivalent.
• Logging and Audit: shall support detailed logging and audit trails for user actions, configuration changes, and access attempts.
3.7 Support and Warranty
• Warrant Period: minimum 3-year warranty on all modules and components, covering parts and labor.
• Firmware and Software updates: Manufacturer shall provide regular firmware and software updates, and security patches for all modules.
bmurphy Highlight
Upper Colorado Basin Region
3.8 Addi�onal Considera�ons
• Documentation: Each component shall include full technical documentation, including wiring diagrams, installation guides, and operating manuals.
• Compliance: UL and CE certifications shall be provided.
• Industrial Certification: Components shall meet IEC 61131-2 for programmable controllers in industrial applications.
• Vendor shall provide assurance of spare parts availability for a minimum of 10 years.
4.0 PRODUCTS:
All components, including the controller, power supply, communica�on modules, I/O modules, and so�ware shall be manufactured by the same vendor and be part of the same pla�orm family. This ensures interoperability, reduces maintenance complexity, and supports seamless integra�on. The ProSo� DNP3 Master/Slave Network Interface Module is the only permissible excep�on, or equivalent DNP3 communica�ons module.
Ensure full compa�bility and uniform func�onality across all modules and accessories. Each component shall be na�vely compa�ble and fully supported within the ControlLogix environment, elimina�ng the need for third-party adapta�ons or compa�bility workarounds.
The following products are specified as the basis for design and performance standards.
Equivalent products shall meet or exceed the specified product’s technical specifica�ons and the listed requirements below each.
4.1 1756-L81E, 3MB Controller
Quan�ty: 2 EA Part Number: 1756-L81E Configura�on -
Nonvola�le Memory: 3MB Ports: 1-Ethernet (10/100/1000Mbps), 1-USB 2.0.
Communica�ons: EtherNet/IP, DeviceNet, ControlNet.
Programming Languages: Relay ladder, structured text, func�on block, and sequen�al func�on chart (SFC) Redundancy: Support for controller redundancy.
4.2 1756-A7, 7-Slot Chassis
Quan�ty: 5 EA Part Number: 1756-A7 Configura�on –
Slot Configura�on: 7-slot
Upper Colorado Basin Region
Moun�ng: Back-panel moun�ng
4.3 1756-N2, Blank Slot Fillers
Quan�ty: 6 EA Part Number: 1756-N2 Configura�on – Provide slot fillers to cover any spare slots from dust and debris.
4.4 1756-OF8, 8-Channel Analog Output Module
Quan�ty: 5 EA Part Number: 1756-OF8 Configura�on –
Outputs: 8 common return voltage/current analog outputs Ra�ng: +/- 10VDC or 0-20mA Resolu�on: 15 bits across 10.4V/21mA
4.5 1756-OH8I, Isolated 8-Channel Digital Output Module
Quan�ty – 17 EA Part Number: 1756-OH8I Configura�on -
Outputs: 8 isolated digital outputs Voltage Category: 125V DC Ra�ngs: 90-146VDC externally sourced, 2A con�nuous per point.
4.6 1756-IH16I, Isolated 16-Channel Digital Input Module
Quan�ty: 5 EA Part Number: 1756-IH16I Configura�on-
Inputs: 16 isolated digital inputs, with so�ware configurable state change defini�on Voltage Category: 125V DC Ra�ngs: 90-146VDC
4.7 1756-EN2TR, EtherNet/IP Communica�on Module
Quan�ty: 5 EA Part Number: 1756-EN2TR Configura�on –
Ports: 2, copper Communica�on Rate: 10/100 Mbps TCP/IP Connec�ons: 128
Upper Colorado Basin Region
4.8 1756-PA75, Power Supply
Quan�ty – 6 EA Part Number: 1756-PA75 Configura�on –
Voltage Category: 120V/240V AC Input Ra�ng: 120VAC, 100W, 60Hz Output Ra�ng: 75W max Inrush: 20A max inrush
4.9 1756-TBNH, Terminal Block for Analog Cards
Quan�ty – 4 EA Part Number: 1756-TBNH Configura�on –
Descrip�on: Removable terminal block, 20 posi�on NEMA screw clamp block for analog circuits. Single wire connec�ons, 22-14 AWG solid or stranded shielded copper wire rated 105°C.
4.10 1756-TBCH, Terminal Block for all other Cards
Quan�ty – 20 EA Part Number: 1756-TBCH Descrip�on – 36-pin cage-clamp removable terminal block. Single wire connec�ons, 22-14
AWG solid or stranded shielded copper wire rated 105°C.
4.11 9324M-RLDT80, Studio 5000 Full Edi�on, perpetual license.
Quan�ty – 2 EA Part Number: 9324M-RLDT80 License Type: Perpetual Descrip�on – Provide a perpetual license for Rockwell Automa�on Studio 5000 Full Edi�on
(9324M-RLTD80), or equivalent, with func�onality for configura�on, programming, valida�on, tes�ng, and op�miza�on of all applica�on code.
4.12 9509-USB-DONG2, Ac�va�on Dongle Quan�ty – 2 EA Park Number: 9509-USB-DONG2 Descrip�on – Provide a portable hardware device that stores so�ware licenses allowing users to ac�vate and run the so�ware on any computer which the dongle is connected to, Upper Colorado Basin Region
4.13 MVI56-DNP, Proso� DNP 3.0 Master/Slave Network Interface Module
Quan�ty – 2 EA Part Number: MV156-DNP Descrip�on – DNP 3.0 module to allow the controller processor to interface with devices over the DNP protocol. Compa�ble with the backplane of the proposed controller. Provides two DNP protocol ports capable of being configured as Master/Slave or Slave/Slave.
5.0 DELIVERY:
All items shall be delivered to the address listed below. Each delivery shall include a detailed packing list and contact informa�on for post-delivery support.
Denver Federal Center Ship to: US Bureau of Reclamation 6th Ave and Kipling St Bldg 56, Room 2730 Denver, CO 80225
Submission Instructions to Offerers:
Review all attachments:
• Clauses and Provisions - Pay close attention to highlighted sections.
• Attachment A Specifications
• Incomplete quotes will be considered non responsive.