140R3024Q0003_Questions_and_Answers_0001.pdf
PDF 83 KB Posted
- Attached to
- Boiler Inspection, Maintenance, Repairs
- Solicitation number
- 140R3024Q0003
About this file
This document contains questions and answers related to federal solicitation number 140R3024Q0003 for boiler inspection, maintenance, and repair services. The solicitation is issued by the Department of the Interior Bureau of Reclamation and seeks a contractor to provide semiannual maintenance, testing, and inspection services for two visits per year on five boilers. Annual visits will be conducted concurrently with the semiannual visits. One question clarifies the estimated annual quantities in the pricing sheet will be corrected in an amendment to the solicitation. Model and serial number details are provided for the Lochnivor boiler. A campus map attachment is also added to the solicitation via amendment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140R3024Q0003_Amd_0002.pdf | ||
| 140R3024Q0003_Questions_and_Answers_1-5_0002.pdf | ||
| Att_2_Price_Quote_0001.xlsx | XLSX spreadsheet | |
| Boilers_LCB_map_0001.pdf | ||
| Att_1_PWS_Boiler_PM_Services_0001.docx | DOCX document | |
| Sol_140R3024Q0003_Amd_0001.pdf | ||
| Att_1_PWS_Boiler_PM_Services.docx | DOCX document | |
| Att__3_WD_2015-5593.pdf | ||
| Sol_140R3024Q0003.pdf | ||
| Att_2_Price_Quote.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140R3024Q0003 Questions and Answers Boiler Maintenance Services and Repairs
Q1. To confirm it is estimated the boilers will be serviced 6 times per year. That is, 2 semiannual visits and 1 annual visit for periodic inspection, testing, maintenance, etc., AND 2 semiannual visits and 1 annual for visit for preventative maintenance services. Correct?
A1. Two times a year for maintenance, testing, and inspection services. Annual visits are done concurrently with semiannual visits for all five boilers. It is possible that “a visit” is for longer than one day.
Q2. I also noticed the pricing sheet does not show an 'estimated annual quantity' for year five. Is this correct or possibly a typo?
A2. This is a typo. A corrected Attachment 2 is provided with this amendment.
Q3. What is the model number of the Lochnivor?
A3. Model # AWN151PM Serial # C11H20026584 Control # M-9
Q4. Would the Government please provide LCB campus map(s)?
A4. Yes, and attachment is added to the solicitation via this amendment.