This is a Materials Specifications document for electrical components required by the Bureau of Reclamation (BOR), Lower Colorado Region, to support water pumping systems at the Planet Ranch Conservation Area as part of the Lower Colorado River Multi-species Conservation Program.

The contractor must supply and deliver nine electrical component line items to BOR's office in Yuma, Arizona (7301 S Calle Agua Salada) within 180 days of contract award. Required components include: two Variable Frequency Drives (VFDs) manufactured by Schneider Electric or equivalent, rated for 460V 3-phase 200 horsepower motors with 250 max output amps and Type 12 enclosure; one Electric Underground Pull Section/Meter-CT rated 480/277V 3PH/4W at 400A; one 3-pole 400A 600V Circuit Breaker; one NEMA 4 Panelboard Enclosure rated for outdoor/dust-prone areas; one 400A Main Lug Interior supporting 3-phase 4-wire systems at 600Y/347VAC; one Panelboard Ground Bar rated 100A-800A; one 400A Main Circuit Breaker Adapter Kit; one 100A 3-pole Miniature Circuit Breaker; and one 480V 3-phase Well Guard-Control Pumping Plant Panel. All electrical components must meet Arizona Public Service (APS) standards and requirements. The contractor is responsible for verifying compliance, coordinating with APS if needed, and providing documentation of compliance. Delivered materials should include typical model accessories such as bolt packs, anchors, and hardware, and should be boxed and palleted where possible.

View the file

Other files

File Type Posted
Sol_140R3026Q0015_Amd_0003.pdf PDF
Sol_140R3026Q0015_Amd_0002.pdf PDF
Sol_140R3026Q0015_Amd_0001.pdf PDF
Sol_140R3026Q0015.pdf PDF
140R3026Q0015-Combined_Synopsis_Solicitation.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Planet Ranch Conservation Area Electrical Components Material and Equipment Specifications

Electrical Components

Materials Specifications

INTRODUCTION

The Bureau of Reclamation (BOR), Lower Colorado Region, requires various electrical components as described in this specification. The components and associated parts will be installed by BOR to ensure that water pumping systems work properly and are able to deliver water at a Lower Colorado River Multi-species Conservation Program (LCR MSCP) conservation area.

LOCATION

For materials and equipment in Table 1.0, the delivery location will be in Yuma, AZ at BOR’s office (Address: 7301 S Calle Agua Salada).

QUANTITIES

The contractor shall supply and deliver the electrical components included in Table 1.0 to the specified locations stated in the previous section. The contractor shall supply documentation ensuring compliance with these specifications. Delivered materials and equipment should include typical model accessories needed for installation (i.e. bolt packs, anchors, hardware, etc.).

(All electrical components must meet APS requirements)

Variable Frequency Drive 2 ea Electric Underground Pull Section/Meter-CT 1 ea

Circuit Breaker 1 ea Panelboard Enclosure/Box 1 ea Main Lug Interior 1 ea Panelboard Ground Bar 1 ea Main Circuit Breaker Adapter Kit 1 ea Miniature Circuit 1 ea Well Guard-Control Pumping Plant Panel 1 ea

1.0 Electrical Components

Description Quantity Unit

1.0 Electrical Components

All components must meet Arizona Public Service (APS) standards and requirements.

The contractor is responsible for verifying that all components meet APS and local standards and requirements. The contractor will be expected to coordinate with APS (if needed) to confirm that all components are approved. Please contact BOR if more specific details are required for these components. Electrical components shall meet the salient characteristics described below.

1. VFD as manufactured by Schneider Electric, 201 Washington Street #2700, Boston MA 02201, (877) 342-5173, https://www.se.com/us/en/, or equal having the following salient characteristics:

i. Main circuit breaker disconnect

ii. 100k AIC rated

iii. Selected for 460 Vac 3 phase motor

iv. 200 horsepower

v. Sized for heavy duty

vi. Drive controller rating: 250 max output amps

vii. Enclosure: Type 12

viii. UL508A Label

ix. RAL7035 (Gray)

x. Power Circuit W: drive combination package

xi. Motor filter: Dv/Dt

xii. Control options: hand-off-auto selector switch

xiii. Speed potentiometer

xiv. Pilot light options:

1. Power on pilot light (red)

2. Run pilot light (green)

3. Trip pilot light (yellow)

xv. Auxiliary contacts:

1. 1 NO/NC run contact

2. 1 NO/NC trip contact

3. 1 NO auto mode contact

xvi. Ethernet/IP, Modbus TCP, MultiDrive-Link – VW 3A 3721

xvii. Line reactor as standard

xviii. Output Filter

2. Electric Underground Pull Section/Meter-CT

i. 480/277V 3PH/4W

ii. 400A

iii. Example: Sun Valley SVWCTCB400-4

1. Note: Selection of this model is not strictly required if all salient characteristic, compatibility, and APS requirements are met by another.

3. Circuit Breaker

i. 3-pole

ii. 400A

iii. 600V

iv. Example: Square D LAL36400 Circuit Breaker https://www.se.com/us/en/

1. Note: Selection of this model is not strictly required if all salient characteristic, compatibility, and APS requirements are met by another.

4. Panelboard Enclosure/Box

i. NEMA 4

ii. Rated for outdoor and dust-prone areas

iii. Example: Square D MH62WP

1. Note: Selection of this model is not strictly required if all salient characteristic, compatibility, and APS requirements are met by another.

5. Main Lug Interior

i. 400A

ii. 3 phase support

iii. 4-wire system support

iv. 600Y/347VAC

v. Example: Square D NF442L4C

1. Note: Selection of this model is not strictly required if all salient characteristic, compatibility, and APS requirements are met by another.

6. Panelboard Ground Bar

i. 100A to 800A

ii. Accept #14 to #4 AWG wire

iii. Top mounted lug to accommodate #6 to 2/0 AWG wire

iv. Example: Square D PK27GTACU

1. Note: Selection of this model is not strictly required if all salient characteristic, compatibility, and APS requirements are met by another.

7. Main Circuit Breaker Adapter Kit

i. 400A

ii. Compatible with LI, LC, LAL, and LHL series circuit breakers

iii. UL listed

iv. CSA certified

v. Example: Square D N400M

1. Note: Selection of this model is not strictly required if all salient characteristic, compatibility, and APS requirements are met by another.

8. Miniature Circuit Breaker

i. 100A rating

ii. 3-poles

iii. 600Y/347VAC

iv. 25kA max interrupt rating

v. Example: Square D EDB36100

1. Note: Selection of this model is not strictly required if all salient another.

9. Well Guard-Control Pumping Plant Panel

i. 480V AC

ii. 3 phase support

iii. Example: Square D 8940XSC4200V81FF4TX

1. Note: Selection of this model is not strictly required if all salient another.

Refer to Table 1.0 for all other components and materials. Please contact BOR if more specific details are required for these components.

2.0 Delivery

For Table 1.0, the supplier shall deliver materials to the Yuma, AZ location. Supply equipment and materials boxed and palleted where possible. The period of performance for delivery of these materials will be for 180 days following contract award. Please coordinate delivery and material questions with TBD .