Q_A_Attachments__Specs___Drawings_0003.pdf
PDF 4 MB Posted
- Solicitation number
- 140R1024B0002
About this file
This document is a set of questions and answers related to a federal contract solicitation for the Grand Coulee Dam RPP, LPP, WPP, and PGP Battery Room Upgrades project in Grand Coulee, Washington. The solicitation is being issued by the Bureau of Reclamation.
The key details include:
- The project involves battery room upgrades at the Grand Coulee Dam facility.
- The contract is tax exempt for services, but not for materials, which are subject to an 8.4% sales tax in the state of Washington.
- Contractors must provide all necessary equipment and transportation for the work. No additional drawings or details on existing equipment and infrastructure will be provided.
- The bid closing date has been extended two weeks to August 5th, 2024 at 1300 MST.
- The contract has various submittal requirements, including plans for concrete removal and repair, painting, and project record documents. Submittals must be approved by the Contracting Officer's Representative.
- The contractor is required to have an Onsite Safety Representative, Part-time Onsite Safety and Health Professional, and Certified Industrial Hygienist to oversee safety and hazardous materials on the project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140R1024B0002_Amd_0005.pdf | ||
| Sol_140R1024B0002_Amd_0004.pdf | ||
| Sol_140R1024B0002_Amd_0003.pdf | ||
| Sol_140R1024B0002_Amd_0002.pdf | ||
| Site_Visit_Attendees_0001.pdf | ||
| Sol_140R1024B0002_Amd_0001.pdf | ||
| Sol_140R1024B0002.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140R1024B0002 GC RPP LPP WPP PGP Battery Room Upgrades
QUESTIONS AND ANSWERS
# Contractor Question Government Answer
This project is tax exempt for services and Bureau of Reclamation will issue tax exempt certificate. As for material, sales tax is not exempt for federal projects in the State of Washington and the sales tax rate is
8.4% in Grand Coulee? Do you want a separate line item showing sales tax?
For Electronic Invoicing and Payment Requirements per Section G.3, sales taxes are not a separate line item.
The removal of the concrete is a large portion of the labor costs, is there an option to leave the existing concrete and install new high hazard rated seismic racking that will be secured to concrete? This will save the Bureau of Reclamation a large portion in labor cost.
No, this question has been addressed by the design and previous analysis. The concrete is to be removed per the design.
What equipment is available for transporting and/or hoisting the batteries in each of the battery rooms
(cranes, hoists, carts, pallet jacks, etc.)?
Contractor is to provide all transportation and/or hoisting equipment to perform the work.
Aside from the drawings furnished with the solicitation, are there any additional one-line drawings for the DC system available for review”?
See attached Drawings.
What is the available GPM of the existing eye wash stations supply?
GPM of the existing eye wash stations are unknown.
The bid documents do not provide the entire haul route that will be needed to move equipment and materials into and out of the battery rooms, please provide a detailed description of the approved route.
A detailed description of the haul route will not be provided. The contractor will need to determine the appropriate path to move equipment and materials into and out of the battery rooms.
Spec Section 26 33 13 1.05 C 4 references drawings
222-100-60445 and 222-100-60448. Can these drawings be provided?
Requested drawings provided
We would like to formally request a two-week extension to the bid date.
Bid closing has been extended two weeks to August 5th at 1300 MST
Grand Coulee Dam RPP, LPP, WPP, and PGP Battery Room Upgrades Grand Coulee Project- Washington Amendment No. P0003
Summary of Work – (Revised)
01 11 00 - 2
B. Imperative statements in these specifications are Contractor requirements, unless otherwise stated.
C. Where specifications are written in streamlined form, words “shall be” are included by inference where a colon (:) is used within sentence or phrase.
D. Door, ventilation, drains, and fire dampers listed on drawings are not part of the scope of this project.
E. Order of Battery Replacement:
1. WPP
2. PGP
3. LPP
4. RPP
1.04 DEFINITIONS
A. When specifications use a word or term defined in Federal Acquisition Regulations (FAR), definition of the word or term shall be in accordance with FAR sections in effect at the time solicitation was issued.
1.05 ACRONYMS
A. The following acronyms apply to specifications Divisions 1 through 52:
1. CO: Contracting Officer.
2. COR: Contracting Officer’s Representative.
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
Not Used
END OF SECTION
Use of Site – (Revised)
01 14 10 - 2
B. COR will assign staging areas determined by staging requirements submitted.
C. Do not interfere with work of other contractors or the Government in vicinity, or with reservations made by the Government for use of such land.
D. Housing for construction personnel will not be permitted on Government land, except housing for guards or watchmen as may be approved by COR.
1.04 WORK HOURS
A. Workdays are Monday through Thursday:
1. The contractor’s working hours shall be 6:30 am to 5:00 pm Monday through
Thursday not to exceed 40 hours, excluding federal holidays.
2. COR must approve any working hours outside this time frame.
3. Contractor will only be allowed on site when an authorized Government representative (i.e., Government inspector) is present.
4. Material deliveries and removal of materials from jobsite shall not be made on weekends and holidays.
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
3.01 RESTORATION
A. Restore Contractor use areas to pre-construction condition.
Submittals – (Revised)
01 33 00 - 12
Table 01 33 00A - List of Submittals
* Submittal Types: A – Approval, I – Information ** Y indicates Yes, the submittal is required to be shown on the Construction Schedule - see Section 01 32 10 -
Construction Program *** CO indicates Contracting Officer, COR indicates Contracting Officer Representative
RSN
Clause or
Section Title
Submittals required
Due date or Delivery time
Type
CP
** Responsible code
No. of sets to be sent to: ***
CO COR
01 74 00-5 Cleaning and Waste Management
Selected Treatment Storage and Disposal facility for hazardous waste
At least 15 days prior to hazardous waste disposal
A COR CDMS
01 74 00-6 Cleaning and Waste Management
Hazardous Waste Manifest
At least 7 days prior to hazardous waste disposal, for approval and signature
A COR CDMS
01 74 00-7 Cleaning and Waste Management
Signed Returned Hazardous Waste Manifest
Within 48 hours of receiving signatures
I COR CDMS
01 74 00-8 Cleaning and Waste Management
Waste Production and Disposal Records
Within 5 days of waste disposal
I COR CDMS
01 74 00-9 Cleaning and Waste Management
Environmental Consultant Resume
At least 35 days before beginning environmental assessment
A COR CDMS
01 74 00-10 Cleaning and Waste Management
Environmental Site Assessment
Within 14 days of completion of work
I COR CDMS
01 78 30-1 Project Record Documents
Electronic Media release Form, Upon Request
Within 7 days of NTP I COR CDMS
01 78 30-2 Project Record Documents
Progress As-built Drawings
Monthly or as required by COR
A COR CDMS
01 78 30-3 Project Record Documents
Draft As-built Drawings
Within 14 days after construction of a particular structure or work is completed
A COR CDMS
01 78 30-4 Project Record Documents
Final As-Built Drawings
Within 14 days of completion of work
A COR CDMS
01 78 30-5 Project Record Documents
Final Drawings Within 7 days after approval of final as-built drawings
A COR CDMS
03 81 10-1 Concrete Removal Concrete Removal Plan
At least 15 days prior to concrete removal
A COR CDMS
03 81 14-1 Concrete Repair Concrete Preparation Plan
At least 15 days prior to concrete repair
A COR CDMS
Submittals – (Revised)
01 33 00 - 12A
Table 01 33 00A - List of Submittals
* Submittal Types: A – Approval, I – Information ** Y indicates Yes, the submittal is required to be shown on the Construction Schedule - see Section 01 32 10 -
Construction Program *** CO indicates Contracting Officer, COR indicates Contracting Officer Representative
RSN
Clause or
Section Title
Submittals required
Due date or Delivery time
Type
CP
** Responsible code
No. of sets to be sent to: ***
CO COR
03 81 14-2 Concrete Repair Approval Data At least 15 days prior to concrete repair
I COR CDMS
03 81 14-3 Concrete Repair Applicator’s References and Qualifications
At least 15 days prior to concrete repair
I COR CDMS
Submittals – (Revised)
01 33 00 - 13
Table 01 33 00A - List of Submittals
* Submittal Types: A – Approval, I – Information ** Y indicates Yes, the submittal is required to be shown on the Construction Schedule - see Section
01 32 10 - Construction Program *** CO indicates Contracting Officer, COR indicates Contracting Officer Representative
RSN
Clause or
Section Title
Submittals Required
Due date or Delivery time
Type
CP
** Responsible
Code
No. of sets to be sent to: ***
CO COR
09 91 11-1 Painting for Concrete
Approval Data At least 15 days prior to coating
A COR CDMS
09 91 11-2 Painting for Concrete
Final Approval Data
At least 15 days prior to coating
I COR CDMS
09 91 11-3 Painting for Concrete
Certifications At least 15 days prior to coating
I COR CDMS
09 91 11-4 Painting for Concrete
Documentation At least 15 days prior to coating
A COR CDMS
09 91 11-5 Painting for Concrete
Contractor Quality Testing Data for “Shop or Field Applied” Coatings
Within 10 days of testing
I COR CDMS
09 91 11-6 Painting for Concrete
“Equal” Products At least 15 days prior to coating
A COR CDMS
26 05 02-1 Basic Electrical Materials and Methods
Conduit and Cable Approval Drawings and Data
At least 15 days prior to installation
A COR CDMS
26 05 10-1 Conductors and Cables
Approval Data At least 15 days prior to installation
A COR CDMS
26 05 10-2 Conductors and Cables
Test Reports Within 10 days of testing
I COR CDMS
26 05 20-1 Grounding and Bonding
As-built drawings Within 10 days of completion of work
A COR CDMS
26 05 20-2 Grounding and Bonding
Test reports Within 10 days of testing
I COR CDMS
26 05 33-1 Electrical Conduit Proposed Conduit Changes
At least 15 days prior to changes
A COR CDMS
26 05 33-2 Electrical Conduit As- built drawings
Within 10 days of completion of work
A COR CDMS
26 05 90-1 Wiring Checkout and Tests
Test Notification At least 10 days prior to testing
I COR CDMS
26 28 30-1 Enclosed Circuit Breakers
Approval Drawings and Data
At least 15 days prior to installation
A COR CDMS
26 33 13-1 125v DC Battery and Charger
Product Data At least 28 days prior to purchase
A COR CDMS
26 33 13-2 125v DC Battery and Charger
Design Data At least 30 days prior to installation of batteries
A COR CDMS
Contractor’s Onsite Safety and Health Personnel – (Revised)
01 35 30 - 6
1. The effectiveness of the Contractor’s Onsite Safety Representative in prosecuting the safety program will be subject to continued review and approval by the COR.
2. Should the Contractor’s Onsite Safety Representative’s effort be deemed insufficient the Contractor will be required to replace the Onsite Safety Representative as directed by the CO.
3. Deleted.
B. Contractor’s Part-time Onsite Safety and Health Professional:
1. The effectiveness of the Contractor’s Part-time Onsite Safety and Health
Professional in the planning, preparation and execution of high risk activities will be subject to continued review and approval by the COR.
2. Should the Contractor’s Onsite Part-time Onsite Safety and Health Professional’s effort be deemed insufficient the Contractor will be required to replace the Part-time Onsite Safety and Health Professional in accordance with paragraph (c) of the “Material and Workmanship” clause in Section E. Onsite activities requiring Part-time Onsite Safety and Health Professional guidance and oversight will be halted until an acceptable replacement is found.
3. Part-time health professional shall be onsite no less than once per calendar month for one full working day.
C. Certified Industrial Hygienist
1. The effectiveness of the Contractor’s Onsite CIH in prosecuting the asbestos and coatings activities will be subject to continued review and approval by the COR.
2. Should the Contractor’s Onsite CIH’s effort be deemed insufficient the Contractor will be required to replace the Onsite CIH as directed by the CO. Onsite activities requiring CIH guidance and oversight will be halted until an acceptable replacement is found.
3. The Contractor’s Onsite CIH shall be onsite for the initial testing of each work location, as needed for any hazardous materials encountered, and at final assessment of each work location.
PART 2 PRODUCTS
Product Requirements – (Revised)
01 60 00 - 2
E. Store curing compounds, sealants, adhesives, paints, coatings, sealers, joint compounds, grouts, and similar products at the temperature and environmental conditions recommended by manufacturer.
1.05 MAINTENANCE
A. Extra Materials:
1. Furnish additional maintenance materials specified as "extra materials" in the specifications. Provide maintenance material identical to installed material and provide from the same manufacturer's production lot as installed material.
2. Package extra materials for storage and label with complete product identification on packaging.
3. Deliver extra materials to the Government at jobsite and place in storage as directed by the COR.
PART 2 PRODUCTS
2.01 MATERIALS
A. Provide materials required for completion of work.
B. Provide type and quality described in these specifications. Make diligent effort to procure specified materials from all available sources.
C. Furnish new materials conforming to referenced standards unless otherwise specified.
D. For materials not covered by these or referenced specifications, furnish materials of standard commercial quality.
E. If materials to be used deviate from or are not covered by recognized specifications and standards, submit, for approval, justification for and exact nature of the deviation, and complete specifications for materials proposed for use.
2.02 SUBSTITUTIONS
A. If materials required by these specifications become unavailable, because of Government priorities or other causes, substitute materials may be used.
B. Obtain written approval to use substitute materials from the CO. State in the request for approval the amount of the adjustment, if any, to be made in favor of the Government.
C. The Government's determination as to whether substitution will be permitted and as to what substitute materials may be used, shall be final and conclusive.
D. If approved substitute materials are of less value to the Government or involve less cost to the Contractor than specified material, a contract adjustment will be made in favor of
Project Record Documents – (Revised)
01 78 30 - 1
SECTION 01 78 30
PROJECT RECORD DOCUMENTS
PART 1 GENERAL
1.01 MEASUREMENT AND PAYMENT
A. Cost:
1. Include in prices offered in the Price Schedule for other items of work.
1.02 UPDATED RECORD DRAWINGS
A. Update record drawings to document work or services performed for progress payments in accordance with the clauses at FAR 52.232-27 - Prompt Payment for Construction Contracts.
1. At a minimum, meet monthly with COR to review and approve progress made to full-sized record drawings prior to the submittal for progress payment. Meeting location to be approved by COR.
2. Verify with the COR that mark-ups to the drawings are current with the progress of the work prior to submitting invoice for progress payment.
1.03 DEFINITIONS
A. Progress As-built Drawings
1. Copies of as-built drawings maintained on site.
B. Draft As-built Drawings:
1. Completed set of marked-up as-built drawings that have been certified by Contractor reflecting all changes to the work and any additional contractor/manufacturer drawings.
C. Final Drawings:
1. Complete set of project drawings incorporating all changes as shown in the as-built drawings and reflecting the final project condition as constructed.
1.04 SUBMITTALS
A. Submit the following in accordance with Section 01 33 00 - Submittals.
B. RSN 01 78 30-1, Electronic Media Release Form, Upon Request.
1. Refer to Article 1.04 Electronic Drawings below.
C. RSN 01 78 30-2, Progress As-built Drawings:
01 78 30 - 2
1. Copies of As-built drawings maintained on site.
2. Include as-built conditions of drawings submitted as required in Table 01 33 00A
– List of Submittals.
D. RSN 01 78 30-3, Draft As-built Drawings:
1. Certified Marked Sets: As-built drawings that have been certified by Contractor as up to date and accurate in the description of work.
2. Submit to COR for approval prior to commissioning, training, request for substantial completion, and/or Government possession.
3. For Information Only (FIO) Drawings: Revision date and details.
E. RSN 01 78 30-4, Final As-built Drawings:
a. Drawings shall be provided in AutoCAD drawing (.dwg) format and Adobe Acrobat (.pdf) format and submitted electronically or by similar means approved by COR.
b. Drawings or output data files produced on a Computer Aided Design and Drafting (CADD) system and furnished to Reclamation shall be compatible with 2021 Autodesk products, .DWG file format, manufactured by Autodesk, Inc., Sausalito, CA. CO may require other versions of Autodesk.
c. Drawings shall be provided in full size hard copy and electronic copy in AutoCAD drawing (.dwg) format and Adobe Acrobat (.pdf) format on CD-ROM or DVD. Any drawings or output data files produced on a Computer Aided Design and Drafting (CADD) system and furnished to Reclamation shall be compatible with AutoCAD 2021, .DWG file format, manufactured by Autodesk, Inc., Sausalito Ca, as used by Reclamation.
ASCII point files must be included, with a point descriptor glossary. All .DWG deliverables must be created using Reclamation’s standard drawing template file (.DWT) and standard 6 support files (to be provided by Reclamation). Deliverables shall be “eTransmit” from within the AutoCAD application, to package .DWG files with all resource files and dependencies including fonts, external references, and images.
d. Reports, memorandums, and documents shall be provided in bound hard copy and electronic copy in Microsoft Word (.docx) format and Adobe Acrobat (.pdf) format on CD-ROM or DVD.
a.e. All deliverables shall be provided in Final form for Reclamation.
b.f. All data developed by Contractor under this submittal is the property of the U.S. Government and shall be made available to Reclamation upon completion of this contract. This data shall include, but not be limited to results of technical analyses, GIS data and products, CADD data and products, coordination materials, photographs, and data sheets.
01 78 30 - 3
G. RSN 01 78 30-5, Final Drawings:
1. Final Electronic Drawings in AutoCAD drawing (.dwg) format and Adobe Acrobat (.pdf) format.
2. Drawings or output data files produced on a Computer Aided Design and Drafting (CADD) system and furnished to Government shall be compatible with 2023 Autodesk products, .DWG file format, manufactured by Autodesk, Inc., Sausalito, CA. CO may require other versions of Autodesk.
3. Topographical drawings shall contain proper point files, point groups, and intelligent Civil 3D object entities such as surfaces, alignments, profiles and cross-sections as required.
4. ASCII point files must be included, with a point descriptor glossary.
5. Deliverables shall be “eTransmit” from with the Civil 3D application, to package .DWG files with all resource files and dependencies including fonts, external references and images.
6. .DWG files with all resource files and dependencies including fonts, external references, and images.
7. Updated with all changes as marked on As-built drawings to reflect approval comments.
1.05 ELECTRONIC DRAWINGS
A. CADD Files, will be distributed upon request, after:
1. Notice to Proceed.
2. Contractor signs form in Section 51 00 50 – Electronic Media Release.
1.06 PROGRESS AS-BUILT DRAWINGS
A. Maintain 2 sets of full-size prints of drawings listed in Division 52 and contractor drawings submitted and approved as required in Table 01 33 00A – List of Submittals marked to show accurate and complete records of as-built conditions:
1. Keep drawings at the jobsite and mark as work progresses.
2. If FIO drawings require changes, mark with revisions.
B. Use the following to represent changes.
1. Supplementary notes, legends, and details necessary to clearly portray as-built construction.
2. In lieu of referencing, incorporate clarifications from other documents such as RFI’s, where as-built construction is identified.
3. Include pictures, sketches or other representations to further explain as-built construction. Do not provide in lieu of as-built drawings.
01 78 30 - 4
4. Mark and dimension to show variations between actual construction and that indicated or specified in contract documents.
a. Include buried or concealed construction and utilities.
b. Include existing items, topographic features, and utility lines revealed during construction which differ from those shown on contract drawings.
5. Mark to define construction actually provided where choice of materials or methods is permitted in specifications, or where variations in scope or character of work from that of the original contract are authorized.
C. Mark drawings in the following colors:
1. Red: Additions.
2. Green: Deletions.
3. Blue: Notations necessary for explanation of markings.
D. Allow the Government to review the drawings at all times.
E. Following successful commissioning of each unit or Government possession, submit As-builts with changes resulting from commissioning and training to COR for review and approval.
1.07 DRAFT AS-BUILT DRAWINGS
A. Convert information shown in progress as-builts into electronic format.
B. Upon completion of work, sign marked as-built drawings.
1. Sign and date each as-built drawing as certified correct. If no revisions were necessary to illustrate as-built conditions mark the drawing with “As-Built, No Changes.”
2. Only certify FIO drawings which require changes.
1.08 FINAL DRAWINGS
A. Incorporate mark-ups from as-built drawings into complete drawings set showing as-built constructed condition.
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
01 78 30 - 5
01 78 30 - 6
This page intentionally left blank.
Concrete Repair – (Revised)
03 81 14 - 3
1.06 EXISTING CONDITIONS
A. Existing concrete consists of cement, sand, and broken rock or gravel.
B. Information drawings provide general locations of embedded reinforcement, pipe, conduit, and metalwork. Actual locations may vary.
PART 2 PRODUCTS
2.01 NEW CONCRETE REPAIR MATERIALS
A. Concrete Age: Between 24 and 72 hours.
B. Packaged Repair Material.
1. Depth: Between 1/4-inch and the bottom of the nearest reinforcing steel.
2. Too small for concrete.
3. Suitable for repair thickness.
a. Mix components in accordance with manufacturer’s instructions.
4. Deleted.
2.02 OLD CONCRETE REPAIR MATERIALS
A. Concrete Age: Greater than 72 hours.
B. Packaged Repair Material.
1. Used on both new and old concrete.
2. Refer to Packaged Repair Material in New Concrete Repair Materials above.
2.03 CURING MATERIALS
A. Water: ASTM C1602, including optional requirements of Table 2.
B. Curing compound:
1. ASTM C309, type 1-D.
2. ASTM C1315, type I-A
C. Polyethylene film: ASTM C171, white opaque.
PART 3 EXECUTION
3.01 GENERAL
A. Cease operations and notify COR if concrete repair operations:
Painting for Concrete - (Revised) 09 91 11 - 3
2) Manufacturer’s designated product name.
C. RSN 09 91 11-2, Final Approval Data:
1. For each coating material:
a. Purchase orders. Include:
1) Supplier’s name, address, and phone number.
2) Purchase order number and date.
3) Manufacturer’s designated product name.
4) Batch number(s) for each material, except thinners.
5) Quantities ordered for each material, except thinners.
D. RSN 09 91 11-3, Certifications:
1. Manufacturer’s certification that materials certified by a Qualified Products List
(QPL) meet specified requirements.
E. RSN 09 91 11-4, Documentation:
1. Coating personnel qualifications by training or experience for each coating. For experience include:
a. Applicator
1) 3 recent jobs using comparable materials under similar conditions.
2) Owners contact information of 3 recent jobs.
b. Inspector
1) 3 recent jobs requiring testing and verification referenced in this section.
2) Owners contact information of 3 recent jobs.
F. RSN 09 91 11-5, Contractor Quality Testing Data for “Shop or Field Applied” Coatings:
1. Date of work.
2. Description of areas and work performed.
3. Surface preparation.
4. Surface cleanliness/ profile.
5. Ambient conditions.
6. Dry film thickness.
G. RSN 09 91 11-6, “Equal” Products:
1. List of projects (not less than three) where material has been successfully used in applications similar to this project. Include:
D
C
B
A
40-D-4334
FIGURE 1
GROUNDING METAL CONDUITS
Equal to Burndy Type GAR or GD
Welded connector equal to
Cadweld Type PC
METAL CONDUIT GROUNDING TABLE
CONDUIT SIZE MINIMUM SIZE NUMBER CLAMP SIMILAn
OF GROUND CABLE OF TAPS 0 BURNOY TYPE
-i"to 1/" No.4 A. W.G. 1 GAR 2" to 3" No.1 A.W.G. 1 GAR Above 3" No. 1 A. W.G. 2 GD
FIGURE4
EMBEDDED GROUND CONNECTOR WITH
EQUIPMENT GROUND CABLE
Insert bolts before plate is embedded.
Leave bolts in place until equipment ground cable is installed.
Floor or wall surface
Ground plate .·"� equal to Cadweld
8-Series
SIDE VIEWS
To equipment being grounded
4Gro.und lug:
Burndy Type /) � • YGHA, or equal
Welded connector equal to Cadweld
Type SS
FIGURE 2
BONDING CONDUITS AT EXPANSION JOINTS
Slip coupling
NOTE
See Fig. 5 for typical grounding details
CLAMPS SHALL BE EQUAL TO BURNDY TYPE GAR OR GD AND BARE
COPPER CABLE IN ACCORDANCE WITH THE TABLE IN FIGURE 1
OR A BONDING JUMPER EQUAL TO O.Z. TYPE BJ {WITH BRONZE
FITTINGS) MAY BE USED.
FIGURE 5
CROSSING EXPANSION AND CONTRACTION
JOINTS WITH GROUNDING CABLE
q
14" Approx.
Joint filler
"Bare Cab/ Ll q
Provide slack in cable to permit i" additional opening at joint
Recess to be formed in concrete by wrapping cable loosely with asphalt saturated cotton fabric and given a heavy coating of asphaltum.
+ This dimension is approximate for No. 4/0 cable only. For larger cables, increase diameter of wrapping accordingly
NOTE
THE CROSSING OF EXPANSION JOINTS WITH EMBEDDED GROUND
CABLE SHOULD BE AVOIDED WHENEVER POSSIBL£ THE EMBEDDED
GROUNDING SYSTEM FOR EACH UNIT OR BLOCK SHOULD BE SELF
CONTAINED.
FIGURE 3
BONDING CONDUITS AROUND JUNCTION BOXES
Ground cable
Ground cable
SECTION A-A
NOTE
CLAMPS SHALL BE EQUAL TO BURNDY TYPE GAR OR GD AND BARE
COPPER CABLE IN ACCORDANCE WITH THE TABLE IN FIGURE 1 OR A
BONDING JUMPER EQUAL TO O.Z. TYPE BJ (WITH BRONZE FITTINGS)
MAY BE USED.
FIGURE 6
GROUNDING OF THREE PHASE BUS STRUCTURE
Copper ground strap under bus support ring
Copper ground strap
GROUND CONNECTORS AS SHOWN IN
FIGURE 4 SHALL BE USED
Anchors
NOTES
1. Ground cables for connection to equipment shall be of sufficient length to bolt to equipment when ultimately installed. Terminations as shown in Figure 4 Dwg 40-D-4334 shall be used in lieu of stubouts.
Approximate locations only are shown on drawings. Exact locations to be determined in field.
2. Refer to conduit drawings or general arrangement drawings whenever available, for more exact location of equipment.
3. Metal conduits shall be grounded at both ends. If a break occurs in a run of metal conduit, the conduit shall be bonded across the break. In case the above is not feasible, the each section shall be grounded separately. Each contractor shall ground each metal conduit run, or portion therof, that he installs. Junction or pull boxes not containing protective equipment in which the conduits are installed with a locknut and bondnut shall not be considered a break when the voltage is below 240 volts to ground, but shall be so considered for higher voltages. All junction or pull boxes in runs of non-metallic conduit shall be individually grounded. All boxes containing overload protective devices shall be individually grounded.
4. Ground cable shall be No.4 A. W.G. or larger.
5. All paint, enamel, and scale shall be removed from point of contact on metal surfaces before applying ground connections.
6. All bolts, machine screws, nuts and washers used in making grounding connections shall be silicon bronze.
7. Cable shields and one conductor of multiconductor cable shall be grounded at both ends.
8. Thermoweld, Cadweld, or an approved equivalent process shall be used in making connections between cables where embedded in concrete, direct buried, or under plant superstructure.
9. Where Thermoweld, Cadweld, or an approved equivalent process is used it shall be performed with heavy duty welding equipment in accordance with manufacturer's instructions and the material shall be new fresh stock.
1 0. All ground connectors shall be UL I isled. All below grade connectors to be in accordance with IEEE 837.
REFERENCE DRAWINGS
TYPICAL GROUNDING DETAILS {SHT 2 OF 2) 40-D-4335
SWITCHYARDS & SUBSTATIONS - GROUNDING
DETAILS 40-D-4 753
PLATFORM GROUNDING DETAILS 40-D-4874
CABLE TRENCH GROUNDING. 40-D-6182
GROUNDING SUPPORTS ON TUBULAR
STEEL STRUCTURES 40-D-6309
FENCE GROUNDING DETAILS 40-D-6376
REV NO 2004-07-06 CHANGED NOTE 10, ADDED FIG.4 CONNECTOR REF., ADDED REF.
3 D - J. R. Z. DRAWINGS, OTHER MINOR REVISIONS.
3 - 70 - 00 REDRAWN IN AUTOCAO R.14 FORMAT
D - L.G.
12 - 2 -85 REVISED TO SHOW CURRENT PRODUCTS OR PRACTfCES.
D - G.D.O.
THIS DRAWING SUPERSEDES
IN PART DRAWING 40-D-4336, 01-14-2003
€19 ALWAYS THINK SAFETY
UNITED STATES
DEPARTMENT OF THE INTERIOR
BUREAU OF RECLAMAT10N
STANDARD DESIGNS
ELECTRICAL INSTALLATION
TYPICAL GROUNDING DETAILS
DRAWN __ R,:f.t:f... = $._.J§. ______ SUBMITTED ___ D:... Cl_AB_K _________ _
TRACED __ J.:.. "1:. f:!:. ________ RECOMMENDED __ H._H<:_P!::PMB ________ _
CHECKED_ Y:fl!.:.P_-3-E:f-!:..-:. T:i-i=. ___ APPROVED _ _ J.._!J._M£Cif'=.._lAjJ _____ _
D
C
B
A
Amendment No. P0003
B
A
40-D-4335
Welded connectors equol to Codweld Type
GY
FIGURE 1
GROUND MATS
g
GROUND ROD DETAILS
PERPENDICULAR
CLAMPS
FIGURE 2
GROUND MATS
HORIZONTAL PARALLEL THRU
CLAMPS
Welded connectors equal to
----- Codwe/d Type PT
Codweld Type XF or XG or equal
Cadweld Type XB or Cadweld Type TC or equal equal
FIGURE 5 FIGURE 6
FLOOR FRAMES
Welded connector equo/ __ ,__ __ _ to Cadweld Type RX
NOTE
WELD CONNECTOR WITH ANGLE
INVERTED PRIOR TO PLACING
FRAME IN FINAL POSITION.
Welded connector equo!--...,...--to Codweld Type RY
<J
RAILING POST BASES AND HANDRAIL SUPPORTS
PLAN VIEW
TO GROUND PLATE - SEE
FIGURE 4, DWG. 40-0-4334.
CONNECTION TO RAILING POST BASE
{DETAILS FOR GROUNDING HANDRAIL SUPPORTS ARE SIMILAR)
FIGURE 3
LIGHTING OR MISC POWER CABINETS
Coup/ ings ,, Recess frame ------....... ' ... ...,,_.
see 40-D-3744 ', 1:
Chaste nipple --------
Cabinet trim,, ....... Breakers '-,,, Terminal lug, equol to ___ _ Burndy Type QA-B <,,,,, Equal to Burndy ---.- --- type GAR or GD
Codweld _,- HT or Equal
.,, ,,,.,,,,, ... --... Recess
-�- --- Ground coble
Codweld ,,- HT or Equal
--;;" • -�;welded connector / equal to Codweld
Type PT Frame ground -----------Hg�'F"'
Trim screw---------
Equal to Burndy type------- _ GAR or GD
SECTIONAL ELEVATION
FIGURE 7
OIL TANK GROUNDING DETAILS
(',...,,,-------------....... "I I I iLEVATIO!iJ
SECTION A-A
SECTION 8-8
Terminal lug, equal to
Burndy Type QA-B
TO GROUND PLATE -
SEE FIGURE 4, DWG.
"-._ 40-D-4334 "---._ -.._________.,. Ground coble
DETAIL A
FIGURE4
RAILS
EXPOSED INSTALLATION
Welded connector equal to Cadweld
Type RX
CONNECTION TO RAIL
EMBEDDED INSTALLATION
CONNECTION TO RAIL
FIGUREB
CONTROL CABLE SHIELD
Ground conductor of EQUIPMENT CABINET cable ---+--..,,,_
Insulated shield gnd.
wire
GROUND BAR
I" X 1" COPPER
Ground wire #4 AWG
To terminal blocks
L-H---t--r-7;::11�g c�� d :g-D-4334 for conduit grounding)
Unwrap shield braid for a distance of 2 to 3 inches. Re-braid into a stranded conductor. Connect to insulated ground conductor by comp.
splice -----
Insulated Conductor to ground bus--�---
Compression splice
Shield Braid
Insulated Conductor Assembly
Sheath
DETAIL A
LONGITUDINAL CABLE SECTION
GROUND LINE
NOTES
1. See drawing 40-D-4334 for notes and list of reference drawings.
GROUND SYMBOLS
(Used on Pion Drawings)
Indicates ground coble embedded in concrete Indicates ground coble concealed but not embedded in concrete Indicates ground coble exposed Indicates ground rod Indicates ground connection Indicates ground coble riser Indicates embedded ground plate
REFERENCE ORA WINGS
ELECTRICAL INSTALLATION - TYPICAL
GROUNDING DETAILS {SHT 1 OF 2) 40-D-4334
REV N 2004--07-06 MINOR REVISIONS; ADDED FIG. 'S 2 AND 8.
3 D-J. R. Z.
3 - 10 - 00 REDRAWN IN AUTOCAD R.14 FORMAT
D - LG.
12 - 2 -85 REVISED TO SHOW CURRENT PRODUCTS OR PRACTICES.
D - G.D.0.
THIS DRAWING SUPERSEDES DRAWING
40-D-4336 IN PART (2003-01-14);
AND DRAWING 104-D-944 (2004-07-06)
� ALWAYS THINK SAFETY
UNITED STATES
DEPARTMENT OF THE INTERIOR
BUREAU OF RECLAMATION
STANDARD DESIGNS
ELECTRICAL INSTALLATION
TYPICAL GROUNDING DETAILS
DRAWN __ R,1'.l:f.,:::: �J.,_S. ______ SUBMrrTED ___ D.,_C,bAf1K _ ________ _
TRACED __ J.:... � I-!:,. ________ RECOMMENDED __ H._H:...Pf_LJM_B ________ _
CHECKED_ '!{"!.:_P_-_E.f:Ji. -:, �J.!::,_ ___ APPROVED _ _ J..l/._M£C!:.E'=.._lAl./ _____ _
D
C
B
B
A it,l
�"i')...
40-D-6182
-rn mm ff'
To ground mat
4 3 2
SECTION A-A
LIST OF MATERIALS
ITEM DESCRIPTION
1 No. 2/0 AWG copper coble
2 No. 4/0 AWG copper cable
3 No. 6 AWG copper cable
5 Connector (Burndy Cat. No. KVSW28)
6 Terminal (Anderson Type VL4S Tinned)
7 1/4" X 1" Aluminum bolt, nut and lockwasher
NOTES
1. The No. 6 AWG copper ground cables shall be installed with enough slack to allow the trench covers to be removed and lie flat without interfering with the steel or concrete foundations where possible.
2. When two or more cable trenches are located ajacent to each other, each trench shall be grounded in accordance with this drawing.
3. All materials shall be equivalent to those referenced,
4. If No. 6 AWG insulated copper cable is installed, the insulation shall be stripped back at least 12-inches from each end.
REFERENCE ORA WINGS
ELECTRICAL INSTALLATION - TYPICAL
GROUNDING DETAILS {SHT 1 OF 2 )
TYPE C CABLE TRENCH OUTLINE
REV NO 2004-07-06 MINOR REVISIONS.
3 D-J.R.Z.
3 - 24 - 00 REDRAWN IN AUTOCAD R.14 FORMAT
D - L. G.
40-D-4334
40-D-5350
5 - 1- 78 CHANGED ITEMS 1, 3 - 6, NOTE 1; ADDED NOTE 4.
D - R. A.£.
THIS DRAWING SUPERSEDES
IN PART DRAWING 40-D-4336, 01-14-2003
€B ALWAYS THINK SAFETY
UNITED STATES
DEPARTMENT OF THE INTERIOR
BUREAU OF RECLAMAnON
STANDARD DESIGNS
ELECTRICAL INSTALLATION
TYPICAL CABLE TRENCH GROUNDING
DESIGNED _S ._ G,....P,:_ _ _ _ _ _ _ _ _ SUBMITTED _ _ f. J!._p[...pfOf:!.. _______ _
DRAWN __ J._M:f!..EJ::P� ______ RECOMMENDED_ !!_ . .!!- §.AE:,_T!_S[ _______ _
CHECKED_ §. �-__________ APPROVED __ ..J. Jf._HQ.L'=..EA.flI_N _____ _
�I it O!� c,� DENVER, COLORADO JUNE J, 1968
40-D-6182 ����,..._ ___________________________________________________________________________________________________ .....,. ___ ����IT"-'1�D�F�1----'---;..;......;;;_.;...;...;;..;;;;_ _ _, 5 4 3 2
D
C
B
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
PL
O
TT
ED
B Y
CA
D
FI
LE
NA
M
E
DA
TE
A
ND
T
IM
E
PL
O
TT
ED
CA
D
SY
ST
EM
D
C
B
A
D
C
B
A
BU
RE
AU
O
F
RE
CL
AM
AT
IO
N U.
S.
D
EP
AR
TM
EN
T O
F
TH
E
IN
TE
RI
O R
Managing
LAR M TA IOCE N
W in theWa estter
C O
LU
M
BI
A
BA
SI
N
PR
O
JE
CT
GR
AN
D
CO
UL
EE
P
RO
JE
CT
H
YD
RO
EL
EC
TR
IC
A
UT
HO
RI
TY
NO
NE
PU
M
P/
GE
NE
RA
TO
R
PL
AN
T
125V DC BATTERY BOARD
BP5A
SCHEMATIC DIAGRAM
BOISE, ID
222-100-60448
2017-05-03
1Au to
CA
D
Re l.
.2 s
2-
0-
8-
RD
-1 .D
W G
JU
LY
3, 5:
ST
RA
XL
ER
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
Colton Reid
Colton Reid
Wesley Johnson
Johnson, Wesley D P.E.
Spindler, Charles F Design Group Manager
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
G
RA
N D
C O
U
LE
E D
AM
AutoCAD SHX Text
125 VOLT BATTERY
AutoCAD SHX Text
AM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 100A
AutoCAD SHX Text
SHUNT
AutoCAD SHX Text 125P
AutoCAD SHX Text 125P1
AutoCAD SHX Text 125N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 2C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
27DB2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BP2
AutoCAD SHX Text M2
AutoCAD SHX Text M1
AutoCAD SHX Text
BP1
AutoCAD SHX Text
DB2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3600%%234
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 64B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 500%%234
AutoCAD SHX Text
BP4
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text A8
AutoCAD SHX Text B8
AutoCAD SHX Text C10
AutoCAD SHX Text D10
AutoCAD SHX Text
GRD
AutoCAD SHX Text B6
AutoCAD SHX Text A6
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text B4
AutoCAD SHX Text A4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
VM
AutoCAD SHX Text
BN
AutoCAD SHX Text
BP
AutoCAD SHX Text D2
AutoCAD SHX Text
SS
AutoCAD SHX Text C2
AutoCAD SHX Text C12
AutoCAD SHX Text
SS
AutoCAD SHX Text D12
AutoCAD SHX Text
BKR. #4, BD. BP5A
AutoCAD SHX Text
BATT. CHARGER #2
AutoCAD SHX Text
BP5B
AutoCAD SHX Text (-60446)
AutoCAD SHX Text C8
AutoCAD SHX Text
SS
AutoCAD SHX Text D8
AutoCAD SHX Text C1P
AutoCAD SHX Text B2
AutoCAD SHX Text
SS
AutoCAD SHX Text A2
AutoCAD SHX Text C1N
AutoCAD SHX Text (-60446)
AutoCAD SHX Text
BP5C
AutoCAD SHX Text
BATT. CHARGER #4
AutoCAD SHX Text
BKR. #2, BD. BP5A
AutoCAD SHX Text
SS
AutoCAD SHX Text C2N
AutoCAD SHX Text B10
AutoCAD SHX Text A10
AutoCAD SHX Text D4
AutoCAD SHX Text
SS
AutoCAD SHX Text C2P
AutoCAD SHX Text C4
AutoCAD SHX Text
BP
AutoCAD SHX Text
BN
AutoCAD SHX Text N
AutoCAD SHX Text P
AutoCAD SHX Text
TO 125V DC DISTRIBUTION SYSTEM
AutoCAD SHX Text (-60443)
AutoCAD SHX Text 64B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MX20A
AutoCAD SHX Text
MAP
AutoCAD SHX Text
ANNUN.
AutoCAD SHX Text (21397)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 64B
AutoCAD SHX Text %%uDESCRIPTION
AutoCAD SHX Text %%uDEVICE
AutoCAD SHX Text %%uLOCATION
AutoCAD SHX Text %%uSCHEMATIC
AutoCAD SHX Text %%uEXPLANATION %%u
AutoCAD SHX Text 2C
AutoCAD SHX Text
27DB2
AutoCAD SHX Text 64B
AutoCAD SHX Text
SS
AutoCAD SHX Text
BP5A
AutoCAD SHX Text
BP5A
AutoCAD SHX Text
BP5A
AutoCAD SHX Text
BP5A
AutoCAD SHX Text
AutoCAD SHX Text
UNDER VOLTAGE RELAY
AutoCAD SHX Text
GROUND DECTECTOR RELAY
AutoCAD SHX Text
VOLTMETER SELECTOR SWITCH
AutoCAD SHX Text %%uREFERENCE DRAWINGS
AutoCAD SHX Text
125V DC BATTERY CHARGERS SCHEMATIC
AutoCAD SHX Text
125V DC BATTERY BOARD WIRING DIAGRAM
AutoCAD SHX Text
125V DC DISTRIBUTION SYSTEM SINGLE LINE
AutoCAD SHX Text 222-100-60443
AutoCAD SHX Text 222-100-60447
AutoCAD SHX Text 222-100-60446
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text N
AutoCAD SHX Text
BP5A CABINET DETAILS & BILL OF MATERIAL
AutoCAD SHX Text 222-117-17867
AutoCAD SHX Text 2C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MX21U
AutoCAD SHX Text 3600%%234
AutoCAD SHX Text
AutoCAD SHX Text
INTERNAL JUMPERS
AutoCAD SHX Text
SS SWITCH DEVELOPMENT
AutoCAD SHX Text
AB-11
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CD-11
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OFF
AutoCAD SHX Text
CHGR. NO. 1
AutoCAD SHX Text
BATT. (+) TO GND.
AutoCAD SHX Text
BATT.
AutoCAD SHX Text
BATT. (-) TO GND.
AutoCAD SHX Text
CHGR. NO. 2
AutoCAD SHX Text
CONTACTS
AutoCAD SHX Text
SWITCH POSITIONS
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
25 SEC.
AutoCAD SHX Text
TDC
AutoCAD SHX Text
TDDO
AutoCAD SHX Text
BN1
AutoCAD SHX Text
225A BKR., BD. BP5A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNATION
AutoCAD SHX Text
1BP5C
AutoCAD SHX Text
1BSA1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
NO.
AutoCAD SHX Text (-60445)
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
REF.
AutoCAD SHX Text
DRAWINGS
AutoCAD SHX Text
1/C-750 MCM
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
%%UCABLE LIST
AutoCAD SHX Text
1BP5C
AutoCAD SHX Text
1BP5B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1/C-#1 AWG
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text (-60445)
AutoCAD SHX Text (-60445)
AutoCAD SHX Text (-60445)
AutoCAD SHX Text
1/C-750 MCM
AutoCAD SHX Text
1/C-#1 AWG
AutoCAD SHX Text WARNING: This information is FOR OFFICIAL USE ONLY and must be protected. This U.S. Government data may be exempt from further public release under the Freedom of Information Act (5 U.S.C. 552.) This information must be controlled in accordance with applicable Bureau of Reclamation directives. The further distribution of this information requires prior approval from an authorized Reclamation official.
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
PL
O
TT
ED
B Y
CA
D
FI
LE
NA
M
E
DA
TE
A
ND
T
IM
E
PL
O
TT
ED
CA
D
SY
ST
EM
D
C
B
A
D
C
B
A
BU
RE
AU
O
F
RE
CL
AM
AT
IO
N U.
S.
D
EP
AR
TM
EN
T O
F
TH
E
IN
TE
RI
O R
Managing
LAR M TA IOCE N
W in theWa estter
C O
LU
M
BI
A
BA
SI
N
PR
O
JE
CT
GR
AN
D
CO
UL
EE
P
RO
JE
CT
H
YD
RO
EL
EC
TR
IC
A
UT
HO
RI
TY
NO
NE
PU
M
P/
GE
NE
RA
TI
NG
P
LA
NT
250V DC BATTERY
DISTRIBUTION BRD. BP3A
SCHEMATIC DIAGRAM
BOISE, ID
222-100-60445
2017-05-03
7Au to
CA
D
Re l.
.2 s
2-
0-
5-
RD
-7 .D
W G
JU
LY
3, 5:
ST
RA
XL
ER
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
Colton Reid
Colton Reid
Wesley Johnson
Johnson, Wesley D P.E.
Spindler, Charles F Design Group Manager
FOR OFFICIAL USE ONLY
FOR OFFICIAL USE ONLY
G
RA
N D
C O
U
LE
E D
AM
AutoCAD SHX Text
%%CB
AutoCAD SHX Text
%%CC
AutoCAD SHX Text
%%CA
AutoCAD SHX Text 460V 3%%C
AutoCAD SHX Text (N)
AutoCAD SHX Text (1P)
AutoCAD SHX Text (P)
AutoCAD SHX Text
DCB
AutoCAD SHX Text 125a
AutoCAD SHX Text
250V DC
AutoCAD SHX Text
%%UBP3C1
AutoCAD SHX Text
250V DC
AutoCAD SHX Text
BATTERY CHARGER
AutoCAD SHX Text No. 1
AutoCAD SHX Text 52-1
AutoCAD SHX Text C1A
AutoCAD SHX Text C1B
AutoCAD SHX Text C1C
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text %%C A1
AutoCAD SHX Text %%C C1
AutoCAD SHX Text %%C B1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text %%C C2
AutoCAD SHX Text %%C B2
AutoCAD SHX Text %%C A2
AutoCAD SHX Text
FROM AUX.
AutoCAD SHX Text
BD. MP9C
AutoCAD SHX Text (D-15238)
AutoCAD SHX Text (D-15235)
AutoCAD SHX Text
BD. MP4A
AutoCAD SHX Text
FROM AUX.
AutoCAD SHX Text
AutoCAD SHX Text 52-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text %%C 2C
AutoCAD SHX Text %%C 2B
AutoCAD SHX Text %%C 2A
AutoCAD SHX Text
BATTERY CHARGER
AutoCAD SHX Text
%%UBP3C2
AutoCAD SHX Text No. 2
AutoCAD SHX Text
250V DC
AutoCAD SHX Text 125a
AutoCAD SHX Text (N)
AutoCAD SHX Text
250V DC
AutoCAD SHX Text 460V 3%%C
AutoCAD SHX Text
DCB
AutoCAD SHX Text
%%CB
AutoCAD SHX Text
%%CC
AutoCAD SHX Text
%%CA
AutoCAD SHX Text (P)
AutoCAD SHX Text (2N)
AutoCAD SHX Text (2P)
AutoCAD SHX Text (1P)
AutoCAD SHX Text
BP3A DC BUS #1 POS.
AutoCAD SHX Text
BP3A DC BUS #1 NEG.
AutoCAD SHX Text
BP3A DC BUS #2 POS.
AutoCAD SHX Text
BP3A DC BUS #2 NEG.
AutoCAD SHX Text (2P)
AutoCAD SHX Text (P)
AutoCAD SHX Text 72-1
AutoCAD SHX Text 72-2
AutoCAD SHX Text
BP3A DC BUS #1 POS.
AutoCAD SHX Text
BP3A DC BUS #2 POS.
AutoCAD SHX Text
BP3A DC BUS #2 NEG.
AutoCAD SHX Text
BP3A DC BUS #1 NEG.
AutoCAD SHX Text 10A
AutoCAD SHX Text 10A
AutoCAD SHX Text
BUS #2 NEG.
AutoCAD SHX Text
BUS #1 NEG.
AutoCAD SHX Text
B1VN
AutoCAD SHX Text
B2VN
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
DETECTION
AutoCAD SHX Text
LOW VOLTAGE &
AutoCAD SHX Text
HIGH VOLTAGE
AutoCAD SHX Text (117-16877)
AutoCAD SHX Text
BUS #2 POS.
AutoCAD SHX Text
BUS #1 POS.
AutoCAD SHX Text 10A
AutoCAD SHX Text 10A
AutoCAD SHX Text
B1VP
AutoCAD SHX Text
B2VP
AutoCAD SHX Text V
AutoCAD SHX Text 0-300
AutoCAD SHX Text V
AutoCAD SHX Text
BUS #1, GROUND
AutoCAD SHX Text
INDICATION 300-0-300
AutoCAD SHX Text V
AutoCAD SHX Text 0-300V
AutoCAD SHX Text V
AutoCAD SHX Text
BUS #2
AutoCAD SHX Text BUS No. 2 GROUND
AutoCAD SHX Text
INDICATION
AutoCAD SHX Text 300-0-300
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 29B-1
AutoCAD SHX Text 29B-2
AutoCAD SHX Text A
AutoCAD SHX Text
BP1
AutoCAD SHX Text
BN5
AutoCAD SHX Text
SH.
AutoCAD SHX Text
BPQ
AutoCAD SHX Text
BPQ1
AutoCAD SHX Text
BATTERY AMMETER
AutoCAD SHX Text
250V P.P. BATTERY
AutoCAD SHX Text
BN1
AutoCAD SHX Text BUS No. 2
AutoCAD SHX Text B2Q
AutoCAD SHX Text A
AutoCAD SHX Text
SH.
AutoCAD SHX Text B2Q
AutoCAD SHX Text 0-200
AutoCAD SHX Text
SH.
AutoCAD SHX Text A
AutoCAD SHX Text BUS No. 1
AutoCAD SHX Text 0-200
AutoCAD SHX Text B1Q
AutoCAD SHX Text B1Q1
AutoCAD SHX Text N3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N4
AutoCAD SHX Text 72-4
AutoCAD SHX Text B2N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-6
AutoCAD SHX Text
AutoCAD SHX Text B1N
AutoCAD SHX Text 72-5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-7
AutoCAD SHX Text
AutoCAD SHX Text N5
AutoCAD SHX Text 1N
AutoCAD SHX Text 2N
AutoCAD SHX Text 1P
AutoCAD SHX Text 2P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-7
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 72-4
AutoCAD SHX Text
AutoCAD SHX Text P3
AutoCAD SHX Text 72-3
AutoCAD SHX Text P4
AutoCAD SHX Text B1P
AutoCAD SHX Text B2P
AutoCAD SHX Text P5
AutoCAD SHX Text
TO 69KV EXCITER SWGR, UP1A & STA. SERVICE
AutoCAD SHX Text
SUBS BUS 3 & 4 (D-14666)
AutoCAD SHX Text (D-15186)
AutoCAD SHX Text TO UNIT CONTROL BOARDS CP1A TO CP6A BUS No. 1 & 2
AutoCAD SHX Text
250VDC RTU-34
AutoCAD SHX Text %%uDESCRIPTION
AutoCAD SHX Text %%uDEVICE
AutoCAD SHX Text %%uLOCATION
AutoCAD SHX Text %%uSCHEMATIC
AutoCAD SHX Text %%uEXPLANATION %%u
AutoCAD SHX Text 29B-1 & 2
AutoCAD SHX Text 52- 1 & 2
AutoCAD SHX Text 72- 1 & 2
AutoCAD SHX Text
BCD
AutoCAD SHX Text 460V DC supply breakers.
AutoCAD SHX Text BP3C1 & BP3C2 250V DC bus isolation circuit breakers.
AutoCAD SHX Text Chargers BP2C1 & 2 250V DC output breaker.
AutoCAD SHX Text Battery isolation circuit breakers.
AutoCAD SHX Text
%%UREFERENCE DRAWINGS
AutoCAD SHX Text 222-117-16899
AutoCAD SHX Text 222-117-16877
AutoCAD SHX Text
PUMPING PLANT 250V DC BATTERY CHARGER
AutoCAD SHX Text
BP3C1 SCHEMATIC & WIRING DIAGRAM
AutoCAD SHX Text
PUMPING PLANT 250V DC BATTERY CHARGER
AutoCAD SHX Text
BP3C2 SCHEMATIC & WIRING DIAGRAM
AutoCAD SHX Text 222-100-60444
AutoCAD SHX Text
PUMPING PLANT MISCELLANEOUS TROUBLE ANNUNCIATOR
AutoCAD SHX Text
PANELS 1,2,3,4 & 5 WIRING DIAGRAM
AutoCAD SHX Text
PUMPING PLANT BATTERY CHARGER BD. BP3A
AutoCAD SHX Text 222-D-15273
AutoCAD SHX Text 222-117-16240
AutoCAD SHX Text
EQUIPMENT LAYOUT DIAGRAM
AutoCAD SHX Text
PUMPING PLANT 250V DC BATTERY CHARGERS BP3C1 & BP3C2
AutoCAD SHX Text
SCHEMATIC DIAGRAM
AutoCAD SHX Text 222-100-60450
AutoCAD SHX Text
LINE DIAGRAM
AutoCAD SHX Text
PUMPING PLANT 250V DC DISTRIBUTION BD.
AutoCAD SHX Text 80-0-200
AutoCAD SHX Text
AutoCAD SHX Text 72-8
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INVERTER INPUT SUPPLY
AutoCAD SHX Text
ELECTRICAL SHOP
AutoCAD SHX Text 72-8
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1N
AutoCAD SHX Text 2N
AutoCAD SHX Text
DESIGNATION
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
REF.
AutoCAD SHX Text
DRAWINGS
AutoCAD SHX Text
CABLE
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
%%UCABLE LIST
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TO 125V DC DISTRIBUTION
AutoCAD SHX Text (-60443)
AutoCAD SHX Text
BP3A
AutoCAD SHX Text
AutoCAD SHX Text (-60444)
AutoCAD SHX Text
125V BATT #1
AutoCAD SHX Text
125V BATTERY #2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BP3A
AutoCAD SHX Text
AutoCAD SHX Text
BP5A-1BP5B
AutoCAD SHX Text
AutoCAD SHX Text
BP5A-1BP5C
AutoCAD SHX Text
AutoCAD SHX Text (-60448)
AutoCAD SHX Text
1/C-#1 AWG
AutoCAD SHX Text
1/C-750 MCM
AutoCAD SHX Text
(N) WIRE FROM BP3C2 TO 72-2 REMOVED
AutoCAD SHX Text
(N) WIRE FROM BP3C1 TO 72-1 REMOVED
AutoCAD SHX Text (-60444)
AutoCAD SHX Text (-60448)
AutoCAD SHX Text
1/C-750 MCM
AutoCAD SHX Text
1/C-#1 AWG
AutoCAD SHX Text
REPLACE W/ NEW
AutoCAD SHX Text
BATTERY CHARGER
AutoCAD SHX Text
REPLACE W/ NEW
AutoCAD SHX Text
BATTERY CHARGER
AutoCAD SHX Text WARNING: This information is FOR OFFICIAL USE ONLY and must be protected. This U.S. Government data may be exempt from further public release under the Freedom of Information Act (5 U.S.C. 552.) This information must be controlled in accordance with applicable Bureau of Reclamation directives. The further distribution of this information requires prior approval from an authorized Reclamation official.
| Att 2. Spec Revisions.pdf |
| Cover |
| Foreword |
| Table of Contents |
| Part I - The Schedule |
| Section A - Solicitation/Contract Form |
| Section B - Supplies or Services and Prices/Costs |
| Section C - Description/Specifications/Statement of Work |
| Certification of Technical Specifications |
| Division 1 - General Requirements |
| Submittal Table |
| Division 2 - Existing Conditions |
| Division 3 - Concrete |
| Division 4 - Masonry |
| Division 5 - Metals |
| Division 6 - Wood, Plastics, and Composites |
| Division 7 - Thermal and Moisture Protection |
| Division 8 - Openings |
| Division 9 - Finishes |
| Division 10 - Specialties |
| Division 11 - Equipment |
| Division 12 - Furnishings |
| Division 13 - Special Construction |
| Division 14 - Conveying Equipment |
| Division 21 - Fire Suppression |
| Division 22 - Plumbing |
| Division 23 - Heating, Ventilating, and Air-Conditioning (HVAC) |
| Divsion 25 - Integrated Automation |
| Divsion 26 - Electrical |
| Division 27 - Communications |
| Divsion 28 - Electronic Safety and Security |
| Divsion 31 - Earthwork |
| Division 32 - Exterior Improvements |
| Division 33 - Utilities |
| Division 34 - Transportation |
| Division 35 - Waterway and Marine Construction |
| Division 40 - Process Integration |
| Division 41 - Material Processing and Handling Equipment |
| Division 42 - Process Heating, Cooling, and Drying Equipment |
| Division 43 - Process Gas and Liquid Handling, Purification, and Storage Equipment |
| Division 44 - Pollution Control Equipment |
| Division 45 - Industry-Specific Manufacturing Equipment |
| Division 48 - Electrical Power Generation |
| Division 51 - Information Available to Offerors |
| Division 52 - Drawings |
| Division 53 - Geologic Investigations and Records |
| Appendix A - |
| Section D - Packaging and Marking |
| Section E - Inspection and Acceptance |
| Section F - Deliveries or Performance |
| Section G - Contract Administration Data |
| Section H - Special Contract Requirements |
| Part II - Contract Clauses |
| Section I - Contract Clauses |
| Part III - List of Documents, Exhibits, and Other Attachments |
| Section J - List of Attachments |
| Part IV - Representations and Instructions |
| Section K - Representations, Certifications, and Other Statements of Offerors or Respondents |
| Section L - Instructions, Conditions, and Notices to Offerors or Respondents |
| Section M - Evaluation Factors for Award |
| Attachments |
| Wage Decision |
| SF-24 Bid Bond |
| Att 3 Drawings Revisions Amd 0003.pdf |
| 222-100-60448-RD-1.pdf |
| Sheets and Views |
| 22 x 34 |
| 222-100-60445-RD-7.pdf |
| Sheets and Views |
| 22 x 34 |
| Att 4 GC Battery Room Photos.pdf |
| Batteries 1 |
| Batteries 2 |
| Batteries 3 |
| Batteries 4 |
| Batteries 5 |
| Batteries 6 |
| Batteries 7 |
| Batteries 9 |
| Batteries 8 |
| 40-D-4334 Sheet No: |
| 40-D-4334 Solicitation No: |
| S40-D-4335 Sheet No: |
| 40-D-4335 Solicitation No: |
| 40-D-6182 Sheet NO: 000 |
| 40-D-6182 Solicitation No: |
File details come from the government source that posted it. Updated .